- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Century
- AMP60S1A-CY
- Installation and Operation Manual
- 24 Pages
Century AMP60S1A-CY 60K MULTI-POSITION A/H PSC Installation, Operation & Maintenance Manual
The Century AMP60S1A-CY is a high-efficiency air handler designed for multi-position installation. It can be installed for vertical upflow, downflow, or horizontal air supply. The unit is designed for easy maintenance with a dual front panel and a slide-out blower and coil assembly. It also features a factory-sealed cabinet certified to achieve 2% or less air leakage rate, an integrated filter rack with tool-less door access, and condensate drain pan with UVC inhibitor.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
24
INSTALLER’S GUIDE SE Series UNITS CONDENSING High Efficiency Air Handlers Multi-Position Air Handler 1.5-5TonsAMP**S1A R410a PSC Motor Instruction Manual Thank you very much for purchasing our product. Before using your unit, please read this manual carefully and keep it for future reference. The figure shown in this manual is for reference only and may be slightly different from the actual product. 517.787.2100 • www.marsdelivers.com AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION WARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instruction may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. WARNING Proposition 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer. For more information, go to www.P65Warnings.ca.gov.” Air Handler Features Multi-speed blower motor. TXV easily installed. Multi-position installation - upflow or horizontal right standard; field convertible to horizontal left or downflow. Multiple electrical entry locations. Field-installed electric heater kits 5, 7.5, 10, 15, 20 kW available as an accessory. Dual front panel design for ease of maintenance. Blower and coil easy slide out for ease of maintenance. Fully-insulated cabinet design. Horizontal and vertical condensate drain pans standard. Condensate drain pan is polymer with UVC inhibitor. Primary and secondary condensate drain fittings. Factory-sealed cabinet certified to achieve 2% or less air leakage rate at 1.0 inch water column. Integrated filter rack with tool-less door access. AHRI and ETL listed. Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual CONTENTS 1 SAFETY 01 2 GENERAL 2.1 Unit Dimensions 04 3 APPLICATIONS 3.1 3.2 3.3 3.4 Vertical Upflow Vertical Downflow Horizontal Installation In An Unconditioned Space 05 05 05 07 4 ELECTRICAL WIRING 4.1 4.2 4.3 4.4 4.5 Power Wiring Control Wiring Grounding Electrical Data Heat Kit Data 07 07 07 08 08 5 AIRFLOW PERFORMANCE 09 6 DUCTWORK 10 7 REFRIGERANT CONNECTIONS 7.1 Condensate Drain Tubing 10 8 AIR FILTER (Not Factory-Installed) 11 9 FILTER INSTALLATION DIMENSIONS 12 10 WIRING DIAGRAM 13 11 PISTON/TXV INSTALLATION 16 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor This document is customer property and should remain with this unit. These instructions do not cover all the different variations systems nor does it provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with national, state, and local codes. If additional information is required, please contact your local distributor. WARNING The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. WARNING 1 SAFETY PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to State of California to cause cancer. This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury. All manufacturer products meet current federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards. This is an attention alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury. California’s Proposition 65 requires warnings for products sold in California that contain or produce any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural vapor. WARNING Disconnect all power to unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death. All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market. WARNING If removal of the blower assembly is required, all disconnect switches supplying power to the equipment must be de-energized and shutoff (if not in sight of unit) so the field power wires can be safely removed from the blower assembly. Failure to do so can cause electrical shock resulting in personal injury or death. You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural vapor used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers. WARNING Glass Wool (Fiberglass) Insulation Carbon Monoxide (CO) Formaldehyde Benzene Because of possible damage to equipment or personal injury, installation, service, and maintenance should be performed by a trained, qualified service personnel. Consumer service is recommended only for filter cleaning/ replacement. Never operate the unit with the access panels removed. More details are available on the following websites: OSHA (Occupational Safety and Health Administration), at www.osha.gov and the State of California’s OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and maintained. WARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. 