- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Haes
- Esento Marine 2-4 zone conventional
- User manual
- 44 Pages
Haes Esento Marine 2-4 zone conventional fire alarm control panel Installation, Commissioning & Operating Manual
The Esento Marine 2 or 4 zone conventional control panel is a fully approved fire alarm system, compliant with European standards EN54-2 & 4. This panel is designed for use on ships and features an integral power supply and space for standby batteries. Key features include two or four fire zone circuits, two monitored sounder circuits, fire & fault VFCO relays, fire & fault switched negative outputs, class change and an alert input.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
MARINE APPROVED 2 - 4 ZONE CONVENTIONAL
CONTROL PANEL
Installation, Commissioning &
Operating Manual
MED Ref: 0832/15
Approved Document UI-ESEN4MAR-01 Issue 4.0
Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP
Model Number
Esento Marine 2-4 zone conventional panel ESEN-2MAR/4MAR
MED Ref No.
0832-MED-1086
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fi re detection and fi re alarm systems for buildings.
Provided Options (with requirements):
Output to fi re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fi re detection and fi re alarm systems for buildings.
European Standard BS IEC60092-504 : 2001
Electrical installations in ships, special features, control and instrumentation.
European Standard BS IEC60533 : 1999
Electrical and electronic installations in ships, electromagnetic compatibility.
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
!
IMPORTANT SAFETY NOTES
ATTENTION
ABOUT THIS PANEL
PRODUCT OVERVIEW
CABINET DETAILS
CIRCUIT BOARDS
MAIN PCB TERMINALS
TECHNICAL SPECIFICATION
POWER SUPPLY MODULE
DESIGN CONSIDERATIONS
GENERAL DETECTION CIRCUIT WIRIING SCHEMATIC
GENERAL SOUNDER CIRCUIT WIRIING SCHEMATIC
INSTALLATION
SAFETY
ESD PRECAUTIONS
GENERAL
MOUNTING THE CABINET
MAINS CONNECTIONS
CONNECTING THE BATTERIES
EARTH FAULT MONITORING
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
ZONE INTERFACE FUNCTION
OPERATING
PANEL CONTROLS & INDICATIONS
DISABLE MODE
TEST MODE
FAULT DIAGNOSIS
FUNCTIONALITY DURING A SYSTEM FAULT
USER INSTRUCTIONS
SERVICE & MAINTENANCE
THE NEED FOR MAINTENANCE
DUTIES OF THE RESPONSIBLE PERSON
ROUTINE MAINTENANCE & TESTING
SCHEDULE OF TESTING LOG BOOK
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK
Esento Marine 2-4 Installation, Commissioning & Operating Manual
1
CONTENTS
10
10
11
11
11
12
13
13
8
8
9
14
14
21
Page
2
5
6
7
2
3
4
22
24
24
25
26
27
27
28
28
28
28
30
36
Approved Document UI-ESENMAR-01 Issue 4.0
ABOUT THIS PANEL
PRODUCT OVERVIEW
Quiesecent and alarm current details for standby battery calculations
Model
ESEN-2MAR
ESEN-4MAR
Standby Current
75mA
85mA
Alarm Current
116mA
133mA
Esento Marine 2-4 Installation, Commissioning & Operating Manual
2
Approved Document UI-ESEN4MAR-01 Issue 4.0
CABINET
ABOUT THIS PANEL
57mm
80mm
Fire Detection System
260mm
308mm
250mm
300mm
Esento Marine 2-4 Installation, Commissioning & Operating Manual
3
Approved Document UI-ESENMAR-01 Issue 4.0
ABOUT THIS PANEL
CIRCUIT BOARDS
Esento Marine 2-4 zone panels comprise of two circuit boards
TPCA01-E2MAR/E4MAR - 2 or 4 zone Master PCB
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR
FLT
CC
PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + -
TPCA02 - LED Display & Controls PCB
+ -
BATTERY
RESOUND SILENCE RESET
1 2 3 4
ENTER
ON
1 2 3
Esento Marine 2-4 Installation, Commissioning & Operating Manual
4
Approved Document UI-ESEN4MAR-01 Issue 4.0
MAIN PCB TERMINALS
Switched -ve inputs
Switched -ve outputs
Max load 40mA
Relay Coil
ABOUT THIS PANEL
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + -
+ -
BATTERY
Esento Marine 2-4 Installation, Commissioning & Operating Manual
5
ON
1 2 3
Approved Document UI-ESENMAR-01 Issue 4.0
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specifi cation Inputs & Outputs - TPCA01-H2/H4
Cabling Fire resistant screened cable, minimum size 1mm
2
. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1 millihenry).
Terminal capacity
PSU @ output
PSU Input + -
28v+, 0v- power output
Common fi re relay
Common fault relay
Outputs; FR, FLT
Inputs; CC, PUL
SNDR 1 - 2
0.5mm
2 to 2.5mm
2 solid or stranded wire.
