FKRS-EU 1.1 – X X FKRS-EUtestregistrierung Fire dampers 1 Type FKRS-EU FKRS-EU with fusible link for 72 °C or 95 °C Compact dimensions, ideal for restricted spaces CE compliant according to European regulations Small circular fire damper for the isolation of duct penetrations# between fire compartments, available in ten nominal sizes ■ Nominal sizes: 100 – 315 mm ■ Low differential pressure and sound power level ■ Optional stainless steel casing or powder-coated casing for increased corrosion protection ■ Air transfer damper as an option ■ Integration into the central BMS with TROXNETCOM ■ Universal installation options Optional equipment and accessories ■ Electric actuator 24 V/230 V With TROXNETCOM as an option H GE TE ET HY G I ISC ■ Duct smoke detector RM-O-3-D ST EN ■ Release temperature 72/95 °C VD I 6022 Tested to VDI 6022 06/2015 – DE/en K4 – 1.1 – 111 Fire dampers General information FKRS-EU Type 1 FKRS-EU Variants FKRS-EU with fusible link Page General information Correct use Order code Installation block ER Installation kit TQ Installation kit GL Wall face frame Cover grille Flexible connector Extension piece Limit switch Spring return actuator TROXNETCOM Duct smoke detectors Quick sizing Free area and resistance coefficient Dimensions and weight – FKRS-EU Dimensions and weight – FKRS-EU/.../Z4* Specification text 1.1 – 112 1.1 – 118 1.1 – 120 1.1 – 121 1.1 – 122 1.1 – 123 1.1 – 124 1.1 – 125 1.1 – 126 1.1 – 128 1.1 – 129 1.1 – 130 1.1 – 131 1.1 – 132 1.1 – 133 1.1 – 134 1.1 – 135 1.1 – 136 1.1 – 137 Basic information and nomenclature 1.3 – 1 FKRS-EU with spring return actuator Product examples K4 – 1.1 – 112 06/2015 – DE/en Fire dampers General information Description FKRS-EU with spring return actuator For detailed information on attachments see Chapter K4 – 1.2. Application – Fire dampers of Type FKRS-EU, with CE marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire – To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments Classification – Class of performance to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S Variants – With fusible link – With spring return actuator – With cover grilles both ends as air transfer damper with general building inspectorate licence: Z-19.18-2128 Nominal sizes – 100, 125, 150, 160, 180, 200, 224, 250, 280, 315 – L: 400 mm Attachments – Limit switch for damper blade position indication – Spring return actuator for 24 V AC/DC or 230 V AC supply voltage – Network module for the integration with AS-i or LON networks Accessories – Circular installation block ER – Square installation kit TQ – Wall face frame WA – Installation kit GL – Cover grille – Flexible connectors – Extension piece Useful additions – Duct smoke detector RM-O-3-D – Duct smoke detector with airflow monitor RM-O-VS-D 06/2015 – DE/en Special characteristics – Declaration of performance according to Construction Products Regulation – Classification to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S – Building inspectorate licence Z-56.4212-991 for fire resistance properties – Complies with the requirements of EN 15650 – Tested to EN 1366-2 for fire resistance properties – Hygiene complies with VDI 6022 part 1 (07/2011), VDI 3803 (10/2002), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007) – Corrosion protection according to EN 15650 in connection with EN 60068-2-52 – Closed blade air leakage to EN 1751, class 3 – Casing air leakage to EN 1751, class C – Low differential pressure and sound power level – Any airflow direction – Integration into the central BMS with TROXNETCOM FKRS-EU Parts and characteristics – Dry mortarless installation into solid walls and ceiling slabs, lightweight partition walls, fire walls, and shaft walls using an installation block – Installation with wall face frame on the face of solid walls – Release temperature 72 °C or 95 °C (for use in warm air ventilation systems) – Approved installation orientation from 0° to 360° Construction features – Rigid circular casing suitable for push fitting into cut circular holes without additional drilling and chiselling being required – Spigot connections with lip seal on both ends, suitable for ventilation ducts according to EN 1506 and EN 13180 plus non-standard but commercial nominal sizes 180, 224 and 280 – Suitable for the connection of flexible connectors or cover grilles – The release mechanism is accessible and can be tested from the outside – One inspection access panel – Remote control with spring return actuator Materials and surfaces Casing: – Galvanised sheet steel – Galvanised sheet steel, powder-coated RAL 7001 – Stainless steel 1.4301 Damper blade: – Special insulation material – Special insulation material with coating Other components: – Damper blade shaft made of galvanised steel or stainless steel – Plastic bearings – Seals of elastomer The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request. K4 – 1.1 – 113 1 Fire dampers General information FKRS-EU Installation and commissioning Install the fire damper according to the operating and installation manual. 