1 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 2 GENERAL CAUTION The unit can be positioned for bottom return air in the upflow position, left and right return in the horizontal position, top return in downflow position. Make sure the blower motor support is tight (3-motor mount bolts), then check to see if wheel is secured to motor shaft before operating unit. This Air Handler provides the flexibility for installation in any upflow or downflow horizontal application. The direct drive motors provide a selection of air volume. Top and side power and control wiring, accessible screw terminals for control wiring all combine to make the installation easy, and minimize installation cost. See Fig.2-5. Fig.1-1 CHECKING MOTOR STATUS Do not install unit in an area where flammable materials are present due to the risk of an explosion resulting in serious injury or death. WARNING The first 6 inches of supply air plenum and ductwork must be constructed of sheet metal as required by NFPA 90B. The supply air plenum or duct must have a solid sheet metal bottom directly under the unit with no openings, registers or flexible air ducts located in it. If flexible supply air ducts are used, they may be located only in the vertical walls of rectangular plenum, a minimum of 6 inches from the solid bottom. Metal plenum of duct may be connected to the combustible floor base, if not, it must be connected to the unit supply duct exposed to the supply air opening from the downflow unit. Exposing combustible (non-metal) material to the supply opening of a downflow unit can cause a fire resulting in property damage, personal injury or death. WARNING If the supporting structural members are not strong enough to take the unit’s weight, the unit could fall out of place and cause serious injury. If a return-air duct is not installed, carefully select the place and method of product installation so that air flow into the product will not be blocked. The unit should be installed in a level position to ensure proper condensation drainage. Up to an additional ¼" rise over the width or depth of the unit is allowed to create additional sloping towards the drain. Unit must be positioned between level and ¼" rise, sloping toward the drain connections. Install the indoor unit, power supply wiring and connecting wires at least 3.5 ft. away from televisions or radios in order to prevent image interference or noise. See Fig.2-1 and Fig.2-2. Exception warning to downflow: Installations on concrete floor slab with supply air plenum and ductwork completely encased must be not less than 2 inches of concrete (See NFPA 90A). AIRFLOW ≥40" ≥40" Fig.2-1 CLEARANCES IN THE HORIZONTAL POSITION ≥0 ≥0 ≥0 ≥25" Front of unit Fig.2-2 CLEARANCES IN THE VERTICAL POSITION 2 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor When the unit is installed in a hot and humid place, If the humidity inside the installation space might exceed 86°F and RH 80%, it is recommended to insulate the cabinet exterior. Use glass wool or polyethylene foam as insulation so that the thickness is more than 2 in. and fits inside the installation space opening. Respectively, condensation may form on the surface of the insulation. Be sure to use insulation that is designed for use with HVAC Systems. Condensation may form on the product during cool operation. It is also recommended to use the second drain pan and secure the unit firmly to prevent it from falling. See Fig.2-3 and Fig.2-4 . Drain piping Second drain pan Second drain pan Drain piping Fig.2-3 INSTALLED VERTICALLY Fig.2-4 INSTALLED HORIZONTALLY 3 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 2.1 Unit Dimensions NOTE: 25” CLEARANCE IS REQUIRED IN THE FRONT OF THE UNIT FOR FILTER AND COIL MAINTENANCE. ELECTRICAL CONNECTIONS MAY EXIT TOP OR EITHER SIDE SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION W A HIGH VOLTAGE CONNECTION 7/8”, 1-3/8”, 1-3/4” DIA KNOCK OUTS 10 5 16 LOW VOLTAGE CONNECTION BREAKER SWITCH (FOR ELECTRIC HEATER ONLY) H VAPOR LINE CONNECTION COPPER (SWEAT) LIQUID LINE CONNECTION COPPER (SWEAT) AUXILIARY DRAIN CONNECTION 3/4" FEMALE PIPE THREAD (NPT) AUXILIARY DRAIN CONNECTION 3/4" FEMALE PIPE THREAD (NPT) D PRIMARY DRAIN CONNCETION 3/4" FEMALE PIPE THREAD (NPT) UPFLOW UNIT SHOWN; UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY. Fig.2-5 DIMENSIONS DIMENSIONAL DATA MODEL SIZE UNIT HEIGHT "H" IN. [mm] UNIT WIDTH "W" IN. [mm] UNIT LENGHT "D" IN. [mm] SUPPLY DUCT "A" UNIT WEIGHT (LBS.[kg]) 24 46-1/2"[1180] 19-5/8"[500] 21-5/8"[550] 18"[456] 128 [58] 36 46-1/2"[1180] 19-5/8"[500] 21-5/8"[550] 18"[456] 128 [58] 48 54-1/2"[1385] 22"[560] 24"[610] 19-1/2"[496] 157 [71] 60 54-1/2"[1385] 22"[560] 24"[610] 19-1/2"[496] 161 [73] Table 2-1 4 04 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor 3 APPLICATIONS Replace breaker by inserting breaker mounting tab opposite white pull tab in opening, hook mounting tab over edge in opening. 