Envire | windsor | Specifications | envire windsor Specifications

SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED PAPER.
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
PELLET STOVE
WINDSOR
TECHNICAL MANUAL
����
Contact your building or fire officials about restrictions and
installation inspection requirements in your area.
PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS
PELLET-BURNING ROOM HEATER. FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.
50-1578
Table of Contents
Safety Warnings & Recommendations.........................................................................3
Installation...............................................................................................................6
Rating Label Location.....................................................................................6
Deciding Where to Locate your Pellet Appliance................................................6
Removing Pellet Stove From Pallet...................................................................6
Dimensions & Specifications............................................................................7
Clearances to Combustibles.............................................................................8
Alcove Clearances...........................................................................................8
Vent Termination Requirements.......................................................................9
Exhaust And Fresh Air Intake Locations..........................................................10
Outside Fresh-Air Connection.........................................................................10
Corner Through Wall Installation....................................................................11
Horizontal Exhaust Through Wall Installation..................................................11
Vertical Rise with Horizontal Termination Installation (Recommended)..............13
Through Concrete Wall With Vertical Rise Installations.....................................13
Inside Vertical Installations............................................................................14
Outside Vertical Installations..........................................................................15
Hearth Mount Installation..............................................................................16
Installation with Exterior Mounted Exhaust Blower...........................................17
Through Wall Vertical Installation With Exhaust Blower....................................19
Thermostat Installation.................................................................................20
Slider/Damper Setting...................................................................................20
Installation..............................................................................................................21
Troubleshooting......................................................................................................22
Wiring Diagram.......................................................................................................25
Parts List - Components...........................................................................................26
Parts List - Cast.......................................................................................................28
Parts Diagram - Components....................................................................................29
Parts Diagram - Steel & Cast....................................................................................30
Installation Data Sheet............................................................................................31
2
Safety Warnings & Recommendations
* This manual is designed for the technician in conjunction with the owner’s manual. *
Please read this entire Owner’s Manual before installing or operating your ENVIRO Pellet
Stove. Failure to follow these instructions may result in property damage, bodily injury or
even death. Any unauthorized modification of the appliance or use of replacement parts
not recommended by the manufacturer is prohibited. All national and local regulations and
European Standards shall be complied with when installing this appliance.
Caution: Do not connect to any air distribution duct or system.
Warning: Parts of the appliance, especially the external surfaces, will be hot to touch when
in operation so use due care and the fire gloves provided. Never place wood, paper, furniture,
drapes or other combustible materials within 80cm (311⁄2”) of the front of the unit, 20cm (77⁄8”) from
each side, and 10cm (4”) from the back of the unit. Do not let children or pets touch it when it is hot.
To prevent the possibility of a fire, ensure that the appliance is properly installed by adhering to the
installation instructions. An ENVIRO dealer will be happy to assist you in obtaining information with
regards to your local building codes and installation restrictions.
FIRE EXTINGUISHER AND SMOKE DETECTION: All homes with a pellet burning stove should have
at least one fire extinguisher in a central location known to all in the household. Smoke detectors should
be installed and maintained in the room containing the stove when installing and operating a pellet
burning appliance. If it sounds the alarm, correct the cause but do not deactivate. You may choose to
relocate the smoke detection devise within the room; DO NOT REMOVE THE SMOKE DETECTOR FROM
THE ROOM.
CHIMNEY OR RUN AWAY FIRE: Call local fire department. Close the draft fully. Extinguish the fire
in the burn pot liner with a cup of water and close the door. Examine the flue pipes, chimney, attic, and
roof of the house, to see if any part has become hot enough to catch fire. If necessary, spray with fire
extinguisher or water from the garden hose. IMPORTANT: Do not operate the stove again until you are
certain the chimney and its lining have not been damaged.
FUEL: This pellet stove is designed and approved to only burn wood pellet fuel with up to 3% ash content.
Dirty fuel will adversely affect the operation and performance of the unit and may void the warranty.
Check with your dealer for fuel recommendations. THE USE OF CORDWOOD IS PROHIBITED BY
LAW. When filling fuel hopper, open lid on top of unit, check hopper for foreign objects, empty the
bag into the hopper, DO NOT OVER FILL, and ensure hopper lid closes completely. DO NOT use this
appliance as an incinerator. DO NOT use unsuitable and non recommended fuels, including liquid fuels.
KEEP ASH PAN FREE OF RAW FUEL. DO NOT PLACE UNBURNED OR NEW PELLET FUEL IN ASH PAN.
A fire in the ash pan may occur.
SOOT: Operation of the stove with insufficient combustion air will result in the formation of soot which
will collect on the glass, the heat exchanger, the exhaust vent system, and may stain the outside of the
house. This is a dangerous situation and is inefficient. Frequently check your stove and adjust the slider/
damper as needed to ensure proper combustion. See: “SLIDER/DAMPER SETTING”.
3
Safety Warnings & Recommendations
CLEANING: There will be some build up of fly ash and small amounts of creosote in the exhaust. This
will vary due to the ash content of the fuel used and the operation of the stove. It is advisable to inspect
and clean the exhaust vent semi-annually or every two tons of pellets. The appliance, flue gas connector
and the chimney flue require regular cleaning. Check them for blockage prior to re-lighting after a
prolonged shut down period.
ASHES: Disposed ashes should be placed in a metal container with a tight fitting lid. The closed container
of ashes should be on a non-combustible surface, well away from all combustible materials pending final
disposal. If the ashes are disposed of by burial in soil or otherwise locally dispensed, they should be
retained in the closed container until all cinders have been thoroughly cooled.
IMPORTANT: The door and ash drawer cover must be kept closed except during ignition, refueling and
removal of residue material to prevent fume spillage.
