Fire dampers Type FKRS-EU

Fire dampers Type FKRS-EU
FKRS-EU
1.1 –
X X FKRS-EUtestregistrierung
Fire dampers
1
Type FKRS-EU
FKRS-EU with fusible
link for 72 °C or 95 °C
Compact dimensions, ideal for restricted spaces
CE compliant according
to European regulations
Small circular fire damper for the isolation of duct penetrations#
between fire compartments, available in ten nominal sizes
■ Nominal sizes: 100 – 315 mm
■ Low differential pressure and sound power level
■ Optional stainless steel casing or powder-coated casing
for increased corrosion protection
■ Air transfer damper as an option
■ Integration into the central BMS with TROXNETCOM
■ Universal installation options
Optional equipment and accessories
■ Electric actuator 24 V/230 V
With TROXNETCOM
as an option
H GE
TE
ET
HY
G
I
ISC
■ Duct smoke detector RM-O-3-D
ST
EN
■ Release temperature 72/95 °C
VD
I 6022
Tested to VDI 6022
06/2015 – DE/en
K4 – 1.1 – 111
Fire dampers
General information
FKRS-EU
Type
1
FKRS-EU
Variants
FKRS-EU with fusible link
Page
General information
Correct use
Order code
Installation block ER
Installation kit TQ
Installation kit GL
Wall face frame
Cover grille
Flexible connector
Extension piece
Limit switch
Spring return actuator
TROXNETCOM
Duct smoke detectors
Quick sizing
Free area and resistance coefficient
Dimensions and weight – FKRS-EU
Dimensions and weight – FKRS-EU/.../Z4*
Specification text
1.1 – 112
1.1 – 118
1.1 – 120
1.1 – 121
1.1 – 122
1.1 – 123
1.1 – 124
1.1 – 125
1.1 – 126
1.1 – 128
1.1 – 129
1.1 – 130
1.1 – 131
1.1 – 132
1.1 – 133
1.1 – 134
1.1 – 135
1.1 – 136
1.1 – 137
Basic information and nomenclature
1.3 – 1
FKRS-EU with spring return actuator
Product examples
K4 – 1.1 – 112
06/2015 – DE/en
Fire dampers
General information
Description
FKRS-EU with
spring return actuator
For detailed information
on attachments
see Chapter K4 – 1.2.
Application
– Fire dampers of Type FKRS-EU,
with CE marking and declaration
of performance, for the isolation
of duct penetrations between fire
compartments in the event of a fire
– To prevent the propagation of fire
and smoke through ductwork to adjacent
designated fire compartments
Classification
– Class of performance to EN 13501-3,
up to EI 120 (ve, ho, i ↔ o) S
Variants
– With fusible link
– With spring return actuator
– With cover grilles both ends as air transfer
damper with general building inspectorate
licence: Z-19.18-2128
Nominal sizes
– 100, 125, 150, 160, 180, 200,
224, 250, 280, 315
– L: 400 mm
Attachments
– Limit switch for damper blade
position indication
– Spring return actuator for 24 V AC/DC
or 230 V AC supply voltage
– Network module for the integration
with AS-i or LON networks
Accessories
– Circular installation block ER
– Square installation kit TQ
– Wall face frame WA
– Installation kit GL
– Cover grille
– Flexible connectors
– Extension piece
Useful additions
– Duct smoke detector RM-O-3-D
– Duct smoke detector
with airflow monitor RM-O-VS-D
06/2015 – DE/en
Special characteristics
– Declaration of performance according
to Construction Products Regulation
– Classification to EN 13501-3,
up to EI 120 (ve, ho, i ↔ o) S
– Building inspectorate licence Z-56.4212-991
for fire resistance properties
– Complies with the requirements of EN 15650
– Tested to EN 1366-2
for fire resistance properties
– Hygiene complies with VDI 6022 part 1
(07/2011), VDI 3803 (10/2002), DIN 1946
part 4 (12/2008), and EN 13779 (09/2007)
– Corrosion protection according to EN 15650
in connection with EN 60068-2-52
– Closed blade air leakage to EN 1751, class 3
– Casing air leakage to EN 1751, class C
– Low differential pressure
and sound power level
– Any airflow direction
– Integration into the central BMS
with TROXNETCOM
FKRS-EU
Parts and characteristics
– Dry mortarless installation into solid walls
and ceiling slabs, lightweight partition walls,
fire walls, and shaft walls using
an installation block
– Installation with wall face frame on the face
of solid walls
– Release temperature 72 °C or 95 °C
(for use in warm air ventilation systems)
– Approved installation orientation
from 0° to 360°
Construction features
– Rigid circular casing suitable for push fitting
into cut circular holes without additional drilling
and chiselling being required
– Spigot connections with lip seal on both ends,
suitable for ventilation ducts according
to EN 1506 and EN 13180 plus non-standard
but commercial nominal sizes 180,
224 and 280
– Suitable for the connection of flexible
connectors or cover grilles
– The release mechanism is accessible
and can be tested from the outside
– One inspection access panel
– Remote control with spring return actuator
Materials and surfaces
Casing:
– Galvanised sheet steel
– Galvanised sheet steel,
powder-coated RAL 7001
– Stainless steel 1.4301
Damper blade:
– Special insulation material
– Special insulation material with coating
Other components:
– Damper blade shaft made of galvanised steel
or stainless steel
– Plastic bearings
– Seals of elastomer
The construction variants with stainless steel
or powder-coated casing meet even more critical
requirements for corrosion protection.
Detailed listing on request.
K4 – 1.1 – 113
1
Fire dampers
General information
FKRS-EU
Installation and commissioning
Install the fire damper according to the operating
and installation manual.
