FG-1625 T | Honeywell FG-1625, T Glassbreak Detector Installation Instructions 2 Pages Pagine ページ
The FlexGuard® FG-1625/FG-1625T Glassbreak Detector is a device that senses the sound of breaking glass. It is compatible with a variety of glass types, including plate, tempered, laminated, wired, coated, and sealed insulating glass. The detector can be mounted on a wall or ceiling, and can be wired for a variety of alarm systems. The detector has DIP switches that allow you to configure the sensitivity (range), LED behavior, and tamper switch status. The detector can be tested with a 9V battery or with a FG-701 Glassbreak Simulator.
advertisement annuncio pubblicitario 広告
Ask Al about FG-1625 T | Honeywell FG-1625
Chatbot has read manual and is ready to answer your questions.
FlexGuard
®
FG-1625/FG-1625T Glassbreak Detector Installation Instructions
Refer to Supplemental Information (next page) for complete descriptions of these installation steps
FG-1625/FG-1625T Glassbreak Detector
Mounting Hole
Microphone
Terminal Block
Tamper Switch
Rear Tamper
(FG-1625T only)
Wire Entry Hole
Terminal Block
(FG-1625T only)
Enable Wall Tamper (FG-1625T only)
• Remove plastic tab from rear of detector.
• Install wall tamper screw as shown.
•
Set screw depth to make contact w/ bottom of tamper cavity when device is installed
Mount Detector
• Place unit over wall tamper screw, if used!
• Use mounting holes as template to mark ceiling or wall.
• Mount detector using appropriate hardware.
Test Mode Pads Wire Channel
Breakout Tabs
Mounting Hole
Front Cover LED Indicators
Cover Screw Location
1625_001-V1
Select Mounting Location
9.7mm [.38”]
Max. screw head size
4.2mm or 4.8mm
[#8 or #10]
3.5mm* or 4.2mm
(#6* or #8)
Wall Mount
(Top View)
Wire Channel
Breakout Tabs
Connect Detector
Connect detector using 18 to 22 AWG wire, with ends stripped approximately 6mm (1/4 in.) Use the appropriate wiring method as shown in these diagrams:
* 3.5mm (#6) screws work best with the screw retention feature.
Ceiling Mount: (Side View)
1625_ceiling_mnt-001-V0
Test Location w/ 9V Battery
V+
V
9V
9V_001-V0
Set Sensitivity & LED Configuration
V+
V-
NC
FG-1625T Only
EOL
C
NO
TMPR
EOL
TMPR
FG-1625T Only
1625Wiring_001-V0
Normally Closed Loop/No EOL Resistor
V+
V-
NC
FG-1625T Only
EOL
C
NO
TMPR
EOL
TMPR
FG-1625T Only
1625Wiring_002-V0
Normally Open Loop/No EOL Resistor
SENS1
SENS2
LATCH
LED
SENS1 & SENS2 configure sensitivity
SENSITIVITY APPROXIMATE SENS1 SENS2
RANGE
MAX
MEDIUM
7.6m (25 ft)
4.6m (15 ft)
OFF OFF
ON OFF
LOW
LOWEST
3m (10 ft)
1.5m (5 ft)
OFF ON
ON ON
NOTE: Ranges are approximate and vary with each room’s acoustic properties. Always verify range with a FG-701
Glassbreak Simulator.
The LATCH and LED DIP switches configure LED indicator behavior.
SWITCH OFF
LATCH Red LED lights for 5 seconds during alarm
ON
Red LED latches ON when
1, 2 detector goes into alarm
LED LEDs disabled (except for power up and test mode
3
)
LEDs always enabled
1
The timing of the alarm relay is not affected by the latched Alarm LED.
2 Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode.
3 LEDs can be enabled/disabled using FG-701.
V+
V-
NC
FG-1625T Only
EOL
C
NO
TMPR
EOL
TMPR
FG-1625T Only
1625Wiring_003-V0
Normally Closed Loop/With EOL Resistor
V+
V-
NC
FG-1625T Only
EOL
C
NO
TMPR
EOL
TMPR
FG-1625T Only
1625Wiring_004-V0
Normally Open Loop/With EOL Resistor
* The screw retention feature simplifies installation. A rib in the screw cavity lightly holds the screw in place when installing the detector
Test Detector Installation
Enter Test Mode using FG-701 (see Testing the
Detector on the next page) or manually by shorting the
Test Mode pads (as below).
