Daikin | VRVIII | VRVIII-S - Brochure

VRVIII-S
LIGHT COMMERCIAL
RESIDENTIAL
AIR COOLED
n
RESIDENTIAL
n
LIGHT COMMERCIAL
n
RENOVATION
n
NEW CONSTRUCTION
The VRVIII®-S completes the mix of
VRV systems offering by allowing the
technology to be available at smaller
capacities. An air-cooled heat pump
condenser with 1-phase power supply
(208-230V), connects to a maximum of
six indoor units for the 3-Ton and eight
indoor units for the 4-Ton model. The
versatility of the VRVIII-S makes it ideal
for most light commercial or residential
projects - retail stores, small offices,
restaurants, hotels, healthcare facilities,
schools, multi-family townhouses, condos
or single-family homes.
A B SO L U T E C O MF O RT
2
DAIKIN AC
The Solution
For Light Commercial and
Residential Applications
HEAT PUMP
INVERTER
R-410A
Light commercial
Whether you are working with space constraints or
want to maximize the amount of commercial space
available, the VRVIII-S system gives you the flexibility
you need. With its simple, versatile design and long
piping (up to 492ft actual piping length one way),
the VRVIII-S can accommodate practically any floor
layout, enabling better use of space.
Its advanced zoning capabilities allow floor-by-floor
installation so that each floor can be occupied quickly
upon completion. And, because the outdoor units
are lightweight and vibration-free, there’s no need to
reinforce floors, reducing both installation time and
costs.
Residential
VRVIII-S is also an excellent alternative when building
a new house or renovating. Its long piping length
allows for multiple floors to be served from one
condenser installed outside.
All indoor units come with fan speed control and
operate extremely softly — as low as 28 decibels, the
equivalent of rustling leaves.
Outdoor units have built-in noise-reducing features,
including an automatic night mode function that lowers
the sound level for any period of time specified.
A feature of particular importance for residential
applications is the ‘night set’ mode, which can be set
on site to function over a 9 hour period during which
operating sound is reduced progressively in three
increments of 3dB(A).
A B SO L UT E C OM F O RT
The VRVIII-S system is a highly efficient solution
for small commercial buildings requiring heating
and cooling of up to 8 zones. A mix of ducted and
duct-free indoor units can be combined to provide
individual comfort and ease of installation. Imagine
a small office application with the reception, the
meeting room, the president’s office; all part of
the same system but yet able to have different set
temperatures or being shut off without affecting
other areas, realizing tremendous energy savings
compared to traditional centralized systems.
VRVIII-S
DAIKIN AC
3
Intelligent to the core
At the core of the VRVIII®-S system
is built-in intelligence that gives you
independent zoning control with
maximum flexibility and energy
savings. With the ability to connect
up to eight indoor units to one
outdoor unit, the space-saving
VRVIII-S system is ideal for most
light commercial or residential
projects.
VRVIII-S Features:
n
All major components of the VRVIII-S
outdoor units are engineered and
manufactured by Daikin to ensure
maximum performance, efficiency
and Absolute Comfort
1
2
3
4
Noise-Reducing Air Inlet Bell
Mouth & Aero Spiral Fan. Bell
mouth guides and bent-edge fan
blades also reduce turbulence.
DC Fan Motor. Improves
efficiency compared to
conventional AC motors, especially
during low-speed rotation.
Super Aero Grille. Spiralshaped ribs align with direction
of discharge flow to minimize
turbulence and reduce noise.
Reluctance Brushless DC
Compressor. Significantly
increases efficiency over AC
inverter motors by using both
normal and reluctance torque
to produce extra power from
small electric currents.
Single-phase technology is perfect
for light commercial and residential
applications in 36,000 and 48,000
Btu/h models.
n
Smaller capacity allows precise
temperature control over every square
inch of space.
n
Space-saving design and flexible
indoor unit options offer quick and
easy installation.
n
5
The 7S for Success Concept
n
Soft sound level operation ensures
a comfortable fit in any room.
n
Single-supplier reliability. The
system - factory engineered and
80% complete upon delivery - is
fully optimized by Daikin, plus has
self-Diagnostics and one of the
best warranties in the industry.
n
Straightforward maintenance and
service with self diagnosis function.
Superior energy efficiency results in
lower operating costs especially under
partial load conditions.
e-Bridge Circuit. Increases
evaporative capacity by adding
super cooling prior to expansion
cycle. This prevents accumulation
of refrigerant in the condenser for
greater energy efficiency.
5
2
7
6
7
i-Demand Function. Optimizes
energy consumption by using a
current sensor to minimize the
difference between actual and
predefined power consumption.
1
e-Pass Heat Exchanger.
Improves operating efficiency by
preventing heat transfer from the
overheated gas section of the
sub-cooled liquid section.
3
6
4
Suction
Ferrite
magnets
Neodymium
magnets
Scroll
Low pressure side
Discharge
High pressure side
A B SO L U T E C O MF O RT
4
Note:
Data are based on studies conducted under
controlled conditions at a Daikin laboratory.
