I n d u s t ry Leading Te c h n o l o g y

Includes
Modbus and
DNP 3.0
Shark 100T
Transducer Only
I n d u s t ry Leading Te c h n o l o g y
• High End Meter Performance
• Low End Economical Pricing
Shark 100
M e t e r / Tr a n s d u c e r
• Our Easiest to Use Meter Ever!
A G G R E S S I V E
T E C H N O L O G Y
Feature Summary
• 0.2% Class Revenue Certifiable Energy and Demand
Metering
• Meets ANSI C12.20 (0.2%) and IEC 687 (0.2%)
Accuracy Classes
• Multifunction Measurements including Voltage,
Current, Power, Frequency, Energy, etc.
• Optional KYZ Pulse
• Power Quality Measurements (%THD and Alarm
Limits)
• V-Switch® Technology - Field Upgrade without
Removing Installed Meter
• 3 Line .56" Bright Red LED Display
• % of Load Bar for Analog Meter Perception
• RS485 Modbus and DNP 3.0 Protocol - 57.6K Baud
• IrDA Port for PDA Remote Read
A G G R E S S I V E
• Ultra Compact, Easy to Install
T E C H N O L O G Y
• Fits Both ANSI and DIN Cut-Outs
Applications
Introduction
Electro Industries introduces one of the industry's highest performance revenue grade panel meters. Based on an all new platform,
this low cost meter significantly outperforms other devices many
times its price. This unit is perfect for new metering applications
and for a simple replacement to existing analog meters.
The Shark excels in metering energy accurately exceeding ANSI
C12.20 (0.2%)
and IEC 687 (0.2%)
energy measurement
standards. The unit utilizes high speed DSP technology with high
resolution A/D conversion to provide revenue certifiable accuracy
for Utility Billing, Substation Metering, Submetering and Critical
Metering applications.
2
• Utility Metering
• Commercial Metering
• Substations
• Industrial Metering
• Power Generation
• Campus Metering
• Submetering
• Analog Meter Replacement
SHARK 100
V-Switch, Measurement Upgrade Packs
The
Shark
100
is
equipped
with
EIG’s
exclusive
V- S w i t c h ®
Te c h n o l o g y. V-Switch® is a virtual firmware-based switch that allows
you to enable meter features through communication, even af t e r
installation. Using V-Switches, you can purchase what you require
now and field upgrade functionality as needed. This allows you to
optimize your metering investment. Begin with a simple indication
meter and upgrade it to full functioning energy billing meter with
advanced measurement capability. Advanced versions of the Shark
Available V-Switches:
•
V-Switch 1 – Volts and Amps Meter – Default
• V-Switch 2 – Volts, Amps, kW, kVAR, PF, kVA, Freq.
• V-Switch 3 – Volts, Amps, kW, kVAR, PF, kVA, Freq.
kWh, kVAh, kVARh and DNP 3.0
• V-Switch 4 – Volts, Amps, kW, kVAR, PF, kVA, Freq.
kWh, kVAh, kVARh, %THD Monitoring, Limit
Exceeded Alarms and DNP 3.0
100 (V3 and V4) also include DNP 3.0 communication protocol.
Accuracy
Measured
Parameters
Accuracy %
of Reading
Display Range
Voltage L-N
0.1%
0-9999 Scalable V or kV
Voltage L-L
0.1%
0-9999 V or kV Scalable
Current
0.1%
0-9999 Amps or kAmps
+/- Watts
0.2%
0-9999 Watts, kWatts, MWatts
+/-Wh
0.2%
5 to 8 Digits Programmable
+/-VARs
0.2%
0-9999 VARs, kVARs, MVARs
+/-VARh
0.2%
5 to 8 Digits Programmable
VA
0.2%
0-9999 VA, kVA, MVA
VAh
0.2%
5 to 8 Digits Programmable
PF
0.2%
+/- 0.5 to 1.0
Frequency
0.01 Hz
45 to 65 Hz
%THD
5.0%
0 to 100%
% Load Bar
1-120%
10 Digit Resolution Scalable
N o t e : Typical results are more accurate. Applies to 3 Element WYE
and 2 Element Delta Connections.
