Raychem Touch 1500 HAZ-TS, HAZ-CPU touch screen Installation Instructions
The Touch 1500-HAZ is a panel mounted touch screen display used in conjunction with Raychem NGC-40 and NGC-20 control and monitoring devices. It is rated NEMA 4X (IP65) and can be mounted indoors or outdoors in a hazardous location. It is designed for operation in ambient temperatures from 0°C to 50°C (32°F to 122°F). It comes with a sealing gasket and hardware to mount the touchscreen. For outdoor installation, a space heater will be required in the panel for low ambient conditions. It comes with all the hardware required for mounting in a suitable electrical panel.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
TOUCH 1500
User Interface termInal for raychem nGc systems InstallatIon InstrUctIons
Touch 1500-HAZ-CPU and
Touch 1500-HAZ-TS installed in a panel
Description
The Touch 1500-HAZ is a panel mounted touch screen display used in conjunction with Raychem NGC-40 and NGC-20 (Europe only) control and monitoring devices. The Touch 1500-HAZ display is rated NEMA
4X (IP65) and can be mounted indoors or outdoors in a hazardous location. For outdoor installation, a space heater will be required in the panel for low ambient conditions. The Touch 1500-HAZ kit includes all hardware required for mounting in a suitable electrical panel.
Additional materials are required for electrical connections and are detailed below. These instructions describe how to mount the Touch
1500-HAZ in an electrical panel and are intended only for personnel experienced in panel construction.
tools requireD
• Metal file • Masking tape
• Phillips screwdriver • #16 (3/16) drill bit
• Jig saw (recommend using carbon steel blade with 24TPI)
ADDitionAl MAteriAls
(to be orDereD sepArAtely)
ApprovAls / certificAtions
Hazardous locations
Class I, Division 2 Groups A, B, C, D
Touch 1500-HAZ-CPU Touch 1500-HAZ-TS
40JY
I.T.E. for use in Hazardous
Locations
23BJ
I.T.E.
Hazardous location designation
Class I, Division 2
Groups A, B, C, D, T5
Hazardous Locations
I.T.E. for use in Hazardous
Locations
316N/23BJ
Hazardous location designation
Class I, Division 2
Groups A, B, C, D, T4A
Hazardous Locations
General
Area of use
Supply voltage
Nonhazardous or hazardous locations, indoor or outdoor (Type 4X, IP66)
Touch 1500-HAZ-CPU: 10 – 36 Vdc
Touch 1500-HAZ-TS: 19 – 30 Vdc
Amperage rating Touch 1500-HAZ-CPU: 2 A @ 24 Vdc
Touch 1500-HAZ-TS: 2.62 A @ 24 Vdc
Operating temp (CE)* Touch 1500-HAZ-CPU: –20°C to 60°C (–4°F to 140°F)
Touch 1500-HAZ-TS: –20°C to 60°C (–4°F to 140°F)
Operating temp (UL)* Touch 1500-HAZ-CPU: –10°C to 60°C (14°F to 140°F)
Touch 1500-HAZ-TS: 0°C to 50°C (32°F to 122°F)
Storage temperature –30°C to 80°C (–22°F to 176°F)
Dimensions (W x D x H) Touch 1500-HAZ-CPU: 85.5 x 139 x 152 mm
(3.4 x 5.5 x 6 in)
Touch 1500-HAZ-TS: 422 x 68 x 338 mm
(16.61 x 2.68 x 13.31 in)
Alarm outputs
Relay output One Form C relay rated 3 A @ 250 Vac.
Relay is used as a common alarm.
* Note: Temperature ratings are without space heaters
1
1
1
1
qty catalog number
1
Description
Touch 1500-HAZ-TS Touch Screen
Touch 1500-HAZ-CPU Computer
Touch 1500-HAZ-CK Cables/Mounting Hardware:
4-ft USB A/B Cable
4-ft VGA Cable
Touchscreen Mounting Clips
(1) 8-ft DB9 to RS-485 Cable
Mfg
TTC
TTC
TTC
ADAM-4069-C1D2 Alarm Module
Push-to-Test Alarm Light
(24 Vdc)
Advantech
Mfg/ptM pn
10332-011
10332-010
10332-027
network connection
remote port (com 3)
Connects to common alarm module (ADAM-4069)
RS-485 A non-insulated 9 pin D sub male
Data rate To 9600 to 57000 baud
field port (com 4) Not used
RS-485 A non-insulated 9 pin D sub male
Data rate To 9600 baud
lAn
usb ports
10/100 Base-T Ethernet port with Link and
Activity Status LEDs (X3)
USB 2.0 host ports (X4)
lcD Display
Display
Touch Screen
LCD is a 15-in XGA, color TFT transflective device with integral LED backlighting.
