Haes Esento Marine 2-4 zone conventional fire alarm control panel Installation, Commissioning & Operating Manual

Haes Esento Marine 2-4 zone conventional fire alarm control panel Installation, Commissioning & Operating Manual

The Esento Marine 2 or 4 zone conventional control panel is a fully approved fire alarm system, compliant with European standards EN54-2 & 4. This panel is designed for use on ships and features an integral power supply and space for standby batteries. Key features include two or four fire zone circuits, two monitored sounder circuits, fire & fault VFCO relays, fire & fault switched negative outputs, class change and an alert input.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Haes Esento Marine 2-4 zone conventional Installation, Commissioning & Operating Manual | Manualzz

MARINE APPROVED 2 - 4 ZONE CONVENTIONAL

CONTROL PANEL

Installation, Commissioning &

Operating Manual

MED Ref: 0832/15

Approved Document UI-ESEN4MAR-01 Issue 4.0

Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP

Model Number

Esento Marine 2-4 zone conventional panel ESEN-2MAR/4MAR

MED Ref No.

0832-MED-1086

European Standard EN54-2 : 1997 + A1 : 2006

Control and indicating equipment for fi re detection and fi re alarm systems for buildings.

Provided Options (with requirements):

Output to fi re alarm devices, dependency type ‘A’, test condition

European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006

Power supply equipment for fi re detection and fi re alarm systems for buildings.

European Standard BS IEC60092-504 : 2001

Electrical installations in ships, special features, control and instrumentation.

European Standard BS IEC60533 : 1999

Electrical and electronic installations in ships, electromagnetic compatibility.

IMPORTANT NOTE

PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND

OBSERVE ALL ADVICE GIVEN IN IT

THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID

E.S.D

!

IMPORTANT SAFETY NOTES

ATTENTION

ABOUT THIS PANEL

PRODUCT OVERVIEW

CABINET DETAILS

CIRCUIT BOARDS

MAIN PCB TERMINALS

TECHNICAL SPECIFICATION

POWER SUPPLY MODULE

DESIGN CONSIDERATIONS

GENERAL DETECTION CIRCUIT WIRIING SCHEMATIC

GENERAL SOUNDER CIRCUIT WIRIING SCHEMATIC

INSTALLATION

SAFETY

ESD PRECAUTIONS

GENERAL

MOUNTING THE CABINET

MAINS CONNECTIONS

CONNECTING THE BATTERIES

EARTH FAULT MONITORING

SETUP & PROGRAMMING

LEVEL 3 ENGINEERING OPTIONS

ZONE INTERFACE FUNCTION

OPERATING

PANEL CONTROLS & INDICATIONS

DISABLE MODE

TEST MODE

FAULT DIAGNOSIS

FUNCTIONALITY DURING A SYSTEM FAULT

USER INSTRUCTIONS

SERVICE & MAINTENANCE

THE NEED FOR MAINTENANCE

DUTIES OF THE RESPONSIBLE PERSON

ROUTINE MAINTENANCE & TESTING

SCHEDULE OF TESTING LOG BOOK

FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK

Esento Marine 2-4 Installation, Commissioning & Operating Manual

1

CONTENTS

10

10

11

11

11

12

13

13

8

8

9

14

14

21

Page

2

5

6

7

2

3

4

22

24

24

25

26

27

27

28

28

28

28

30

36

Approved Document UI-ESENMAR-01 Issue 4.0

ABOUT THIS PANEL

PRODUCT OVERVIEW

Quiesecent and alarm current details for standby battery calculations

Model

ESEN-2MAR

ESEN-4MAR

Standby Current

75mA

85mA

Alarm Current

116mA

133mA

Esento Marine 2-4 Installation, Commissioning & Operating Manual

2

Approved Document UI-ESEN4MAR-01 Issue 4.0

CABINET

ABOUT THIS PANEL

57mm

80mm

Fire Detection System

260mm

308mm

250mm

300mm

Esento Marine 2-4 Installation, Commissioning & Operating Manual

3

Approved Document UI-ESENMAR-01 Issue 4.0

ABOUT THIS PANEL

CIRCUIT BOARDS

Esento Marine 2-4 zone panels comprise of two circuit boards

TPCA01-E2MAR/E4MAR - 2 or 4 zone Master PCB

PSU

@ + -

28V 0V

+

-

FIRE FAULT

C NC NO C NC NO

FR

FLT

CC

PUL

-OP -OP -IP -IP

SNDR1 SNDR2

+ -

ZONE1 ZONE2 ZONE3 ZONE4

+ + + + + -

TPCA02 - LED Display & Controls PCB

+ -

BATTERY

RESOUND SILENCE RESET

1 2 3 4

ENTER

ON

1 2 3

Esento Marine 2-4 Installation, Commissioning & Operating Manual

4

Approved Document UI-ESEN4MAR-01 Issue 4.0

MAIN PCB TERMINALS

Switched -ve inputs

Switched -ve outputs

Max load 40mA

Relay Coil

ABOUT THIS PANEL

PSU

@ + -

28V 0V

+

-

FIRE FAULT

C NC NO C NC NO

FR FLT CC PUL

-OP -OP -IP -IP

SNDR1 SNDR2

+ -

ZONE1 ZONE2 ZONE3 ZONE4

+ + + + + -

+ -

BATTERY

Esento Marine 2-4 Installation, Commissioning & Operating Manual

5

ON

1 2 3

Approved Document UI-ESENMAR-01 Issue 4.0

ABOUT THIS PANEL

TECHNICAL SPECIFICATION

Electrical Specifi cation Inputs & Outputs - TPCA01-H2/H4

Cabling Fire resistant screened cable, minimum size 1mm

2

. Max cable length 1Km (20

Ohm). FireBurn, FP200 or equivalent

(max capacitance 1uF, max inductance 1 millihenry).