Traceable Watt-Hour Test Pulse for
Accuracy Verification
Measured
Values
Voltage L-N
•
•
•
Voltage L-L
•
•
•
Current Per Phase
•
•
•
•
Watts
•
•
•
•
VAr
•
•
•
•
VA
•
•
•
•
PF
•
•
•
•
+Watt-hr
•
-Watt-hr
•
Watt-hr net
•
+VAR-hr
•
-VAR-hr
•
VAR-hr net
•
VA-hr
•
Frequency
•
•
•
%THD
•
•
•
Voltage Angles
•
Current Angles
•
% of Load Bar
•
To be certified for revenue metering, power providers and utility companies
need to know that the billing energy meter will perform to the stated accuracy.
To verify the meter’s performance and calibration, power providers use field
test standards to ensure that the unit’s energy measurements are correct.
Real-Time Avg Max Min
Since Shark 100 is a traceable revenue meter, it contains a utility grade test
pulse allowing power providers to verify and confirm that the meter is
performing to its rated accuracy. This is an essential feature required of all
billing grade meters.
3
Easy To Use and Install
EIG Engineers designed this meter to be as easy to use and
install as possible. From user interface to mechanical construction, many hours were spent to make the Shark straightforward
and intuitive so an installer with minimal meter experience and
• Easy to Use Faceplate Programming
• PC Setup
• PDA Setup using IrDA Port
training can succeed with the product. Shark is programmed
• Phasor Diagram Showing Wiring Status
using a PDA, a PC Computer or through a simple keypad inter-
• Auto Scroll Feature
face. Additionally, using the PC or PDA, a technician or electrician
can see a visual phasor diagram of the vectors insuring that CT
and Voltage polarities are correct. All inputs are color coordinated
and have clear simple-to-understand labeling to avoid cross wiring
mistakes by installers. This is very useful in OEM applications in
which time of install affects the cost of the product.
• Analog Style % of Load Bar
• Shallow Panel Depth
• Quick Connect Voltage and Com Leads
• Quick Connect Current Pass Through
• Color Coordinated Voltage and Current Inputs
Large .56” LEDs
Only 3.25”
Reading Type
Designator
Tx Rx Indicator LEDs
Screen
Selectors
RS 485
Communication
IrDA
Port
Wh Pulse
% Load Bar
Universal
Voltage Inputs
Auto Scale
Indicator
Standard Feature Includes Real Time Phasor Analysis
4
Current
“Gills”
SHARK 100
Superior Voltage and Current Inputs
The Shark 100 is ruggedly designed for harsh electrical appli-
•
cations on both high voltage as well as low voltage power sys-
through the meter without any physical termination on the meter.
tems. This is especially important in Power Generation, Utility
This insures that the meter cannot be a point of failure on the CT
Substation and Critical User applications. The structural and
circuit. This is preferable to utility users when sharing relay class
electrical design of this meter was developed based on the rec-
CTs. No Burden is added to the secondary CT circuit.
ommendations and approvals of many of our Utility customers.
Method One – CT Pass Through. The CT passes directly
• Method Two – Current “Gills.” This unit additionally provides
Universal Voltage Inputs
ultrarugged termination pass-through bars, allowing the CT
Voltage inputs allow measurement to 416 Volts Line to Neutral
leads to be terminated on the meter. This, too, eliminates any
and 721 Volts Line to Line. This insures proper meter safety
possible point of failure at the meter. This method is also a pre-
when wiring directly to high voltage systems. One unit will per-
ferred technique for insuring that relay class CT integrity is not
form to specification on 69 Volt, 120 Volt, 230 Volt, 277 Volt and
compromised. Inferior designs do not provide this advanced
347 Volt power systems.
protective aspect and utilize terminal blocks to pass CT current
through a soldered connection on a printed circuit board.
Current Inputs
Shark’s stud-based design insures that your CTs will not open in
Current inputs uniquely use a dual input method:
a fault condition.
Nickel Plated
Brass Current
“Gill”
Method One
Method Two
CT wires pass
through meter
(dia. 0.177” / 4.5mm)
Inherently
Safe Design
CT wires terminate
to meter
Utility Peak Demand Metering
The Shark 100 provides user-configured Block Window or
using 3 subintervals, providing a new demand reading
Rolling Window Demand. This allows you to set up a
every 5 minutes based on the last 15 minutes. Readings for
particular utility demand profile. Block Window Demand is
k W, kVA R, kVA and PF are calculated using utility demand
demand used over a fixed user-configured demand period
structures. All other parameters offer max and min capabil-
(usually 5, 15 or 30 minutes). Rolling Window Demand is a
ity over the user-selectable averaging period. Vo l t a g e
f i xed window demand that moves for a user specified sub-
provides an instantaneous max and min reading, displaying
interval period. An ex a m p l e would be a 15-minute demand
the highest surge and lowest sag seen by the meter.