5-wire resistive touch screen interface with enhanced ITO film for user entry.
WARNING:
The TOUCH 1500 is an electronic unit. During installation, take the following precautions to avoid damage to its electronic components.
inDustriAl HeAt trAcinG solutions
• Handle with care to avoid mechanical damage.
• Keep electronics dry.
• Avoid exposure to static electricity.
• Avoid contamination with metal filings, liquids, or other foreign matter.
• Use agency-approved conduit bushings, adapters, and cable glands to keep the enclosure protected from dust and fluids.
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 1 / 10
provide suitable panel enclosure, and Determine locations for toucH 1500-HAZ Assembly in panel
1. provide suitable panel enclosure
To protect its electronic components, the Touch 1500-HAZ must be mounted in a non-hazardous location panel with a minimum of IP32 (NEMA 1) enclosure or hazardous location panel with a minimum IP65 (NEMA 4) enclosure. The Touch 1500 assembly comes with a sealing gasket and hardware to mount the touchscreen.
The Raychem Touch 1500-HAZ is designed for operation in ambient temperatures from 0°C to 50°C (32°F to 122°F). If the ambient temperature is outside this range, a space heater with screen window kit and/or cooling fan will be required in the panel.
2. Determine locations for the touch 1500-HAZ-ts and touch
1500-HAZ-cpu assembly in the electrical panel
The Touch 1500-HAZ-TS should be located on the front of the panel near eye level (for convenient viewing).
The Touch 1500-HAZ-CPU should be located on the sidewall or backpan of the enclosure.
The Touch 1500-HAZ assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
Panel door
Touch 1500-HAZ assembly location
Panel
Panel alarm light
Touchscreen alarm light
21
23
25
27
29
11
13
15
17
19
5
7
9
3
1
31
33
35
37
39
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10
CB1
CB3
CB5
CB7
CB9
CB11
CB13
CB15
CB17
CB19
CB21
CB23
CB25
CB27
CB29
CB31
CB33
CB35
CB37
CB39
CB22
CB24
CB26
CB28
CB30
CB32
CB34
CB36
CB38
CB40
CB42
CB2
CB4
CB6
CB8
CB10
CB12
CB14
CB16
CB18
CB20
12
14
16
18
20
6
8
2
4
10
22
24
26
28
30
36
38
32
34
40
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 2 / 10
cut opening and Mount toucH 1500-HAZ on front of panel
.
1. locate the toucH 1500-HAZ on the front of panel
Locate the Touch 1500-HAZ assembly ion the front of the panel at the level convenient for viewing. Make sure the cover on the back of the assembly will not interfere with existing panel hardware.
4. Mount the user interface assembly on the panel door
• Place the Touch 1500-HAZ-TS assembly in position. Secure the screen to the enclosure with the 10 mounting clips.
Panel door
Panel Door
396 mm
15.59 in.
Cutting
Area
TOUCH 1500 display with sealing gasket
TOUCH 1500 display
note: Cutting the opening for the display is a craft sensitive procedure; if it is not done correctly, the panel door can be damaged. The procedure for laying out and cutting the opening for the display must be undertaken with care and by personnel qualified and experienced in panel construction.
2. prepare and mark the position of the display opening and mounting holes
• Use the cut-out directions to lay out the opening for the Touch
1500-HAZ-TS.
• Apply two layers of masking tape around the outer perimeter of the intended opening to prevent scratching the panel surface with the jigsaw.
3. cut the display opening
Cut the opening for the Touch 1500-HAZ-TS with a jigsaw using a 24 TPI blade. Take care not to damage the panel door.
Remove all rough edges and burrs with a metal file before proceeding.
note: The following steps are most easily accomplished if the panel door is on a horizontal surface.