1625_008-V1
TEST
Install Cover Screw (optional)
2.9 mm (#4) screw,
6 mm (1/4-in.) long
5-051-736-00 Rev C Page 1
FlexGuard
®
FG-1625/FG-1625T Glassbreak Detector Supplemental Information
Refer to Installation Instructions and diagrams (next page) when installing this product
1. General Information 8. Wiring the Detector
The FG-1625/FG-1625T glassbreak detector senses the sound of breaking plate, tempered, laminated, wired, coated and sealed insulating glass.
These products are both UL and ULC listed.
Refer to the wiring diagrams (page 1) to select the appropriate wiring configuration.
NOTE: This sensor must be connected to a UL Listed power supply or UL Listed control unit capable of supplying a minimum of four hours of standby power.
2. Choosing Mounting Location
*
The preferred mounting location for the device is on a wall or ceiling, opposite the protected glass.
For the best detector performance, select a mounting location that is:
• within 7.6 m (25 feet) of the protected glass;
• within clear view of the protected glass;
•
at least 2 m (6.5 feet) from the floor;
• at least 1 m (3.3 feet) from forced air ducts;
• at least 1 m (3.3 feet) from sirens or bells greater than 5 cm (2 inches) in diameter.
• between the protected glass and any heavy window coverings that may be present.
Alternatively, when heavy window coverings are present, the detector can be mounted on the frame of the window.
Avoid mounting the detector on the same wall as the protected glass, on free-standing posts or pillars, or in rooms with noisy equipment (air compressors, bells, power tools, etc.), if this equipment is operated when the detector is armed.
3. Testing Mounting Location With 9V Battery
4. Configuring Sensitivity (Range)
Sensitivity must be set to match the distance between the detector and the protected glass, as verified using the FG-701 Glassbreak Simulator.
5. Configuring LED Switch
9. Testing the Detector
The detector should be tested at least once each year.
Test the detector with the FG-701 Glassbreak Simulator.
The model FG-700 Glassbreak Simulator can also be used if it is set for the TEMPered glass sound. Other simulators will not give accurate indication of range.
To enter Test Mode manually:
1. Open the front cover.
2. Use a screwdriver to short the Test Mode pads on the PC board (see diagram on next page).
3. Close the front cover.
The detector’s green LED blinks approximately once per second to indicate that it has entered Test Mode.
To enter the Test Mode with the FG-701:
You may test the detector in the desired mounting location before drilling/wiring. If the 9V battery cannot supply sufficient power, the detector will not operate and the red and green LEDs will flash on/off.
Follow the procedure described in “Testing the
Detector” (next column) to confirm proper operation.
1. Stand within 4.6 m (15 feet) of the detector.
2. Switch the FG-701 to ACTIVATE and MANual modes.
3. Point the front [speaker] of the glassbreak simulator towards the detector. Press the red
START button to send a short activation code.
When the detector enters Test Mode, the green LED on the detector flashes about once per second. If the green LED does not flash, move closer to the detector and repeat the procedure.
Testing the Detector (flex and audio signals):
To test the FG-1625/FG-1625T, do the following:
DIP switches SENS1 and SENS2 set detector sensitivity (range), as shown:
MAX
MEDIUM
LOW
LOWEST
7.6m (25 ft)
4.6m (15 ft)
3m (10 ft)
1.5m (5 ft)
OFF OFF
1. Place the detector in Test Mode.
2. Set the FG-701 switches to the TEST and FLEX positions.
3. Position the FG-701 near the farthest point of the protected glass, and point the speaker directly at the detector. If window coverings are present, close them fully and hold the FG-701 between the coverings and the protected glass.
ON OFF
OFF ON
ON ON
4. Press the red START button. The simulator clicks on and starts an 8-second armed period.
5. Generate a flex signal by carefully striking the glass with a cushioned tool. The FG-701 responds with a burst of glassbreak audio.