Power supply voltage control line.
28vdc supply input. Diode protected for reversal and independent short circuit.
Max current 3 amps.
28vdc supply output for fi re alarm accessory relays etc. Max continuous use = 400mA.
Fire relay contact. Clean C/O.
Max 3A @ 30vdc
Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc
Switched -ve voltage outputs for relay control.
Switched -ve inputs, connect to 0v to trigger. Max input voltage = 28vdc. Non latching, max resistance 100R.
28vdc polarity reversal monitored sounder outputs to fi re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Zone 1 - 4 Fire alarm zone circuits. Conventionally wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Suitable cable glands must be used.
For temperature compensation control.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
Fused @ 500mA. Fuse = 500mA resettable fuse.
Unfused
Unfused
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Protected via 10K Ohm impedance, 3v6 zener diode.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 0.9A is not exceeded.
Monitoring current limit 50mA, fused
@ 500mA. Typical max load 22 alarm devices @ 18mA each per circuit. Ensure
0.9A is not exceeded.
General Specifi cation
Enclosure
Temperature range
Vibration
Inclination
Number of conventional detection circuits
Detector compatibility
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
-5 deg C to +55 deg C max RH 95%
IEC 60068-2-6 Test F
IEC 60092-501 22.5
o
2 or 4
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
Esento Marine 2-4 Installation, Commissioning & Operating Manual
6
Approved Document UI-ESEN4MAR-01 Issue 4.0
ABOUT THIS PANEL
POWER SUPPLY MODULE
Power Supply Specifi cation
Mains supply
Mains supply fuse
Internal power supply rating
230vac +10% / -15% 50Hz max current
1A
2 Amp (T2A 250V) Not accessible for servicing. Internal to switch mode power unit
1.5 Amps total including battery charging Maximum load shared between outputs
= 0.9A
19.92 - 30.09vdc
Tolerance +/- 0.1%
ImaxA = 575mA ImaxB = ImaxA
Power supply output voltage
Max continuous load (ImaxA). Max continuous load whilst battery charging is not required (ImaxB).
Minimum current drawn by panel
(example)
Maximum ripple
Min/max battery size and type
Battery charging voltage
Battery charging output current
4 Zone
I min = 85mA
1.0 V p-p
2 x 3.2Ahr 12volt VRLA
Use Yuasa NP range batteries
2 Zone
I min = 75mA
Supply and charger fault monitored
Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.
Temperature compensated
Battery high impedance fault (Batt Hi Z)
Max current drawn from batteries
27.3 vdc nominal at 20 deg C
1.5A PSU 630mA
Current limited 10 Ohms
Resistance = 1 Ohm or greater
1.5 Amps with main power source disconnected. Battery fuse 3A LBC
20mm.
1 hour reporting time
Esento Marine 2-4 Installation, Commissioning & Operating Manual
7
Approved Document UI-ESENMAR-01 Issue 4.0
DESIGN CONSIDERATIONS
TYPICAL DETECTION CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
APOLLO S65 BASE
45681-201
-
R L2
IN
L1
OUT
L1
+
MANUAL CALL POINT
MCP1A-R-470
470
_ _
+ +
1 2 3 4
APOLLO S65 BASE
45681-201
-
R
L2
IN
L1
OUT
L1
APOLLO S65 BASE
45681-201
-
R
L2
IN
L1
OUT
L1
ZONE 1
+ -
Esento Marine 2-4 Installation, Commissioning & Operating Manual
8
Approved Document UI-ESEN4MAR-01 Issue 4.0
TYPICAL SOUNDER CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
DESIGN CONSIDERATIONS
MOTORISED BELL
POLARISED
+VE
-VE
MOTORISED BELL
POLARISED
+VE -VE
+VE
ELECTRONIC SOUNDER
POLARISED
-VE
+VE
ELECTRONIC SOUNDER
POLARISED
-VE
SNDR1
+ -
Esento Marine 2-4 Installation, Commissioning & Operating Manual
9
Approved Document UI-ESENMAR-01 Issue 4.0
INSTALLATION
SAFETY
(i) Codes of Practice
(ii) Statutory requirements
(iii) Any instructions specifi cally advised by the manufacturer
!
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives
Esento Marine 2-4 Installation, Commissioning & Operating Manual
10
Approved Document UI-ESEN4MAR-01 Issue 4.0
INSTALLATION
ESD PRECAUTION
GENERAL
segregated away from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.
MOUNTING THE CABINET
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to reconnect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any knockouts and ensure the cabinet is clear of swarf etc prior to refi tting the PCB. Always ensure that if a knockout is removed, the hole is fi lled with a good quality cable gland. Any unused knockouts must be securely blanked off.
Knockouts should be removed with a sharp tap at the rim of the knockout using a fl at 6mm broad bladed screwdriver.