3.1 Vertical Upflow With a screwdriver or pencil, pull the blue tab with hole away from breaker while setting that side of breaker into opening. When breaker is in place, release tab, locking circuit breaker into location in opening. Upflow is the default factory configuration. See Fig.2-5. If return air is to be ducted, install duct flush with floor. Use fireproof resilient gasket 1/8 to 1/4 in. thick between the ducts, unit and floor. Set unit on floor over opening. Repeat above operation for remaining breaker(s) (if more than one is provided). IMPORTANT NOTE Replace single point wiring jumper bar, if it is used, on line side of breaker and tighten securely. Torque applied to drain connections should not exceed 15ft.lbs. See Fig.2-5 & 3-1. Double check wires and lugs to make sure all are secure and tight. Check to make sure unit wiring to circuit breaker load lugs match that shown on the unit wiring diagram. Note The switch on the front of the panel is only used with an electric heater. 2-3/4 1-9/16 3.3 Horizontal 2-15/16 5/16 1-3/8 Conversion to Horizontal left: A vertical upflow unit may be converted to horizontal left by removing indoor coil assembly and reinstalling coil as shown for left hand air supply. See Fig. 3-2 5/16 2-13/16 1-1/4 Secondary drain pan kits are recommended when the unit is configured for the horizontal position over a finished ceiling and/or living space. Fig.3-1 DIMENSIONS FOR FRONT CONNECT COIL 3.2 Vertical Downflow Conversion to Vertical Downflow: A vertical upflow unit may be converted to vertical downflow. Remove the door and indoor coil and reinstall 180° from original position. See Fig.3-2. IMPORTANT: To comply with certification agencies and the National Electric Code for downflow application, the circuit breaker(s) on field-installed electric heater kits must be re-installed per procedure below so that the breaker switch “on” position and marking is up and, “off” position and marking is down. To rotate breaker(s): Rotate one breaker set (circuit) at a time starting with the one on the right. Loosen both lugs on the load side of the breaker. (Make sure that wires are identified and are reinstalled into proper breaker). Wires are bundled with wire ties, one bundle going to the right lug and one bundle going to the left lug. Using a screwdriver or pencil, lift white plastic tab with hole away from breaker until breaker releases from mounting opening. With breaker held in hand, rotate breaker so that “on” position is up, “off” position is down with unit in planned vertical mounting position. Insert right wire bundle into top right breaker lug, ensuring all strands of all wires are inserted fully into lug, and no wire insulation is in lug. Tighten lug as tight as possible while holding circuit breaker. Check wires and make sure each wire is secure and none are loose. Repeat for left wire bundle in left top circuit breaker lug. 5 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual A 1:4 ENSURE THE RETAINING CHANNEL IS FULLY ENGAGED WITH THE COIL RAIL. DETAIL A RAILS AIRFLOW A AIRFLOW RAILS Fig.3-2 VERTICAL DOWNFLOW & HORIZONTAL LEFT APPLICATIONS (lower front service panel removed “view”.) REAR WATER CATCHER STRAPS TOP AIR STOP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION FRONT WATER CATCHER AUXILIARY HORIZONTAL DRAIN CONNECTION VERTICAL DRAIN PAN PRIMARY DRAIN CONNECTION AUXILIARY UPFLOW/DOWNFLOW DRAIN CONNECTION THIS SYSTEM IS CHARGED WITH NITROGEN BEFORE SHIPMENT 48K,60K 36K,24K STRAPS Fig.3-3 INDOOR COIL AND DRAIN PAN SET-UP 6 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor Power wiring may be connected to either the right, left side or top. Three 7/8", 1-3/8", 1-3/4" dia. concentric knockouts are provided for connection of power wiring to unit. CAUTION Horizontal units must be configured for right hand air supply or left hand air supply. Horizontal drain pan must be located under indoor coil. Failure to use the drain pan can result in property damage. Power wiring is connected to the power terminal block in unit electric cabinet. 4.2 Control Wiring Conversion in Horizontal Direction: Horizontal right-hand supply can be changed to horizontal lefthand supply by removing the indoor coil and reinstalling 180° from original position. IMPORTANT: Class 2 low voltage control wiring should not be run in conduit with main power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used. 3.4 Installation In An Unconditioned Space Low voltage control wiring should be 18 Awg. color-coded. For lengths longer than 100 ft., 16 Awg. wire should be used. IMPORTANT: There are two pairs of coil rails in the air handler for default and counter flow application. If the air handler is installed in an unconditioned space, the two unused coil rails should be removed to minimize air handler surface sweating. The coil rails can be easily removed by taking off the 6 mounting screws from both sides of the cabinet. Low voltage control connections are made to low voltage pigtails extending from top of air handler (upflow position - see Fig 2-5). Connections for control wiring are made with wire nuts. Control wiring knockouts (5/8"and 7/8") are also provided on the right and left side of the unit for side connection. 4. ELECTRICAL WIRING See wiring diagrams attached to indoor and outdoor sections to be connected. Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local ordinance. Make sure, after installation, separation of control wiring and power wiring has been maintained. WARNING Disconnect all power to unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death. 