GLASS: Do not abuse the glass by striking or slamming the door. Do not attempt to operate the stove
with broken glass. The stove uses ceramic glass. Replacement glass must be purchased from an ENVIRO
dealer. Do not attempt to open the door and clean the glass while the unit is in operation or if glass is
hot. To clean the glass, use a soft cotton cloth and mild window cleaner, gas or wood stove glass cleaner,
or take a damp paper towel and dip into the fly ash. This is a very mild abrasive and will not damage the
glass.
ELECTRICAL: The use of a surge protected power bar is recommended. The unit must be
grounded. The grounded electrical cord should be connected to a standard 220-240 volts (2.0-2.3 Amps),
50 hertz electrical outlet and also must be accessible. If this power cord should become damaged, a
replacement power cord must be purchased from the manufacturer or a qualified ENVIRO dealer. Be
careful that the electrical cord is not trapped under the appliance and that it is clear of any hot surfaces
or sharp edges. This unit’s maximum power requirement is 525 watts.
OPERATION: The door and ash drawer cover must be kept closed securely when the unit is in operation
to prevent fume spillage and for proper and safe operation of the pellet stove. Also ensure all gaskets on
the door are checked and replaced when necessary.
CAUTION: When operating during adverse weather, if the unit exhibits dramatic changes in combustion
stop using the unit immediately.
INSTALLATION: Contact your local building or fire official to obtain a permit and any information on
installation restrictions and inspection requirements for your area. All local regulations, including those
referring to national and European Standards need to be complied with when installing this appliance.
Be sure to maintain the structural integrity of your home when passing a vent through walls, ceilings, or
roofs. It is recommended that the unit be secured into its position in order to avoid any displacement. This
appliance must be installed on a floor with an adequate load bearing capacity. If an existing construction
doesn’t meet these prerequisite, suitable measures (e.g. load distributing plate) shall be taken to achieve
it.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
4
Safety Warnings & Recommendations
FRESH AIR: Outside Fresh Air connection is optional. Fresh Air must be connected to all units installed
in “Air Tight Homes” or where required by local codes.
Consider all large air moving devices when installing your unit and provide room air accordingly. NOTE:
Extractor fans when operating in the same room or space as the appliance, may cause problems. Limited
air for combustion may result in poor performance, smoking and other side effects of poor combustion.
The stove’s exhaust system works with negative combustion chamber pressure and a slightly positive
chimney pressure. It is very important to ensure that the exhaust system be sealed and airtight. The ash
pan and viewing door must be locked securely for proper and safe operation of the pellet stove.
Do not burn with insufficient combustion air. A periodic check is recommended to ensure proper
combustion air is admitted to the combustion chamber. Setting the proper combustion air is achieved by
adjusting the slider damper located on the left side of the stove.
Minor soot or creosote may accumulate when the stove is operated under incorrect conditions such as an
extremely rich burn (black tipped, lazy orange flames).
If you have any questions with regards to your stove or the above-mentioned information, please feel
free to contact your local dealer for further clarification and comments.
SINCE SHERWOOD INDUSTRIES LTD. HAS NO CONTROL OVER THE INSTALLATION OF
YOUR STOVE, SHERWOOD INDUSTRIES LTD. GRANTS NO WARRANTY IMPLIED OR STATED
FOR THE INSTALLATION OR MAINTENANCE OF YOUR STOVE. THEREFORE, SHERWOOD
INDUSTRIES LTD. ASSUMES NO RESPONSIBILITY FOR ANY CONSEQUENTIAL DAMAGE(S).
SAVE THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE
5
Installation
RATING LABEL LOCATION:
The rating label is located on the back of the hopper.
DECIDING WHERE TO LOCATE YOUR PELLET APPLIANCE:
1. Check clearances to combustibles (see INSTALLATION - CLEARANCES TO COMBUSTIBLES and INSTALLATION - ALCOVE
CLEARANCES).
2. Do not obtain combustion air from an attic, garage or any unventilated space. Combustion air may
be obtained from a ventilated crawlspace.
3. Do not install the stove in a bedroom.
4. You can vent the stove through an exterior wall behind the unit or connect it to an existing masonry
or metal chimney (must be lined if the chimney is over 6” (15 cm) diameter, or over 28 inches² (180
cm²) cross sectional area). An interior vent can be used with approved pipe passing through the
ceiling and roof.
5. Locate the stove in a large and open room that is centrally located in the house. This will optimize
heat circulation.
6. The power cord is 8 feet (2.43 m) long and may require a grounded extension cord to reach the
nearest electrical outlet.
REMOVING PELLET STOVE FROM PALLET:
Remove screws from the two (2) hold-down
brackets that secure the Windsor to the pallet.
Lift the brackets up to unhook from the chassis.
Hold-down brackets.
Figure 1: Removing Freestanding Stove From the Pallet.
6
Installation
DIMENSIONS & SPECIFICATIONS:
141/4"
(360mm)
153/8"
(390mm)
257/8"
(659mm)
253/4"
(653mm)
271/8"
(689mm)
241/8"
(614mm)
Figure 2: Windsor Dimensions.
Table 1: Windsor Specifications.
Classification
Testing Standard
Description
Class I IP-20
EN14785:2006
Residential Wood Pellet Heater
Voltage
Current
Frequency
220 - 240 V
2.0 - 2.3 Amps
50 Hz
Maximum Power Requirement
Fuel type
Calorific value of Pellet used
525W (1793 BTU/hr)
wood pellets - 6mm (1⁄4”) dia.
