Display - Siemens Industry Online Support Portals

Display - Siemens Industry Online Support Portals

SCALANCE XB-200

SIMATIC NET

Industrial Ethernet switches

SCALANCE XB-200

Operating Instructions

09/2015

C79000-G8976-C359-03

Legal information

Warning notice system

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION indicates that minor personal injury can result if proper precautions are not taken.

NOTICE indicates that property damage can result if proper precautions are not taken.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel

The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions.

Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products

Note the following:

WARNING

Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks

All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability

We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG

Division Process Industries and Drives

Postfach 48 48

90026 NÜRNBERG

GERMANY

C79000-G8976-C359-03

Ⓟ 09/2015 Subject to change

Copyright © Siemens AG 2015.

All rights reserved

Introduction

Purpose of the Operating Instructions

These operating instructions support you when installing and connecting up devices of the

SCALANCE XB-200 product group.

The configuration and the integration of the devices in a network are not described in these operating instructions.

Validity of the Operating Instructions

These operating instructions apply to the following devices:

● SCALANCE XB208

● SCALANCE XB205-3 (SC)

● SCALANCE XB205-3LD (SC)

● SCALANCE XB205-3

● SCALANCE XB216

● SCALANCE XB213-3 (SC)

● SCALANCE XB213-3LD (SC)

● SCALANCE XB213-3

Unless mentioned otherwise, the descriptions in these operating instructions refer to all devices of the SCALANCE XB-200 product group named above in the section on validity.

There are two variants of each device, refer to the section "Product overview (Page 11)".

Designations used

Classification

Product line

Product group

Device

Description

The product line includes all devices and variants of all product groups.

If information applies to all product groups within the product line, the term SCALANCE X-200 is used.

If information applies to all devices and variants of a product group, the term SCALANCE XB-200 is used.

If information relates to a specific device, the device name is used.

Terms used

SCALANCE X-200

SCALANCE XB-200 e.g. SCALANCE XB205-3

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

3

4

Introduction

Documentation on configuration

You will find detailed information on configuring the devices in the following configuration manuals:

● SCALANCE XB-200 Web Based Management

● SCALANCE XB-200 Command Line Interface

You will find the configuration manuals here:

● on the data medium that ships with some products:

– Product CD / product DVD

– SIMATIC NET Manual Collection

● On the Internet pages of Siemens Industry Online Support.

Further documentation

In the system manuals "Industrial Ethernet / PROFINET Industrial Ethernet" and "Industrial

Ethernet / PROFINET passive network components", you will find information on other

SIMATIC NET products that you can operate along with the devices of this product line in an

Industrial Ethernet network.

There, you will find among other things optical performance data of the communications partner that you require for the installation.

You will find the system manuals here:

● On the data medium that ships with some products:

– Product CD / product DVD

– SIMATIC NET Manual Collection

● On the Internet pages of Siemens Industry Online Support under the following entry IDs:

– 27069465 ( http://support.automation.siemens.com/WW/view/en/27069465 )

Industrial Ethernet / PROFINET Industrial Ethernet System Manual

– 84922825 ( http://support.automation.siemens.com/WW/view/en/84922825 )

Industrial Ethernet / PROFINET - Passive network components System Manual

SIMATIC NET manuals

You will find the SIMATIC NET manuals here:

● On the data medium that ships with some products:

– Product CD / product DVD

– SIMATIC NET Manual Collection

● On the Internet pages of Siemens Industry Online Support

( https://support.industry.siemens.com/cs/ww/en/ps/15247 ).

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Introduction

SIMATIC NET glossary

Explanations of many of the specialist terms used in this documentation can be found in the

SIMATIC NET glossary.

You will find the SIMATIC NET glossary here:

● SIMATIC NET Manual Collection or product DVD

The DVD ships with certain SIMATIC NET products.

● On the Internet under the following address:

50305045 ( http://support.automation.siemens.com/WW/view/en/50305045 )

Catalogs

You will find the order numbers for the Siemens products of relevance here in the following catalogs:

● SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI

● SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog

ST 70

● Industry Mall - catalog and ordering system for automation and drive technology, Online catalog

( https://eb.automation.siemens.com/goos/WelcomePage.aspx?regionUrl=/en&language= en )

You can request the catalogs and additional information from your Siemens representative.

Unpacking and checking

WARNING

Do not use any parts that show evidence of damage

If you use damaged parts, there is no guarantee that the device will function according to the specification.

If you use damaged parts, this can lead to the following problems:

Injury to persons

Loss of the approvals

Violation of the EMC regulations

Damage to the device and other components

Use only undamaged parts.

1.

Make sure that the package is complete.

2.

Check all the parts for transport damage.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

5

Introduction

Security information

Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.

For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit http://www.siemens.com/industrialsecurity .

To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com

.

Trademarks

The following and possibly other names not identified by the registered trademark sign

® registered trademarks of Siemens AG:

are

SIMATIC NET, SCALANCE, C-PLUG, OLM

6

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Table of contents

1

2

3

4

5

6

Introduction ............................................................................................................................................. 3

Safety notices ......................................................................................................................................... 9

Description of the device ....................................................................................................................... 11

2.1

Product overview .................................................................................................................... 11

2.2

2.2.1

2.2.2

2.2.3

Device views ........................................................................................................................... 13

Device view of a SCALANCE XB208 ..................................................................................... 13

Device view of a SCALANCE XB205-3 .................................................................................. 14

Device view of a SCALANCE XB213-3 .................................................................................. 15

2.3

2.4

RESET button ......................................................................................................................... 16

LED display ............................................................................................................................. 18

Installation ............................................................................................................................................ 19

3.1

Safety notices for installation .................................................................................................. 19

3.2

Mounting on DIN rails ............................................................................................................. 21

Connecting up ....................................................................................................................................... 23