Use of excessive force will damage the enclosure around the knockout.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
11
Approved Document UI-ESENMAR-01 Issue 4.0
INSTALLATION
Typical panel layout
Incoming mains wiring
Filter
Low voltage detection and sounder circuit wiring
PSU
@ + -
28V 0V
+
-
C
FIRE
NC NO C
FAULT
NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1
+ -
SNDR2
+ -
ZONE1
+ -
ZONE2 ZONE3
+ + -
ZONE4
+ -
ON
1 2 3
+ -
BATTERY
Battery
Clamp
12V 3.2Ah VRLA BATTERY
12V 3.2Ah VRLA BATTERY
Drawing shows typical internal layout of the panel cabinet with two 3.2Ah, 12v batteries fi tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.
A rating plate is attached to the power supply module describing the nature of the supply permitted.
The incoming mains supply should be brought into the panel via one of the knockouts provided.
A suitable cable gland must be used to secure the outer sheath of the cable used. The earth must fi rst be connected to the primary earth stud (peg) marked with a symbol, using the ring crimp provided.
Suffi cient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
12
Approved Document UI-ESEN4MAR-01 Issue 4.0
INSTALLATION
CONNECTING THE BATTERIES
Batteries of even very small capacity are capable of delivering very high currents which can cause fi re or injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
+ -
BATTERY
ON
1 2 3
2 x 12v batteries should be connected in series using the white jumper lead provided. See diagram.
To optimise the service life of the batteries, the battery charger output voltage varies with temperature.
-ve
12v SLA Battery 12v SLA Battery
+ve
N.B.
In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below 19v. When the mains supply is restored the batteries will be automatically reconnected.
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute until the monitoring cylce has fi nished polling. This is normal. If the fault doesn’t clear after 1 minute, check connections.
For on ship use:- battery retaining clamps must be fi tted.
BATTERY CHARGING VOLTAGE CHECKS
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20 o
C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11 o
C - 40 o
C.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the battery voltage, should be 26.8v for a good battery or 22v for a fl at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will over ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
EARTH FAULT MONITORING
The Marine panels are equipped with earth fault monitoring to the 28v supply rails. Any cable connected to earth will cause an earth fault to be indicated. The earth fault LED is located internally next to the program options switch on the main circuit board. If an earth fault exists a PSU Fault (and General Fault) will be indicated externally. The internal LED will show continuously for earth faults on the -ve polarity cables and pulse for +ve polarity cables. (Be aware sounder cables monitor in reverse). Identifying the source of the earth fault requires systematically removing cables until the fault clears. There is a 30 second delay to the earth fault signal to avoid spurious faults due to noise.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
13
Approved Document UI-ESENMAR-01 Issue 4.0
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
A series of programmable engineering options are available. These programming modes are initiated by entering a four digit code using buttons 1 - 4 on the keypad followed by the ENTER button.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
To access Level 3 options, fi rst set switch 3 on the 3 way DIL switch located on the main PCB to the
‘ON’ position. Then activate the controls by entering the four digit code (see Activate Controls in the
OPERATING section).
1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + -
The ‘Access Level’ indicator will pulse rapidly to signify that Level 3 access is active.
1 2 3 4 5 6 7
ON
1 2 3
ON
1 2 3
ON
1 2 3
Options
1 1 1 3
Reset all disablements, test modes and parameters back to factory settings.
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings.
The panel will bleep to acknowledge the reset.
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3 4
Mute
Buzzer
Test
Lamps
RESET
ENTER
2 2 2 4
Set fault buzzer volume.
There are two levels of volume for the internal fault buzzer, high and low.
Enter the above code and press the ENTER button to increase or decrease the fault buzzer tone from the previous level.
Setting will change when ENTER button is pressed.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
14
Approved Document UI-ESEN4MAR-01 Issue 4.0
SETUP & PROGRAMMING
1 2 2 2
Muster Alarm Signal.
This option is used to select zones for activation of a muster alarm signal. A muster alarm is defi ned as 7 short blasts of the sounders, followed by 1 long blast. This is repeated until silenced. The activated muster alarm zone will show a fi re indication at the panel but no common fi re LED. The panels outputs can be programmed to respond to a muster alarm using seperate option codes.
A second setting is provided to enable the panels ‘RESOUND’ button to activate the muster alarm signal.
Note: With panel software V4.1 and above, muster alarm will have priority over any new fi re alarms by
default. It is possible to make fi re a higher priority using option 3.
Enter the above code and press the ENTER button.
The zone 1 fi re LED will be on steady. Use button 1 to toggle between steady fi re LEDs 1, for setting muster alam zones,
2, for setting RESOUND button to activate muster alarm or 3, for changing muster alarm priority.
LED 1
Select muster alarm zones
LED 2
Set
RESOUND button
LED 3
Set muster alarm priority
OFF
Set Muster Alarm Zones [LED 1]
With the zone 1 fi re LED lit press the ENTER button and the LED will pulse to indicate setting zone 1 to muster alarm. Use button 1 to move the pulsing fi re LED to the required zone and then use button 2 to change the setting, indicated by the amber fault LED ON or OFF. Any or all zones may be set for muster alarm.