1 Mortar-based installation: – In solid walls and ceiling slabs – In non-load-bearing solid walls with flexible ceiling joint – In lightweight partition walls and fire walls with metal support structure and cladding on both sides – In shaft walls with metal support structure and cladding on one side Dry mortarless installation: – In solid walls and ceiling slabs with installation block ER – In solid walls and ceiling slabs using a fire batt – In lightweight partition walls with metal support structure and cladding on both sides using a fire batt – On the face of solid walls with wall face frame WA – In lightweight partition walls with metal support structure, cladding on both sides and flexible ceiling joint: with installation kit GL – In lightweight partition walls with metal support structure and cladding on both sides with installation kit TQ – In fire walls with metal support structure and cladding on both sides with installation kit TQ – In shaft walls with or without metal support structure and cladding on one side with installation kit ES Technical data Nominal sizes Casing length Volume flow rate range Differential pressure range Operating temperature Release temperature Upstream velocity* Standards and guidelines – Construction Products Regulation – EN 15650:2010 – Ventilation for buildings – Fire dampers – EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers – EN 13501-3:2010 Fire classification of construction products and building elements – EN 1751:1999 Ventilation for buildings – Air terminal devices Maintenance – The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later. – A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control – Fire dampers must be included in the regular cleaning schedule of the ventilation system. – For details on maintenance and inspection, refer to the installation and operating manual 100 – 315 mm 400 mm Up to 770 l/s or up to 2770 m³/h Up to 1500 Pa At least 0 – 50 °C ** 72 °C or 95 °C (for warm air ventilation systems) ≤ 8 m/s with standard construction; ≤ 10 m/s with spring return actuator * Data applies to uniform upstream and downstream conditions for the fire damper ** Temperatures may differ for units with attachments K4 – 1.1 – 114 06/2015 – DE/en Fire dampers General information FKRS-EU Functional description In the event of a fire, fire dampers shut automatically to prevent the propagation Construction with fusible link of fire and smoke through ductwork to adjacent designated fire compartments. In the event of a fire, the damper is triggered at 72 °C or at 95 °C (use in warm air ventilation systems) by a fusible link. The release mechanism is accessible and can be tested from the outside. Function 1 Schematic illustration of FKRS-EU with fusible link ݥ ݤ ݦ ݣ ݢ ݧ ݨ ① Casing ② Fusible link ③ Damper blade with seal ④ Inspection access (12 mm) 06/2015 – DE/en ⑤ Lip seal ⑥ Handle with interlock and damper blade position indicator ⑦ Release mechanism K4 – 1.1 – 115 Fire dampers General information 1 Function Construction with spring return actuator FKRS-EU Functional description The spring return actuator enables the motorised opening and closing of the damper blade; it can be activated by the central BMS. In the event of a fire, the damper is triggered thermoelectrically at 72 °C or 95 °C (use in warm air ventilation systems). As long as power is supplied to the actuator, the damper blade remains open. If the supply voltage fails, the damper closes (power off to close). Motorised fire dampers can be used to shut off ducts. The torque of each actuator is sufficient to open and close the damper blade even while the fan is running. The spring return actuator is fitted with limit switches that can be used for capturing the damper blade position. Schematic illustration of FKRS-EU with spring return actuator ݥ ݤ ݦ ݣ ݢ ݧ ݨ ① Casing ② Temperature sensor ③ Damper blade with seal ④ Inspection access (12 mm) K4 – 1.1 – 116 ⑤ Lip seal ⑥ Spring return actuator ⑦ Thermoelectric release mechanism 06/2015 – DE/en Fire dampers General information Function Use as an air transfer damper FKRS-EU Functional description Air transfer dampers prevent fire and smoke from spreading in buildings. The thermal release mechanism closes the damper blade when the release temperature (72 °C) is reached. Smoke can, however, spread below this temperature. Air transfer dampers are installed (mortar-based installation) in places where the general building inspectorate sees no risk, for example: Special characteristics – General building inspectorate licence Z-19.18-2128 – Air transfer damper without duct smoke detector 1 – As an inlet for additional supply air in the walls of required corridors (escape routes) if the dampers are installed near the ground (up to 500 mm above OKFF) – In installation shafts as long as they have sufficient fire resistance where they penetrate compartment floors – In installation ducts as long as they have sufficient fire resistance where they penetrate compartment floors or walls (except for necessary corridors or escape routes) The air transfer damper is an FKRS-EU fire damper with 72 °C thermal release mechanism (construction with fusible link) and cover grilles both ends. Schematic illustration of the FKRS-EU as air transfer damper, with fusible link and cover grille ݥ ݤ ݦ ݣ ݢ ݦ ݧ ݨ ① Casing ② Fusible link ③ Damper blade with seal ④ Inspection access (12 mm) 06/2015 – DE/en ⑤ Cover grille ⑥ Handle with interlock and damper blade position indicator ⑦ Release mechanism K4 – 1.1 – 117 Fire dampers Correct use FKRS-EU Design information – Approved only for use in ventilation and air conditioning sytems – A class of performance up to EI 120 (ve, ho, i ↔ o) S can only be achieved with ducts connected on both ends, or with a duct on one end and a cover grille on the other end. – If the fire damper is installed in a solid wall, solid ceiling slab, lightweight partition wall or shaft wall with a lower fire resistance class than that of the fire damper, the fire