Terminal capacity

PSU @ output

PSU Input + -

28v+, 0v- power output

Common fi re relay

Common fault relay

Outputs; FR, FLT

Inputs; CC, PUL

SNDR 1 - 2

0.5mm

2 to 2.5mm

2 solid or stranded wire.

Power supply voltage control line.

28vdc supply input. Diode protected for reversal and independent short circuit.

Max current 3 amps.

28vdc supply output for fi re alarm accessory relays etc. Max continuous use = 400mA.

Fire relay contact. Clean C/O.

Max 3A @ 30vdc

Maintained fault relay contact. Clean

C/O. Max 3A @ 30vdc

Switched -ve voltage outputs for relay control.

Switched -ve inputs, connect to 0v to trigger. Max input voltage = 28vdc. Non latching, max resistance 100R.

28vdc polarity reversal monitored sounder outputs to fi re alarm devices.

4K7 Ohm 5% 0.25W EOL resistor.

Zone 1 - 4 Fire alarm zone circuits. Conventionally wired detection circuit. 4K7 Ohm 5%

0.25W EOL resistor.

Suitable cable glands must be used.

For temperature compensation control.

Max input current 3 amps. Input voltage

22vdc to 32vdc.

Fused @ 500mA. Fuse = 500mA resettable fuse.

Unfused

Unfused

Overload voltage protected to 52vdc.

Current limited 680R. Max load = 40mA

Protected via 10K Ohm impedance, 3v6 zener diode.

Monitoring current limit 28mA, fused @

500mA. Typical max load 22 devices @

18mA each per circuit. Ensure 0.9A is not exceeded.

Monitoring current limit 50mA, fused

@ 500mA. Typical max load 22 alarm devices @ 18mA each per circuit. Ensure

0.9A is not exceeded.

General Specifi cation

Enclosure

Temperature range

Vibration

Inclination

Number of conventional detection circuits

Detector compatibility

Steel IP30. Epoxy powder coated Interpon Radon, silver grey

-5 deg C to +55 deg C max RH 95%

IEC 60068-2-6 Test F

IEC 60092-501 22.5

o

2 or 4

Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV

Esento Marine 2-4 Installation, Commissioning & Operating Manual

6

Approved Document UI-ESEN4MAR-01 Issue 4.0

ABOUT THIS PANEL

POWER SUPPLY MODULE

Power Supply Specifi cation

Mains supply

Mains supply fuse

Internal power supply rating

230vac +10% / -15% 50Hz max current

1A

2 Amp (T2A 250V) Not accessible for servicing. Internal to switch mode power unit

1.5 Amps total including battery charging Maximum load shared between outputs

= 0.9A

19.92 - 30.09vdc

Tolerance +/- 0.1%

ImaxA = 575mA ImaxB = ImaxA

Power supply output voltage

Max continuous load (ImaxA). Max continuous load whilst battery charging is not required (ImaxB).

Minimum current drawn by panel

(example)

Maximum ripple

Min/max battery size and type

Battery charging voltage

Battery charging output current

4 Zone

I min = 85mA

1.0 V p-p

2 x 3.2Ahr 12volt VRLA

Use Yuasa NP range batteries

2 Zone

I min = 75mA

Supply and charger fault monitored

Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.

Temperature compensated

Battery high impedance fault (Batt Hi Z)

Max current drawn from batteries

27.3 vdc nominal at 20 deg C

1.5A PSU 630mA

Current limited 10 Ohms

Resistance = 1 Ohm or greater

1.5 Amps with main power source disconnected. Battery fuse 3A LBC

20mm.

1 hour reporting time

Esento Marine 2-4 Installation, Commissioning & Operating Manual

7

Approved Document UI-ESENMAR-01 Issue 4.0

DESIGN CONSIDERATIONS

TYPICAL DETECTION CIRCUIT SCHEMATIC

4K7 OHM

END OF LINE

RESISTOR

APOLLO S65 BASE

45681-201

-

R L2

IN

L1

OUT

L1

+

MANUAL CALL POINT

MCP1A-R-470

470

_ _

+ +

1 2 3 4

APOLLO S65 BASE

45681-201

-

R

L2

IN

L1

OUT

L1

APOLLO S65 BASE

45681-201

-

R

L2

IN

L1

OUT

L1

ZONE 1

+ -

Esento Marine 2-4 Installation, Commissioning & Operating Manual

8

Approved Document UI-ESEN4MAR-01 Issue 4.0

TYPICAL SOUNDER CIRCUIT SCHEMATIC

4K7 OHM

END OF LINE

RESISTOR

DESIGN CONSIDERATIONS

MOTORISED BELL

POLARISED

+VE

-VE

MOTORISED BELL

POLARISED

+VE -VE

+VE

ELECTRONIC SOUNDER

POLARISED

-VE

+VE

ELECTRONIC SOUNDER

POLARISED

-VE

SNDR1

+ -

Esento Marine 2-4 Installation, Commissioning & Operating Manual

9

Approved Document UI-ESENMAR-01 Issue 4.0

INSTALLATION

SAFETY

(i) Codes of Practice

(ii) Statutory requirements

(iii) Any instructions specifi cally advised by the manufacturer

!

This equipment must only be installed and maintained by a suitably skilled and technically competent person.

THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED

Equipment Guarantee

This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.

This product has been manufactured in conformance with the requirements of all applicable EU Council

Directives

Esento Marine 2-4 Installation, Commissioning & Operating Manual

10

Approved Document UI-ESEN4MAR-01 Issue 4.0

INSTALLATION

ESD PRECAUTION

GENERAL

segregated away from mains voltage.

• Any junction boxes used should be clearly labelled FIRE ALARM.

• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.

• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.

MOUNTING THE CABINET

Before mounting the cabinet remove the main PCB.

Remove the power supply module connecting wires from the main PCB, taking care to note where to reconnect them. The main PCB can then be carefully pulled off it’s mounting clips.

Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level and in a convenient location where it may be easily operated and serviced.

External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any knockouts and ensure the cabinet is clear of swarf etc prior to refi tting the PCB. Always ensure that if a knockout is removed, the hole is fi lled with a good quality cable gland. Any unused knockouts must be securely blanked off.

Knockouts should be removed with a sharp tap at the rim of the knockout using a fl at 6mm broad bladed screwdriver.

Use of excessive force will damage the enclosure around the knockout.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

11

Approved Document UI-ESENMAR-01 Issue 4.0

INSTALLATION

Typical panel layout

Incoming mains wiring

Filter

Low voltage detection and sounder circuit wiring

PSU

@ + -

28V 0V

+

-

C

FIRE

NC NO C

FAULT

NC NO

FR FLT CC PUL

-OP -OP -IP -IP

SNDR1

+ -

SNDR2

+ -

ZONE1

+ -

ZONE2 ZONE3

+ + -

ZONE4

+ -

ON

1 2 3

+ -

BATTERY

Battery

Clamp

12V 3.2Ah VRLA BATTERY

12V 3.2Ah VRLA BATTERY

Drawing shows typical internal layout of the panel cabinet with two 3.2Ah, 12v batteries fi tted

MAINS CONNECTIONS

Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.

A rating plate is attached to the power supply module describing the nature of the supply permitted.

The incoming mains supply should be brought into the panel via one of the knockouts provided.

A suitable cable gland must be used to secure the outer sheath of the cable used. The earth must fi rst be connected to the primary earth stud (peg) marked with a symbol, using the ring crimp provided.

Suffi cient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

12

Approved Document UI-ESEN4MAR-01 Issue 4.0

INSTALLATION

CONNECTING THE BATTERIES

Batteries of even very small capacity are capable of delivering very high currents which can cause fi re or injury, therefore battery connections should be done with caution.

The panel is supplied with battery leads already connected to the battery terminals on the main PCB.

These leads are coloured red for +ve and black for -ve.

+ -

BATTERY

ON

1 2 3

2 x 12v batteries should be connected in series using the white jumper lead provided. See diagram.

To optimise the service life of the batteries, the battery charger output voltage varies with temperature.

-ve

12v SLA Battery 12v SLA Battery

+ve

N.B.

In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below 19v. When the mains supply is restored the batteries will be automatically reconnected.

NOTE:

If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute until the monitoring cylce has fi nished polling. This is normal. If the fault doesn’t clear after 1 minute, check connections.

For on ship use:- battery retaining clamps must be fi tted.

BATTERY CHARGING VOLTAGE CHECKS

The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20 o

C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.

a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.

b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11 o

C - 40 o

C.

c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the battery voltage, should be 26.8v for a good battery or 22v for a fl at battery.

d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will over ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, switch off Access Level 3 DIL switch and re-connect the batteries.

e) When the panel is re-charging a low battery, it should be possible to see the voltage across the batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.

EARTH FAULT MONITORING

The Marine panels are equipped with earth fault monitoring to the 28v supply rails. Any cable connected to earth will cause an earth fault to be indicated. The earth fault LED is located internally next to the program options switch on the main circuit board. If an earth fault exists a PSU Fault (and General Fault) will be indicated externally. The internal LED will show continuously for earth faults on the -ve polarity cables and pulse for +ve polarity cables. (Be aware sounder cables monitor in reverse). Identifying the source of the earth fault requires systematically removing cables until the fault clears. There is a 30 second delay to the earth fault signal to avoid spurious faults due to noise.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

13

Approved Document UI-ESENMAR-01 Issue 4.0

SETUP & PROGRAMMING

LEVEL 3 ENGINEERING OPTIONS

A series of programmable engineering options are available. These programming modes are initiated by entering a four digit code using buttons 1 - 4 on the keypad followed by the ENTER button.

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

To access Level 3 options, fi rst set switch 3 on the 3 way DIL switch located on the main PCB to the

‘ON’ position. Then activate the controls by entering the four digit code (see Activate Controls in the

OPERATING section).

1 SNDR2

+ -

ZONE1 ZONE2 ZONE3 ZONE4

+ + + + -

The ‘Access Level’ indicator will pulse rapidly to signify that Level 3 access is active.

1 2 3 4 5 6 7

ON

1 2 3

ON

1 2 3

ON

1 2 3

Options

1 1 1 3

Reset all disablements, test modes and parameters back to factory settings.

Enter the above code and press the ENTER button.

Then press the ENTER button again and hold for 3 seconds.

Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings.

The panel will bleep to acknowledge the reset.

1

RESOUND

Disable

Mode

2

Test

Mode

SILENCE

3 4

Mute

Buzzer

Test

Lamps

RESET

ENTER

2 2 2 4

Set fault buzzer volume.

There are two levels of volume for the internal fault buzzer, high and low.

Enter the above code and press the ENTER button to increase or decrease the fault buzzer tone from the previous level.

Setting will change when ENTER button is pressed.

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

When fi nished, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

14

Approved Document UI-ESEN4MAR-01 Issue 4.0

SETUP & PROGRAMMING

1 2 2 2

Muster Alarm Signal.

This option is used to select zones for activation of a muster alarm signal. A muster alarm is defi ned as 7 short blasts of the sounders, followed by 1 long blast. This is repeated until silenced. The activated muster alarm zone will show a fi re indication at the panel but no common fi re LED. The panels outputs can be programmed to respond to a muster alarm using seperate option codes.

A second setting is provided to enable the panels ‘RESOUND’ button to activate the muster alarm signal.

Note: With panel software V4.1 and above, muster alarm will have priority over any new fi re alarms by

default. It is possible to make fi re a higher priority using option 3.

Enter the above code and press the ENTER button.