ON = muster alarm zone, OFF = standard.
Set RESOUND Button Operation For Muster Alarm [LED 2]
With the zone 2 fi re LED lit press the ENTER button. Fire LED 2 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
ON = RESOUND button activates muster alarm, OFF = RESOUND button activates evacuate (default).
Set Fire As Priority Over Muster Alarm [LED 3]
With the zone 3 fi re LED lit press the ENTER button. Fire LED 3 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
OFF = muster alarm has priority, ON = fi re has priority.
When fi nished, press and hold button 1 to store settings and exit programming mode. Then enter next programming code or return DIL switch 3 to ‘OFF’ position and disable controls.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
15
Approved Document UI-ESENMAR-01 Issue 4.0
SETUP & PROGRAMMING
2 1 2 3
Panel Wide Settings
There are 4 general, panel wide, settings available.
RESOUND
Enter the above code and press the ENTER button. The 4 programmable options are represented by fi re zone LEDs 1 - 4.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Use button 1 to move to option required as per table;
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
2
3
4
Fire LED Programming Option
1 Change / remove keypad access code
Set presence of output card
Inhibit muted tone beeps
UPS Mode / Disable battery monitoring
OPTION 1.
Change / Remove Keypad Access Code
The keypad can be used to activate the panel controls instead of using the key switch. The default code is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable controls, forcing the use of the key switch only.
With the zone 1 fi re LED lit, press the ENTER button. Zone 1 fi re LED will pulse to indicate ‘edit mode’ and the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When fi nished entering the new four digit code, press the ENTER button. The panel will then confi rm the new code with rapidly pulsing LEDs in sequence and zone 1 fi re LED will return to steady ‘view mode’.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3. (The panel will confi rm the new access code one more time before exiting the programming mode).
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
16
Approved Document UI-ESEN4MAR-01 Issue 4.0
SETUP & PROGRAMMING
OPTION 2
. Set Presence of Output Card
An output/relay card may be added to each control panel to provide additional common or zonal outputs.
The presence of the card must be setup to enable operation.
With the zone 2 fi re LED lit, the amber, fault LED (zone 1) will show the current setting.
Zone 1 amber fault LED ON = Output Card present.
Press the ENTER button, zone 1 fi re LED will pulse to indicate adding or removing the card.
Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF
(removed).
When fi nished press the ENTER button again and the zone 2 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 3
. Inhibit Muted Tone Beeps
With the zone 3 fi re LED lit press the ENTER button. The zone 1 fi re LED will pulse to indicate ‘edit mode’.
Press button 1 to light the zone 1 amber fault LED. - Beeps are now silenced.
OPTION 4.
UPS Mode / Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)
The battery monitoring may be disabled for applications where this is appropriate such as non fi re alarm use or where no battery backup is required.
Note: There is no remote PSU fault input available on the
panel. This is also known as ‘UPS Mode’ where the panel is supplied from a local 24v supply rather than
mains and intenal batteries.
With the zone 4 fi re LED lit, the amber, fault LEDs will show the current setting.
FAULT LED 1
OFF
ON
ON
OFF
FAULT LED 2
ON
ON
OFF
OFF
SETTINGS
Battery & Hi Z monitoring normal (default)
Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
Battery monitoring ‘ON’, Hi Z monitoring ‘OFF’
Press the ENTER button, zone 1 fi re LED will pulse to indicate ‘edit mode’ for std battery monitoring.
Use button 1 to toggle between pulsing fi re LEDs 1 & 2 for editing std or Hi Z battery monitoring as per above.
Now use button 2 to change the setting indicated by the amber fault LED as per above.
When fi nished press the ENTER button again and the zone 4 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Note: When batteries are unmonitored the input 24v dc voltage may vary between 20v dc & 32v dc.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
17
Approved Document UI-ESENMAR-01 Issue 4.0
SETUP & PROGRAMMING
1 1 1 4
Select sounder resound options for zones.
By default, after an initial fi re condition and the (blue) Silence Alarms button has been activated, any new fi re condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault
LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to not resound alarms, the LED will be off. If kept as default, new fi re condition will resound alarms, then the LED will be on steady.
Rapid Pulse = Zone is under selection and is set to have alarms resound (default).
Slow Pulse = Zone is under selection and has been set to not resound alarms on new fi re condition.
LED Off = Zone has been set to not resound alarms on new fi re condition.
LED On = Zone is set to have alarms resound (default).
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
18
Approved Document UI-ESEN4MAR-01 Issue 4.0
SETUP & PROGRAMMING
3 1 2 1
Zone Function Settings
There are 4 functional settings available for each zone. These are as follows:
Fire latching
Normally a zone latches a fi re input signal. This setting allows the panel to clear automatically when a fi re signal is removed. This is useful for interfacing purposes.
