Lexing F-A16L Smoke alarm Instructions
Advertisement
Advertisement
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
Fire Alarm Panel-F-A16L
CONTENTS
1. FIRE ALARM CONTROL PANEL SAFETY ISSUES………………………..……………… 2
How to use this Fire Alarm Panel safely
2. THE PURPOSE OF A FIRE ALARM SYSTEM……………………………………………… 2
Introduction to fire alarms
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, INCLUDING THE
FACP & ITS INTEGRAL PSE ………………………………………………………….………… 3
What the end users responsibility is, including daily, weekly, quarterly & annual checks
4. PANEL INDICATIONS & CONTROLS …………………………..……………….………….. 5
A list of indicator LEDs & Control Buttons on the F-A16L Fire Alarm Panel
4.1 GENERAL CONTROLS
4.2 ACCESSED CONTROLS
4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING
4.4 CHECKING THE PANELS INDICATION LEDS
4.5 FIRE ALARM SYSTEM AND ITS ACCESSORIES
4.6 LX928-V7 SMOKE DETECTOR USING INSTRUCTION
4.7GLASS BROKEN CALL POINT INSTALLATION INSTRUCTIONS
5. THE FIRE CONDITION ……………………………………………………………………… 14
5.1 HOW THE F-A16L INDICATES AN ALARM
5.2 TO TURN OFF THE ALARM SOUNDERS
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE
5.4 TURNING ON THE ALARM SOUNDERS FROM THE FACP (I.E. EVACUATE).
5.5 RESETTING THE PANEL
6. THE FAULT CONDITIONS …………………………………………………………………….15
6.1 DIFFERENT TYPES OF FAULT
6.2 WHAT TO DO IF A FAULT CONDITION OCCURS
7. DISABLEMENTS …………………………………..…………………………………………… 15
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM
8. SYSTEM DESCRIPTION ………………………………………………………….……….…... 15
List of system comments
9. FIRE ALARM LOG BOOK………………………………………………………………………17
A place for you to record details of events such as fires, false alarms, callouts, etc.
10. COMMISSIONING THE SYSTEM, INCLUDING P.S.E…………………………..……….. 20
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
1. FIRE ALARM CONTROL PANEL SAFETY ISSUES
There is no need to open this fire alarm during normal operation. Any work carried out on this system must be performed by a competent person who is familiar with this type of system. This equipment will operate safely provided it has been installed correctly in compliance with the Installation Manual. It is recommended that the system is serviced frequently. It is customary to arrange a regular maintenance contract with a competent organisation. (Ask the installation company for recommendations). The system needs a thorough maintenance check annually at the very minimum.
If any part of this Fire Alarm Control Panel becomes damaged, contact the company responsible for system maintenance to arrange repair / replacement.
European Union Directives Conformance
Statement, This product has been manufactured in conformance with the requirements of all applicable EU Council Directives.
2. THE PURPOSE OF A FIRE ALARM SYSTEM
A Fire Alarm System is used to provide an early warning of a fire, so that the property can be evacuated and the fire extinguished if it can be safely tackled, or the local fire brigade called, according to the company evacuation procedure. Alarms can come from Smoke or
Heat Detectors, or manually be a person operating a Manual Call Point. Split the system into
Zones, each covering a different area of a building. This will indicate which area of the system is giving the alarm (or fault).During an alarm; the panel will start its sounders, and indicate which zone has the fire. It will also activate its auxiliary relay.
Fault Monitoring
All circuits must be checked for line integrity. If a part of the system has a problem which may affect its operation, a fault warning must be given by the fire alarm panel (LED & buzzer indication). The fault will not be activated.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
Disablements
An engineer may be required to work on part of a system, while the system is still active
(e.g. extending a detection zone). During such circumstances, it would be advisable to disable that zone, so that it will not give false alarms. Similarly you may wish to disable a zone that has a fault that has not been fixed, or a zone covering an area with a temporary unusual environment, such as an area which is dusty because of construction work etc.
Power Supply Equipment - General Description
The F-A16L is composed of two parts, Electricity (AC220V) and lead-acid batteries. Under normal circumstances the power of the product offered by Electricity (AC220V). When power is cut, the standby battery (lead-acid batteries) is enabled.meanwhile, the products will make the corresponding instructions and the buzzer will also sound. At this point you can press the mute button as long as the product can still work properly. Note: When the batteries is installed you should switch on Electricity (AC220V) fist, this will prevent a spark occurring.
