PRIMA Plank Cladding Technical Manual
PRIMA Plank is a versatile cladding product designed for external applications where superb weatherability and long-lasting durability are essential. It can be used for a range of applications, including external wall cladding, gable end cladding, cladding to masonry walls, fascia board, and decorative fencing. The planks are available in two patterns: Woodgrain and Smooth, and come in standard thicknesses of 7.5mm and 9.0mm.
Advertisement
Advertisement
Technical Manual
Designed to attain pure luxury
Aesthetic Cladding | Decorative Fencing | Gable End Cladding | External Wall Cladding | Fascia Board
1. Introduction
1.1 General
1.2 Applications
1.3 Features & Benefits
1.4 Tests and Certification
2. General Fixing Instructions
2.1 Material Selection
2.2 Framing Specification
2.3 Batten Specification
2.4 Fasteners
2.5 Sealing Joints & Gaps
2.6 Jointing Against Other Materials
3. External Wall & Gable End Cladding
3.1 General
3.2 Framing Construction
3.3 Flashing
3.4 Sarking
3.5 Plank Overlaps
3.6 Installation Procedures
3.7 Fixing to Timber
3.8 Fixing to Steel
3.9 Joints
3.10 Ground Clearance
3.11 Corners
3.12 Details at Openings
4. Cladding to Masonry Wall
4.1 General
4.2 Battening Requirement
4.3 Installation Method
4.4 Sarking
4.5 Jointing
4.6 Corners
4.7 Openings
4.8 Wall to Eaves Junction
5. Fascia Board
5.1 General
5.2 Support
5.3 Installation
5.4 Joints
6. Decorative Fencing
6.1 General
6.2 Framing Requirememt
6.3 Installation
7. Finishes Recommendation
8. Working Instructions
8.1 Cutting
8.2 Drilling
8.3 Handling & Stroage
02
02
03
06
08
09
10
10
2.1 Material Selection
thickness should be selected based on the intended applications. For general cladding, fascia board and fencing applications, 7.5mm thick plank is adequate. When higher performance (stronger and more impact resistant) material is desired, use 9.0mm .
For best result, the use of 9.0mm thick is highly recommended for fascia board application where rafters are to be exposed (in absence of eaves lining board).
Trimming plank to a size less than the standard width will reduce its capacity to withstand loads. In instances where reduced-width planks are desirable such as for fencing application, always refer to Hume
Cemboard before specifying or applying them.
Do not apply in areas where it remains in contact with standing water.
2.2 Framing Specification
can be applied to timber or light gauge steel framing members. Construction shall be in accordance with local building practice.
Framing components must have adequate durability for the intended use. These durability criteria shall among others include resistance to weather; corrosion and pest (i.e. termite attack).
Framing timber should be thoroughly dry and selected to minimize shrinkage when planks are installed.
Steel framing must be fabricated from cold-formed galvanized light gauge steel of a minimum 0.55mm to 1.60mm base metal thickness.
As the straightness of finished wall is highly dependent on workmanship of framework, best result can be achieve when frame straightness is between 3mm to 4mm in any 3000mm length.
2.3 Batten Specification
Thick hot rolled structural steel sections and masonry wall must be battened prior to installation of cladding.
Use timber batten with a minimum of 25mm thick x 50mm wide to allow adequate nail penetration.
Steel battens must have a minimum 35mm face width. They are typically 'Z' or top hat sections. Use only galvanised light gauge steel of a minimum 0.55mm to 1.55mm base metal thickness.
2.4 Fasteners
Select the appropriate type of fasteners based on the type of framing.
Fasteners should have acceptable level of durability and be suitably coated for the intended application.
can be fixed by hand nailing or air gun nailing. For screw
fixing, use screw gun with high torque and variable speed of zero to
2,500 revolution per minute fitted with a depth control attachment.
Nail head should finish flush with the face and avoid overdriving.
Drive screw slightly below the plank face and cover fastener head with exterior grade cementitious patching compound. Smoothen with sandpaper if necessary before painting.
2.5 Sealing Joints and Gaps
Gaps at plank joints, corners and openings must be sealed with flexible/ paintable polyurethane sealant. Sealant must be compatible with cementitious panel products. Apply masking tape at both plank edges and start filling the bottom edge and squeezing the sealant in the upward direction. Use spatula to smoothen and remove any excess sealant Remove masking tape immediately upon completion.
Sealant manufacturer's instruction must be adhered to. Sealant must only be painted as recommended by the manufacturer.
2.6 Jointing Against other Material
When butt jointing and other building materials such as masonry wall, a minimum of 6mm gap must be provided. Seal gap with paintable/ flexible sealant, as shown in Figure 1.
2.4 Fasteners
Select the appropriate type of fasteners based on the type of framing.
Fasteners should have acceptable level of durability and be suitably coated for the intended application.
can be fixed by hand nailing or air gun nailing. For screw
fixing, use screw gun with high torque and variable speed of zero to
2,500 revolution per minute fitted with a depth control attachment.
Nail head should finish flush with the face and avoid overdriving.
Drive screw slightly below the plank face and cover fastener head with exterior grade cementitious patching compound. Smoothen with sandpaper if necessary before painting.
2.5 Sealing Joints and Gaps
Gaps at plank joints, corners and openings must be sealed with flexible/ paintable polyurethane sealant. Sealant must be compatible with cementitious panel products. Apply masking tape at both plank edges and start filling the bottom edge and squeezing the sealant in the upward direction. Use spatula to smoothen and remove any excess sealant Remove masking tape immediately upon completion.
Sealant manufacturer's instruction must be adhered to. Sealant must only be painted as recommended by the manufacturer.
2.6 Jointing Against other Material
When butt jointing and other building materials such as masonry wall, a minimum of 6mm gap must be provided. Seal gap with paintable/ flexible sealant, as shown in Figure 1.