Short circuit as alarm (EN54!)
For Older non EN54 or BS5839 compliant systems. This allows a short circuit to activate a fi re rather than a fault condition.
Intrinsically safe operation
This option changes the zone alarm and short circuit thresholds to allow for an MTL 5061 type intrinsically safe barrier to be used in the circuit.
Detector removal monitoring (EN54!)
The detector removal monitoring can be turned off. For use with older, non compliant detectors.
RESOUND SILENCE RESET
Enter the above code and press the ENTER button.
The zone 1 fi re LED will light. This indicates setting the above attributes for zone 1.
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
The amber, fault / disabled / test LEDs will show the current settings for that zone.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
Use button 1 to move to the zone that requires editing.
RESOUND
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
The fi re zone 1 LED will now pulse to indicate the editing of attribute 1 (fi re latching) for the selected zone.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
19
Approved Document UI-ESENMAR-01 Issue 4.0
SETUP & PROGRAMMING
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 4 as per table below.
Fire LED
(pulsing)
LED 1
Attribute
Fire latching
Amber fault LED
(default setting)
ON
LED 2
Short circuit as fi re
OFF OFF ON
RESOUND SILENCE RESET
1
Disable
Mode
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
ENTER
LED 3 LED 4
Intrinsically safe operation
Detector removal monitoring
The setting of the attribute is indicated by the amber, fault LED,
ON or OFF.
Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault LED.
Then use button 1 to move to the next attribute if required.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
20
Approved Document UI-ESEN4MAR-01 Issue 4.0
SETUP & PROGRAMMING
2 1 1 4
Type ‘A’ dependency mode.
Dependency ‘A’ (confi rmation alarm) is a requirement by some monitoring stations and local fi re authoities to reduce the possibility of false alarms.
Dependency ‘A’ zones will apply the following sequence:
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.
A 470Ω call point will be included in the dependency delay sequence.
By default this is set to ‘off’ for all zones.
To set zones to Type ‘A’ Dependency, enter the above code and press the ENTER button. The Aux Output
Status LED will pulse slowly. Zone Fault LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to confi rmation alarm mode, the LED will remain on. If kept as standard alarm mode then the
LED will be off.
Slow Pulse = Zone is under selection and is set to standard alarm mode.
Rapid Pulse = Zone is under selection and has been set to confi rmation alarm mode.
LED Off = Zone is set to standard alarm mode.
LED On = Zone has been set to confi rmation alarm mode.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
21
Approved Document UI-ESENMAR-01 Issue 4.0
SETUP & PROGRAMMING
4 2 4 2
Common fi re outputs cancel on silence alarms
The Common Fire VFCO relay output and the Common Fire switched -ve output, when activated, normally remain until the panel is RESET.
This option changes these outputs to reset on SILENCE ALARMS. This may be useful for panel interlink purposes.
Both outputs can be programmed independently.
RESOUND SILENCE RESET
1 2
Disable
Mode
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + + -
Enter the above code and press the ENTER button.
The red Zone 1 fi re LED will illuminate, this LED represents the Common Fire VFCO relay output.
Pressing Button 1 (Disable Mode) will move to red Zone 2 fi re LED which represents the Common Fire switched -ve output. Subsequent presses will toggle between them.
With the required fi re LED lit press the ENTER button and Zone 1, fi re LED will pulse.
Press button 2 (Test Mode) to alter the status of the output, represented by the Zone 1, Fault LED either off or on.
Off = Output cancels on RESET (factory default)
On = Output cancels on SILENCE ALARMS.
When the output status has been set, press the ENTER button to return to the output selection mode.
When fi nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10 seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
22
Approved Document UI-ESEN4MAR-01 Issue 4.0
SETUP & PROGRAMMING
4 3 4 4
Conventional Sounder Circuit Functional Options
This option is used to programme each of the conventional sounder circuits on the main circuit board with custom reponses as below.
Enter the above code and press ENTER. Then use button 1 to select the sounder circuit to be programmed (indicated by a steady fi re zone LED) as per table.
LED 1
SNDR1
(Main
LED 2
SNDR2
(Main
With the required sounder LED lit, press the ENTER button. Fire zone LED 1 will now pulse. This indicates setting up function 1 (resets on silence alarms) for the selected
PCB) PCB) circuit. Use button 1 to scroll to the required function, indicated buy pulsing fi re LEDs 1- 4 as per table below.
Fire LED
(pulsing)
LED 1 LED 2 LED 3 LED 4
Use button 2 to change the response to ON or OFF, indicated by the amber fault LEDs.
Function
Resets on
Silence
Alarms
Activates on
Evacuate
Activates on Class
Change
Activates on Alert
Then use button 1 again to scroll to the next function if required.
Amber fault LED
(default setting)
OFF ON OFF OFF
Press the ENTER button to return back to sounder circuit selection, indicated by a steady fi re LED.