4.1

4.2

Safety when connecting up ..................................................................................................... 23

Power supply .......................................................................................................................... 25

4.3

4.4

Serial interface ........................................................................................................................ 27

Functional ground ................................................................................................................... 28

Upkeep and maintenance ..................................................................................................................... 29

5.1

Downloading new firmware using TFTP without WBM and CLI ............................................. 29

6.3

6.4

6.5

6.6

5.2

Restoring the factory settings ................................................................................................. 31

Technical specifications ........................................................................................................................ 33

6.1

6.2

Technical specifications of the SCALANCE XB208 ............................................................... 33

Technical specifications of the SCALANCE XB205-3 (SC) .................................................... 35

Technical specifications of the SCALANCE XB205-3LD (SC) ............................................... 37

Technical specifications of the SCALANCE XB205-3 ............................................................ 39

Technical specifications of the SCALANCE XB216 ............................................................... 41

Technical specifications of the SCALANCE XB213-3 (SC) .................................................... 42

6.7

6.8

6.9

6.10

Technical specifications of the SCALANCE XB213-3LD (SC) ............................................... 44

Technical specifications of the SCALANCE XB213-3 ............................................................ 46

Cable lengths .......................................................................................................................... 48

Switching properties ................................................................................................................ 49

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

7

Table of contents

7

A

Dimension drawings .............................................................................................................................. 51

Approvals ............................................................................................................................................. 55

Index .................................................................................................................................................... 61

8

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Safety notices

Read the safety notices

Note the following safety notices. These relate to the entire working life of the device.

You should also read the safety notices relating to handling in the individual sections, particularly in the sections "Installation" and "Connecting up".

1

Safety notices on use in hazardous areas

General safety notices relating to protection against explosion

WARNING

EXPLOSION HAZARD

DO NOT OPEN WHEN ENERGIZED.

Safety notices when using the device according to Hazardous Locations (HazLoc)

If you use the device under HazLoc conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion:

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or nonhazardous locations only.

This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

9

Safety notices

10

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Description of the device

2

2.1

Product overview

Article numbers

There are two variants of each device with different article numbers. The two variants differ only in their factory settings. All other properties are identical.

Device Description

SCALANCE XB208 8 x 10/100 Mbps RJ-45 ports

SCALANCE XB205-3 (SC) 5 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps SC ports, multimode fiberoptic cable

SCALANCE XB205-3LD

(SC)

5 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps SC ports, single mode fiber-optic cable

SCALANCE XB205-3 5 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps ST ports, multimode fiberoptic cable

SCALANCE XB216 16 x 10/100 Mbps RJ-45 ports

SCALANCE XB213-3 (SC) 13 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps SC ports, multimode fiberoptic cable

SCALANCE XB213-3LD

(SC)

SCALANCE XB213-3

13 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps SC ports, single mode fiber-optic cable

13 x 10/100 Mbps RJ-45 ports, 3 x

10/100 Mbps ST ports, multimode fiberoptic cable

Article number

(Ethernet/IP)

Article number

(PROFINET)

6GK5 208-0BA00-2TB2 6GK5 208-0BA00-2AB2

6GK5 205-3BD00-2TB2 6GK5 205-3BD00-2AB2

6GK5 205-3BF00-2TB2 6GK5 205-3BF00-2AB2

6GK5 205-3BB00-2TB2 6GK5 205-3BB00-2AB2

6GK5 216-0BA00-2TB2 6GK5 216-0BA00-2AB2

6GK5 213-3BD00-2TB2 6GK5 213-3BD00-2AB2

6GK5 213-3BF00-2TB2 6GK5 213-3BF00-2AB2

6GK5 213-3BB00-2TB2 6GK5 213-3BB00-2AB2

Factory settings

EtherNet/IP variants

● Industrial Ethernet protocol: EtherNet/IP

● Base bridge mode: 802.1Q VLAN Bridge

● Redundancy mechanism: RSTP

● Trust mode: Trust DSCP

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

11

Description of the device

2.1 Product overview

PROFINET variants

● Industrial Ethernet protocol: PROFINET

● Base bridge mode: 802.1D transparent bridge

● Redundancy mechanism: Ring redundancy

● Trust mode: Trust COS

Type designation

The type designation of a SCALANCE XB-200 is made up of several parts that have the following meaning:

Interfaces of devices with optical connectors:

Interface

(SC)

LD (SC)

[-]

Property

10/100 Mbps SC port, multimode fiber-optic cable, up to 5 km

10/100 Mbps SC port, single mode fiber-optic cable, up to 26 km

10/100 Mbps ST port, multimode fiber-optic cable, up to 5 km

Components of the product

The following components are supplied with a SCALANCE XB-200:

● One device

● Two 3-terminal blocks for the power supply

● One product DVD with documentation and software

Accessories

The following accessories are available for SCALANCE XB-200:

Cable

Component

Connecting cable (RJ-

11/RS-232)

Description

Preassembled, serial cable with RJ-11 and RS-232 plug,

Length: 3 m pack of 1

Article number

6GK5 980-3BB00-0AA5

12

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

2.2

2.2.1

Description of the device

2.2 Device views

Device views

Device view of a SCALANCE XB208

The following figure shows an overview of the components of the SCALANCE XB208.

Electrical ports with port LEDs

Power supply with connector for grounding

Serial interface

"RESET" button (rear)

Fault LED

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

13

Description of the device

2.2 Device views

2.2.2

Device view of a SCALANCE XB205-3

The following figure shows an overview of the components of the SCALANCE XB205-3.

Optical ports with port LEDs

Power supply with connector for grounding

Serial interface

Electrical ports with port LEDs

"RESET" button (rear)

Fault LED

14

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

2.2.3

Description of the device

2.2 Device views

Device view of a SCALANCE XB213-3

The following figure shows an overview of the components of the SCALANCE XB213-3.

