P-SERIES
P-SERIES
SUBMITTAL DATA: PLA-A36BA4 & PUZ-HA36NHA4
36,000 BTU/H CEILING-CASSETTE HYPER HEAT-PUMP SYSTEM
Job Name:
System Reference:
Date:
Indoor Unit: PLA-A36BA4
Outdoor Unit: PUZ-HA36NHA4
GENERAL FEATURES
•
•
•
•
•
•
•
High heating capacity at low outside temperatures
Exhibits 100% of rated heating capacity at 5º F; 90% of rated heating capacity at -4º F
Built-in drain lift mechanism for condensate removal; lifts up to 33-7/16 inches
Wide air flow pattern for better air distribution; independently adjustable vanes
Auto wave airflow in heating mode—unit independently cycles through horizontal and vertical positions for a more even heat distribution
Self-check function—integrated diagnostics
Limited warranty: five years parts and seven years compressors
ACCESSORIES
Indoor Unit
□□ Multi-function Casement (PAC-SH53TM-E)
□□ Air Outlet Shutter Plates (PAC-SH51SP-E)
□ High-efficiency [MERV 10] Filter (PAC-SH59KF; req. PAC-SH53TM)
Outdoor Unit
□□ M-NET Adapter (PAC-SF80MA-E)
□□ Wind Baffle (One Piece)* (WB-PA2)
□□ Air Outlet Guide (One Piece)* (PAC-SG59SG)
*PUY(Z) requires two outlet guides or wind baffles for installation.
Controller Options
□□ Wireless Wall-mounted Remote Controller Kit (MHK1)**
□□ Portable Central Controller (MCCH1)**
□□ Outdoor Air Sensor (MOS1)**
□□ Wired Wall-mounted Controller (PAR-31MAA)**
□□ Simple MA Remote Controller (PAC-YT53CRAU)**
**See Submittal for information on each option.
□□ M-NET Adapter (PAC-SF81MA)
□□ i-see Sensor Corner Panel (PAC-SA1ME-E)
□□ Hand-held Wireless Remote Controller (PAR-FL32MA; req. PAR-FA32MA-E)
□□ Wireless Signal Receiver Module (PAR-FA32MA-E)
SEACOAST PROTECTION
• External Outer Panel: Phosphate coating + Acrylic-Enamel coating
• Fan Motor Support: Epoxy resin coating (at edge face)
• Separator Assembly ; Valve Bed: Epoxy resin coating (at edge face)
• Screws (used outer side): Zinc nickel coating 5μm + Polyvinylidene chloride coating
“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants..
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
SPECIFICATIONS: PLA-A36BA4 & PUZ-HA36NHA4
Cooling
Rated Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,000 Btu/h
SEER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17.0 Btu/h/W
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,690 W
Heating at 47°F
Rated Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,000 Btu/h
HSPF (IV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10.0 Btu/h/W
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,230 W
Heating at 17°F
Rated Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28,000 Btu/h
Rated Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,590 W
Maximum Capacity** . . . . . . . . . . . . . . . . . . . . . . . . . . 38,000 Btu/h
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,300 W
Heating at 5°F
Maximum Capacity** . . . . . . . . . . . . . . . . . . . . . . . . . . 38,000 Btu/h
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,860 W
* Rating Conditions per AHRI Standard
Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB
Cooling | Outdoor: 95º F (35º C) DB / 75º F (24º C) WB
Heating at 47º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 47º F | Outdoor: 47º F (8º C) DB / 43º F (6º C) WB
Heating at 17º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 17º F | Outdoor: 17º F (-8º C) DB / 15º F (-9º C) WB
Heating at 5º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 5º F | Outdoor: 5º F (-15º C) DB / 5º F (-15º C) WB
** Maximum Capacity is at full speed and performance for
INVERTER-driven System.
ELECTRICAL REQUIREMENTS
Power Supply . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
Breaker Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 A
Voltage
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . DC ±24V
Indoor - Remote Controller . . . . . . . . . . . . . . . . . . . . . MKH1 DC 3V
PAR-21MAAU DC 12V
PAR-FL32MA DC 3V
OPERATING RANGE
Indoor Intake Air Temp. Outdoor Intake Air Temp.
90º F (32º C) DB
Maximum
115º F (46º C) DB
73º F (23º C) WB
Cooling
66º F (19º C) DB
Minimum
0º F** (-18º C) DB
59º F (15º C) WB
70º F (21º C) DB
Maximum 83º F (28º C) DB
59º F (15º C) WB
Heating
-13º F (-25º C) DB
Minimum 63º F (17º C) DB
-13º F (-25º C) WB
Note: With optional wind baffle accessory installed. If not installed,
the minimum temperature will be 23º F (-5º C) DB.
Notes:
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
INDOOR UNIT
Fan Motor (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.00 F.L.A.