resistance class of the wall or ceiling slab applies also to the FKRS-EU (details upon request) – Ducting must be installed in such a manner that it does not impose any significant loads on the fire damper in the event of a fire. 1 – For particular applications it is recommended that flexible connectors are used to connect rigid ducting to the unit. – Fire dampers must be installed, connected and secured according to the operating and installation manual. Incorrect use Never use the fire damper: – without specially approved attachments in areas with potentially explosive atmospheres – as a smoke control damper – outdoors without sufficient protection against the effects of weather – in atmospheres where chemical reactions, whether planned or unplanned, may cause damage to the fire damper or lead to corrosion Correct use in solid walls and ceiling slabs Installation location Construction and building material Minimum Performance class Mortar-based thickness installation mm EI TT (ve–ho, i ↔ o) S Dry mortarless installation Solid walls Solid walls, gross density ≥ 500 kg/m³ 100 EI 120 S N W¹ Solid walls, gross density ≥ 500 kg/m³ 100 EI 90 S N E/W Solid walls, gross density ≥ 500 kg/m³ 100 EI 90 S – E Solid ceiling slabs, gross density ≥ 600 kg/m³ 150 EI 120 S N – Solid ceiling slabs, gross density ≥ 600 kg/m³ 150 EI 90 S – E/W Solid ceiling slabs, gross density ≥ 600 kg/m³ 150 EI 90 S N – On the face of solid walls Solid ceiling N = Mortar-based installation, E = Installation block/Wall face frame (ER, WA), W = Fire batt ¹ of ∅ DN 100 to 200 K4 – 1.1 – 118 06/2015 – DE/en Fire dampers Correct use FKRS-EU Correct use in lightweight partition walls and fire walls Installation location Lightweight partition walls with metal support structure and cladding on both sides Lightweight partition walls with metal support structure and cladding on both sides, and with flexible ceiling joint Fire walls with metal support structure and cladding on both sides Lightweight partition walls with metal support structure and cladding on both sides Construction and building material Minimum thickness Performance class mm EI TT (ve–ho, i ↔ o) S Mortar-based Dry mortarless installation installation Lightweight partition walls 100 EI 120 S N¹ E¹ / W¹ Lightweight partition walls 100 EI 90 S N E/W Lightweight partition walls 100 EI 90 S – E Fire walls 115 EI 90 S N E Shaft walls 90 EI 90 S N E1 N = Mortar-based installation, E = Installation block (TQ, GL), E1 = E = Installation block (EQ), W = Fire batt ¹ of ∅ DN 100 to 200 06/2015 – DE/en K4 – 1.1 – 119 1 Fire dampers Order code Order code FKRS-EU FKRS-EU 1 FKRS – EU – 1 / DE / 160 / ER / A0 / Z43 ݈ ݇ ݉ Type FKRS-EU Fire damper ݊ ݍ Accessories 1 No entry: none ER Circular installation block TQ Square installation kit WA Wall face frame GL Installation kit for flexible ceiling joint Construction No entry: standard construction 1 Powder-coated casing 2¹ Stainless steel casing 7 Coated damper blade 1 – 7 Powder-coated casing and coated damper blade 2 – 7¹ Stainless steel casing and coated damper blade W² With fusible link 95 °C (only for use in warm air ventilation systems) Accessories 2 No entry: none S0 – AS Attachments Z00 – ZL08 Country of destination DE Germany Other destination countries upon request ¹ Only up to DN 200 when a fire batt system is used ² W can be combined with all constructions listed under Nominal size [mm] 100 125 150 160 180 200 224 250 280 315 Order example FKRS-EU-2-7/DE/200/TQ/SS/ZL06 Construction Country of destination Nominal size Installation kit Accessories Attachment 06/2015 – DE/en Casing made of stainless steel, damper blade coated/with impregnating agent Germany 200 mm Square Flexible connector on operating and installation sides Spring return actuator 24 V AC/DC and LON module LON-WA1/B2 K4 – 1.1 – 120 Accessories 1 Installation block ER 1 Description / ER / Order code detail FKRS-EU Application – Circular installation block ER for dry mortarless installation into solid walls and ceiling slabs – Installation openings can be created using a commercially available core drill – The unit is installed without a mortar mix by simply inserting it into the prepared installation opening – The installation block is factory mounted to the fire damper – In the event of a fire the intumescent seal closes the remaining gap. – A cover plate conceals any gaps and is used for screw fixing Materials and surfaces – The installation block is sheet steel with a special sealing compound – Cover plate and casing of the installation block made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1)# and stainless steel (2) dampers) Note For more information please refer to the installation and operating manual. Accessories 1 Order code Circular installation block Technical data ER Weight [kg] of FKRS-EU with fusible link and installation block Nominal size Installation block ER 100 5.7 125 8.6 150 160 7.6 7.3 180 11 200 9.8 224 250 13.5 12.1 280 315 16.0 15.0 FKRS-EU with spring return actuator: weight +1.8 kg. Installation opening/cover plate dimensions [mm] Nominal size ØD1 □B 100 200 250 125 250 300 150 160 250 300 250 300 180 300 350 200 300 350 224 250 350 400 350 400 280 315 400 450 400 450 FKRS-EU with circular installation block ER ݥ ݤ ϯ ① Installation block ② Seal K4 – 1.1 – 121 ݣ ݢ ͌D1 ③ Cover plate ④ Solid wall 06/2015 – DE/en Accessories 1 Installation kit TQ Description / TQ / Order code detail FKRS-EU Application – Square dry mortarless installation kit TQ for dry mortarless installation into