Optical ports with port LEDs

Power supply with connector for grounding

Serial interface

Electrical ports with port LEDs

"RESET" button (rear)

Fault LED

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

15

Description of the device

2.3 RESET button

2.3

Position

RESET button

The "RESET" button is located on the rear of the SCALANCE XB-200.

Figure 2-1 Position of the "RESET" button, for example on the SCALANCE XB213-3

Resetting the device to factory defaults

Note

Damage to the button

The RESET button is a short-stroke button with only a slight pressure point. To operate the button, you only need a force 2.5 N (approx. 250 g).

To avoid damaging the button press it with little force. Hold the tool you are using, for example, with only two fingers.

Note

If you reset, all the changes you have made will be overwritten by factory defaults.

To reset the device to the factory defaults, follow the steps below:

1.

Press the "RESET" button with only slight force.

A screwdriver for example with following size is suitable:

– Blade thickness 0.8 - 1.8 mm

– Blade width 4.0 - 4.8 mm

2.

Hold down the button for approximately 12 seconds.

After 9 seconds, the fault LED "F" flashes for 3 seconds.

– If you release the button after approximately 12 seconds, the device is restarted and the factory settings are restored.

– If you release the button before the 12 seconds have elapsed, the reset is canceled.

16

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Description of the device

2.3 RESET button

Enabling and disabling the button

Using the WBM and CLI, you can enable or disable the button function.

You will find detailed information about configuration of the button in the Configuration manuals (Page 3):

● SCALANCE XB-200 Web Based Management, section "Button"

● SCALANCE XB-200 Command Line Interface, section "Panel-Button"

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

17

Description of the device

2.4 LED display

2.4

LED display

Fault LED "F"

The fault LED "F" indicates the incorrect functioning of the device.

LED color

-

Green

Red

LED status

Off

Lit

Lit

Meaning

The device is a turned off.

The device has not detected a problem.

The device has detected a problem.

The connected power supply is too low.

Using the WBM and CLI, you can set when the device signals an error and which errors should be signaled.

Port LEDs "P"

The port LEDs indicate the status of the ports.

RJ-45 ports

Each RJ-45 port has 2 integrated LEDs.

The upper green LED shows the status of the link.

LED color

Green

-

LED status

Lit

Off

Meaning link exists

No link exists

The lower yellow LED shows the status of data reception.

LED color

Yellow

-

LED status

Flashing

Off

Meaning

Receiving data at port

Not receiving data at port

SC/ST ports

There is an LED for each SC/ST port.

LED color

Green

-

LED status

Lit

Off

Meaning

Link exists, data reception at port

No link exists

18

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Installation

3

3.1

Safety notices for installation

Safety notices

When installing the device, keep to the safety notices listed below.

WARNING

If a device is operated in an ambient temperature of more than 50 °C, the temperature of the device housing may be higher than 70 °C. The device must therefore be installed so that it is only accessible to service personnel or users that are aware of the reason for restricted access and the required safety measures at an ambient temperature higher than

50 °C.

Safety notices on use in hazardous areas

General safety notices relating to protection against explosion

WARNING

EXPLOSION HAZARD

SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION

2 OR ZONE 2.

WARNING

The device may only be operated in an environment with pollution degree 1 or 2 (see IEC

60664-1).

WARNING

When used in hazardous environments corresponding to Class I, Division 2 or Class I,

Zone 2, the device must be installed in a cabinet or a suitable enclosure.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

19

Installation

3.1 Safety notices for installation

Safety notices for use according to ATEX and IECEx

If you use the device under ATEX or IECEx conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion:

WARNING

To comply with EC Directive 94/9 (ATEX95) or the conditions of IECEx, this enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN 60529.

WARNING

If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air ambient in excess of 60 ℃ , only use cables with admitted maximum operating temperature of at least 80 ℃ .

Further notes

CAUTION

Use only approved components

If you use components and accessories that are not approved for SIMATIC NET devices or their target systems, this may violate the requirements and regulations for safety and electromagnetic compatibility.

Only use components approved for the SIMATIC NET devices.

NOTICE

Warming and premature aging of the IE switch due to direct sunlight

Direct sunlight can heat up the device and can lead to premature aging of the IE switch and its cabling.

Provide suitable shade to protect the IE switch against direct sunlight.

Note

During installation and operation, keep to the installation guidelines and safety notices described in this document and in the system manuals "Industrial Ethernet / PROFINET

Industrial Ethernet" and "Industrial Ethernet / PROFINET passive network components".

You will find information on the system manuals in the section "Introduction (Page 3)", in

"Further documentation".

20

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

3.2

Installation

Mounting on DIN rails

Installation

3.2 Mounting on DIN rails

Figure 3-1 DIN rail mounting

To install the device on a 35 mm DIN rail complying with DIN EN 60715, follow the steps below:

1.

2.

Place the housing guide of the device on the top edge of the DIN rail

.

Press the device down against the DIN rail until the spring catch locks in place

.

3.

Fit the connectors for the power supply, see the section "Power supply (Page 25)".

4.

Insert the terminal blocks into the sockets on the device.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

21

Installation

3.2 Mounting on DIN rails

Removal

Figure 3-2 Removing from a DIN rail

To remove the device from a DIN rail, follow the steps below:

1.

2.

3.

Disconnect all connected cables.

Release the DIN rail locking mechanism by pressing down on the release button

.

Pull the lower part of the device away from the DIN rail

.

22

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Connecting up

4

4.1

Safety when connecting up

Safety notices

When connecting up the device, keep to the safety notices listed below.

WARNING

The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a

Limited Power Source (LPS).

This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1 must be connected to the power supply terminals. The power supply unit for the equipment power supply must comply with NEC Class 2, as described by the National Electrical Code

(r) (ANSI / NFPA 70).

