Vermont Castings DVR28IN Operating instructions

Direct Vent Model:
DVR28IN
Homeowner’s Installation
and Operating Instructions
� � � � � ��
� � �� � � � � �
��
��������
IMPORTANT SAFETY INFORMATION
ALWAYS READ THIS MANUAL FIRST BEFORE ATTEMPTING
TO INSTALL OR USE THIS FIREPLACE
�����
WARNING!
�����������
IF THE INFORMATION IN THIS MANUAL IS
NOT
����
FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch; do not use
any phone in your building.
• Immediately call your gas supplier from your
neighbor’s phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas supplier call the
fire department.
FOR YOUR SAFETY
Installation and service must be performed
by a qualified installer, service agency or
the gas supplier.
DO NOT STORE OR USE GASOLINE OR
OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY
OTHER APPLIANCE.
INSTALLER: Leave this manual with the appliance CONSUMER: Retain this manual for future reference.
20012301 6/08 Rev. 6
Vermont Castings DVR28 Direct Vent Gas Fireplace
Table of Contents
Thank you and congratulations on your purchase of a CFM Corporation fireplace.
Installation & Operating Instructions
Safety Information ...............................................................................................................................3
Requirements for the Commonwealth of Massachusetts ....................................................................5
Fireplace Dimensions ..........................................................................................................................6
Minimum Clearance Illustrations .........................................................................................................6
Firestop Framing .................................................................................................................................6
Locating Your Fireplace .......................................................................................................................7
Clearance to Combustibles .................................................................................................................7
Installation Instructions ........................................................................................................................7
Mounting the Fireplace ........................................................................................................................7
Gas Specifications, Gas Inlet and Manifold Pressures........................................................................8
High Elevations....................................................................................................................................8
Remote ON/OFF Hi/Lo Wall Mounted Transmitter ..............................................................................8
Gas Line Installation ............................................................................................................................8
DVR28 Wiring Diagram .......................................................................................................................9
Restrictor Plate Installation ..................................................................................................................9
General Venting Information
General Venting .................................................................................................................................10
General Venting - Termination Location ............................................................................................ 11
General Venting - Assembling Vent Pipes .........................................................................................12
How to Use the Vent Graph ...............................................................................................................13
Rear Wall Venting Applications and Installation.................................................................................13
Vertical Side Wall Venting Applications and Installation ....................................................................14
Below Grade Installation....................................................................................................................15
Vertical Through-the-Roof Applications and Installation ....................................................................16
Venting Components .........................................................................................................................18
Operating Instructions
Glass Information ..............................................................................................................................19
Window Frame Assembly Removal ...................................................................................................19
Glass Cleaning ..................................................................................................................................19
Removal and Re-fitting of Curve Face ..............................................................................................19
Initial Lighting of the Fireplace ...........................................................................................................20
Flame & Temperature Adjustment .....................................................................................................20
Flame Characteristics ........................................................................................................................20
Inspecting the Venting System ..........................................................................................................20
Lighting & Operating Instructions ......................................................................................................21
Remote Control Transmitter Operating Instruction ............................................................................22
Troubleshooting .................................................................................................................................25
Maintenance
Cleaning the Standing Pilot Control System......................................................................................29
Accessories
Curve Face Kit ...................................................................................................................................29
Screen Door Kit .................................................................................................................................29
Replacement Parts.........................................................................................................................................30
Warranty..........................................................................................................................................................32
Energuide .......................................................................................................................................................32
Always read the warnings and operating instructions first, before attempting to install or use this fireplace, to
prevent personal injury, property damage or voiding of the warranty.
2
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Installation & Operating Instructions
WARNING
Safety Information for the Installer
1. Always read all warnings and installation instructions before attempting to install this fireplace.
2. Always use a qualified installer, preferably NFI or
WETT (Canada) certified, to install this fireplace
in compliance with local building codes and with
current CSA B149.1 Installation Codes for Gas
Burning Appliances and Equipment. For USA Installations, always comply with local codes and/or
the current National Fuel Gas Code, ANSI Z223.1/
NFPA 54.
3. This appliance may be installed in an aftermarket
permanently located manufactured home or mobile home, where not prohibited by local codes.
4. Never install this fireplace in any room or other
location where a water source is present.
5. Always operate this fireplace with the type of gas
designated on the rating plate. Never attempt to
use any other type of gas, unless a certified conversion kit has first been installed.
6. Always provide this direct vent fireplace with
its own separate vent pipe system that passes
through a wall or roof and terminates outside
the structure. Never connect this fireplace to an
existing chimney flue which concurrently serves
another fireplace, to prevent the risk of carbon
monoxide poisoning.
Safety Information for the User
1. Always read all warnings and operating instructions before attempting to use this fireplace.
2. This fireplace is extremely hot when in use. Never
touch the unit, and never attempt to perform any
routine maintenance while it is in operation or
before it has cooled to room temperature.
3. Never operate the fireplace while it is unattended.
Extreme caution is necessary if either children or
disabled persons are present.
4. Always keep combustible materials, including furniture, pillows, bedding, clothes, curtains, drapes
and paper, at least 3 feet (914 mm) away from the
front of this fireplace when it is in use.
5. Never operate the fireplace if it has malfunctioned
and has not yet been serviced, or if it has been
exposed to water or damaged in any manner and
has not yet been fully repaired.
20012301
6. Never attempt to operate this direct vent fireplace
if the front glass panel is missing, open, cracked
or broken, as carbon monoxide poisoning could
result. Always use a qualified service technician
to replace a faulty glass panel and always install a
replacement glass panel that has been approved
by the CFM Corporation.
7. Never attempt to modify this fireplace in any way.
Always replace any components that have been
removed for servicing prior to attempting to operate the fireplace again.
8. Never store or use gasoline or other volatile substances in the vicinity of the fireplace.
9. Never use this fireplace as a drying rack for clothing, and never hang Christmas stockings or decorations on or near it.
10.Never use this fireplace for any purpose or in any
manner not expressly set forth in this manual. Any
use not specifically intended by the manufacturer
may create a fire hazard or cause damage to the
fireplace.
11.Never place any solid fuel, such as wood, coal,
paper or cardboard, in this fireplace.
12.Always turn the gas valve to the OFF position
when the fireplace is not in use.
13.Never obstruct the flow of combustion and ventilation air in any way. This direct vent fireplace
requires adequate ventilation and combustion air
to operate properly.
14.Always keep the control compartments, burners
and air passages in this fireplace clean and free
of dust and lint. Periodic inspection and cleaning
may be required, due to excess dust and lint from
carpeting and bedding. Always confirm that the
gas valve and pilot light are turned OFF, before
you attempt to clean this fireplace.
15.Always use a qualified service technician to
inspect this fireplace and the venting system
(chimney) for this fireplace at least once a year. If
needed, the venting system should be cleaned at
that time.
16.Always use a qualified technician or service
agency to perform any repairs to this fireplace.
3
Vermont Castings DVR28 Direct Vent Gas Fireplace
Installation & Operating Instructions
�
�������
��������������
������������
������������������
�������������
��������������������
���������������
BREAKING IN YOUR NEW FIREPLACE
• Remove any plastic covering materials that
may still be adhering to the trim parts, before
turning the fireplace ON for the first time.
• Burn the fireplace for at least ten (10) hours
the first time you use it, to break it in properly. If the
optional fan kit has been installed, place the fan
switch in the “OFF” position during this time.
• It is normal for fireplaces fabricated of steel to give
off some expansion and/or contraction noises during
the start up and cool down cycles. Similar noises are
produced by your furnace heat exchanger and your
car engine.
• It is also not unusual for your gas fireplace to give off
some odor the first time it is burned. This is due to the
curing of the paint and any undetected oil from the
manufacturing process.
Proposition 65 Warning:
Fuels used in gas, wood burning or oil fired
appliances, and the products of combustion
of such fuels, contain chemicals known to
the State of California to cause cancer, birth
defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
CAUTION
Check with your electronics manufacturer before
installing a television set or other electronic device
above this fireplace.
NOTICE
DVR28IN Certified to ANSI Z21.88b-2008 / CSA 2.33b2008 Vented Gas Fireplace Heaters
This Direct Vent Gas Fireplace utilizes a sealed
combustion system in which outside air is brought
into the fireplace and the products of combustion
are exhausted from the fireplace through two separate concentric passageways within the same metal
vent pipe. Since the vent pipe extends vertically
through an exterior wall or through the roof to the
atmosphere, the fireplace does not use room air for
combustion.
