York | THRU H*RA036 THRU 090 | Corel Ventura - N2_1Y.CHP

OUTDOOR
SPLIT-SYSTEM AIR-CONDITIONER
3 TO 5 TONS
INSTALLATION
INSTRUCTIONS
(TABULAR DATA)
Supersedes: 550.46-N2.1Y (298)
550.46-N2.1Y (1098)
035-15808-601B
MODELS H*RA036 THRU 060
3 Phase - 10 SEER
PHYSICAL AND ELECTRICAL DATA
H1RA
036S25
MODEL
UNIT SUPPLY VOLTAGE
H1RA
060S46
460 - 3 - 60
432 to 504
17.3
21.3
8.0
8.3
25
30
35
15
15
15
Recip
Recip
Scroll
Recip
Recip
Scroll
10.9
11.7
16.0
5.8
6.1
8.0
78
78
125
40
39
67
No
No
No
No
No
No
RATED LOAD
1.4
1.3
1.3
.8
.7
8
18
22
22
18
22
22
RATED HP
1/4
1/5
1/4
1/4
1/5
1/4
COMPRESSOR TYPE
RATED LOAD
LOCKED ROTOR
CRANKCASE HEATER
FAN DIAMETER INCHES
10.8
NOMINAL RPM
1,100
850
850
1,100
850
850
NOMINAL CFM
2,750
3,250
3,450
2,750
3,250
3,450
23.58
FACE AREA SQ. FT.
COIL
H1RA
048S46
15.0
MAXIMUM OVERCURRENT DEVICE AMPS2
FAN MOTOR
H1RA
036S46
187 to 252
MINIMUM CIRCUIT AMPACITY
FAN MOTOR AMPS
H1RA
060S25
208 / 230 - 3 - 60
NORMAL VOLTAGE RANGE1
COMPRESSOR AMPS
H1RA
048S25
9.15
15.72
23.58
9.15
15.72
ROWS DEEP
1
1
1
1
1
1
FIN / INCH
18
18
18
18
18
18
LIQUID LINE OD (Factory Supplied)
3/8
3/8
3/8
3/8
3/8
3/8
VAPOR LINE OD (Factory Supplied)
3/4
7/8
7/8
3/4
7/8
7/8
3 - 15
7-5
9-7
3 - 15
7-5
9-7
UNIT CHARGE (LBS - OZ)3
3
CHARGE PER FT. (OZ)
.68
.70
.70
.68
.70
.70
OPERATING WEIGHT LBS.
170
206
228
170
206
228
1
Utilization range “A” in accordance with ARI standard 110.
Dual element fuses or HACR circuit breaker. Refer to the NEC for proper wire sizing and length.
3
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other
than 15 feet, add or subtract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.
2
All dimensions are in inches. They are subject
to change without notice. Certified dimensions
will be provided upon request.
DIMENSIONS
C
UNIT
MODEL
HRA
A
LINE SIZE
A1
B
C
036
19
35
23
048
27
37
27
060
39
37
27
1
B
RECOMMENDED
REFRIGERANT
CONNECTION
DIMENSIONS
Includes fan guard
LIQUID
VAPOR
3/8
7/8
3/4
7/8
R-22 SYSTEM CHARGING PROCEDURE
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
OUTDOOR UNIT
UNIT ORIFICE(S)1
FACTORY R-22 CHARGE, LBS.- OZ.
INDOOR COIL
H1RA036
H1RA048
H1RA060
67, 71, 73
81
90
3 - 15
7-5
9-7
COIL ORIFICE2
SYSTEM ORIFICE + ADDITIONAL CHARGE, OZ
G1NA036S17J
67
67 + 7
—
—
G1NA036S21C
67
67 + 7
—
—
G1NA048S21D
78
—
78 + 4
—
G1NA048S24P
78
—
78 + 4
—
G1NA060S24T
87
—
—
87 + 0
G1UA036S17, 21
73
71 + 0
—
—
G1UA048S21, 24
84
75 + 11
81 + 13
—
G1UA060S24
90
—
—
90 + 5
G2FD036S(H)17
75
73 + 4
—
—
G2FD036S(H)21
75
71 + 5
—
—
G2FD042S(H)17
78
—
—
—
G2FD048S(H)21, 24
78
—
81 + 15
—
G2FD060S(H)24
90
—
—
90 + 5
G1NF048SOF
73
67 + 7
—
—
G1NF048SOF
78
—
78 + 4
—
G1NF060SOF
87
—
—
87 + 0
1
These orifices are packed in the instruction/warranty packet of each outdoor unit.
These orifices are factory-mounted in the flow control device of each indoor coil.
A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07...series).
2
3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet
of interconnecting line tubing.
2. Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the following above
table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge.
Total System Charge = Base charge (as shipped) + adder for evaporator + adder for line set
5. If the orifice in the evaporator was changed verify the evaporator nameplate has been marked with the correct orifice size.