N.C
COM NO GND +12 GND R+ GND R+
+
+
Lead-acid batteries
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM
SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE
The owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm System. Below is a summary of the main functions the “Responsible Person” is expected to carry out. It is meant to give a brief outline of user responsibilities for the safe upkeep of the Fire Alarm System.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
The responsible person must:
1. Check the system at least once every 24 hours to ensure there are no faults present.
2. Ensure there are arrangements for testing and maintaining the system.
3. Ensure the log book is up to date, and available for inspection.
4. Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence alarms, silence faults and system reset.
5. Take appropriate action to limit the rate of false alarms.
6. Ensure that all detectors and manual call points remain unobstructed at all times.
7. Liaise with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere with the functioning and reliability of the fire alarm system.
8. Ensure any changes to the system are recorded with updated drawings, operating instructions etc.
9. Ensure that there are spare parts (especially Call point elements) held on site. With the
F-A16L Range of Fire Alarm Panels, we recommend the following tests are carried out.
Daily Inspection
Check that the green Power LED is lit. If there are any yellow fault LED’s lit, or the green
Power LED is not lit, report the fault(s) to the designated site maintenance engineer.
Weekly Test
Insert the key, Turn the key to the "CONTROLS ENABLED" then press the “STOP-START” to detect buzzer, external alarm, relays. Press the button again to Closed. Press the “LED
TEST” testing the LED’S capabilities; Press the “CHECK” testing whether all accessories are OK.
Quarterly Test (to be carried out by authorised service personnel only
Check that any servicing or repairs required by all previous logbook entries has been undertaken.
Visual inspect of the batteries and connections. Check the alarm sounders work on battery only.
Activate a device from each zone to test the fire alarm (As weekly test).
Annual Test (to be carried out by authorised service personnel only
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
Check every detector, call point, sounder and all auxiliary equipment for correct operation.
Check Transformer output Voltage (32 VAC), Charger Voltage.
Every Five Years (to be carried out by authorised service personnel only)
Carry out a complete wiring check in accordance with the testing and inspection requirements of the relevant National wiring regulations. The Batteries should be replaced because SLA batteries have a working life of 5 years.
4. PANEL INDICATIONS & CONTROLS
CURRENT ALERT
STOP-START
SILENCE
RESET
LED TEST
CHECK
ALERT MEMORY
ALARM
0
1
2
3
POWER
SUPPLY FAULT
CHECK
NORMAL
WAITING
ABNORMAL
6
7
8
9
4
5
10
11
12
TROUBLE
ALARM
13
14
15
OFF ON
Two list of control are available to the User(s) of this Fire Alarm Panel.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
4.1 GENERAL CONTROLS
When the Panel is in its Normal state, the indicator lights on the front of the enclosure give a comprehensive overview of the System’s current status. Any Fire and Fault conditions are clearly displayed, and any disablements highlighted. For detailed descriptions of what each indicator means, please refer to the table on the opposite page.
4.2 ACCESSED CONTROL (AVAILABLE TO AUTHORISED USERS ONLY)
To avoid unauthorized changes to critical parts of the Fire Alarm System controls such as silencing the Sounders, resetting an Alarm condition and implementing Disablements are only accessible via a secure method of entry which puts the panel into the Accessed state.
To put the Panel into the Accessed State: Turn the key to the “CONTROLS ENABLED” position (please note the key should not be removed when in this position). To leave the
Accessed state, turn the key back to the OFF position.
Information on how to use the accessed control can be found on Pages 6 to 7 of this User
Manual.
4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING
Use the table below to determine the condition of the panel.
LEDS LIT
POWER
LED CONDITION
CONSTANT GREEN
SUPPLY FAULT CONSTANT RED
CHECK
WAITING
NORMALT
CONSTANT
FLASHING WHITE
WITH YELLOW
CONSTANT GREEN
CONSTANT GREEN
ABNORMALT
TROUBLE
CONSTANT YELLOW
CONSTANT YELLOW
PANEL STATUS
The panel is supplied with power (System Normal)
A lack of power supply (such as electricity cut, or battery badness)
Checking system
System waiting
System normal
Some channel detector is abnormal or lost
Some channel detector is fault or shatteris abnormal or lost
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
ALARM
ON
OFF
ALARM
CURRENT ALERT
CONSTANT RED
CONSTANT GREEN
CONSTANT
YELLOW
CONSTANT
FLASHING RED
CONSTANT GREEN
ABNORMALT SHOW FIGURES
ALERT MEMORY SHOW FIGURES
Some channel detector is alarm
There is a detector in this channels
There is no detector in this channels
This channels of detectors have already alarm, has lost or damaged
System normal
It is display the channels of detector which was unusual / trouble / alarm
Cycle displays the channels of detector which was unusual / trouble / alarm
4.4 CHECKING THE PANELS INDICATION LEDS
Turn the key switch to “CONTROLS ENABLED” position then press the “LED TEST” button.