≥ 5.10 kWh/kg (≥ 8000 BTU/lb)
Maximum Flue Gas Temperature
Mean Flue Gas Temperature
Mean Flue Gas Temperature (Reduced)
230°C (446°F)
180.5°C (357°F)
128.5°C (263°F)
Nominal Heat Output
CO emissions from Combustion
Energy Efficiency
6.9 KWh (23544 BTU)
0.035%
82.6%
Reduced Heat Output
CO emissions from Combustion (Reduced Output)
Energy Efficiency (Reduced Output)
2.3 KWh (7848 BTU)
0.052%
77.3%
CO2 at Nominal Output
Nominal Fuel Consumption Rate
Unit with Full Hopper
8.16%
1.65 Kg/hr (3.64 lb/hr)*
~ 151kg (333lb)
CO2 at Reduced Output
Fuel Consumption Rate (Reduced Output)
Hopper Capacity
4.142%
0.59 Kg/hr (1.30 lb/hr)*
~ 20kg (45lb)
*Note: Consumption will vary with the type of fuel used.
7
Installation
CLEARANCES TO COMBUSTIBLES:
These dimensions are minimum clearances but it
is recommended that you ensure sufficient room
for serving, routine cleaning and maintenance.
200mm
100mm
100mm
800mm
(77⁄8 inches)
(4 inches)
(4 inches)
(311⁄2” inches)
This pellet stove requires floor protection. The
floor protection must be non-combustible,
extending beneath the stove the full width and
depth of the unit including 150mm (6“) in front
for ember protection.
Hearth Pad Size:
Width:
650 mm
Depth:
815mm
100mm
(4")
100mm (4")
Side wall
Side wall to unit
Back wall to unit
Corner to unit
In Front of unit
Back wall
Adjacent
wall
200mm
(77/8 inches)
150mm
(6")
(25 5⁄8”)
(32 1⁄8”)
Floor Protection
Figure 3: Minimum Clearances to Combustibles for
Freestanding Windsor.
ALCOVE CLEARANCES:
This unit may be installed in an alcove. Maintain the
clearances to combustibles shown in Figure 4.
Minimum Width
1220mm (48")
Minimum Alcove width 1220mm (48 inches)
Minimum Alcove height 1220mm (48 inches)
Maximum Alcove depth 915mm (36 inches)
Install vent at clearances specified by
the vent manufacturer.
Minimum Height
1220mm (48")
Maximum Depth
915mm (36")
Figure 4: Alcove Clearances.
8
Installation
VENT TERMINATION REQUIREMENTS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Table 2: Use in conjunction with Figure 5 for allowable exterior vent termination locations.
Letter
Minimum Clearance
Description
A
24 in (61 cm)
B
48 in (122 cm)
Beside/below any door or window that may be opened. (18” (46 cm) if outside
fresh air install.)
C
12 in (30 cm)
Above any door or window that may be opened. (9” (23 cm) if outside fresh air
install.)
D
24 in (61 cm)
To any adjacent building, fences and protruding parts of the structure.
E
24 in (61 cm)
Below any eave or roof overhang
F
12 in (30 cm)
To outside corner.
G
12 in (30 cm)
To inside corner, combustible wall (vertical and horizontal terminations).
H
3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
Above grass, top of plants, wood, or any other combustible materials.
To each side of center line extended above natural gas or propane meter/
regulator assembly or mechanical vent.
I
3 ft (91 cm)
J
12 in (30 cm)
Clearance to non-mechanical air supply inlet to building, or the combustion air
inlet to any appliance.
K
24 in (61 cm)
Clearance above roof line for vertical terminations.
L
7 ft (2.13 m)
Clearance above paved sidewalk or paved driveway located on public property.
1. Do not terminate the
vent in any enclosed or
semi-enclosed areas such
as a carport, garage,
attic, crawlspace, narrow
walkway, closely fenced
area, under a sundeck
or porch, or any location
that can build up a
concentration of fumes
such as stairwells, covered
breezeway, etc.
From any forced air intake of other appliance
G
K
E
D
F
B
Opens
G
Opens
B
A
Termination Cap
Air Supply Inlet
G
C
I
G Gas Meter
Opens
Restriction Zone
L
H
(Termination not allowed)
Figure 5: Use in conjunction with Table 2 for allowable exterior vent termination
locations.
2. Vent surfaces can become
hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be
installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the
possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a
nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred
venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the
plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located
in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior
of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no
guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
9
Installation
EXHAUST AND FRESH AIR INTAKE LOCATIONS:
8 3/8”
(214 mm)
4 3/8”
(112 mm)
12 7/8”
(326 mm)
INSTALL VENT AT CLEARANCES SPECIFIED
BY THE VENTING MANUFACTURER
10 1/2”
(265 mm)
8 1/2”
(216 mm)
Figure 6: Inlet and Outlet Location.
EXHAUST
Base of unit to center of flue
Side of unit to center of flue
Center of unit to center of flue
270 mm
308 mm
19 mm
(10 5⁄8”)
(12 1⁄8”)
(3⁄4”)
FRESH AIR INTAKE.
Base of unit to center of intake
Side of unit to center of intake
Center of unit to center of flue
222 mm
197 mm
130 mm
(8 3⁄4”)
(7 3⁄4”)
(5 1⁄8”)
OUTSIDE FRESH-AIR CONNECTION:
This Heater must have adequate air for proper combustion in the room that it is installed.
A Fresh-air intake is strongly recommended for all
installations. Failure to install intake air may result in improper
combustion as well as the unit smoking during power failures.
�������
����
The inlet to the intake must be below and a minimum of 305mm
(12”) away from the unit exhaust outlet.
Outside fresh air is mandatory when installing this unit
in airtight homes.
When connecting to an outside fresh air source, do not use
plastic or combustible pipe. A 50mm minimum (2”) ID (inside
diameter) steel, aluminum or copper pipe should be used. It is
recommended, when you are installing a fresh air system, to
keep the number of bends in the pipe to a minimum.