If the equipment is connected to a redundant power supply (two separate power supplies), both must meet these requirements.

NOTICE

Failure of the data traffic due to contamination of optical plug-in connections

Optical sockets and plugs are sensitive to contamination of the end face. Contamination can lead to the failure of the optical transmission network.

Close unused optical sockets and plugs as well as pluggable transceivers and slots with the supplied protective caps.

Remove the protective caps only immediately before you use the plug-in connection.

Safety notices on use in hazardous areas

General safety notices relating to protection against explosion

WARNING

EXPLOSION HAZARD

DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR

COMBUSTIBLE ATMOSPHERE IS PRESENT.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

23

Connecting up

4.1 Safety when connecting up

Safety notices when using the device according to Hazardous Locations (HazLoc)

If you use the device under HazLoc conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion:

WARNING

EXPLOSION HAZARD

DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE

NON-HAZARDOUS.

Safety notices for use according to ATEX and IECEx

If you use the device under ATEX or IECEx conditions you must also keep to the following safety notices in addition to the general safety notices for protection against explosion:

WARNING

Take measures to prevent transient voltage surges of more than 40% of the rated voltage.

This is the case if you only operate devices with SELV (safety extra-low voltage).

WARNING

Safety notice for connecting with a LAN ID (Local Area Network)

A LAN or LAN segment with all the interconnected devices should be contained completely in a single low voltage power distribution in a building. The LAN is designed either for

“Environment A” according to IEEE802.3 or "Environment 0" according to IEC TR 62102.

Do not connect any electrical connectors directly to the telephone network (telephone network voltage) or a WAN (Wide Area Network).

24

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Connecting up

4.2 Power supply

4.2

Power supply

Notes on the power supply

WARNING

Incorrect power supply

Never operate the device with AC voltage or DC voltage higher than 32 V DC.

CAUTION

Damage to the device due to overvoltage

The connector of the external power supply is not protected against strong electromagnetic pulses that can, for example, result from lightning strikes or switching large loads.

One of the tests used to attest the immunity of devices of the SCALANCE CB-200 IE switches to electromagnetic interference is the "surge immunity test" according to

EN61000-4-5. This test requires overvoltage protection for the power supply lines. A suitable device is, for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable protective element.

Manufacturer: DEHN+SOEHNE GmbH+Co.KG, Hans-Dehn-Str.1, Postfach 1640, D92306

Neumarkt, Germany

Operate the SCALANCE XB-200 with suitable overvoltage protection.

Information on the power supply

● The power supply is connected using a 3-pin plug-in terminal block (spring-loaded terminal). The terminal block ships with the device and can also be ordered as a spare part.

● The power supply can be connected redundantly. Both inputs are isolated. There is no distribution of load.

● The power supply is connected over a high resistance with the enclosure to allow an ungrounded set up. The two power inputs are non-floating.

● To wire up the power connector, use a copper cable of category 24-16 AWG or a cable with a cross-section of 0.25 to 1.5 mm².

● To wire up the functional ground, use a copper cable of category 20-16 AWG or a cable with a cross-section of 0.75 to 1.5 mm².

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

25

Connecting up

4.2 Power supply

Position and assignment

Figure 4-1

Contact

L1+

M1

Position of the power supply, for example on the SCALANCE XB213-3

Assignment

24 VDC

Ground

Functional ground

Assignment

24 VDC

Ground

Functional ground

Contact

L2+

M2

26

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Connecting up

4.3 Serial interface

4.3

Serial interface

Information on the serial interface

● Via the serial interface (RJ-11 jack), you can access the CLI of the device directly via an

RS-232 connection (115200 8N1) without assigning an IP address.

● Access to the device is also possible independent of the Ethernet ports.

● To connect the serial interface to the PC, you require a cable with an RJ-11 plug and 9pin D-sub female connector. You can order the connecting cable for the serial interface as an accessory.

Position and assignment

Figure 4-2 Position and pin assignment of the serial interface (RJ-11 jack), for example on the

SCALANCE XB213-3

Assignment of the terminal block

3

4

5

6

1

2

7

8

9

The connecting cable listed in the "Accessories" section has the following pin assignment:

Contact Pin assignment of the RJ-11 plug

-

-

-

TD (Transmit Data)

SG (Signal Ground)

RD (Receive Data)

Pin assignment of the D-sub female connector

-

TD (Transmit Data)

RD (Receive Data)

-

-

-

-

SG (Signal Ground)

-

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

27

Connecting up

4.4 Functional ground

Note

Pin assignment of the RJ-11 jack on the device

The RJ-11 jack on the device has a pinout to match the RJ-11 plug of the connecting cable mentioned above.

4.4

Functional ground

EMC disturbances are diverted to ground via the functional ground. This ensures the immunity of the data transmission.

The functional ground must be implemented with low impedance. The connection of the functional ground must be established directly on the mounting plate or the DIN rail terminal.

The IE switch has a terminal for functional ground, refer to the section "Power supply

(Page 25)". Keep to the specified cross-sectional area for the functional ground.

The terminal is identified by the following symbol for the functional ground

Follow the steps below to connect the functional ground:

.

1.

Connect the terminal of the IE switch with as short a cable as possible ≤ 150 mm and with the required cross-sectional area to a grounded part of the system (DIN rail).

2.

Connect the DIN rail with the ground of the system.

Protective/functional ground

The connection of the reference potential surface with the protective ground system is normally in the cabinet close to the power feed-in. This ground conducts fault currents to ground safely and according DIN/VDE 0100 is a protective ground to protect people, animals and property from too high contact voltages.

Apart from the protective ground, there is functional grounding in the cabinet. According to

EN60204-1 (DIN/VDE 0113 T1) electrical circuits must be grounded. The chassis (0 V) is grounded at one defined point. Here, once again the grounding is implemented with the lowest leakage resistance to ground in the vicinity of the power feed-in.

