Bosch | D7212GV2 | D7212GV2 Control Panel - Bosch Security Systems

Intrusion Alarm Systems | D7212GV2 Control Panel
D7212GV2 Control Panel
www.boschsecurity.com
The D7212GV2 Control Panel provides an integrated
solution for intrusion (commercial and residential) and
residential fire alarm system applications. Monitor
alarm points for intruder or fire alarms while operating
user command centers and other outputs. The
D7212GV2 Control Panel includes a communicator
that sends event reports to selected public switched
telephone network (PSTN) or IP network destinations
through four programmable route groups. Program all
system functions on-site through a D5200 Programmer
or remotely through Remote Programming Software
(RPS).
The D7212GV2 Control Panel provides up to 40
individually identified points. Each point
accommodates normally-open and normally-closed
devices with end-of-line (EOL) resistor supervision.
Each point is programmable for fire, fire supervisory,
or intrusion applications.
Notice
The D7212GV2 Control Panel is available
exclusively to Bosch Certified Security Dealers
(BCSD).
u
Fully integrated intrusion and fire functions allow
users to interface with one system instead of two
u
Conettix IP based communication option provides
high-speed, secure alarm transport and control
u
Four programmable areas with perimeter and
interior partitioning
u
40 points with flexible configuration options to meet
application specific requirements
u
Your choice of vacuum fluorescent or ATM style user
interface command centers
Functions
Programmable Outputs
•
•
•
•
•
•
2 A alarm power at 12 VDC
1.4 A auxiliary power at 12 VDC
Four alarm output patterns
Automatic bell test
Programmable bell shut-off timer
Three on-board outputs, 24 off-board programmable
outputs
System Response
•
•
•
•
•
•
31 custom point indexes, including fire supervisory
Selectable point response time
Cross point capability
Fire alarm verification
Watch mode
Scheduled events (skeds) arm, disarm, bypass and
unbypass points, control relays, and control authority
levels
Area Configurations
Area programming offers a wide selection of different
system configurations. Each area is assigned an
account number to define annunciation, control, and
reporting functions. Multiple areas can be linked to a
shared area which is automatically controlled (hallway
or lobby). Area arming can be conditional on other
areas (master or associate).
2 | D7212GV2 Control Panel
User Interface
• Supervises up to eight command centers (up to 32
non-supervised command centers can be used)
• Custom command center text
• Four custom functions
• Full function command menu including custom
functions
• Each user has authority by area and 16-character
name
• 14 custom authority levels control user’s authority to
change, add, delete passcodes, delete access control
tokens, delete cards, disarm, bypass points, and
initiate system tests
• Up to 40 programmable, scheduled events and up to
16 event functions for controlling relays, enabling
passcodes and windows, and automatically arming
and disarming areas
• Adjustable brightness or volume for command center
display or sounder
• One parallel printer
The D7212GV2 provides on-premises point and system
status annunciation. The fully selectable user interface
customizes command center displays and allows users
to create appropriate menu items and functions.
Function lists can help a user become familiar with the
operation of the control panel and custom functions
allow users to perform complex functions with a few
keystrokes. Each function can be programmed and
identified by sixteen characters of custom text and can
contain up to 32 keystrokes.
Notice
At least one command center per system is
recommended.
Two Man Rule
Two Man Rule requires two unique passcodes on the
same command center to disarm an area. Without the
second passcode, the system denies entry. Two Man
Rule requires the presence of two people at opening,
providing added security.
Early Ambush
Early Ambush requires two passcode entries on the
same command center. Enter the same passcode
twice or have two unique passcodes, depending on
the configuration. The first entry disarms the area and
the second entry stops a timer programmed to send a
duress event. If the second entry does not occur
within the programmed time, the system generates a
duress event. Early Ambush allows users to inspect the
premises and use the system to confirm that the area
is safe to enter, providing added security.
Easy Exit Control
The D7212GV2 Control Panel changes from one armed
state to another armed state without disarming. For
example, if you change the state from Master Arm to
Perimeter Arm, the control panel complies and reports
the change. Easy Exit Control reduces the number of
keystrokes, simplifying system operation.
Programmable Passcode-controlled Menu List
The system prompts users to enter a passcode prior to
viewing the command center menu. The command
center display shows the user the menu options
allowed according to the user’s authority level.
Passcode-controlled menus provide users only with
the options and information pertinent to them,
simplifying system operation.