10
���� ��
��� ���
��������
�����
Figure 7: Outside Air Connection.
Installation
CORNER THROUGH WALL INSTALLATION:
Fresh Air Intake
100mm
(4")
Wall thimble
manufactured
by pellet vent
manufacturer.
100mm
(4")
Figure 8: Corner Installation.
HORIZONTAL EXHAUST THROUGH WALL INSTALLATION:
Vent installation: install vent at clearances specified by the vent manufacturer.
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces,
or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired,
the installation must conform with all local regulations, including those referring to regional, national or
European Standards. Use 80mm stainless steel vent pipe to exhaust the unit to the outside.
1. Choose a location for your stove that meets the requirements stated in this manual and allows
installation with the least amount of interference to house framing, plumbing, wiring, etc.
2. Install a non-combustible hearth pad (where necessary).
3. Place the appliance 375 mm (15”) away from the wall. If the stove is to be set on a hearth pad, set
the unit on it.
4. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located
the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole
size and clearance to combustibles.
5. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour
barrier in accordance with local building codes.
6. Install a length of 80mm (3”) vent pipe into the wall thimble. The pipe should install easily into the
thimble.
7. Install the fresh air intake (see OUTSIDE FRESH AIR CONNECTION).
8. Connect the exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with high
temperature silicone.
11
Installation
9. Push the stove straight
back, leaving a minimum
of 100mm (4”) clearance
from the back of the
stove to the wall. Seal the
vent pipe to the thimble
with high temperature
silicone.
Exhaust
80mm (3") or 100mm (4")
Vent Pipe
10. The pipe must extend at
Wall Thimble
least 30 cm (12”) away
from the building. If
45o Elbow with Screen
necessary, bring another
Fresh Air Intake
or Termination Cap
length of pipe to the
outside of the home
to connect to the first
High Temperature RTV
section. Do not forget to
Silicone Required
place high temperature
Figure 9: Straight through wall Installation.
silicone around the pipe
that passes through the thimble.
11. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination. The
stainless steel cap termination manufactured by the vent manufacturer is recommended. However,
when the vent terminates several feet above ground level and there are no trees, plants, etc. within
several feet, a 45° elbow can be used as termination. The elbow must be turned down to prevent
rain from entering.
NOTE:
• Some horizontal through wall installations may require a “T” and 91 to 152 cm (3 to 5 feet) of vertical
pipe outside the building to help naturally draft in the unit.
• This may be required if a proper burn
Wall framing
cannot be maintained, after the stove
has been tested and the airflow set.
• This is due to the back pressure in the
exhaust caused by airflow around the
structure.
Horizontal frame
for thimble
• All sections of pipe must have three (3)
screws evenly spaced and all horizontal
and vertical vent sections located within
the house must have a bead of high
temperature silicone installed on the
male end of the pipe before installation
to create a gas tight seal.
Vent pipe
Termination cap
Wall thimble
������ �������
Figure 10: Straight through Wall Installation - Side View.
12
Installation
VERTICAL RISE WITH HORIZONTAL TERMINATION INSTALLATION (RECOMMENDED):
Termination cap
90°elbow
Wall framing
A 45° elbow with a rodent screen may be used
in place of the termination cap (or stainless
steel termination hood).
Vertical section
of vent pipe
Wall strap
Horizontal frame
for thimble
Clean out tee
Wall thimble
������ �������
Figure 11: Through Wall with Horizontal Termination.
THROUGH CONCRETE WALL WITH VERTICAL RISE INSTALLATIONS:
A 45° down elbow with a rodent screen may
be used in place of the termination cap (or
stainless steel termination hood).
Installation to use if there is a concrete or
retaining wall in line with exhaust vent on pellet
stove.
Horizontal frame
for thimble
Termination
cap
Wall thimble
90°elbow
Wall framing
Vertical section
of vent pipe
The termination must be 305mm (12”) from
the outside wall and 305mm (12”) above the
ground.
Concrete
Wall
������ �������
Clean out tee
Figure 12: Vertical rise with Horizontal Termination.
13
Installation
INSIDE VERTICAL INSTALLATIONS:
1. Choose a stove location that is ideal. See the section “DECIDING WHERE
TO
LOCATE
YOUR
PELLET APPLIANCE.”
2. Place a non-combustible hearth pad where necessary.
3. Place the unit on the hearth pad (if installed on a carpeted surface) and space the unit in a manner
so when the pellet vent is
installed vertically, it will be
Rain cap - ensure cap is at
100mm (4”) away from a
least
900mm (3 feet) above
combustible wall.
the roof at the lowest point
4. Locate the center of the fresh
air intake pipe on the unit.
Match that center with the
same point on the wall and
cut a hole about 40mm (15⁄8”)
in diameter.
5. Install the fresh air intake
pipe.
Storm Collar
Roof Flashing
Roof Rafters
Fire Stop with
Support Collar
Ceiling Joist
6. Install the tee with clean out.
7. Install the pellet vent upward
from there. When you reach
the ceiling, make sure that the
vent goes through the ceiling
fire stop. Maintain a 100mm
(4”) distance to combustibles
and keep attic insulation away
from the vent pipe. Maintain
an effective vapor barrier.
8. Finally, extend the pellet
vent to go through the roof
flashing.
9. Ensure that the rain cap is
approximately 900 mm (36”)
above the roof.
Vertical Vent Pipe
Clean Out Tee
with Pipe Adapter
ENVIRO Windsor
Note:
All vent sections must maintain
3" (75mm) clearances to
combustibles.
Figure 13: Inside Vertical Installation.