ZONE INTERFACE FUNCTION
This is a special setting to confi gure the last zone on the panel, (i.e. zone 2 on the 2 zone or zone 4 on the
4 zone), to be used for interconnection from other control panels.
The function is enabled by setting switch 2 on the 3 way DIL switch located on the main PCB to the ‘ON’ position.
1 2 3 4 5 6 7
With switch 1 in the ‘ON’ position, the last zone becomes;
ON
1 2 3
Example connection
ZONE2 ZONE3 ZONE4
+ + + -
PANEL 1
Esento Marine 2-4 Installation, Commissioning & Operating Manual
23
3K3Ω
470Ω
C NC NO C NC NO
FIRE
FAULT
(optional)
PANEL 2
Approved Document UI-ESENMAR-01 Issue 4.0
OPERATING
PANEL CONTROLS & INDICATIONS
Zonal Fire Indicator LEDs
Status Indicator LEDs
Zones In Fault, Zones Disabled or
Zones In Test Indicator LEDs
1
Zones in Fire
2 3
Zone Fault / Disabled / Test
4
RESOUND SILENCE RESET
1 2 3 4
ENTER
Supply Healthy
General Fire
General Fault
General Disablement
Test Mode
Sounder Status
Aux Output Status
Power Supply Fault
System Fault
Access Level
Fire Detection System
8 Button Keypad For Controls
And Programming
Activate Controls Key Switch
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the engineering functions.
To activate the controls using the key switch; turn the key clockwise to the ‘On’ position. The ‘Access
Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE : It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad; enter the four digit code using buttons 1 - 4. The factory
default code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press the ‘ENTER’ button. The ‘Access Level’ indicator LED will light and all buttons on the keypad will now be operational.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
24
Approved Document UI-ESEN4MAR-01 Issue 4.0
OPERATING
Status LED Indicators
Zones in Fire 1 - 4
Zone Fault/Disabled/Test
1 - 4
Supply Healthy:
General Fire:
General Fault:
General Disablement:
Test Mode:
Sounder Status:
Aux Output Status:
Power Supply Fault:
System Fault:
Access Level:
Earth Fault (internal LED)
LED On
N/A
LED Pulsing
Indicates alarm condition in zone.
Indicates zone circuit is disabled or in test mode.
Indicates a fault in the zone circuit.
Indicates mains and/or battery supply is present.
N/A
N/A
Indicates panel is in alarm condition.
Indicates one or more faults are present.
N/A
Indicates one or more circuits have been disabled.
Indicates one or more circuits are in test mode
Indicates sounder circuits have been disabled or are in test mode
Indicates auxiliary outputs have been disabled.
N/A
Indicates a system failure, panel not functional.
Indicates controls are active (access level
2).
Indicates disablement selection mode is active.
Indicates test mode selection is active.
Indicates a fault on one or more sounder circuits.
N/A
Indicates a power supply, battery or earth fault.
Indicates the panel has recovered from a system fault.
Indicates panel is in confi guration mode (access level 3).
-ve earth fault +ve earth fault
RESOUND SILENCE RESET
Keypad
1
Disable
Mode
2
Test
Mode
3
Mute
Buzzer
4
Test
Lamps
ENTER
RESOUND (red):
SILENCE (blue):
RESET (green):
1: (Disable Mode)
2: (Test Mode)
3: (Mute Buzzer)
4: (Test Lamps &
Buzzer)
ENTER:
Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.
Use to silence the sounders during an alarm condition.
Resets the panel back to standby mode.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the numeric value 1 for code entry.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric value 2 for code entry.
Mutes the panels internal fi re and fault buzzer. (The buzzer will still blip every 5-6 seconds during a fi re or fault condition). This function is operational without the need to activate controls. Also has the numeric value 3 for code entry.
Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working correctly. This function is operational without the need to activate controls. Also has the numeric value
4 for code entry.
This button is used to confi rm code entries. It can also be used for fault diagnosis (see FAULT
DIAGNOSIS section).
Some buttons have other functions within the engineering facilities. These functions are described in the relevant sections.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
25
Approved Document UI-ESENMAR-01 Issue 4.0
OPERATING
DISABLE MODE
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits or all auxiliary outputs.
To initialise Disable Mode, fi rstly activate the controls by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Zone 1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in disable selection mode.
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by the Sounder
Status LED and then to the Aux outputs, indicated by the Aux Output Status LED. Pressing the button once more will move the selection back to Zone 1 again.
When the desired circuit or output to be disabled is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the circuit between disabled and enabled. Then use Disable Mode button again to move to the next circuit. Any or all circuits can be disabled simultaneously.
1
RESOUND
2
SILENCE
3 4
RESET
ENTER
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When all disablements have been set, press and hold the Disable Mode button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby.