Passcode Follows Scope
Use Passcode Follows Scope to restrict passcode
arming and disarming only to the command center's
immediate local area, even if the command center can
report events from other areas. Passcode follows
scope simplifies the arming and disarming procedure
without limiting any other command center command
capabilities.
Passcodes
User passcodes contain three to six digits. Assign each
user one of 14 customized authority levels in each
area. Restrict passcodes to operate only during certain
times.
The Two Man Rule and Early Ambush options require
two passcodes, providing additional security in
financial establishments such as banks.
Communications
The D7212GV2 prioritizes and sends reports to four
route groups. Each group has a programmable primary
and backup destination.
The D7212GV2 works with the D6600 NetCom
Communications System using a DX4020 Network
Interface Module. It has programmable anti-replay antisubstitution features when using a DX4020.
The Modem IIIa2 Communications Format, available
with Bosch receivers, adds reporting capabilities such
as:
•
•
•
•
Individual point numbers and text
Opening or closing reports by area number
Remote programming attempts
Diagnostic reports
Security and Fire Detection
The D7212GV2 Control Panel provides eight on-board
points, and up to 32 additional off-board points
(depending on model and expansion interfaces). You
can program individual points to monitor all types of
burglar alarms, fire alarms, and supervision devices.
Event Log
The event log stores up to 1,000 local and transmitted
events. The event log includes time, date, event, area,
point, and user number. View the event log from select
command centers or remotely retrieve event
information using RPS. RPS operators can retrieve
events periodically using one phone call, rather than
receiving several calls each day. When the event log
reaches a programmed threshold of stored events, it
can send an optional report to a receiver.
3 | D7212GV2 Control Panel
Scheduled Events (Skeds)
The internal clock and calendar start individually
scheduled events (skeds). Skeds perform functions
such as arm or disarm, relay control, or point
bypassing. The D7212GV2 Control Panel offers:
Installation/configuration notes
Compatible Products
Keypads
• 40 scheduled events with up to 16 different functions
available
• Eight opening windows and eight closing windows
• Eight user windows
• Day-of-week, date-of-month, or holiday only schedules
• Four holiday schedules of 366 days each (leap year)
Fire Test
When a user activates Fire Test Mode, the control
panel suppresses all reports to the central station. The
command center and annunciator show all testing
data. An automatic sensor reset feature saves time;
you do not need to reset the sensors manually. At the
end of test, the command center shows the number of
untested points.
D1260 Series Keypads
(D1260, D1260W, D1260R, D1260BLK,
D1260B)
D720 Series Keypads
(D720, D720W, D720R, D720B)
D1255 Series Keypads
(D1255, D1255W, D1255R, D1255B)
D1256 and D1256RB Fire Keypads
D1257 and D1257RB Remote Fire Alarm
Annunciator
D279A Independent Zone Control
Detectors
D278S Four-wire Addressable Detector Base
D285/TH Photoelectric Smoke Detector Heads
Programming, Diagnostics and Controls
Users can program on-site with a D5200 Programmer,
or program remotely through RPS. A programmable
system passcode prevents unauthorized remote
programming.
D7212GV2 Control Panels accommodate up to four
separate telephone numbers for primary, alternate,
and backup receivers for automatic test reports.
When resetting alarms or arming or disarming a
system, the user is identified by name and number.
D298S Addressable Detector Base
D7050 Series Addressable Photoelectric Smoke
and Smoke Heat Detector Heads
F220-B6PM/S Addressable Detector Bases with
POPITs
MX250 Series Smoke Detectors
MX775i Addressable PIR Detector
MX794i Long Range Multiplex PIR Detector
Certifications and approvals
MX934i Addressable PIR Detector
Region
Certification
MX938i Addressable PIR Detector
USA
UL
ZX776Z PIR Detector
Canada
AMCX: Central Station Alarm Units
(UL1610, UL1635), AMCX7: Central
Station Alarm Units Certified for Canada
(CAN/ULC-S304-M88, UL 1635),
AMTB: Control Panels, SIA False Alarm
Reduction (ANSI/SIA CP-01-2000),
AOTX: Local Alarm Units (UL464,
UL609), AOTX7: Local Alarm Units Certified for Canada (CAN/ULC-S303, CAN/
ULC-S525), APAW: Police Station Alarm
Units (UL365, UL464), APAW7: Police
Station Alarm Units Certified for Canada
(CAN/ULC -S303, CAN/ULC-S304,
CAN/ULC-S525), APOU: Proprietary
Alarm Units (UL1076), APOU7: Proprietary Alarm Units Certified for Canada
(ULC/ORD-C1076), NBSX: Household
Burglar Alarm System Units (UL1023),
NBSX7: Household Burglar Alarm System Units Certified for Canada (ULC/
ORD-C1023), UTOU: Control Units and
Accessories - Household System Type
(UL985), UTOU7: Control Units and Accessories - Household System Type Certified for Canada (ULC-S545)
CSFM
7167-1615:0100 CONTROL UNIT
(HOUSEHOLD)
FCC
AJ9-MUL-46532-AL-E
IC
1249A-GV2
ZX794Z Long Range PIR Detector
ZX835 TriTech Microwave/PIR Detector
ZX935Z PIR Detector
ZX938Z PIR Detector
ZX970 PIR/Microwave Detector
Bosch conventional detectors, including Blue
Line, seismic, PIR, TriTech PIR Microwave,
photoelectric, heat, and smoke.