14
Installation
OUTSIDE VERTICAL INSTALLATIONS:
To accomplish a outside vertical pipe installation, follow steps 1 through 5 in the “INSIDE VERTICAL INSTALLATIONS
- FREESTANDING” section and then finish it by performing the following (refer to Figure 14).
1. Install a tee with clean out on the outside of the house.
2. Install vent pipe upward from the tee. Make sure that you install support brackets to keep the vent
straight and secure.
3. Install ceiling thimble and secure the flashing as you go through the roof.
4. Ensure that the rain cap is approximately 900 mm (36”) above the roof.
Rain cap
Flashing
900mm
(36")
75mm (3")
Clearance
100mm
(4")
Support
bracket
Tee with
cleanout
Type "L"
vent
Fresh air
intake
Figure 14: Outside Vertical Installation.
15
Installation
HEARTH MOUNT INSTALLATION:
Damper Removed
or Fastened Open
Mantel
Minimum 200mm (8")
from top of stove
Clean-out
Fresh-air intake
should com from
chimney. If holes
already exist fresh-air
intake can be taken
through back of the
fireplace or through
the ash dump.
Min 150mm
(6")
Floor
Protection
Masonry Fireplace
Combustible Floor
Figure 15: Hearth Mount - Side View.
Rain cap - ensure cap is at
least 900mm (3 ft) above
the roof at the lowest point
Storm Collar
Seal Plate
1. Lock fireplace damper in the open
position.
2. Install a positive flue connector at the
fireplace dampers.
3. Connect a clean-out tee or a 90° elbow
to the exhaust pipe.
4. Install flexible stainless steel liner or listed
pellet vent to the top of the chimney.
Existing Masonary Flue
Vertical Vent Pipe (single
wall stainless flex pipe or
solid PL vent)
Flexible Vent Connector (use
this 1.5m (5ft) section of pipe
to vent past the fireplace
damper or smoke shelf)
Fireplace Damper
Location
Clean Out Tee
Existing Fireplace
ENVIRO Windsor
Figure 16: Hearth Mount - Over View.
16
Installation
INSTALLATION WITH EXTERIOR MOUNTED EXHAUST BLOWER:
The WINDSOR can be equipped with an externally mounted exhaust blower (PART #50-492). This
optional kit will include all components necessary to install the exhaust blower on any external vertical
wall surface.
Choose a location for your stove that meets the requirements stated in this manual and allows installation
with the least amount of interference to house framing, plumbing, wiring, etc.
Included
are:
1
1
1
in the exterior mounted exhaust blower kit
- Exhaust blower housing box.
- Blower cover plate.
- Hardware bag
1. Open the left side of the unit and disconnect the
exhaust blower wires from the harness. Remove the
exhaust blower by undoing the six (6) 6mm (1⁄4”)
hex head sheet metal screws that fasten the blower
to the housing.
Exhaust Motor
2. Remove the back grill from the exterior exhaust
vent housing and remove the round cover plate
installed on the blower housing.
3. Install the round cover plate over the gasketed
opening in the stove where the exhaust motor was
removed from.
4. Install the exhaust blower motor in the Exterior Vent
Housing Box onto the exhaust blower housing.
Cover Plate
Access Panel
Figure 17: Removing Exhaust Blower.
5. Follow the procedures for INSTALLATION - HORIZONTAL EXHAUST THROUGH WALL INSTALLATION. Place the unit in
the desired location. Cut the hole in the wall at the desired location. Install a wall thimble.
6. Drill holes in the wall thimble in the corresponding locations for wire and fresh air if needed. Install
wire clamps and feed wire through the hole in the thimble into the house. Tighten clamp on wire and
attach green ground wire (at the symbol) with the screw and star washer provided.
7. Attach a short or an adjustable section of 80mm (3”) of double wall pellet vent through the wall
thimble to the stove. Seal all
joints with silicone. Maintain
clearances to combustibles.
8. Apply silicone to the pipe in
the Exhaust Box, slide the pipe
into the exhaust vent. Mount
the Exhaust Box to the house.
Reinstall the back grill on the
Exterior Vent Housing Box.
Apply normal venting practices
when installing the vertical
vent pipe.
Install blower
motor onto
exhaust blower
housings.
Completed assembly.
Figure 18: Exterior Exhaust Blower.
17
Installation
9. Connect the wires in the stove. Re-install the left side access cover to the stove and the back grill on
the exterior vent housing.
10. Set the Slider Damper as described in the INSTALLATION - SLIDER/DAMPER SETTING“ section.
NOTE:
Ensure that all vent connections are installed by placing three (3) screws evenly spaced and a small bead
of high temperature silicone at each chimney connection. Also ensure that all vertical vent sections are
properly supported and that all clearances to combustibles are maintained in accordance with the vent
manufacturer’s specifications.
Vent termination cap
(stainless steel termination
hood) or 45° elbow with
rodent screen
Siding
Wall strap
(recommended with
use of vent pipe)
90° elbow
Wall framing
Vent pipe or 610mm
(2 foot) riser
Wall thimble
Pipe adapter (if using riser)
Exterior blower
and housing
Horizontal frame
for thimble
Armour cable supplying
power to exterior blower
Figure 19: Exhaust Blower Installation; Horizontal Termination.
TO SUPPLY POWER TO THE EXHAUST BLOWER:
Install an amour coated electrical cable from the exhaust blower housing, through the wall thimble, and
attach to the pre-drilled hole in the left hand rear hopper pillar. Hook up to wires from the wiring harness
for the exhaust blower. All electrical connections must be in accordance with local code requirements (see
WIRING DIAGRAM).