4.3 Grounding WARNING The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. 4.1 Power Wiring It is important that proper electrical power is available for connection to the unit model being installed. See the unit nameplate, wiring diagram and electrical data in the installation instructions. Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet. Grounding may also be accomplished by attaching ground wire(s) to ground lug(s) provided in the unit wiring compartment. If required, install a branch circuit disconnect of adequate size, located within sight of, and readily accessible to the unit. Ground lug(s) are located close to wire entrance on left side of unit (up-flow). Lug(s) may be moved to marked locations near wire entrance on right side of unit (up-flow). If alternate location is more convenient. IMPORTANT: After the Electric Heater is installed, units may be equipped with one two or three 30-60 amp. circuit breakers. These breaker(s) protect the internal wiring in the event of a short circuit and serve as a disconnect. Circuit breakers installed within the unit do not provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection. Supply circuit power wiring must be 167°C/75°C minimum copper conductors only. See Electrical Data in this section for ampacity, wire size and circuit protector requirement. Supply circuit protective devices may be either fuses or “HACR” type circuit breakers. Use of multiple supply circuits require grounding of each circuit to lug(s) provided in unit. 7 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 4.4 Electrical Data MODEL VOLTAGE HERTZ HP SPEEDS CIRCUIT AMPS. MAXIMUM CIRCUIT PROTECTOR 24 208/230 60 1/5 3 2.6 15(A) 36 208/230 60 1/3 3 3.2 15(A) 48 208/230 60 1/2 3 4.3 15(A) 60 208/230 60 3/4 3 4.4 15(A) 4.5 Heat Kit Data Air Handler Model Heater Kit Model Used EHK-05A 24 EHK-08A Electric Heat (kW) Min. Circuit Ampacity Max. Fuse or Breaker (HACR) Ampacity 240V 208V 240V 208V 5 29 25.5 30 30 7.5 42 36.8 45 40 40 -- -- 50 -- ---- 55 48.1 60 50 5 29.4 25.9 30 30 7.5 42.4 37.2 45 40 10 55.4 48.5 60 50 EHK-15B 15 55.4/26.1 48.5/22.6 60/30 50/25 EHK-20B 20 55.4/52.1 48.5/45.2 60/60 60/50 EHK-05A 5 30.3 26.8 35 30 EHK-08A 7.5 43.3 38.1 45 10 56.3 49.4 60 36 48 EHK-10A • • • • • • • • EHK-15B 15 56.3/26.1 49.4/22.6 60/30 50/25 -- EHK-20B 20 56.3/52.1 49.4/45.2 60/60 50/50 -- EHK-05A 5 31.8 28.3 35 30 EHK-08A 7.5 44.8 39.6 45 40 10 57.8 50.9 60 60 EHK-15B 15 57.8/26.1 50.9/22.6 60/30 60/25 EHK-20B 20 57.8/52.1 50.9/45.2 60/60 60/50 60 EHK-10A Medium High -- 10 EHK-05A EHK-10A Low • • • • • • • • EHK-10A EHK-08A Fan speed (AC/HP) • • •• • -- • • •• • • • • • • • • • • • • • • • • • • • Heat kit suitable for AHU 4-way position installation. Ampacities for MCA and Fuse/breaker including the blower motor. Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally. Electric Heater Kits NO. Kit Description Ref.Air Handler Use 1 EHK-05A 5kW Heat Strip 24/36/48/60 2 EHK-08A 7.5kW Heat Strip 24/36/48/60 3 EHK-10A 10kW Heat Strip 24/36/48/60 4 EHK-15B 15kW Heat Strip, double Breaker panel 5 EHK-20B 20kW Heat Strip, double Breaker panel 8 36/48/60 3648/60 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor 5. AIRFLOW PERFORMANCE Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size. External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. AIRFLOW PERFORMANCE DATA Model Number Low 24 Medium High Low 36 Medium High Low 48 Medium High Low 60 CFM Wet Coil without filter and Electric Heat Motor Speed Medium High External Static Pressure-Inches W.C.[kPa] 0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200] CFM Watts Current/A CFM Watts Current/A CFM Power/W Current/A CFM Watts Current/A CFM Watts Current/A CFM Power/W Current/A 999 316 1.38 1176 342 1.49 1409 456 2.01 1028 362 1.64 1315 406 1.82 1532 524 2.39 953 310 1.36 1127 336 1.47 1359 446 1.96 985 353 1.62 1266 399 1.8 1478 513 2.36 905 306 1.34 1086 334 1.45 1306 438 1.93 930 345 1.6 1208 392 1.78 1421 502 2.34 847 302 1.32 1028 326 1.42 1253 429 1.9 859 335 1.57 1146 385 1.75 1347 491 2.31 757 288 1.28 944 315 1.38 1192 419 1.86 781 323 1.54 1065 372 1.72 1284 478 2.28 681 279 1.24 842 303 1.33 1108 404 1.8 712 313 1.51 981 361 1.69 1184 462 2.23 610 270 1.21 746 292 1.29 986 384 1.73 649 303 1.49 866 344 1.65 1082 446 2.2 543 256 1.16 668 281 1.25 870 368 1.67 571 290 1.45 775 331 1.62 932 423 2.14 411 240 1.1 569 266 1.19 743 348 1.61 468 276 1.42 686 320 1.59 805 407 2.11 CFM Watts Current/A CFM Watts Current/A CFM Power/W Current/A CFM Watts Current/A CFM Watts Current/A CFM Power/W Current/A 1336 492 2.24 1654 550 2.4 1918 717 3.2 1726 678 2.95 1983 695 3.02 2138 793 3.45 1310 483 2.22 1610 537 2.38 1875 703 3.18 1693 658 2.87 1933 675 2.93 2086 773 3.7 1282 474 2.17 1569 526 2.35 1817 686 3.14 1655 639 2.78 1879 655 2.85 2024 751 3.27 1234 463 2.13 1510 512 2.32 1771 670 3.1 1637 619 2.69 1828 635 2.76 1952 726 3.17 1182 452 2.1 1461 503 2.3 1715 652 3.04 1584 602 2.62 1760 615 2.67 1873 702 3.06 1140 443 1.93 1394 489 2.18 1651 635 3 1500 576 2.52 1685 596 2.59 1797 679 2.97 1049 422 2.03 1350 475 2.16 1584 617 2.9 1421 553 2.42 1597 574 2.5 1722 658 2.88 925 393 1.9 1265 458 2.08 1511 600 2.87 1328 526 2.31 1507 550 2.4 1646 638 2.79 833 374 1.87 1034 416 2.04 1395 570 2.85 1217 495 2.18 1403 522 2.28 1516 604 2.65 --- Shaded boxes represent airflow outside the required 300-450 cfm/ton, which are not recommended. NOTES: Airflow based upon cooling performance at 230V with no electric heat and no filter. The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures. Heat pump systems require a specified airflow for electric heat operating. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally. Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship. Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise. The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space. An air velocity meter or airflow hood can be used to balance and verify branch and system airflow (CFM). 9 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 6. DUCTWORK 7. REFRIGERANT CONNECTIONS Field ductwork must comply with the National Fire Protection Association NFPA 90A, NFPA 90B and any applicable local ordinance. Keep the coil connections sealed until refrigerant connections are made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information. Coil is shipped with Nitrogen. Evacuate the system before charging with refrigerant. Install refrigerant tubing so that it does not block service access to the front of the unit. Nitrogen should flow through the refrigerant lines while brazing. Use a brazing shield to protect the cabinet’s paint and a wet rag to protect the rubber grommet and input pipe’s Piston seal ring from being damaged by torch flames. After the refrigerant connections are made, seal the gap around the connections with pressure sensitive gasket. WARNING Do not, under any circumstances, connect return ductwork to any other heat producing device such as fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage. Sheet metal ductwork in unconditioned spaces must be insulated and covered with a vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance with SMACNA Construction Standard on Fibrous Glass Ducts. Ductwork must comply with National Fire Protection Association as tested by UL Standard 181 for Class I Air Ducts. Check local codes for requirements on ductwork and insulation. WARNING Use a wet rag to protect the two seal rings in the input pipe from being damaged by torch flames while brazing. Duct system must be designed within the range of external static pressure the unit is designed to operate against. It is important that the system airflow be adequate. Make sure supply and return ductwork, grills, special filters, accessories, etc. are accounted for in total resistance. See airflow performance tables in this manual. After the work is finished, make sure to check that there is no vapor leak after checking for vapor leaks, be sure to insulate the piping connections referring to Fig.7-1. Do not leave a gap Vapor piping Design the duct system in accordance with “ACCA” Manual “D” Design for Residential Winter and Summer Air Conditioning and Equipment Selection. Latest editions are available from: “ACCA” Air Conditioning Contractors of America, 1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure pressure drop information (straight length plus all turns) shown in “ACCA” Manual “D” are accounted for in the system. Air handler Supply plenum is attached to the 3/4” duct flanges supplied with the unit. Attach flanges around the blower outlet. Piping heat insulation material Liquid piping Do not leave a gap Fig.7-1 PIPING CONNECTIONS IMPORTANT: If an elbow is included in the plenum close to the unit, it can not be smaller than the dimensions of the supply duct flange on the unit. IMPORTANT: The front flange on the return duct if connected to the blower casing must not be screwed into the area where the power wiring is located. Drills or sharp screw points can damage insulation on wires located inside unit. Secure the supply and return ductwork to the unit flanges, using proper fasteners for the type of duct used and tape the duct-to-unit joint as required to prevent air leaks. 10 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor 7.1 Condensate Drain Tubing Test condensate drain pan and drain line after installation is complete. Pour water into drain pan, enough to fill drain trap and line. Check to make sure drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the termination of the primary drain line. Consult local codes for specific requirements. CONDENSATE DRAIN TRAP DO NOT OPERATE UNIT WITHOUT CONDENSATE DRAIN TRAP. Be sure to install a drain trap at the drain outlet since the inside of the unit is at negative pressure relative to atmospheric pressure during operation. DO NOT OVERTIGHTEN DRAIN FITTING TOWARD DRAIN CONNECTION UNIT MUST BE SLIGHTLY INCLINED 3" 3" UNIT Be sure to insulate the drain piping and drain socket since condensation may cause water leakage. 8. AIR FILTER (not factory-installed) TO APPROVED DRAIN Fig.7-2 CONDENSATE DRAIN TRAP External filter or other means of filtration is required. Units should be sized for a maximum of 300 feet/min air velocity or what is recommended for the type of filter installed. IMPORTANT: 1. When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, silicone or Teflon tape and install, hand tighten. 