The zone 1 fi re LED will be on steady. Use button 1 to toggle between steady fi re LEDs 1, for setting muster alam zones,

2, for setting RESOUND button to activate muster alarm or 3, for changing muster alarm priority.

LED 1

Select muster alarm zones

LED 2

Set

RESOUND button

LED 3

Set muster alarm priority

OFF

Set Muster Alarm Zones [LED 1]

With the zone 1 fi re LED lit press the ENTER button and the LED will pulse to indicate setting zone 1 to muster alarm. Use button 1 to move the pulsing fi re LED to the required zone and then use button 2 to change the setting, indicated by the amber fault LED ON or OFF. Any or all zones may be set for muster alarm.

ON = muster alarm zone, OFF = standard.

Set RESOUND Button Operation For Muster Alarm [LED 2]

With the zone 2 fi re LED lit press the ENTER button. Fire LED 2 will now pulse to indicate editing mode.

Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.

ON = RESOUND button activates muster alarm, OFF = RESOUND button activates evacuate (default).

Set Fire As Priority Over Muster Alarm [LED 3]

With the zone 3 fi re LED lit press the ENTER button. Fire LED 3 will now pulse to indicate editing mode.

Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.

OFF = muster alarm has priority, ON = fi re has priority.

When fi nished, press and hold button 1 to store settings and exit programming mode. Then enter next programming code or return DIL switch 3 to ‘OFF’ position and disable controls.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

15

Approved Document UI-ESENMAR-01 Issue 4.0

SETUP & PROGRAMMING

2 1 2 3

Panel Wide Settings

There are 4 general, panel wide, settings available.

RESOUND

Enter the above code and press the ENTER button. The 4 programmable options are represented by fi re zone LEDs 1 - 4.

1

Disable

Mode

2

Test

Mode

SILENCE

3

Mute

Buzzer

4

Test

Lamps

RESET

ENTER

Use button 1 to move to option required as per table;

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

2

3

4

Fire LED Programming Option

1 Change / remove keypad access code

Set presence of output card

Inhibit muted tone beeps

UPS Mode / Disable battery monitoring

OPTION 1.

Change / Remove Keypad Access Code

The keypad can be used to activate the panel controls instead of using the key switch. The default code is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable controls, forcing the use of the key switch only.

With the zone 1 fi re LED lit, press the ENTER button. Zone 1 fi re LED will pulse to indicate ‘edit mode’ and the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.

Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4

Note: Enable Controls codes must always start with a 1 or 2.

When fi nished entering the new four digit code, press the ENTER button. The panel will then confi rm the new code with rapidly pulsing LEDs in sequence and zone 1 fi re LED will return to steady ‘view mode’.

Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.

Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3. (The panel will confi rm the new access code one more time before exiting the programming mode).

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

16

Approved Document UI-ESEN4MAR-01 Issue 4.0

SETUP & PROGRAMMING

OPTION 2

. Set Presence of Output Card

An output/relay card may be added to each control panel to provide additional common or zonal outputs.

The presence of the card must be setup to enable operation.

With the zone 2 fi re LED lit, the amber, fault LED (zone 1) will show the current setting.

Zone 1 amber fault LED ON = Output Card present.

Press the ENTER button, zone 1 fi re LED will pulse to indicate adding or removing the card.

Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF

(removed).

When fi nished press the ENTER button again and the zone 2 fi re LED will return to steady ‘view mode’.

Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.

OPTION 3

. Inhibit Muted Tone Beeps

With the zone 3 fi re LED lit press the ENTER button. The zone 1 fi re LED will pulse to indicate ‘edit mode’.

Press button 1 to light the zone 1 amber fault LED. - Beeps are now silenced.

OPTION 4.

UPS Mode / Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)

The battery monitoring may be disabled for applications where this is appropriate such as non fi re alarm use or where no battery backup is required.

Note: There is no remote PSU fault input available on the

panel. This is also known as ‘UPS Mode’ where the panel is supplied from a local 24v supply rather than

mains and intenal batteries.

With the zone 4 fi re LED lit, the amber, fault LEDs will show the current setting.

FAULT LED 1

OFF

ON

ON

OFF

FAULT LED 2

ON

ON

OFF

OFF

SETTINGS

Battery & Hi Z monitoring normal (default)

Battery & Hi Z monitoring both ‘OFF’ (UPS mode)

Battery & Hi Z monitoring both ‘OFF’ (UPS mode)

Battery monitoring ‘ON’, Hi Z monitoring ‘OFF’

Press the ENTER button, zone 1 fi re LED will pulse to indicate ‘edit mode’ for std battery monitoring.

Use button 1 to toggle between pulsing fi re LEDs 1 & 2 for editing std or Hi Z battery monitoring as per above.

Now use button 2 to change the setting indicated by the amber fault LED as per above.

When fi nished press the ENTER button again and the zone 4 fi re LED will return to steady ‘view mode’.

Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.

Note: When batteries are unmonitored the input 24v dc voltage may vary between 20v dc & 32v dc.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

17

Approved Document UI-ESENMAR-01 Issue 4.0

SETUP & PROGRAMMING

1 1 1 4

Select sounder resound options for zones.

By default, after an initial fi re condition and the (blue) Silence Alarms button has been activated, any new fi re condition in a different zone will cause the alarms to resound.

It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the alarms.

Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault

LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.

Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to not resound alarms, the LED will be off. If kept as default, new fi re condition will resound alarms, then the LED will be on steady.

Rapid Pulse = Zone is under selection and is set to have alarms resound (default).

Slow Pulse = Zone is under selection and has been set to not resound alarms on new fi re condition.

LED Off = Zone has been set to not resound alarms on new fi re condition.

LED On = Zone is set to have alarms resound (default).

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.

Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

18

Approved Document UI-ESEN4MAR-01 Issue 4.0

SETUP & PROGRAMMING

3 1 2 1

Zone Function Settings

There are 4 functional settings available for each zone. These are as follows:

Fire latching

Normally a zone latches a fi re input signal. This setting allows the panel to clear automatically when a fi re signal is removed. This is useful for interfacing purposes.