18
Installation
THROUGH WALL VERTICAL INSTALLATION WITH EXHAUST BLOWER:
Refer to INSTALLATION - INSTALLATION WITH EXTERIOR MOUNTED EXHAUST BLOWER and INSTALLATION - OUTSIDE VERTICAL
INSTALLATIONS. Ensure that vent pipe is properly secured to wall using wall straps. Maintain clearances to
combustibles on vent pipe as well as unit.
Rain cap - ensure
cap is at least
900mm (3 ft)
above the roof at
the lowest point
Roof Sheathing
Storm Collar
Roof Flashing
Roof Rafters
Ceiling Joist
Vertical Vent Pipe
Exterior Wall
Sheathing
Outside Vent
Termination
Figure 20: Exhaust Blower Installation; Vertical Termination.
19
Installation
THERMOSTAT INSTALLATION:
1. Install the wall thermostat (12 or 24 Volt rated) in a location that is not to close too the unit but will
effectively heat the desired area.
2. Connect the Thermostat or Timer using an 2 x 18 gauge wire from the unit to the thermostat.
Remove jumper
wire and install
thermostat wires here.
If the unit has been placed in the HI / LOW mode,
the unit will be taken to a low or idle setting when
the thermostat is not calling for heat. When the
thermostat calls for heat, the unit will go to the
setting that is displayed on the control board Heat
Indicator. If the heat in the room becomes to great,
the high limit switch may turn the stove off and
the switch will have to be manually reset. To reset
the high limit switch, remove the right cabinet
side. The switch is found behind the control panel.
Avoid setting off the high limit switch.
Figure 21: Thermostat wire placement.
SLIDER/DAMPER SETTING:
THE SLIDER / DAMPER MUST BE SET AT TIME OF INSTALLATION, IT IS USED TO REGULATE
THE AIRFLOW THROUGH THE PELLET STOVE.
A Qualified Service Technician or Installer must set the Slider Damper.
The slider damper should
be set only on a hot stove
(operating for thirty (30)
minutes or more) by placing
a Magnahelic Pressure Gauge
in the firebox (test port is
located in the center of the
stove just below the door
opening). Set the slider
damper so that the pressure
reads 0.18” to 0.20” W.C.
(44.8 to 49.8 Pa). Some
fuels may require higher
or lower settings. The
pressure readings are taken
through a hole in the front
of the firebox under the door,
using a Magnehelic Gauge.
Note: Some parts have been removed in
order to see components more clearly.
Slider Damper Plate
Exhaust Channel
Exhaust Blower
Figure 22: Slider / Damper
20
Installation
The slider damper is located behind the left cab side. Undo the two (2) T-20 torx screws that hold the
inspection cover on the left side and remove.
The combustion exhaust blower is a variable speed blower controlled by the heat output button. This
blower will decrease the vacuum pressure inside the stove and as the heat output button is turned down.
The vacuum pressure inside the firebox will increase as the combustion exhaust blower increases in
speed (higher heat output setting).
• If the fire should happen to go out and the heat output indicator has been set on the lowest setting,
the Slider Damper should be pushed in slightly, decreasing the air in the firebox.
• If, after long periods of burning, the fire builds up and overflows the burn pot or there is a build up
of clinkers, this would be a sign that the pellet quality is poor, this requires more primary air, the slider
damper must be pulled out to compensate. Pulling the slider damper out gives the fire more air.
The easiest way to make sure that an efficient flame is achieved is to understand the characteristics of
the fire.
•
•
•
A tall, lazy flame with dark orange tips requires more air
– Open slider (pull out) slightly.
A short, brisk flame, like a blowtorch, has too much air
– Close slider (push in) slightly.
If the flame is in the middle of these two
characteristics with a bright yellow/orange, active
flame with no black tips then the air is set for proper
operation.
SPECIAL NOTES:
Pellet quality is a major factor in how the pellet stove will
operate. If the pellets have a high moisture content or
ash content the fire will be less efficient and has a higher
possibility of the fire building up and creating clinkers (hard
ash build-up). If this happens, pull the Slider Damper out
slightly to increase the air flow to the fire.
Figure 23: Efficient Flame.
21
Troubleshooting
DO NOT:
● Service the stove with wet hands. The stove is an electrical appliance, which may pose a shock hazard
if handled improperly. Only qualified technicians should deal with possible internal electrical failures.
● Do not remove from the firebox any screws without penetrating oil lubrication.
● Hold the ON / OFF BUTTON down. This is a momentary contact switch and can be damaged if held
down too long.
WHAT TO DO IF:
1. The stove will not start.
2. The stove will not operate when hot.
3. The exhaust blower will not function normally.
4. Light # 2 on Heat output bar flashing.
5. The auger motor will not function normally.
6. The 200 °F (93 °C) high limit temperature sensor has tripped.
7. The convection blower will not function normally.
8. Ignitor- the pellets will not light.
9. Control settings (Heat Level) has no effect on the fire.
10. The stove keeps going out.
*NOTE: All troubleshooting procedures should be carried out by qualified technicians or
installers.
1. The stove will not start.
üMake sure the stove is plugged in and the wall outlet is supplying power.
üPush the ON /OFF button. You may need to wait approximately 30 seconds for circuit board to initiate
the stove is on.
üIf the control board has been placed in the on/off thermostat mode, then turn the thermostat up to
call for heat.
üCheck the heat level indicator. - If the # 2 light is flashing refer to “4. Light # 2 on Heat output bar
flashing.”)
üCheck the fuse on the circuit board.
üIf the unit still does not start, contact your local service dealer for service.
2. The stove will not operate when hot.
üCheck the heat level indicator if a fire is not detected, or if the fire has gone out the #3 light will
flash because the exhaust temperature sensor’s contacts have opened.
üCheck the hopper for fuel.