With automation components, functional ground also ensures interference-free operation of a controller. Via the functional ground, interference currents coupled in via the connecting cables are discharged to ground.

28

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Upkeep and maintenance

5

5.1

Firmware

Downloading new firmware using TFTP without WBM and CLI

The firmware is signed and encrypted. This ensures that only firmware created by Siemens can be downloaded to the device.

Pressing the "RESET" button

To load new firmware, you require the "RESET" button. When pressing the button,

remember the information in the section "RESET button (Page 16)".

Procedure with Microsoft Windows

Using TFTP, you can supply a device with new firmware even when it cannot be reached using WBM or CLI. This section explains the procedure based on the example of Microsoft

Windows.

Follow the steps below to load new firmware using TFTP:

1.

Turn off the power to the device.

2.

Press the "RESET" button applying only slight pressure button and reconnect the power to the device while holding down the button.

3.

Hold down the button until the red fault LED "F" starts to flash.

4.

Release the button as long as the red error LED is still flashing..

Note

This time only lasts a few seconds.

The bootloader of the device waits in this status for a new firmware file that you can download by TFTP.

5.

Connect a PC to port 0.1 via an Ethernet cable.

6.

Assign an IP address to the device using DHCP or the Primary Setup Tool.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

29

Upkeep and maintenance

5.1 Downloading new firmware using TFTP without WBM and CLI

7.

Open a Windows command prompt and change to the directory where the file with the new firmware is located and then execute the following command : tftp -i <IP address> put <firmware file>

Note

You can enable TFTP in Microsoft Windows as follows:

"Control Panel" > "Programs and Features" > "Turn Windows features on or off" > "TFTP

Client".

8.

Once the firmware has been transferred completely to the device and validated, there is an automatic restart on the device. This may take several minutes.

30

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Upkeep and maintenance

5.2 Restoring the factory settings

5.2

Restoring the factory settings

Note

When you reset the device parameters, all previously changed settings are lost.

With the "RESET" button

When pressing the button, remember the information in the section "RESET button

(Page 16)".

Follow the steps below to reset the device parameters to the factory settings with the

"RESET" button:

1.

Turn off the power to the device.

2.

Press the "RESET" button for example with a screwdriver and reconnect the power to the device while holding down the button.

3.

Hold down the button until the red error LED "F" stops flashing after approximately 20 seconds and is permanently lit.

4.

Release the button and wait until the fault LED "F" goes off.

The device starts automatically with the factory settings.

With the PST

Follow the steps below to reset the device parameters to the factory settings with the PST:

1.

Select the device whose parameters you want to reset.

2.

Click on the menu item "Reset" in the "Module" tab.

3.

Confirm the prompt with "OK".

During configuration

You will find detailed information on resetting the device parameters using the WBM and CLI

in the configuration manuals (Page 3):

● SCALANCE XB-200 Web Based Management, section "Restart"

● SCALANCE XB-200 Command Line Interface, section "Reset and Defaults"

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

31

Upkeep and maintenance

5.2 Restoring the factory settings

32

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6

6.1

Technical specifications of the SCALANCE XB208

The following technical specifications apply to the SCALANCE XB208.

Technical specifications

Attachment to Industrial Ethernet

Diagnostics interface

Serial interface

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

8

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Design

Cable cross-section

Minimum

Maximum

24 VDC

19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Current consumption

Effective power loss

Fusing

Permitted ambient conditions

Ambient temperature

Property at 24 VDC at 24 VDC

Implemented redundantly

170 mA

4.1 W

F 2.5 A / 125 V

During operation up to 2000 m

During storage

During transportation

During operation at 25 ℃

0 ℃ to +60 ℃

-40 ℃ to +70 ℃

-40 ℃ to +70 ℃

≤ 95 % no condensation Relative humidity

Housing, dimensions and weight

Design

Housing material

Degree of protection

Dimensions (W x H x D)

Weight

Installation options compact

Polycarbonate (PC-GF10)

IP20

40 x 117 x 109 mm

250 g

Installation on a DIN rail

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

33

Technical specifications

6.1 Technical specifications of the SCALANCE XB208

Technical specifications

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 84 years

34

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.2 Technical specifications of the SCALANCE XB205-3 (SC)

6.2

Technical specifications of the SCALANCE XB205-3 (SC)

The following technical specifications apply to the SCALANCE XB205-3 (SC).

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

5

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

SC socket

Full duplex acc. to 100Base-FX

100 Mbps

Multimode glass FO cable

-19 dBm

-14 dBm

Diagnostics interface

Serial interface

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

50/125 μ m

62.5/125 μ m

Quantity

Connector

Cable length

0 ... 5 km

0 ... 5 km

-34 dBm

-3 dBm

Attenuation

≤ 1 dB/km at 1310 nm; 1200 MHz * km

≤ 1 dB/km at 1310 nm; 1200 MHz * km

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

300 mA

*)

7.2 W

F 2.5 A / 125 V

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

35

Technical specifications

6.2 Technical specifications of the SCALANCE XB205-3 (SC)

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

80 x 117 x 109 mm

350 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 55 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

36

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.3 Technical specifications of the SCALANCE XB205-3LD (SC)

6.3

Technical specifications of the SCALANCE XB205-3LD (SC)

The following technical specifications apply to the SCALANCE XB205-3LD (SC).

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

5

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

SC socket

Full duplex acc. to 100Base-FX

100 Mbps

Single mode glass FO cable

-15 dBm

-8 dBm

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

• 9/125 μ m

Cable length

• 0 to 26 km

-32 dBm

-3 dBm

Attenuation

• ≤ 0.5 dB/km at 1310 nm

Diagnostics interface

Serial interface Quantity

Connector

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

290 mA

*)

7 W

F 2.5 A / 125 V

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

37

Technical specifications

6.3 Technical specifications of the SCALANCE XB205-3LD (SC)

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

80 x 117 x 109 mm

350 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 50 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

38

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.4 Technical specifications of the SCALANCE XB205-3

6.4

Technical specifications of the SCALANCE XB205-3

The following technical specifications apply to the SCALANCE XB205-3.