lightweight partition walls and fire walls with metal support structure and cladding on both sides, and into shaft walls with or without metal support structure – The installation kit is factory mounted to the fire damper – The unit is installed without a mortar mix by simply inserting it into the prepared installation opening – In the event of a fire the intumescent seal closes the remaining gap. – A cover plate conceals any gaps and is used for screw fixing Materials and surfaces – Installation kit made of calcium silicate – Cover plate of the installation kit made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers) Note For more information please refer to the installation and operating manual. Accessories 1 Order code Square installation kit Technical data 1 TQ Weight [kg] of FKRS-EU with fusible link and installation kit Nominal size 100 Installation kit TQ 125 5.4 6.1 150 160 7.0 7.9 180 8.8 200 9.7 224 10.6 250 12.0 280 315 13.7 15.8 FKRS-EU with spring return actuator: weight +1.8 kg. Installation opening/cover plate dimensions [mm] Nominal size 100 □A2 □B1 125 210 300 235 325 150 260 350 160 270 360 180 290 380 200 310 400 224 334 424 250 360 450 280 315 390 480 425 515 FKRS-EU with square installation kit TQ ݥ ݤ ݣ ϯB ① Installation kit ② Seal 06/2015 – DE/en 1 ݢ ϯʹ ③ Cover plate ④ Lightweight partition wall or shaft wall K4 – 1.1 – 122 Accessories 1 Installation kit GL 1 Description / GL / Order code detail FKRS-EU Application – Dry mortarless installation in lightweight partition walls with metal support structure, cladding on both sides, and with flexible ceiling joint, directly underneath solid ceiling slabs, requires an installation kit. – The installation kit allows for subsidence of the slab whilst maintaining sealing integrity around the fire damper – Distance between ceiling and installation kit may be 0 – 180 mm (filler strips to be provided by others) – The installation kit is factory mounted and can be fixed to the ceiling with the supplied fixing brackets – The installation kit can be adapted to different wall thicknesses using cut-to-size fire-rated plasterboard panels Materials and surfaces – Installation kit made of special insulation material – Fixing brackets made of galvanised sheet steel – Threaded rods made of galvanised steel – Fixing elements made of galvanised steel Note For more information please refer to the installation and operating manual. Installation kit for lightweight partition walls with flexible ceiling joint Wall thickness [mm] Order code ≥ 100¹ GL ¹can be adapted to thicker walls (by others) FKRS-EU with installation kit GL (installation near the ceiling) ݣ ʹʹʷ ݢ ϯ̊ ʸʷʷ Installation kit GL, consisting of: ① Installation subframe ② Fixing bracket FKRS-EU with installation kit GL (installation near the ceiling, 180 mm max. distance) ݣ ʹʹʷ ݢ ϯ Installation kit GL, consisting of: ① Installation subframe K4 – 1.1 – 123 ̊ʸʷ ʷ ② Fixing bracket 06/2015 – DE/en Accessories 1 Wall face frame 1 Description / WA / Order code detail FKRS-EU Application – Dry mortarless installation of FKRS-EU fire dampers on the face of solid walls requires a wall face frame – The wall face frame is factory mounted to the fire damper – The unit is installed without mortar – The wall face frame is fixed with suitable screws and anchors (with suitability certificate for fire resistance) – Instead of anchors, threaded rods can be used (push through installation). Materials and surfaces – Wall face frame made of calcium silicate Note For more information please refer to the installation and operating manual. Accessories 1 Order code Wall face frame Technical data WA Weight [kg] of FKRS-EU with fusible link and wall face frame Nominal size Wall face frame WA 100 125 4.4 150 5.2 160 6.1 180 6.6 7.4 200 224 8.2 250 9.0 10.2 280 11.7 315 13.6 FKRS-EU with spring return actuator: weight +1.8 kg. Dimensions [mm] of installation opening/wall face frame Nominal size ØD2¹ □B2 100 125 130 200 150 155 225 160 180 250 190 260 180 210 280 200 224 230 300 250 254 324 280 350 280 310 380 315 345 415 ¹ Tolerance limits: –20 mm/+2 mm FKRS-EU with wall face frame WA W ̟ 100 ~ 102 ϯB ① Wall face frame K4 – 1.1 – 124 2 ݢ ݣ ͌D2 ② Solid wall 06/2015 – DE/en Accessories 2 Cover grille Description Cover grille with extension piece for FKRS-EU / / / / / A0 0A AS SA AA / / / / / FKRS-EU Application – If only one end is to be ducted on site, the other end must have a cover grille – To ensure that the open damper blade is contained within the damper casing on the installation side, an extension piece is required for nominal size 224 and above – Fire damper, cover grille and, if applicable, extension piece are factory assembled to form a unit – The free area of the cover grille is approx. 70% – Fire dampers with cover grilles or flexible connectors are supplied without lip seals – Cover grilles are also available separately – Cover grilles both ends may be used in Germany only for air transfer dampers with general building inspectorate licence, e.g. Z-19.18-2128 Materials and surfaces – Cover grilles made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers) – Extension piece same as casing 1 Note For more information please refer to the installation and operating manual. Cover grille for FKRS-EU Operating side Installation side Cover grille – Cover grille Flexible connector Cover grille Order code – Cover grille Flexible connector Cover grille Cover grille Order code detail Note: AA for FKRS-EU as air transfer damper The distance »a« between the open damper blade and the spigot should be 50 mm. Cover grille A0 0A AS SA AA ݢ ݢ ݣ ① Cover grille, mesh aperture 10 mm × 10 mm, wire width 2 mm; grille thickness approx. 