üIncorrect air damper setting. - Excessive air may consume the fire too quickly before the next drop of
fuel, leaving completely unburned fuel in the burn pot liner. - Insufficient air will cause build up, further
restricting the air flow through the burn pot liner. This in turn will cause the fuel to burn cold and very
slowly. Fuel may build up and smother the fire. In this case clean the burn pot. (Note: the unit may
require a change to the vent system or installation of fresh air to correct air to fuel ratio
problems).
üCombustion blower failure. - The combustion blower is not turning fast enough to generate the proper
vacuum in the fire box. Visual check – is the blower motor turning.
üCheck the exhaust blower voltage across the blower wires (>=220V on #5 setting and >= 165V on
#1 setting). – Replace the Circuit Board if the Voltage reading is less than 160V. with a line voltage
>220V AC.
22
Troubleshooting
üCheck vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the vacuum
hose from vacuum switch. Check exhaust vacuum readings by placing the open end of the vacuum
hose on a Magnahelic Gauge (readings must be above 0.18” to 0.20” W.C. (44.8 to 49.8 Pa) on low
fire). If the motor fails to reach a 0.10” W.C. readings, then replace the combustion blower.
üPoor quality fuel – insufficient energy in the fuel to produce enough heat to keep the stove burning or
operational.
üExhaust temperature sensor failure. – Bypass sensor located on exhaust blower if stove now operates
properly, the unit may require cleaning or a new sensor. Contact your local dealer for service.
üThe burn pot liner may require cleaning. Build up in the burn pot will cause the unit to shut off.
üCheck the fuse on the circuit board.
üContact your local dealer for service.
3. The exhaust motor will not function normally.
üOpen the left side access panel; check all connections against the wiring diagram.
üSee “2. The stove will not operate when hot.” Section.
4. Light # 2 on Heat output bar flashing
(The Vacuum Switch contacts have opened for more than 15 sec.)
üPinch, break or blockage in vacuum hose - check hose for pinch points or damage, replace or re-route
as required. Blow out vacuum hose
üBlocked hose barb on exhaust channel - use a paper clip to clean out hose barb or remove the vacuum
hose from the vacuum switch and blow into the hose to remove blockage.
üBlocked exhaust / venting system - have stove and venting cleaned and inspected.
üSevere negative pressure in area where unit is installed - check the operation by opening a window,
does this solve the problem? If it does, install fresh air intake to unit or room. Venting system may
require vertical section to move termination into a low pressure zone.
üVacuum switch failure - bypass the vacuum switch, if this corrects the problem check for above problems
before replacing the vacuum switch.
üDamage to gray wires between circuit board and vacuum switch - inspect wires and connectors
üCombustion blower failure - the combustion blower is not turning fast enough to generate the proper
vacuum in the exhaust channel. Visual check; is the blower motor turning? Check the exhaust blower
voltage across the blower wires (>=220V on #5 setting and >= 165V on #1 setting). – Replace the
Circuit Board if the Voltage reading is less than 160V. with a line voltage >220V AC.
üCheck vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the Vacuum
hose from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum
Hose on a Magnahelic Gauge. (readings must be above .10” W.C. on low fire).
If the motor fails to reach a 0.10” W.C. readings, then replace the combustion blower
To reset Circuit Board after a trouble code - push the ON/OFF button
5. The auger motor will not function normally.
üThe burn pot liner may require cleaning. Build up in the burn pot will cause the unit to shut off.
üCheck for obstructions in the hopper system.
üEnsure door is closed and ash pan is closed. The auger motor will stop if there is not enough vacuum
in the stove.
üCall your local dealer for service.
Auger light flashes but auger motor does not turn at all.
23
Troubleshooting
üIf the auger gear box does not turn but the motor’s armature does try to spin then the auger is jammed.
– Try to break apart jam by poking at the jam through the drop tube. If this fails then empty the hopper
and remove the auger cover **remember to re-seal the cover after installation**
üCheck the fuse on the circuit board.
6. The 200 °F ( 93 °C) high limit temperature sensor has tripped.
üReset sensor and determine cause – was it convection blower failure or 160 °F ( 71 °C) temperature
sensor failure? Bypass the 160 °F ( 71 °C) sensor, does the convection blower come on high? If no,
replace the blower. If yes, replace sensor (located on the left side of the firewall).
üCheck the fuse on the circuit board.
7. The convection blower will not function normally.
üClean all grill openings at the back and below unit .
üPress the fan button; does the fan come on? Press again to verify that the blower turns on; if, not
contact your local dealer for service.
8. Ignitor- the pellets will not light.
(Everything else in the stove operates but the ignitor will not light the pellets.)
üMake sure the burn pot liner is up tight and square to the ignitor tube by pushing the burn pot back
against the ignitor tube.
üCheck to see if the exhaust blower is operating. If not, contact your local dealer for service.
üCheck the fuse on the circuit board.
NOTE: The ignitor should be bright orange in color. If not replace the ignitor.
9. Control settings (Heat Level) has no effect on the fire.
üNote: If the system light is flashing the control board has complete control of the unit. When the units
system light becomes solid then control of the unit is given back to the operator.
üIf there is no control of the heat level button make sure the thermostat is calling for heat.
üCall your local dealer for service.
10. The stove keeps going out.
a) If the stove goes out and leaves fresh unburned pellets or cigarette-like ashes in the burn pot liner,
the fire is going out before the stove shuts off.
üCheck to see that the slider / damper is in the correct position.
üTurn the heat level up slightly (poor quality pellets will require slightly higher settings).
üSet the auger trim till the #1 and #5 lights are illuminated.
b) If the stove goes out and there are partially burned pellets left in the burn pot liner, the stove has shut
down due to a lack of air, exhaust temperature, or power failure.