Short circuit as alarm (EN54!)

For Older non EN54 or BS5839 compliant systems. This allows a short circuit to activate a fi re rather than a fault condition.

Intrinsically safe operation

This option changes the zone alarm and short circuit thresholds to allow for an MTL 5061 type intrinsically safe barrier to be used in the circuit.

Detector removal monitoring (EN54!)

The detector removal monitoring can be turned off. For use with older, non compliant detectors.

RESOUND SILENCE RESET

Enter the above code and press the ENTER button.

The zone 1 fi re LED will light. This indicates setting the above attributes for zone 1.

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

The amber, fault / disabled / test LEDs will show the current settings for that zone.

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

Use button 1 to move to the zone that requires editing.

RESOUND

With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.

1

Disable

Mode

2

Test

Mode

SILENCE

3

Mute

Buzzer

4

Test

Lamps

RESET

ENTER

The fi re zone 1 LED will now pulse to indicate the editing of attribute 1 (fi re latching) for the selected zone.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

19

Approved Document UI-ESENMAR-01 Issue 4.0

SETUP & PROGRAMMING

Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 4 as per table below.

Fire LED

(pulsing)

LED 1

Attribute

Fire latching

Amber fault LED

(default setting)

ON

LED 2

Short circuit as fi re

OFF OFF ON

RESOUND SILENCE RESET

1

Disable

Mode

2 3 4

Test

Mode

Mute

Buzzer

Test

Lamps

ENTER

LED 3 LED 4

Intrinsically safe operation

Detector removal monitoring

The setting of the attribute is indicated by the amber, fault LED,

ON or OFF.

Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault LED.

Then use button 1 to move to the next attribute if required.

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

RESOUND SILENCE RESET

Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

When fi nished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

20

Approved Document UI-ESEN4MAR-01 Issue 4.0

SETUP & PROGRAMMING

2 1 1 4

Type ‘A’ dependency mode.

Dependency ‘A’ (confi rmation alarm) is a requirement by some monitoring stations and local fi re authoities to reduce the possibility of false alarms.

Dependency ‘A’ zones will apply the following sequence:

Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.

A 470Ω call point will be included in the dependency delay sequence.

By default this is set to ‘off’ for all zones.

To set zones to Type ‘A’ Dependency, enter the above code and press the ENTER button. The Aux Output

Status LED will pulse slowly. Zone Fault LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.

Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to confi rmation alarm mode, the LED will remain on. If kept as standard alarm mode then the

LED will be off.

Slow Pulse = Zone is under selection and is set to standard alarm mode.

Rapid Pulse = Zone is under selection and has been set to confi rmation alarm mode.

LED Off = Zone is set to standard alarm mode.

LED On = Zone has been set to confi rmation alarm mode.

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.

Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

21

Approved Document UI-ESENMAR-01 Issue 4.0

SETUP & PROGRAMMING

4 2 4 2

Common fi re outputs cancel on silence alarms

The Common Fire VFCO relay output and the Common Fire switched -ve output, when activated, normally remain until the panel is RESET.

This option changes these outputs to reset on SILENCE ALARMS. This may be useful for panel interlink purposes.

Both outputs can be programmed independently.

RESOUND SILENCE RESET

1 2

Disable

Mode

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

ENTER

PSU

@ + -

28V 0V

+

-

FIRE FAULT

C NC NO C NC NO

FR FLT CC PUL

-OP -OP -IP -IP

SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4

+ + + + + + -

Enter the above code and press the ENTER button.

The red Zone 1 fi re LED will illuminate, this LED represents the Common Fire VFCO relay output.

Pressing Button 1 (Disable Mode) will move to red Zone 2 fi re LED which represents the Common Fire switched -ve output. Subsequent presses will toggle between them.

With the required fi re LED lit press the ENTER button and Zone 1, fi re LED will pulse.

Press button 2 (Test Mode) to alter the status of the output, represented by the Zone 1, Fault LED either off or on.

Off = Output cancels on RESET (factory default)

On = Output cancels on SILENCE ALARMS.

When the output status has been set, press the ENTER button to return to the output selection mode.

When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.

Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

22

Approved Document UI-ESEN4MAR-01 Issue 4.0

SETUP & PROGRAMMING

4 3 4 4

Conventional Sounder Circuit Functional Options

This option is used to programme each of the conventional sounder circuits on the main circuit board with custom reponses as below.

Enter the above code and press ENTER. Then use button 1 to select the sounder circuit to be programmed (indicated by a steady fi re zone LED) as per table.

LED 1

SNDR1

(Main

LED 2

SNDR2

(Main

With the required sounder LED lit, press the ENTER button. Fire zone LED 1 will now pulse. This indicates setting up function 1 (resets on silence alarms) for the selected

PCB) PCB) circuit. Use button 1 to scroll to the required function, indicated buy pulsing fi re LEDs 1- 4 as per table below.

Fire LED

(pulsing)

LED 1 LED 2 LED 3 LED 4

Use button 2 to change the response to ON or OFF, indicated by the amber fault LEDs.

Function

Resets on

Silence

Alarms

Activates on

Evacuate

Activates on Class

Change

Activates on Alert

Then use button 1 again to scroll to the next function if required.

Amber fault LED

(default setting)

OFF ON OFF OFF

Press the ENTER button to return back to sounder circuit selection, indicated by a steady fi re LED.

ZONE INTERFACE FUNCTION

This is a special setting to confi gure the last zone on the panel, (i.e. zone 2 on the 2 zone or zone 4 on the

4 zone), to be used for interconnection from other control panels.

The function is enabled by setting switch 2 on the 3 way DIL switch located on the main PCB to the ‘ON’ position.