5
Advanced Communication Capability with IrDA Interface
The Shark 100 provides two independent Communication ports with advanced features.
Back Mounted Port with KYZ Pulse
•
Front Mounted IrDA Communication
(option 485P)
RS485 - This port allows RS485 communication using Modbus
or DNP3.0 Protocols. Baud rate are from 9600 to 57.6k.
Uniquely, the Shark also has an optical IrDA port, allowing the
unit to be set up and programmed using a PDA or remote lap-
• KYZ Pulse - In addition to the RS485, the meter also
top without need for a communication cable. Just point at the
includes a KYZ pulse mapped to positive energy. This is a
meter with an IrDA-equipped PC or PDA and configure it. COPI-
fixed energy pulse. Pulse values are:
K(h) at Test Volts less than 150V=0.0501151926
LOT EXT is a Windows CE software package that allows you to
K(h) at Test Volts more than 150V=0.2004607704
simply point at a Shark, configure it and poll readings.
COPILOT EXT (Windows CE)
Wireless Communication
Serial
Modbus or DNP 3.0
Serial RS485
Master
Host
Direct PDA Interface
Simultaneous Dual Communication Paths
Shark 100T ANSI
and DIN Mounting
Shark 100 ANSI
and DIN Mounting
The unit mounts directly in an ANSI C39.1 (4” Round form) or an IEC
The Shark 100T is a transducer version of the Shark100 which does not
92 mm DIN square form. This is perfect for new installations and for
include a display. The unit mounts directly to a DIN rail and provides an
existing panels. In new installations, simply use existing DIN or ANSI
RS485 Modbus or DNP 3.0 output.
punches. For existing panels, pull out old analog meters and replace
them with the Shark 100. The meter uses standard voltage and current inputs so that CT and PT wiring do not need to be replaced.
ANSI Mounting
DIN Mounting
3.56”
(90.4mm)
3.38” Sq
(85.9mm)
4 x 0.2”
(5.1mm)
DIN Mounting
Brackets
4.0” dia.
(102mm)
3.56”
(90.4mm)
1.69”
(43mm)
6
Shark 100T - DIN Rail Mounted Transducer
SHARK 100
Dimensional Drawings
Shark 100 Face
Shark 100 T Side
Shark 100 Side
Wiring Diagrams
3 Phase 4 Wire WYE Direct
3 Phase 3 Wire Delta Direct
3 Phase 4 Wire WYE with PTS
3 Phase 3 Wire Delta with PTS
7
Specifications
Max at 11Amps
Voltage Inputs
• 0-416 Volts Line To Neutral,
0-721 Volts Line to Line
• Universal Voltage Input
•
•
Input Withstand Capability –
Meets IEEE C37.90.1 (Surge
Withstand Capability)
• Burden: 0.36VA per phase Max
at 600V, 0.014VA at 120 Volts
• Input wire gauge max (AWG
2
12 / 2.5mm )
• Note: Accuracy specs doubled for
2.5 Element connections.
Current Inputs
Class 10: (0 to 11) A,
5 Amp Nominal
• Class 2: (0 to 2) A,
1A Nominal Secondary
Programmable Current to
Any CT Ratio
•
Burden 0.005VA per phase
Pass through wire gauge
dimension: 0.177” / 4.5mm
Option D2:
• (90 to 265) Volts AC and
(100 to 370) Volts DC.
Universal AC/DC Supply
Option: D:
• 24-48VDC +/- 10%
Environmental Rating
Communication Format
Storage: (-40 to +85)° C
Operating: (-30 to +70)° C
Humidity: to 95% RH NonCondensing
Faceplate Rating:
NEMA12
(Water Resistant)
Mounting Gasket Included
• 2 Com Ports (Back and
Face Plate)
•
•
350VDC: 1 mA
Opto-Islolation: 3750V
(60Hz, 1min)
Dimensions and Shipping
•
Weight: 2 lbs
•
Basic Unit: H4.85 x W4.82 x
L4.25
• Shark100 - mounts in 92mm
DIN and ANSI C39.1 Round
Cut-outs
Burden: 10VA max.