1
Mortar-based installation:
– In solid walls and ceiling slabs
– In non-load-bearing solid walls
with flexible ceiling joint
– In lightweight partition walls
and fire walls with metal support structure
and cladding on both sides
– In shaft walls with metal support structure
and cladding on one side
Dry mortarless installation:
– In solid walls and ceiling slabs
with installation block ER
– In solid walls and ceiling slabs using a fire batt
– In lightweight partition walls with metal support
structure and cladding on both sides using
a fire batt
– On the face of solid walls
with wall face frame WA
– In lightweight partition walls with metal support
structure, cladding on both sides
and flexible ceiling joint: with installation kit GL
– In lightweight partition walls with metal support
structure and cladding on both sides
with installation kit TQ
– In fire walls with metal support structure and
cladding on both sides with installation kit TQ
– In shaft walls with or without metal support
structure and cladding on one side
with installation kit ES
Technical data
Nominal sizes
Casing length
Volume flow rate range
Differential pressure range
Operating temperature
Release temperature
Upstream velocity*
Standards and guidelines
– Construction Products Regulation
– EN 15650:2010 – Ventilation for buildings –
Fire dampers
– EN 1366-2:1999 Fire resistance tests
for service installations – Fire dampers
– EN 13501-3:2010 Fire classification
of construction products and building elements
– EN 1751:1999 Ventilation for buildings –
Air terminal devices
Maintenance
– The functional reliability of the fire damper
must be tested at least every six months;
this has to be arranged by the owner
of the ventilation system; functional tests
must be carried out in compliance with
the basic maintenance principles stated
in EN 13306 and DIN 31051. If two consecutive
tests, one 6 months after the other,
are successful, the next test can be
conducted one year later.
– A functional test involves closing the damper
blade and opening it again; with a spring return
actuator this can be done via remote control
– Fire dampers must be included in the regular
cleaning schedule of the ventilation system.
– For details on maintenance and inspection,
refer to the installation and operating manual
100 – 315 mm
400 mm
Up to 770 l/s or up to 2770 m³/h
Up to 1500 Pa
At least 0 – 50 °C **
72 °C or 95 °C (for warm air ventilation systems)
≤ 8 m/s with standard construction; ≤ 10 m/s with spring return actuator
* Data applies to uniform upstream and downstream conditions for the fire damper
** Temperatures may differ for units with attachments
K4 – 1.1 – 114
06/2015 – DE/en
Fire dampers
General information
FKRS-EU
Functional description
In the event of a fire, fire dampers shut
automatically to prevent the propagation
Construction with fusible link
of fire and smoke through ductwork to adjacent
designated fire compartments. In the event of a
fire, the damper is triggered at 72 °C or at 95 °C
(use in warm air ventilation systems) by a fusible
link. The release mechanism is accessible
and can be tested from the outside.
Function
1
Schematic illustration of FKRS-EU with fusible link
‫ݥ‬
‫ݤ‬
‫ݦ‬
‫ݣ‬
‫ݢ‬
‫ݧ‬
‫ݨ‬
① Casing
② Fusible link
③ Damper blade with seal
④ Inspection access (12 mm)
06/2015 – DE/en
⑤ Lip seal
⑥ Handle with interlock and damper blade position indicator
⑦ Release mechanism
K4 – 1.1 – 115
Fire dampers
General information
1
Function
Construction with
spring return actuator
FKRS-EU
Functional description
The spring return actuator enables the motorised
opening and closing of the damper blade;
it can be activated by the central BMS.
In the event of a fire, the damper is triggered
thermoelectrically at 72 °C or 95 °C
(use in warm air ventilation systems).
As long as power is supplied to the actuator,
the damper blade remains open.
If the supply voltage fails, the damper closes
(power off to close). Motorised fire dampers
can be used to shut off ducts. The torque
of each actuator is sufficient to open and close
the damper blade even while the fan is running.
The spring return actuator is fitted with limit
switches that can be used for capturing
the damper blade position.
Schematic illustration of FKRS-EU with spring return actuator
‫ݥ‬
‫ݤ‬
‫ݦ‬
‫ݣ‬
‫ݢ‬
‫ݧ‬
‫ݨ‬
① Casing
② Temperature sensor
③ Damper blade with seal
④ Inspection access (12 mm)
K4 – 1.1 – 116
⑤ Lip seal
⑥ Spring return actuator
⑦ Thermoelectric release mechanism
06/2015 – DE/en
Fire dampers
General information
Function
Use as an
air transfer damper
FKRS-EU
Functional description
Air transfer dampers prevent fire and smoke
from spreading in buildings. The thermal release
mechanism closes the damper blade when
the release temperature (72 °C) is reached.
Smoke can, however, spread below
this temperature. Air transfer dampers
are installed (mortar-based installation)
in places where the general building
inspectorate sees no risk, for example:
Special characteristics
– General building inspectorate licence
Z-19.18-2128
– Air transfer damper
without duct smoke detector
1
– As an inlet for additional supply air in the walls
of required corridors (escape routes)
if the dampers are installed near the ground
(up to 500 mm above OKFF)
– In installation shafts as long as they have
sufficient fire resistance where they penetrate
compartment floors
– In installation ducts as long as they have
sufficient fire resistance where they penetrate
compartment floors or walls
(except for necessary corridors
or escape routes)
The air transfer damper is an FKRS-EU
fire damper with 72 °C thermal release
mechanism (construction with fusible link)
and cover grilles both ends.
Schematic illustration of the FKRS-EU as air transfer damper, with fusible link and cover grille
‫ݥ‬
‫ݤ‬
‫ݦ‬
‫ݣ‬
‫ݢ‬
‫ݦ‬
‫ݧ‬
‫ݨ‬
① Casing
② Fusible link
③ Damper blade with seal
④ Inspection access (12 mm)
06/2015 – DE/en
⑤ Cover grille
⑥ Handle with interlock and damper blade position indicator
⑦ Release mechanism
K4 – 1.1 – 117
Fire dampers
Correct use
FKRS-EU
Design information
– Approved only for use in ventilation
and air conditioning sytems
– A class of performance up to EI 120
(ve, ho, i ↔ o) S can only be achieved
with ducts connected on both ends,
or with a duct on one end and a cover grille
on the other end.
– If the fire damper is installed in a solid wall,
solid ceiling slab, lightweight partition wall
or shaft wall with a lower fire resistance class
than that of the fire damper, the fire resistance
class of the wall or ceiling slab applies also
to the FKRS-EU (details upon request)
– Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire damper in the event of a fire.
1
– For particular applications it is recommended
that flexible connectors are used to connect
rigid ducting to the unit.