1 2 3 4 5 6 7

With switch 1 in the ‘ON’ position, the last zone becomes;

ON

1 2 3

Example connection

ZONE2 ZONE3 ZONE4

+ + + -

PANEL 1

Esento Marine 2-4 Installation, Commissioning & Operating Manual

23

3K3Ω

470Ω

C NC NO C NC NO

FIRE

FAULT

(optional)

PANEL 2

Approved Document UI-ESENMAR-01 Issue 4.0

OPERATING

PANEL CONTROLS & INDICATIONS

Zonal Fire Indicator LEDs

Status Indicator LEDs

Zones In Fault, Zones Disabled or

Zones In Test Indicator LEDs

1

Zones in Fire

2 3

Zone Fault / Disabled / Test

4

RESOUND SILENCE RESET

1 2 3 4

ENTER

Supply Healthy

General Fire

General Fault

General Disablement

Test Mode

Sounder Status

Aux Output Status

Power Supply Fault

System Fault

Access Level

Fire Detection System

8 Button Keypad For Controls

And Programming

Activate Controls Key Switch

Activate Controls

In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.

The use of a code entry to activate the controls is enabled by default but can be disabled in the engineering functions.

To activate the controls using the key switch; turn the key clockwise to the ‘On’ position. The ‘Access

Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.

If the key switch is in the ‘On’ position the keypad will remain active.

NOTE : It is not possible to remove the key in the ‘On’ position.

To activate the controls using the keypad; enter the four digit code using buttons 1 - 4. The factory

default code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press the ‘ENTER’ button. The ‘Access Level’ indicator LED will light and all buttons on the keypad will now be operational.

After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode.

The test lamps and mute buzzer functions are operational without the need to activate controls.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

24

Approved Document UI-ESEN4MAR-01 Issue 4.0

OPERATING

Status LED Indicators

Zones in Fire 1 - 4

Zone Fault/Disabled/Test

1 - 4

Supply Healthy:

General Fire:

General Fault:

General Disablement:

Test Mode:

Sounder Status:

Aux Output Status:

Power Supply Fault:

System Fault:

Access Level:

Earth Fault (internal LED)

LED On

N/A

LED Pulsing

Indicates alarm condition in zone.

Indicates zone circuit is disabled or in test mode.

Indicates a fault in the zone circuit.

Indicates mains and/or battery supply is present.

N/A

N/A

Indicates panel is in alarm condition.

Indicates one or more faults are present.

N/A

Indicates one or more circuits have been disabled.

Indicates one or more circuits are in test mode

Indicates sounder circuits have been disabled or are in test mode

Indicates auxiliary outputs have been disabled.

N/A

Indicates a system failure, panel not functional.

Indicates controls are active (access level

2).

Indicates disablement selection mode is active.

Indicates test mode selection is active.

Indicates a fault on one or more sounder circuits.

N/A

Indicates a power supply, battery or earth fault.

Indicates the panel has recovered from a system fault.

Indicates panel is in confi guration mode (access level 3).

-ve earth fault +ve earth fault

RESOUND SILENCE RESET

Keypad

1

Disable

Mode

2

Test

Mode

3

Mute

Buzzer

4

Test

Lamps

ENTER

RESOUND (red):

SILENCE (blue):

RESET (green):

1: (Disable Mode)

2: (Test Mode)

3: (Mute Buzzer)

4: (Test Lamps &

Buzzer)

ENTER:

Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.

Use to silence the sounders during an alarm condition.

Resets the panel back to standby mode.

With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the numeric value 1 for code entry.

With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric value 2 for code entry.

Mutes the panels internal fi re and fault buzzer. (The buzzer will still blip every 5-6 seconds during a fi re or fault condition). This function is operational without the need to activate controls. Also has the numeric value 3 for code entry.

Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working correctly. This function is operational without the need to activate controls. Also has the numeric value

4 for code entry.

This button is used to confi rm code entries. It can also be used for fault diagnosis (see FAULT

DIAGNOSIS section).

Some buttons have other functions within the engineering facilities. These functions are described in the relevant sections.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

25

Approved Document UI-ESENMAR-01 Issue 4.0

OPERATING

DISABLE MODE

Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits or all auxiliary outputs.

To initialise Disable Mode, fi rstly activate the controls by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.

After 3 seconds the panel will bleep and the General Disablement

LED and Zone 1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in disable selection mode.

1

RESOUND

Disable

Mode

2

Test

Mode

SILENCE

3

Mute

Buzzer

4

Test

Lamps

RESET

ENTER

Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault/

Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.

After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by the Sounder

Status LED and then to the Aux outputs, indicated by the Aux Output Status LED. Pressing the button once more will move the selection back to Zone 1 again.

When the desired circuit or output to be disabled is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the circuit between disabled and enabled. Then use Disable Mode button again to move to the next circuit. Any or all circuits can be disabled simultaneously.

1

RESOUND

2

SILENCE

3 4

RESET

ENTER

Disable

Mode

Test

Mode

Mute

Buzzer

Test

Lamps

When all disablements have been set, press and hold the Disable Mode button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby.

All disabled circuits and the General Disablement will now be indicated by a steady LED.

To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement.

Tip:

With the controls active, pressing the Disable Mode button briefl y will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

26

Approved Document UI-ESEN4MAR-01 Issue 4.0

OPERATING

TEST MODE

Test Mode is used when testing the fi re alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person. It is possible to test head removal monitoring and to test the system with or without the sounders.

To initialise Test Mode, fi rstly activate the controls by entering the four digit code. Then press and hold the Test Mode button (2) for 3 seconds.

After 3 seconds the panel will bleep and the Test Mode LED and Zone

1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in test selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be

with sounders. (Test mode

without sounders is explained below)

1

RESOUND

Disable

Mode

2

Test

Mode

SILENCE

3

Mute

Buzzer

4

Test

Lamps

RESET

ENTER

Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault/

Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.