2. When making drain fitting connections to drain pan, do not overtighten. Over tightening fittings can split pipe connections on the drain pan. Filter application and placement are critical to airflow, which may affect the heating and cooling system performance. Reduced airflow can shorten the life of the system’s major components, such as motor, limits, elements, heat relays, evaporator coil or compressor. Consequently, we recommend that the return air duct system have only one filter location. For systems with a return air filter grill or multiple filter grills, can have a filter installed at each of the return air openings. Install drain lines so they do not block service access to front of the unit. Minimum clearance of 24 inches is required for filter, coil or blower removal and service access. Make sure unit is level or pitched slightly toward primary drain connection so that water will drain completely from the pan. (See Fig.7-2) If adding high efficiency filters or electronic air filtration systems, it is very important that the air flow is not reduced. If air flow is reduced the overall performance and efficiency of the unit will be reduced. It is strongly recommended that a professional installation technician is contacted to ensure installation of these such filtration systems are installed correctly. Do not reduce drain line size less than connection size provided on condensate drain pan. Use 3/4" PVC piping for drain piping connections. All drain lines must be pitched downward away from the unit a minimum of 1/8" per foot of line to ensure proper drainage. IMPORTANT: Do not double filter the return air duct system. Do not filter the supply air duct system. This will change the performance of the unit and reduce airflow. Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or run line to a safe outdoor area. WARNING The drain line should be insulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line. Do not operate the system without filters. A portion of the dust entrained in the air may temporarily lodge in the duct and run at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler heating elements. This residue could soil ceilings, walls, drapes, carpets and other articles in the house. Soot damage may occur with filters in place, when certain types of candles, oil lamps or standing pilots are burned. Make provisions for disconnecting and cleaning of the primary drain line should it become necessary. Install a 3 inch trap in the primary drain line as close to the unit as possible. Make sure that the top of the trap is below connection to the drain pan to allow complete drainage of pan. (See Fig. 7-2). Auxiliary drain line should be run to a place where it will be noticeable if it becomes operational. Homeowner should be warned that a problem exists if water should begin running from the auxiliary drain line. Plug the unused drain connection with the plugs provided in the parts bag, using a thin layer of teflon paste, silicone or teflon tape to form a water tight seal. 11 Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 9. FILTER INSTALLATION DIMENSIONS FILTER RAILS FILTER COVER H MANUAL BOLT RE TU RN AIR A OP D EN IN G B DE PT W H NOTE: Air filter is optional part, isn't factory-installed. Fig.9-1 EXTERNAL FILTER BASE DIMENSIONAL DATA FILTER SIZE IN [mm] "W" IN [mm] "D" IN [mm] "H" IN [mm] Return width "A" IN Return length MODEL "B" IN 24/36 18Χ20[457Χ508] 18.3[466] 21.6[548] 1[25.4] 20.8 16.3 48/60 20Χ22[508Χ559] 20.7[526] 23.9[608] 1[25.4] 23 18.8 MODEL AIR FILTER REMOVAL 1. Remove bolts manually, remove air filter recover. See in Fig.9-1. 2. Hold the edge of the air filter and extract out. 3. Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy, use soft brush and mild detergent to clean it and dry out in cool place). See in Fig.9-2. 4. Install new filter so that the arrow on the filter is in the same direction as airflow. Fig.9-2 AIR FILTER CLEAN 12 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor 10. WIRING DIAGRAM THERMOSTAT 24C 24RC G R C W1 W2 BLACK YELLOW BLACK/WHITE WHITE BLACK RED G Fan GREEN W1/B W2 Y1 Comp Y INDOOR UNIT C OUTDOOR UNIT Fig.10-1 CONTROL WIRING FOR AC SYSTEMS THERMOSTAT W2 W1/B 24C G R C W1 W2 INDOOR UNIT C PURPLE B OUTDOOR UNIT Fig.10-2 CONTROL WIRING FOR HP SYSTEMS 13 Y BLUE YELLOW BLACK RED WHITE BLACK RED G Fan GREEN Y1 Comp BLACK/WHITE 24RC W Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. FOR OPTIONAL ELECTRIC HEAT L1 L2 CN3 CN6 CN8 M1 M2 LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED FACTORY OPTIONAL LOW VOLTAGE FACTORY STANDARD FIELD INSTALLED FACTORY OPTIONAL USE COPPER CONDUCTORS ONLY WARNING CABINET MUST BE PERMANMENTLY GOUNDED AND ALL WIRING TO CONFORM TO I.E.C,N.E.C,C.E.C,C.L.C,AND LOCAL CODES AS APPLICABLEREPLACEMENT WIRE MUST BE THE SAME GAUGE AND INSULATION TYPE AS ORIGINAL WIRE ~ CN4 CN7 CN11 FAN CN1 FAN MOTOR CAPACITANCE TO THERMOSTAT FOR SINGLE AUXILARY HEAT MODE CONNECT W1 OR CONNECT W1 WITH W2 Fig.10-3 INDOOR UNIT WIRING DIAGRAM FOR PSC MOTOR SYSTEMS Note: Description of fan speed switch with PSC motor 1. Default as medium speed of factory settings. 