– Fire dampers must be installed,
connected and secured according
to the operating and installation manual.
Incorrect use
Never use the fire damper:
– without specially approved attachments
in areas with potentially explosive atmospheres
– as a smoke control damper
– outdoors without sufficient protection
against the effects of weather
– in atmospheres where chemical reactions,
whether planned or unplanned, may cause
damage to the fire damper or lead to corrosion
Correct use in solid walls and ceiling slabs
Installation location
Construction
and building material
Minimum
Performance class Mortar-based
thickness
installation
mm
EI TT (ve–ho, i ↔ o) S
Dry
mortarless
installation
Solid walls
Solid walls,
gross density ≥ 500 kg/m³
100
EI 120 S
N
W¹
Solid walls,
gross density ≥ 500 kg/m³
100
EI 90 S
N
E/W
Solid walls,
gross density ≥ 500 kg/m³
100
EI 90 S
–
E
Solid ceiling slabs,
gross density ≥ 600 kg/m³
150
EI 120 S
N
–
Solid ceiling slabs,
gross density ≥ 600 kg/m³
150
EI 90 S
–
E/W
Solid ceiling slabs,
gross density ≥ 600 kg/m³
150
EI 90 S
N
–
On the face of solid walls
Solid ceiling
N = Mortar-based installation, E = Installation block/Wall face frame (ER, WA), W = Fire batt
¹ of ∅ DN 100 to 200
K4 – 1.1 – 118
06/2015 – DE/en
Fire dampers
Correct use
FKRS-EU
Correct use in lightweight partition walls and fire walls
Installation location
Lightweight
partition walls
with metal support
structure
and cladding
on both sides
Lightweight
partition walls
with metal support
structure
and cladding
on both sides,
and with flexible
ceiling joint
Fire walls
with metal support
structure
and cladding
on both sides
Lightweight
partition walls
with metal support
structure
and cladding
on both sides
Construction
and building material
Minimum
thickness
Performance class
mm
EI TT (ve–ho, i ↔ o) S
Mortar-based Dry mortarless
installation
installation
Lightweight partition walls 100
EI 120 S
N¹
E¹ / W¹
Lightweight partition walls 100
EI 90 S
N
E/W
Lightweight partition walls 100
EI 90 S
–
E
Fire walls
115
EI 90 S
N
E
Shaft walls
90
EI 90 S
N
E1
N = Mortar-based installation, E = Installation block (TQ, GL), E1 = E = Installation block (EQ), W = Fire batt
¹ of ∅ DN 100 to 200
06/2015 – DE/en
K4 – 1.1 – 119
1
Fire dampers
Order code
Order code
FKRS-EU
FKRS-EU
1
FKRS – EU – 1 / DE / 160 / ER / A0 / Z43
݈
݇
݉
 Type
FKRS-EU Fire damper
݊
‫݋‬
‫݌‬
‫ݍ‬
 Accessories 1
No entry: none
ER
Circular installation block
TQ
Square installation kit
WA
Wall face frame
GL
Installation kit for flexible ceiling joint
 Construction
No entry: standard construction
1
Powder-coated casing
2¹
Stainless steel casing
7
Coated damper blade
1 – 7 Powder-coated casing
and coated damper blade
2 – 7¹ Stainless steel casing
and coated damper blade
W²
With fusible link 95 °C
(only for use in warm
air ventilation systems)
 Accessories 2
No entry: none
S0 – AS
 Attachments
Z00 – ZL08
 Country of destination
DE
Germany
Other destination countries upon request
¹ Only up to DN 200
when a fire batt system is used
² W can be combined with all constructions
listed under 
 Nominal size [mm]
100
125
150
160
180
200
224
250
280
315
Order example
FKRS-EU-2-7/DE/200/TQ/SS/ZL06
Construction
Country of destination
Nominal size
Installation kit
Accessories
Attachment
06/2015 – DE/en
Casing made of stainless steel, damper blade coated/with impregnating agent
Germany
200 mm
Square
Flexible connector on operating and installation sides
Spring return actuator 24 V AC/DC and LON module LON-WA1/B2
K4 – 1.1 – 120
Accessories 1
Installation block ER
1
Description
/ ER /
‫݋‬
Order code detail
FKRS-EU
Application
– Circular installation block ER for dry mortarless
installation into solid walls and ceiling slabs
– Installation openings can be created using
a commercially available core drill
– The unit is installed without a mortar
mix by simply inserting it into the prepared
installation opening
– The installation block is factory mounted
to the fire damper
– In the event of a fire the intumescent seal
closes the remaining gap.
– A cover plate conceals any gaps
and is used for screw fixing
Materials and surfaces
– The installation block is sheet steel
with a special sealing compound
– Cover plate and casing of the installation block
made of galvanised sheet steel
(and powder-coated silver grey, RAL 7001,
when used with powder-coated (1)#
and stainless steel (2) dampers)
Note
For more information please refer
to the installation and operating manual.
Accessories 1
Order code
Circular installation block
Technical data
ER
Weight [kg] of FKRS-EU with fusible link and installation block
Nominal size
Installation block ER
100
5.7
125
8.6
150
160
7.6
7.3
180
11
200
9.8
224
250
13.5
12.1
280
315
16.0
15.0
FKRS-EU with spring return actuator: weight +1.8 kg.
Installation opening/cover plate dimensions [mm]
Nominal size
ØD1
□B
100
200
250
125
250
300
150
160
250
300
250
300
180
300
350
200
300
350
224
250
350
400
350
400
280
315
400
450
400
450
FKRS-EU with circular installation block ER
‫ݥ‬
‫ݤ‬
ϯ
① Installation block
② Seal
K4 – 1.1 – 121
‫ݣ‬
‫ݢ‬
͌D1
③ Cover plate
④ Solid wall
06/2015 – DE/en
Accessories 1
Installation kit TQ
Description
/ TQ /
‫݋‬
Order code detail
FKRS-EU
Application
– Square dry mortarless installation kit TQ
for dry mortarless installation into lightweight
partition walls and fire walls with metal support
structure and cladding on both sides,
and into shaft walls with
or without metal support structure
– The installation kit is factory mounted
to the fire damper
– The unit is installed without a mortar
mix by simply inserting it into the prepared
installation opening
– In the event of a fire the intumescent seal
closes the remaining gap.