1 Introduction
1.1 General
is an autoclaved cellulose fibre reinforced cement siding board manufactured by Hume Cemboard Industries Sdn Bhd, an MS
ISO 9001:2000 accredited company. Manufactured from Portland cement, cellulose fibre, finely ground sand and water, has become extremely popular when a relatively maintenance free timber planking appearance is desired.
1.2 Applications
is designed for external applications where superb weatherability and long-lasting durability form part and parcel of performance criteria. These applications includes:-
• External wall cladding
• Gable end cladding
• Cladding to masonry wall
• Fascia board
• Decorative fencing
is used where there is a requirement for traditional timber look and to add character and depth to flat mundane surfaces.
1.3 Features & Benefits
• Natural timber look (Woodgrain)
• Weather resistant
• Will not rust or rot
• Termite resistant
• Does not warp or twist
• Fire resistant- Class '0'
1.4 Tests and Certification
has been approved by Fire and Rescue Department,
Malaysia as a Class '0' building material under the Malaysian Uniform
Building By-law 1984.
has been tested in accordance with BS 476; Fire tests on building material and structure. The test results are as follows:-
1.4.1 Serviceable Life
When installed and maintained as per good building practice and specifications described in this manual, is expected to have serviceable life of 50 years.
1.4.2 Standard Sizes and Mass
comes in standard thickness of 7.5mm and 9.0mm. It is available in two patterns:
- Woodgrain
has a texture on the front surface
- Smooth
is available with a flat unsanded surface
Approximate masses at Equilibrium Moisture Content of 7%, at temperature of 27°C ± 2°C and relative humidity of 65% to 95% are:-
Thickness x Width x Length
Smooth & Woodgrain
• 7.5mm x 230mm x 3660mm
• 7.5mm x 230mm x 4200mm
• 7.5mm x 300mm x 3660mm
• 7.5mm x 300mm x 4200mm
Smooth
• 9.0mm x 230mm x 3660mm
• 9.0mm x 230mm x 4200mm
Approximate Mass per Piece
9.1kg
10.6kg
11.8kg
13.8kg
10.9kg
12.7kg
2 General Fixing Instructions
2.1 Material Selection
thickness should be selected based on the intended applications. For general cladding, fascia board and fencing applications, 7.5mm thick plank is adequate. When higher performance (stronger and more impact resistant) material is desired, use 9.0mm .
For best result, the use of 9.0mm thick is highly recommended for fascia board application where rafters are to be exposed (in absence of eaves lining board).
Trimming plank to a size less than the standard width will reduce its capacity to withstand loads. In instances where reduced-width planks are desirable such as for fencing application, always refer to Hume
Cemboard before specifying or applying them.
Do not apply in areas where it remains in contact with standing water.
2.2 Framing Specification
can be applied to timber or light gauge steel framing members. Construction shall be in accordance with local building practice.
Framing components must have adequate durability for the intended use. These durability criteria shall among others include resistance to weather; corrosion and pest (i.e. termite attack).
Framing timber should be thoroughly dry and selected to minimize shrinkage when planks are installed.
Steel framing must be fabricated from cold-formed galvanized light gauge steel of a minimum 0.55mm to 1.60mm base metal thickness.
As the straightness of finished wall is highly dependent on workmanship of framework, best result can be achieve when frame straightness is between 3mm to 4mm in any 3000mm length.
2.3 Batten Specification
Thick hot rolled structural steel sections and masonry wall must be battened prior to installation of cladding.
Use timber batten with a minimum of 25mm thick x 50mm wide to allow adequate nail penetration.
Steel battens must have a minimum 35mm face width. They are typically 'Z' or top hat sections. Use only galvanised light gauge steel of a minimum 0.55mm to 1.55mm base metal thickness.
02
2.1 Material Selection
thickness should be selected based on the intended applications. For general cladding, fascia board and fencing applications, 7.5mm thick plank is adequate. When higher performance (stronger and more impact resistant) material is desired, use 9.0mm .
For best result, the use of 9.0mm thick is highly recommended for fascia board application where rafters are to be exposed (in absence of eaves lining board).
Trimming plank to a size less than the standard width will reduce its capacity to withstand loads. In instances where reduced-width planks are desirable such as for fencing application, always refer to Hume
Cemboard before specifying or applying them.
Do not apply in areas where it remains in contact with standing water.
2.2 Framing Specification
can be applied to timber or light gauge steel framing members. Construction shall be in accordance with local building practice.
Framing components must have adequate durability for the intended use. These durability criteria shall among others include resistance to weather; corrosion and pest (i.e. termite attack).
Framing timber should be thoroughly dry and selected to minimize shrinkage when planks are installed.
Steel framing must be fabricated from cold-formed galvanized light gauge steel of a minimum 0.55mm to 1.60mm base metal thickness.
As the straightness of finished wall is highly dependent on workmanship of framework, best result can be achieve when frame straightness is between 3mm to 4mm in any 3000mm length.
2.3 Batten Specification
Thick hot rolled structural steel sections and masonry wall must be battened prior to installation of cladding.
Use timber batten with a minimum of 25mm thick x 50mm wide to allow adequate nail penetration.
Steel battens must have a minimum 35mm face width. They are typically 'Z' or top hat sections. Use only galvanised light gauge steel of a minimum 0.55mm to 1.55mm base metal thickness.
2.4 Fasteners
Select the appropriate type of fasteners based on the type of framing.
Fasteners should have acceptable level of durability and be suitably coated for the intended application.
can be fixed by hand nailing or air gun nailing. For screw
fixing, use screw gun with high torque and variable speed of zero to
2,500 revolution per minute fitted with a depth control attachment.
Nail head should finish flush with the face and avoid overdriving.
Drive screw slightly below the plank face and cover fastener head with exterior grade cementitious patching compound. Smoothen with sandpaper if necessary before painting.