• Provide adequate ventilation during the breaking in
process by opening all windows.
4
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Installation & Operating Instructions
Requirements for the Commonwealth of
Massachusetts
All gas fitting and installation of this heater shall only be
done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
Inspection
The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gas fitter shall observe that a hard wired carbon
monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure
served by the side wall horizontally vented gas fueled
equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors.
In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
floor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be
installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in
accordance with the above provisions shall comply with
NFPA 720 and ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently
mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW, KEEP CLEAR OF
ALL OBSTRUCTIONS”.
20012301
•
“Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board;
and
Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
•
system design or the venting system components;
and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not
provide the parts for venting the flue gases, but identifies
“special venting systems”, the following requirements
shall be satisfied by the manufacturer:
• The referenced “special venting system” instructions
•
shall be included with the appliance or equipment
installation instructions; and
The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the
completion of the installation.
5
Vermont Castings DVR28 Direct Vent Gas Fireplace
DVR28 Fireplace Dimensions
1”
(25 mm)
Min.
7����”
(183 mm)
6���”
(162 mm)
20���”
(511 mm)
15����"
(395 mm)
14�����”
(377 mm)
28” (711 mm)
Wall Mount
Bracket
12”
(305 mm)
Min.
Finished Wall
Fig. 1 Fireplace specifications and framing dimensions.
Minimum Ceiling and
Floor Clearance
Side View
Typ. 16” (406 mm) o.c.*
24”
27” (610 mm)
(686 mm) Min.
Ceiling
Finished Wall
12301
DVR28 specs
3/07
Top of Unit
10���”
(264 mm)
NOTE: Minimum
clearances are with
face trim in place.
1“
(25 mm)
Min.
9���”
(238 mm)
10”
(254 mm)
Min.
Floor
FP1782
Minimum Side Wall Clearance
FP1783
Fig. 3 Firestop framing.
FP1782
DVR29 min. clearances
3/07
Curve Face Trim
6“
(152 mm)
Min.
������
����������������
����
Top View
FP1784
Fig. 2 Minimum clearances.
20012301
6
������
Vermont Castings DVR28 Direct Vent Gas Fireplace
3. Make sure framing for firestop is correct. NOTE:
Firestop is for combustible walls. Refer to firestop
framing instructions on Pages 6 and 14, Figures 3
and 17.
4. Plumb for gas connection. Refer to Gas Line Installation on Page 8.
5. Finish wall as desired.
Install the firestop in accordance with the
applicable instructions, if the wall is finished with combustible materials.
Locating Your Fireplace
A
E
Y
B
X
C
D
Y
X
B
Mounting the Fireplace
LU584-R
Fig. 4 Locate gas fireplace.
A) Flat on wall
D) *Room divider
B) Cross corner
E) *Flat on wall corner
LU584-R
C) **Island
Locating
unit
Y) 6”
minimum
2/23/01 sta
NOTE: (Fig. 4)
** Island (C) and Room Divider (D) installation is possible as
long as the horizontal portion of the vent system (X) does not
exceed 20’ (610 cm). See details in Venting Section.
* When you install your fireplace in (D) Room divider or (E)
Flat on wall corner positions (Y), a minimum of 6” (153 mm)
clearance must be maintained from the perpendicular wall and
the front side edge of the fireplace trim.
Refer to (Y) in Figure 4.
Never place the fireplace on the floor or
on any hard surface with the bottom side
down, to avoid damaging the exposed
components.
1. The DVR28 comes with a wall mount bracket to
secure the fireplace to the wall. Standoffs on the
back of the bracket allow for proper clearances to
combustibles. (Fig. 5)
16” o.c.
(406 mm)
Finished
Wall
Clearance to Combustibles
Front of Unit to Combustibles ...................36” (914 mm)
Appliance
Top of Unit to Ceiling ..........................27” (686 mm)
Top of Face Trim to Ceiling ........ 24” (610 mm) Min.
Bottom of Unit to Floor .......................12” (305 mm)
Side of Unit to Sidewall ...................10¹⁄₂” (267 mm)
Back .......................................................1” (25 mm)
Venting
Concentric sections of DV Vent ....................1” (25 mm)
Nonconcentric sections of DV Vent
Sides and Bottom ...................................1” (25 mm)
Top .........................................................2” (51 mm)
Installation Instructions
Preparation
Confirm that the fireplace is level and
properly positioned, before finalizing the
installation.
1. Choose the location for the fireplace. Maintain
proper height and clearances.
2. Make sure framing is 16” (406 mm) o.c. for placement of wall mount brackets pre-drilled holes. If
framing is not 16” o.c., the installer can drill new
holes in wall mounting brackets to align with existing
framing dimensions.
20012301
Firestop
Framing
(if required)
Wall Mounting
Bracket
FP1786
Fig. 5 Secure wall mounting bracket in desired location.
2. Align pipe clearance hole in wall mounting bracket
with through-the-wall clearance opening on noncombustible wall or through firestop opening on combustible walls.
3. Make sure wall mount������
bracket is level. Secure to
framing studs using mounting
screws supplied. En������������
sure framing is 16” (406
mm)
o.c.
to accommodate
����
mounting bracket.
4. Align the top and bottom mounting holes of the fireplace with the top and bottom holes of the mounting
bracket. Secure fireplace to mounting bracket using
sheet metal screws supplied. (Fig. 6)
Be careful not to damage any exposed
components on the bottom of the fireplace
while securing it to the mounting bracket.
7
Vermont Castings DVR28 Direct Vent Gas Fireplace
Gas Line Installation
Sheet Metal
Screws (8)
Always remove the front window frame assembly before purging the gas lines.
Wall Mounting Bracket
Secured to Walll
DVR28
Sheet Metal
Screws (4)
FP1785
Fig. 6 Secure fireplace to wall mounting bracket.
The gas pipeline can be brought in under the bottom of
the fireplace. The gas line connections will be covered
by bottom trim. Refer to Figure 7 for gas line dimensions. Use 1/2” rigid pipe. When gas line is in place under the fireplace, install supplied 1/2” FPT to 3/8” flare
brass fitting. Connect preinstalled flex line on fireplace
to brass fitting with 3/8” flare fitting on supply line.
The gas line connection can be made with 3/8” rigid
pipe or an approved flex connector. Since some municipalities have additional local codes, it is always best to
consult your local authority and the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 in the USA or the CSAB149.1 installation code.
Gas Specifications
Model
Fuel
DVR28IN
Nat.
������
Max.
Min.
����������������Input Input
����Control BTU/h BTU/h
Gas
Air
Shutter
Setting
1/8”
Millivolt Hi/Lo 18,500 16,500
open
on sides
Gas Inlet and Manifold Pressures
Inlet Minimum
Inlet Maximum
Manifold Pressure
Natural
5.5” w.c.
14.0” w.c.
3.5” w.c.
High Elevations
Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).
Remote ON/OFF Hi/Lo
Wall Mounted Transmitter
The DVR28 is equipped with a wireless transmitter. No
wires are required. Refer to Page 20 for first time use
and battery installation.
8
12���”
(318 mm)
1���”
(32 mm)
6”
(152 mm)
Gas Line
Through Wall
Gas Line
Opening in
Wall
FP1787
Fig. 7 Recommended gas line installation.
Always check for gas leaks with a mild
soap and water solution applied with a
brush no larger FP1787
than 1” (25 mm). Never
line
installwith a spray
apply soap and gas
water
solution
3/07
bottle. Never use
an open flame for leak
testing.
Never subject the fireplace valve to any
test pressures exceeding 1/2 psi. Always
isolate or disconnect the valve from the
gas line when pressure testing.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to provide a 1/8” test point up stream of the control.
When using a flex connector use only approved fittings.
Always provide a union when using black iron pipe
so the gas line can be easily disconnected for burner
servicing. See gas specification for pressure details and
ratings.
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Wireless Remote
White or Green
Green or White
Orange or White
No wiring
required.
(Refer to
Pages
6,18, 21)
ON
OFF
Solenoid
Pilot
Main
Main
Module
AF-4000
HI
LO
Learn Button
Remote/Off Switch
Red
AF-4000B/P
Black
Red
Black
Red
Black
FP1796
Orange
Continuous
Wireless remote
Pilot ON/OFF
3/07
Switch
Optional IMTFK
Wall Thermostat
(for Bedroom Use
Canada ONLY)*
Brown
Black
Gnd
Brown
Brown
HI/LO DC Battery Pack
Black
Red
FP1750
Optional DC
Battery Back-up
Fig. 8 DVR28 wiring diagram.
