Aerco | BENCHMARK 6000 | AERCO Benchmark (BMK) Gas Fired Hot Water

MODEL BMK-2.0 GWB
TECHNICAL DATA
AERCO Benchmark (BMK) Gas Fired Hot Water Boiler System
The AERCO Benchmark Water Boiler is a true industry advance that meets the needs
of today’s energy and environmental concerns. Designed for application in any closed
loop hydronic system, it relates energy input directly to fluctuating system load, yielding
seasonal efficiencies as high as 95%. Its efficiency actually increases as the load
decreases due to its unique inverse efficiency curve. The boiler can be used singly or
in modular arrangements for inherent standby with minimum space requirements.
Venting flexibility permits installation without normal restrictions.
The advanced electronics of each boiler module offer selectable modes of operation for
temperature control. (see reverse side)
Regardless of the mode of operation, the load tracking capability of every unit delivers
the ultimate in energy control through energy input modulation with a 15:1 ratio while
meeting all load demands.
BENCHMARK 2.0 BOILER THERMAL EFFICIENCY
100
Thermal Efficiency (%)
98
96
94
92
25% input
50% input
90
100% input
88
86
84
82
80
70
80
90
100
110
120
130
140
150
160
170
180
Return Water Temperature (deg F)
BMK 2.0 FEATURES
•
•
•
•
•
•
Natural Gas
15:1 Turndown Ratio
Direct Vent or Conventional Capabilities
Vent Material Required per UL 1738 (AL29-4C)
ASME 150 PSIG Working Pressure Certified
UL, CUL, FM Approved, ASME Coded
•
•
•
•
•
•
Quiet Operation throughout Firing Range
Internal Low Water Cutoff (Manual Reset)
Compact footprint (H 79”, W28”, D 55”)
Precise Temperature Control +/- 2F
(Optional) Sealed Combustion
UL, CUL, for Alcove Installation on
Combustible Flooring
BMK 2.0 Specifications
BTU Input..................................................2,000,000 BTU/Hr†
Net Output @ full input..............1,720,000-1,840,000 BTU/H*
ASME Working Pressure........................................150 PSIG
Electrical Options.................220/1/60 30 Amp (10 Amp FLA)
208-230/3/60, 480/3/60 20 Amp (6 Amp FLA)
Gas Requirements...............7.5 W.C. Minimum @ Full Load
14” W.C. Maximum
Vent Size.............................................................8” Diameter
Water Connections..........................4” Flanged 150 lb. ANSI
* Output is dependent upon return water temp. and firing rate
Gas Connection..........................................................2” NPT
Minimum Water Flow.................................................25 GPM
Maximum Water Flow..............................................350 GPM
Water Pressure Drop.............................4.4 psig @ 170 GPM
Water Volume........................................................27 Gallons
Control Range.....................................................50F. to 200F
Standard Listings & Approvals..UL, CUL, FM, CSD-1, ASME
Optional Approval.................................(IRI) Factory Installed
Weight, Installed (WET)..........................................1,785 lbs.
†Up to 2,000’ Altitude
R
O
LISTED
C
R
O
LISTED
Dimensions BMK-2.0 Boiler
62"
3/4" ELECTRICAL
CONDUIT CONNECTION
28"
55 1/2”
23"
DOOR SWING
4"-150# FLG'D
HOT WATER OUTLET CONN.
CONNECTION FOR OPTIONAL
8" DIAMETER SEALED
COMBUSTION AIR DUCTWORK
THIS AREA TO
BE ACCESSIBLE
FOR
MAINTENANCE
PRESS. RELIEF VA.
18"
30"
LIFTING LUGS
CONTROL
PANEL
DISPLAY
PRESS./TEMP. GAUGE
LOVE
INDEX
AL
2" NPT GAS
INLET CONN.
CONTROLS CORP.
ENTER
AL
79"
4"-150# FLG'D
COLD WATER
INLET CONN.
1-1/2" NPT
DRAIN CONN.
8" EXHAUST
OUTLET
CONDENSATE DRAIN
4" CONCRETE PAD - SET
UNIT FLUSH AT REAR
Ratings and Dimensions
Modules
Model
(a)
Mbh Input
(b)
MBH Output
(b) (c)
Width
(1)
One (1)
BM/2000
2000mbh
1720mbh-1840mbh
2’3”
Depth
Height
Weight
6’5”
1785#
4’5”
Two (2)
BM/2000-2
4000mbh
3440mbh-3680mbh
6’7”
4’5”
6’5”
3570#
Three (3)
BM/2000-3
6000mbh
5160mbh-5520mbh
11’0”
4’5”
6’5”
5355#
Four (4)
BM/2000-4
8000mbh
6880mbh-7360mbh
15’3”
4’5”
6’5”
7140#
Five (5)
BM/2000-5
10,000mbh
8600mbh-9200mbh
19’7”
4’5”
6’5”
8925#
Six (6)
BM/2000-6
12,000mbh
10,320mbh-11,040mbh
24’0”
4’5”
6’5”
10710#
Seven (7)
BM/2000-7
14,000mbh
12,040mbh-12,880mbh
28’3”
4’5”
6’5”
12495#
Eight (8)
BM/2000-8
16,000mbh
13,760mbh-14,720mbh
32’7”
4’5”
6’5”
14280#
(a) Style to be determined by individual application requirement
(b) Altitude below 2,000’. Apply Altitude Correction Factor above 2,000’.
(c) Output dependent upon application-see efficiency curves.
(1) assumes 24” between units. Zero side wall clearance is not
provided. Consult local sales representative.
Programmable Modes of Operation
Indoor/Outdoor Reset
Constant Temp Setpoint
4-20ma Direct Drive
Supply Water Temp
200F
100%
Firing Rate
Setpoint
0%
4-20 ma Signal
4
20
Load %
200F
EMS
4-20ma Signal
100
Energy Management System
RS-485 Communications
4-20ma Remote Signal
50F
4
50F
0
200F
70F
70F
Outdoor
0F
Temperature
Boiler Management System
BMS
20
Represented by:
Industrial Heater
8400Wolf Lake Dr.
Suite 116
Bartlett, Tennessee 38133
Tel (888) 451-4328
Fax (901) 382-4766