SUBMITTAL AM018FNMDCH/AA
Samsung DVM S Series, MSP (Medium Static) Ducted Unit
Job Name
Purchaser
Submitted to
Unit Designation
Location
Engineer
Reference
Schedule #
Approval
Construction
Specifications
Cooling (Btu/h)
18,000 (13,800 SH)
Heating (Btu/h)
20,000
Nominal Capacity
Performance
&RQGHQVDWH
3LQWV+RXU
Voltage
ø/V/Hz
Power
4.86
1 / 208-230 / 60
Nominal Running Current (A)
Type
Fan
1.4
Sirocco (2)
Type
Motor
Non Feedback SSR (1)
Output (W)
&)08/
H/M/L
External Static
Pressure
Standard
"WC
0.157
Min. / Max.
"WC
0 - 0.315
Type
Piping
Connections
Unit
Dimensions
Sound Level
Accessories
512 / 459 / 406
R410A
Control Method
• High-voltage terminal block temperature sensor to disable unit in
the event overheating of power connection.
124
$LUIORZ
Refrigerant
• Compatible with Samsung DVM S and Mini DVM systems:
AM***FXVA*R/AA, AM***FXVA*H/AA, AM0**FXMDCH/AA only.
Electronic Expansion Valve
Liquid (flare)
Inches
1/4
Suction (flare)
Inches
1/2
Drain
rain
IQFKHV
OD 1 1/4, ID 1
WXHXD
Inches
35 7/16 X 10 1/4 X 18 7/8
WHLJKW
OEV
Duct Connections
(inches)
Supply
33 1/4 X 7 9/32
Return,'
27 1/2 X 6 1/4
H / 0L
dB
64
35 / 33 / 31
• Discharge air temperature sensor with target discharge
temperature control capability (consult technical data books or
Quietside Corporation for full details)
Construction
The unit shall be constructed of insulated, galvanized steel
Heat Exchanger
The heat exchanger shall be mechanically bonded fin to copper
tube
Indoor Fan
Indoor fan is a twin, backward curved centrifugal type with a single
fan motor
Three fan speed settings and auto setting
Controls
The unit shall be operated via a wireless or wired remote control
with DDC type signal
The unit shall integrate with the Samsung NASA Controls Network
Solution
Controls shall integrate with a BMS system
Condensate Pump
MDP-M075SGU3D
Filter Box
FB-M1824
External Contact Control
MIM-B14
Air Filtration
The unit does not include an air filter as standard
Wireless Receiver Kit
MRK-A10N
Filtration is field provided/installed
Safety Certifications
ETL & ETLc
Control wiring shall be 2 X 16 AWG shielded wire
Pressure drop across the filter must be factored into the total ESP.
Nominal cooling capacities are based on: Indoor temperature: 80 ͼF DB, 67ͼF WB. Outdoor temperature: 95 ͼF DB, 75ͼF WB.
Nominal heating capacities are based on: Indoor temperature: 70 ͼF DB, 60ͼF WB. Outdoor temperature: 47 ͼF DB, 43ͼF WB.
Samsung and Quietside maintains a policy of ongoing development, specifications are subject to change without notice.
QS-DVMS-042014A
www.SamsungDVM-S.com
888-699-6067
2 of 2
Page
SUBMITTAL AM018FNMDCH/AA
Samsung DVM S Series, MSP (Medium Static) Ducted Unit
3" 1/2"
4 5/8"
Unit Bottom
Recommended Service Access (min.)
(Verify Local Codes)
Suction
6
18 7/8"
15 5/8" Suspension Point
7
3 3/8"
8 3/4"
18 7/8"
TOP
23 5/8"
35 1/4" Supply Outlet Duct Flange
35 7/16"
36 7/8" Suspension Point
8
Suspension Bolt Hanger
Outlet Flange
10 1/4"
7 9/32"
Discharge
2
Suction
1
3"
Supply Side
4
3"
5 1/4"
5 5/8"
3
5
No.
Description
Name
Liquid Pipe Connection
Ø " Flare
2
Gas Pipe Connection
Ø " Flare
3
Drain Pipe Connection, Without Optional Condensate Pump
OD 1 1/4", ID 1"
4
Drain Pipe Connection, With Optional Condensate Pump
OD 1 1/4", ID 1"
5
Controls Box
-
6
Conduit for Power & Communication Wiring
-
7
Return Air Side
-
8
Supply Air Outlet Duct Flange
-
1
)DQ3HUIRUPDQFH'DWD
Inspection Opening Requirements
Unit Depth + 2"
+
/
/
B=23 5/8"
In applications where there is not a tile ceiling, an inspection hole is required.
If height between ceiling and structure is 3.25' or more, inspection opening "B" is recommended.
If height between ceiling and structure is less than 3.25', inspection opening "A" and "B" is recommended.
(verify state and local codes).
Unit Clearance From Structure
6WUXFWXUH
([WHUQDO6WDWLF3UHVVXUHLQ+2
A=W+4"
+
Unit Width (W)
/
+
13/16" or more
Unit
13/16" or more
Ceiling
+
/
$LU)ORZ5DWH&)0
Service Access
www.SamsungDVM-S.com
/ /RZ+ +LJK