Installation manual controller

Installation manual controller
EXCELLUM2
CONTROLLER
ENGLISH
General instructions
Excellum2 Controller unit must only be installed and put into operation by a qualified electrician.
The applicable safety regulations and accident prevention regulations must be observed.
Safety instructions
•
•
•
•
Use B 10 A or B 16 A type unit as circuit breaker. The DALI interface is insulated by a basic
insulation.
Use wires that can handle power line voltages for the entire DALI wiring.
Include DALI wiring, with a 5-core cable (e.g. NYM 5 x 1.5 mm²) if necessary, together with the
mains voltage (L, N).
Do not connect the DALI wiring with external voltage, especially not with 230 V mains voltage.
Potential overvoltage is only checked once when the controller switched on.
CAUTION!
• Incorrect mounting can lead to destruction of
the controller unit and other devices.
• The control unit should only be mounted in
switch cabinets (DIN 43880).
• The DALI standard as per IEC 62386 must be
complied with.
• Danger of electric shock.
Wiring
11-12: Mains voltage
13-14: Current Transformer (optional)
15-18: Auxiliary input
21-22: DA+/DA- line 4
23-24: DA+/DA- line 3
25-26: DA+/DA- line 2
27-28: DA+/DA- line 1
KNX: KNX Connection
A: Ethernet Slave
B: Ethernet Master
KNX
conn
A
B
(continues on next page)
Service information
Status LED
blinks green
blinks orange
blinks green/orange
press 5 sec
Button
when everything is ok, meaning controller
runs with good configuration, no electrical
connections errors under power up
when a problem was detected on power up
or configuration has problems
when its doing a firmware upgrade
will switch lights off (even unaddressed DALI
devices) a second long press switch lights on
Technical data
Operation voltage
Max. Power consumption with full DALI load
Working temperature
Leads diameter
100-240 V AC/ 50-60 Hz
23 W
0 °C … +40 °C
0.5 ... 2.5 mm² (fixed)
0.5 ... 1.5 mm² (flexible)
5-7 mm
DALI power supply
Max. number of DALI devices
(addressed)
Dimensions (L x W x H)
4 x 200 mA (basically insulated)
4 x 64
160 x 91 x 58 mm (9 HP)
Applicable standards
Safety
EMC emission
EMC resistance
DALI standard
EN 60950
EN 55022
IEC/EN 61000
IEC 62386
ETAP NV – Progress Business Centre – 7 Whittle Park Way – Slough – Berkshire – SL1 6DQ – UK
Tel. +44 (0)1628559650 – Fax +44(0)1628559012 – [email protected]
www.etaplighting.com
252077
C4E1060 – 07/2015
Conformity with applicable EU directives is confirmed by the
CE symbol. Specifications subject to change without notice