Restrictor Plate Installation
Flue Diverter
The DVR28IN is shipped with a restrictor plate for extended pipe runs other than straight out installations. A
guide for usage is shown in Figure 10.
NOTE: Some installations may require some adjustFP1750
FP1789
DVR28 wiring diagram
ment by the installer for optimum flame appearance.
2/07
Flue
Optimum flame appearance would be a flame not
Opening
subject to tall dirty yellow flames or lifting of flames from
Remove
burner tube.
Two (2)
Installation
1. Remove front glass assembly. Refer to Window
Frame Removal section on Page 19.
2. Remove three (3) screws securing flue diverter to top
of combustion case. Remove flue diverter. (Fig. 9)
CAUTION: Use care not to damage rear refractory.
3. Remove two (2) screws on sides of flue opening.
4. Install restrictor plate with two (2) screws removed
from back of unit. (Fig. 9)
5. Re-install flue diverter with three (3) screws removed
earlier.
6. Reinstall glass assembly. (Refer to Page 19)
*NOTE: If optional IMTFK wall thermostat is installed,
switch on module for remote/off switch must be in the
“OFF” position. When the wall thermostat is used, wall
transmitter supplied with DVR28IN cannot be used at
this time.
20012301
Screws
Remove
Three (3)
Screws
Restrictor
Plate
Fig.
r to
10
Refe
FP1788
FP1790
Fig. 9 Install restrictor plate for optimum flame appearance.
������
Examples for Extended Run/Restrictor Plate Settings
���������������
1. 90° Elbow, vertical 8’ (2.4 m), 90° elbow, out 20’ (6 m)
���� 11’ (3.4 m), 90° elbow, out 13’ (4 m)
2. 90° Elbow, vertical
3. 90° Elbow, vertical 20’ (6 m), 90° elbow, out 7’ (2 m)
4. 90°, 40’ (12 m) vertical
Flue restricted to
:
������
1.
2.
3.
4.
������
������������������
1¹⁄₈” (29 mm)
opening in flue pipe outlet
�������������
����
����
7/8” (22 mm)
opening in flue pipe outlet
3/4” (79 mm) opening in flue pipe outlet
1³⁄₈” (35 mm) opening in flue pipe outlet
Figure 10
9
Vermont Castings DVR28 Direct Vent Gas Fireplace
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertically through the roof.
• Only CFM Corporation venting components specifi•
•
•
cally approved and labelled for this fireplace may be
used.
If vent termination is installed in an accessible location, Vent Termination Guard #53525 shall be installed.
Vent terminations shall not be recessed into a wall or
siding.
Horizontal venting which incorporates the twist lock
pipe must be installed on a level plane without an
inclining or declining slope.
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24” (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on the next
page.
*Check with local codes or in absence of same with
CSA B149.1 Installation Codes (1991) for Canada
or follow the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54 for installations in the USA.
10
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
General Venting Information - Termination Location
INSIDE
CORNER DETAIL
G
V
H
A
N
N
D
L
V
E
C
B
V
F
B
�����
������
B
V
Ope
Operable
rable
V
B
B
B
J
X
X AIR SUPPLY INLET
M
I
A
CFM145a
V VENT TERMINATION
V
V
Fixed
Closed
V
K
X
AREA WHERE TERMINAL IS NOT PERMITTED
Canadian Installations1
US Installations2
A = Clearance above grade, veranda, porch,
deck, or balcony
B = Clearance to window or door that may be
opened
CFM145a
12”
(30 cm)
DV Termin
Location
C = Clearance to permanently closed window
12” (305 mm) recommended to
prevent window condensation
6” (15 cm) for appliances
< 10,000 Btuh (3kW), 9”
(23 cm) for appliances > 10,000
Btuh (3kW) and < 50,000 Btuh
(15kW), 12” (30 cm) for
appliances > 50,000 Btuh (15kW)
12” (305 mm) recommended to
prevent window condensation
18” (458 mm)
18” (458 mm)
12” (305 mm)
see next page
see next page
3’ (91 cm) within a height of 15’ (5 m)
above the meter/regulator assembly
12” (305 mm)
see next page
see next page
3’ (91 cm) within a height of 15’
(5 m) above the meter/regulator
assy
3’ (91 cm)
6” (15 cm) for appliances
< 10,000 Btuh (3kW), 9”
(23 cm) for appliances > 10,000
Btuh (3kW) and < 50,000 Btuh
(15kW), 12” (30 cm) for
appliances > 50,000 Btuh (15kW)
3’ (91 cm) above if within 10
feet (3 m) horizontally
7’ (2.13 m)†
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal
distance of 2’ (610mm) from the center
line of the terminal
E = Clearance to unventilated soffit
F = Clearance to outside corner
G = Clearance to inside corner (see next page)
H = Clearance to each inside of center line
extended above meter/regulator assembly
5/01/01 Rev. 12/05/01
sta
6” (15 cm) for appliances
< 10,000 Btuh (3kW), 12” (30 cm)
for appliances > 10,000 Btuh (3kW) and
< 100,000 Btuh (30kW), 36” (91 cm)
for appliances > 100,000 Btuh (30kW)
I = Clearance to service regulator vent outlet
J = Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to any
other appliances
3’ (91 cm)
6” (15 cm) for appliances < 10,000 Btuh
(3kW), 12” (30 cm) for appliances
> 10,000 Btuh (3kW) and < 100,000 Btuh
(30kW), 36” (91cm) for appliances
> 100,000 Btuh (30kW)
K = Clearance to a mechanical air supply inlet
6’ (1.83 m)
12” (30 cm)
L = Clearance above paved sidewalk or paved 7’ (2.13 m)†
driveway located on public property
M = Clearance under veranda, porch, deck or
12” (30 cm)‡
12” (30 cm)‡
balcony
N = Clearance above a roof shall extend a minimum of 24” (610 mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450 mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and
serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not
meet these requirements.
Fig. 11 Vent termination locations.
20012301
11
Vermont Castings DVR28 Direct Vent Gas Fireplace
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
Alcove Applications*
Outside Corner
G=
Combustible
6" (152 mm)
G
F=
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
V
Noncombustible
2" (51 mm)
V
C
V
E
O
F
Balcony with perpendicular side wall
Balcony with no side wall
D
C
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
M
M
No.
of Caps
1
2
3
4
V
V
P
M=
Combustible &
Noncombustible
12" (305 mm)
Combustible &
Noncombustible
M = 24" (610 mm)
P = 20” (508 mm)
DMin.
3’ (914 mm)
6’ (1.8 m)
9’ (2.7 m)
12’ (3.7 m)
CMax.
2 x DActual
1 x DActual
2/3 x DActual
1/2 x DActual
DMin. = # of Termination caps x 3
CMax. = (2 / # termination caps) x DActual
584-15
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 12 Termination clearances.
General Information Assembling Vent Pipes
Canadian Installations:
USA Installations:
until the flange on the female end contacts the external
flange on the male end. It is recommended that you
secure the joints with three (3) sheet metal screws,
however this is not mandatory with twist lock pipe.
The venting system must conform with local codes and/
or the current National Fuel Gas code ANSI Z223.1/
NFPA 54.
To make it easier to assemble the joints we suggest
putting a lubricant (Vaseline or similar) on the male end
of the twist lock pipe prior to assembly.
Venting system must be installed in accordance with the
current CSA-B149.1 installation code.
Only venting components manufactured by CFM Corporation can be used in Direct Vent systems.
Male End
Female End
Twist Lock Pipes
When using CFM Corporation twist-lock pipe it is not
necessary to use sealant on the joints. The only areas
of the venting system that need to be sealed with high
temperature silicone sealant are the sliding joints of any
telescopic vent section used in the system.
To join the twist lock pipes together, simply align the
beads of the male end with the grooves of the female
end, then while bringing the pipe together, twist the pipe
12
Screw Holes
TWL100
Fig. 13 Twist-lock pipe joints.
TWL100
Twist Lock Pipe
3/12/99 djt
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
How to Use the Vent Graph
Rear Wall Venting Applications
The vent chart should be read in conjunction with the
following vent installation instructions to determine the
relationship of the vertical and horizontal dimensions of
the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 14)
locate the point intersecting with slanted graph line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
Example A:
If the vertical dimension from the floor of the
fireplace is 11’ (3.4 m) the horizontal run to the face
of the outer wall must not exceed 14’ (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is
7’ (2.14 m), the horizontal run to the face of the outer
wall must not exceed 8¹⁄₂’ (2.6 m).