If the detector receives both the flex and audio signals properly, its red Alarm LED lights. (Red Alarm LED does not latch in Test Mode).
The LATCH and LED DIP switches determine LED indicator operation.
Testing the Detector (audio signals only):
SWITCH OFF
LATCH Red LED lights for 5 seconds during alarm
ON
Red LED latches ON when
1, 2 detector goes into alarm
LED LEDs disabled (except for power up and test mode
3
)
LEDs always enabled
1
Alarm relay timing is not affected by the latched Alarm LED.
2
Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode.
3 LEDs can be enabled/disabled using FG-701.
The FG-701 can also be used to test the detector’s ability to receive audio signals only. See the FG-701
Operating Instructions for additional information. When it receives the audio signal, the detector flickers its green Event LED.
Exiting Test Mode:
When you have finished testing, exit Test Mode by following the same procedure used to enter Test Mode.
6. Enabling Optional Rear Tamper
(FG-1625T only)
The FG-1625T is equipped with a combination normallyclosed (NC) cover and wall tamper switches. Each unit is shipped with the cover tamper operational, and the wall tamper disabled.
To enable the rear tamper, remove the plastic tab on the back of the detector, using needle-nose pliers. The wall tamper arm will then extend through the hole. Proceed with the following mounting instructions to install the wall tamper screw.
7. Mounting the Detector
NOTE: If ceiling mounted, the end with the hole
(micro-phone end) should face the glass being protected.
The FG-1625/T will automatically exit Test Mode five minutes after the last event is detected.
10. LED Indicators
The detector is equipped with two LEDs: a green Event
LED and a red Alarm LED. When the LEDs are enabled, they light in a variety of patterns to convey the detector’s operational status. The following table summarizes the LED messages.
Normal, event detected
Normal, break detected
Normal, alarm latched
Flicker
OFF
OFF
OFF
ON 5 seconds
ON
Power up ON 1 second ON 1 second
1. If using optional Wall Tamper (FG-1625T):
Mark the mounting location for the wall tamper screw based on the final location of the detector. Then, install the wall tamper screw so that it will just make contact with the bottom of the tamper cavity when the unit is mounted.
Use a flat head 4.2mm or 4.8mm screw (#8 or
#10).
2. Position the unit over the wall tamper screw (if used), then mark the mounting screw and wire openings. If required by the location, install wall
anchors for the mounting screws.
3. Secure the unit to the wall or ceiling, oriented so the microphone has the best line of sight to the protected glass.
Low Voltage
Test Mode
Test Mode, event detected
Test Mode, alarm
Flash ON/OFF
Flash once per sec
Flicker
Flash once per sec
Flash ON/OFF
OFF
OFF
ON 5 seconds
11. Cover Screw
The front cover can be secured after installation. To do so, remove the cover breakout flash and secure the front cover with a 2.9 mm x 6.0 mm (#4 x ¼ in.) screw.
12. Remote LED Enable/Disable Mode
The detector’s Remote LED Enable/Disable Mode allows you to enable or disable the detector’s LEDs with the
FG-701 Glassbreak Simulator.
To enable or disable the LEDs with the FG-701
Activation Code:
1. Set LED switch, S4 position 4, to off.
2. Enter Test Mode, and then exit Test Mode.
3. Within two (2) seconds, enter Test Mode again; this changes LED enable/disable status.
4. Clap your hands to test the LEDs. If enabled, the green LED will flicker. If disabled, the green LED will remain off.
13. Nominal Glass Thickness Chart
Glass Type*
Plate 3a
Tempered
Laminated 1
Nominal Thickness
Minimum Maximum
2mm (3/32 in.)
3mm (1/8 in.)
3mm (1/8 in.)
10mm (3/8 in.)
10mm (3/8 in.)
14mm (9/16 in.)
Wired
Coated
2,3b
6mm (1/4 in.)
3mm (1/8 in.)
6mm (1/4 in.)
6mm (1/4 in.)
Sealed
Insulating 1,3b, 4
3mm (1/8 in.)