All the LED(s) on the left will light and the panel’s internal buzzer will also sound.
OFF CONTROLS ENABLED
Press
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
4.5 FIRE ALARM SYSTEM AND ITS ACCESSORIES
To strengthen security, besides the standard configure we provide, you can add other fittings. Our fittings for your choice have: Wireless smoke alarm (LX928-V7)
/siren(LX-SR)/glass broken call.
Maximum number of connectable products: 64
+
+
N.C
COM NO GND +12 GND R+ GND R+
The connection-wire of smoking alarm
Connect “R+” with “+”
Connect “GND” with “-”
The connection-wire of alarm
Connect “COM” with “GND”
Connect “+12” with “+”
Connect “NO” with “-”
+
+
Lead-acid batteries
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
4.6 LX928-V7 SMOKE DETECTOR USING INSTRUCTION
The product is a new type of photoelectric smoke detector, it use matched with F-A16L.When it detects smoke, its LEDs flash quickly and the main F-A16L alarm, dial, which tell you in advance that fire will occurs and avoid unwanted loss, and take you safety and convenience.
Specification
Power supply: DC18V~ DC35V
Static current: 3mA
Working current: 5mA
Double LED: flash once every 10sec(when no alarming) quickly flash(when alarming).
Connect-wire method: two-wire connection
Where Fit To Install Smoke Detector
1. At first, you need install one item in every bedroom and route way at least.
2. Stairway is important for you to rush out when fires occur, so there must install smoke detector on the top of stairway.
3. You at least require one detector in every space of every floor, including finished attics and basements.
4. Install one detector beside every electric facility.
5. You’d better Install smoke detectors in the middle of ceiling, because smoke always spread up;
6. If some reasons cause you can’t install them in the middle of ceiling, you also need to install them at least 10cm away from the wall.
7. If you like to install them on the wall, they should be installed 10-30.5cm away under the ceiling. Diagram 1.
8. You need install more than one detector when the length of your hall exceeds 9m.
9. In an oblique roof room, install the detector 0.9m away from the top. Diagram 2.
10. How to install smoke detectors in a removable house. The removable house is short of heat isolation, so you’d better install the alarm 10-30.5cm away from the ceiling.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
10CM(4'')
MINIMUM CEILING
ANYWGERE
IN THIS AREA
BEST HERE NEVER HERE
ACCEPTABLE HERE
DIAGRAM 1
SIDE WALL
0.9M(3ft) 0.9M(3ft)
HORIZONTAL DISTANCE
FROM PEAK
DIAGRAM 2
Where Not Fit To Install Smoke Detector
1. Where combustion are permitted to produce. For example unventilated kitchens, garages,and furnace.
2. Near fanner.
3. In very damp, humid or steamy areas: Keep units at least 3m away from showers saunas, dishwashers, etc.
4. In very dusty, dirty, or greasy areas.
5. In very drafty areas, where smoke will be blown away from the unit completely.
6. In air-logged areas, that will clog the sensing chamber.
7. Where Less than 305mm away from fluorescent lights. Electrical “noise” can interfere with the sensor.
8. In “dead air” space, for example, in Diagram 1, near the corner less than 10cm.
9. In smoking meeting room, don’t install the alarm there for the unit will alarm when several persons smoke.
BEDROOM
SINGLE FLOOR PLAN
KITCHEN
BEDROOM
BEDROOM
MULTIPLE FLOOR PLAN
BEDROOM BEDROOM
KITCHEN
LIVING ROOM
BEDROOM
SMOKE ALARM FOR MINIMUM PROTECTION
SMOKE ALARM FOR ADDITIONAL PROTECTION
BASEWENT
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
Connection-wire Diagram
Loosen the screws arrow pointing in the right figure and twine the line head on the screw thread under gasket. And then tighten up the screws.