Fan Motor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 W
Airflow (Lo - M1 - M2 - Hi) . . . . . . 710 - 810 - 920 - 1,060 Dry CFM
670 - 770 - 880 - 1,030 Wet CFM
Sound Pressure Level (Lo - M1 - M2 - Hi) . . . 32 - 34 - 37 - 40 dB(A
DIMENSIONS
W
D
H
UNIT INCHES / MM
33-1/16 / 840
33-1/16 / 840
11-3/4 / 295
PANEL INCHES / MM
37-3/8 / 950
37-3/8 / 950
1-3/8 / 35
Weight (Unit/Grille)
lbs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 / 13
kg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 / 6
External Finish . . . . . . . . . . . . . . . . . . . . . . Munsell No. 6.4 8.9 / 0.4
Field Drainpipe Size O.D. . . . . . . . . . . . . . . . . . . . . . 1-1/4” / 32 mm
OUTDOOR UNIT
Compressor . . . . . . . . . . . . . . . . . . . . . . . . DC Inverter-driven Scroll
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 A
Fan Motor (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.4 + 0.4 F.L.A.
Sound Pressure Level
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 dB(A)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 dB(A)
DIMENSIONS
W
D
H
INCHES / MM
37-3/8 / 950
13 + 1-3/16 / 330 + 30
53-1/8 / 1,350
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 lbs. / 120 kg
External Finish . . . . . . . . . . . . . . . . . . . . . . Munsell No. 3Y 7.8 / 1.1
Refrigerant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5/8” / 15.88 mm
Liquid Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8” / 9.52 mm
Max. Refrigerant Pipe Length . . . . . . . . . . . . . . . . . . . . . 245’ / 75 m
Max. Refrigerant Pipe Height Difference . . . . . . . . . . . . 100’ / 30 m
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
DIMENSIONS: PLA-A36BA4
25/32 to
1-25/32
(20~45)
23-1/2 (597)
Air intake hole
Air outlet hole
(83)
3-17/64
(36)
1-27/64
19-11/16 (500)
Air outlet hole
37-3/8 (950)
Vane motor
1-27/64
3-17/64
(83)
Indoor unit
Ceiling
Grille
Min.94-1/2(2400)
from floor
Min.19-11/16(500)
Entire
periphery
Floor
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
6-9/16(167)
70
)
( 150)
Burring hole
3- 1/8(3- 2.8)
Burring hole pitch
4-29/32( 125)
120°
Cut out hole
6-7/32
120°
Keep 25/64(10) to 19/32(15)
between unit ceiling
and ceiling slab.
3-15/16( 100)
Ceiling
In case of standard grille
In case of IR wireless remote controller
Emergency operation switch<Cooling>
Emergency operation switch<Heating>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Models
M
Corner pocket
2.8)
Auto vane
(Air outlet)
Air intake grille
M
Burring hole
Detail drawing of fresh air intake hole
23-1/2 (597)
Air intake hole
19-11/16 (500)
M
14- 1/8 (14-
(350)
( 158)
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
37-3/8 (950)
11/16
Ceiling
Grille
+3/16
0
(17+5
0 )
(190)
7-15/32
(50~70)
Suspension bolt
lower edge
1-15/16~2-3/4
5-1/2
(140)
(170)
6-11/16
2
13-25/32
Cut out hole
(
B
14-27/32
A
11-3/16
6-9/64 (156)
(377)
(284)
2-3/8
( 175) 6-7/8
Burring hole pitch
Connected the attached
Drain pipe
connected to VP-25 flexible pipe or socket.
4-1/8 (105)
(60)
1
(160)
33-1/16 (840)
Cut out hole
Branch duct hole
25/32
to 1-25/32
(20~45)
(7.5)
C
D
6-5/16
7-3/8
(187.5)
Suspension bolt
M10 or W3/8
3-17/32 (90)
5-29/32
(5/16)
3-17/32 (90)
5-29/32(150)
For wiring replacement kit
terminal block
24-13/32 (620)
15/16 (24)
6-5/16 (160)
Suspension bolt pitch
+1-3/8
+35
23-13/16 -3/16 (605 -5 )
Indoor unit/Outdoor unit
connecting terminal block
Branch duct hole
3-15/16 (100)
3-15/16 (100)
3-17/32 (90)
Ceiling hole
(7.5)
(160)
6-5/16
33-1/16(840)
For MA-Remote controller
terminal block
Detail connecting of Branch duct(Both aspects)
33-27/32 to 35-13/16 (860~910)
(5/16)
(160)
3-15/16 (100)
5-1/8 (130)
31-7/8(810)
Suspension bolt pitch
(35)
6-5/16
1-3/8
Fresh air
intake hole
Unit : inch(mm)
25/32 to 1-25/32(20~45)
6-3/32 (155)
Ceiling hole
33-27/32 to 35-13/16(860~910)
25/32 to 1-25/32(20~45)
(36)
1
2
A
B
C
D
Refrigerant pipe
PLA-A12BA4 ···· 6.35
PLA-A18BA4 Flared connection
····1/4 inch
Refrigerant pipe
···· 12.7
Flared connection
9-1/2 10-3/16 3-5/32 2-29/32
····1/2 inch
PLA-A24BA4
PLA-A30BA4 Refrigerant pipe
···· 9.52
Flared connection
PLA-A36BA4 ····3/8 inch
PLA-A42BA4
Refrigerant pipe
···· 15.88
Flared connection
····5/8 inch
11-1/16 11-3/4 3-11/32 3-1/32
(241) (258) (80) (74)
(281) (298) (85)
(77)
Note1. As for drain pipe, please use VP-25(O.D. 1-1/4( 32) PVC TUBE).