– A cover plate conceals any gaps
and is used for screw fixing
Materials and surfaces
– Installation kit made of calcium silicate
– Cover plate of the installation kit made
of galvanised sheet steel
(and powder-coated silver grey, RAL 7001,
when used with powder-coated (1)
and stainless steel (2) dampers)
Note
For more information please refer
to the installation and operating manual.
Accessories 1
Order code
Square installation kit
Technical data
1
TQ
Weight [kg] of FKRS-EU with fusible link and installation kit
Nominal size
100
Installation kit
TQ
125
5.4
6.1
150
160
7.0
7.9
180
8.8
200
9.7
224
10.6
250
12.0
280
315
13.7
15.8
FKRS-EU with spring return actuator: weight +1.8 kg.
Installation opening/cover plate dimensions [mm]
Nominal size
100
□A2
□B1
125
210
300
235
325
150
260
350
160
270
360
180
290
380
200
310
400
224
334
424
250
360
450
280
315
390
480
425
515
FKRS-EU with square installation kit TQ
‫ݥ‬
‫ݤ‬
‫ݣ‬
ϯB
① Installation kit
② Seal
06/2015 – DE/en
1
‫ݢ‬
ϯʹ
③ Cover plate
④ Lightweight partition wall or shaft wall
K4 – 1.1 – 122
Accessories 1
Installation kit GL
1
Description
/ GL /
‫݋‬
Order code detail
FKRS-EU
Application
– Dry mortarless installation in lightweight
partition walls with metal support structure,
cladding on both sides, and with flexible ceiling
joint, directly underneath solid ceiling slabs,
requires an installation kit.
– The installation kit allows for subsidence
of the slab whilst maintaining sealing
integrity around the fire damper
– Distance between ceiling and installation kit
may be 0 – 180 mm
(filler strips to be provided by others)
– The installation kit is factory mounted
and can be fixed to the ceiling
with the supplied fixing brackets
– The installation kit can be adapted to different
wall thicknesses using cut-to-size fire-rated
plasterboard panels
Materials and surfaces
– Installation kit made of special
insulation material
– Fixing brackets made of galvanised sheet steel
– Threaded rods made of galvanised steel
– Fixing elements made of galvanised steel
Note
For more information please refer
to the installation and operating manual.
Installation kit for lightweight partition walls with flexible ceiling joint
Wall thickness [mm]
Order code
≥ 100¹
GL
¹can be adapted to thicker walls (by others)
FKRS-EU with installation kit GL (installation near the ceiling)
‫ݣ‬
ʹʹʷ
‫ݢ‬
ϯ̊
ʸʷʷ
Installation kit GL, consisting of:
① Installation subframe
② Fixing bracket
FKRS-EU with installation kit GL (installation near the ceiling, 180 mm max. distance)
‫ݣ‬
ʹʹʷ
‫ݢ‬
ϯ
Installation kit GL, consisting of:
① Installation subframe
K4 – 1.1 – 123
̊ʸʷ
ʷ
② Fixing bracket
06/2015 – DE/en
Accessories 1
Wall face frame
1
Description
/ WA /
‫݋‬
Order code detail
FKRS-EU
Application
– Dry mortarless installation of FKRS-EU
fire dampers on the face of solid walls requires
a wall face frame
– The wall face frame is factory mounted
to the fire damper
– The unit is installed without mortar
– The wall face frame is fixed
with suitable screws and anchors
(with suitability certificate for fire resistance)
– Instead of anchors, threaded rods can be used
(push through installation).
Materials and surfaces
– Wall face frame made of calcium silicate
Note
For more information please refer
to the installation and operating manual.
Accessories 1
Order code
Wall face frame
Technical data
WA
Weight [kg] of FKRS-EU with fusible link and wall face frame
Nominal size
Wall face frame WA
100
125
4.4
150
5.2
160
6.1
180
6.6
7.4
200
224
8.2
250
9.0
10.2
280
11.7
315
13.6
FKRS-EU with spring return actuator: weight +1.8 kg.
Dimensions [mm] of installation opening/wall face frame
Nominal size
ØD2¹
□B2
100
125
130
200
150
155
225
160
180
250
190
260
180
210
280
200
224
230
300
250
254
324
280
350
280
310
380
315
345
415
¹ Tolerance limits: –20 mm/+2 mm
FKRS-EU with wall face frame WA
W ̟ 100
~ 102
ϯB
① Wall face frame
K4 – 1.1 – 124
2
‫ݢ‬
‫ݣ‬
͌D2
② Solid wall
06/2015 – DE/en
Accessories 2
Cover grille
Description
Cover grille with extension
piece for FKRS-EU
/
/
/
/
/
A0
0A
AS
SA
AA
/
/
/
/
/
‫݌‬
FKRS-EU
Application
– If only one end is to be ducted on site,
the other end must have a cover grille
– To ensure that the open damper blade
is contained within the damper casing
on the installation side, an extension piece
is required for nominal size 224 and above
– Fire damper, cover grille and, if applicable,
extension piece are factory assembled
to form a unit
– The free area of the cover grille is approx. 70%
– Fire dampers with cover grilles or flexible
connectors are supplied without lip seals
– Cover grilles are also available separately
– Cover grilles both ends may be used
in Germany only for air transfer dampers
with general building inspectorate licence,
e.g. Z-19.18-2128
Materials and surfaces
– Cover grilles made of galvanised sheet steel
(and powder-coated silver grey, RAL 7001,
when used with powder-coated (1)
and stainless steel (2) dampers)
– Extension piece same as casing
1
Note
For more information please refer
to the installation and operating manual.
Cover grille for FKRS-EU
Operating side
Installation side
Cover grille
–
Cover grille
Flexible connector
Cover grille
Order code
–
Cover grille
Flexible connector
Cover grille
Cover grille
Order code detail
Note: AA for FKRS-EU as air transfer damper
The distance »a«
between the open damper
blade and the spigot
should be 50 mm.