üAdjust the slider / damper.
üCheck to see if the stove needs a more complete cleaning.
üTurn the heat level up slightly (poor quality pellets will require slightly higher settings).
üDid the power go out?
üContact your local dealer for service.
24
Wiring Diagram
Armor Cable Supplied
Optional Exterior
Exhaust Blower
Black
White
Combustion
Blower
Brown
Exhaust
Temperature
Sensor
Brown
White
Blue
Red
White
Black
Black
Ground
Brown
Thermostat
5 Amp
Fuse
Ignitor
Blue
240V
Filter
White
Auger
Motor
Yellow
Ground
Red
Red
Yellow
Black
White
Orange
Orange
Purple
Blue
Yellow
Red
Grey
Grey
Brown
Brown
Connect
Thermostat
Here
Vacuum
Switch
Purple
White
Orange
Orange
Convection
Blower
High Limit
Temperature
Sensor
25
Parts List - Components
Reference
Number
1
2
3
120 °F (49 °C) Ceramic Fan Temperature Sensor
Auger Motor - 220V
High Limit Temp Sensor 200 °F (93 °C) Manual Reset
Silicone Hose
External Exhaust Back
External Exhaust Box
External Exhaust Bottom
Part
Number
EC-001
EF-001-220V
EF-016
EF-018
EF5-143
EF5-144
EF5-145
4
4
NZ Power Cord - 220V
20-011
IEC Power Cord - 220V
20-013
5
Ignitor - 220V
Door Screen
Heat Exchanger Rod
Cast Brick Panel - Left
Cast Brick Panel - Right
Cast Brick Panel - Center
Brick Panel Retainers (set of 2)
Inner Door Complete with Glass & Tape
Glass With Tape
Inner Door Only - Painted
Inner Door Handle
Door Hinge Bracket
Ash Pan With Painted Knob
Rear Casting Mounts - Right & Left
Bottom Casting Mounts - Right & Left
Front Casting Mounts - Right & Left
Door Knob - Brushed Nickel
Air Deflector
External Exhaust Kit (80mm pipe)
Convection Blower - 220V
Self Adhesive Vinyl Spacers (set of 4)
Dual bulb door gasket - 10 ft (3.05m)
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
26
Description
20-016-220V
50-177
50-181
50-183
50-184
50-1585
50-185
50-1671
50-1468
50-1672
50-189
50-1530
50-191
50-197
50-198
50-199
50-262
50-363
50-492
50-513
50-1149
50-634
Parts List - Components
Reference
Number
22
23
24
25
26
27
28
29
29
30
31
32
33
34
35
36
37
38
39
40
Description
Auger Motor Mount
Auger Plate with bushing
Auger Mounting Hardware
IEC Power Cord Inlet Socket
Hinge Pin - Silver
Oval Ceramic Gasket
Circuit Board 5 Amp Fuses - 220V (Pair)
Exhaust Starter Tube 80mm x 21⁄2” Long
Combustion/ Exhaust Blower - 220V
Door Bolt, Hardened Bushing & Nut
Ignition Burn Pot
Vacuum Switch - Low Presure
Burn Pot Liner with Sides
Control Panel with Decal
Control Panel Decal
Circuit Board with Thermostat Switch - 220V
Gloves
Windsor International Owner’s Manual
Windsor International Technical Manual
Hopper Lid with Hinges
Fan Cover
Slider Damper
Ignitor Tube
EMI Filter
Back grill
Access Panel - Right
Access Panel - Left
Pewter Knob
Wiring Harness
Auger
Part
Number
50-687
50-688
50-689
50-713
50-750
50-766
50-834
50-898
50-900
50-995
50-1366
50-1390
50-1401
50-1481
50-1482
50-1522
50-1525
50-1577
50-1578
50-1580
50-1581
50-1582
50-1583
50-1584
50-1586
50-1587
50-1588
50-1589
50-1625
50-1626
27
Parts List - Cast
Reference
Number
41
42
43
44
45
46
28
Description
Cast Ash Shelf - Painted
Cast Front Complete (Doors & Ash Shelf) - Painted
Cast Side Left - Painted
Cast Side Right - Painted
Cast Grate - Painted
Cast Top Only (No Grate) - Painted
Complete Cast Body - Painted
Complete Cast Body - Antique White
Complete Cast Body - Diamond Black
Complete Cast Body - Inferno Red
Complete Cast Body - Pearl Grey
Complete Cast Body - Wedgewood Blue
Complete Cast Body - Westport Green
Complete Cast Body - Antique Chestnut
Part
Number
50-192
50-202
50-203
50-204
50-205
50-206
50-576
50-577
50-578
50-579
50-580
50-581
50-582
50-867
��
��
��
��
��
�
��
�
��
�
�
��
��
��
May 2007
WINDSOR - Components
Parts Diagram - Components
29
Parts Diagram - Steel & Cast
May 2007
��
��
��
��
WINDSOR - Steel & Cast
��
��
��
��
��
��
�
�
��
��
��
��
��
�
��
��
�
��
��
��
�
��
��
��
��
��
��
��
��
��
��
��
30
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
NAME OF DEALER:
_________________________________________
_________________________________________
ADDRESS:
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
PHONE:___________________________________
MODEL:___________________________________
NAME OF INSTALLER:
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________
_________________________________________
(dd/mm/yyyy)
DATE OF INSTALLATION:___________(dd/mm/yyyy)
ADDRESS:
MAGNEHELIC AT INSTALL:___________________
_________________________________________
INSTALLER’S SIGNATURE:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
WARRANTY: If you have any concerns with your unit please contact the dealer where you purchased
the stove.
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
www.enviro.com
May 16, 2007
C-11304
31
Download PDF