All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefl y will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
26
Approved Document UI-ESEN4MAR-01 Issue 4.0
OPERATING
TEST MODE
Test Mode is used when testing the fi re alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person. It is possible to test head removal monitoring and to test the system with or without the sounders.
To initialise Test Mode, fi rstly activate the controls by entering the four digit code. Then press and hold the Test Mode button (2) for 3 seconds.
After 3 seconds the panel will bleep and the Test Mode LED and Zone
1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in test selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be
with sounders. (Test mode
without sounders is explained below)
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 and 4.
After Zone 4 the next press will move the selection mode to the sounder circuits, indicated by no Zone
Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test.
Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the zone between in and out of test. Then use Test Mode button again to move to the next zone. Any or all zones can be in test mode simultaneously.
RESOUND
1
Disable
Mode
When at the sounder status position, use the ENTER button to toggle between testing with or without sounders. A rapid pulse = with sounders
(default), a slow pulse = without sounders.
SILENCE
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
RESET
ENTER
When all zones to be tested have been set, press and hold the Test Mode button for 3 seconds again. This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and the ENTER button to change the status.
Test Mode With Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset.
Removal of a detector - sounders will pulse once.
Test Mode Without Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefl y will reveal which circuits are in test mode
(as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
27
Approved Document UI-ESENMAR-01 Issue 4.0
OPERATING
FAULT DIAGNOSIS
If the panel has detected a fault on the system the General Fault LED will be illuminated and the internal fault buzzer will sound. Secondary LEDs will also be illuminated depending on the location of the fault.
Pressing and holding the ENTER button will reveal more detailed information about the loction and type of fault.
RESOUND
This function will not work if the panel is in a fi re condition. If no faults exist pressing the ENTER button will have no effect.
This function is only operational when controls are not active.
1
Disable
Mode
2
Test
Mode
The following table shows details of the indications in fault diagnosis mode:
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
LED Indicator
& State before pressing ENTER
LED Pulsing after pressing ENTER
Zone 1 Fire LED
(off)
Zone 2 Fire LED
(off)
Zone 1 - 4 Fault/
Disabled/Test LED
(pulsing)
Zone 1 - 4 Fault/
Disabled/Test LED
(steady)
Power Supply
Fault LED (pulsing)
Sounder circuit 1 short circuit
Sounder circuit 2 short circuit
Zone # short circuit
N/A
Mains failure
LED Steady after pressing ENTER
Sounder circuit 1 open circuit
Sounder circuit 2 open circuit
Zone # open circuit
N/A
Battery failure or high impedance
LED Off after pressing ENTER
OK
OK
Voltage fault
Location
Main PCB SNDR 1
Main PCB SNDR 2
(slow pulse)
Zone # detector removed
Zone # disabled or in test mode
Main PCB Zones
1 - 4
Main PCB
Esento Marine 2-4 Installation, Commissioning & Operating Manual
28
Approved Document UI-ESEN4MAR-01 Issue 4.0
OPERATING
FUNCTIONALITY DURING A SYSTEM FAULT
A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. In the event of a system fault the particular board affected may not be functional. The following indications may be observed.
Display Board
System Fault LED only continous and continous buzzer sound. Display board TPCA02 is halted and no other indication or control is possible. Fault relay and fault output are activated. If a fi re occurs alarm sounders and outputs will still function.
Main Board
System Fault LED continous and General Fault LED pulsing and continous buzzer sound. Main board is halted. Fault relay is activated. No alarms may be activated on the system.
System Fault recovery
System Fault LED pulsing and General Fault LED pulsing along with a pulsed buzzer (fault tone) a system fault has occurred and the affected board has recovered. The indication will remain until the panel is reset.
USER INSTRUCTIONS
If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.
A responsible person should then:-
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 1
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 2
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 3
ENTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
29
Approved Document UI-ESENMAR-01 Issue 4.0
SERVICE & MAINTENANCE
The following section is a summary of the requirements in BS5839 Part 1
For comprehensive information a copy of BS5839 Part 1 can be purchased from the British Standards
Institution via their web site at www.bsi-global.com.
THE NEED FOR MAINTENANCE
Your Fire Alarm System is working 24 hours a day, 365 days a year. The detectors and control & indicating panel are operating continuously and the fi re alarm circuits are constantly monitored.
Legislation such as the Regulatory Reform (Fire Safety) Order 2005 and other legislation protecting both employees and the public require premises operators to conform with standards for Fire Alarm Systems.
It is a requirement of BS 5839 Part 1 that the system is subject to periodic inspection and servicing so that faults are identifi ed, preventive measures can be taken to ensure the continued reliability of the system, false alarm problems are identifi ed and suitably addressed, and the user is made aware of any changes to the building that affect the protection afforded by the system.
The inspection and servicing recommendations in this clause should be carried out by a competent person. A ‘Competent Person’ is a person or fi re alarm servicing organisation with specialist knowledge of fi re detection and fi re alarm systems, including knowledge of the causes of false alarms, suffi cient information regarding the system, and adequate access to spares.