Cover grille
A0
0A
AS
SA
AA
‫ݢ‬
‫ݢ‬
‫ݣ‬
① Cover grille, mesh aperture 10 mm × 10 mm, wire width 2 mm; grille thickness approx. 1 mm
② Extension piece
Cover grille
L = 400
150
‫ݢ‬
‫ݢ‬
‫ݣ‬
200
① Cover grille, mesh aperture 10 mm × 10 mm, wire width 2 mm; grille thickness approx. 1 mm
② Extension piece from nominal size 224
06/2015 – DE/en
K4 – 1.1 – 125
Accessories 2
Flexible connector
1
Description
Flexible connector
for FKRS-EU
/
/
/
/
/
S0
0S
SS
SA
AS
/
/
/
/
/
‫݌‬
Order code detail
FKRS-EU
Application
– Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire damper in the event of a fire.
– For information on how to limit such loads
please refer to the guideline regarding fire
protection requirements on ventilation systems
(Lüftungsanlagen-Richtlinie, LüAR)
– As ducts may expand and walls may become
deformed in the event of a fire, we recommend
for the following applications using flexible
connectors when connecting the fire damper
to rigid ducts: installation into lightweight
partition walls, into lightweight shaft walls,
and installation with a fire batt
– Flexible connectors should be installed
in such a way that both ends can compensate
both tension and compression
– Flexible ducts can be used as an alternative
– To ensure that the open damper blade
is contained within the damper casing
on the installation side, an extension piece
is required for nominal size 224 and above
– Flexible connectors are supplied separately
and can be fixed with clamps,
for example (by others)
– Flexible connectors
are also available separately
Materials and surfaces
– Flexible connectors
made of fibre-reinforced plastic
– Fire resistance properties to 4102; B2
Note
For more information please refer
to the installation and operating manual.
Flexible connector for FKRS-EU
Operating side
Flexible connector
–
Flexible connector
Flexible connector
Cover grille
Installation side
Order code
–
Flexible connector
Flexible connector
Cover grille
Flexible connector
S0
0S
SS
SA
AS
Flexible connector
‫ݢ‬
‫ݢ‬
‫ݣ‬
① Flexible connector
K4 – 1.1 – 126
② Extension piece
06/2015 – DE/en
Accessories 2
Flexible connector
The distance »a« between
the open damper blade
and the flexible connector
should be 50 mm.
FKRS-EU
Up to nominal size 200/from nominal size 224
~ 190*
1
~ 190*
L = 400
‫ݢ‬
‫ݢ‬
215
215
L = 400
~ 190
~ 340
‫ݢ‬
‫ݢ‬
‫ݣ‬
215
~ 390
① Flexible connector
② Extension piece
* flexible length ≥ 100 mm when installed
Flexible connector
͌
͌
215
~ 200*
* flexible length ≥ 100 mm when installed
06/2015 – DE/en
K4 – 1.1 – 127
Accessories 2
Extension piece
Circular extension piece
for FKRS-EU
Application
– Fire dampers from nominal size 224
ordered with flexible connector or cover grille
are supplied including extension piece
on the installation side
– Extension pieces are also available separately
Materials and surfaces
– Extension pieces
made of galvanised sheet steel
(and powder-coated silver grey, RAL 7001,
when used with powder-coated (1)
and stainless steel (2) dampers)
Installation and commissioning
– The distance »a« between the open damper
blade and the cover grille or circular spigot
should be 50 mm
Note
For more information please refer
to the installation and operating manual.
Extension piece
͌ˣ
54
͌
1
Description
FKRS-EU
50
200
K4 – 1.1 – 128
06/2015 – DE/en
Attachments
Limit switch
FKRS-EU
Description
FKRS-EU with limit switch
– Limit switches with volt-free contacts
enable the damper blade position indication.
– Up to the maximum switch rating,
relays or indicator lights for fire alarm systems
can be used
– One limit switch each is required for damper
blade positions OPEN and CLOSED
– Fire dampers with a fusible link
can be supplied with one or two limit switches;
the switches can also be fitted later
Limit switch
Note
For more information please refer
to the installation and operating manual.
For detailed information
on limit switches
see Chapter 1.2
/ Z01
/ Z02
/ Z03
‫ݍ‬
Attachments
1
Order code
Limit switch for damper blade position CLOSED
Z01
Limit switch for damper blade position OPEN
Z02
Limit switches for damper blade positions CLOSED and OPEN
Z03
Order code detail
06/2015 – DE/en
K4 – 1.1 – 129
Attachments
Spring return actuator
1
Description
FKRS-EU with
spring return actuator
For detailed information
on the spring return
actuator see Chapter 1.2
FKRS-EU
FKRS-EU with spring return actuator
– An open/close actuator allows for the remote
control of the fire damper and/or release
by a suitable duct smoke detector
– If the supply voltage fails, or with thermoelectric
release, the damper closes (power off to close)
– Fire dampers with spring return actuators
can be functionally checked
OPEN/CLOSED/OPEN
– Ambient temperature of the actuator,
normal operation –30 to 50 °C
– Two integral limit switches with volt-free
contacts enable the damper blade position
indication (OPEN and CLOSED)
– BLF24-T-ST TR: The connecting cables
of the spring return actuator are fitted
with plugs, which ensure quick and easy
connection to the TROX AS-i bus system
– A conversion kit is available for adding
an actuator to the standard construction
– In case of conventional wiring (Z45) the voltage
must be supplied by a safety transformer
Note
For more information please refer
to the installation and operating manual.
/ Z43
/ Z45
‫ݍ‬
Attachments
BLF230-T TR
BLF24-T-ST TR
Order code
Z43
Z45
Bestellschlüsseldetail
K4 – 1.1 – 130
06/2015 – DE/en
Attachments
TROXNETCOM
Description
FKRS-EU with
TROXNETCOM module
For detailed information
on TROXNETCOM
see Chapter 1.2
/
/
/
/
ZL06
ZL07
ZL08
ZA07
‫ݍ‬
FKRS-EU
FKRS-EU with spring return actuator
and TROXNETCOM
– Fire dampers with spring return actuator
BLF24-T-ST TR and the modules shown
here as attachments form a functional
unit ready for automatic operation.