Enclosures
D8103 Universal Enclosure
D8108A Attack-Resistant Enclosure
D8109 Fire Enclosure
Magnetic Contacts
Bosch magnetic contacts include recessed,
terminal connection, miniature, overhead door,
and surface mount.
Modules
C900V2 Dialer Capture Module
D113 Battery Lead Supervision Module
D125B Dual Class B Initiating Module
4 | D7212GV2 Control Panel
D127 Reversing Relay Module
ISW‑EN4016SK Survey Receiver
D129 Class A Initiating Module
ISW‑EN5040‑T High‑power Repeater
D130 Auxiliary Relay Module
ISW‑EN1210 Universal Transmitter
(Single‑input)
D185 Reverse Polarity Signaling Module
D192C Notification Appliance Circuit Module
ISW‑EN1210EOL Universal Transmitter with EOL
Resistor
D192G Notification Appliance Circuit Module
ISW‑EN1210SK Survey Transmitter
D928 Phone Line Switcher
ISW‑EN1210W Door‑Window Transmitter with
Reed Switch
D5060 MUX Programmer
ISW‑EN1215EOL Universal Transmitter with Wall
Tamper and EOL Resistor
D8125 POPEX Point Expander
D8128D OctoPOPIT Eight Point Expander
ISW‑EN1215WEOL Door‑Window Transmitter
with Wall Tamper, Reed Switch, and EOL
Resistor
D8125MUX Point Expander
D8125INV Wireless Interface Module
ISW‑EN1223D Water‑resistant Pendant
Transmitter (Double‑button)
D8129 Octo-relay Module
D8130 Door Release Module
ISW‑EN1223S Water‑resistant Pendant
Transmitter (Single‑button)
D9127 Series POPIT Modules
ISW‑EN1223SK Survey Pendant Transmitter
D9131A Parallel Printer Interface Module
ISW‑EN1233D Necklace Pendant Transmitter
(Double‑button)
DS7432 Eight-input Remote Module
DS7457i Series Single Zone Multiplex Input
Modules
ISW‑EN1233S Necklace Pendant Transmitter
(Single‑button)
DS7460i Two-input Module
ISW‑EN1235D Beltclip Pendant Transmitter
(Double‑button)
DS7461i Single-input Multiplex Module
ISW‑EN1235S Beltclip Pendant Transmitter
(Single‑button)
DS7465i Input and Output Module
DX4010i RS-232 Serial Interface Module
DX4020 Network Interface Module
ISW‑EN1235DF Fixed‑location Transmitter
(Double‑button)
Peripheral
Hardware
rvm4c Remote Video Module
ISW‑EN1235SF Fixed‑location Transmitter
(Double‑button)
Communications
Modem IIIa2
Formats
BFSK
Programming
D5200 Series Programmers
ISW‑EN1242 Smoke Detector‑Transmitter
ISW‑EN1247 Glass‑break Sensor Transmitter
ISW‑EN1249 Billtrap Transmitter
ISW‑EN1260 PIR Motion Sensor Transmitter
(Commercial and High‑end Domestic
Applications)
Remote Programming Software (RPS)
SAFECOM Radio
SC2104 Series Slave Communicators
Communicators
SC3100 Series Data Transfer Radio
Communicators
ISW‑EN1261HT PIR Motion Sensor Transmitter
(High‑traffic Areas)
ISW‑EN1262 PIR Motion Sensor Transmitter
(Residential and Low‑traffic Commercial
Applications)
SC4000 Series Full Data Transfer Radio
Communicator
Commercial
ISW‑D8125CW Commercial Wireless Interface
Wireless Products
ISW‑EN7280 Serial Receiver
ISW‑EN4200 Serial Receiver
ISW‑EN4204R LED Receiver
ISW‑EN4216R LCD Receiver
ISW‑EN1265 PIR Motion Sensor Transmitter