The period between successive inspection and servicing visits should be based upon a risk assessment, taking into account the type of system installed, the environment in which it operates and other factors that may affect the long term operation of the system. The recommended period between successive inspection and servicing visits should not exceed six months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this part of BS 5839
DUTIES OF THE RESPONSIBLE PERSON
The system user needs to appoint a single, named member of the premises management to supervise all matters pertaining to the fi re detection and fi re alarm system. The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1, that appropriate records are kept and that relevant occupants in the protected premises are aware of their roles and responsibilities in connection with the fi re detection and fi re alarm system.
This person also needs to ensure that necessary steps are taken to avoid situations that are detrimental to the standard of protection afforded by the system and to ensure that the level of false alarms is minimized.
ROUTINE MAINTENANCE & TESTING
DAILY
The ‘Responsible Person’ should check the control panel to make sure no faults or pre-alarm conditions are indicated and that the green ‘Supply Healthy’ lamp is lit.
WEEKLY
The Fire Alarm System should be tested on a weekly basis as recommended in BS5839 Part 1 clause 44.2.
Every week a manual call point should be operated during normal working hours. The weekly test should be carried out at approximately the same time each week. Instructions to the occupants should be that they report any instance of poor audibility of the fi re alarm signal.
A different manual call point should be used at the time of every weekly test so that all manual call points in the building are tested in rotation over a prolonged period.
The result of the weekly test and the identity or location of the manual call point used should be recorded in the system log book.
Esento Marine 2-4 Installation, Commissioning & Operating Manual
30
Approved Document UI-ESEN4MAR-01 Issue 4.0
SERVICE & MAINTENANCE
WEEKLY TEST
The call point test key should be inserted fi rmly and deliberately into the bottom of the manual call point.
Once activated it may be necessary to wait up to four seconds before the alarms sound.
Your manual call points may not be the same as the ones described above. If not please refer to your service and maintenance company for instructions.
Note:
Before testing the fi re alarm system it may be necessary to isolate ancillary outputs.
It is essential that any alarm receiving centre is contacted immediately before and immediately after, the weekly test to ensure that unwanted alarms are avoided and that fi re alarm signals are correctly received at the alarm receiving centre.
PERIODIC INSPECTION & SERVICING
Inspection & servicing should only be carried out by a ‘Competent Person’ who has suffi cient knowledge to check the whole system. This would normally be a qualifi ed electrical contractor or fi re alarm specialist.
Inspection & servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis. The maximum period between inspections must not exceed six months.
Recommendations of BS5839-1 for periodic service visits include:
• Every device on the system should be tested annually. The testing of each device can be split between periodic visits but with a minimum of one detector or call point tested on each circuit, per visit.
• On each visit the ‘Competent Person’ should check the record of false alarms. Any persistent occurrence should be investigated and corrective action taken as appropriate.
• Battery and connections should be examined and load tested to check serviceable condition and that they are not likely to fail before the next service visit.
• All other devices and control & indicating equipment should be checked for correct operation and any faults should be recorded and rectifi ed.
• Details of the service visit must be recorded in the log book
EVERY FOUR YEARS
Renew the sealed lead acid batteries and record the fact in the log book
Esento Marine 2-4 Installation, Commissioning & Operating Manual
31
Approved Document UI-ESENMAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
32
Approved Document UI-ESEN4MAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
33
Approved Document UI-ESEN4MAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
34
Approved Document UI-ESEN4MAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
35
Approved Document UI-ESEN4MAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
36
Approved Document UI-ESEN4MAR-01 Issue 4.0
D DATE &
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
Esento Marine 2-4 Installation, Commissioning & Operating Manual
37
Approved Document UI-ESEN4MAR-01 Issue 4.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Esento Marine 2-4 Installation, Commissioning & Operating Manual
38
Approved Document UI-ESEN4MAR-01 Issue 4.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Esento Marine 2-4 Installation, Commissioning & Operating Manual
39
Approved Document UI-ESEN4MAR-01 Issue 4.0
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Esento Marine 2-4 Installation, Commissioning & Operating Manual
40
Approved Document UI-ESEN4MAR-01 Issue 4.0
USER INSTRUCTIONS
If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.
A responsible person should then:-
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 1
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
fi g 2
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
fi g 3
3 4
Mute
Buzzer
Test
Lamps
ENTER
The internal fault buzzer can be silenced by pressing MUTE BUZZER (button 3 on the keypad). DO
NOT RESET THE SYSTEM UNTIL AN ENGINEER HAS INVESTIGATED THE FAULT.
www.haes-systems.com
advertisement
Key Features
- European standards EN54-2 & 4 compliant
- Integral power supply
- Space for standby batteries
- Two or four fire zone circuits
- Two monitored sounder circuits
- Fire & fault VFCO relays
- Fire & fault switched negative outputs
- Class change and an alert input