Inside of panel door
• Place the supplied mounting clips in each slot along the sides of the Touch 1500-HAZ-TS. Only fasten hand tight.
TOUCH 1500 display
Mounting clips
• Look at the front of the panel, and align the Touch 1500-HAZ-
TS assembly so it is level (loosen clips if necessary to reposition the assembly).
• After the display is properly positioned, tighten the mounting clips. Do not overtighten and risk damage to hardware.
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 3 / 10
toucH 1500 cut out Dimensions
296 mm (11.65 in)
Panel Cut Out
396 mm
(15.59 in)
Top of Display
Panel Cut Out Area
Drawing
NOT TO SCALE
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 4 / 10
touch 1500-HAZ-ts port Diagram
Not used USB-B Touchscreen interface to CPU
Incoming power
Not used VGA Touchscreen interface to CPU touch 1500-HAZ-cpu port Diagram (back view)
VGA (display)
CPU to touchscreen interface
COM3
RS-485
Remote
Port
USB ports
(X2)
Not used
USB ports (X2)
VGA
USB USB
COM3
RS-232/422/485
COM4
RS-232/422/485
USB LAN2 AUDIO
LAN3
LAN1
COM4
RS-485
Field
Port
Ethernet ports (X3)
ADAM-4069 pin Diagram touch 1500-HAZ-cpu port Diagram (side view)
Power switch
Incoming power
Not used
Optional mouse/ keyboard input
ADAM-4069
Relay Output
Module
8 Outputs
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 5 / 10
connect power
Connect 24 Vdc to the connection fittings to the Touch 1500-HAZ-CPU,
Touch 1500-HAZ-TS, ADAM-4069 module, and ADAM-4510I modules per the schematic on the following pages.
Line
100 – 240 Vac
50/60 Hz
Terminal block
Neutral
Terminal block
Terminal block
L N
INPUT
AC 100-240V
Phoenix Power Supply
QUINT-PS-100-240AC/24DC/10EX
Output DC 24V 10A
13 14
DC
OK + + – –
Terminal block
Alarm Lamp
Alarm
Lamp
24 V Lamp
Idec Switch/Lamp
1
2
4
3
Terminal blocks
ADAM-4069
Relay Output
Module
8 Outputs
Terminal block Terminal block
+24 Vdc
+ –
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 6 / 10
+
+24 Vdc
Power switch
Touch 1500-HAZ-CPU
Incoming power
Not used
G
– +
–
+
Terminal block Terminal block
VGA Touchscreen interface to CPU
Not used
Touch 1500-HAZ-TS
Incoming power USB-B
TS interface
Not used
G
– +
Terminal block Terminal block
+24 Vdc
–
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 7 / 10
field port communication rs-485 common Alarm light and Alarm relay
Mount the supplied ADAM-4069 modules on a DIN rail inside the panel enclosure. Mount the alarm lights on the panel’s door below the touch screen.
Wire per the schematic below.
USB VGA
Touch 1500-HAZ-TS
VGA
VGA cable
COMM 3
USB
Touch 1500-HAZ-CPU
To Alarm Lamp on Panel Door
ADAM-4069
Relay Output
Module
8 Outputs
Custom 9 pin RS-485 cable
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 8 / 10
servicing
The Touch 1500-HAZ-CPU and Touch 1500-HAZ-TS contains no user-serviceable parts. Contact your Tyco Thermal Controls representative for service and an authorization number if required.
cleaning
The touchscreen are of the Touch 1500-HAZ-TS may be cleaned with a damp or dry cloth. Typical window cleaning agents may be applied to aid in the removal of dirt, dust and grease. Do not use
abrasive cleaners.
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 9 / 10
WWW.pENTAIRTHERMAl.COM
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
AsIA pACIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
lATIN AMERICA
Tel: +1.713.868.4800
Fax: +1.713.868.2333
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2012-2015 Pentair.
inDustriAl HeAt trAcinG solutions
GB-RaychemTouch1500HAZ-IM-H58823 INSTALL-216 05/15 10 / 10
advertisement
Key Features
- Panel mounted touch screen display
- Rated NEMA 4X (IP65)
- Designed for hazardous locations
- Operates in ambient temperatures from 0°C to 50°C
- Includes sealing gasket and mounting hardware