FG-1625 T | Honeywell FG-1625, T Glassbreak Detector Installation Instructions 2 Pages

The FlexGuard® FG-1625/FG-1625T Glassbreak Detector is a device that senses the sound of breaking glass. It is compatible with a variety of glass types, including plate, tempered, laminated, wired, coated, and sealed insulating glass. The detector can be mounted on a wall or ceiling, and can be wired for a variety of alarm systems. The detector has DIP switches that allow you to configure the sensitivity (range), LED behavior, and tamper switch status. The detector can be tested with a 9V battery or with a FG-701 Glassbreak Simulator.

advertisement

Ask Al about FG-1625 T | Honeywell FG-1625

Chatbot has read manual and is ready to answer your questions.

Honeywell FG-1625/FG-1625T Glassbreak Detector Installation Instructions | Manualzz

FlexGuard

®

FG-1625/FG-1625T Glassbreak Detector Installation Instructions

Refer to Supplemental Information (next page) for complete descriptions of these installation steps

FG-1625/FG-1625T Glassbreak Detector

Mounting Hole

Microphone

Terminal Block

Tamper Switch

Rear Tamper

(FG-1625T only)

Wire Entry Hole

Terminal Block

(FG-1625T only)

Enable Wall Tamper (FG-1625T only)

• Remove plastic tab from rear of detector.

• Install wall tamper screw as shown.

Set screw depth to make contact w/ bottom of tamper cavity when device is installed

Mount Detector

• Place unit over wall tamper screw, if used!

• Use mounting holes as template to mark ceiling or wall.

• Mount detector using appropriate hardware.

Test Mode Pads Wire Channel

Breakout Tabs

Mounting Hole

Front Cover LED Indicators

Cover Screw Location

1625_001-V1

Select Mounting Location

9.7mm [.38”]

Max. screw head size

4.2mm or 4.8mm

[#8 or #10]

3.5mm* or 4.2mm

(#6* or #8)

Wall Mount

(Top View)

Wire Channel

Breakout Tabs

Connect Detector

Connect detector using 18 to 22 AWG wire, with ends stripped approximately 6mm (1/4 in.) Use the appropriate wiring method as shown in these diagrams:

* 3.5mm (#6) screws work best with the screw retention feature.

Ceiling Mount: (Side View)

1625_ceiling_mnt-001-V0

Test Location w/ 9V Battery

V+

V

9V

9V_001-V0

Set Sensitivity & LED Configuration

V+

V-

NC

FG-1625T Only

EOL

C

NO

TMPR

EOL

TMPR

FG-1625T Only

1625Wiring_001-V0

Normally Closed Loop/No EOL Resistor

V+

V-

NC

FG-1625T Only

EOL

C

NO

TMPR

EOL

TMPR

FG-1625T Only

1625Wiring_002-V0

Normally Open Loop/No EOL Resistor

SENS1

SENS2

LATCH

LED

SENS1 & SENS2 configure sensitivity

SENSITIVITY APPROXIMATE SENS1 SENS2

RANGE

MAX

MEDIUM

7.6m (25 ft)

4.6m (15 ft)

OFF OFF

ON OFF

LOW

LOWEST

3m (10 ft)

1.5m (5 ft)

OFF ON

ON ON

NOTE: Ranges are approximate and vary with each room’s acoustic properties. Always verify range with a FG-701

Glassbreak Simulator.

The LATCH and LED DIP switches configure LED indicator behavior.

SWITCH OFF

LATCH Red LED lights for 5 seconds during alarm

ON

Red LED latches ON when

1, 2 detector goes into alarm

LED LEDs disabled (except for power up and test mode

3

)

LEDs always enabled

1

The timing of the alarm relay is not affected by the latched Alarm LED.

2 Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode.

3 LEDs can be enabled/disabled using FG-701.

V+

V-

NC

FG-1625T Only

EOL

C

NO

TMPR

EOL

TMPR

FG-1625T Only

1625Wiring_003-V0

Normally Closed Loop/With EOL Resistor

V+

V-

NC

FG-1625T Only

EOL

C

NO

TMPR

EOL

TMPR

FG-1625T Only

1625Wiring_004-V0

Normally Open Loop/With EOL Resistor

* The screw retention feature simplifies installation. A rib in the screw cavity lightly holds the screw in place when installing the detector

Test Detector Installation

Enter Test Mode using FG-701 (see Testing the

Detector on the next page) or manually by shorting the

Test Mode pads (as below).