(Ceiling‑mount Applications)
Parts included
D7212GV2 Components
Quantity
D7212GV2 Board
1
5 | D7212GV2 Control Panel
Mounting Skirt
1
Faceplate with D7212GV2 Label
1
Technical specifications
Communications
SDI Bus A (+):
9 VDC
4572 m (15,000 ft)
SDI Bus B (-):
9 VDC
4572 m (15,000 ft)
Telephone Connection:
RJ31X or RJ38X
Environmental Considerations
Relative Humidity:
5% to 85% at +30°C (+86°F),
non-condensing
Temperature (Operating):
0°C to +50°C (+32°F to +120°F)
Number of…
Areas:
4
Custom Functions:
4
Programmable Relay Outputs:
27
Events:
Store up to 1,000
Parallel Printers:
1
Passcode Users:
99, plus 1 service passcode
Points:
40 (eight on-board, up to 32
off‑board)
RF Points:
32
SKEDs:
40
Power Requirements
Current Draw (Minimum):
200 mA
Current Draw (Maximum):
500 mA
Output (Alarm):
2 A at 12 VDC
Output (Auxiliary, Continuous
Power, and Switched Auxiliary
combined):
1.4 A at 10.2 VDC to 13.9 VDC
Voltage (Operating):
12 VDC
Voltage (AC):
16.5 VAC 40 VA plug-in
transformer (D1640)
Voltage (DC):
• Up to 2 12 VDC, 7 Ah
sealed lead acid
rechargeable batteries
• Up to 2 12 VDC, 18 Ah
sealed lead acid
rechargeable batteries
The D7212GV2 Control Panel is available exclusively to
Bosch Certified Security Dealers (BCSD).
6 | D7212GV2 Control Panel
D7212GV2 Kit Ordering Information
Components
D7212GV2 Board
D7212GV2-CA Board
D101 Lock and Key Set
D1255 Keypad
D7212GV2K1
1
1
1
1
1
1
1
1
1
2
1
2
D7212GV2K3
1
D7212GV2-CA-K2
1
1
1
1
1
1
2
1
2
1
1
1
2
D7212GV2-CA-K3
Kits
D7212GV2K3W
1
D7212GV2K4
1
D7212GV2-CA-K4
1
1
1
1
1
1
1
1
1
D1255W Keypad (White)
D1260 Keypad
D1640 Transformer
D1640-CA Transformer
D8103 Enclosure
D8125 Addressable Expansion
Module
D9127U POPIT Module
without Tamper
DS835i PIR Detector
D8128D OctoPOPIT
Eight-Point Expander
DX4020 Network
Interface Module
D7212GV2K2
1
1
Components
D7212GV2 Board
D7212GV2-CA Board
D101 Lock and Key Set
D1255 Keypad
D1255W Keypad
(White)
D1260 Keypad
D1640 Transformer
D1640-CA Transformer
D8103 Enclosure
Kits
D7212GV2K1W
1
1
1
D1255W Keypad (White)
D1260 Keypad
D1640 Transformer
D1640-CA Transformer
D8103 Enclosure
DS835i PIR Detector
Components
D7212GV2 Board
D7212GV2-CA Board
D101 Lock and Key Set
D1255 Keypad
D7212GV2-CA-K1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
10
10
D7212GV2-CA-K5
Kits
D7212GV2K5W
1
D7212GV2K6
1
D7212GV2K7
1
D7212GV2K8
1
1
1
1
1
1
1
1
1
D7212GV2K5
1
1
1
1
1
1
1
1
1
1
Ordering information
D7212GV2 Kit with Keypad and PIR Detectors (2) for
Canada
Contains one PCB, one lock and key set, one
transformer, one universal enclosure, two PIR
detectors, and one D1260 Keypad.
Order number D7212GV2-CA-K2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
D7212GV2 Kit with Keypad and POPIT Modules (10) for
Canada
For use in Canada. Contains one PCB, one lock and
key set, one transformer, one universal enclosure, one
expansion module, ten POPIT modules, and one
D1255 Keypad.