After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by no Zone

Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test.

Pressing the button once more will move the selection back to Zone 1 again.

When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the zone between in and out of test. Then use Test Mode button again to move to the next zone. Any or all zones can be in test mode simultaneously.

RESOUND

1

Disable

Mode

When at the sounder status position, use the ENTER button to toggle between testing with or without sounders. A rapid pulse = with sounders

(default), a slow pulse = without sounders.

SILENCE

2 3 4

Test

Mode

Mute

Buzzer

Test

Lamps

RESET

ENTER

When all zones to be tested have been set, press and hold the Test Mode button for 3 seconds again. This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.

To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and the ENTER button to change the status.

Test Mode With Sounders

Activation of a call point or detector - sounders will pulse twice, device is automatically reset.

Removal of a detector - sounders will pulse once.

Test Mode Without Sounders

Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.

Tip:

With the controls active, pressing the Test Mode button briefl y will reveal which circuits are in test mode

(as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

27

Approved Document UI-ESENMAR-01 Issue 4.0

OPERATING

FAULT DIAGNOSIS

If the panel has detected a fault on the system the General Fault LED will be illuminated and the internal fault buzzer will sound. Secondary LEDs will also be illuminated depending on the location of the fault.

Pressing and holding the ENTER button will reveal more detailed information about the loction and type of fault.

RESOUND

This function will not work if the panel is in a fi re condition. If no faults exist pressing the ENTER button will have no effect.

This function is only operational when controls are not active.

1

Disable

Mode

2

Test

Mode

The following table shows details of the indications in fault diagnosis mode:

SILENCE

3

Mute

Buzzer

4

Test

Lamps

RESET

ENTER

LED Indicator

& State before pressing ENTER

LED Pulsing after pressing ENTER

Zone 1 Fire LED

(off)

Zone 2 Fire LED

(off)

Zone 1 - 4 Fault/

Disabled/Test LED

(pulsing)

Zone 1 - 4 Fault/

Disabled/Test LED

(steady)

Power Supply

Fault LED (pulsing)

Sounder circuit 1 short circuit

Sounder circuit 2 short circuit

Zone # short circuit

N/A

Mains failure

LED Steady after pressing ENTER

Sounder circuit 1 open circuit

Sounder circuit 2 open circuit

Zone # open circuit

N/A

Battery failure or high impedance

LED Off after pressing ENTER

OK

OK

Voltage fault

Location

Main PCB SNDR 1

Main PCB SNDR 2

(slow pulse)

Zone # detector removed

Zone # disabled or in test mode

Main PCB Zones

1 - 4

Main PCB

Esento Marine 2-4 Installation, Commissioning & Operating Manual

28

Approved Document UI-ESEN4MAR-01 Issue 4.0

OPERATING

FUNCTIONALITY DURING A SYSTEM FAULT

A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. In the event of a system fault the particular board affected may not be functional. The following indications may be observed.

Display Board

System Fault LED only continous and continous buzzer sound. Display board TPCA02 is halted and no other indication or control is possible. Fault relay and fault output are activated. If a fi re occurs alarm sounders and outputs will still function.

Main Board

System Fault LED continous and General Fault LED pulsing and continous buzzer sound. Main board is halted. Fault relay is activated. No alarms may be activated on the system.

System Fault recovery

System Fault LED pulsing and General Fault LED pulsing along with a pulsed buzzer (fault tone) a system fault has occurred and the affected board has recovered. The indication will remain until the panel is reset.

USER INSTRUCTIONS

If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.

A responsible person should then:-

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

fi g 1

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

fi g 2

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

fi g 3

ENTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

29

Approved Document UI-ESENMAR-01 Issue 4.0

SERVICE & MAINTENANCE

The following section is a summary of the requirements in BS5839 Part 1

For comprehensive information a copy of BS5839 Part 1 can be purchased from the British Standards

Institution via their web site at www.bsi-global.com.

THE NEED FOR MAINTENANCE

Your Fire Alarm System is working 24 hours a day, 365 days a year. The detectors and control & indicating panel are operating continuously and the fi re alarm circuits are constantly monitored.

Legislation such as the Regulatory Reform (Fire Safety) Order 2005 and other legislation protecting both employees and the public require premises operators to conform with standards for Fire Alarm Systems.

It is a requirement of BS 5839 Part 1 that the system is subject to periodic inspection and servicing so that faults are identifi ed, preventive measures can be taken to ensure the continued reliability of the system, false alarm problems are identifi ed and suitably addressed, and the user is made aware of any changes to the building that affect the protection afforded by the system.

The inspection and servicing recommendations in this clause should be carried out by a competent person. A ‘Competent Person’ is a person or fi re alarm servicing organisation with specialist knowledge of fi re detection and fi re alarm systems, including knowledge of the causes of false alarms, suffi cient information regarding the system, and adequate access to spares.

The period between successive inspection and servicing visits should be based upon a risk assessment, taking into account the type of system installed, the environment in which it operates and other factors that may affect the long term operation of the system. The recommended period between successive inspection and servicing visits should not exceed six months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this part of BS 5839

DUTIES OF THE RESPONSIBLE PERSON

The system user needs to appoint a single, named member of the premises management to supervise all matters pertaining to the fi re detection and fi re alarm system. The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1, that appropriate records are kept and that relevant occupants in the protected premises are aware of their roles and responsibilities in connection with the fi re detection and fi re alarm system.

This person also needs to ensure that necessary steps are taken to avoid situations that are detrimental to the standard of protection afforded by the system and to ensure that the level of false alarms is minimized.

ROUTINE MAINTENANCE & TESTING

DAILY

The ‘Responsible Person’ should check the control panel to make sure no faults or pre-alarm conditions are indicated and that the green ‘Supply Healthy’ lamp is lit.