•Terminal 5 connect R+ " +" of control unit
•Terminal 2 connect GND "–" of control unit.
Installation
1. Press and hold the base and turn it counterclockwise, take down base.
2. According to the number mark on base and connection-wire diagram, connect wire to number corresponding screw with gasket.
3. Fix the base on the selected position.
4. Cover the alarm body: make the short line on the base aim at the long line on alarm body and turn clockwise until the long line on base aim at the long line on alarm body.
Test
1. Switch on power, the LEDS should flash once at the same time every about 10sec.
2. Put magnet near inner pole reed tube and attract it(attention the position like right fig.), the LEDs turn to flash quickly and the main
F-A16L alarm and dial.
3. If the LEDs don’t flash quickly, please check whether the magnet using is correct or not.
magnetism
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
Regular Maintenance
1. Test it at least once a week.
2. Clean the smoke alarm at least once a month. Gently vacuum off dust using vacuum’s soft brush attachment.
3. Never use water, cleansers to clean your smoke alarm since they may damage the unit.
Coding Method
LX928-V7 smoke detector can be identified by channel code; by 6-bit coding switch its channel code has 64 coding methods (detail in following table).
Coding
000000
000001
000010
000011
000100
000101
000110
000111
001000
001001
001010
001011
001100
001101
001110
001111
1
0
6
SABRE
5 4 3
8
9
10
11
12
13
14
Channel Coding Channel Coding
0 010000 16 100000
1
2
010001
010010
17
18
100001
100010
3
4
5
6
7
010011
010100
010101
010110
010111
19
20
21
22
23
100011
100100
100101
100110
100111
011000
011001
011010
011011
011100
011101
011110
24
25
26
27
28
29
30
101000
101001
101010
101011
101100
101101
101110
15 011111 31 101111
2
ON
1
40
41
42
43
44
45
46
Channel
32
33
34
35
36
37
38
39
47
Coding
110000
110001
110010
110011
110100
110101
110110
110111
111000
111001
111010
111011
111100
111101
111110
111111
56
57
58
59
60
61
62
Channel
48
49
50
51
52
53
54
55
63
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
4.7 GLASS BROKEN CALL POINT INSTALLATION INSTRUCTIONS
Function
Under emergency condition break the glass and make the main alarm.
Electrical Rating
AC (50Hz) 8V min. 250V max up to 10A
DC 8V min. 24V max up to 10A
48V max up to 3A
Contact resistance 0.1ohms max.
Glass Fitting
Feed the glass upward to push the cam down and fit under slider, locate bottom of glass into recess.
Hold the bottom of glass in position and rotate the thumbwheel to raise the top of the glass.
Fit the call point cover by hooking it into the top of the unit and making sure that the glass. is properly seated, and then tighten the cover fixing screw.
Testing
Push the test key through the hole in the underside of the call point to engage the test cam mechanism and push to operate the cam mechanism. At this point the test key is retained in the call point and pulling it out will reset the glass.
Glass Replacement
Open front cover, remove broken glass and follow procedure outlined under glass fitting.
Warning
Do not fit more that one core per terminal screw, always use one screw for ‘IN’ and one screw for ‘OUT’ to avoid possible bad connections. Maximum size cable 4.0mm
².
Connection
Terminals 1&3: Normally open contacts.
Notes
The unit as supplied is suitable for indoor application.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
5. THE FIRE CONDITION
5.1 HOW THE F-A16L INDICATES AN ALARM
When the F-A16L Fire Alarm Panel is set into alarm: LED will show that which zone is alarm.
Then the ALARM LED in the alarm panel will light. ALARM LED which corresponds to the area of fire will glimmer .The internal buzzer will sound, warning sounder and output equipment assisted will be started.
5.2 TO TURN OFF THE ALARM SOUNDERS
Turn the key switch to the “CONTROLS ENABLED” position, make controller quiet sound according to press “SILENCE”, shut off the warning generator of outside according to press “STOP-START”. But the LED is in charge of still revealing the area that calls the police, red “ALARM” LED on the panel still keeps on, red “ALARM” LED in the area of alarm still glimmers continuously, the fire insurance relay assisted will be in the state of activating.
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE
If another detection Zone is activated then the Alarm Sounders which have been silenced will activated again. LED “CURRENT ALERT” will show the alarm zone and the LED “ALERT
MEMORY” will shows the area zone this and last time by turns. In addition red “ALARM”
LED of the new warning area glimmers; originally fire zone is keep previous condition.