2. High speed wiring: Switch to high speed (black wire) and connect with FAN terminal, while medium speed (red wire) connect with M2 terminal. 3. Low speed wiring: Switch to low speed (blue wire) and connect with FAN terminal, while medium speed (red wire) connect with M1 terminal. 4.For the 36K model , in order to make the AHRI 14.3 SEER2 system rating the fan speed must be changed from Medium to High. Terminal Fan speed Fan M1 M2 Medium Red Blue Black High Black Blue Red Low Blue Red Black 14 6 5 4 3 2 1 6 5 4 3 2 1 C 0 1 0 1 0 1 0 1 RED BLACK WHITE W1 C BLUE BLACK BROWN WHITE BLACK BLACK/WHITE W2 WHITE BLACK 2 6 2 6 2 6 2 6 15 6 5 4 3 2 1 C HEATER KIT PLUG Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 2 4 8 RED BLACK YELLOW BLUE CB CIRCUIT BREAKER LS LIMIT SWITCH FL FUSE LINK RELAY1 6 LS FL FL L2 L1 CB2 CB1 FL POWER L2’ L1’ 2 1 ELEMENTS 4 3 CB1 POWER L2 L1 4 3 L2’ BLACK BLACK L1’ 2 1 LS ELEMENTS LS ELEMENTS YELLOW YELLOW FL FL L2 4 3 L2’ POWER L1 2 1 L1’ BLACK BLACK 6 5 4 3 2 1 6 5 4 3 2 1 NOTE1 6 5 4 3 2 1 0 1 RED 2 6 2 6 4 8 4 8 RED RED BLUE BLUE RELAY2 RELAY1 RELAY2 2 6 2 6 2 6 4 8 4 8 4 8 RED RED BLUE BLUE RED BLUE YELLOW BLACK Fig.10-4 INDOOR UNIT WIRING DIAGRAM FOR ELECTRIC HEAT LS ELEMENTS CB1 4 3 L2 L2’ BLACK BLACK FL FL FL 4 3 L2 L2’ POWER L1 2 1 CB2:30A L1’ 10kW CB1 60A 7.5kW CB1 50A POWER L2 4 3 L2’ BLACK L1 POWER L1 2 1 L1’ ELEMENTS CB1:60A LS LS FL FL BLACK L1’ 2 1 ELEMENTS ELEMENTS ELEMENTS LS LS YELLOW YELLOW YELLOW YELLOW CB CIRCUIT BREAKER LS LIMIT SWITCH FL FUSE LINK RELAY2 RELAY1 CB CIRCUIT BREAKER LS LIMIT SWITCH KIT(10kW+5kW) FL FUSE LINK RED BLACK 0 1 0 1 BLACK WHITE W1 C BLUE WHITE 0 1 0 1 BLACK WHITE W1 C BLUE BROWN BLACK 15kW HEAT 6 5 4 3 2 1 BLACK/WHITE BLACK WHITE C W2 BROWN 10kW HEAT KIT 7.5kW HEAT KIT PCB CN6 PCB NOTE1: WHEN THE AHU MACHINE DOES NOT CONTAIN PCB BOARDS, SHORT LINES IN THE ACCESSORY BAG DOES NOT NEED. RED BLACK WHITE W1 BLUE RED RED BLUE BLUE RED RED BLUE BLUE LS ELEMENTS LS ELEMENTS YELLOW YELLOW HEATER KIT PLUG 5kW HEAT KIT NOTE1 PCB 6 5 4 3 2 1 BROWN 20kW HEAT KIT/CB 60A 4 8 4 8 4 8 4 CB CIRCUIT BREAKER LS LIMIT SWITCH FL FUSE LINK RELAY2 RELAY1 RELAY2 RELAY1 15kW HEAT KIT(7.5kW+7.5kW )/CB 50A PCB CN6 NOTE1 HEATER KIT PLUG CN6 HEATER KIT PLUG CN6 8 AMP**S1A - Instruction Manual Multi-Position Air Handler-PSC Motor Multi-Position Air Handler-PSC Motor AMP**S1A - Instruction Manual 11. PISTON/TXV INSTALLATION Table 11-3.Superheat Charging Chart Charge the system by superheat when using a piston. Reference the outdoor unit installation guide to charge the system by subcooling when using a TXV. This coil comes with a factory installed piston metering device. See Table 11-1 for factory installed piston size. Some system combinations will require a different sized piston to be field installed. Indoor Temperature(°F) Dry Bulb/wet Bulb Outdoor 95/79 90/75 85/71 80/67 75/63 70/58 Temp (°F) Superheat (°F) A TXV may be required to achieve minimum efficiency ratings or for long refrigerant line set applications. Reference AHRI for system combination ratings. 115 110 105 100 95 90 85 80 75 70 65 60 55 Reference Table 11-3 to charge the system by superheat when using a piston. Reference the outdoor unit installation guide to change the system by subcooling when using a TXV. Table 11-1. Factory installed piston size for each model. Additional piston sizes are provided in the ship with literature bag as necessary. MODEL 50 52 56 58 60 64 68 70 73 75 80 83 90 24 X* 36 X X X* 48 X X* 60 X* * means that this piston is pre-installed WARNING Failure to install the proper piston can lead to poor system performance and possible compressor damage. Table 11-2 . Optional TXV kit part numbers. Some combinations may require a TXV. See AHRI for system combination ratings. Outdoor Unit Capacity (Tons) R410a TXV Kit 1.5-3.0 TR6-3TONNB 3.5-4.0 TR6-4TONB 5.0 TR6-5TONB 16 23 24 26 27 29 30 32 34 35 37 38 40 41 16 17 19 21 23 25 26 28 30 32 34 36 37 7 9 11 13 14 18 20 22 24 26 29 31 34 6 6 6 7 9 12 15 17 19 21 24 27 30 5 5 5 6 6 7 9 11 13 16 19 22 26 5 5 5 5 5 5 6 6 7 10 13 17 21 SE SERIES LIMITED WARRANTY Congratulations on purchasing your new HVAC equipment. Your unit automatically qualifies for the warranty coverage listed below provided you meet the warranty conditions. APPLIES TO MODELS: RSA*, RSH*, AMP*, WMP*, WMX*, GFM*, MAA*, RHP*, RGP* YEAR 1 PRODUCT REPLACEMENT If the heat exchanger, evaporator coil (packaged systems only), condenser coil, or compressor fails within the first year (365 days) after the date of installation to the original consumer for the original installation, the original purchase cost of the unit will be reimbursed to the authorized Comfort-Aire/ Century distributor who has received prior authorization from Comfort-Aire/Century for the failure. The owner is responsible for additional labor, freight, and miscellaneous charges. Units installed in a commercial application, defined as any application other than a residential/multifamily (personal, family or household) purpose, are not eligible for the one year product replacement. LIMITED FIVE (5) YEAR WARRANTY All parts, the compressor, and the heat exchanger are warranted to