1625_008-V1

TEST

Install Cover Screw (optional)

2.9 mm (#4) screw,

6 mm (1/4-in.) long

5-051-736-00 Rev C Page 1

FlexGuard

®

FG-1625/FG-1625T Glassbreak Detector Supplemental Information

Refer to Installation Instructions and diagrams (next page) when installing this product

1. General Information 8. Wiring the Detector

The FG-1625/FG-1625T glassbreak detector senses the sound of breaking plate, tempered, laminated, wired, coated and sealed insulating glass.

These products are both UL and ULC listed.

Refer to the wiring diagrams (page 1) to select the appropriate wiring configuration.

NOTE: This sensor must be connected to a UL Listed power supply or UL Listed control unit capable of supplying a minimum of four hours of standby power.

2. Choosing Mounting Location

*

The preferred mounting location for the device is on a wall or ceiling, opposite the protected glass.

For the best detector performance, select a mounting location that is:

• within 7.6 m (25 feet) of the protected glass;

• within clear view of the protected glass;

at least 2 m (6.5 feet) from the floor;

• at least 1 m (3.3 feet) from forced air ducts;

• at least 1 m (3.3 feet) from sirens or bells greater than 5 cm (2 inches) in diameter.

• between the protected glass and any heavy window coverings that may be present.

Alternatively, when heavy window coverings are present, the detector can be mounted on the frame of the window.

Avoid mounting the detector on the same wall as the protected glass, on free-standing posts or pillars, or in rooms with noisy equipment (air compressors, bells, power tools, etc.), if this equipment is operated when the detector is armed.

3. Testing Mounting Location With 9V Battery

4. Configuring Sensitivity (Range)

Sensitivity must be set to match the distance between the detector and the protected glass, as verified using the FG-701 Glassbreak Simulator.

5. Configuring LED Switch

9. Testing the Detector

The detector should be tested at least once each year.

Test the detector with the FG-701 Glassbreak Simulator.

The model FG-700 Glassbreak Simulator can also be used if it is set for the TEMPered glass sound. Other simulators will not give accurate indication of range.

To enter Test Mode manually:

1. Open the front cover.

2. Use a screwdriver to short the Test Mode pads on the PC board (see diagram on next page).

3. Close the front cover.

The detector’s green LED blinks approximately once per second to indicate that it has entered Test Mode.

To enter the Test Mode with the FG-701:

You may test the detector in the desired mounting location before drilling/wiring. If the 9V battery cannot supply sufficient power, the detector will not operate and the red and green LEDs will flash on/off.

Follow the procedure described in “Testing the

Detector” (next column) to confirm proper operation.

1. Stand within 4.6 m (15 feet) of the detector.

2. Switch the FG-701 to ACTIVATE and MANual modes.

3. Point the front [speaker] of the glassbreak simulator towards the detector. Press the red

START button to send a short activation code.

When the detector enters Test Mode, the green LED on the detector flashes about once per second. If the green LED does not flash, move closer to the detector and repeat the procedure.

Testing the Detector (flex and audio signals):

To test the FG-1625/FG-1625T, do the following:

DIP switches SENS1 and SENS2 set detector sensitivity (range), as shown:

MAX

MEDIUM

LOW

LOWEST

7.6m (25 ft)

4.6m (15 ft)

3m (10 ft)

1.5m (5 ft)

OFF OFF

1. Place the detector in Test Mode.

2. Set the FG-701 switches to the TEST and FLEX positions.

3. Position the FG-701 near the farthest point of the protected glass, and point the speaker directly at the detector. If window coverings are present, close them fully and hold the FG-701 between the coverings and the protected glass.

ON OFF

OFF ON

ON ON

4. Press the red START button. The simulator clicks on and starts an 8-second armed period.

5. Generate a flex signal by carefully striking the glass with a cushioned tool. The FG-701 responds with a burst of glassbreak audio.

If the detector receives both the flex and audio signals properly, its red Alarm LED lights. (Red Alarm LED does not latch in Test Mode).

The LATCH and LED DIP switches determine LED indicator operation.

