Technical Data
Industrial Tower Uninterruptible Power Supply
Specifications
Bulletin Numbers 1609-P
Topic
Page
1609-P Specifications
2
1609-P Approximate Dimensions and Shipping Weights
3
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
1609-P Tower Uninterruptible Power Supply
Specifications
Specifications
Electrical Ratings
Input
1609-P3000N
1609-P3000A
1609-P5000E
1609-P8000E
1609-P10000E
V nom. (V AC)
120
230
208/230
208/230
208/230
Voltage Range,
default (V AC)
90…150V
Current (A)
20 nom., 28 max.
Capacity
160…280V
11 nom., 14 max.
3000VA (2100 W)
Frequency
19 nom., 24 max.
30 nom., 40 max.
39 nom., 48 max.
5000VA (3500 W)
8000VA (6400 W)
10 000VA (8000 W)
45…65 Hz (self sensing)
PFC
Output
> 0.95
Protection
N/A
V nom.
120V
Capacity
N/A
N/A
3000VA (2100 W)
Protection
5000VA (3500 W)
Reg.
Protection
+/- 2% static
+/- 5% dynamic
<5% at full load
Crest Factor
3:01
On Battery
86%
On Line
88%
Surge
IEC 1000-4-4
Overload
125% : 1 minute, 150% : 30 seconds
Output Short
Input circuit breakers and/or premises branch protection
Yes
Bypass
N/A
Safety
EN 61000-3-2
UL 1778, cULus, IEC 60950
EMC
FCC (Class A)
EN50091-2
FCC (Class A), EN50091-2
Markings
cULus, CSA
CE
Indicators and
Controls
Sealed Lead Acid, valve regulated, hot swappable, user replaceable
192V
Charger
Temperature compensated current limited, float charger
Less than 3 hours to
90% capacity
Less than 3 hours to 85% capacity
Lifetime
2…4 years @ 25 °C ambient
Temperature
0…40 °C (operating), -20…60 °C (short term storage)
Altitude
10 000 ft (operating)
Humidity
0…95% non-condensing (operating)
Heat Output (Full
Load)
655 BTU/hour
Audible Noise
<50 dB @ 1 meter
(full load)
AC Outlets
(6) NEMA 5…15
(2) NEMA 5…20
AC Inlets
NEMA L5…30
DB9
Communication
5…7 minutes @ full load, 13…18 minutes @ half load
Voltage
Recharge Time
Rear Panel
cULus, CSA, CE
14 minutes @ full load, 34 minutes @ half
load
Type
Environment
70 A input circuit breaker
UL 1778, cULus, IEC
60950
Run Time
Battery Pack
N/A
+/- 1% static, +/- 5% dynamic
Thermal Protection
Regulatory
10 000VA (8000 W)
N/A
Nominal +/- 3 Hz
THD
Efficiency
8000VA (6400 W)
3…15 A circuit breaker
Frequency
On Battery
70 A input circuit breaker
208V
1040 BTU/hour
1536 BTU/hour
2216 BTU/hour
<55 dB @ 1 meter (full load)
(8) IEC C13
(2) IEC C19
IEC C14
(12) IEC C13
(2) IEC C19
IEC C20
3 position terminal blocks
Serial and Contact Closures
EPO
Via Contact Closure
Network
Via Network Management Card (1609-NMC, provided as standard with units >3 KVA)
LED Status
On-line, In Bypass Mode, On Battery, Overload and Replace Battery, Fault, Bar graph for Load, Bar graph for
Battery Fuel Gauge, Bar graph for Measured Input Voltage when recessed switch is held
Control
(Front panel) On/self-test/alarm silence/cold start/load off
Audible
On Battery: 4 short beeps repeats about 20 seconds (mutable), Low Battery: persistent 0.5 second beep every 1
second (mutable), In Bypass: continuous beeping, Failure: continuous tone, Replace Battery: occasional on/off
change - single beep
Wiring of the UPS should be performed by a qualified electrician. Use appropriate size wires.
In 230V AC applications, the UPS must be protected with a circuit breaker that complies with European standards for
branch rated protection per the country of installation.
In 208V AC applications, the UPS must be protected by a dual-pole, 10 A branch rated, UL 489 circuit breaker.
The 120V AC 1609-P3000N has supplementary circuit breaker protection. The unit should be protected by a singlepole, 15 A branch rated, UL 489 circuit breaker.
Allen-Bradley part number 1492-MCAA115 is suggested.
The branch circuit breaker must be off prior to wiring the unit.
2
Rockwell Automation Publication -1609-TD001A-EN-P
1609-P Tower Uninterruptible Power Supply
Approximate Dimensions
Notes
208V AC applications: The 1609-P5000E, 1609-P8000E, and 1609-P10000E, ship ready for 230V AC sources. When operating one of these in
208V AC applications, the UPS low transfer voltage settings are adjusted through the PowerChute® software or the Network Management
Card.
Refer to the PowerChute® User Guide or the Network Management Card instructions for details.
Approximate Dimensions and Shipping Weights
Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
(5.1)
(25.3)
(17.4)
(10.3)
(25.3)
(17.4)
Approximate Shipping Weights
Output Power
Input Voltage
Cat. No.
Approx. Shipping Weight
[kg (lb)]
63.5 (140)
3000VA (2100 W)
120V AC
1609-P3000N
3000VA (2100 W)
230V AC
1609-P3000A
63.5 (140)
5000VA (3500 W)
208/230V AC
1609-P5000E
63.5 (140)
8000VA (6400 W)
208/230V AC
1609-P8000E
128.8 (284)
10000VA (8000 W)
208/230V AC
1609-P10000E
128.8 (284)
Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
Rockwell Automation Publication -1609-TD001A-EN-P
3
1609-P Tower Uninterruptible Power Supply
Approximate Dimensions
(3.7)
(22.8)
(4.8)
(25.3)
(5.1)
(17.4)
(25.3)
(5.1)
(17.4)
Approximate Shipping Weights
Description
Cat. No.
Approx. Shipping Weight
[kg (lb)]
Replacement battery
1609-PBAT
37.2 (82)
External battery pack
1609-PXBP
101.2 (223)
1609-5000CCT
63.5 (140)
1609-PRK1
3.6 (8)
5000VA CCT (120V step down transformer)
Rail kit
4
Rockwell Automation Publication -1609-TD001A-EN-P
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 1609-TD001A-EN-P - August 2014
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.