be free from defects in workmanship and materials for normal residential use and maintenance for five (5) years from the date of purchase by the original consumer for the original residential installation. LIMITED EXTENDED WARRANTY When registered with Comfort-Aire/Century, the heat exchanger is warranted to be free from defects in material and workmanship for twenty (20) years and the compressor is warranted to be free from defects in material and workmanship for ten (10) years from the date of purchase by the original consumer for the original installation. DURATION OF WARRANTY The warranty begins on the date of purchase by the original consumer (homeowner). The original consumer must retain a receipted bill of sale or invoice showing model and serial number as proof of the warranty period initiation. CONDITIONS FOR WARRANTY COVERAGE Unit must be properly installed and maintained by a licensed HVAC service provider in accordance with the installation, operation, and maintenance instructions provided with each unit. Unit cannot have been subjected to accident, alteration, improper repair, neglect/misuse, or force majeure. Proof of proper maintenance over the lifetime of the unit must be supplied. Performance cannot be impaired by use of any product not authorized by Comfort-Aire/ Century, or by any adjustments or adaptations to components. Serial numbers and/or rating plate have not been altered or removed. Damage has not been a result of inadequate wiring or voltage conditions, use during brown-out conditions, or circuit interruptions. Unit remains in the original residential installation and is not transferrable. Unit was not purchased over the internet or at auction. Non-approved refrigerant and/or non-approved system additives will void this warranty. WARRANTY EXCEPTIONS The Limited Express Warranty does not cover costs associated with normal maintenance, utility usage, labor, shipping and handling, or collateral damage. It also does not cover any portion or component of the system that is not supplied by Comfort-Aire/Century, regardless of the cause of failure of such portion or component. LIMITATION OF LIABILITY There are no other express or implied warranties. Comfort-Aire/Century makes no warranty of merchantability and does not warrant that the unit is suitable for any particular purpose, building, room size, or condition except as specifically provided in this document. There are no other warranties, express or implied, which extend beyond the description in this document. All warranties implied by law are limited in duration to the five-year term of the Parts Warranty. Your exclusive remedy is limited to the replacement of defective parts. Comfort-Aire/Century will not be liable for any consequential or incidental damages caused by any defect in this unit. This warranty gives you specific legal rights and you may also have other rights which vary from state to state. Some states do not allow a limitation on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. No warranties are made for units sold outside the continental United States and Canada. Your distributor or final seller may provide a warranty on units sold outside these areas. Comfort-Aire/Century will not be liable for damages if our performance regarding warranty resolution is delayed by events beyond our control including accident, alteration, abuse, war, government restrictions, strikes, fire, flood, or force majeure. Please register your new equipment to enjoy an extended warranty. For Comfort-Aire: www.comfort-aire.com/wps/portal/product-registration For Century: www.century-hvac.com/wps/portal/product-registration KEEP THIS INFORMATION AS A RECORD OF YOUR PURCHASE Apply Serial Number and Model Number sticker here (from product carton). if unavailable, write serial number and model number below (can be found on unit rating plate). Date of Purchase o Component of new HVAC system Date Installation Completed o Replacement furnace only Remember to retain your bill of sale as proof of warranty period and ownership. SE_WARRANTY_2/2024 Page Intentionally Left Blank Page Intentionally Left Blank Page Intentionally Left Blank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
advertisement
Key Features
- Multi-position installation
- High-efficiency operation
- PSC Motor
- Easy maintenance
- Factory-sealed cabinet
- Integrated filter rack
- Condensate drain pan with UVC inhibitor
Frequently Answers and Questions
What are the possible positions for installation of Century AMP60S1A-CY?
This air handler can be installed in vertical upflow, downflow or horizontal positions.
What is the maximum external static pressure the unit is designed to operate against?
The external static pressure that the unit can operate against is provided in the Airflow Performance Data table in the manual.
How do I convert the unit from upflow to downflow?
Remove the door and indoor coil and reinstall 180° from the original position.
What type of filter is required for this unit?
An external filter or other means of filtration is required. Units should be sized for a maximum of 300 feet/min air velocity or what is recommended for the type of filter installed.