Testing the Detector (audio signals only):

SWITCH OFF

LATCH Red LED lights for 5 seconds during alarm

ON

Red LED latches ON when

1, 2 detector goes into alarm

LED LEDs disabled (except for power up and test mode

3

)

LEDs always enabled

1

Alarm relay timing is not affected by the latched Alarm LED.

2

Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode.

3 LEDs can be enabled/disabled using FG-701.

The FG-701 can also be used to test the detector’s ability to receive audio signals only. See the FG-701

Operating Instructions for additional information. When it receives the audio signal, the detector flickers its green Event LED.

Exiting Test Mode:

When you have finished testing, exit Test Mode by following the same procedure used to enter Test Mode.

6. Enabling Optional Rear Tamper

(FG-1625T only)

The FG-1625T is equipped with a combination normallyclosed (NC) cover and wall tamper switches. Each unit is shipped with the cover tamper operational, and the wall tamper disabled.

To enable the rear tamper, remove the plastic tab on the back of the detector, using needle-nose pliers. The wall tamper arm will then extend through the hole. Proceed with the following mounting instructions to install the wall tamper screw.

7. Mounting the Detector

NOTE: If ceiling mounted, the end with the hole

(micro-phone end) should face the glass being protected.

The FG-1625/T will automatically exit Test Mode five minutes after the last event is detected.

10. LED Indicators

The detector is equipped with two LEDs: a green Event

LED and a red Alarm LED. When the LEDs are enabled, they light in a variety of patterns to convey the detector’s operational status. The following table summarizes the LED messages.

Normal, event detected

Normal, break detected

Normal, alarm latched

Flicker

OFF

OFF

OFF

ON 5 seconds

ON

Power up ON 1 second ON 1 second

1. If using optional Wall Tamper (FG-1625T):

Mark the mounting location for the wall tamper screw based on the final location of the detector. Then, install the wall tamper screw so that it will just make contact with the bottom of the tamper cavity when the unit is mounted.

Use a flat head 4.2mm or 4.8mm screw (#8 or

#10).

2. Position the unit over the wall tamper screw (if used), then mark the mounting screw and wire openings. If required by the location, install wall

anchors for the mounting screws.

3. Secure the unit to the wall or ceiling, oriented so the microphone has the best line of sight to the protected glass.

Low Voltage

Test Mode

Test Mode, event detected

Test Mode, alarm

Flash ON/OFF

Flash once per sec

Flicker

Flash once per sec

Flash ON/OFF

OFF

OFF

ON 5 seconds

11. Cover Screw

The front cover can be secured after installation. To do so, remove the cover breakout flash and secure the front cover with a 2.9 mm x 6.0 mm (#4 x ¼ in.) screw.

12. Remote LED Enable/Disable Mode

The detector’s Remote LED Enable/Disable Mode allows you to enable or disable the detector’s LEDs with the

FG-701 Glassbreak Simulator.

To enable or disable the LEDs with the FG-701

Activation Code:

1. Set LED switch, S4 position 4, to off.

2. Enter Test Mode, and then exit Test Mode.

3. Within two (2) seconds, enter Test Mode again; this changes LED enable/disable status.

4. Clap your hands to test the LEDs. If enabled, the green LED will flicker. If disabled, the green LED will remain off.

13. Nominal Glass Thickness Chart

Glass Type*

Plate 3a

Tempered

Laminated 1

Nominal Thickness

Minimum Maximum

2mm (3/32 in.)

3mm (1/8 in.)

3mm (1/8 in.)

10mm (3/8 in.)

10mm (3/8 in.)

14mm (9/16 in.)

Wired

Coated

2,3b

6mm (1/4 in.)

3mm (1/8 in.)

6mm (1/4 in.)

6mm (1/4 in.)

Sealed

Insulating 1,3b, 4

3mm (1/8 in.)

[13mm (1/2 in.) overall]

6mm (1/4 in.)

[19mm (3/4 in.) overall]

* Minimum size for all types is 28cm (11 in.) square; glass must be framed in the wall or mounted in a barrier at least 0.9m (36 in.) wide.

1 Protected only if both plates in the unit are broken

2 Coated glass with security films up to 0.3mm (12 mils) thick (including films for solar protection) may be used. Film Technologies

International, Inc.’s GLASS-GARD GGLL 1200 has been evaluated with this product by Underwriters Laboratories, Inc. at Honeywell’s request

3 In compliance with Underwriters Laboratories of Canada’s Standard for Intrusion Detection Units (CAN/ULC-S306-M89): a.

Plate glass 3mm (1/8 in.) to 10mm (3/8 in.) can be protected. b.