WEEKLY

The Fire Alarm System should be tested on a weekly basis as recommended in BS5839 Part 1 clause 44.2.

Every week a manual call point should be operated during normal working hours. The weekly test should be carried out at approximately the same time each week. Instructions to the occupants should be that they report any instance of poor audibility of the fi re alarm signal.

A different manual call point should be used at the time of every weekly test so that all manual call points in the building are tested in rotation over a prolonged period.

The result of the weekly test and the identity or location of the manual call point used should be recorded in the system log book.

Esento Marine 2-4 Installation, Commissioning & Operating Manual

30

Approved Document UI-ESEN4MAR-01 Issue 4.0

SERVICE & MAINTENANCE

WEEKLY TEST

The call point test key should be inserted fi rmly and deliberately into the bottom of the manual call point.

Once activated it may be necessary to wait up to four seconds before the alarms sound.

Your manual call points may not be the same as the ones described above. If not please refer to your service and maintenance company for instructions.

Note:

Before testing the fi re alarm system it may be necessary to isolate ancillary outputs.

It is essential that any alarm receiving centre is contacted immediately before and immediately after, the weekly test to ensure that unwanted alarms are avoided and that fi re alarm signals are correctly received at the alarm receiving centre.

PERIODIC INSPECTION & SERVICING

Inspection & servicing should only be carried out by a ‘Competent Person’ who has suffi cient knowledge to check the whole system. This would normally be a qualifi ed electrical contractor or fi re alarm specialist.

Inspection & servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis. The maximum period between inspections must not exceed six months.

Recommendations of BS5839-1 for periodic service visits include:

• Every device on the system should be tested annually. The testing of each device can be split between periodic visits but with a minimum of one detector or call point tested on each circuit, per visit.

• On each visit the ‘Competent Person’ should check the record of false alarms. Any persistent occurrence should be investigated and corrective action taken as appropriate.

• Battery and connections should be examined and load tested to check serviceable condition and that they are not likely to fail before the next service visit.

• All other devices and control & indicating equipment should be checked for correct operation and any faults should be recorded and rectifi ed.

• Details of the service visit must be recorded in the log book

EVERY FOUR YEARS

Renew the sealed lead acid batteries and record the fact in the log book

Esento Marine 2-4 Installation, Commissioning & Operating Manual

31

Approved Document UI-ESENMAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

32

Approved Document UI-ESEN4MAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

33

Approved Document UI-ESEN4MAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

34

Approved Document UI-ESEN4MAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

35

Approved Document UI-ESEN4MAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

36

Approved Document UI-ESEN4MAR-01 Issue 4.0

D DATE &

TIME OF TEST

SCHEDULE OF TESTING

This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System

DEVICE TESTED &

LOCATION

COMMENTS

(IF ANY)

INITIALS OF

TESTER

Esento Marine 2-4 Installation, Commissioning & Operating Manual

37

Approved Document UI-ESEN4MAR-01 Issue 4.0

FALSE ALARMS, FAULTS & ENGINEERS VISITS

Fault/Reason For

Call-Out

Action Taken Date Work Completed Engineer’s Details

Esento Marine 2-4 Installation, Commissioning & Operating Manual

38

Approved Document UI-ESEN4MAR-01 Issue 4.0

FALSE ALARMS, FAULTS & ENGINEERS VISITS

Fault/Reason For

Call-Out

Action Taken Date Work Completed Engineer’s Details

Esento Marine 2-4 Installation, Commissioning & Operating Manual

39

Approved Document UI-ESEN4MAR-01 Issue 4.0

FALSE ALARMS, FAULTS & ENGINEERS VISITS

Fault/Reason For

Call-Out

Action Taken Date Work Completed Engineer’s Details

Esento Marine 2-4 Installation, Commissioning & Operating Manual

40

Approved Document UI-ESEN4MAR-01 Issue 4.0

USER INSTRUCTIONS

If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.

A responsible person should then:-

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

fi g 1

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

3 4

Mute

Buzzer

Test

Lamps

fi g 2

ENTER

RESOUND SILENCE RESET

1

Disable

Mode

2

Test

Mode

fi g 3

3 4

Mute

Buzzer

Test

Lamps

ENTER

The internal fault buzzer can be silenced by pressing MUTE BUZZER (button 3 on the keypad). DO

NOT RESET THE SYSTEM UNTIL AN ENGINEER HAS INVESTIGATED THE FAULT.

www.haes-systems.com

advertisement

Key Features

  • European standards EN54-2 & 4 compliant
  • Integral power supply
  • Space for standby batteries
  • Two or four fire zone circuits
  • Two monitored sounder circuits
  • Fire & fault VFCO relays
  • Fire & fault switched negative outputs
  • Class change and an alert input

Frequently Answers and Questions

What are the quiescent and alarm current details for standby battery calculations?
The standby current is 75mA for the ESEN-2MAR and 85mA for the ESEN-4MAR. The alarm current is 116mA for the ESEN-2MAR and 133mA for the ESEN-4MAR.
What are the minimum and maximum battery size and type?
The minimum battery size and type is 2 x 3.2Ahr 12volt VRLA. The recommended battery type is Yuasa NP range batteries. Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.
What are the maximum load shared between outputs?
The maximum load shared between outputs is 0.9A.
What is the maximum input current?
The maximum input current is 3 Amps.
What is the maximum load for the 28v+, 0v- power output?
The maximum continuous use of the 28v+, 0v- power output is 400mA.
How do I connect the batteries?
The panel is supplied with battery leads already connected to the battery terminals on the main PCB. Connect two 12v batteries in series using the white jumper lead provided.
How do I adjust the battery charging voltage?
You can adjust the battery charging voltage using the potentiometer on the power supply module. Disconnect the batteries and set the Access Level 3 DIL switch to ‘ON’. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, switch off Access Level 3 DIL switch and re-connect the batteries.

Related manuals

Download PDF

advertisement