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

5

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

ST(BFOC) socket

Full duplex acc. to 100Base-FX

100 Mbps

Multimode glass FO cable

-19 dBm

-14 dBm

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

50/125 μ m

62.5/125 μ m

Cable length

0 ... 5 km

0 ... 5 km

-32 dBm

-3 dBm

Attenuation

≤ 1 dB/km at 1310 nm; 1200 MHz * km

≤ 1 dB/km at 1310 nm; 1200 MHz * km

Diagnostics interface

Serial interface Quantity

Connector

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

300 mA

*)

7.2 W

F 2.5 A / 125 V

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

39

Technical specifications

6.4 Technical specifications of the SCALANCE XB205-3

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

80 x 117 x 109 mm

350 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 55 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

40

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.5 Technical specifications of the SCALANCE XB216

6.5

Technical specifications of the SCALANCE XB216

The following technical specifications apply to the SCALANCE XB216.

Technical specifications

Attachment to Industrial Ethernet

Diagnostics interface

Serial interface

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

16

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Design

Cable cross-section

Minimum

Maximum

24 VDC

19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Current consumption

Effective power loss

Fusing

Permitted ambient conditions

Ambient temperature

Property at 24 VDC at 24 VDC

Implemented redundantly

280 mA

6.7 W

F 2.5 A / 125 V

During operation up to 2000 m

During storage

During transportation

During operation at 25 ℃

0 ℃ to +60 ℃

-40 ℃ to +70 ℃

-40 ℃ to +70 ℃

≤ 95 % no condensation Relative humidity

Housing, dimensions and weight

Design

Housing material

Degree of protection

Dimensions (W x H x D)

Weight

Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) compact

Polycarbonate (PC-GF10)

IP20

80 x 117 x 109 mm

400 g

Installation on a DIN rail

> 60 years

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

41

Technical specifications

6.6 Technical specifications of the SCALANCE XB213-3 (SC)

6.6

Technical specifications of the SCALANCE XB213-3 (SC)

The following technical specifications apply to the SCALANCE XB213-3 (SC).

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

13

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

SC socket

Full duplex acc. to 100Base-FX

100 Mbps

Multimode glass FO cable

-19 dBm

-14 dBm

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

50/125 μ m

62.5/125 μ m

Cable length

0 ... 5 km

0 ... 5 km

-34 dBm

-3 dBm

Attenuation

≤ 1 dB/km at 1310 nm; 1200 MHz * km

≤ 1 dB/km at 1310 nm; 1200 MHz * km

Diagnostics interface

Serial interface Quantity

Connector

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

410 mA

*)

9.8 W

F 2.5 A / 125 V

42

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.6 Technical specifications of the SCALANCE XB213-3 (SC)

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

120 x 117 x 109 mm

500 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 45 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

43

Technical specifications

6.7 Technical specifications of the SCALANCE XB213-3LD (SC)

6.7

Technical specifications of the SCALANCE XB213-3LD (SC)

The following technical specifications apply to the SCALANCE XB213-3LD (SC).

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

13

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

SC socket

Full duplex acc. to 100Base-FX

100 Mbps

Single mode glass FO cable

-15 dBm

-8 dBm

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

• 9/125 μ m

Cable length

• 0 to 26 km

-32 dBm

-3 dBm

Attenuation

• ≤ 0.5 dB/km at 1310 nm

Diagnostics interface

Serial interface Quantity

Connector

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

400 mA

*)

9.6 W

F 2.5 A / 125 V

44

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.7 Technical specifications of the SCALANCE XB213-3LD (SC)

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

120 x 117 x 109 mm

500 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 40 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

45

Technical specifications

6.8 Technical specifications of the SCALANCE XB213-3

6.8

Technical specifications of the SCALANCE XB213-3

The following technical specifications apply to the SCALANCE XB213-3.

Technical specifications

Attachment to Industrial Ethernet

Electrical connectors

Optical connectors

Quantity

Connector

Properties

Transmission speed

Quantity

Connector

Properties

Transmission speed

Cable type

Transmitter output (optical)

Minimum

Maximum

13

RJ-45 jack

Half/full duplex, MDI-X pinning

10 / 100 Mbps

3

ST(BFOC) socket

Full duplex acc. to 100Base-FX

100 Mbps

Multimode glass FO cable

-19 dBm

-14 dBm

Receiver input

Sensitivity min.

Input power max.

Cable cross-section

50/125 μ m

62.5/125 μ m

Cable length

0 ... 5 km

0 ... 5 km

-32 dBm

-3 dBm

Attenuation

≤ 1 dB/km at 1310 nm; 1200 MHz * km

≤ 1 dB/km at 1310 nm; 1200 MHz * km

Diagnostics interface

Serial interface Quantity

Connector

1

RJ-11 jack

Electrical data

Power supply Rated voltage

Voltage range

Current consumption

Effective power loss

Fusing

Design

Cable cross-section

Minimum

Maximum

Properties at 24 VDC at 24 VDC

24 VDC

19.2 to 28.8 VDC Safety Extra Low Voltage

(SELV)

Terminal block, 3 terminals

0.25 mm

2

(24 AWG)

1.5 mm

2

(16 AWG)

Implemented redundantly

410 mA

*)

9.8 W

F 2.5 A / 125 V

46

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.8 Technical specifications of the SCALANCE XB213-3