1 mm ② Extension piece Cover grille L = 400 150 ݢ ݢ ݣ 200 ① Cover grille, mesh aperture 10 mm × 10 mm, wire width 2 mm; grille thickness approx. 1 mm ② Extension piece from nominal size 224 06/2015 – DE/en K4 – 1.1 – 125 Accessories 2 Flexible connector 1 Description Flexible connector for FKRS-EU / / / / / S0 0S SS SA AS / / / / / Order code detail FKRS-EU Application – Ducting must be installed in such a manner that it does not impose any significant loads on the fire damper in the event of a fire. – For information on how to limit such loads please refer to the guideline regarding fire protection requirements on ventilation systems (Lüftungsanlagen-Richtlinie, LüAR) – As ducts may expand and walls may become deformed in the event of a fire, we recommend for the following applications using flexible connectors when connecting the fire damper to rigid ducts: installation into lightweight partition walls, into lightweight shaft walls, and installation with a fire batt – Flexible connectors should be installed in such a way that both ends can compensate both tension and compression – Flexible ducts can be used as an alternative – To ensure that the open damper blade is contained within the damper casing on the installation side, an extension piece is required for nominal size 224 and above – Flexible connectors are supplied separately and can be fixed with clamps, for example (by others) – Flexible connectors are also available separately Materials and surfaces – Flexible connectors made of fibre-reinforced plastic – Fire resistance properties to 4102; B2 Note For more information please refer to the installation and operating manual. Flexible connector for FKRS-EU Operating side Flexible connector – Flexible connector Flexible connector Cover grille Installation side Order code – Flexible connector Flexible connector Cover grille Flexible connector S0 0S SS SA AS Flexible connector ݢ ݢ ݣ ① Flexible connector K4 – 1.1 – 126 ② Extension piece 06/2015 – DE/en Accessories 2 Flexible connector The distance »a« between the open damper blade and the flexible connector should be 50 mm. FKRS-EU Up to nominal size 200/from nominal size 224 ~ 190* 1 ~ 190* L = 400 ݢ ݢ 215 215 L = 400 ~ 190 ~ 340 ݢ ݢ ݣ 215 ~ 390 ① Flexible connector ② Extension piece * flexible length ≥ 100 mm when installed Flexible connector ͌ ͌ 215 ~ 200* * flexible length ≥ 100 mm when installed 06/2015 – DE/en K4 – 1.1 – 127 Accessories 2 Extension piece Circular extension piece for FKRS-EU Application – Fire dampers from nominal size 224 ordered with flexible connector or cover grille are supplied including extension piece on the installation side – Extension pieces are also available separately Materials and surfaces – Extension pieces made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers) Installation and commissioning – The distance »a« between the open damper blade and the cover grille or circular spigot should be 50 mm Note For more information please refer to the installation and operating manual. Extension piece ͌ˣ 54 ͌ 1 Description FKRS-EU 50 200 K4 – 1.1 – 128 06/2015 – DE/en Attachments Limit switch FKRS-EU Description FKRS-EU with limit switch – Limit switches with volt-free contacts enable the damper blade position indication. – Up to the maximum switch rating, relays or indicator lights for fire alarm systems can be used – One limit switch each is required for damper blade positions OPEN and CLOSED – Fire dampers with a fusible link can be supplied with one or two limit switches; the switches can also be fitted later Limit switch Note For more information please refer to the installation and operating manual. For detailed information on limit switches see Chapter 1.2 / Z01 / Z02 / Z03 ݍ Attachments 1 Order code Limit switch for damper blade position CLOSED Z01 Limit switch for damper blade position OPEN Z02 Limit switches for damper blade positions CLOSED and OPEN Z03 Order code detail 06/2015 – DE/en K4 – 1.1 – 129 Attachments Spring return actuator 1 Description FKRS-EU with spring return actuator For detailed information on the spring return actuator see Chapter 1.2 FKRS-EU FKRS-EU with spring return actuator – An open/close actuator allows for the remote control of the fire damper and/or release by a suitable duct smoke detector – If the supply voltage fails, or with thermoelectric release, the damper closes (power off to close) – Fire dampers with spring return actuators can be functionally checked OPEN/CLOSED/OPEN – Ambient temperature of the actuator, normal operation –30 to 50 °C – Two integral limit switches with volt-free contacts enable the damper blade position indication (OPEN and CLOSED) – BLF24-T-ST TR: The connecting cables of the spring return actuator are fitted with plugs, which ensure quick and easy connection to the TROX AS-i bus system – A conversion kit is available for adding an actuator to the standard construction – In case of conventional wiring (Z45) the voltage must be supplied by a safety transformer Note For more information please refer to the installation and operating manual. / Z43 / Z45 ݍ Attachments BLF230-T TR BLF24-T-ST TR Order code Z43 Z45 Bestellschlüsseldetail K4 – 1.1 – 130 06/2015 – DE/en Attachments TROXNETCOM Description FKRS-EU with TROXNETCOM module For detailed information on TROXNETCOM see Chapter 1.2 / / / / ZL06 ZL07 ZL08 ZA07 ݍ FKRS-EU FKRS-EU with