ULC recognizes a maximum range for protecting sealed insulating glass and coated glass of 3.8 m (12.5 ft).

4

UL recognizes a maximum range for protecting sealed insulating glass of 6.1m (20 ft.) with sensitivity set at maximum.

14. Specifications

Range:

7.6 m (25 ft.) maximum, omni directional

No minimum range

Operating Temperature:

-10° C to 55° C (14° F to 131° F)

UL: -10° C to 50° C (14° F to 122° F)

(Indoor use environment)

Storage:

-20° C to 55° C (-4° F to 131° F)

UL: -20° C to 50° C (-4° F to 122° F)

Alarm Duration:

5 seconds (unaffected by alarm

LED latching)

Alarm Relay:

FG-1625 Form A

FG-1625T Form C

100 mA maximum

25 VDC maximum

ON/closed 22

±6

OFF/open >1M

Tamper Switch:

FG-1625T Only

Combination cover/ wall tamper

25 mA maximum

24 VDC maximum

RFI Immunity:

30 V/m,

10 MHz - 1000 MHz

ESD Immunity:

10 kV discharges of either polarity to exposed surfaces

Power Requirements:

6 - 18 VDC; 12 mA typical at

12 VDC, 22 mA max, (Latched LED)

AC Ripple: 4 Volts peak-topeak at Nominal 12 VDC

Dimensions:

115 mm x 72 mm x 27 mm

(4.5 in. H x 2.8 in. W x 1.05 in. D)

Weight:

98 g (3.5 oz.)

Packaged Product: 126g (4.5 oz.)

Approvals / Listings:

FCC and IC verified,

CE, C-Tick, UL Listed, ULC

Listed

Suitable for connection to an

EN60950 Class II Limited

Power Source.

Customers in

European Union countries are advised to dispose of this product, at the end of its useful life, as per applicable local laws, regulations and procedures.

FG-1625T Only:

EN 50131-1; Security Grade

2, Environmental Class II

To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our Website http://www.security.honeywell.com/hsce/international/index.html.

For any additional information regarding the compliance of this product to any EU specific requirements, please contact –

Quality Assurance Department,

Honeywell Security & Custom Electronics,

Newhouse Industrial Estate,

Motherwell,

Lanarkshire ML1 5SB,

Scotland,

United Kingdom

Tel: +44(0)1698 738200

Email: [email protected]

NOTICES

FCC NOTICE: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

The user is cautioned that changes or modifications not expressly approved by Honeywell could void the user’s authority to operate this equipment.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. The installer can also consult an experienced radio/television technician for additional suggestions, if necessary.

IC Notice: This Class B digital apparatus complies with the Canadian ICES-003.

Cet appareil numérique de la Classe B est conforme à la norme NMB-003 du Canada

©2002 Honeywell International Inc. All rights reserved.

Honeywell, FlexGuard and IntelliSense are registered trademarks of Honeywell International

Inc. - All other brands mentioned are the trademarks or registered trademarks of their respective owners. Specifications subject to change without prior notice.

5-051-736-00 Rev C

advertisement

Key Features

  • Senses breaking glass
  • Mountable on walls or ceilings
  • Adjustable sensitivity
  • LED indicators for status
  • Compatible with a variety of alarm systems
  • UL and ULC Listed
  • Optional rear tamper switch

Frequently Answers and Questions

What is the maximum range of the FlexGuard® FG-1625/FG-1625T Glassbreak Detector?
The maximum range is 7.6 meters (25 feet).
What types of glass can the FlexGuard® FG-1625/FG-1625T Glassbreak Detector sense?
The detector can sense plate, tempered, laminated, wired, coated, and sealed insulating glass.
How do I configure the sensitivity of the FlexGuard® FG-1625/FG-1625T Glassbreak Detector?
The sensitivity can be configured using the SENS1 and SENS2 DIP switches.
How do I test the FlexGuard® FG-1625/FG-1625T Glassbreak Detector?
The detector can be tested with a 9V battery or with a FG-701 Glassbreak Simulator.

Related manuals

Download PDF

advertisement