DAIKIN AC
Reluctance
DC motor
VRV Indoor Units
Capacity Range
Indoor Type
MBH
7.5
09
12
18
24
30
36
42
48
54
72
96
Tons
0.6
0.75
1
1.5
2
2.5
3
3.5
4
4.5
6
8
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
FXTQ_PAVJU
Vertical air handling unit
(horizontal right
configuration is possible)
FXMQ_PVJU
Ducted
DC ducted concealed
ceiling (medium static)
OSA
OSA
OSA
FXMQ_MVJU
Concealed ceiling unit
(medium static)
FXDQ_MVJU
Slim duct built-in
concealed ceiling unit
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
OSA
FXFQ_PVJU
Round flow ceiling
mounted cassette
OSA
OSA
OSA
FXZQ_M7VJU
2’ x 2’ 4-way ceiling
mounted cassette
OSA
FXAQ_MVJU
Duct-free
Wall mounted unit
FXHQ_MVJU
Ceiling suspended unit
FXLQ_MVJU
Floor standing unit
FXNQ_MVJU
FXMQ_MFVJU
100% Outside Air
Processing Unit
OSA
Available (11 types, 51 models)
Condensate pump standard on model
OSA
OSA
Outside air connection possible on model
Note: 72 MBH and 96 MBH indoor units are not connectable to the VRVIII-S system
A B SO L UT E C OM F O RT
Ventilation
Concealed floor standing
unit
VRVIII-S
DAIKIN AC
5
VRVIII-S Specifications
Condensing Units Specifications
VRVIII-S 208-230V Heat Pump
Model
Name
Cooling Capacity1
Cooling Input Power
Heating Capacity2
Heating Input Power
Performance
Operation Range - Cooling
Operation Range - Heating
Power
Sound Pressure Level @ 3ft.
Refrigerant Type and Quantity
Liquid Pipe (Main Line)
Suction Gas Pipe (Main Line)
Refrigerant Piping
Vertical Pipe Length
Actual Pipe Length (Equivalent Length)
Total Pipe Length
Connectable Indoor Unit Ratio
Connection Ratio
Number of Indoor Units
Weight
Unit
Dimensions (H x W x D)
Air Flow
Fan
External Static Pressure
Fan Motor Output and Quantity
Maximum Overcurrent Protection (MOP)
Electrical
Minimum Circuit Amps (MCA)
Compressor Rated Load Amps (RLA)
Compressor Type
Compressor
Compressor Set-Up
Compressor Capacity Control
Btu/h
kW
Btu/h
kW
°F DB
°F DB/°FWB
V/ph/Hz
dB(A)
(lbs.)
in.
in.
ft.
ft.
ft.
%
Qty.
lbs.
in.
cfm
W.G.
kW (Qty.)
A
A
A
%
3-Ton
4-Ton
RXYMQ36PVJU
RXYMQ48PVJU
36,000
47,500
Refer to Engineering Data Book
42,000
52,500
Refer to Engineering Data Book
23 - 115
23 - 115
0 - 64/-5 - 60
0 - 64/-5 - 60
208-230/1/60
208-230/1/60
58
58
R-410A (8.8)
R-410A (8.8)
3/8 (Flare)
3/8 (Flare)
5/8 (Flare)
5/8 (Flare)
164
164
492
492
984
984
50-130%
6
8
283
283
52 5/16 x 35 7/16 x 12 5/8
3,740
3,740
0.070
0.070
30
30
27.0
27.0
17.6
23.3
Daikin G-Type Scroll Daikin G-Type Scroll
1 INV
1 INV
29 - 100
29 - 100
1 Indoor temp. : 80°F DB or 67°F WB/Outdoor temp. : 95°F DB/Equivalent piping length : 25ft (7.5m), level difference: 0 ft.
2 Indoor temp. : 70°F DB, 70°F DB/Outdoor temp. : 47°F DB or 43°F WB/Equivalent piping length: 25ft. (7.5m), level difference: 0ft.
1. Where there is an obstacle on the suction side:
(a) No obstacle above
(1) Stand-alone installation
• Obstacle on the suction side only
A B SO L U T E C O MF O RT
6
2. Where there is an obstacle on the discharge side:
(a) No obstacle above
(1) Stand-alone installation
DAIKIN AC
492ft. Linear piping length
• Obstacle on both sides
49ft. Level difference
between indoor units
The unit values are in inches
In case of series installation, some space between the
units is needed for wiring with conduit and servicing.
Piping Specifications
Ft.