2.5 Sealing Joints and Gaps
Gaps at plank joints, corners and openings must be sealed with flexible/ paintable polyurethane sealant. Sealant must be compatible with cementitious panel products. Apply masking tape at both plank edges and start filling the bottom edge and squeezing the sealant in the upward direction. Use spatula to smoothen and remove any excess sealant Remove masking tape immediately upon completion.
Sealant manufacturer's instruction must be adhered to. Sealant must only be painted as recommended by the manufacturer.
2.6 Jointing Against other Material
When butt jointing and other building materials such as masonry wall, a minimum of 6mm gap must be provided. Seal gap with paintable/ flexible sealant, as shown in Figure 1.
Fasteners to Timber
Table: Fastener Specification
Fasteners to Steel masonry wall
2.8mm Ø x 40mm Wire Nails
Steel thickness 0.55mm to 0.75mm
No. 8 x 32mm Self-embedding head, self-drilling Screws
Steel thickness 0.8mm to 1.6mm
No. 8 x 32mm Self-embedding head, self-drilling “Wing Teks” Screws
1.
2.
3.
4.
5.
Note:
Drive nail head snug or flush with plank face.
Pre-drilling is required when nailing between 20mm to 50mm from the plank end.
Drive screw heads not more than 1mm below plank face.
Overdriven fastener point should be cover with exterior grade cementitious patching compound before painting.
Hold plank firmly against the frame while driving the fasteners.
apply sealant
6mm
vapour permeable sarking/ building paper (optional) cladding
Figure 1: Jointing with other material
3 External Wall & Gable End Cladding
3.1 General
is suitable for general wall cladding application when a lightweight wall system is preferred. The usage includes construction of new buildings such as residential dwellings and resorts. In addition,
PRIMAplank can also be used for renovation/ extension of existing buildings especially in the construction of upper storey.
3.2 Framing Construction
must be supported at 600mm maximum centres. Refer
Figure 2. The minimum stud face width shall be as follows:-
• Timber framing - 50mm min.
• Steel framing - 35mm min.
Timber framing is typically 50mm x 75mm and light-gauge metal framing is typically 35mm x 64mm x 0.55mm BMT.
When on-stud jointing is preferred, stud face width must be increased to provide for adequate edge fixing distance. Use frame off-cuts to
pack stud at plank joint if required.
nogging top plate stud
maximum tres stud spacing
600mm
600mm
600mm
mineral wool/ fibreglass insulation (optional) vapour permeable sarking/ building paper (optional) end joints to be staggered
(refer joint detail options) cladding
Figure 2: Horizontal planking
flashing starter strip
03
3.3 Flashing
When applied as external wall cladding it is a good building practice to apply flashing material at corners, above the head and under the
sill of an opening.
3.4 Sarking
During windy condition, the external pressure would generally be greater than the building's internal pressure. The pressure differential will likely draw water into the wall cavity through the plank's joints and laps. It is recommended to install vapour permeable sarking between and the framing surface. The use of reflective
sarking will enhance the thermal insulation property of the cladding system.
3.5 Plank Overlaps
For external cladding applications, plank must overlap the previous course by a minimum of 25mm. Plank overlap may be increased to achieve the desired exposed plank surface. Higher overlaps may also improve the weatherproofing of a framed-wall particularly when sarking material is not applied. When necessary, overlap may be increased to obtain full-course planking to match the wall height.
To facilitate plank installation with consistent overlaps, use a lap
gauge. A lap gauge can be fabricated from off-cuts or timber piece. Refer Figure 3.
3.7 Fixing to Timber
When applied onto timber framing, must be nailed at centre of overlap through both thicknesses, as shown in Figure 4.
3.8 Fixing to Steel
Planks are screwed to light gauge steel framing through the top plank only. Refer Figure 5.
3.9 Joints
Joint options are shown below. When applied as wall cladding, plank joints should preferably be staggered between each plank course.
"off-stud" jointing method incorporates proprietary PVC
jointer between plank ends. Refer Figure 6.
On-stud jointing can be done by butt jointing plank ends with moderate contact. Alternatively, provide a nominal 3mm gap and seal joint with exterior grade paintable/ flexible sealant. Refer Figure 7.
3.11 Corners
Internal and external corners may be finished with timber stops as illustrated in Figure 9.
Alternatively, when timber posts are utilized, abutted to the side of the posts. Refer Figure 10.
3.10 Ground Clearance
Provide a minimum of 150mm clearance between bottom edge of plank (or starter strip) and the earth as shown in Figure 8.
3.12 Details at Openings
When applying plank at around window or door openings, allow an approximately 5mm clearance at the sill, jamb and head. Seal gap with paintable/ flexible sealant Do not apply sealant between head
flashing and plank edge.
2.1 Material Selection
thickness should be selected based on the intended applications. For general cladding, fascia board and fencing applications, 7.5mm thick plank is adequate. When higher performance (stronger and more impact resistant) material is desired, use 9.0mm .
For best result, the use of 9.0mm thick is highly recommended for fascia board application where rafters are to be exposed (in absence of eaves lining board).
Trimming plank to a size less than the standard width will reduce its capacity to withstand loads. In instances where reduced-width planks are desirable such as for fencing application, always refer to Hume
Cemboard before specifying or applying them.
Do not apply in areas where it remains in contact with standing water.
2.2 Framing Specification
can be applied to timber or light gauge steel framing members. Construction shall be in accordance with local building practice.
Framing components must have adequate durability for the intended use. These durability criteria shall among others include resistance to weather; corrosion and pest (i.e. termite attack).
Framing timber should be thoroughly dry and selected to minimize shrinkage when planks are installed.
Steel framing must be fabricated from cold-formed galvanized light gauge steel of a minimum 0.55mm to 1.60mm base metal thickness.
As the straightness of finished wall is highly dependent on workmanship of framework, best result can be achieve when frame straightness is between 3mm to 4mm in any 3000mm length.
