Aerionics Inc.
3601 N. St. Paul Ave.
Sioux Falls, SD 57104
Attn: Jeffrey Christiansen
RESEARCH REPORT NO.: 930483
Approval Date: August 9, 2014
Approval Expires: August 9, 2015
GENERAL APPROVAL - Carbon Monoxide Detection System - Manufactured by Macurco / Aerionics
Inc. - Controller Model “DVP-120" - Rated 120VAC, 60HZ, 1.0 Amp and Carbon Monoxide (CO) Sensor
Model “CM-6" - Rated 24VAC, 60HZ, 5VA.
DETAILS
This approval is for fire, shock, and electrical hazards only and does not address those aspects of detection
of gases the device is designed or calibrated to detect.
CONDITIONS OF APPROVAL
The installation and use of the carbon monoxide detection system is approved when the following
provisions are met:
1.
The Controller Model DVP-120 - shall be plainly and permanently marked in letter heights not
smaller than 1/8 inch on a contrasting background where readily visible with the following:
A.
Manufacturer's name,
(Macurco / Aerionics Inc.)
B.
Model designation,
(DVP-120 )
C.
Serial Number,
D.
Electrical rating, in Volts, Amperes and Frequency,
E.
“NOT SUITABLE FOR HAZARDOUS LOCATIONS”,
H.
“For Carbon Monoxide Detection Only.”,
I.
“For use with Macurco / Aerionics, Inc., CM-6 Carbon Monoxide Sensor ONLY”,
J.
“For Indoor / Dry Installations ONLY.”,
K.
“The installation of this CO detection system shall be based on the conditions of approval
listed in Research Report number 930483. Not valid if RR is not current. For a copy of the
RR visit www.LADBS.org or call 323-224-2168.”
LADBS G-5 (Rev.6/08)
(120VAC, 1.0Amp, 60HZ)
AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER
Aerionics Inc.
Carbon Monoxide Detection System
2.
Page 2 of 3
RR 930483
The Carbon Monoxide Sensor Model CM-6 shall be plainly and permanently marked on a
contrasting background where readily visible with the following:
A.
B.
C.
D.
E.
F.
G.
Manufacturer's name,
(Macurco / Aerionics Inc.)
Model designation,
(CM-6)
Electrical rating,
(24VAC, 60HZ, 5VA)
Manufactured date,
“Carbon Monoxide Sensor”
“For use with Macurco / Aerionics, Inc. DVP-120 Controller ONLY.”
“This CO Sensor must be replaced within 7 years of the manufactured date.”
3.
The detection system shall be installed, calibrated, and maintained by qualified personnel in
accordance with the manufacturer's instructions. The installation of the detection system shall
comply with the applicable provisions of the Los Angeles City Codes (Building, Electrical,
Mechanical and Fire).
4.
Plans for the installation of the carbon monoxide detection system shall be submitted to and
approved by the Mechanical Plan Check and the Electrical Plan Check prior to each installation.
5.
The performance and sensitivity of the Carbon Monoxide (CO) Detection System must be
evaluated, tested and listed by an approved recognized testing agency.
6.
An electrical permit shall be obtained prior to installation or relocation of this equipment in the
City of Los Angeles.
7.
When the concentration of carbon monoxide reaches 50 ppm, the ventilation system shall activate
and shall operate until the carbon monoxide level drops below 35 ppm.
8.
An audible and visible alarm shall be provided in at a constantly manned monitoring location.
When the carbon monoxide concentration reaches 150 ppm for more than 15 minutes or when the
concentration reaches 200 ppm, the visual and audible alarms shall be activated.
9.
The audible device shall have a different tone from life safety devices.
10.
The carbon monoxide monitoring system shall be serviced by qualified personnel at least once a
year and it shall always be in optimum operating condition. The owner shall maintain all service
records and make them available to the Department of Building and Safety for inspection when
requested.
11.
A part, when replaced, shall be of the identical original approved manufactured part and rating,
unless otherwise approved by the Los Angeles City Electrical Testing Laboratory.
12.
This approval shall be void if the product is modified without prior authorization from the Los
Angeles City Electrical Testing Laboratory.
13.
A copy of this conditional approval letter shall be made available at each installation site.
Aerionics Inc.
Carbon Monoxide Detection System
Page 3 of 3
RR 930483
DISCUSSION
The product covered in this Research Report is a Carbon Monoxide (CO) Detection System for use in nonhazardous locations such as commercial buildings. The detection system monitors the carbon monoxide
level in the surrounding air and activates the ventilation system when the gas level exceeds 50 ppm. If the
gas concentration rises above OSHA-recommended upper limits, an audible and visual alarm will be
activated. The performance and sensitivity of this Carbon Monoxide (CO) Detection System was evaluated
and accepted by an approved recognized testing agency.
An on-board microcomputer supervises and verifies the operation of the system and displays the status to
the indicator lights. If a malfunction occurs, the ventilation system is activated and a fault warning signal
is activated.
When this system is installed in accordance with the provisions of this General Approval, it should meet
the minimum safety standards of the Los Angeles City Electrical Code.
For this General Approval to be valid on any installation in the City of Los Angeles, an engineer or
inspector of the Department of Building and Safety may make a determination that all conditions of the
General Approval required to provide equivalency have been met.
This General Approval is in accordance with Section 93.0303 of the Electrical Code pertaining to "New
Materials and Methods of Construction", and does not waive the requirements of the City of Los Angeles
Building Code.
This General Approval is neither a product endorsement nor a certification of function of accuracy of the
approved item.
APPROVED BY:
Behrooz Hooriani, P.E.
Electrical Engineer
Electrical Testing Laboratory
2319 Dorris Place
Los Angeles, CA 90031
(323) 224-2168 Tel
(323) 224-2161 Fax
www.LADBS.org
CO Sensor, Model CM-6
Controller, Model DVP-120