– The components
are factory assembled and wired
– It enables the integration of different
components (modules) into a network
regardless of the manufacturer
– The modules control actuators and/or
receive signals from sensors
Application
LON:
– LON indicates a standard local operating
network system with manufacturer-independent
communications
– Data transmission
is based on a uniform protocol
– LonMark defines standards
to ensure product compatibility
– Only the bus line and the supply
voltage remain to be connected by others
– LON-WA1/B2: To provide the control
input signal for up to two fire dampers
– LON-WA1/B2-AD: Connection box
for connecting the second fire damper with
24 V DC supply voltage to LON-WA1/B2-AD
– LON-WA1/B2-AD230: Connection box
with integral 230/24 V power supply unit
for the connection of a second actuator-driven
24 V fire damper to LON-WA1/B2
Attachments
LON-WA1/B2 and BLF24-T-ST TR
LON-WA1/B2-AD and BLF24-T-ST TR
LON-WA1/B2-AD230 and BLF24-T-ST TR
AS-EM and BLF24-T-ST TR
AS-i:
– The AS interface is a global
standard bus system according
to EN 50295 and IEC 62026-2
– The module sends the control signals
between the spring return actuator
and the controller and power unit
– This allows for controlling the actuator
and monitoring of its running time during
functional testing
– The voltage (24 V DC) for the module
and the actuator is supplied via
the two-wire AS-i flat cable
– Function display: operation, 4 inputs, 2 outputs
Note
For more information please refer
to the installation and operating manual.
Order code
ZL06
ZL07
ZL08
ZA07
Order code detail
06/2015 – DE/en
K4 – 1.1 – 131
1
Attachments
Duct smoke detectors
1
Description
Duct smoke detector
RM-O-3-D
FKRS-EU
General
– To prevent smoke from spreading in buildings,
it is extremely important that the smoke
is detected at an early stage.
– Duct smoke detectors that operate
on the principle of light scattering detect
the smoke regardless of its temperature
so that the fire dampers can be closed before
the release temperature of 72 °C is reached
– If the air contains suspended particles,
as is the case with smoke, beams of light
are deflected off these. A sensor (photodiode),
which does not receive light in clear air,
is illuminated by the scattered light.
– The fire damper or smoke protection damper
blade is released when the brightness of the
scattered light exceeds a certain threshold
Application
RM-O-3-D:
– Duct smoke detector for fire dampers
and smoke protection dampers
– General building inspectorate
licence Z-78.6-125
– For airflow velocities from 1 – 20 m/s
– Independent of the airflow direction
– Supply voltage 230 V AC, 50/60 Hz or 24 V DC
with voltage monitoring module (VWM)
(upon request)
– Volt-free signal and alarm relays
– Integral signal lamps
– Contamination level indicator
– Automatic adjustment of alarm threshold
– Long service life
– Temperature range 0 – 60 °C
RM-O-VS-D:
– Duct smoke detector for fire dampers
and smoke protection dampers
– General building inspectorate
licence Z-78.6-67
– For airflow velocities from 1 – 20 m/s
– Independent of the airflow direction
– Airflow monitoring with warning
for lower limit 2 m/s
– Supply voltage 230 V AC, 50/60 Hz
– Volt-free signal and alarm relays
– Integral signal lamps
– Contamination level indicator
– Automatic adjustment of alarm threshold
– Long service life
– Temperature range 0 – 60 °C
Duct smoke detector
RM-O-VS-D
For detailed information
on the duct smoke
detector see Chapter 1.2
Note
For more information please refer
to the installation and operating manual.
Attachments
Smoke detector
Order code
RM-O-3-D
RM-O-VS-D
Duct smoke detectors are attachments and to be ordered separately.
K4 – 1.1 – 132
06/2015 – DE/en
Fire dampers
Quick sizing
FKRS-EU
Volume flow rate at differential pressure Δpst < 35 Pa
LWA [dB(A)]
25
35
45
Nominal size
mm
100
125
150
160
180
200
224
250
280
315
25
35
1
45

l/s
22
40
70
80
105
140
170
215
280
360
m³/h
35
65
105
125
165
210
245
315
405
525
50
90
150
180
235
295
345
445
570
735
79
144
252
288
388
504
612
774
1008
1296
126
234
378
450
587
756
882
1134
1458
1890
180
324
540
648
847
1062
1242
1602
2052
2646
The Easy Product Finder allows you to size products using your project-specific data.
You will find the Easy Product Finder on our website.
06/2015 – DE/en
K4 – 1.1 – 133
Fire dampers
Free area and resistance coefficient
1
Nominal size
100
125
150
160
200
224
250
280
315
FKRS-EU
A [m²]
ζ
0.005
0.009
0.013
0.016
0.025
0.032
0.040
0.052
0.067
1.71
1.08
0.76
0.67
0.44
0.56
0.45
0.36
0.28
Maximum upstream velocity: ≤ 8 m/s for standard construction, ≤ 10 m/s for construction with spring return actuator.
K4 – 1.1 – 134
06/2015 – DE/en
Fire dampers
Dimensions and weight – FKRS-EU
Dimensions
FKRS-EU
FKRS-EU with fusible link
1
L = 400
270
220
~ 180
50
50
~ 75
FKRS-EU with fusible link
Ø DN
‫ݢ‬
① Keep clear to provide access to the release mechanism
Dimensions [mm] / Weight [kg]
Nominal size
ØD
Weight
06/2015 – DE/en
100
99
1.3
125
124
1.6
150
149
1.8
160
159
2
180
179
2.3
200
199
2.5
224
223
2.7
250
249
3.3
280
279
3.8
315
314
4.4
K4 – 1.1 – 135
Fire dampers
Dimensions and weight – FKRS-EU/.../Z4*
FKRS-EU with spring return actuator
L = 400
270
220
~ 190
50
50
~ 115
‫ݢ‬
FKRS-EU with
spring return actuator
Ø DN
1
Dimensions
FKRS-EU
① Keep clear to provide access to the release mechanism
Dimensions [mm] / Weight [kg]
Nominal size
ØD
Weight
K4 – 1.1 – 136
100
99
3.1
125
124
3.4
150
149
3.6
160
159
3.7
180
179
4.0
200
199
4.2
224
250
223
4.5
249
5
280
279
5.5
315
314
6.2
06/2015 – DE/en
Fire dampers
Specification text
Description
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.