spring return actuator and TROXNETCOM – Fire dampers with spring return actuator BLF24-T-ST TR and the modules shown here as attachments form a functional unit ready for automatic operation. – The components are factory assembled and wired – It enables the integration of different components (modules) into a network regardless of the manufacturer – The modules control actuators and/or receive signals from sensors Application LON: – LON indicates a standard local operating network system with manufacturer-independent communications – Data transmission is based on a uniform protocol – LonMark defines standards to ensure product compatibility – Only the bus line and the supply voltage remain to be connected by others – LON-WA1/B2: To provide the control input signal for up to two fire dampers – LON-WA1/B2-AD: Connection box for connecting the second fire damper with 24 V DC supply voltage to LON-WA1/B2-AD – LON-WA1/B2-AD230: Connection box with integral 230/24 V power supply unit for the connection of a second actuator-driven 24 V fire damper to LON-WA1/B2 Attachments LON-WA1/B2 and BLF24-T-ST TR LON-WA1/B2-AD and BLF24-T-ST TR LON-WA1/B2-AD230 and BLF24-T-ST TR AS-EM and BLF24-T-ST TR AS-i: – The AS interface is a global standard bus system according to EN 50295 and IEC 62026-2 – The module sends the control signals between the spring return actuator and the controller and power unit – This allows for controlling the actuator and monitoring of its running time during functional testing – The voltage (24 V DC) for the module and the actuator is supplied via the two-wire AS-i flat cable – Function display: operation, 4 inputs, 2 outputs Note For more information please refer to the installation and operating manual. Order code ZL06 ZL07 ZL08 ZA07 Order code detail 06/2015 – DE/en K4 – 1.1 – 131 1 Attachments Duct smoke detectors 1 Description Duct smoke detector RM-O-3-D FKRS-EU General – To prevent smoke from spreading in buildings, it is extremely important that the smoke is detected at an early stage. – Duct smoke detectors that operate on the principle of light scattering detect the smoke regardless of its temperature so that the fire dampers can be closed before the release temperature of 72 °C is reached – If the air contains suspended particles, as is the case with smoke, beams of light are deflected off these. A sensor (photodiode), which does not receive light in clear air, is illuminated by the scattered light. – The fire damper or smoke protection damper blade is released when the brightness of the scattered light exceeds a certain threshold Application RM-O-3-D: – Duct smoke detector for fire dampers and smoke protection dampers – General building inspectorate licence Z-78.6-125 – For airflow velocities from 1 – 20 m/s – Independent of the airflow direction – Supply voltage 230 V AC, 50/60 Hz or 24 V DC with voltage monitoring module (VWM) (upon request) – Volt-free signal and alarm relays – Integral signal lamps – Contamination level indicator – Automatic adjustment of alarm threshold – Long service life – Temperature range 0 – 60 °C RM-O-VS-D: – Duct smoke detector for fire dampers and smoke protection dampers – General building inspectorate licence Z-78.6-67 – For airflow velocities from 1 – 20 m/s – Independent of the airflow direction – Airflow monitoring with warning for lower limit 2 m/s – Supply voltage 230 V AC, 50/60 Hz – Volt-free signal and alarm relays – Integral signal lamps – Contamination level indicator – Automatic adjustment of alarm threshold – Long service life – Temperature range 0 – 60 °C Duct smoke detector RM-O-VS-D For detailed information on the duct smoke detector see Chapter 1.2 Note For more information please refer to the installation and operating manual. Attachments Smoke detector Order code RM-O-3-D RM-O-VS-D Duct smoke detectors are attachments and to be ordered separately. K4 – 1.1 – 132 06/2015 – DE/en Fire dampers Quick sizing FKRS-EU Volume flow rate at differential pressure Δpst < 35 Pa LWA [dB(A)] 25 35 45 Nominal size mm 100 125 150 160 180 200 224 250 280 315 25 35 1 45 l/s 22 40 70 80 105 140 170 215 280 360 m³/h 35 65 105 125 165 210 245 315 405 525 50 90 150 180 235 295 345 445 570 735 79 144 252 288 388 504 612 774 1008 1296 126 234 378 450 587 756 882 1134 1458 1890 180 324 540 648 847 1062 1242 1602 2052 2646 The Easy Product Finder allows you to size products using your project-specific data. You will find the Easy Product Finder on our website. 06/2015 – DE/en K4 – 1.1 – 133 Fire dampers Free area and resistance coefficient 1 Nominal size 100 125 150 160 200 224 250 280 315 FKRS-EU A [m²] ζ 0.005 0.009 0.013 0.016 0.025 0.032 0.040 0.052 0.067 1.71 1.08 0.76 0.67 0.44 0.56 0.45 0.36 0.28 Maximum upstream velocity: ≤ 8 m/s for standard construction, ≤ 10 m/s for construction with spring return actuator. K4 – 1.1 – 134 06/2015 – DE/en Fire dampers Dimensions and weight – FKRS-EU Dimensions FKRS-EU FKRS-EU with fusible link 1 L = 400 270 220 ~ 180 50 50 ~ 75 FKRS-EU with fusible link Ø DN ݢ ① Keep clear to provide access to the release mechanism Dimensions [mm] / Weight [kg] Nominal size ØD Weight 06/2015 – DE/en 100 99 1.3 125 124 1.6 150 149 1.8 160 159 2 180 179 2.3 200 199 2.5 224 223 2.7 250 249 3.3 280 279 3.8 315 314 4.4 K4 – 1.1 – 135 Fire dampers Dimensions and weight – FKRS-EU/.../Z4* FKRS-EU with spring return actuator L = 400 270 220 ~ 190 50 50 ~ 115 ݢ FKRS-EU with spring return actuator Ø DN 1 Dimensions FKRS-EU ① Keep clear to provide access to the release mechanism Dimensions [mm] / Weight [kg] Nominal size ØD Weight K4 – 1.1 – 136 100 99 3.1 125 124 3.4 150 149 3.6 160 159 3.7 180 179 4.0 200 199 4.2 224 250 223 4.5 249 5 280 279 5.5 315 314 6.2 06/2015 – DE/en Fire dampers Specification text Description This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme. Circular fire dampers for the isolation of duct penetrations between fire compartments. Tested for fire resistance properties to EN 1366-2, with CE marking and declaration of performance according to the Construction Products Regulation. Ready-for-operation unit, which includes a fire-resistant damper blade and a release mechanism. For mortar-based installation and dry mortarless installation into solid walls and ceiling slabs, mortar-based installation into non-load-bearing solid walls with flexible ceiling joint, mortar-based and dry mortarless installation into lightweight partition walls with cladding on both sides, lightweight fire walls and lightweight shaft walls, and dry mortarless installation on the face of solid walls. For dry mortarless installation in lightweight partition walls with metal support structure and flexible ceiling joint; for dry mortarless installation in solid walls and ceiling slabs when using a fire batt; in lightweight partition walls with metal support structure and cladding on both sides. Casing length 400 mm, for the connection to ducts made of non-combustible or combustible materials. Thermal or thermoelectric release at 72 °C or 95 °C (warm air ventilation systems). Constructions with spring return actuator for opening and closing the fire damper independent of the nominal size and even while the ventilation system is running, e.g. for a functional test. Simple construction for dry mortarless installation with installation kit: ER, TQ, GL, WA Special characteristics – Declaration of performance according to Construction Products Regulation – Classification to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S – Building inspectorate licence Z-56.4212-991 for fire resistance properties – Complies with the requirements of EN 15650 – Tested to EN 1366-2 for fire resistance properties – Hygiene complies with VDI 6022 part 1 (07/2011), VDI 3803 (10/2002), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007) – Corrosion protection according to EN 15650 in connection with EN 60068-2-52 – Closed blade air leakage to EN 1751, class 3 – Casing air leakage to EN 1751, class C – Low differential pressure and sound power level – Any airflow direction – Integration into the central BMS with TROXNETCOM 06/2015 – DE/en FKRS-EU Materials and surfaces Casing: – Galvanised sheet steel – Galvanised sheet steel, powder-coated RAL 7001 – Stainless steel 1.4301 1 Damper blade: – Special insulation material – Special insulation material with coating Other components: – Damper blade shaft made of galvanised steel or stainless steel – Plastic bearings – Seals of elastomer The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request. Technical data – Nominal sizes: 100 to 315 mm – Casing length: 400 mm – Volume flow rate range: Up to 770 l/s or 2770 m³/h – Differential pressure: up to 1500 Pa – Operating temperature: at least 0 – 50 °C ** – Release temperature 72 °C or 95 °C (for use in warm air ventilation systems) – Upstream velocity: ≤ 8 m/s with standard construction; ≤ 10 m/s * with spring return actuator Note: * Data applies to uniform upstream and downstream conditions for the fire damper ** Temperatures may differ for units with attachments Sizing data – ______________________________ [m³/h] – Δpst ______________________________ [Pa] – LWA Air-regenerated noise __________ [dB(A)] K4 – 1.1 – 137 Fire dampers Specification text 1 Order options Type FKRS-EU Fire damper Construction No entry: standard construction 1 Powder-coated casing 2¹ Stainless steel casing 7 Coated damper blade 1 – 7 Powder-coated casing and coated damper blade 2 – 7¹ Stainless steel casing and coated damper blade W² With fusible link 95 °C (only for use in warm air ventilation systems) Country of destination DE Germany Other destination countries upon request FKRS-EU Accessories 1 No entry: none ER Circular installation block TQ Square installation kit WA Wall face frame GL Installation kit for flexible ceiling joint Accessories 2 No entry: none S0 – AS Attachments Z00 – ZL08 ¹ Only up to DN 200 when a fire batt system is used ² W can be combined with all constructions listed under Nominal size [mm] 100 125 150 160 180 200 224 250 280 315 K4 – 1.1 – 138 06/2015 – DE/en 1.3 – X X Basic information and nomenclaturetestregistrierung Fire dampers 1 Basic information and nomenclature ■ Product selection ■ Principal dimensions ■ Nomenclature ■ Colour codes according to IEC 60757 ■ Sizing 06/2015 – DE/en K4 – 1.3 – 1 Fire dampers Basic information and nomenclature 1 Product selection Fire dampers Usage Type FK-EU Installation location Construction/ building material Minimum thickness FKS-EU Mortar-based installation Dry mortarless installation peri- partimeter ally⁵ Fire batt Installation kit² mm In solid walls 100 EI 90 S EI 90 S EI 120 S EI 90 S In solid walls with movement joint Walls/gross density ≥ 500 kg/m³ 100 EI 90 S – – On the face of solid walls Adjacent to solid walls¹ Remote from solid walls¹ Walls/gross density ≥ 500 kg/m³ Walls/gross density ≥ 500 kg/m³ Walls/gross density ≥ 500 kg/m³ Ceiling slabs/gross density ≥ 600 kg/m³ Ceiling slabs/gross density ≥ 600 kg/m³ 100 – – 100 – 100 – 125 EI 90 S 150 EI 90 S Ceiling slabs/gross density ≥ 600 kg/m³ 125 EI 