[13mm (1/2 in.) overall]
6mm (1/4 in.)
[19mm (3/4 in.) overall]
* Minimum size for all types is 28cm (11 in.) square; glass must be framed in the wall or mounted in a barrier at least 0.9m (36 in.) wide.
1 Protected only if both plates in the unit are broken
2 Coated glass with security films up to 0.3mm (12 mils) thick (including films for solar protection) may be used. Film Technologies
International, Inc.’s GLASS-GARD GGLL 1200 has been evaluated with this product by Underwriters Laboratories, Inc. at Honeywell’s request
3 In compliance with Underwriters Laboratories of Canada’s Standard for Intrusion Detection Units (CAN/ULC-S306-M89): a.
Plate glass 3mm (1/8 in.) to 10mm (3/8 in.) can be protected. b.
ULC recognizes a maximum range for protecting sealed insulating glass and coated glass of 3.8 m (12.5 ft).
4
UL recognizes a maximum range for protecting sealed insulating glass of 6.1m (20 ft.) with sensitivity set at maximum.
14. Specifications
Range:
7.6 m (25 ft.) maximum, omni directional
No minimum range
Operating Temperature:
-10° C to 55° C (14° F to 131° F)
UL: -10° C to 50° C (14° F to 122° F)
(Indoor use environment)
Storage:
-20° C to 55° C (-4° F to 131° F)
UL: -20° C to 50° C (-4° F to 122° F)
Alarm Duration:
5 seconds (unaffected by alarm
LED latching)
Alarm Relay:
FG-1625 Form A
FG-1625T Form C
100 mA maximum
25 VDC maximum
ON/closed 22
Ω
±6
Ω
OFF/open >1M
Ω
Tamper Switch:
FG-1625T Only
Combination cover/ wall tamper
25 mA maximum
24 VDC maximum
RFI Immunity:
30 V/m,
10 MHz - 1000 MHz
ESD Immunity:
10 kV discharges of either polarity to exposed surfaces
Power Requirements:
6 - 18 VDC; 12 mA typical at
12 VDC, 22 mA max, (Latched LED)
AC Ripple: 4 Volts peak-topeak at Nominal 12 VDC
Dimensions:
115 mm x 72 mm x 27 mm
(4.5 in. H x 2.8 in. W x 1.05 in. D)
Weight:
98 g (3.5 oz.)
Packaged Product: 126g (4.5 oz.)
Approvals / Listings:
FCC and IC verified,
CE, C-Tick, UL Listed, ULC
Listed
Suitable for connection to an
EN60950 Class II Limited
Power Source.
Customers in
European Union countries are advised to dispose of this product, at the end of its useful life, as per applicable local laws, regulations and procedures.
FG-1625T Only:
EN 50131-1; Security Grade
2, Environmental Class II
To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our Website http://www.security.honeywell.com/hsce/international/index.html.
For any additional information regarding the compliance of this product to any EU specific requirements, please contact –
Quality Assurance Department,
Honeywell Security & Custom Electronics,
Newhouse Industrial Estate,
Motherwell,
Lanarkshire ML1 5SB,
Scotland,
United Kingdom
Tel: +44(0)1698 738200
Email: [email protected]
NOTICES
FCC NOTICE: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
The user is cautioned that changes or modifications not expressly approved by Honeywell could void the user’s authority to operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. The installer can also consult an experienced radio/television technician for additional suggestions, if necessary.
IC Notice: This Class B digital apparatus complies with the Canadian ICES-003.
Cet appareil numérique de la Classe B est conforme à la norme NMB-003 du Canada
©2002 Honeywell International Inc. All rights reserved.
Honeywell, FlexGuard and IntelliSense are registered trademarks of Honeywell International
Inc. - All other brands mentioned are the trademarks or registered trademarks of their respective owners. Specifications subject to change without prior notice.
5-051-736-00 Rev C
advertisement
Key Features
- Senses breaking glass
- Mountable on walls or ceilings
- Adjustable sensitivity
- LED indicators for status
- Compatible with a variety of alarm systems
- UL and ULC Listed
- Optional rear tamper switch