2.3 Batten Specification
Thick hot rolled structural steel sections and masonry wall must be battened prior to installation of cladding.
Use timber batten with a minimum of 25mm thick x 50mm wide to allow adequate nail penetration.
Steel battens must have a minimum 35mm face width. They are typically 'Z' or top hat sections. Use only galvanised light gauge steel of a minimum 0.55mm to 1.55mm base metal thickness.
2.4 Fasteners
Select the appropriate type of fasteners based on the type of framing.
Fasteners should have acceptable level of durability and be suitably coated for the intended application.
can be fixed by hand nailing or air gun nailing. For screw
fixing, use screw gun with high torque and variable speed of zero to
2,500 revolution per minute fitted with a depth control attachment.
Nail head should finish flush with the face and avoid overdriving.
Drive screw slightly below the plank face and cover fastener head with exterior grade cementitious patching compound. Smoothen with sandpaper if necessary before painting.
2.5 Sealing Joints and Gaps
Gaps at plank joints, corners and openings must be sealed with flexible/ paintable polyurethane sealant. Sealant must be compatible with cementitious panel products. Apply masking tape at both plank edges and start filling the bottom edge and squeezing the sealant in the upward direction. Use spatula to smoothen and remove any excess sealant Remove masking tape immediately upon completion.
Sealant manufacturer's instruction must be adhered to. Sealant must only be painted as recommended by the manufacturer.
2.6 Jointing Against other Material
When butt jointing and other building materials such as masonry wall, a minimum of 6mm gap must be provided. Seal gap with paintable/ flexible sealant, as shown in Figure 1.
3.1 General
is suitable for general wall cladding application when a lightweight wall system is preferred. The usage includes construction of new buildings such as residential dwellings and resorts. In addition,
PRIMAplank can also be used for renovation/ extension of existing buildings especially in the construction of upper storey.
3.2 Framing Construction
must be supported at 600mm maximum centres. Refer
Figure 2. The minimum stud face width shall be as follows:-
• Timber framing - 50mm min.
• Steel framing - 35mm min.
Timber framing is typically 50mm x 75mm and light-gauge metal framing is typically 35mm x 64mm x 0.55mm BMT.
When on-stud jointing is preferred, stud face width must be increased to provide for adequate edge fixing distance. Use frame off-cuts to
pack stud at plank joint if required.
3.3 Flashing
When applied as external wall cladding it is a good building practice to apply flashing material at corners, above the head and under the
sill of an opening.
3.4 Sarking
During windy condition, the external pressure would generally be greater than the building's internal pressure. The pressure differential will likely draw water into the wall cavity through the plank's joints and laps. It is recommended to install vapour permeable sarking between and the framing surface. The use of reflective
sarking will enhance the thermal insulation property of the cladding system.
3.5 Plank Overlaps
For external cladding applications, plank must overlap the previous course by a minimum of 25mm. Plank overlap may be increased to achieve the desired exposed plank surface. Higher overlaps may also improve the weatherproofing of a framed-wall particularly when sarking material is not applied. When necessary, overlap may be increased to obtain full-course planking to match the wall height.
To facilitate plank installation with consistent overlaps, use a lap
gauge. A lap gauge can be fabricated from off-cuts or timber piece. Refer Figure 3.
3.6 Installation Procedure
These steps provide a general guide for installation of .
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Ensure framing is true and align prior to fixing .
Apply building paper sarking over the framework.
Fix flashing at all internal and external corner and heads of openings such as door and window.
Install timber moulds at internal and external corners.
Secure a 40mm wide starter strip or treated timber strip along the bottom plate.
Use a spirit level to locate the top edge of the first course of the plank
Drive a series of guide nails around the perimeter of the timber framework to indicate the top edge of the first course of the plank.
Fix the first plank starting from the external corner. Set the top
edge of the plank flush against the guide nails and the end
abutting the (moderate contact) timber corner stop. Drive fastener to the bottom plate through the plank thickness and the starter strip at 200mm centres maximum.
Fix the balance of the planks of the first course around the building. Planks may be joined with proprietor PVC jointer.
Provide a minimum of 25mm overlap between each successive plank course. Measure the total wall height to be clad and calculate the suitable overlap so that a near full-width plank finishes at the top of the clad wall. Remove the guide nails and continue the next course of the plank with an off-cut plank. This is done to ensure that the plank joints would be staggered
between courses.
Check level occasionally.
7.5mm
new/ subsequent plank course sarking/ building previous course stud
7.5mm
x= net cover width (plank width - overlap) eg 230mm - 25mm = 205mm
Figure 3: Lap gauge
3.7 Fixing to Timber
When applied onto timber framing, must be nailed at centre of overlap through both thicknesses, as shown in Figure 4.
vapour permeable sarking/ building paper (optional)
(
25mm min. overlap internal lining board
3.8 Fixing to Steel
Planks are screwed to light gauge steel framing through the top plank only. Refer Figure 5.
vapour permeable sarking/ building paper (optional)
( flat head nail fixed at centre of overlap cladding
/
Figure 4: Fastening to timber frame
25mm min. overlap cladding screw fixed through the top plank only
25mm min. overlap internal lining board
/
Figure 5: Fastening to steel frame
04
3.9 Joints
Joint options are shown below. When applied as wall cladding, plank joints should preferably be staggered between each plank course.
"off-stud" jointing method incorporates proprietary PVC
jointer between plank ends. Refer Figure 6.
On-stud jointing can be done by butt jointing plank ends with moderate contact. Alternatively, provide a nominal 3mm gap and seal joint with exterior grade paintable/ flexible sealant. Refer Figure 7.
3.11 Corners
Internal and external corners may be finished with timber stops as illustrated in Figure 9.
Alternatively, when timber posts are utilized, abutted to the side of the posts. Refer Figure 10.
3.10 Ground Clearance
Provide a minimum of 150mm clearance between bottom edge of plank (or starter strip) and the earth as shown in Figure 8.