When installed as a rear vent unit this appliance may
be vented directly to a termination located on the rear
wall behind the appliance.
• Only CFM Corporation venting components are
•
•
•
•
approved to be used in these applications. (Refer to
“Venting Components” listed for different installation
requirements)
The maximum horizontal distance between the rear
of the appliance (or end of the transition elbow in a
corner application) and the outside face of the rear
wall is 20” (508 mm). (Fig. 15 & 16)
Only one 45° elbow is allowed in these installations.
If using a 45° elbow at fireplace, you must start
out using an 8” (203 mm) or 12” (305 mm) section of pipe first attached to heater then a 45°
elbow.
Minimum clearances between vent pipe and combustible materials are as follows:
Top - 2” (51 mm)
Sides - 1” (25 mm)
Bottom - 1” (25 mm)
30
29
28
27
26
25
23
22
21
20
19
18
17
16
15
14
13
eg: A
12
11
10
9
8
7
eg: B
6
Vertical dimension from the floor of the unit
to the center of the horizontal vent pipe
24
20”
(508 mm)
Max.
Rear Vent Top View
FP1780
Fig. 15 Rear vent application, no elbows.
FP1780
20”
20”
(508 mm)
(508 mm)
rear
vent
no
elbows
Max.
Max.
3/07
45°
45°
5
4
3
�������� ����� ����������������������������������������������������������������
Horizontal dimension from the outside face of the
wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical
and horizontal dimensions for a Direct Vent flue system.
Fig. 14 Sidewall venting graph. (Dimensions in feet)
20012301
FP1779
Start with 8” (203 mm) or 12”
(305 mm) Pipe Section
Fig. 16 Rear vent application, one 45° elbow.
FP1779
Rear Vent-Top View
3/07
13
Vermont Castings DVR28 Direct Vent Gas Fireplace
Rear Wall Installation
Twist Lock Pipe
Adjustable
Zero Clearance Sleeve
STEP 1
Locate vent opening on the wall. To locate hole center
consult with appropriate fireplace dimensions, Page 4.
Frame as shown below.
Combustible Walls (Fig. 17): Cut a 10³⁄₈”H x 9³⁄₈” W
(264 x 240 mm) hole through the exterior wall and
frame as shown.
Noncombustible Walls (Fig. 17): Hole opening must
be 7¹⁄₂” (190 mm) in diameter.
Always use a zero clearance sleeve when
the wal is combustible.
#8 Screws
(2)
STEP 3
Measure the horizontal length requirement for the venting including a 2” (51 mm) overlap, i.e. from the elbow
to the outside wall face plus 2” (51 mm). (Fig. 15 or 16)
Vent Opening for Combustible Wall
9³⁄₈”
(240mm)
Framing
Detail
10³⁄₈”
(264mm)
#8 Screws (2)
Firestop
Adjustable Zero
Clearance
Sleeve
#8 Screws
(2)
Max. Length
12” (305mm)
FP1752
Fig. 18 AdjustableFP1752
zero clearance sleeve.
Zero Clearance Sleeve
attach the elbow 2/07
to the appliance in the
same manner
then attach the venting to the elbow.
Never permit a downward slope (away from
the fireplace) to occur anywhere in the system when installing the vent or an elbow in
the vent.
STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12”/305 mm). Assemble sleeve and attach to firestop with #8 sheet metal
screws (supplied). (Fig. 18)
1” (25 mm) Clearance between Zero
Clearance Sleeve
and Framing
STEP 5
Guide the venting through the vent hole a you place the
appliance in its installed position. Guide the 4” (102 mm)
and 7” (178 mm) collar of the vent termination into the
outer ends of the venting. Do not force the termination. If
the vent pipes do not align with the termination, remove
and realign the venting at the appliance flue collars.
(Fig. 19) Attach the termination to the wall as outlined in
the instruction sheet supplied with the termination.
Finished Wall
Firestop
Fireplace Hearth
Maintain 1” (25 mm) Air
Space from Zero Clearance Sleeve to Framing
Firestop
Vent
Termination
Install provided firestop with zero
clearance sleeve into framing
opening after drywall or finish
material is installed. Use the tabs
for clearance locators top and
bottom.
Top Tabs
Opening for
Noncombustible Wall
Zero Clearance
Sleeve
7¹⁄₂”
(190 mm)
Bottom Tabs
FP1753
FP1751
Fig. 17 Locate vent opening on wall.
STEP 4
FP1751
Install the 4” (102 mm) vent to the appliance collar and
vent opening
secure with three (3) sheet metal screws. Install the 7”
2/07
(178 mm) vent pipe to the
appliance collar and secure
with three (3) sheet metal screws. It is not necessary
to seal this connection. If a 45° elbow is being used,
14
Fig. 19 Side view of final unit location.
VerticalFP1005
Sidewall Applications
Side View Vent Termination
Since it is very important
for the venting system
1/25/00 djt
to maintain balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
The Vent Graph shows the relationship between vertical
and horizontal side wall venting and will help to determine the various dimensions allowable.
B 7’
(178 cm)
A 10’
(254 cm)
Minimum clearance between vent pipes and combustible materials is 2”(51 mm) on top and 1” (25
mm) on the bottom and sides unless otherwise
noted.
When vent termination exits through foundations less
than 20” below siding outcrop, the vent pipe must
flush up with the siding. It is always best to locate the
fireplace in such a way that minimizes the number of
offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace to the face of
the outer wall.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
When installing the appliance as a rear
vent unit, the 90° or 45° transition elbow
is NOT INCLUDED in the following criteria
and calculations, and unless specifically
mentioned should be ignored when calculating venting layouts.
• The maximum number of 90° elbows per side wall
installation is three (3). (Fig. 20)
3 x 90°
Elbows
A + B = 17’
(518 cm) Max.
8’
(244 cm)
FP1755
Fig. 21 Maximum vent run with elbows.
• For each 45° elbow installed in the horizontal run,
FP1755
the length of the horizontal
run MUST be reduced by
Horizontal Run
18” (45 cm). This 2/07
does not apply if the 45° elbows
are installed on the vertical part of the vent system.
• The maximum number of elbow degrees in a system
is 270°. (Fig. 22)
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total angular variation = 270°
1 + 2 + 3 + 4 = 270°
1
2
3
4
Transition
Elbow
FP1754
Fig. 20 Maximum three (3) 90° elbows per installation.
• If a 90° elbow is used
in the horizontal vent run
������
(level height maintained)
the maximum horizontal
������������
vent length is reduced by 36” (914 mm). This does
����
not apply if the 90°
elbows are used to increase or
redirect a vertical rise. (Fig. 21)
Example: According to the vent graph (Page 11) the
maximum horizontal vent length in a system with a 7.5’
(2.3 m) vertical rise is 20’ (6 m) and if a 90° elbow is
required in the horizontal vent it must be reduced to 17’
(5.2 m). In Figure 21 Dimension A plus B must not be
greater than 17’ (5.2 m).
In Figure 21, dimension A plus B must not be greater
than 17’ (5.2 m).
• The maximum number of 45° elbows permitted per
installation is six (6). These elbows can be installed
in either the vertical or horizontal run.
20012301
Transition Elbow
FP1756
Fig. 22 Maximum elbow usage.
Below Grade
������Installations
When it is not possible�������������
to meet the required vent terminal clearances of 12”
(305 mm) above grade level
����
a snorkel kit is recommended. This allows installation
depth of down to 7” (178 mm) below grade level. The
7” is measured from the center of the horizontal vent
pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed.
If venting system is installed below ground, we recommend a window well with adequate and proper drainage
to be installed around the termination.
15
Vermont Castings DVR28 Direct Vent Gas Fireplace
If installing a snorkel, a minimum 24” (610 mm) vertical
rise is necessary. The maximum horizontal run with the
24” vertical pipe is 36” (914 mm). This measurement
is taken from the collar of the fireplace (or transition
elbow) to the face of the exterior wall. See the Sidewall
Venting Graph for extended horizontal run if the vertical
exceeds 24” (610 mm).
1. Establish vent hole through the wall. (Fig. 17)
2. Remove soil to a depth of approximately 16”
(406 mm) below base of snorkel. Install window
well (not supplied). Refill hole with 12” (305 mm) of
coarse gravel leaving a clearance of approximately
4” (102 mm) below snorkel. (Fig. 23)
3. Install vent system. Refer to Page 12.
4. Ensure a watertight seal is made around the vent
pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4” and 7” snorkel collars.
6. Slide the snorkel into the vent pipe and secure to the
wall.
7. Level the soil to maintain a 4” (102 mm) clearance
below snorkel. (Fig. 23)
Zero Clearance Sleeve
(if required)
Snorkel
Foundation
Recess
Wall Screws
Watertight Seal
Around Pipe
BG401
Fig. 24 Snorkel installation, recessed foundation.
BG401
Vertical Through-the-Roof Application
Snorkel
This gas fireplace
has beendjt
approved for:
2/10/99
• Vertical installations up to 40’ (12 m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 25)
7TDVSNORK
(Snorkel)
Screws
Max. Height 40’
(12.2 m)
Min. Height 8’
(2.4 m)
Firestop
7” Pipe
4” Clearance Min.
Window
Well
24” (610 mm )
Minimum *
Sheet Metal
Screws
Max. 10’ (3 m)
Support Straps
Every 3’ (914 mm)
Gravel
Drain
FP1757
Foundation Wall
*A minimum of 24” (610 mm)
vertical pipe must be installed
when using the 7TDVSNORK.
BG404
Fig. 23 Below grade installation.
Never backfill around snorkel.
�����
Always maintain a clearance of at least 4”
�����������
between the snorkel and the soil.
����
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary
to extend vent pipes out as far as the protruding wall
face. (Fig. 24)
16
Fig. 25 Support straps for horizontal runs.
• Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the
maximum horizontal length must be
������
reduced by �����������������
18” (450 mm).
����� horizontal length:
Example: Maximum
No elbows
= 10’ (3 m)
1 x 45° elbow = 8.5’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)
• A minimum of an 8’ (2.5m) vertical rise is required.
• Two sets of 45° elbow offsets may be used within the
•
vertical sections. From 0 to a maximum of 8’ (2.5 m)
of vent pipe can be used between elbows. (Fig. 26)
7DVCS supports offsets. (Fig. 28) This application
will require that you first determine the roof pitch
and use the appropriate starter kit. (Refer to Venting
Components List)
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
• The maximum angular variation allowed in the sys•
tem is 270°. (Fig. 26)
The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610 mm).
(Fig. 29)
1 + 2 + 3 + 4 = 270°
Attic Insulation Shield
Upper Floor
11”
(279mm)
1
Ceiling Installation
1
2
11”
(279mm)
2
3
3
4
Joist
4
Firestop
Spacer
Nails (4)
FP1029
Fig. 27 Place firestop spacer(s) and secure.
FP1179
FP1029
attic insulation shield
firestop spacers
1/28/00 djt
Fig. 26 Maximum elbow usage.
Vertical Through-the-Roof Installation
1. Locate your fireplace.
2. Plumb to center of the (4”) flue collar from ceiling
above and mark position.
3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
4. Proceed to plumb for additional openings through
the roof. In all cases, the opening must provide a
minimum of 1 inch clearance to the vent pipe, i.e.,
the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield
#7DVAIS into position and secure. (Fig. 27)
7. Install roof support (Fig. 44) and roof flashing making
sure upper flange is below the shingles. (Fig. 28)
8. Install appropriate pipe sections until the venting is
above the flashing. (Fig. 30)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.
29)
11. Apply high temperature sealant to 4” and 7” collars
of vertical vent termination and install.
If there is a room above ceiling level, fire stop spacer
must be installed on both the bottom ad the top side
of the ceiling joists. If an attic is above ceiling level a
7DVAIS (Attic Insulation Shield) must be installed.
The enlarged ends of the vent section always face
downward.
Typical Roof
Support
Application
Typical Ceiling Support
Application
FP1184
Fig. 28 Venting supports.
FP1184
Min.
Typical roof/ceiling
2' (610 mm)
support apps.
FP1185
Fig. 29 Minimum termination to roof clearance.
3 #5 Sheet Metal
Screws per Joint
Sealant
Storm Collar
TWL101a
Fig. 30 Roof flashing.
20012301
17
TWL101a
Twist Lock Pipe
2/8/99 djt
Vermont Castings DVR28 Direct Vent Gas Fireplace
Venting Components
7TDVRVT - Through the wall Rear Vent Termination
584A
venting components
rear vent term
4/6/99 djt
584B
Vent components
Starter Kit
2/25/99 djt
Starter Kit Model 7TDVSK - Sidewall Venting (Twist Lock Pipe)
Model 7FDVSK - Sidewall Venting (Flex Vent Pipe)
Models 7TDVTK/TV - Hot Touch Termination Kits
Model 7TDVTVTK/TV - Cool Touch Termination Kit
Starter Kit - Model 7TDVSKV - Vertical Venting
for 7TDVSKV-A order 1/12 to 6/12 roof pitch
for 7TDVSKV-B order 7/12 to 12/12 roof pitch
for 7TDVSKV-F order flat roof
Starter Kit for Below Grade Installation
Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe)
Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)
Starter Pipe
Model 7TDVP 20/8 - 24” Starter Pipe Bulk
Model 7FDVP 30/8 - 30” Flex Pipe Bulk
45o Elbow
7TDV45 for Rear Vent to Vertical Vent
or Vertical/Horizontal Offsets
584C
584D
Vent components
Vent
Components
45 degree
elbow
90 degree elbow
2/25/99djt djt
2/25/99
10/20/99
twistlock
584E
10/20/99
twist
lock
Venting Components
Telescope vent
2/25/99 djt
10/20/99 twist lock
584F
Venting Components
Pipe sections
2/25/99 djt
10/20/99 twist lock
584G
Venting Components
Firestop spacer
2/25/99 djt
584H
Venting components
attic insulation shield
2/25/99 djt
90o Transition Elbow
7TDVRT90 for Rear Vent to Vertical Vent
90° Elbow
7TDV90 Vertical/Horizontal Offset
Telescopic vent sections
7TDVP1218 -11” to 17” adjustable length
7TDVTP3564 -35” to 67” adjustable length
Pipe sections for vertical or horizontal venting
Model 7TDVP8”
4 per box
Model 7TDVP12”
4 per box
Model 7TDVP24”
4 per box
Model 7TDVP36”
Model 7TDVP48”
Firestop Spacer
20012362
Attic Insulation Shield
Model 7DVAIS
Vertical/Horizontal Combination Offset Support
Model 7DVCS
20012301
18
584I
vent components
Vermont Castings DVR28 Direct Vent Gas Fireplace
Operating Instructions
Glass Information
Window Frame
Assembly
WARNING
Fireplace
Front
Never attempt to operate this direct vent fireplace
if the front glass panel is missing, open, cracked
or broken, as carbon monoxide poisoning could
result.
Always use a licensed, qualified service technician
to install replacement glass.
Glass
Panel
Always install genuine CFM Corporation
replacement glass in this fireplace. Authorized
replacement glass (complete with gasket and
window frame) is available from your CFM
Corporation dealer.
The installation of non-authorized replacement
glass will also void all product warranties.
�
�������
��������������
������������
FP1758
Fig. 31 Window frame assembly removal.
two or three times with������
a non-ammonia household
�������������
cleaner and warm water
(gas fireplace glass cleaner
����
is recommended). After
the initial cleaning process the
glass should be cleaned two or three times during each
operating season depending on the environment in the
house.
������������������
�������������
Clean the glass after the first two weeks of
operation.
Never clean the glass while it is still hot.
Never use abrasive cleaners.
Never strike or slam the glass.
��������������������
���������������
Window Frame Assembly Removal
1. Turn the fireplace OFF (including the pilot).
2. If the unit has been operating, allow time for the
components to cool.
3. Remove two (2) bolts on bottom side of unit holding
front trim face on. (Fig. 32)
4. Remove front trim face by tilting bottom out and lifting face off unit. (Fig. 32)
5. Remove two (2) bolts securing bottom door frame to
unit. (Fig. 31)
6. Tilt window frame assembly out slightly at the bottom, lift the frame up and away from the fireplace.
(Fig. 31)
7. To replace window frame assembly reverse procedure.
Removal and Re-fitting the Curve Face
The Curve face is fitted to the fireplace by hooking the
top edge of the face over the mounting brackets as
shown in Figure 32. Secure with two (2) screws on the
bottom face of the trim. (Fig. 32)
Top Mounting
Brackets
Curve Face
Glass Cleaning
It is necessary to clean the glass periodically. During
start-up condensation, which is normal, forms on the
inside of the glass and causes lint, dust and other
airborne particles to cling to the glass surface. Also
initial paint curing may deposit a slight film on the glass.
It is therefore recommended the glass be cleaned
20012301
Bottom Bracket
Control Cover Plate
KT779
Fig. 32 Hang Curve Face in place.
19
Vermont Castings DVR28 Direct Vent Gas Fireplace
Initial Lighting of Fireplace
Flame Characteristics
1. Install batteries supplied with remote control according to instructions on Page 22.
2. Install AA batteries supplied in bolt bag into “Battery Pack” on bottom side of fireplace according to
instructions on Page 23. NOTE: Sheet metal holding
box may need loosened to slide battery pack out.
3. Press and hold learn button on back side of module
for 10 seconds. You should hear a series of beeps.
Press and release learn button. You should hear a
single beep immediately. Press either the “ON” or
“OFF” button on the remote control transmitter. You
should hear a series of beeps indicating the transmitter code has been learned.
It is important to periodically perform a visual check of
the pilot and the burner flames. Compare them to Figures 35-36. If any of the flames appear abnormal call a
service person.
Front of Fireplace
FP1778
Battery Pack
Fig. 35 Correct pilot flame appearance.
Electronic
Module
������
���������
����
Back of Fireplace
Learn Button
(Back of electronic
control module)
Bottom View
FP1815
Fig. 33 Battery pack location������
on bottom of fireplace.
������������
Flame & Temperature
Adjustment
����
To adjust Hi/Lo setting, push either the high or low control button on remote control transmitter.
LG480
Fig. 36 Correct DVR28 flame. Center flame should be approximately 5¹⁄₂” (140 mm) above bottom window frame.
Inspecting the Venting System
ON
This appliance venting system is designed and constructed to develop a positive flow adequate to remove
�����������������
flue gases to the outside atmosphere.
OFF
HI
����
Any foreign objects in the venting system, except those
designed specifically for the venting system, may cause
spillage of flue gases.
LO
FP1759
FP1796
Fig. 34 Flame adjustment
for American Flame valve.
Wireless remote
3/07
20
To inspect the venting system, make sure the main gas
valve is off. Remove window frame assembly (Refer to
Window Frame Assembly Removal Section). Using a
flashlight, check the area above the baffle in the combustion dome. Clean if necessary.
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Lighting & Operating Instructions
For Fireplaces equipped with AF4000 Gas Valve
Warning: If you do not follow these instructions exactly, a fire or explosion may
result, causing property damage, personal injury and loss of life.
For Your Safety, Read the Following Warnings
before Lighting the Appliance
•
A. This fireplace is equipped with an ignition device
which automatically lights the pilot. DO NOT try to
light the pilot by hand.
B. BEFORE OPERATING, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than the
air and will settle on the floor.
What to do if you smell gas
• Do not try to light any appliance.
• Do not operate any electrical switch.
• Do not use any phone in your building.
•
Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
suppliers instructions.
If you cannot contact your gas supplier call
the Fire Department
C. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and replace
any part of the control system and any gas control
that has been under water.
Lighting Instructions
Spark to Pilot
1. STOP! Read the safety information above before
Pilot Assembly
continuing.
2. This appliance is equipped with an ignition device
“S” Connection
which automatically lights the pilot. DO NOT try to
Connect to Module
light the pilot by hand.
3. Access the gas control by removing the side cover
Pilot Adjustment
access door on the left side of the unit.
Screw
Pilot Gas Connection
4. Turn the remote switch, if used, OFF. Turn the Inlet Pressure
Side or Back
wireless remote, if used, OFF.
Tap
“I” Connection
Connect to
5. Wait five (5) minutes to clear out any gas.
Module
Then smell for gas, including near the floor.
If you smell gas, STOP. Follow instruction B
in the safety warnings above. If you do not
smell gas, go on to the next step.
6. Close the access door.
7. If the appliance will not operate, follow the
instructions TURNING OFF THE GAS TO
THE APPLIANCE, and call your service
Pilot Internal
Main Valve Internal Solenoid
Outlet
technician or gas supplier.
Solenoid
Connection
Connection
Orange &
white Wires
Pressure Tap
Green & White Wires
Turning Off the Gas to the Appliance
1. Turn the remote switch to the OFF position.
2. Turn OFF all electrical power to the fireplace if
service is required.
3. Open the lower access panel.
4. Turn the shut-off valve on the flexible gas line to
the OFF position.
1/2” Gas Supply
������
������������
����
1/2” NPT x 3/8” Flare
Shut-Off Valve
3/8” Flex Line
(From Valve)
Valve in the “ON” position
FP297A
20012301
21
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY
7/1/98
Vermont Castings DVR28 Direct Vent Gas Fireplace
Hand-Held Remote Transmitter Operating Instructions
If you cannot read or understand these installation instructions, do not attempt to operate.
Introduction
This transmitter operating range is approximately 20 feet (6 m). The transmitter operates on one of 1,048,576 security
codes that are programmed into the transmitter at the factory; this transmitter operates on radio frequencies with nondirectional signals. The receiver for this transmitter is built into the AF-4000 MOD module.
Transmitter
Wall Clip
Slot
The transmitter operates on (2) 1.5V AAA batteries. It is recommended that ALKALINE batteries always be used for longer
battery life and maximum operational performance.
��
On H/L
Button
Off
Continuous
Pilot Button
ON H/L
Before using the transmitter, install the (2) AAA transmitter batteries into the battery compartment. (Use caution that batteries
are installed in the proper direction.)
OFF/CONTINUOUS
PILOT BUTTON
MODE
Mode Button
SET
Set Button
Battery
Compartment
FP1818
ON H/L
1
FP1818
Skytech remote
9/07
Key Settings
1. ON H/L
OFF
Continuous
Pilot
2
MODE
3
2. OFF
CONTINUOUS PILOT
3. MODE
4. SET
SET
— Turns unit to ON and operates
the flame control HI or LO.
4
— Shuts the unit OFF and activates the continuous pilot on
feature.
— Changes unit from manual
mode to thermo mode.
— Sets temperature in thermo
mode.
LCD - Liquid Crystal Display
7
2
�����
1
4
3
����
���
����
5
1.
2.
3.
4.
5.
6.
DISPLAY
° F or ° C
FLAME
ROOM
TEMP
SET
7. PILOT
Indicates CURRENT room temperature.
Indicates degrees Fahrenheit or Celsius
Indicates burner/valve in operation
Indicates remote is in THERMO operation
Appears during manual operation
Appears while setting the desired temperature in the thermo operation
Appears in the Continuous Pilot mode
6
20012301
22
FP1819
LCD display
9/07
Vermont Castings DVR28 Direct Vent Gas Fireplace
Setting ° F / ° C Scale
�����
����
The factory setting for temperature is ° F. To change this
setting to ° C;
Press the ON H/L key and the OFF CONTINUOUS PILOT
key on the transmitter at the same time. This will change
from ° F to ° C. Follow this same procedure to change from
° C to ° F.
���
Manual Function
To operate the system in the manual “MODE” do the following:
����
Screen while depressing ON key
Screen after 3 second default
����
Screen while depressing OFF key
Screen after 3 second default
ON - HI Flame Operation
Press and release the ON H/L key. The appliance flame will
come ON and flame on HI.
During this time the LCD screen will show “HI”. After 3
seconds, the LCD screen will default to display room temperature and the word “TEMP” will show. (Flame icon will
FP1820
appear on the LCD screen in ON mode)
F-C display
ON - LO Flame Operation
9/07
Press and release the ON H/L key. The appliance flame will
stay ON and flame on LO.
During this time, the LCD screen will show “LO”. After 3
seconds, the LCD screen will default to display room temperature and the word “TEMP” will show. (Flame icon will
appear on the LCD screen in ON mode)
NOTE: If this SP1001H/LTH transmitter is used with the DC
motor drive HI/LO flame control, press and hold the ON H/L
key to raise or lower the flame height.
OFF Operation
����
Screen whild depressing OFF key
Screen after 3
second default
Press the OFF Continuous Pilot key and the appliance
flame will shut off. During this time the LCD screen will show
“OF”. After 3 seconds, the LCD screen will default to display room temperature and the word “TEMP” will also show
on the screen. (Flame icon will NOT appear on the LCD
screen in OFF mode)
Thermostat Function
Setting Desired Room Temperature
����
����
Screen after depressing MODE key
20012301
���
����
Screen while depressing SET key
This remote control system can be thermostatically controlled when the transmitter is in the THERMO mode. To set
the THERMO MODE and DESIRED room temperature.
Press the MODE key until the LCD screen shows the word
“ROOM”. The remote is now in the thermostatic mode.
NOTE: When the word “ROOM” is displayed on the
screen, the transmitter is in the thermo mode.
23
Vermont Castings DVR28 Direct Vent Gas Fireplace
To Change the Set Temperature
Press and hold the SET key until the desired set temperature is reached. (By pressing and holding the set
key, the LCD screen set numbers will increase from 45°
to 99°, then restart at 45°)
���
���
����
����
Release the SET key. The LCD screen will display the set
temperature for 3 seconds, then will flash the set temperature for 3 seconds, then the LCD screen will default
to display the room temperature.
To Disengage Thermo Mode
Press and release the MODE key or press the OFF
CONTINUOUS PILOT key to disengage the thermo
mode. The word “ROOM” on the LCD screen will not
show when the thermo is not in operation.
����
����
����
This feature allows you to change from a spark to pilot
system to a standing pilot system for appliances during
Cold Climate to keep the firebox warm.
�����
����
����
NOTE: The highest SET temperature is 99° Fahrenheit
FP1821
(32° Celsius) and the lowest temperature is 45° Fahrenset temp
heit (6° Celsius).
9/07
Continuous Pilot Feature
To operate the CONTINUOUS PILOT FEATURE do the
following:
����
ON OR OFF OPERATION
Press and hold the OFF CONTINUOUS PILOT key for
approximately 5 seconds, until the word “PILOT” appears
on the LCD screen.
NOTE: The word “PILOT” will appear on the LCD screen
in ON mode.
CP (Childproof) Feature
This SKYTECH remote control includes a CHILDPROOF
“LOCK-OUT” feature that allows the user to “LOCK-OUT”
operation of the appliance from the transmitter.
Setting “LOCK-OUT” - (CP)
• To activate the “LOCK-OUT” feature, press and hold
the ON H/L key and the MODE key at the same time
for 5 seconds. The letters “CP” will appear in the
TEMP frame on the LCD screen.
• To disengage the “LOCK-OUT”, press and hold the
ON H/L key and the MODE key at the same time for
5 seconds and the letters “CP” will disappear from
the LCD screen and the transmitter will return to its
normal operating condition.
• To verify the transmitter is in the CP lock-out mode,
press any key and the LCD screen will show “CP”.
NOTE: If the appliance is already operating in the ON or THERMO modes, engaging the “LOCK-OUT” will not cancel
the operating mode. Engaging the “LOCK-OUT” prevents only the manual operation of the transmitter. If in the auto
modes, the THERMO operation will continue to operate normally. To totally “LOCK-OUT” the operation of the transmitter’s operating signals; the transmitter’s mode must be set to OFF.
24
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Troubleshooting
AF4000 Valve
If erratic system behavior is observed that cannot be resolved by the methods outlined below, ensure that there is
not a transmitter with batteries installed that may be interfering. If a transmitter is packed with batteries installed, its
buttons may be depressed sending a constant signal which can interfere with the transmission of desired signals. A
transmitter with new batteries can have a range of over 100’ (30.4 m).
Module will not learn transmitter
• Ensure the REMOTE/OFF switch on the side of the module (Fig. 37) is set to REMOTE.
• Make sure the batteries in both the transmitter and receiver are installed in the
proper direction (Fig. 41) and are not drained. Individual battery voltage should be
no less than 1.4V for AA and AAA batteries, 2.8V for button cells, and 9,0V for 12V
batteries.
• Verify the transmitter indicates a signal is being sent. With thermostat transmitters,
the LCD display should indicate ON or OFF depending on which button is being
pressed. The LED indicator should illuminate on wall transmitters and on/off handheld transmitters. (Fig. 43) Buttons should be pressed and held for 1 to 2 seconds
to ensure a complete signal is sent.
• Make sure the transmitter is within the 20’ (6 m) operational range of the receiver.
• Ensure the 4-pin lead-set is securely connected from the battery pack to the
control module’s AUX connection. (Figs. 38, 41) If the A/C power adapter is used,
make sure the leads from the adapter are securely connected to the POWER
terminals on the control module. (Fig. 39)
• Press and hold the LEARN button on the module (Fig. 38) for approximately 10
seconds to clear the memory (you should hear a series of beeps from the receiver). Then press and release the learn button (you should hear a single beep
from the receiver), immediately press either the ON or OFF button on the transmitter (you should hear a series of beeps indicating the transmitter code has been
learned).
Figure 37: AF4000
MOD Module Right
Side
Continuous PIlot
Off/On Switch
Remote/Off
Switch
“S” Pilot Connection
Figure 38: AF4000
MOD Module Left Side
Adjustment
FP1762
“I” Pilot
Connection
Learn Button
AUX Connection
������
������������������������
����
FP1763
20012301
������
�����������������������
����
25
Vermont Castings DVR28 Direct Vent Gas Fireplace
Troubleshooting AF4000 Valve (continued)
Pilot will not light/stay lit
• Verify the gas supply is turned on.
• Verify the receiver is receiving the signal from the transmitter by listening for a
beep from the receiver when ON is pressed on the transmitter. If you do not hear
a beep, ensure the module has learned the transmitter (see above).
• Ensure the orange lead from the pilot assembly igniter is securely connected to
the terminal labeled “I” and the white lead from the flame rectification sensor is
securely connected to the terminal labeled “S” on the control module. (Fig. 37)
• Make sure the orange and white leads from the module are securely connected to
the terminals labeled “PILOT” on the valve body. (Fig. 42)
• Ensure the black GROUND wire is securely connected to an appropriate metal
portion of the valve or pilot assembly. A proper ground is essential to spark
igniter operation.
• Make certain the pilot flame is in contact with the flame rectification sensor on the
pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.
42) If the pilot flame is too small it will not contact the flame rectification sensor
and will not complete the safety circuit.
Figure 39: AF4000 MOD Module End
6 Volt DC Adapter
Power Connection
8 Pin IPI
Connection
FP1764
Figure 40: Wall Transmitter Face
Indicator Light
������
�����������������
����
30 MIN
60 MIN
120 MIN
Insert batteries into
holder and snap into
holder.
(Plus sides face front)
OFF
+
Plus
Side
+
Plus
Side
FP1766
FP1766
wall transmitter face
2/07
26
20012301
Vermont Castings DVR28 Direct Vent Gas Fireplace
Troubleshooting AF4000 Valve (continued)
• Ensure the CONTINUOUS PILOT switch on the control module (Fig. 37) is set
Pilot flame is always on/ will
not extinguish
to OFF.
• Verify the gas supply is turned on.
• Ensure the pilot flame will ignite. If not, see pilot flame troubleshooting above.
• Make sure the green and white leads from the module are securely connected to
Main flame will not light
the terminals labeled “MAIN: on the valve body. (Fig. 42)
• Make certain the pilot flame is in contact with the flame rectification sensor on
the pilot assembly. This valve is equipped with a pilot flame adjustment screw.
(Fig. 42) If the pilot flame is too small it will not contact the flame rectification
sensor and will not complete the safety circuit.
• Ensure the pilot flame is properly located to ignite the main flame.
• Ensure the black and red leads from the battery pack or the AF4000 110H/L
Flame height adjustment will
not work/works backwards
module are securely connected to the red and black leads from the motor drive
or H/L latching solenoid located on the valve body (red to red and black to
black).
• Verify the selector switch on the battery pack is set to DC MOTOR DRIVE or
LATCHING SOLENOID, depending upon which device is installed. (Fig. 41)
• Check functionality with all transmitters to determine if there is an issue with the
main control system or an individual transmitter. If the issue is with an individual
transmitter, make sure the batteries in both the transmitter and receiver are installed in the proper direction (Fig. 41, 43) and are not drained. Individual battery
voltage should be no less than 1.4V for AA and AAA batteries, 2.8V for button
cells, and 9.0V for 12V batteries.
Battery Pack - Back
Selector Switch
Latching Solenoid / DC Motor Drive
Figure 41: Battery Pack - Battery Compartment
HI/LO Connection
RED Wire
HI/LO Connection
BLACK WIRE
+
+
-
4 Pin AUX
Connection
FP1767
Figure 42: AF4000 Valve Face
FP1767
battery pack
2/07
MAIN
Main Connection
Inlet
Pilot Adj.
