xpr MTPADP-MHWO Keypad Installation Guide
xpr MTPADP-MHWO is a versatile keypad with an integrated reader that combines advanced security features with user-friendly operation. It supports a wide range of credentials, including EM4100 or HID Compatible, HID iClass CSN, NTAG, Mifare, and ISO 15693 cards. With its ability to read cards up to 6 cm away, it offers convenient and efficient access control.
Advertisement
Advertisement
MTPADP-MHWO
MTPADPBK-MHWO, MTPADPS-MHWO
EN
Keypad with integrated reader
INSTALLER’S MANUAL
SPECIFICATIONS
Technology: Keypad + RFID (125 KHZ, 13.5 MHz)
Interface: Wiegand, OSDP, WS4, Custom RS-485 (Factory default: Wiegand 34)
Supported credentials: EM4100 or HID Compatible , HID iClass CSN, NTAG, Mifare (Classic, Desfire, Plus, Ultralight), ISO 15693
Card encryption: Desfire EV1, EV2, EV3
Read range: Up to 6 cm
Power supply: 9 - 14 VDC, 150 mA
Sound Indicator: Internal buzzer
LED Indicators: Red, Green and Orange (Red + Green)
Built-in Micro USB connector for protocol selection, configuration and firmware update
Environmental rating: Outdoor, IP65
Operating temperature: -20°C to +50°C
Operating humidity: 5% - 95% relative humidity, non-condensing
Mounting: Surface mount
Panel connection: Terminal
Dimensions (mm): 92 x 51 x 27
MOUNTING
Rubber gasket
5 mm
3 (3 x 30mm)
MOUNTING WITH MT-SPACER
1 (M3 x 8mm)
Front Back
Bus for the readers
6 mm
Ferrite Core
2 (4 x 30mm) 3 (M3 x 8mm) 1 (M3 x 8mm)
Wrap the wires around the ferrite core (1 turn).
The ferrite core is provided with the kit and it is used to reduce the EMI.
TERMINAL BLOCKS AND DIPSWITCH
Micro USB
1. OSDP mode: SCBK reset
WS4 mode: Reader address
2. RS-485 120 Ohm termination
ON=0 OFF=1 www.xprgroup.com
Rev. 1.14 - 28.09.2022
1
TERMINALS AND DESCRIPTION
TERMINALS
A
B
D0
D1
LG
LR
BUZZ
+12V
GND
T
T
DIP SWITCH
SW 1
SW 2
CABLING
Max length
Cable
DESCRIPTION OSDP CONFIGURATION WS4 CONFIGURATION
RS-485 line RS-485 A (+) RS-485 A (+)
RS-485 line RS-485 B (-) RS-485 B (-)
Output
Output
Input
Input
Input x x
Input 1
(Dry contact to GND only)
Input 1
(Dry contact to GND only) x x x x x x
Power Supply
Ground
Tamper
Tamper x
(Tamper state is reported by
RS-485) x x
(Tamper state is reported by
RS-485) x
DESCRIPTION OSDP CONFIGURATION WS4 CONFIGURATION
WIEGAND
CONFIGURATION x x
D0
D1
Green LED input
Red LED input
Buzzer input
WIEGAND
CONFIGURATION
Setup
SCBK Reset: Power the reader. Set DIP Switch 1 to ON and in the less than
5 sec set it back to OFF position
The readers for Doors 1.0 and 2.0 must be at address
0 and those for Doors 1.1 and 2.1 at address 1. For doors equipped with 2 readers, one must be at address 0 and the other at address 1.
RS-485 120 OHM termination
DESCRIPTION OSDP CONFIGURATION WS4 CONFIGURATION
Cable Length
Recommended cable type
1200m
Multiconductor cable
2 twisted pair with
shielding
80m
Multiconductor cable
2 twisted pair with shielding x x
WIEGAND
CONFIGURATION
150m
Untwisted, shielded, 0.22 mm 2 min.
For longer distance above 20 m use larger diameter.
CUSTOM RS-485
CONFIGURATION
RS-485 A (+)
RS-485 B (-) x x
Green LED input
Red LED input
Buzzer input
CUSTOM RS-485
CONFIGURATION x
CUSTOM RS-485
CONFIGURATION
1200m
Multiconductor cable 2 twisted pair with shielding
SIGNALISATION DESCRIPTION OSDP CONFIGURATION WS4 CONFIGURATION WIEGAND
CONFIGURATION
CUSTOM RS-485
CONFIGURATION
Reader
ON-LIne
Reader
OFF-LIne
Reader is in communication with controler
Reader lost comunication with controler
Managed by Controller
Red LED Blinks
Managed by Controller
Red LED Blinks fast
Managed by
Controller x
Managed by
Controller x
SOFTWARE SETTINGS
XPR Toolbox is software for settings and firmware update of the reader. XPR Toolbox can be downloaded from a https://software.xprgroup.com/.
To setup the reader or update the firmware, run the XPR Toolbox and select ”Generation 2” and ”MTPADP-MHWO” and click on “Open” tab. Follow the instruction in the software to set up or update firmware. Connect the reader to PC using Micro USB connector. No additional power for the reader is required. If the reader is used with EWS Controller, reader setting must be done by PROS-CS software.
CARD ENCRYPTION
Cards encryption can be used with Mifare Desfire cards. Encryption provide higher level of security where card is accepted by its encrypted content instead of built in card serial number.
For OSDP, Wiegand and Custom RS-485 modes, reader should be programmed with the XPR Toolbox software to use encryption. Cards can be encrypted using application “XPR Card encoder” and desktop reader (PROX-USB). This application is installed together with XPR Toolbox software.
When used with WS4 controller, encryption is managed by the WS4 controller.
When used with EWS controller, encryption, reader setting and cards are managed by PROS CS software.
www.xprgroup.com
2
ACCESSORIES (Optional)
• MT-SPACER
16.50
Braking Wall for Cable
SECTION
B-B
A
Braking Wall for Cable
3(M3x3mm)
2(3mm x 4mm)
B B
12
C
R4.10
R2.4
0
8.15
33.40
53.42
19
A
TRUE R3.99
SECTION
C-C
C
Braking Wall for Cable
Braking Wall for Cable
• MC-MINI
SECTION
A-A
9.04
Breaking Wall for cable
• USP
*Important: These accessories are not included with the reader!
This product herewith complies with requirements of EMC directive 2014/30/EU, Radio Equipment Directive 2014/53/EU. In addition it complies with RoHS2 directive EN50581:2012 and RoHS3 Directive 2015/863/EU.
www.xprgroup.com
3