3.12 Details at Openings
When applying plank at around window or door openings, allow an approximately 5mm clearance at the sill, jamb and head. Seal gap with paintable/ flexible sealant Do not apply sealant between head
flashing and plank edge.
3.3 Flashing
When applied as external wall cladding it is a good building practice to apply flashing material at corners, above the head and under the
sill of an opening.
3.4 Sarking
During windy condition, the external pressure would generally be greater than the building's internal pressure. The pressure differential will likely draw water into the wall cavity through the plank's joints and laps. It is recommended to install vapour permeable sarking between and the framing surface. The use of reflective
sarking will enhance the thermal insulation property of the cladding system.
3.5 Plank Overlaps
For external cladding applications, plank must overlap the previous course by a minimum of 25mm. Plank overlap may be increased to achieve the desired exposed plank surface. Higher overlaps may also improve the weatherproofing of a framed-wall particularly when sarking material is not applied. When necessary, overlap may be increased to obtain full-course planking to match the wall height.
To facilitate plank installation with consistent overlaps, use a lap
gauge. A lap gauge can be fabricated from off-cuts or timber piece. Refer Figure 3.
3.7 Fixing to Timber
When applied onto timber framing, must be nailed at centre of overlap through both thicknesses, as shown in Figure 4.
3.8 Fixing to Steel
Planks are screwed to light gauge steel framing through the top plank only. Refer Figure 5.
3.1 General
is suitable for general wall cladding application when a lightweight wall system is preferred. The usage includes construction of new buildings such as residential dwellings and resorts. In addition,
PRIMAplank can also be used for renovation/ extension of existing buildings especially in the construction of upper storey.
3.2 Framing Construction
must be supported at 600mm maximum centres. Refer
Figure 2. The minimum stud face width shall be as follows:-
• Timber framing - 50mm min.
• Steel framing - 35mm min.
Timber framing is typically 50mm x 75mm and light-gauge metal framing is typically 35mm x 64mm x 0.55mm BMT.
When on-stud jointing is preferred, stud face width must be increased to provide for adequate edge fixing distance. Use frame off-cuts to
pack stud at plank joint if required.
3.9 Joints
Joint options are shown below. When applied as wall cladding, plank joints should preferably be staggered between each plank course.
"off-stud" jointing method incorporates proprietary PVC
jointer between plank ends. Refer Figure 6.
stud vapour permeable sarking/ building paper (optional)
( internal lining board
/ damp-proof course or flashing cladding vapour permeable sarking/ building paper (optional) exterior grade timber or fibre cement trim
150mm min. clearance
PVC jointer cladding concrete slab
Figure 8: Ground Clearance
3.11 Corners
Internal and external corners may be finished with timber stops as illustrated in Figure 9.
Figure 6: Off-stud joint
On-stud jointing can be done by butt jointing plank ends with moderate contact. Alternatively, provide a nominal 3mm gap and seal joint with exterior grade paintable/ flexible sealant. Refer Figure 7.
3mm
gap trim-packing for narrow stud as required
(at plank joint only) vapour permeable sarking/ building paper (optional) nailing to support (pre-drilling when nailing between 20mm to 50mm from plank end) moderate contact or allow
3mm gap and seal gap with paintable/ flexible sealant cladding internal lining corner studs vapour permeable sarking/ building paper (optional) flashing (not required when reflective sarking is used)
External Corner
25 x 50mm timber stop cladding
Figure 9: Timber stop corners
Internal Corner
Alternatively, when timber posts are utilized, abutted to the side of the posts. Refer Figure 10.
stud timber post
3.10 Ground Clearance
Figure 7: On-stud joint
Provide a minimum of 150mm clearance between bottom edge of plank (or starter strip) and the earth as shown in Figure 8.
cladding
3mm gap (apply sealant) vapour permeable sarking/ building paper (optional)
External corner
internal lining
Internal corner
Figure 10: Timber post corners
05
3.12 Details at Openings
When applying plank at around window or door openings, allow an approximately 5mm clearance at the sill, jamb and head. Seal gap with paintable/ flexible sealant Do not apply sealant between head
flashing and plank edge.
4.1 General
can be clad onto masonry wall to enhance the aesthetic appearance of residential or commercial buildings.
4.2 Battening Requirement
Masonry wall must be battened prior to applying . Battens must be spaced vertically at 600mm maximum centres. Ensure batten's straightness is within the acceptable tolerance. Battens must be adequately fastened onto the masonry wall.
4.3 Installation Method
may be installed horizontally. In any case, support must be provided at 600mm centres. lnstallation method is similar to that of external cladding application.
Battens can be applied directly onto relatively flat/ even masonry wall. Refer Figure 15.
Provide spacers or brackets when battening uneven masonry wall as shown in Figure 16. Alternatively, sub-framing may be installed horizontally to uneven surface at approximately 1500mm maximum interval before securing the battens. All framing components must be adequately secured onto masonry wall. Consult a qualified engineer to verify structural adequacy if required.
4.8 Wall-to-Eaves Junction
Provide adequate ventilation between masonry wall and cladding. The ventilation can either be provided through the roof or below the eaves. Ventilated path though the roof is depicted in
Figure 21 below.
4.4 Sarking
It is recommended to install a vapour permeable sarking material on the masonry wall prior to fixing battens.
4.5 Jointing
Planks can be jointed with PVC jointer or Butt Joined. These jointing methods are similar to the external cladding joints shown in Figure 6
& 7.
4.6 Corners
Internal and external corners can be decorated with exterior grade timber trim. Trim can also be fabricated using cladding, cut to the desired width. Refer Figure 17.
4.7 Opening
Door or window opening may be finished with trims. Provide Smm gap between and trims around the opening as described in Figure11.
When desired, opening may be decorated with in-situ concrete or
pre-formed coping as illustrated in Figure 18, 19 and 20.