Linear piping between condensing unit and furthest located fan coil
492 (580)
unit (equivalent)
Total “one-way” piping in the complete piping network
984
Vertical (height) separation between the condensing unit and the fan
164 (130)
coil units (if outdoor unit is below)
Vertical (height) separation between fan coil units
49
Linear piping between first REFNET and furthest located fan coil unit
130
164ft. Vertical separation between
indoor and outdoor units
Installation Space
VRVIII-S Specifications
Certified Performance Data
Indoor Units Combination
Nominal
Cooling
Capacity
(Btu/h)
Non-Ducted Indoor Units
36,000
Ducted Indoor Units
36,000
Mixed Ducted and Non-Ducted Indoor Units
EER
COP
COP
SEER
Nominal
Heating
Capacity
(Btu/h)
11.5
14.9
42,000
2.8
26,000
2.0
9.9
14.0
42,000
2.9
29,500
2.1
8.4
36,000
10.7
14.45
42,000
2.85
27,750
2.05
8.15
Non-Ducted Indoor Units
47,500
9.0
15.1
52,500
2.6
33,000
2.0
9.1
Ducted Indoor Units
47,500
9.0
13.2
52,500
2.7
36,500
2.0
8.8
Mixed Ducted and Non-Ducted Indoor Units
47,500
9.0
14.15
52,500
2.65
34,750
2.0
8.95
Outdoor Unit
RXYMQ36PVJU
RXYMQ48PVJU
VRVIII-S Accessories
Cool/Heat Selector
Fixing Box
Refnet header
Distributive
Piping
Refnet joint
Central Drain Plug
Fixture for Preventing Overturning
Wire Fixture for Preventing Overturning
Wind Baffle (2 required per unit)
95 °F
RXYMQ36-48PVJU
KRC19-26A
KJB111A
KHRP26M22H (Max. 4 branches)
KHRP26M33H (Max. 8 branches)
KHRP26A22T
KKPJ5F180
KPT-60B160
K-KYZP15C
KPW5E80
47 °F
Low Heating
Capacity (Btu/h)
17 °F
HSPF
7.9
REFNET®
REFNET joints distribute an equal flow
of refrigerant in every branch of the
piping network.
Choosing the right controls
Daikin controls are optimized for VRV technology and offers highly scalable solutions for all
applications and budgets. It also allows for lower cost alternatives to traditional energy management
systems when centralized control is required.
Project Requirements
Daikin VRV Controls
BRC1E71
Navigation
BRC2A71
Simplified
DCS302C71
Centralized
DCS301C71
Unified
DCS601C71
Intelligent Touch
Intelligent
Manager
BACnet
Interface
LonWorks
Interface
Simple individual zone control
Individual zone control with 7-day programmable scheduling
Multi-zone control without scheduling functions
Basic central point on/off control of all air handling units
Advanced multi-zone control of small to medium size projects
Advanced multi-zone control of large commercial projects
Advanced multi-zone control with scheduling logic and calender
Automatic cooling/heating changeover for heat pump systems
Single input batch shutdown of all connected air handlers
Web browser control and monitoring via Intranet and Internet
E-mail notification of system alarms and equipment malfunctions
Multiple tenant power billing for shared condenser applications
Temperature set-point range restrictions
Graphical user interface based upon a PC platform
A B SO L UT E C OM F O RT
Start/stop control of ancillary building systems1
Daikin VRV integration with BACnet based automation systems
Daikin VRV integration with LonWorks based automation systems
1
Requires one or more DEC102A51-US2 Digital Input/Output units.
Native application or feature for this device.
Dependent upon capabilities of the third party energy management system.
VRVIII-S
DAIKIN AC
7
WARNINGS:
•Always use a licensed installer or contractor to install this product. Do not try to install the product yourself. Improper installation can
result in water or refrigerant leakage, electrical shock, fire or explosion.
•Use only those parts and accessories supplied or specified by Daikin. Ask a licensed contractor to install those parts and accessories.
Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage,
electrical shock, fire or explosion.
•Read the User’s Manual carefully before using this product. The User’s Manual provides important safety instructions and warnings.
Be sure to follow these instructions and warnings.
For any inquiries, contact your local Daikin sales office.
© 2011 Daikin Industries, Limited.
Daikin , Daikin AC Absolute Comfort, and its design, VRV and REFNET ™ are trademarks pending or registered trademarks of Daikin Industries, Limited. All rights reserved. LonWorks and LON are
registered trademarks of Echelon Corporation. BACnet is a Data Communication Protocol for Building Automation and Control Networks, developed under the auspices of the American Society of Heating,
Refrigerating and Air-Conditioning Engineers (ASHRAE).
®
®
®
®
®
®
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING DIVISION
JMI-0107
Scope of Registration:
THE DESIGN/DEVELOPMENT AND MANUFACTURE
OF COMMERCIAL AIR CONDITIONING, HEATING,
COOLING, REFRIGERATING EQUIPMENT,
COMMERCIAL HEATING EQUIPMENT, RESIDENTIAL
AIR CONDITIONING EQUIPMENT, HEAT RECLAIM
VENTILATION, AIR CLEANING EQUIPMENT,
MARINE TYPE CONTAINER REFRIGERATION UNITS,
COMPRESSORS AND VALVES.
Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.
Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR THEM.
All of the Daikin Group's business
facilities and subsidiaries in Japan
are certified under the ISO 14001
International standard for
environmental management.
JQA-1452
Daikin AC (Americas), Inc.
Dealer Information
PCVSUSE11-02B
Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in
this brochure without notice and without incurring any obligations.
DAIKIN AC
A B SO L UT E C OM F O RT
1645 Wallace Drive, Suite 110
Carrollton, TX 75006 USA
www.daikinac.com
info@daikinac.com
866-4DAIKIN
972-245-1510
8