• Shark100T-DIN rail mounted
transducer
•
RS485 Port (Through
Back Plate)
Shipping Container Dimensions:
6” cube
Meter Accuracy
• IrDA (Through Faceplate)
• See page 3
•
Com Port Baud Rate: (9600
to 57,600)
Compliance:
•
Com Port Address: 0-247
• IEC 687 (0.2% Accuracy)
Sensing Method
• 8 Bit, No parity
• ANSI C12.20 (0.2% Accuracy)
• True RMS
• Modbus RTU, ASCII or
DNP 3.0 Protocols
• ANSI (IEEE) C37.90.1 Surge
Withstand
KYZ Pulse
•
ANSI C62.41 (Burst)
• Type Form A
• On Resistance: 23-35 Ω
• Peak Voltage: 350 VDC
• Continuous Load Current:
120 mA
• Peak Load Current: 350mA
(10ms)
• Off Stat Leakage Current @
•
IEC1000-4-2 – ESD
• Sampling at 400+ Samples
per Cycle on all channels
measured readings
simultaneously
• Fault Current Withstand: 100
Amps for 10 Seconds, 300
Amps for 3 Seconds, 500
Amps for 1 Second.
•
Power Supply
•
All Inputs and Outputs are
galvanically isolated to 2500
Volts AC.
Programmable Voltage
Range to Any PT ratio
All other parameters-1second
5mA Pickup Current
Isolation
• Supports: 3 Element WYE,
2.5 Element WYE, 2 Element
Delta, 4 Wire Delta Systems
•
•
•
•
Harmonic %THD (% of Total
Harmonic Distortion)
Update Rate
• Watts, VAr and VA-100msec
• IEC1000-4-3 – Radiated
Immunity
•
IEC 1000-4-4 – Fast Transient
•
IEC 1000-4-5 – Surge Immunity
Ordering Information
To order, please fill out ordering guide:
Model
Option
Numbers:
Example: Shark100
Frequency
-
Shark100
(Meter/Transducer)
Shark100T
(Transducer Only)
-60
Current Class
-
-10
V-Switch Pack
-
-V2
-50
50 Hz
System
-10
5 Amp
Secondary
-V1
Default V-Switch
Volts / Amps
-60
60 Hz
System
-2
1 Amp
Secondary
-V2
Above with
Power and Freq
-V3
Above with
Energy Counters
COM
Power Supply
-
-D2
Mounting
(Shark100 Only)
-
-D2
90-265V
AC/DC
-D
24-48V
DC
-X
(Shark100 Only)
-
-X
-X
No Com
-X
ANSI Mounting
-485P
RS485+Pulse
-DIN
DIN Mounting
Brackets
(Standard in
Shark 100T)
-V4
Above with
Harmonics and Limits
Additional Accessories
Communication Converters
Current Transformer Kits
9PINC – RS232 Cable
CT200K – 200/5 Ratio .94” Window 3 CTs
CT400K – 400/5 Ratio, 1.25” Window, 3 CTs
CT800K – 800/5 Ratio, 2.06” Window, 3 CTs
CT2000K – 2000/5 Ratio, 3.00” Window, 3 CTs
CAB6490 - USB to IrDA Adapter
Unicom 2500 - RS485 to RS232 Converter
Unicom 2500-F – RS485 to RS232 to Fiber Optic Converter
Modem Manager, Model #, MM1 – RS485 to RS232 Converter
for Modem Communication
IrDA232 - IrDA to RS232 Adapter for Remote Read
CT Specifications:
Frequency: 50 to 400Hz; Insulation: 600 Volts, 10kV BIL
Flexible Leads: UL 1015 105°C, CSA Approved, 24” Long, #16AWG
Compliance Documents
Software
Certificate of Calibration, Part #: CCal – This provides
Certificate of Calibration with NIST traceable Test Data.
COMEXT3 – CommunicatorEXT 3.0 for Windows ®
Option Numbers
* Consult factory application engineer for additional transformer
ratios, types or window sizes.
Electro Industries/ GaugeTech
1800 Shames Drive • Westbury, NY 11590
1- 877- EIMETER (1- 877- 346-3837) • E-Mail: sales@electroind.com
Tel: 516-334-0870 • Web Site: www.electroind.com • Fax: 516-338-4741
E145702 081105 D