90 S – Lightweight partition walls with metal support structure and cladding on both sides Lightweight partition walls 100 EI 90 S – Lightweight partition walls with metal support structure and cladding on both sides, flexible ceiling joint¹ Lightweight partition walls 100 – – – Fire walls 115 EI 90 S – Shaft walls 90 – Shaft walls 40 or 50⁴ In solid ceiling slabs, with concrete base Fire walls with metal support structure and cladding on both sides Lightweight partition walls with metal support structure and cladding on one side Lightweight partition walls without metal support structure but with cladding on one side In self supporting fire-resistant suspended ceilings Tile ceilings, screw-fixed and primed Lay-in ceiling tiles made of panel materials Metal ceilings perimeter Installation Installation perimeter kit² kit² Fire resistance class Walls/gross density ≥ 500 kg/m³ In solid ceiling slabs FKR-EU MortarDry MortarDry based mortarless based mortarless installation installation installation installation EI 120 S EI 90 S EI 120 S – – – – – – – EI 90 S – – – – – – EI 90 S – – – – – – EI 90 S – – – – – – – – EI 120 S EI 90 S EI 120 S – EI 90 S – EI 90 S – EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S – – – – – EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S – – EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S – – – EI 90 S – – EI 90 S EI 90 S – – – – – – – – – – – – – – – – – – – – – – – – – – – – – EI 120 S – – – EI 120 S EI 90 S ¹ Not for FK-EU as air transfer damper ² Installation kit for the selected installation situation ³ For ØDN 100 to 200 in lightweight partition wall with metal support structure and mineral wool ⁴ 50 only for FKR-EU ⁵ Additional mineral wool K4 – 1.3 – 2 06/2015 – DE/en Fire dampers Basic information and nomenclature Product selection Fire dampers 1 Usage Type FKRS-EU Installation location Minimum Construction/building thickness material Mortar-based installation perimeter FV-EU Dry mortarless installation Fire batt mm Installation kit² KA-EU FVZK30 KU-K30 Mortar-based installation perimeter Mortarbased installation Dry Instal- mortarless lation installation kit Fire resistance class In solid walls Walls/gross density ≥ 500 kg/m³ 100 EI 120 S EI 120 S³, EI 90 S EI 90 S In solid walls with movement joint Walls/gross density ≥ 500 kg/m³ 100 – – On the face of solid walls Adjacent to solid walls¹ Remote from solid walls¹ Walls/gross density ≥ 500 kg/m³ Walls/gross density ≥ 500 kg/m³ Walls/gross density ≥ 500 kg/m³ Ceiling slabs/gross density ≥ 600 kg/m³ Ceiling slabs/gross density ≥ 600 kg/m³ 100 EI 90 S 100 EI 120 S K90 – – – – – – – – EI 90 S – – – – – – – – – – – 100 – – – – – – – 125 – – – – – – – 150 EI 120 S EI 120 S K90 – – Ceiling slabs/gross density ≥ 600 kg/m³ 125 – – – – – Lightweight partition walls with metal support structure and cladding on both sides Lightweight partition walls 100 EI 120 S³, EI 90 S K90 – – Lightweight partition walls with metal support structure and cladding on both sides, flexible ceiling joint¹ Lightweight partition walls 100 – – EI 90 S – – – – Fire walls 115 EI 90 S – EI 90 S – K90 – – Shaft walls 90 EI 90 S – EI 90 S – – – – Shaft walls 40 or 50⁴ – – – – – – – – – – – – – K30-U K30-U – – – – – – K30-U K30-U – – – – – – K30-U K30-U In solid ceiling slabs In solid ceiling slabs, with concrete base Fire walls with metal support structure and cladding on both sides Lightweight partition walls with metal support structure and cladding on one side Lightweight partition walls without metal support structure but with cladding on one side In self supporting fire-resistant suspended ceilings Tile ceilings, screw-fixed and primed Lay-in ceiling tiles made of panel materials Metal ceilings EI 120 S³, EI 90 S EI 90 S – – EI 120 S³, EI 120 S³, EI 120 S EI 90 S EI 90 S ¹ Not for FK-EU as air transfer damper ² Installation kit for the selected installation situation ³ For ØDN 100 to 200 in lightweight partition wall with metal support structure and mineral wool ⁴ 50 only for FKR-EU ⁵ Additional mineral wool 06/2015 – DE/en K4 – 1.3 – 3 Fire dampers Basic information and nomenclature 1 Principal dimensions Nomenclature Rectangular fire dampers Circular fire dampers B [mm] Width of the fire damper Nominal size [mm] Diameter of the fire damper H [mm] Height of the fire damper L [mm] Length of the fire damper [m³/h] and [l/s] Volume flow rate Δpst [Pa] Static differential pressure LWA [dB(A)] A-weighted sound power level of air-regenerated noise for the fire damper v [m/s] Airflow velocity based on the upstream cross section (B × H or diameter) A [m²] Free area K Correction value ζ Resistance coefficient (fully ducted) Wiring Colour codes according to IEC 60757 Code BK BN RD OG YE GN BU Sizing with the help of this catalogue Colour codes according to IEC 60757 Colour Code black brown red orange yellow green blue VT GY WH PK TQ GNYE Colour violet grey white pink turquoise green-yellow This catalogue provides convenient quick sizing tables for fire dampers. The volume flow rates for all available dimensions and nominal sizes are provided based on a particular differential pressure. Sizing data for other volume flow rates and differential pressures can be determined quickly and precisely using the Easy Product Finder design programme. Easy Product Finder The Easy Product Finder allows you to size products using your project-specific data. You will find the Easy Product Finder on our website. K4 – 1.3 – 4 06/2015 – DE/en
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement