APC | 10000VA | Smart-UPS RT APC Smart-UPS RT 10000VA 208V

Smart-UPS RT
APC Smart-UPS RT 10000VA 208V
APC Smart-UPS RT, 8000 Watts / 10
kVA,Input 208V / Output 208V, Interface Port
DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot,
Extended runtime model, Rack Height 6 U
Includes: CD with software, Service Manual,
Smart UPS signalling RS-232 cable, User
Manual, Web/SNMP Management Card
Standard Lead Time: Usually in Stock
Smart-UPS RT Features & Benefits
Availability
Automatic internal
bypass
Scalable runtime
Intelligent Battery
Management
Hot-swappable
batteries
Automatic restart of
loads after UPS
shutdown
Temperaturecompensated battery
charging
Supplies utility power to the connected loads in the event of a UPS overload
condition or fault.
Allows additional run time to be quickly added as needed.
Maximizes battery performance, life, and reliability through intelligent,
precision charging.
Ensures clean, uninterrupted power to protected equipment while batteries
are being replaced
Automatically starts up the connected equipment upon the return of utility
power.
Prolongs battery life by regulating the charge voltage according to battery
temperature.
Manageability
Network manageable
InfraStruXure
Manager Compatible
SmartSlot
LED status indicators
Serial Connectivity
Provides remote management of the UPS over the network.
Enables centralized management via the APC InfraStruXure® Manager.
Customize UPS capabilities with management cards.
Quickly understand unit and power status with visual indicators.
Provides management of the UPS via a serial port.
Adaptability
Plug-and-Play external Ensures clean, uninterrupted power to the loads when adding extra runtime to
batteries
the UPS.
Rack/Tower
Protects the initial investment in the UPS when migrating from tower to rackconvertible
mount environment.
Flash-upgradeable
Easy implementation of new firmware upgrades.
firmware
Serviceability
User-replaceable
batteries
Automatic self-test
Increases availability by allowing a trained user to perform upgrades and
replacements of the batteries reducing Mean Time to Repair (MTTR)
Periodic battery self-test ensures early detection of a battery that needs to be
replaced.
Predictive failure
Provides early-warning fault analysis ensuring proactive component
notification
replacement.
Disconnected battery Warns when a battery is not available to provide backup power.
notification
Audible Alarms
Actively let you know if the unit is on battery, if the battery is low or if there
is an overload condition.
Protection
Frequency and voltage Gives higher application availability by correcting poor frequency and
regulation
voltage conditions without using the battery.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power
disturbances.
Input power factor
Minimizes installation costs by enabling the use of smaller generators and
correction
cabling.
Generator Compatible Ensures clean, uninterrupted power to the loads in the event of an extended
power outage
Cold-start capable
Provides temporary battery power when the utility power is out.
Resettable circuit
Enables a quick recovery from overload events.
breakers
Safety-agency
Ensures the product has been tested and approved to work safely with the
approved
connected service provider equipment and within the specified environment.
UL, FCC, CE, C-Tick approvals.
Output
Output Power Capacity
8000 Watts / 10 kVA
Max Configurable Power
8000 Watts / 10 kVA
Nominal Output Voltage
208V
Output Voltage Note
Configurable for 208 or 240 nominal output voltage
Efficiency at Full Load
92%
Output Voltage Distortion
Less than 3%
Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor
3:1
Waveform Type
Sine wave
Output Connections
(1) Hard Wire 3-wire (2PH + G)
(2) NEMA L6-20R
(2) NEMA L6-30R
Bypass
Internal Bypass (Automatic and Manual)
Input
Nominal Input Voltage
208V
Input Frequency
50/60 Hz +/- 5 Hz (auto sensing)
Input Connections
Hard Wire 3-wire (2PH + G)
Input voltage range for main
operations
160 - 280V
Other Input Voltages
240
Batteries & Runtime
Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules
4
Typical recharge time
2.20 hour(s)
Replacement Battery
RBC44
RBC™ Quantity
2
Typical Backup Time
at Half Load
14.9 minutes (4000 Watts)
Typical Backup Time
at Full Load
4.8 minutes (8000 Watts)
Runtime Chart
Smart-UPS RT
Extended Run Options
APC Smart-UPS RT 10000VA 208V
Communications & Management
Interface Port(s)
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot
Pre-Installed SmartSlot™ Cards
AP9619
Control panel
LED status display with load and battery bar-graphs and On Line : On Battery :
Replace Battery : Overload and Bypass Indicators
Audible Alarm
Alarm when on battery : distinctive low battery alarm : overload continuous tone
alarm
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping
response time : meets UL 1449
Physical
Maximum Height
432.00 mm
Maximum Width
263.00 mm
Maximum Depth
736.00 mm
Rack Height
6U
Net Weight
110.91 KG
Shipping Weight
129.09 KG
Shipping Height
552.00 mm
Shipping Width
597.00 mm
Shipping Depth
991.00 mm
Color
Black
Units per Pallet
1.00
Environmental
Operating Environment
0 - 40 °C
Operating Relative Humidity
0%
Operating Elevation
0-3000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from
surface of unit
55.00 dBA
Online Thermal Dissipation
2216.00 BTU/hr
Conformance
Regulatory Approvals
CSA,FCC Part 15 Class A,UL 1778
Standard Warranty
2 years repair or replace
ROHS/WEEE Compliance
RoHS 7b Exemption
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full
load rating of the UPS.
Hardwiring
Attention: Wiring must be performed by a qualified electrician.
1.
2.
3.
4.
5.
6.
Install a utility circuit breaker in accordance with local electrical codes (see tables below) for
input wiring only.
Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
Remove the access panel (see B).
Remove circular knockouts.
Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all
national and local electrical codes. (See tables and graphics.)
Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.
XLT, XLJ, AND XLTW MODELS
Input Connection
Output Connection (optional)
Wire to L1, L2, and
.
System
Wiring
Voltage
Current
Full Load
(Nominal)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)
SURT7500XLJ,
SURT7500XLT,
SURT7500XLTW
Input & Output
200/208/220V
40 amps
XLTW- 38 amps
50 amps / 2-pole for
Input Wiring Only
#8AWG/
10mm2
SURT10000XLJ,
SURT10000XLT,
SURT10000XLTW
Input & Output
200/208/220V
54 amps
XLTW-50 amps
70 amps / 2-pole for
Input Wiring only
#6AWG/
16mm2
Wire to L1A, L2A, and
.
XLI MODELS
Input Connections
Output Connection (optional)
Single-Phase: Wire to L1, N, and
.
Wire to L1A, N1, and
.
Three-Phase: Wire to L1, L2, L3, N, and
.
System
Wiring
Number
of
Phases
Voltage
Current
Full Load
(Nominal)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)
SURT7500XLI
Input
1
220/230/240V
38 amps
50 amps / 2-pole
10mm2
Input
3+
Neutral
380/400/415V
14 amps / phase when
online, 38 amps on L1
in bypass
50 amps / 4-pole
10mm2
Output
1
220/230/240V
38 amps
(not required)
10mm2
Input
1
220/230/240V
50 amps
63 amps / 2-pole
16mm2
Input
3+
Neutral
380/400/415V
18 amps / phase when
online, 50 amps on L1
in bypass
63 amps / 4-pole
16mm2
Output
1
220/230/240V
50 amps
(not required)
16mm2
SURT10000XLI
2