3.3 Flashing
When applied as external wall cladding it is a good building practice to apply flashing material at corners, above the head and under the
sill of an opening.
3.4 Sarking
During windy condition, the external pressure would generally be greater than the building's internal pressure. The pressure differential will likely draw water into the wall cavity through the plank's joints and laps. It is recommended to install vapour permeable sarking between and the framing surface. The use of reflective
sarking will enhance the thermal insulation property of the cladding system.
3.5 Plank Overlaps
For external cladding applications, plank must overlap the previous course by a minimum of 25mm. Plank overlap may be increased to achieve the desired exposed plank surface. Higher overlaps may also improve the weatherproofing of a framed-wall particularly when sarking material is not applied. When necessary, overlap may be increased to obtain full-course planking to match the wall height.
To facilitate plank installation with consistent overlaps, use a lap
gauge. A lap gauge can be fabricated from off-cuts or timber piece. Refer Figure 3.
3.7 Fixing to Timber
When applied onto timber framing, must be nailed at centre of overlap through both thicknesses, as shown in Figure 4.
3.8 Fixing to Steel
Planks are screwed to light gauge steel framing through the top plank only. Refer Figure 5.
3.1 General
is suitable for general wall cladding application when a lightweight wall system is preferred. The usage includes construction of new buildings such as residential dwellings and resorts. In addition,
PRIMAplank can also be used for renovation/ extension of existing buildings especially in the construction of upper storey.
3.2 Framing Construction
must be supported at 600mm maximum centres. Refer
Figure 2. The minimum stud face width shall be as follows:-
• Timber framing - 50mm min.
• Steel framing - 35mm min.
Timber framing is typically 50mm x 75mm and light-gauge metal framing is typically 35mm x 64mm x 0.55mm BMT.
When on-stud jointing is preferred, stud face width must be increased to provide for adequate edge fixing distance. Use frame off-cuts to
pack stud at plank joint if required.
3.9 Joints
Joint options are shown below. When applied as wall cladding, plank joints should preferably be staggered between each plank course.
"off-stud" jointing method incorporates proprietary PVC
jointer between plank ends. Refer Figure 6.
On-stud jointing can be done by butt jointing plank ends with moderate contact. Alternatively, provide a nominal 3mm gap and seal joint with exterior grade paintable/ flexible sealant. Refer Figure 7.
3.10 Ground Clearance
Provide a minimum of 150mm clearance between bottom edge of plank (or starter strip) and the earth as shown in Figure 8.
3.11 Corners
Internal and external corners may be finished with timber stops as illustrated in Figure 9.
Alternatively, when timber posts are utilized, abutted to the side of the posts. Refer Figure 10.
3.12 Details at Openings
When applying plank at around window or door openings, allow an approximately 5mm clearance at the sill, jamb and head. Seal gap with paintable/ flexible sealant Do not apply sealant between head
flashing and plank edge. optional vapour permeable sarking to lap over flashing head flashing backing piece as required
5mm gap between plank and flashing
5mm clearance around opening
(apply sealant) window frame minimum 25mm thick window trim cladding full plank width is recommended
Figure 11: Window/ door opening detail
cladding vapour permeable sarking/ building paper (optional) nominal 5mm clearance
(do not apply sealant) head flashing
( internal lining board
/
Figure 12: Head Flashing Detail
lintel
) architrave window frame window frame sill flashing architrave window frame backing piece as required architrave
( internal lining board
/
) vapour permeable sarking/ building paper (optional) cladding backing piece as required
( internal lining board
/
nominal 5mm clearance
(apply sealant) vapour permeable sarking/ building paper (optional)
Figure 14: Door/ window jamb detail
cladding
Figure 13: Sill Flashing Detail
4.1 General
can be clad onto masonry wall to enhance the aesthetic appearance of residential or commercial buildings.
4.2 Battening Requirement
Masonry wall must be battened prior to applying . Battens must be spaced vertically at 600mm maximum centres. Ensure batten's straightness is within the acceptable tolerance. Battens must be adequately fastened onto the masonry wall.
4.3 Installation Method
may be installed horizontally. In any case, support must be provided at 600mm centres. lnstallation method is similar to that of external cladding application.
4 Cladding To Masonry Wall
Battens can be applied directly onto relatively flat/ even masonry wall. Refer Figure 15.
Provide spacers or brackets when battening uneven masonry wall as shown in Figure 16. Alternatively, sub-framing may be installed horizontally to uneven surface at approximately 1500mm maximum interval before securing the battens. All framing components must be adequately secured onto masonry wall. Consult a qualified engineer to verify structural adequacy if required.
06
4.8 Wall-to-Eaves Junction
Provide adequate ventilation between masonry wall and cladding. The ventilation can either be provided through the roof or below the eaves. Ventilated path though the roof is depicted in
Figure 21 below.
4.4 Sarking
It is recommended to install a vapour permeable sarking material on the masonry wall prior to fixing battens.
4.5 Jointing
Planks can be jointed with PVC jointer or Butt Joined. These jointing methods are similar to the external cladding joints shown in Figure 6
& 7.
4.6 Corners
Internal and external corners can be decorated with exterior grade timber trim. Trim can also be fabricated using cladding, cut to the desired width. Refer Figure 17.
4.7 Opening
Door or window opening may be finished with trims. Provide Smm gap between and trims around the opening as described in Figure11.
When desired, opening may be decorated with in-situ concrete or
pre-formed coping as illustrated in Figure 18, 19 and 20.
masonry wall masonry wall vapour permeable sarking/ building paper (optional) timber/ steel batten installed vertically at 600mm max. centres cladding installed horizontal
Figure 15: Battening onto flat masonry wall
vapour permeable sarking/ building paper (optional) framing spacer or bracket at
1200mm centres timber/ steel batten installed vertically at 600mm max. centres cladding installed horizontal
Figure 16: Battening onto uneven masonry wall
4.4 Sarking
It is recommended to install a vapour permeable sarking material on the masonry wall prior to fixing battens.