Drain pump is included.
Max. liftng height is 70-7/18(850mm) from the ceiling.
2. As for suspension bolt, please use M10 or W3/8.(Procured at local site)
3. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/power wires connection.
4. The height of the indoor unit is able to be adjusted with the grille attached.
5. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Add 5-5/16(135mm) to the dimensions marked on the figure.
2) The optional high efficiency filter must be used jointly with the multi-functional casement.
6. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
7. As for necessary installation/service space, please refer to the left figure.
Min. 150mm
<5-29/32>
Min. 10mm
<3/8>
Service space
Min.
10mm<3/8>
92
/8>
<3-5
92<3-5/8>
65<2-9/16>
Front piping hole
(Knockout)
Front trunking hole 40<1-9/16>
(Knockout)
45<1-25/32>
Min.
500mm
<19-11/16>
19<3/4>
92
<3-5/8
>
40<1-9/16>
92<3-5/8>
45<1-25/32>
2- 22.2<7/8>
Rear piping hole
(Knockout)
74<2-19/32>
40<1-9/16>
Rear trunking hole
(Knockout)
(2- 27<1-1/16>Knockout)
<3-5 92
/8>
92<3-5/8>
65<2-9/16>
Right trunking hole
(Knockout)
Handle
1/2 Conduit attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
Handle
Handle
Side Air Intake
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
Rear Air Intake
40<1-9/16> Conduit hole
FOUNDATION
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
Conduit hole
(2- 27<1-1/16>Knockout)
55<2-3/16>
75
<2-31/32>
Right piping hole
(Knockout)
Air intake
73<2-7/8>
23<29/32>
73<2-7/8>
Conduit hole
(2- 27<1-1/16>Knockout)
Piping Knockout Hole Details
55<2-3/16>
63
<2-1/2>
27<1-1/16>
Handle
····Refrigerant GAS pipe connction (FLARE) 15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE) 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
Example of Notes
Min. 1000mm
<39-3/8>
Min. 10mm
<3/8>
73<2-7/8>
63<2-1/2>
23<29/32>
FREE
27<1-1/16>
92<3-5/8>
63<2-1/2>
23<29/32>
Min.
30mm
<1-3/16>
Min.
150mm
<5-29/32>
Min.
500mm
<19-11/16>
3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS
31<1-7/32>
330<13>
30<1-3/16>
23<29/32>
30<1-3/16>
220
<8-21/32>
66<2-5/8>
42<1-21/32>
Earth terminal
950<37-13/32>
Drain hole
5- 33<1-5/16>
71<2-13/16>
2
1
Handle
Service panel
Terminal Block
Left···Power supply wiring
Right····Indoor/Outdoor wiring
2-12 36 Oval hole
(Foundation Bolt M10<W3/8>)
145
145
145
<5-23/32> <5-23/32> <5-23/32>
322<12-11/16>
Air Discharge
175<6-7/8>
175<6-7/8>
600<23-5/8>
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
Rear Air Intake
45<1-25/32>
Dimensions of space needed
for service access are
shown in the below diagram.
55<2-3/16>
27<1-1/16>
1350<53-5/32>
417<16-13/32>
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
71<2-13/16>
635<25>
371<14-19/32>
219<8-5/8>
81<3-3/16>
56<2-7/32>
19<3/4>
370<14-9/16>
28<1-3/32>
53<2-3/32>
© 2014 Mitsubishi Electric US, Inc.
Bottom piping hole
(Knockout)
Rear piping cover
Front piping cover
* 1 447<17-19/32>
Specifications are subject to change without notice.
* 1 443<17-7/16>
FORM# PLA-A36BA4 / PUZ-HA36NHA4 - 201406
1076<42-3/8>
1 FREE SPACE (Around the unit) 2 SERVICE SPACE
DIMENSIONS: PUZ-HA36NHA4
Unit : mm<inch>
1340 Satellite Boulevard
Suwanee, GA 30024
Toll Free: 800-433-4822