PILOT
Outlet
FP1769
Pilot Connection
20012301
27
FP1769
AF4000 valve face
Vermont Castings DVR28 Direct Vent Gas Fireplace
Troubleshooting AF4000 Valve (continued)
Room temperature displayed on handheld transmitter is not correct. (When
using Thermostatic transmiiters only).
Unit will not respond in
THERMO mode. Thermostatic transmitters only).
• Ensure the transmitter was not recently stored in a different environment (air-conditioned, heated) from that in which the transmitter is being tested. It may take up
to 3 hours for the temperature inside a packaged transmitter, and several minutes
for an unpackaged transmitter, to equalize with the room temperature.
• Ensure the thermostatic transmitter is within the 20’ (6 m) operational range.
• Make sure an ON or OFF command was not last sent from another transmitter.
These commands will over-ride the thermal commands from the handheld transmitter. To return the system to THERMO mode, press either ON or OFF on the
thermostatic transmitter, then press the MODE button to put the system in THERMO mode. Press and hold the SET button to change the set temperature. (Fig. 43)
• Verify the set temperature on the thermostatic remote is at least 2 degrees above
or below the room temperature. The system will not react to temperatures within 2
degrees of the set temperature.
Figure 43: Hand Transmitter
Back
Front
LCD Display
ON HI/LO
Button
��
OFF
ON H/L
OFF/Continuous
Pilot Button
OFF
HI
OFF/CONTINUOUS
PILOT BUTTON
LOW
MODE
AAA
Set Button
FP1768
12V (A23)
SET
AAA
Mode Button
ON
ON
FP1765
Figure 44: Continuous Pilot Indication on LCD Screen
FP1765
transmitter back
FP1768
2/07
transmitter front
2/07
�����
����
����
FP1770
20012301
28
������
��������������������������
Vermont Castings DVR28 Direct Vent Gas Fireplace
Maintenance
Burner and Burner Compartment
It is important to keep the burner and the burner
compartment clean. At least once per year the burner
compartment should be vacuumed and wiped out.
Cleaning the Standing
Pilot Control System
The burner and control system consists of
• burner tube
• pilot assembly
• gas valve
• gas orifice
Most of these components may require only an occasional checkup and cleaning and some may require
adjustment.
ROUTINE MAINTENANCE PROCEDURE
1. Turn off pilot light at remote wall switch.
2. Let fireplace cool if it has been running.
3. Remove window frame assembly. (Refer to Window
Frame Assembly Removal section)
4. Vacuum burner compartment especially around
orifice primary air openings.
5. Visually inspect pilot. Brush or blow away any dust
or lint accumulation.
6. Ignite pilot - Refer to Lighting Instructions.
7. Reinstall window frame assembly.
WARNING
Always use a qualified technician or service agency
to perform any repairs to this fireplace.
To obtain proper operation, it is imperative that the pilot
and burner’s flame characteristics are steady, not lifting
or floating.
Typically, the top 3/8” or 1/2” of the thermopile should
be engulfed in the pilot flame. (Fig. 45)
To adjust pilot burner; (by qualified service technician)
1. Remove pilot adjustment cap.
2. Adjust pilot screw to provide properly sized flame.
3. Replace pilot adjustment cap.
The primary air shutter is set at the factory and should
only be adjusted, if necessary, by a qualified service
technician.
FP1778
Fig. 45 Correct pilot flame appearance.
Optional Accessories
Curve Face Kit
Model #
ICVCTK04
ICVCTK05
������
���������
����
Color
Rustic Bronze
Charcoal
Screen Door Kit
Model #
ICVCSTK
Thermostatic Controls
(for bedroom use in Canada ONLY)
Model #
IMTFK
20011904
20012301
Description
Wall mounted thermostatic control
(wired)
Hand held ON/OFF and temperature
29
Vermont Castings DVR28 Direct Vent Gas Fireplace
2
1
3
4
5
6
7
11
9
10
8
13
17
12
15
16
14
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
without notice.
DVR28IN (GFYN4G0)
Ref.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
30
Description
Burner Tube
Rear Refractory
Ceramic Retainer
Bracket, Upper Trim
Lower Bracket Assembly
Valve Assy, VF4000
Main Module
SIT Pilot Assembly
24” Wire Harness 8-Pin, 8-Wire
Battery Power Pack
Solenoid Remote Hi/Lo
Glass Frame Assembly
On/Off HI/LO Remote Control
Restrictor Plate
Wall Mount Assy.
Burner Orifice #45 (.0820”)
Firestop
12301
DVR28 parts
3/07
DVR28
20012266
20011551
20012350
20011581
20011579
20012290
20011895
20012381
20012258
20012263
20012265
20011597
20012267
20012396
20012219
20012302
20012362
20012301
LIMITED LIFETIME WARRANTY
Vermont Castings DVR28 Direct Vent Gas Fireplace
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with
an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY
CFM Corporation (hereinafter referred to collectively as the Company)
warrants that your new Vermont Castings or Majestic Gas Fireplace/
Stove is free from manufacturing and material defects for a period of
one year from the date of purchase, subject to the following conditions
and limitations.
•
•
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber
of every Vermont Castings or Majestic gas product is warranted for
life against through wall perforation. All appliances equipped with an
Insta-Flame Ceramic Burner have limited lifetime coverage on the
ceramic burner plaque. Warrantees are made to the original owner
subject to proof of purchase and the conditions and limitations listed
on this Warranty Document
•
•
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a
period of three years.
Note: On porcelain enamel finished external parts and accessories The
Company offers no Warranty on chipping of enamel surfaces. Inspect
all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment
can be corrosive to the porcelain enamel finish. These conditions can
cause rusting of the cast iron beneath the porcelain enamel finish,
which will cause the finish to flake off.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year.
Glass doors are not warranted for breakage due to misuse or accident.
Glass doors are not covered for discoloration or burned in stains due to
environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar
mix and masonry cleaners may corrode the brass finish. The Company
will not be responsible for, nor will it warrant any brass parts which are
damaged by external chemicals or down draft conditions.
•
•
•
•
•
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and
mechanical components of the burner assembly are covered for one year.
All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and CFM
Corporation company supplied accessories are covered for a period of
one year.
CONDITIONS AND LIMITATIONS
•
•
•
•
This new Vermont Castings or Majestic product must be installed or
serviced by a qualified installer, preferably NFI or WETT (Canada)
certified, as prescribed by the local jurisdiction. It must be installed and
operated at all times in accordance with the Installation and Operating
instructions furnished with the product. Any alteration, willful abuse,
accident, or misuse of the product shall nullify this warranty.
This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier
of the Company.
The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
whether the repair work will be done in the customer’s home or in the
dealer’s shop.
If upon inspection, the damage is found to be the fault of the manufacturer,
repairs will be authorized at no charge to the customer parts and/or
labor.
20012301
•
•
Any part and/or component replaced under the provisions of this
warranty is covered for six months or the remainder of the original
warranty, whichever is longest.
This warranty is limited to the repair of or replacement of part(s) found
to be defective in material or workmanship, provided that such part(s)
have been subjected to normal conditions of use and service, after
said defect is confirmed by the Company’s inspection.
The company may, at its discretion, fully discharge all obligations
with respect to this warranty by refunding the wholesale price of the
defective part(s)
Any installation, labor, construction, transportation, or other related
costs/expenses arising from defective part(s), repair, replacement,
or otherwise of same, will not be covered by this warranty, nor shall
the Company assume responsibility for same. Further, the Company
will not be responsible for any incidental, indirect, or consequential
damages except as provided by law.
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR
LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC
RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM
STATE TO STATE.
All other warranties-expressed or implied- with respect to the product,
its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
The Company neither assumes, nor authorizes any third party to
assume on its behalf, any other liabilities with respect to the sale of
this Vermont Castings or Majestic product
The warranties as outlined within this document do not apply to
chimney components or other non CFM Corporation accessories used
in conjunction with the installation of this product..
Damage to the unit while in transit is not covered by this warranty but
is subject to claim against the common carrier. Contact the dealer
from whom you purchased your fireplace/stove (do not operate the
appliance as this might negate the ability to process the claim with the
carrier).
The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
This warranty is void if:
a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the
result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty,
your sales receipt, and the model/serial number of your CFM
Corporation product.
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK
YOURSELF.
31
Efficiency Ratings
Model
DVR28IN
EnerGuide Ratings
Fireplace Efficiency (%)
67.6
Steady State (%)
Fan-OFF
Fan-ON
85
n/a
CFM Corporation
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3
800-668-5323 • www.cfmcorp.com
D.O.E.
(AFUE%)
64.3