4.5 Jointing
Planks can be jointed with PVC jointer or Butt Joined. These jointing methods are similar to the external cladding joints shown in Figure 6
& 7.
4.6 Corners
Internal and external corners can be decorated with exterior grade timber trim. Trim can also be fabricated using cladding, cut to the desired width. Refer Figure 17.
External Corner
masonry wall exterior timber or fibre cement trim vapour permeable sarking/ building paper (optional) masonry wall timber/ steel batten installed vertically at 600mm max. centres cladding nominal 5mm clearance
(apply sealant) in-situ concrete or pre-formed coping to architect’s approval window frame
Figure 18: Window head detail
cladding vapour permeable sarking/ building paper (optional)
internal Corner
Figure 17: Corner details
4.7 Opening
Door or window opening may be finished with trims. Provide Smm gap between and trims around the opening as described in Figure11.
When desired, opening may be decorated with in-situ concrete or
pre-formed coping as illustrated in Figure 18, 19 and 20.
in-situ concrete or pre-formed coping to architect’s approval window frame nominal 5mm clearance
(apply sealant) vapour permeable sarking/ building paper (optional) cladding masonry wall
Figure 19: Window sill detail
07
4.1 General
can be clad onto masonry wall to enhance the aesthetic appearance of residential or commercial buildings.
4.2 Battening Requirement
Masonry wall must be battened prior to applying . Battens must be spaced vertically at 600mm maximum centres. Ensure batten's straightness is within the acceptable tolerance. Battens must be adequately fastened onto the masonry wall.
4.3 Installation Method
may be installed horizontally. In any case, support must be provided at 600mm centres. lnstallation method is similar to that of external cladding application.
Battens can be applied directly onto relatively flat/ even masonry wall. Refer Figure 15.
Provide spacers or brackets when battening uneven masonry wall as shown in Figure 16. Alternatively, sub-framing may be installed horizontally to uneven surface at approximately 1500mm maximum interval before securing the battens. All framing components must be adequately secured onto masonry wall. Consult a qualified engineer to verify structural adequacy if required.
4.8 Wall-to-Eaves Junction
Provide adequate ventilation between masonry wall and cladding. The ventilation can either be provided through the roof or below the eaves. Ventilated path though the roof is depicted in
Figure 21 below.
4.4 Sarking
It is recommended to install a vapour permeable sarking material on the masonry wall prior to fixing battens.
4.5 Jointing
Planks can be jointed with PVC jointer or Butt Joined. These jointing methods are similar to the external cladding joints shown in Figure 6
& 7.
4.6 Corners
Internal and external corners can be decorated with exterior grade timber trim. Trim can also be fabricated using cladding, cut to the desired width. Refer Figure 17.
4.7 Opening
Door or window opening may be finished with trims. Provide Smm gap between and trims around the opening as described in Figure11.
When desired, opening may be decorated with in-situ concrete or
pre-formed coping as illustrated in Figure 18, 19 and 20.
4.1 General
can be clad onto masonry wall to enhance the aesthetic appearance of residential or commercial buildings.
4.2 Battening Requirement
Masonry wall must be battened prior to applying . Battens must be spaced vertically at 600mm maximum centres. Ensure batten's straightness is within the acceptable tolerance. Battens must be adequately fastened onto the masonry wall.
4.3 Installation Method
may be installed horizontally. In any case, support must be provided at 600mm centres. lnstallation method is similar to that of external cladding application.
Battens can be applied directly onto relatively flat/ even masonry wall. Refer Figure 15.
Provide spacers or brackets when battening uneven masonry wall as shown in Figure 16. Alternatively, sub-framing may be installed horizontally to uneven surface at approximately 1500mm maximum interval before securing the battens. All framing components must be adequately secured onto masonry wall. Consult a qualified engineer to verify structural adequacy if required.
window frame masonry wall
4.8 Wall-to-Eaves Junction
Provide adequate ventilation between masonry wall and
plank
cladding. The ventilation can either be provided through the roof or below the eaves. Ventilated path though the roof is depicted in
Figure 21 below.
vapour permeable sarking/ building paper (optional) fascia board ventilation through soffit/ roof
/
eaves lining board masonry wall masonry wall vapour permeable sarking/ building paper (optional) cladding in-situ concrete or pre-formed coping to architect’s approval nominal 5mm clearance
(apply sealant)
Figure 20: Window detail
cladding timber/ steel batten installed vertically at 600mm max. centres
Figure 21: Wall ventilation detail
5 Fascia Board Introductions
5.1 General
superior durability makes it a perfect choice for fascia board around the roof perimeter. With the choice of 'smooth' and
'woodgrain' texture, fascia board is not only aesthetically pleasing but also cost effective.
5.2 Support
fascia board is normally fixed to timber or metal rafters/
trusses with spacing not exceeding 600mm centres. When support spacing exceeds 600mm, provide a continuous battening behind the fascia board. Alternatively, a 'dummy' rafter/ truss should be provided as intermediate support. The use of 9mm thick plank is highly recommended when support spacing is more than 600mm centres.
5.3 Installation
Apply a minimum of 2 fasteners at each rafter or truss end. Drive fastener 12mm from plank edge and 50mm from corner.
Fix a metal angle capping at ends of metal rafters/ trusses to facilitate
fascia board installation as described in Figure 23.
Fixings of attachment (such as bracket for gutter) to fascia board must be connected to the roof structural element.
5.4 Joints
Planks can be jointed with PVC jointer or Butt Joined. Provide 3mm gap if joint is to be sealed. These jointing options are shown in Figure
22 & 23. When Off-support Joint without PVC jointer is preferred, provide additional metal/ timber backing piece behind the fascia board. Ensure planks are secured to the backing piece. Hold backing
piece firmly while driving the fasteners.
rafter/ truss at 600mm centres roof batten fastener fascia board t fast ener a
300mm
max.