Circular fire dampers for the isolation
of duct penetrations between fire compartments.
Tested for fire resistance properties to EN 1366-2,
with CE marking and declaration of performance
according to the Construction Products
Regulation. Ready-for-operation unit,
which includes a fire-resistant damper blade
and a release mechanism. For mortar-based
installation and dry mortarless installation
into solid walls and ceiling slabs, mortar-based
installation into non-load-bearing solid walls
with flexible ceiling joint, mortar-based and dry
mortarless installation into lightweight partition
walls with cladding on both sides, lightweight fire
walls and lightweight shaft walls, and dry
mortarless installation on the face of solid walls.
For dry mortarless installation in lightweight
partition walls with metal support structure and
flexible ceiling joint; for dry mortarless installation
in solid walls and ceiling slabs when using a fire
batt; in lightweight partition walls with metal
support structure and cladding on both sides.
Casing length 400 mm, for the connection
to ducts made of non-combustible or combustible
materials. Thermal or thermoelectric release
at 72 °C or 95 °C (warm air ventilation systems).
Constructions with spring return actuator for
opening and closing the fire damper independent
of the nominal size and even while the ventilation
system is running, e.g. for a functional test.
Simple construction for dry mortarless installation
with installation kit: ER, TQ, GL, WA
Special characteristics
– Declaration of performance according
to Construction Products Regulation
– Classification to EN 13501-3,
up to EI 120 (ve, ho, i ↔ o) S
– Building inspectorate licence Z-56.4212-991
for fire resistance properties
– Complies with the requirements of EN 15650
– Tested to EN 1366-2
for fire resistance properties
– Hygiene complies with VDI 6022 part 1
(07/2011), VDI 3803 (10/2002), DIN 1946
part 4 (12/2008), and EN 13779 (09/2007)
– Corrosion protection according to EN 15650
in connection with EN 60068-2-52
– Closed blade air leakage to EN 1751, class 3
– Casing air leakage to EN 1751, class C
– Low differential pressure
and sound power level
– Any airflow direction
– Integration into the central BMS
with TROXNETCOM
06/2015 – DE/en
FKRS-EU
Materials and surfaces
Casing:
– Galvanised sheet steel
– Galvanised sheet steel,
powder-coated RAL 7001
– Stainless steel 1.4301
1
Damper blade:
– Special insulation material
– Special insulation material with coating
Other components:
– Damper blade shaft made of galvanised steel
or stainless steel
– Plastic bearings
– Seals of elastomer
The construction variants with stainless steel
or powder-coated casing meet even more critical
requirements for corrosion protection.
Detailed listing on request.
Technical data
– Nominal sizes: 100 to 315 mm
– Casing length: 400 mm
– Volume flow rate range:
Up to 770 l/s or 2770 m³/h
– Differential pressure: up to 1500 Pa
– Operating temperature: at least 0 – 50 °C **
– Release temperature 72 °C or 95 °C
(for use in warm air ventilation systems)
– Upstream velocity:
≤ 8 m/s with standard construction;
≤ 10 m/s * with spring return actuator
Note:
* Data applies to uniform upstream
and downstream conditions for the fire damper
** Temperatures may differ for units
with attachments
Sizing data
–  ______________________________ [m³/h]
– Δpst ______________________________ [Pa]
– LWA Air-regenerated noise __________ [dB(A)]
K4 – 1.1 – 137
Fire dampers
Specification text
1
Order options
 Type
FKRS-EU Fire damper
 Construction
No entry: standard construction
1
Powder-coated casing
2¹
Stainless steel casing
7
Coated damper blade
1 – 7 Powder-coated casing
and coated damper blade
2 – 7¹ Stainless steel casing
and coated damper blade
W²
With fusible link 95 °C
(only for use in warm
air ventilation systems)
 Country of destination
DE
Germany
Other destination countries
upon request
FKRS-EU
 Accessories 1
No entry: none
ER
Circular installation block
TQ
Square installation kit
WA
Wall face frame
GL
Installation kit for flexible ceiling joint
 Accessories 2
No entry: none
S0 – AS
 Attachments
Z00 – ZL08
¹ Only up to DN 200 when a fire batt system
is used
² W can be combined with all constructions
listed under 
 Nominal size [mm]
100
125
150
160
180
200
224
250
280
315
K4 – 1.1 – 138
06/2015 – DE/en
1.3 –
X X Basic
information and nomenclaturetestregistrierung
Fire dampers
1
Basic information
and nomenclature
■ Product selection
■ Principal dimensions
■ Nomenclature
■ Colour codes according to IEC 60757
■ Sizing
06/2015 – DE/en
K4 – 1.3 – 1
Fire dampers
Basic information and nomenclature
1
Product selection
Fire dampers
Usage
Type
FK-EU
Installation
location
Construction/
building material
Minimum
thickness
FKS-EU
Mortar-based
installation
Dry
mortarless
installation
peri- partimeter ally⁵
Fire
batt
Installation
kit²
mm
In solid walls
100
EI 90 S EI 90 S EI 120 S EI 90 S
In solid walls
with movement joint
Walls/gross
density ≥ 500 kg/m³
100
EI 90 S
–
–
On the face
of solid walls
Adjacent
to solid walls¹
Remote
from solid walls¹
Walls/gross
density ≥ 500 kg/m³
Walls/gross
density ≥ 500 kg/m³
Walls/gross
density ≥ 500 kg/m³
Ceiling slabs/gross
density ≥ 600 kg/m³
Ceiling slabs/gross
density ≥ 600 kg/m³
100
–
–
100
–
100
–
125
EI 90 S
150
EI 90 S
Ceiling slabs/gross
density ≥ 600 kg/m³
125
EI 90 S
–
Lightweight
partition walls