5.4 TURNING ON THE ALARM SOUNDERS FROM THE FACP
(I.E. TO EVACUATE THE BUILDING)
With the control key in “CONTROLS ENABLED” position, momentarily pressing the
Start-Stop will cause the Alarm sounders to sound. Pressing the Start-Stop button again will Silence the Alarm Sounders.
5.5 RESETTING THE PANEL
Check the cause of the alarm activation. If the cause of the alarm was by detector activation
(e.g. cooking smoke), the smoke will have to be cleared from the room before the panel can be reset. Reset the panel by pressing the reset after the sounders and panel buzzer have been silenced.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
If the call point is still active, or the detector is still smoky, this will cause another alarm straight after the panel is reset, so will set off alarm bells again.
6. THE FAULT CONDITION
6.1 DIFFERENT TYPES OF FAULT
If a fault occurs, the responsible person should:
Turn key switch to “CONTROLS ENABLED” and press “SILENCE” button to silence the fault buzzer.
Write down the fault (s) in the Log Book at the back of this Manual. Take appropriate action to correct the fault (Usually by contacting the service engineer) On the F-A16L panel, the fault indications (except system fault) are non latching. That is, when the fault has been cleared, the fault indication will turn off. When all faults have been cleared, the panel will return to its quiescent (normal) condition. When a fault has been rectified the indicator light for that Fault is automatically turned off. If all Faults are cleared, the General Fault light will go out and the Panel’s Internal Sounder will be silent (if not already muted).
7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled, that is zones already in fire cannot be disabled. External sounders can also be disabled as could be required in certain conditions.
8. SYSTEM DESCRIPTION
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
FIRE ALARM SYSTEM SUMMARY:
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
9. FIRE ALARM LOG BOOK
It is recommended that this LOG BOOK section of the Manual be maintained by the responsible person(s) on site, who should ensure every event is properly recorded
(including fire alarm conditions, failures, tests, temporary disconnections, disablements, enablements, dates of installing engineers’ visits together with a note of any outstanding work or panel conditions). This LOG BOOK must be available for inspection at all times.
You can photocopy this log book to provide extra pages for when this book is full.
Fire alarm events should be subdivided & recorded on separate sheets in the log book. The event categories are:
Maintenance work
False alarms – Where the sounders have activated with no signs of a fire.
Any other events- This would be genuine alarms or faults.
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
MAINTENANCE WORK
DATE TIME ZONE / LOCATION REASON FOR WORK WORK CARRIED OUT
ADDITIONAL WORK
REQUIRED
SIGNED
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
FALSE ALARMS
DATE TIME ZONE /
LOCATION
CAUSE (IF
KNOWN) OR
ACTIVITIES IN
ALARM AREA
MAINTENANCE
VISIT NEEDED
(YES/NO)
MAINTENANCE
FINDINGS
CATEGORY
OF FALSE
ALARM
FURTHER
ACTION
REQUIRED
SIGNED
Addressable Fire Alarm Systems /
Fire Alarm System
Maintenance Guide & Log Book
10. COMMISSIONING THE SYSTEM, INCLUDING P.S.E.
The commissioning of this fire alarm system should be performed by a qualified commissioning engineer (i.e. Design considerations, Limitations of false alarms,
Installation recommendations).
• The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer.
• The system set-up data chart should be checked for accuracy.
• The fire alarm log book contact details should be checked for completeness.
• The insulation of cables should be checked.
• The Earthing should be checked.
• The PSE mains feed from a 3A spur should be checked.
It should be protected by an over current device (MCB)
NOT an earth leakage device (RCD)
• The PSE Charger voltage should be checked & adjusted if necessary (28.3 with batteries disconnected).
• The battery voltage should be checked (should be between 24 & 27V).
• All call points & detectors can signal an alarm condition and indicate the correct zone (and text message) on the fire alarm panel.
• The Certificate of Installation & Commissioning should be completed, and the whole user manual passed to the relevant person on site.
NINGBO LEXING INDUC
T
OR ELECTRONIC CO.,
LTD
Add:No.35 Zhuquan Road,Science&Technology Area.
Ninghai,Ningbo,Zhejiang,China
Tel:+86-574-65335088
Fax:+86-574-65335000 65335333
E-mail:[email protected]
E-mail:[email protected]
www.lexing.com.cn
www.lexing.com

Public link updated
The public link to your chat has been updated.
Advertisement