Order number D7212GV2-CA-K3
7 | D7212GV2 Control Panel
D7212GV2 Kit with Keypad and POPIT Modules (10) for
Canada
For use in Canada. Contains one PCB, one lock and
key set, one transformer, one universal enclosure, one
expansion module, ten POPIT modules, and one
D1260 Keypad.
Order number D7212GV2-CA-K4
D7212GV2 Kit with Keypad and Network Interface Module
Contains one PCB, one lock and key set, one
transformer, one universal enclosure, one D1255
Keypad, and one DX4020 Network Interface Module.
Order number D7212GV2K5
D1224 Battery (12 V, 26‑28 Ah)
A 12 V sealed lead‑acid battery for standby and
auxiliary power with two bolt‑fastened terminals.
Includes hardware for attaching battery leads or spade
connectors.
Order number D1224
D1238 Battery (12 V, 38 Ah)
A 12 V sealed lead-acid battery for standby and
auxiliary power with two bolt‑fastened terminals.
Includes hardware for attaching battery leads or spade
connectors.
Order number D1238
D1640 Transformer
Accessories
System transformer rated at 16.5 VAC, 40 VA.
ICP‑EZTS Dual Tamper Switch
Order number D1640
Combination tamper switch with a wire loop for
additional tamper outputs.
D1640-CA Transformer
Order number ICP-EZTS
For use in Canada. System transformer rated at
16.5 VAC, 40 VA.
D101 Lock and Key Set
Order number D1640-CA
Short-body lock set with one key supplied. Uses the
D102 (#1358) replacement key.
D8103 Enclosure
Order number D101
Grey steel enclosure measuring 41 cm x 41 cm x 9 cm
(16 in. x 16 in. x 3.5 in.).
D122 Dual Battery Harness
Order number D8103
Harness with circuit breaker. Connects two batteries
to a compatible control panel.
Order number D122
D122L Dual Battery Harness with Long Leads
Color-coded harness with circuit breaker and leads
measuring 89 cm (35 in.). Connects 12 V batteries to
compatible control panels.
Order number D122L
D126 Standby Battery (12 V, 7 Ah)
A rechargeable sealed lead‑acid power supply used as
a secondary power supply or in auxiliary or ancillary
functions.
D8108A Attack Resistant Enclosure
Grey steel enclosure measuring 41 cm x 41 cm x 9 cm
(16 in. x 16 in. x 3.5 in.). UL Listed. Includes lock and
key set. Requires the D2402 Mounting Plate.
Order number D8108A
D9002‑5 Mounting Skirt
Mounts inside D8103, D8108A, and D8109 enclosures.
Can accept up to six standard 7.62 cm x 12.7 cm (3 in.
x 5 in.) cards.
Order number D9002-5
D136 Plug‑In Relay
D137 Mounting Bracket
Maximum rating is 1 A at 24 VDC or 2 A at 12 VDC.
Available individually (D136) or in a package of 25
(D136‑25).
Used to mount accessory modules in D8103, D8108A,
and D8109 enclosures.
Software Options
Order number D126
Order number D137
D138 Mounting Bracket, Right Angle
Used to mount accessory modules in D8103, D8108A,
and D8109 enclosures.
Order number D138
D1218 Battery (12 V, 18 Ah)
A 12 V sealed lead‑acid battery for standby and
auxiliary power with two bolt‑fastened terminals.
Includes hardware for attaching battery leads or spade
connectors
Order number D1218
Order number D136
RPS Kit (LPT)
Account management and control panel-programming
software with LPT connection.
Order number D5500C-LPT
RPS Kit (USB)
Account management and control panel programming
software with USB security key (dongle).
Order number D5500C-USB
8 | D7212GV2 Control Panel
Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2013 | Data subject to change without notice
2494115723 | en, V1, 01. Oct 2013
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
China:
America Latina:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
201 Building, No. 333 Fuquan Road
Via Anhanguera, Km 98
North IBP
CEP 13065-900
Changning District, Shanghai
Campinas, Sao Paulo, Brazil
200335 China
Phone: +55 19 2103 2860
Phone +86 21 22181111
Fax: +55 19 2103 2862
Fax: +86 21 22182398
latam.boschsecurity@bosch.com
www.boschsecurity.com.cn
www.boschsecurity.com
Download PDF