PVC mould (to be located not more than 150mm away from rafter/ truss in absence of eaves lining batten) timber beading as required eaves lining batten/ support
*PVC mould is available for
7.5mm thick plank only eaves lining board
Figure 22: PVC joint (Timber frame)
08
metal rafter/ truss at
600mm max. centres backing piece
12mm
min.
fascia board
09
50mm
min fastener
3mm gap sealed with flexible/ paintable sealant butt joint (moderate contact) timber beading as required eaves lining board
Figure 23: Butt joint & sealant (Metal rafter/ truss)
6 Decorative Fencing
6.1 General
can be incorporated in the construction of conventional
masonry, timber or steel framed fencing for medium to high-end terrace houses as well as semi-D or bungalows. 9mm is recommended for this application.
6.2 Framing Requirement
Framing durability must satisfy the minimum requirement of the intended use. It is recommended to use exterior grade (treated
timber) or steel hollow section to form the support. Steel hollow
section must be suitably coated to resist external weather.
6.3 Installation
can be installed vertically or horizontally. In any case, support must be provided at 400mm centres maximum. Install fasteners approximately 30mm from edge and 50mm from corner of plank. Fix at least 2 fasteners at each support.
ends must not overhang (cantilever) more than 100mm from the support.
The following fasteners are suitable if it is desired to have screw heads exposed:-
• Timber Support: Use No.10 x 30mm Hexagon head, Type 17 point screws
• Steel support: Use No.10 x 25mm Hexagon head, self-drilling
point screws
Refer to screw manufacturer's instruction on the minimum screw penetration to framing member: gap to architect approval
30mm min.
Horizontal Section
fencing applied vertically gap to architect approval
100mm overhang
100mm overhang timber/ steel frame
Front Elevation
Figure 24: Vertical fencing
30mm min.
from edge masonry wall
timber/ steel frame at
400mm max.centre
gap to architect approval fencing applied horizontally
610mm
max.
timber/ steel frame
30mm min. from edge
Horizontal Section
Figure 25: Horizontal fencing
7 Finishes Recommendations
Under normal circumstances must be coated within
3 months after installation. For best result, decorate with
2 coats of 100% quality acrylic paint. For general-purpose applications, there is no requirement for primers or sealers. Ensure planks are dry prior to painting. For decorative fencing application, plank must be coated on both surfaces and all edges. All plank exposed surfaces and edges must be painted.
masonry work gap to architect approval
Front Elevation
Semi-transparent stains and shellac/ varnish are generally formulated for wood and not suitable for fibre cement products.
In all cases, coating manufacturer's recommendations must be strictly adhered to.
8 Working Instructions
8.1 Cutting
Cutting must be carried out in a well-ventilated area using one of the following methods:-
• Score and Snap - Score the plank face with 'score and snap'. Repeat until depth reaches 1/3 of plank thickness. Snap plank upward to achieve clean break. Trim cut edge with rasp if necessary.
Handling & Storage
must be stacked on flat ground and supported wfth level bearers prior to installation. Ensure all timber bearers of a stacked plank are aligned with other stacks. Improper plank stacking may result in permanent plank deformation that causes unsightly appearance such as waviness.
must always be kept dry, preferably stored under a protected shade. When stored outdoors, it must be protected from water ingress and weather by covering with tarpaulin sheet. Allow wet plank to dry to equilibrium under a natural ventilated condition prior to installation.
To minimize breakages. must be carried with up-right.
Figure 26: Score and Snap Method (left), Machine Cut (right)
8.2 Hand Saw
The use of fine-toothed hand saw coupled with quick jabbing action will normally'produced best result.
8.3 Power Tool
When large amount of plank cutting is involved, use power cutting tool equipped with carbide-tipped or diamondtipped circular saw.
Drilling
Small holes can be formed using high-speed (HSS) drill bits. Larger circular holes can be created by drilling a series of small holes around the perimeter of the proposed hole, and gently tapping out the waste piece. Smoothen the rough drilled edge with rasp if necessary.
10
50 Years Durability
WARRANTY
Hume Cemboard Industries Sdn Bhd (“the Company”) warrants that it will at all times ensure that the products referred to herein (“the Products”) shall be supplied by it to the purchaser free of any manufacturing defects and defective materials used in their manufacture.
In the event and if contrary to this assertion the Products prove to be defective, whether as a result of manufacturing defects or arising from the Company’s use of defective materials, the Company will supply replacement Products. The Company shall, however, have the option and may choose to reimburse the purchaser the purchase price of the Products instead. The Company shall not be liable for any economic or consequential losses arising from any use of defective Products.
This warranty shall be void unless the purchaser has, in its handling and installation of the Products, complied with the recommendations contained in this brochure and other good building practices expected of a reasonable purchaser.
ADVISORY NOTE
Successful installations of Hume Cemboard Industries Sdn Bhd’s Products depend on a large number of factors that are outside of the scope of this brochure. Particular design, detail, construction requirements and workmanship are beyond the control of the Company. As such, Hume Cemboard Industries Sdn Bhd’s warranty does not extend to non-usability of Products or damage to Products arising from poor or defective designs or systems or poor quality of workmanship in the installation of Products.
For more information, please contact us at:
No. 12 Jalan Tandang, 46050 Petaling Jaya, Selangor, Malaysia.
Malaysia Sales Tel: + 603 7625 9999 Fax: +603 7625 7822 Email: [email protected]
Oversea Sales Tel: + 603 7625 3880 Fax: +603 7625 3990 Email: [email protected]
www.primaf
ibrecement.com
Advertisement
Key Features
- Natural timber look (Woodgrain)
- Weather resistant
- Will not rust or rot
- Termite resistant
- Does not warp or twist
- Fire resistant- Class '0'