with metal
support structure
and cladding
on both sides
Lightweight
partition walls
100
EI 90 S
–
Lightweight
partition walls
with metal
support structure
and cladding
on both sides,
flexible ceiling joint¹
Lightweight
partition walls
100
–
–
–
Fire walls
115
EI 90 S
–
Shaft walls
90
–
Shaft walls
40 or 50⁴
In solid ceiling slabs,
with concrete base
Fire walls
with metal
support structure
and cladding
on both sides
Lightweight
partition walls
with metal
support structure
and cladding
on one side
Lightweight
partition walls
without metal
support structure
but with cladding
on one side
In self supporting
fire-resistant
suspended ceilings
Tile ceilings,
screw-fixed and primed
Lay-in
ceiling tiles made
of panel materials
Metal ceilings
perimeter
Installation
Installation
perimeter
kit²
kit²
Fire resistance class
Walls/gross
density ≥ 500 kg/m³
In solid ceiling slabs
FKR-EU
MortarDry
MortarDry
based
mortarless
based
mortarless
installation installation installation installation
EI 120 S
EI 90 S
EI 120 S
–
–
–
–
–
–
–
EI 90 S
–
–
–
–
–
–
EI 90 S
–
–
–
–
–
–
EI 90 S
–
–
–
–
–
–
–
–
EI 120 S
EI 90 S
EI 120 S
–
EI 90 S
–
EI 90 S
–
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
–
–
–
–
–
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
–
–
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
–
–
–
EI 90 S
–
–
EI 90 S
EI 90 S
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
EI 120 S
–
–
–
EI 120 S EI 90 S
¹ Not for FK-EU as air transfer damper
² Installation kit for the selected installation situation
³ For ØDN 100 to 200 in lightweight partition wall with metal support structure and mineral wool
⁴ 50 only for FKR-EU
⁵ Additional mineral wool
K4 – 1.3 – 2
06/2015 – DE/en
Fire dampers
Basic information and nomenclature
Product selection
Fire dampers
1
Usage
Type
FKRS-EU
Installation
location
Minimum
Construction/building thickness
material
Mortar-based
installation
perimeter
FV-EU
Dry mortarless
installation
Fire batt
mm
Installation kit²
KA-EU
FVZK30
KU-K30
Mortar-based installation
perimeter
Mortarbased
installation
Dry
Instal- mortarless
lation installation
kit
Fire resistance class
In solid walls
Walls/gross
density ≥ 500 kg/m³
100
EI 120 S
EI 120 S³,
EI 90 S
EI 90 S
In solid walls
with movement joint
Walls/gross
density ≥ 500 kg/m³
100
–
–
On the face
of solid walls
Adjacent
to solid walls¹
Remote
from solid walls¹
Walls/gross
density ≥ 500 kg/m³
Walls/gross
density ≥ 500 kg/m³
Walls/gross
density ≥ 500 kg/m³
Ceiling slabs/gross
density ≥ 600 kg/m³
Ceiling slabs/gross
density ≥ 600 kg/m³
100
EI 90 S
100
EI 120 S
K90
–
–
–
–
–
–
–
–
EI 90 S
–
–
–
–
–
–
–
–
–
–
–
100
–
–
–
–
–
–
–
125
–
–
–
–
–
–
–
150
EI 120 S
EI 120 S
K90
–
–
Ceiling slabs/gross
density ≥ 600 kg/m³
125
–
–
–
–
–
Lightweight
partition walls
with metal
support structure
and cladding
on both sides
Lightweight
partition walls
100
EI 120 S³,
EI 90 S
K90
–
–
Lightweight
partition walls
with metal
support structure
and cladding
on both sides,
flexible ceiling joint¹
Lightweight
partition walls
100
–
–
EI 90 S
–
–
–
–
Fire walls
115
EI 90 S
–
EI 90 S
–
K90
–
–
Shaft walls
90
EI 90 S
–
EI 90 S
–
–
–
–
Shaft walls
40 or 50⁴
–
–
–
–
–
–
–
–
–
–
–
–
–
K30-U
K30-U
–
–
–
–
–
–
K30-U
K30-U
–
–
–
–
–
–
K30-U
K30-U
In solid ceiling slabs
In solid ceiling slabs,
with concrete base
Fire walls
with metal
support structure
and cladding
on both sides
Lightweight
partition walls
with metal
support structure
and cladding
on one side
Lightweight
partition walls
without metal
support structure
but with cladding
on one side
In self supporting
fire-resistant
suspended ceilings
Tile ceilings,
screw-fixed and primed
Lay-in ceiling tiles
made of panel materials
Metal ceilings
EI 120 S³,
EI 90 S
EI 90 S
–
–
EI 120 S³, EI 120 S³,
EI 120 S
EI 90 S
EI 90 S
¹ Not for FK-EU as air transfer damper
² Installation kit for the selected installation situation
³ For ØDN 100 to 200 in lightweight partition wall with metal support structure and mineral wool
⁴ 50 only for FKR-EU
⁵ Additional mineral wool
06/2015 – DE/en
K4 – 1.3 – 3
Fire dampers
Basic information and nomenclature
1
Principal dimensions
Nomenclature
Rectangular fire dampers
Circular fire dampers
B [mm]
Width of the fire damper
Nominal size [mm]
Diameter of the fire damper
H [mm]
Height of the fire damper
L [mm]
Length of the fire damper
 [m³/h] and [l/s]
Volume flow rate
Δpst [Pa]
Static differential pressure
LWA [dB(A)]
A-weighted sound power level
of air-regenerated noise for the fire damper
v [m/s]
Airflow velocity based on
the upstream cross section (B × H or diameter)
A [m²]
Free area
K
Correction value
ζ
Resistance coefficient (fully ducted)
Wiring
Colour codes according to IEC 60757
Code
BK
BN
RD
OG
YE
GN
BU
Sizing with the help
of this catalogue
Colour codes according to IEC 60757
Colour
Code
black
brown
red
orange
yellow
green
blue
VT
GY
WH
PK
TQ
GNYE
Colour
violet
grey
white
pink
turquoise
green-yellow
This catalogue provides convenient
quick sizing tables for fire dampers.
The volume flow rates for all available
dimensions and nominal sizes are provided
based on a particular differential pressure.
Sizing data for other volume flow rates
and differential pressures can be determined
quickly and precisely using
the Easy Product Finder design programme.
Easy Product Finder
The Easy Product Finder
allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.
K4 – 1.3 – 4
06/2015 – DE/en