Technical specifications

Permitted ambient conditions

Ambient temperature During operation up to 2000 m 0 ℃ to +60 ℃

Relative humidity

Housing, dimensions and weight

Design

During storage

During transportation

During operation at 25 ℃

-40

-40

to +70

to +70

95 % no condensation

Housing material

Degree of protection

Dimensions (W x H x D)

Weight compact

Polycarbonate (PC-GF10)

IP20

120 x 117 x 109 mm

500 g

Installation on a DIN rail Installation options

Mean time between failure (MTBF)

MTBF (EN/IEC 61709; 40 °C) > 45 years

)

*

For every optical port that you set to "link down", the current consumtion of the device is reduced by 30 mA.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

47

Technical specifications

6.9 Cable lengths

6.9

Cable lengths

The following technical specifications apply to the following devices:

● SCALANCE XB208

● SCALANCE XB205-3 (SC)

● SCALANCE XB205-3LD (SC)

● SCALANCE XB205-3

● SCALANCE XB216

● SCALANCE XB213-3 (SC)

● SCALANCE XB213-3LD (SC)

● SCALANCE XB213-3

Cable

IE TP torsion cable with IE FC Outlet RJ-45 + 10 m TP cord

IE TP torsion cable with IE FC RJ-45 Plug 180

IE FC TP Marine / Trailing / Flexible cable with IE FC Outlet RJ-45 + 10 m TP cord

IE FC TP Marine / Trailing / Flexible cable with IE FC RJ-45 Plug 180

IE FC TP standard cable with IE FC Outlet RJ-45 + 10 m TP cord

IE FC TP standard cable with IE FC RJ-45 Plug 180

Permitted cable length

0 to 45 m

+ 10 m TP cord

0 to 55 m

0 to 75 m

+ 10 m TP cord

0 to 85 m

0 to 90 m

+ 10 m TP cord

0 to 100 m

48

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Technical specifications

6.10 Switching properties

6.10

Switching properties

The following technical specifications apply to the following devices:

● SCALANCE XB208

● SCALANCE XB205-3 (SC)

● SCALANCE XB205-3LD (SC)

● SCALANCE XB205-3

● SCALANCE XB216

● SCALANCE XB213-3 (SC)

● SCALANCE XB213-3LD (SC)

● SCALANCE XB213-3

Switching properties

Aging time

Max. number of learnable addresses

Switching technique

Latency

Full wire speed switching:

Note

Can be configured (default value: 40 seconds)

8192

Store and forward

10 microseconds

Number of frames per second (at 100 Mbps)

148810

84459

45290

23496

11973

9615

8127

Frame length

64 bytes

128 bytes

256 bytes

512 bytes

1024 bytes

1280 bytes

1518 bytes

The number of SCALANCE XB-200 modules connected in a line influences the frame delay.

When a frame passes through the switch, this is delayed by the store-and-forward function of the SCALANCE XB-200 by 10-130 microseconds (at 100 Mbps).

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

49

Technical specifications

6.10 Switching properties

50

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Dimension drawings

Note

Dimensions are specified in mm.

Front view of the SCALANCE XB208

7

Figure 7-1 Width and height

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

51

Dimension drawings

Front view of the SCALANCE XB205-3 (SC), XB205-3LD (SC), XB205-3 and XB216

52

Figure 7-2 Width and height based on the example of the SCALANCE XB205-3

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Front view of the SCALANCE XB213-3 (SC), XB213-3LD (SC) and XB213-3

Dimension drawings

Figure 7-3 Width and height based on the example of the SCALANCE XB213-3

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

53

Dimension drawings

Side view of the SCALANCE XB-200

Figure 7-4 Depth

54

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Approvals

A

The SIMATIC NET products described in these Operating Instructions have the approvals listed below.

Note

Issued approvals on the type plate of the device

The specified approvals apply only when the corresponding mark is printed on the product.

You can check which of the following approvals have been granted for your product by the markings on the type plate.

Current approvals on the Internet

You will find the current approvals for the product on the Internet pages of Siemens Industry

Online Support ( http://support.automation.siemens.com/WW/view/en/33118389/134200 ).

→ Entry type "Certificates"

EC directives

SIMATIC NET products meet the requirements and aims of the following EC directives.

EMC directive (electromagnetic compatibility)

The SIMATIC NET products described in these operating instructions meet the requirements of EC directive 2004/108/EC "Electromagnetic Compatibility" for the following areas of application:

Field of application

Industry

Emission

EN 61000-6-4 : 2007

Requirements

Immunity to interference

EN 61000-6-2 : 2005

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

55

Approvals

WARNING

Personal injury and property damage can occur

The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility.

Only use expansions that are approved for the system.

● Keep to the installation guidelines

The devices meet the requirements if you adhere to the installation and safety instructions contained in this documentation and in the following documentation when installing and operating the devices.

● You can always find the latest documentation on the Internet

The current descriptions of the currently available products can always be found on the

Internet under the specified entry IDs/Internet pages:

– "Industrial Ethernet / PROFINET Industrial Ethernet" System Manual

– "Industrial Ethernet / PROFINET - Passive network components" System Manual

You will find information on the system manuals in the section "Introduction (Page 3)",

in "Further documentation".

– "EMC Installation Guidelines" configuration manual

60612658 ( http://support.automation.siemens.com/WW/view/en/60612658 )

● Working on the device

To protect the device from electrostatic discharge, personnel must first discharge any electrostatic charge from their body before touching the device.

Note

The test was performed with a device and a connected communications partner that also meets the requirements of the standards listed above.

When operating the device with a communications partner that does not comply with these standards, adherence to the corresponding values cannot be guaranteed.

Safety of electrical equipment

In the version put into circulation by Siemens AG, the SIMATIC NET products described in these Operating Instructions conform to the regulations of the following European directive:

● EN 60950-1

Information technology equipment - Safety - Part 1: General requirements

EU declaration of conformity

You will find EC declaration of conformity for these products on the Internet pages of

Siemens Industry Online Support

( http://support.automation.siemens.com/WW/view/en/33118389/134200 ).

56

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Approvals

ATEX (explosion protection directive)

WARNING

When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that the associated conditions in the following document are adhered to:

"SIMATIC NET Product Information Use of subasseblies/modules in a Zone 2 Hazardous

Area".

You will find this document

• on the data medium that ships with some devices. on the Internet pages of Siemens Industry Online Support

( http://support.automation.siemens.com/WW/view/en ).

Enter the document identification number C234 as the search term.

SIMATIC NET products meet the requirements of the EC directive:94/9/EC "Equipment and

Protective Devices for Use in Potentially Explosive Atmospheres".

ATEX classification:

II 3 G Ex nA IIC T4 Gc

KEMA 07ATEX0145 X

The products meet the requirements of the following standards:

● EN 60079-15 (electrical apparatus for potentially explosive atmospheres; Type of protection "n")

● EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)

You will find the current versions of the standards in the currently valid ATEX certificates.

IECEx

The SIMATIC NET products meet the requirements of explosion protection according to

IECEx.

IECEx classification:

Ex nA IIC T4 Gc

DEK 14.0025X

The products meet the requirements of the following standards:

● IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of protection "n")

● IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)

You will find the current versions of the standards in the currently valid IECEx certificates.

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

57

Approvals

FM

The product meets the requirements of the standards:

● Factory Mutual Approval Standard Class Number 3611

● FM Hazardous (Classified) Location Electrical Equipment:

Non Incendive / Class I / Division 2 / Groups A,B,C,D / T4 and

Non Incendive / Class I / Zone 2 / Group IIC / T4

cULus Approval for Information Technology Equipment

cULus Listed I. T. E.

Underwriters Laboratories Inc. complying with

● UL 60950-1 (Information Technology Equipment)

● CSA C22.2 No. 60950-1-03

Report no. E115352

cULus Approval Hazardous Location

cULus Listed I. T. E. FOR HAZ. LOC.

Underwriters Laboratories Inc. complying with

● UL 60950-1 (Information Technology Equipment)

● ANSI/ISA 12.12.01-2007

● CSA C22.2 No. 213-M1987

Approved for use in

Cl. 1, Div. 2, GP A, B, C, D T4

Cl. 1, Zone 2, GP IIC T4

Report no. E240480

RCM

The product meets the requirements of the AS/NZS 2064 standard (Class A).

KC (Korean Standard)

The products meet the requirements of the "Korean Standard".

Marking for the customs union

EAC (Eurasian Conformity)

Customs union of Russia, Belarus and Kazakhstan

Declaration of the conformity according to the technical regulations of the customs union

(TR CU)

58

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

FDA and IEC marks

The following devices meet the FDA and IEC requirements listed below:

Device

SCALANCE XB208

SCALANCE XB205-3 (SC)

SCALANCE XB205-3LD (SC)

SCALANCE XB205-3

SCALANCE XB216

SCALANCE XB213-3 (SC)

SCALANCE XB213-3LD (SC)

SCALANCE XB213-3

CLASS 1 LASER Product

-

-

-

-

-

-

-

-

-

CLASS 1 LED Product

-

Approvals

Figure A-1 FDA and IEC approvals

CAUTION

Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure.

Mechanical stability (in operation)

Device IEC 60068-2-27 shock

15 g, 11 ms duration

6 shocks per axis

SCALANCE XB208

SCALANCE XB205-3

SCALANCE XB205-3 (LD)

SCALANCE XB205-3 (ST)

SCALANCE XB216

SCALANCE XB213-3

SCALANCE XB213-3 (LD)

SCALANCE XB213-3 (ST)

IEC 60068-2-6 vibration

10 - 58 Hz: 0.075 mm

85 - 150 Hz: 1 g

1 octave/min, 20 sweeps

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

59

Index

A

Accessories, 12

Ambient temperature, 33, 36, 38, 40, 41, 43, 45, 47

Article numbers, 11

Attachment to Industrial

Ethernet, 33, 35, 37, 39, 41, 42, 44, 46

I

Installation, 33, 36, 38, 40, 41, 43, 45, 47

Installation on a DIN rail, 21

Installation on a DIN rail, 21

C

CLI, 27, 29

Command Line Interface, 27, 29

Components of the product, 12

Configuration manuals, 17, 31

Connecting up

Grounding, 28

L

LED displays, 18

Fault LED, 18

Port LEDs, 18

M

MTBF, 34, 36, 38, 40, 41, 43, 45, 47

D

Dimensions, 33, 36, 38, 40, 41, 43, 45, 47

P

E

Electrical data, 33, 35, 37, 39, 41, 42, 44, 46

Environmental conditions, 33, 36, 38, 40, 41, 43, 45, 47

R

RESET button, 13, 14, 15, 16, 29

Reset device, 16

F

Permitted ambient

conditions, 33, 36, 38, 40, 41, 43, 45, 47

Power supply, 13, 14, 15, 25

Factory defaults, 16

Fault LED, 13, 14, 15

Firmware, 29

S

G

Glossary, 5

Grounding, 13, 14, 15, 28

H

Safety notices

for installation, 19

general, 9

Use in hazardous areas, 9, 19, 23 when connecting up, 23

Serial interface, 13, 14, 15, 27

SIMATIC NET glossary, 5

SIMATIC NET manual, 4

Spring-loaded terminal, 25

System manual, 4, 20, 56

Housing, 33, 36, 38, 40, 41, 43, 45, 47

W

WBM, 29

Web Based Management, 29

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

61

Index

Weight, 33, 36, 38, 40, 41, 43, 45, 47

62

SCALANCE XB-200

Operating Instructions, 09/2015, C79000-G8976-C359-03

Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement