null  User manual
WORLD LEADER OF INNOVATIVE SOLUTIONS
IN FIRE DETECTION AND ALARM SYSTEMS
Product Catalogue Australia 2015
Contents
Fire Control Panels
ZoneSense DH4 Conventional
ZoneSense PLUS Conventional
ZoneSense PLUS AR Conventional
LoopSense Intelligent
FireFinder PLUS Intelligent
FireFinder Intelligent
Add Ons
Alarm Systems
Standalone Occupant Warning Panel
Occupant Warning System Add-Ons
EV3000 Emergency Control Panel
EV3000 Emergency Control Panel - Add Ons
Graphics Package
Smart GraphicsHD
4
6
8
10
12
14
16
28
30
32
34
38
Detection & MCP’s
Conventional
Series 65 Detection
Heat Detection
Manual Call Points
Sampling Duct Units
Beam Detection
Addressable
XP95 Detection
Discovery Detection
Manual Call Points
Duct Sampling Unit
Specialist Detection
Flame Detection
Hazardous Area Detection
Marine Detection
Xpander Wireless Detection
Aspirating Smoke Detection -Wagner Titanus Family
High Sensitivity Detection System
Aspirating Smoke Detection - FastSense
40
42
45
46
47
48
50
53
54
55
58
64
66
70
72
73
Audio Visual & Interfaces
XP95 Interfaces
76
Conventional Audio Visual
80
Remote Indicators
83
Bells84
Warning Signs
85
Addressable Audio & Visual
89
Hazardous Area - Intrinsically Safe
92
Hazardous Area- Flameproof Equipment
93
Cable
2 Core TPS Cable
94
Ancillaries
Electro-Magnetic Door Holders
97
Power Supplies
101
Batteries103
Test Equipment
103
Ancillary Equipment
105
Contact Page
107
www.ampac.net
www.ampac.net
4
5
Fire Control Panels
ZoneSense DH4 Conventional
Specifications
Power Supply
Mains Supply voltage
Nom. Operating voltage
Power Supply Current
Quiescent Current
Operating Temperature
Relative Humidity
Zone Detection Circuit
No of Zones
Zone Monitoring
Zone Quiescent Current
No of Detectors/Circuits
End Of Line (EOL)
Max Cable Length
Outputs Available
Alarm Outputs (monitored)
Door Holder outputs (monitored)
Fire Output Relay (voltage free)
Fault Output Relay (voltage free)
Auxiliary DC Output
204 – 264 VAC @ 47 – 63Hz
27 VDC
1.6 A (max)
20 mA (without Door Holder)
-5° to +55° C (no icing)
25% - 75% (non condensing)
Four (4) x 2-wire system
Open and Short circuit
4mA, 10uF EOL
40 (max)
10uF EOL
3km (Based on cable resistive and capacitive
values of 50Ω and 1uF respectively)
Open Collector, 250mA (2 O/P’s available) 10KΩ EOL
Open Collector, 250mA (2 O/P’s available) 10KΩ EOL
NO, C, NC Contact rating: 1A @ 30VDC
NO, C, NC Contact rating: 1A @ 30VDC
150mA @ 24VDC
Miscellaneous Features
Class Change Input
Alert Input
Battery Monitoring
Non-Latching, switched -ve
Non-Latching, switched -ve
4 Way DIP switch array (factory set to “OFF”)
Mechanical
Packed
Material
Weight Packed excluding batteries
H 310mm x W 500mm x D 110mm
ABS Cabinet
ABS/Blend High Impact
Finish ABS Light Grey
H 300 x W 360 x D 100
3kg
Metal Cabinet
1.2mm Mild Steel
Metal Oyster Matt Ripple
H 300 x W 360 x D 100
5.2kg
Product Overview
The ZoneSense DH4 Control Panel is a simple and low cost 4 zone panel. It is an ideal fire panel for any small residential applications (not requiring brigade monitoring) or can also be used as a door holder control panel. Each of the 4 zones can be
connected up to 40 x high quality commercial grade conventional fire detectors to deliver a high quality detection & alarm
system. It is possible to use the ZoneSense panel in ‘Mains only’ option mode which eliminates the need to connect back up
batteries. Both ABS and Metal versions are available.
••
••
••
••
••
••
••
Dual Door Holder Outputs
Mains Only Mode
Low Quiescent Current
Walk Test Facility
Alert Input
Up to 40 Conventional detectors per Zone
Available in ABS (BX1) and Metal (BX10) cabinet versions
www.ampac.net
Item Numbers
ZoneSense DH4 ABS (BX1) excl Batteries
ZoneSense DH4 METAL (BX10) excl Batteries
Metal BX10 Surround
2250-4200
2250-4250
ENC3016-A
www.ampac.net
6
7
Fire Control Panels
ZoneSense PLUS Conventional
Specifications
Power Supply
Mains Supply voltage
Nom. Operating voltage
Power Supply Current
Quiescent Current
Zone Detection Circuit
No of Zones
Zone Monitoring
Zone Quiescent Current
No of Detectors/Circuits
End Of Line Value (EOL)
Max Cable Length
respectively)
Product Overview
The Ampac ZoneSense PLUS Fire Alarm Control Panel is a versatile four or eight zone conventional panel. The user friendly
navigation system provides simple operation during an emergency while also enabling complex cause and effect programming to be undertaken.
A range of modular panel add-on kits allows the panel to be professionally tailored to the requirements of each installation.
This means small conventional panels can now be used in a wider range of applications.
ZoneSense PLUS offers you complete control. The panel can be easily upgraded and programmed on site. ZoneSense PLUS is
approved to AS4428 and is available in ABS (BX1) or metal cabinets (BX20) with either four (4) or eight (8) zone conventional
detection circuits
••
••
••
••
••
Complies with AS4428.1
Available in 4 Zone or 8 Zone Panels
Up to 40 Conventional detectors per zone
RS485 port supports a range of Add-on modules
vailable in ABS (BX1) and Metal (BX20) cabinet versions
www.ampac.net
204 – 264 VAC @ 47 – 63Hz
27 VDC
2 A (max)
40.5 mA (min)
Four (4) or Eight (8) x 2-wire system
Open and Short circuit
4mA, 10uF EOL
40 (max)
3K3Ω (default), 4K7Ω, 6K8Ω, 10KΩ and 10uF
3km (Based on cable resistive and capacitive values of 50Ω and 1uF
Outputs
Comms Output
EXT Bell Output (monitored)
Warning Sys Output (monitored)
ACF Output (monitored)
ASE Output (monitored)
Reset/Buzzer
Fire Alarm Output Relay (voltage free)
Fault Output Relay (voltage free)
Auxiliary DC Output (monitored)
RS485 (4 and 8 zone only)
1A (max) 10KΩ EOL
1A (max) 10KΩ EOL
1A (max) 10KΩ EOL
1A (max) 10KΩ EOL
Output Open Collector, 40mA 15sec pulse
NO, C, NC. Contact rating: 1A @ 30VDC
NO, C, NC. Contact rating: 1A @ 30VDC
500mA @ 24VDC10KΩ EOL
Environmental
Operating Temperature
Relative Humidity
-5° to +55° C (no icing)
25% - 75% (non condensing)
Mechanical Material
Finish
Weight packed ex Batteries
Dimensions (mm)
ABS
Metal
Ancillary ABS Cabinet ABS/Blend High Impact
ABS Light Grey
3kg
Metal Cabinet
1.2mm Mild Steel
Metal Oyster Matt Ripple
8.5kg
300 H x 360 W x 100 D
500 H x 405 W x 145 D
250 H x 405 W x 145 D
Item Numbers
ZoneSense PLUS 4 Zone SPX1 Inc Batteries
ZoneSense PLUS SP1x OWS25W Inc Batteries ZoneSense PLUS 4 Zone SP1x OWS50W Inc Batteries ZoneSense PLUS 8 Zone SP1X Inc Batteries
ZonesSense PLUS 8 Zone SP1X OWS25W Inc Batteries ZoneSense PLUS 8 Zone SP1X OAWS50W Inc Batteries
Ancillary Cabinet
2553-0410
2553-0410-1100
2553-0410-1200
2553-0810
2553-0810-1100
2553-0810-1200
4210-0040
www.ampac.net
8
9
Fire Control Panels
ZoneSense PLUS AR Conventional
Product Overview
The ZoneSense PLUS AR (Agent Release) Panel is a dedicated panel for agent release systems. Housed in a metal cabinet,
the ZoneSense PLUS AR is available in either four (4) or eight (8) zones. Based on a ZoneSense PLUS Fire Alarm Control Panel
(FACP), the AR version is fitted with an Agent Release Panel Add-on (control card and termination board) and a dual action yellow manual call point as standard. The Agent Release panel add-on option is factory set.
••
••
••
••
••
••
Dedicated Agent Release system - purpose built with a host of ancillary products to suit
Comprehensive system status – the AR panel includes a number of system status indicators that facilitates ease of operation and maintenance
Local Control Station with control and indication – mimics full status of the Agent Release panel. An outdoor version of this product is available
User interface and operation based around Industry Fire Emergency procedures – ensures that the system installed is intuitive and easy to use
Dual action Manual Call Point – the yellow MCP is a break glass type and requires a dual action to be activated i.e. lift the protective transparent cover and break the glass
Agent Release Panel is compliant with AS4214
www.ampac.net
Specifications
Power Supply
Mains Supply voltage
Nom. Operating voltage
Power Supply Current
Quiescent Current
204 – 264 VAC @ 47 – 63Hz
27 VDC
2 A (max)
40.5 mA (min)
Zone Detection
No of Zones
Zone Monitoring
Zone Quiescent Current
No. of Detectors per Zone
Zone End Of Line Value
4 or 8, 2 Wire
Open and Short circuit
4mA, 10uF EOL
40 max
3K3Ω (default), 4K7Ω, 6K8Ω 10KΩ and 10uF
Outputs
EXT Bell Output
Warning Sys Output
ACF Output
ASE Output
Fire Alarm Output Relay
Fault Output Relay
Auxiliary DC Output
Reset/Buzzer Output
500mA (max) 10KΩ EOL monitored
500mA (max) 10KΩ EOL monitored
500mA (max) 10KΩ EOL monitored
500mA (max) 10KΩ EOL monitored
NO, C, NC Contact: 1A @ 30VDC
NO, C, NC Contact rating: 1A @ 30VDC
500mA @ 24VDC 10KΩ EOL monitored
Open Collector, 40mA 15sec pulse
Environmental
Comms Output
Operating Temperature Relative Humidity
RS485
-5° to +55° C
25% - 75% non condensing
Dedicated Agent Release Inputs and Outputs
Pressure Switch Input
Low Pressure Switch Input
Interlock Input
Gas Fired Output
System Inoperative Output
Stage 1 Relay Output
Stage 1 Monitored Output
Stage 2 Relay Output
Stage 2Monitored Output
Release Initial Agent Output
Release Reserve Agent Output
Monitored Input
Monitored Input
Monitored Input
Volt Free Changeover [email protected]
Volt Free Changeover [email protected]
Volt Free Changeover [email protected]
1Amp 10KΩ EOL (Voltage reversal)
Volt Free Changeover [email protected]
1Amp 10KΩ EOL (Voltage reversal)
Monitored current limited 2A max
Monitored current limited 2A max
Mechanical
Material
1.2mm Mild Steel
FinishRipple
Cabinet Dimensions (mm)
500(H) x 405(W) x 150(D)
Ancillary Cabinet Dimensions (mm)
250(H) x 405(W) x 145(D)
Weight packed ex Batteries
Metal 8.5kg
Item Numbers
ZoneSense PLUS 4 Zone SP1X Agent Release Inc Batteries
ZoneSense PLUS 8 Zone SP1X Agent Release Inc Batteries 2553-0410-0100
2553-0810-0100
www.ampac.net
10 Fire Control Panels
LoopSense Intelligent
11
Specifications
Power Supply (General)
Dimensions Weight Power Supply
Maximum Battery Capacity
Input Voltage Output Voltage Battery Discharged Cut Off Voltage
Material
Finish SP1XP8X
00H x 405W x 150Dmm
845H x 515W x 175Dmm
9kg
15kg
3 Amp PSU version
5 Amp PSU version
26Ah
40.0Ah
204 - 264VAC
27.5VDC +/- 0.1VDC
21VDC
21VDC
1.2 mm steel
Surf Mist Ripple
Loop
Quiescent Current(1 Loop Panel)
Quiescent Current (2 Loop Panel)
Loop Capacity
Max No of Detectors/Devices per Loop
Cabling Requirements Fault supervision 115mA
135mA
500mA max
126
2 core 1.5 to 2.5 mm2
O/C, S/C, overcurrent
Outputs/Inputs
Outputs (SupervisedProgrammale)
Relay outputs (Programmable)
Open Collector Output (Programmable)
Auxiliary VDC(Programmable)
Inputs (Programmable)
4 x 24VDC @ 500mA max
3 x Voltage free 24VDC @ 1A
2 x 30mA
2 x 24VDC @ 500mA
4 x O/C, S/C, 10K EOL
Communications Port
Internal to LoopSense External to LoopSense Printer port PC Interfacing RS485
RS485
RS232 or Parallel
RS232 or USB 2.0
Environmental
Operating temperature
Relative humidity
IP rating
-5°C to +55°C (no icing)
25% to 75% (non condensing)
IP30
Product Overview
LoopSense is an Intelligent Analogue Addressable Fire Alarm Control Panel. Available in one or two loops, the LoopSense
comes packed with options and features that facilitate flexibility, ease of installation and commissioning.
••
••
••
••
••
••
••
••
••
Complies to AS7240-2:2004, AS7240-4:2004, and AS4428-3:2010 -ActivFire listed
Clear back-lit 240 x 64 graphic LCD
500mA loop current
Advanced balanced loop design for noise rejection
Auto learn facility
Supports extensive range of Add Ons, including the SmartTerminal Repeater
User friendly Loopmaster programming software tool
Laptop connection using USB2.0 or RS232 serial port
Available in ABS (BX1) and Metal (BX10) cabinet versions
www.ampac.net
Item Numbers
LoopSense 1 Loop 3A SP1X
LoopSense 1 loop 6A SP8X
LoopSense 2 Loop 3A SP1X
LoopSense 2 Loop 6A SP8X
LoopSense 1 Loop 3A SP1X OWS25
LoopSense 2 Loop 3A SP1X OWS25
LoopSense 1 Loop 3A SP1X OWS50
LoopSense 1 Loop 6A SP8X OWS50
LoopSense 2 Loop 6A SP8X OWS50
8251-0210
8251-0210
8251-0113
8251-0213
8251-0110-1100
8251-0210-1100
8251-0110-1200
8251-0213-1200
8251-0213-1200
www.ampac.net
12 Fire Control Panels
FireFinder PLUS Intelligent
13
Specifications
Power Supply (Gereral)
Cabinet SP1X
Power Supply 5A PSU version
Input Voltage
195 - 264VAC Protection 2 Amp 3AG Output Current 5.6 Amps
Charger Current 1.25A Maximum Battery Capacity:
26Ahr
Charger Output Voltage:
27.5 +/- 0.1VDC
Battery Type:
2 x 12V Sealed Lead Acid
Discharge Cut-off voltage: 21VDC
Loop
Panel Quiescent Current
1 Loop
Additional Loops (even)
Additional Loops (odd)
Loop Capacity Max No of Devices per Loop
Cabling Requirements
Fault supervision Inputs/Outputs
Outputs (Programmable)
Relay outputs (Programmable)
Auxiliary Power Outputs
Inputs (Programmable)
Product Overview
FireFinder Plus is an Intelligent Analogue Addressable Fire Alarm Control Panel that is available in 1 to 8 loop panel options.
The FireFinder Plus is suitable for medium to large sized fire detection systems and is compatible with Apollo XP95, Discovery
and Series 90 detectors. Powerful and flexible programming is achieved via AMPAC’s configuration tool ConfigManager Plus
which includes many dedicated pre-engineered programming functions. Simple system programming is easily achieved via
the front panel. FireFinder Plus is configurable as a peer to peer network up to 100 panels/nodes with a maximum of 150
Loops.
••
••
••
••
••
••
••
••
••
••
••
••
Fully approved to AS2740-2 , AS720-4 and AS4428.3:2010
Fully Expandable 1 to 8 Loop Fire Alarm Control Panel
Large Graphic (240 x 64 pixel) Display
500mA Loop Current
4 Programmable Monitored Inputs
4 Programmable Monitored Outputs
5 Programmable Relays
2 Auxiliary Power Outputs
Programmable via front panel
Networkable
Supports High Level Graphics Interface
Supports a Range of Panel Add-ons
www.ampac.net
220mA
+40mA for each Loop
+75mA for each Loop
500mA max per Loop
126
2 core 1.5 to 2.5mm²
O/C, S/C, Over current
4 x 24VDC @ 1 Max, 10K EOL
5 x Voltage Free - [email protected]
2 x 24VDC @ 500mA
4 x O/C, S/C, 10K EOL
Communication
Comms External to FACP
Comms Printer port
Comms PC Interface
RS485
RS232 or Parallel
RS232 or USB 2.0
Environmental
Temperature
Humidity
-5ºC to + 40ºC
25% to 95% (non-condensing)
Mechanical
Material
Colour/Finish
Dimensions (mm)
SP1M
SP1X
SP8X
SP16X
IP Rating
Cabinet SP8X/SP16X
5A PSU / 22A PSU Version
195 - 264VAC
2 Amp 3AG (5A PSU)/
5 Amp 3AG (18A PSU)
22 Amp
1.25A / 3A
40Ahr
1.2mm Mild Steel
Surf Mist Ripple
500H x 405W x 150D
500H x 405W x 150D
845H x 518.5W x 173D
1200H x 625X x 240D
IP30 (Indoor Use Only) Item Numbers
(Addressable) FireFinder PLUS 1 Loop 5A SP1X
FireFinder PLUS 1 Loop 5A Agent SP1
FireFinder PLUS 1 Loop OWS25 5A SP1
FireFinder PLUS 1 Loop OWS50 5A SP1
FireFinder PLUS 1 Loop 5A SP8X
FireFinder PLUS 1 Loop Agent 5A SP8
FIREFINDER+ 1 Loop AGENT 5A SP8
FIREFINDER+ 1 Loop OWS50 5A SP8
8651-0110
8651-0110-0100
8651-0110-1100
8651-0110-1200
8651-0113
8651-0113-0100
8651-0113-0700
8651-0113-1200
(Conventional)
FireFinder PLUS 8 Zone 5A SP1X
FireFinder PLUS 8 Zone OWS25 5A SP1
FireFinder PLUS 8 Zone OWS50 5A SP1
8653-0810
8653-0810-1100
8653-0810-1200
www.ampac.net
14 Fire Control Panels
FireFinder Intelligent
Product Overview
FireFinder is a state of the art multi microprocessor controlled Intelligent Fire Alarm Control Panel. Modular in design, the
FireFinder provides flexibility and versatility that can be configured to operate with both intelligent analogue addressable and
conventional devices in the one system.
Available in single loop or multiple loop configurations, the FireFinder supports the leading Apollo XP95 and Discovery detector protocols. The Ampac ConfigManager software tools provide a powerful combination with the FireFinder to configure the
system operational and functional characteristics of an installation. Enhanced networking capabilities offer the user extended
applications with FireFinder incorporating a Master/ Slave Fire control panel arrangement, true Peer to Peer systems, data
gathering panels and SmartGraphics a PC based application for the supervision, monitoring and control of
larger fire management systems.
••
••
••
••
••
••
••
••
••
••
••
••
••
Complies with AS4428.1 and AS1603.4
Clear back-lit 40 character 8 line LCD display
Programming options via the front panel or laptop computer
Remote system interrogation and diagnostics
Extensive Alarm Management resources
Self Auto Learn capabilities
Day Night sensitivity settings
Versatile multi processor architecture
Event log and printer options
SPOT – Single Person Operation Test
Flexible modular expansion and panel Add Ons
Optional 32, 64, 96 & 128 zone indicators
SmartTerminal repeater options
www.ampac.net
15
Specifications
Power Supply
Finish
Material
Input Voltage
Output Voltage Output Current Battery Type Arch White Ripple
1.2mm steel
85 to 264Vac (47-63Hz)
27Vdc
2A, 5.6A or 18A
2 x 12V SLA batteries
Loop
Quiescent Current Devices per Loop Loop Current Devices per Zone Conventional Zone EOL
Cable (Loop and Conventional Circut)
240mA (min 1 Loop no load)
126
250mA
40
3K3
2 core 1.5 to 2.5mm²
Outputs/Inputs
Outputs
Bell 1
Bell 2
Plant Monitored
Plant Un-Monitored
Warn Sys Monitored
Warn Sys Un-Monitored
Fault Monitored
Fault Un-Monitored
Isolate
Alarm
Valve Monitor
Batt Fail (normally energised)
Battery Output
Aux Power Output 1
Aux Power Output 1 EV40 use
Aux Power Output 2
DBA/MCP
2 Amp Fused
2 Amp Fused
1 Amp Fused, 10K EOL
1 Amp voltage free contact
1 Amp Fused, 10K EOL
1 Amp voltage free contact
1 Amp Fused, 10K EOL
1 Amp voltage free contact
1 Amp voltage free contact
1 Amp voltage free contact
1 Amp voltage free contact
1 Amp voltage free contact
Protected
1 Amp Fused
3 Amp Fused
1 Amp Fused
Monitored 10K EOL
Environmental
Temperature
Humidity
IP Rating
5ºC to + 55ºC
25% to 75% (non-condensing)
IP51
Item Numbers
(Conventional)
FireFinder SP1X 16 Zone AS4428 FireFinder SP1X 16 Zone ASE
FireFinder SP1X 16Zone OWS25
FireFinder SP1X 16Zone OWS50
FireFinder SP1X 16Zone
(Addressable)
FireFinder SP1X 1Loop AS4428
FireFinder SP1X 1Loop ASE
FireFinder SP1X 1Loop OWS50
8550-1150
8550-1250
8550-1450-1100
8550-1530-1200
8550-1151
8550-1100
8550-1200
8550-1440-1200
www.ampac.net
16 Fire Control Panels
17
Add Ons
(*FF+ - FireFinder PLUS compatable, *FF - FireFinder compatable, *LS - LoopSense compatable, *ZSP- ZoneSense PLUS compatable)
Analogue Loop Upgrade Kit *FF+
SmartTerminal Repeater *FF+ *LS *FF
•• This kit adds an intelligent analogue loop to the FireFinder PLUS Control Panel
•• For an odd numbered loop upgrade the kit consists of an I/O CPU module, cable and termination card
•• An even numbered loop upgrade consists of an I/O CPU module and cable
The SmartTerminal has been designed to display the status of and provide limited
controls for the FireFinder Plus and LoopSense Fire Alarm Control Panels (FACP) in m
Voltage
Quiescent current
Loop current
Operating temperature
Relative humidity
Weight
24 VDC
40 mA
500 mA max.
-5°C to +55°C (no icing)
0 to 95% (non condensing)
200 grams
FireFinder Plus Slave CPU Board
FireFinder Plus Term Board FireFinder
Terminal Repeater
8610-0001
8610-0002
Operating Voltage
Internal (24Vdc)
18 – 27 V DC
External (240Vac)
204 - 264VAC
Quiescent Current 12.5mA (backlight off, buzzer off )
Maximum Current
43.8mA (backlight on, buzzer on)
Temperature
-5ºC to + 55ºC
Humidity
25% to 75% (non-condensing)
Cabling Requirements
2 core 1.5 to 2.5mm²
External Power Supply
1.8A plus 400mA Battery Charging
(4350-0005 only)
Battery Size
3.2AHr
(4350-0005 only)
MaterialABS
Dimensions
BX05 195 (H) x 325 (W) x 50 (D)
BX1 300 (H) x 360 (W) x 100 (D)
Loop Module Expansion Kit *FF+
••
••
Expands the capacity of the FireFinder to accommodate a further four loops, 64 conventional zones, four I/O modules or any combination of the above
Requires a main controller board
Voltage
Quiescent current
Operating temperature
Relative humidity
Weight
24 VDC
5 mA
-5°C to +55°C (no icing)
0 to 95% (non condensing)
110 grams
FireFinder Plus Loop Expansion Board
4350-0001
4350-0002
4350-0003
FireFinder Plus and LoopSense
FF+/LS SmartTerminal (BX1 enclosure)
FF+/LS SmartTerminal inc PSU (BX1 enclosure)
FF+/LS SmartTerminal (BX05 slimline enclosure)
Wall Mount Surround
4350-0004
4350-0005
4350-0006
4210-0046
8610-0003
2 Wire Network Interface Board *FF+
High Level Interface Expander or Port Expander Board *FF+ *LS *FF
••
••
••
••
••
••
••
••
••
••
••
Supports Redundant Network, with Isolated Network In and Out Ports
Up to 99 Network Nodes
115200 Baud Rate
Distance Between Nodes 1.2km
Uses Industry Standard RS485
Diagnostic LEDs
Voltage
27 VDC
Quiescent Current
41 mA
ProtocolRS485
Max distance (between NICs)
1.2km
Cable requirements
2 Core Screened Fire Resistant
Operating temperature
-5°C to +40°C
Relative humidity
0 to 95% (non condensing)
Network Interface Card 2 Wire
www.ampac.net
LoopSense/FireFinder Plus
Terminal Repeater
FireFinder
FF SmartTerminal (BX1 enclosure)
FF SmartTerminal inc PSU (BX1 enclosure)
FF SmartTerminal (BX05 slimline enclosure)
4210-0006
Building Management
Paging system
Nurse Call Systems
SmartGraphics
MODBUS
Voltage
Quiescent current
Max current
Relay contact rating
Operating temperature
Relative humidity
Weight High Level Interafce - Factory Fitted
High Level Interface - Add-On Kit
24 VDC
2.4 mA
80 mA
1 amp at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
130 grams
159-0268
4310-0080
www.ampac.net
18 Fire Control Panels
19
Add Ons
8 Way Relay Board *FF+ *LS *ZSP
8-way Sounder Board *FF+ *LS *ZSP
••
••
••
••
••
••
Provides volt free change over contacts
8 relay outputs per board
Remote version available – DIN Mount chassis
Remote version communication via RS485 serial link
Voltage
Quiescent current
Max current
Relay contact rating
Operating temperature
Relative humidity
Weight
Provides 8 monitored switched 24 VDC outputs per board
Max 1 per FireFinder PLUS
Voltage
Quiescent current
Max current
Output rating (ea)
EOL Monitoring Value
Operating temperature
Relative humidity
Weight
24 VDC
2.4 mA
80 mA
3 amp at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
130 grams
24 VDC
5.6 mA
26 mA
500 mA at 24 VDC
10k Ω
-5°C to +55°C (no icing)
0 to 95% (non condensing)
100 grams
Sounder Board
Relay Board
Relay Board (Remote)
4310-0060
4310-0050
4310-0055
Fire Fan Module *FF+ *LS *FF *ZSP
8 Zone Conventional Board *FF+ *LS
•• Supports up to eight conventional zones
•• Selectable end of line device 3K3, 4K7, 6K8, 10K or 10µF capacitor
•• Supports head removal requirement on each zone
•• Supports up to 40 conventional devices per zone circuit (ORBIS/Series 65)
•• Programmable latching and non-latching (self-resetting) input on each zone circuit
Voltage
Quiescent current
Alarm current
Operating temperature
Relative humidity
Size
Weight
24 VDC
15mA (including capacitive EOL
current) plus device current
43mA (one circuit in alarm)
-5°C to +55°C (no icing)
0 to 95% (non condensing)
72.5 x 155mm
120 grams
8 Zone Conventional Board
••
••
••
••
••
••
••
Four (4) Controls per Module
Status indication for Run / Fault / Stop
Controls for On / Auto / Off
Audible and visual feedback of button press
Built in Plant Trip Reset
Supports 3, 4 and 5 Wire Connections
Available in Hard Wired or loop driven versions
Operating Voltage
27VDC
Dimensions
Controller Card
Fits standard Panel Cut-Out
Termination Board
155mm x 72mm
Contact Rating
1 @ 24VDC
ApprovalAS1668
Hard Wired (Includes controls and termination board)
Loop Driven (Controls only)
4310-0021
4310-0071
4310-0082
32 Zone Indicator Card *FF+ *LS
••
••
••
••
••
16 way Input Board *FF+ *LS *ZS
••
••
••
••
Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc
16 inputs per board
Inputs map to relays or indicators
Programmed via the LoopMaster
Voltage
Quiescent current
Max current
Output rating
Operating temperature
Relative humidity
Weight
Input Board
www.ampac.net
24 VDC
2.6 mA
45 mA
0.5 amp at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
120 grams
Provides 32 Zone LED’s capable of indicating zone Fire, Disabled, Fault and Dependency B.
Suitable for use with the FireFinder range of FACP’s
Suitable for use with LoopSense FACP
Customisable zone identification label
Fully programmable via LoopMaster
Voltage
Quiescent current
Max current
Output rating
Operating temperature
Relative humidity
Weight
4310-0040
32 Zone Indicator Card
27 VDC
3.6 mA
8mA
0.5 amp at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
100 grams
4310-0086
www.ampac.net
20 Fire Control Panels
21
Add Ons
Zone Disable and Indicator Module *FF+ *LS *FF
Agent Release Module *FF+ *LS *FF *ZSP
••
••
••
••
••
••
••
••
••
••
Provides 8 Programmable Zone Disable Switches
Provides 8 Status LEDs
Customisable Switch Identification Label
Voltage27VDC
Quiescent current
3.6 mA
Max current
8 mA
CommunicationRS485
Operating temperature
-5°C to +55°C (no icing)
Relative humidity
0 to 95% (non condensing)
Weight
100 grams
Zone Disable & Indicator Module
4310-0087
8 Switch/Indicator Module *FF+ *LS *ZSP
••
••
••
••
••
8 x Push Button On / Off switches
Controls and Monitors solenoid test switches, manual shutdowns and etc
Programmable via the ZoneSense PLUS front panel
Programmable via ConfigManager for the FireFinder range of panels
Programmable via LoopMaster for the LoopSense range of panels
Voltage
Quiescent current
Max current
Operating temperature
Relative Humidity
Weight
24 VDC
3.6 mA
8 mA
-5°C to 55°C (no icing)
0 to 95% (non condensing)
100 grams
Switch/Indicator Card
Network Interface Card (NIC)- 2 Wire Network *FF
24 VDC
9 mA
52 mA
1 amp at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
110 grams
Fire Brigade Board
4310-0070
Agent Release- Local Control Station *FF+ *LS *FF *ZSP
••
••
••
••
••
••
Remote Agent release LCS
Complies with AS4214
For use only with Agent release Module 4310-0011
Double Action manual Agent release facility
Toggle between initial & reserve agent
Can install up to 8 x LCSs per panel
Local Control Station
www.ampac.net
4310-0011
4310-0030
Provides common outputs for connection to fire brigade signalling equipment
5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm
Voltage
Quiescent current
Max current
Output rating
Operating temperature
Relative humidity
Weight
Pressure Switch Input
Monitored Input
Low Pressure Switch Input
Monitored Input
Interlock Input
Monitored Input
Gas Fired Output
Volt Free Changeover
[email protected]
System Inoperative Output
Volt Free Changeover
[email protected]
Stage 1 Output
Monitored
Stage 2 Output
Monitored
Release Initial Agent Output
Monitored current limited
2A max
Release Reserve Agent Output
Monitored current limited
2A max
System Capacity
FireFinder
8 Maximum
LoopSense
8 Maximum
ZoneSense Plus
1 Maximum
Agent Release Module
Fire Brigade Board *LS ZSP
••
••
ompliance with AS4214
C
Controls & Monitors Agent release system
Outputs for warning signs & activation devices
Inputs for signals from pressure switches & valves
Serial connection to Agent release (LCS) Local control Station
Programmed via the FACP front panel
Location or title descriptor label
4310-0019
•• The NIC gives the FireFinder network capabilities via the RS422 communications port
•• Provides an additional RS232 communications port when connected to Controller Interface Card (CIC)
•• High level interface for Building Management or ModBus protocol for
SmartGraphics and PLCs
•• The NIC can be isolated from other network devices
•• Loop In/Loop Out for easy installation
Voltage
Quiescent Current
Available Ports
Max distance (between NICs)
Cable requirements
Operating temperature
Relative humidity
Weight
24 VDC
65 mA
RS422 – network
RS232 – serial comms
1.2km
RS485 – 1 pair twisted/screened
RS232 – 1 pair twisted/screened
-5°C to +55°C (no icing)
0 to 95% (non condensing)
225 grams
SP1X159-0258
SP8X159-0259
SP16X/Rack159-0260
Add-On Kit
4310-0079
www.ampac.net
22 Fire Control Panels
23
Add Ons
Module Expansion Kit for Modules (5-8) *FF
8-Way 5A Relay *FF
••
••
••
••
E xpands the capacity of the FireFinder to accommodate a further four loops, 64
conventional zones, four I/O modules or any combination of the above
Requires a main controller board
Voltage
Quiescent current
Operating temperature
Relative humidity
Weight
24 VDC
5 mA
-5°C to +55°C (no icing)
0 to 95% (non condensing)
110 grams
SP8X Loop Module Expansion Kit
SP16x/Rack Loop Module Expansion Kit
••
159-0012
159-0022
Each upgrade panel add-on offers 8 voltage free relay outputs. Each output is rated at 5 amps, 24 VDC
Each relay has a single normally open/close volt-free contact extended to a wireprotected screw terminal
The standard 8-way relay upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O module
Voltage
Quiescent current
Operating temperature
Relative Humidity
Weight
24 VDC
5 mA (Serial Relay Board)
-5°C to 55°C (no icing)
0 to 95% (non condensing)
190 grams
SPX 8-Way 5A O/P Relay
Rack 8-Way 5A O/P Relay
159-0013
159-0015
8 Way Serial Relay Output Board *FF
••
••
••
Each serial relay output board offers 8 voltage free relay outputs, each rated at 5 amps, 24 VDC
Each relay has a single normally open/close volt-free contact extended to a wireprotected screw terminal
The serial 8-way relay is driven directly from the main controller board
Voltage
Quiescent current
Relay output current
Operating temperature
Relative humidity
Weight
Rack 8 Way Serial Relay Output Board
SPX8 8 Way Serial Relay Output Board
24 VDC
5 mA
5 Amps at 24 VDC
-5°C to +55°C (no icing)
0 to 95% (non condensing)
190 grams
159-0072
159-0079
8 Way Bell Monitor Board *FF
••
••
••
The 8-Way Bell Monitor has 8 switched 24V DC sounder outputs
The outputs are programmable and monitored for open or short circuit
The board connects directly to the main controller board
Voltage
Quiescent current
Max sounder output current
Max output current
Operating temperature
Relative humidity
Weight
24 VDC
20 mA
1 Amp each
4 Amps per board
-5°C to +55°C (no icing)
0 to 95% (non condensing)
250 grams
8 Way Bell Monitor Board
159-0071
4 Plus 4 Bell Monitor *FF
••
••
••
The 4 Plus 4 Bell Monitor has screw terminals for 4 voltage free contacts and 4 switched 24V DC sounder outputs
The outputs are programmable and monitored for open or short circuit
The board connects directly to the main controller board
Voltage
Quiescent Current
Available Ports
Max distance (between NICs)
Cable requirements
Operating temperature
Relative humidity
Weight
4 Plus 4 Bell Monitor Board
www.ampac.net
RS422 RS232
24 VDC
65 mA
Network
Serial comms
1.2km
2 pair twisted/screened
1 pair twisted/screened
-5°C to +55°C (no icing)
0 to 95% (non condensing)
225 grams
159-0069
16 Way Conventional Zone Card *FF
••
••
••
••
Adds 16 conventional Alarm Zone Circuits
Kit consists of an I/O CPU module, cable and 16 zone termination card
Supports up to 40 conventional detectors (Series 60, Series 65 or Orbis) per zone
Fixed 3K3 End-Of-Line device
Voltage
Quiescent current
Operating temperature
Relative humidity
Weight
SP8X/SP16X 16 Way Conventional Zone Card
Rack 16 Way Conventional Zone Card
24 VDC
145 mA
-5°C to +55°C (no icing)
0 to 95% (non condensing)
185 grams
159-0005
159-0006
www.ampac.net
24 Fire Control Panels
25
Add Ons
16 Opto Inputs *FF
Panel Mounted LED Indicators *FF
••
••
••
•• Provide flexibility to include additional LED indicators to the FireFinder SP1X and SP8X
•• Available in three versions:
•• – 32 zone alarm only indication (red)
•• – 16 zone alarm/fault indication (red/amber)
•• – 32 zone general indication (amber)
•• Serial connection to the FireFinder panel
•• Simple clip installation
•• Indicators remain illuminated until reset by the panel
•• Indicators are tested by the FireFinder panel’s lamp test control
The Opto Input panel add-on provides 16 programmable electrically isolated inputs to the FACP
The input from a third party source should be a volt-free contact
This upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O Interconnect Module
Voltage
Quiescent current
Operating temperature
Relative Humidity
Weight
24 VDC
5 mA
-5°C to 55°C (no icing)
0 to 95% (non condensing)
185 grams
SP 16 Opto Input
Rack 16 Opto Input
159-0010
159-0011
Voltage
Quiescent current
Max current
Operating temperature
Relative humidity
Weight
27 VDC
30 mA
40 mA
-5°C to +55°C (no icing)
0 to 95% (non condensing)
100 grams
FireFinder SP1X 32 Zone Alarm Only Indication (Red)
FireFinder SP8X 32 Zone Alarm Only Indication (Red)
FireFinder SP1X 16 Zone Alarm/Fault Indication (Red/Amber)
FireFinder SP8X 16 Zone Alarm/Fault Indication (Red/Amber)
FireFinder SP1X 32 Zone General Indication (Amber)
FireFinder SP8X 32 Zone General Indication (Amber)
159-0106
159-0089
159-0107
159-0108
159-0123
159-0124
Remote Mounted LED Indicators *FF
••
••
••
••
The remote LED indicator boards provide facilities to mimic the FireFinder zone LEDs and switches
Connects to the RS485 communications bus via the controller interface card
Allows the custom design of geographic site layout mimics
Each termination board connects up to 32 zone LEDs – 31 boards maximum – total 992 zone indications
Voltage
Quiescent current
Max current
Communication mode
Baud rate
Communication cable
No. of boards
No. of zones
Buzzer external max current
On board status indication
Common inputs
Operating temperature
Relative humidity
FireFinder LED Mimic Driver 32 Way
Mimic Output Termination Board
FireFinder 16 Zone LED Display Board
www.ampac.net
27 VDC
8 mA max
100 mA
RS485
19200 max
1 x pair twisted and screened
31 max
992 zones max
20 mA
Power on – green
Normal – green
Fault – yellow
Reset
Lamp test
Buzzer mute
Bell isolate
Manual evacuate
-5°C to +55°C (no icing)
0 to 95% (non condensing)
Modem *FF
••
••
••
••
••
T he modem allows a remote access to FireFinder
Configuration and application software can be uploaded or downloaded via the
modem
Wireless Modem requires available signal from appropriate network
All modems are AUSTEL approved
Great tool to provide remote support
Voltage
Data transfer rate
Comms to FACP
Operating temperature
Relative Humidity
Weight
159-0145
159-0152
159-0218
SPX Modem
Rack Modem
Wireless Modem
27 VDC
9600 baud max
RS 232
-5°C to 55°C (no icing)
0 to 95% (non condensing)
SP & Rack: 1kg
Wireless: 5kg
159-0033
159-0065
159-0068
www.ampac.net
26 Fire Control Panels
27
Add Ons
Fibre Optic Network Interface *FF
Panel Printer *FF+ *LS *FF
••
••
••
••
••
••
••
••
••
4 versions available to suit your cabling scheme on site
Redundant loop integrity (same as copper)
A network interface card is still required at each FACP node
Maximum distance using ‘Multimode’ (between nodes) up to 5km; using Single
Mode 50km
Supply Voltage
24 VDC
Quiescent Current
80 mA @ 24 VDC
Optical Connector
ST standard
Ports Available
RS422/RS485
Size (mm)
104D x 104W x 25H
Weight280g
Operating Temperature
-20°C to +75°C
Humidity
0 to 95% relative,
non-condensing
FireFinder Fibre Optic Multimode 2 Core
FireFinder Fibre Optic Multimode 1 Core
FireFinder Fibre Optic Single Mode 2 Core
FireFinder Fibre Optic Single Mode 1 Core
The dot matrix printer provides hardcopy activity report
Alarms, faults, isolates and system logs may be printed
3 colour status LED
Self test mode
Easy maintenance for replaceable ribbon cassette and paper roll
Voltage
Quiescent current
Character size
Operating temperature
Relative humidity
Weight
159-0251
159-0252
159-0253
159-0254
5 VDC
1A @ 5 VDC
5 x 7 dots
-5°C to +55°C (no icing)
25 to 95% (non condensing)
380 grams
Printer C/W Mounting plate (Suit Australian White SP1 cabinet)
159-0084
Printer C/W Mounting plate (Suit Australian)
159-0110
Paper Rolls (10)
MIS1981
RibbonMIS1982
Analogue Loop Upgrade Kit *FF
••
••
••
This kit adds an intelligent analogue loop to the FireFinder Control Panel
For an odd numbered loop upgrade the kit consists of an I/O CPU module, cable
and termination card
An even numbered loop upgrade consists of an I/O CPU module and cable
Voltage
Quiescent current
Loop current
Operating temperature
Relative humidity
Weight
24 VDC
40 mA
250 mA max.
-5°C to +55°C (no icing)
0 to 95% (non condensing)
200 grams
1 Loop Upgrade Kit- even numbered loop SP1X
1 Loop Upgrade Kit and Processor- odd numbered loop SP1X
Even No. Loop SP16X/Rack
Even No. Loop SP8
Odd No. Loop SP16X/Rack
www.ampac.net
159-0001
159-0003
159-0002
159-0046
159-0004
www.ampac.net
28 Alarm Systems
29
Standalone Occupant Warning Panel
Item Numbers
EvacU 25W 3A
EvacU 50W 3A
EvacU 100W (2 x 50W) 5A
EvacU 150W (3 x 50W) 10A
EvacU 200W (4 x 50W) 10A
Handheld Microphone
Dual XENON
Dual LED Beacon Shallow Base
Dual LED Beacon Deep Base 6050-0010-1100
6050-0010-1200
6050-0010-1400
6050-0010-1500
6050-0010-0800
6010-0010 OWS
208-0011
4107-1005
4107-1006
8 Zone Indicator Module
••
••
An optional Zone Indicator module is available when more than one emergency zone is programmed and the user requires individual Zone Alarm, Alert, Evacuation and Fault indications
The Zone Module also provides the ability to select and broadcast live speech to individual emergency zones
Quiescent Current
Zone Indicator Module
Product Overview
10.5 mA
6010-0012 OWS
The Ampac EvacU is a fully self-contained Occupant Warning System. Systems are available from 25W up to 200W and
incorporate Ampac’s new range of Class “D” 25N & 50N Amplifiers, Control & Indicating modules and Line splitters.
Up to eight Emergency zones and eight seperate Paging Zones can be configured using the dedicated EvacUwiz
programming tool.
••
••
••
••
••
••
••
••
••
••
Highly Efficient Class D Amplifier Technology
Alert and Evacuation Signals to AS1670.1
Speaker Line Fault Monitoring and Protection
Monitored Strobe Output
Dedicated Emergency Microphone Input
Secondary BGM and PA Analogue Audio Input
False Alarm, System Test and Lock Down Messages
Custom Messages
Up to 8 Emergency Zones
8 Zone Remote Paging console
4 Way Line Splitter
••
••
••
Quiescent Current
100V Line outs
Monitoring EOL
4 Way Line Splitter
Specifications
Power Supply (General)
Power Supply
Battery Size Max
(Battery box may be required)
Cabinet Dimension (mm)
Amplifiers
Amplifiers (Audio)
25W (Max 4)
50W (Max 4)
Amplifiers (Visual)
Strobe Output
Strobes Xenon
Strobes LED
Amplifiers Audio O/P
Emergency Zones
Front Controls (Max 1)
www.ampac.net
A four way Line splitter provides the ability to have a single emergency zone split into 4 separate monitored branches
When a remote paging console is connected each split can be assigned to separate paging zones
Up to two splitters can be connected to a single amplifier with a maximum of four splitters per system
3, 5 or 10Amps @ 24V
17 Ahr
(depends on No. of Amplifiers fitted)
500(H) x 405(W) x 150(D)
10.5mA
4 (Max 100W each to a max of
250W total)
10K – 47K Ω
6010-0013 OWS
8 Zone Paging Console
•• The Remote Paging Console allows up to 8 individual paging zones to be programmed when a combination of more than one amplifier and/or Line
Splitters are included in the system
Current Quiescent / Alarm
20 mA / 1.19 A each
20 mA / 2.39 A each
••
1A Max per Amplifier
Max 8 sets
Max 40 sets
100Vac
Up to 8 max
10.5 mA Quiescent
Number of Zones
BGM Input Source
Cable
Cable Distance
Additionally the RPC includes a back ground music input which can be programmed to each zone via the Remote Paging Console
Quiescent Current
8 Zone Paging Console
5.5 mA
8
3.5mm Audio Jack
CAT5 RJ45 connection
100m
6010-0014 OWS
www.ampac.net
30 Alarm Systems
31
Occupant Warning System Add-Ons
120W OWS
Product Overview
The Ampac Single Zone Occupant Warning System is available with a 25 Watt and 50 Watt audio output with an optional front
panel control. The alert and evacuation signals are compliant to AS1670.1 including voice messages as standard. The speaker
circuit is protected and monitored for shorts and interruptions. Up to three spur lines (branches) are supported. A monitored
strobe output is provided as standard which i supports both xenon and led strobes.
Each audio source (alert / evacuation signals, emergency paging and secondary analogue audio input) has a dedicated
volume control. Three programmable relays are provides, which default to fault, volume control override and test mode.The
optional front panel control has an integrated emergency microphone (and can optionally support a hand held microphone)
The Single Zone Occupant Warning System is suitable for use in Ampac’s FireFinder, LoopSense and ZoneSense Plus Fire Alarm
Control Panels.
••
••
••
••
••
••
••
••
••
••
Supply Voltage 27VDC (nominal)
Max Audio Load
120Watt
Quiescent Current (no audio load, no strobe load)
240mAmps
Max. Current (full audio load, no strobe load)
8Amps
Strobe Output (Xenon)
8 sets (208-0011)
Strobe Output (LED)
40 sets (4107-1005/6)
Audio output voltage
100VAC
Temperature
-20°C to 70°C
Humidity
0-95% non-condensing
Alert / Evac Changeover time (secs)
Alert only, Evac only, 60, 90, 120,
180, 300 or under manual control
Speaker EOL
Nominal 47kΩ 5% 1/3 Watt
THD<0.6%
Signal to Noise Ratio
91dB
Amplifier Dimension(L x W x H)
170mm x 210mm x 85mm
OWS 120W Amplifier
OWS Indicator & Controls
vailable in 25Watt and 50Watt versions
A
Alert and Evacuation Signals to AS1670.1
Speaker Line Monitoring and Protection
Monitored strobe output
Volume Control
Dedicated emergency microphone input
Secondary analogue audio input
Programmable evacuation strategies
False Alarm, System test and Lock Down Messages
Three programmable output relays
25 W& 50W OWS 25watt 250W OWS
Supply Voltage 27VDC (nominal)
Max Audio Load
250Watt
Quiescent Current (no audio load, no strobe load)
380mAmps
Max. Current (full audio load, no strobe load)
17
Strobe Output (Xenon)
8 sets (208-0011)
Strobe Output (LED)
40 sets (4107-1005/6)
Audio output voltage
100VAC
Temperature
-20°C to 70°C
Humidity
0-95% non-condensing
Alert / Evac Changeover time (secs)
Alert only, Evac only, 60, 90, 120, 180, 300 or under manual control
Speaker EOL
Nominal 47kΩ 5% 1/3 Watt
THD<0.6%
Signal to Noise Ratio
91dB
Amplifier Dimension(L x W x H)
300mm x 240mm x 95mm
50watt
Max. Curret (full audio load, no strobe load)
1.19Amps
2.39Amps
Supply Voltage
27VCD (nominal)
Quiescent Current (no audio load, no strobe load)20mamps
Strobe Output (Xenon)
8 sets (208-0011)
Strobe Ouput (LED)
40 sets (4107-1005/6)
Audio Output Voltage
100VAC
Temperature
-20° to +70° C
Humidity
0-95% non-condensing
Alert / Evac Changeover time (secs)
Alert only, Evac only, 60, 90, 120, 180, 300 or under manual control
Speaker EOL
Nominal 47KΩ 5% 1/3 Watt
THD
0.12%
0.89%
Signal to Noise Ratio
80.5dB 82.1dB
Alert Signal
To AS1670.1 including voice
Evacuate Signal
To AS1670.1 including voice
Amplifier (L x W x H)
100 x 77 x 35mm
OWS 50W Amplifier
OWS 25W Amplifier
OWS Indicator & Controls
www.ampac.net
6010-0004
6010-0003
6010-0001
6010-0002
6010-0003
OWS 250W Amplifier
OWS Indicator & Controls
6010-0005
6010-0003
500w OWS
Supply Voltage 240VAC/27VDC (nominal)
Max Audio Load
500Watt
Quiescent Current (no audio load, no strobe load)
500mAmps
Max. Current (full audio load, no strobe load)
35Amps
Strobe Output (Xenon)
8 sets (208-0011)
Strobe Output (LED)
40 sets (4107-1005/6)
Audio output voltage
100VAC
Temperature
-20°C to 70°C
Humidity
0-95% non-condensing
Alert / Evac Changeover time (secs)
Alert only, Evac only, 60, 90, 120, 180, 300 or under manual control
Speaker EOL
Nominal 47kΩ 5% 1/3 Watt
THD<0.5%
Signal to Noise Ratio
90dB
Amplifier Dimension(L x W x H)
83mm x 380mm x 88mm
OWS 500W Amplifier
OWS Indicator & Controls
6010-0006
6010-0003
www.ampac.net
32 Alarm Systems
EV3000 Emergency Control Panel
33
Specifications
Mechanical
Material
Finish
Dimensions
Approvals
Signals
1.6mm Mild Steel
Powder Coated Arch White
10U 700H x 625W x 240D mm (SECP only)
12U 900H x 650W x 290D mm
16U 1200H x 700W x 375D mm
29U 1800H x 700W x 375D mm
SSL – AS2220.1
Compliant with AS1670.4:2004
Electrical
Power Supply
7.5, 13, 19.5 or 26 A mps @ 24 VDC
Communication
RS485 @ 9600 bps
EWS Zones
144 max
EIS Zones
288 max
Paging Console
8 max (recommended)
ECP’s
12 max (recommended)
Visual Warning
Option 1EV3000 Visual Outputs Maximum of 8 pairs per
visual circuit (for Xenon 208-0011). Not T3 compliant
Option 2EV3000 Visual Outputs Maximum of 40 pairs per
visual circuit (for LED 208-0063). T3 compliant
Note: The LED visual pairs require the Ampac 4210-0031 Visual Driver Kit
fitted
Product Overview
The Ampac EV3000 Occupant Warning and Intercom System is designed for the purpose of enabling the orderly evacuation of
occupants, from a building or structure, in the event of an emergency.
The system comprises of two (2) sub-systems. The first being the Occupant Warning System (OWS) and the other the
Occupant Intercom System (OIS). While the Warning and Intercom System have separate controls, they coexist in a Apanel that
is logically presented and aesthetically pleasing.
The Occupant Warning System makes use of speakers strategically placed around the site, to broadcast ALERT, and/or
EVACUATION signals or public address announcements. The OWS may be automatically initiated or manually operated. When
not used in an emergency situation, the EV3000 can broadcast background music and/or general paging announcements.
The Occupant Intercom System (OIS) consists of front panel control at the Emergency Control Panel (ECP) and Warden
Intercom Phones (WIP) that are strategically placed throughout the building. Communication is only possible between the
WIP and ECP.
Item Numbers
EV3000 12U 1 AMP RACK + FIRST
EV3000 16U 1 AMP RACK + FIRST
EV3000 29U 1 AMP RACK + FIRST
EV3000 29U DBL CABINET 1 AMP
EV3000 10U SECP C/W FIRST 8
EV3000 12U SECP C/W FIRST 8
EV3000 16U SECP C/W FIRST 8
EV3000 29U SECP C/W FIRST 8
105-0001
105-0002
105-0003
105-0007
105-0004
105-0005
105-0006
105-0009
For larger sites, multiple control panels may be networked. ABS (BX1) and Metal (BX10) cabinet versions.
••
••
••
••
••
••
••
••
••
••
••
••
Network System
Modular System Design.
Discrete Front Panel Controls.
40, 120, 240 & 480 Watts Amplifiers to suit your need.
Visual Output for Hearing Impaired or Noisy Environments.
Common or Individual Fire Alarm Inputs.
Common or Zoned Background Music Inputs.
Monitoring of Speaker Circuits.
Monitoring of Visual Warning Indicators.
Automatic Volume Control incorporating Ambient Noise Sensing Microphone.
Stand-by Signal Generators.
Digital Paging Console
www.ampac.net
www.ampac.net
34 Alarm Systems
35
EV3000 Emergency Control Panel - Add Ons
40 Watt Power Amplifier
240 Watt Power Amplifier
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
A modular power amplifier that is rated at 40 watts
Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and
background music
Continuous monitoring of amplifier and 100 volt speaker circuit
Overload protection with Automatic
Easily plugs into an Ampac EV3000 amplifier frame
Can fit up to 8 amplifiers per frame
Voltage
24 VDC
Quiescent current
58mA
Max current
3400mA
Max output power
40 Watts
Output voltage
100 VAC RMS
Freq. Response
150Hz to 12kHz (±1dB)
Distortion
Max 1% at full load
(typical 0.5%)
Sensitivity
+5dB <200Kohm balanced)
(1.4VRMS)
Overload
100 VRMS + 10%
Weight
675 grams
40 Watt Power Amplifier
Voltage
Quiescent current
Max current
Max output power
Output voltage
Freq. Response
Distortion
Signal to Noise
Overload
Weight
154-0075
120 Watt Power Amplifier
••
••
••
••
••
••
A modular power amplifier that is rated at 120 watts
Multi-channel audio input supports Alert tone, Evacuation tone, Public Address, and
background music
Continuous monitoring of amplifier and 100 volt speaker circuit
Overload protection with Automatic
Easily plugs into an Ampac EV3000 amplifier frame
Can fit up to 4 amplifiers per frame
Voltage
Quiescent current
Max current
Max output power
Output voltage
Freq. Response
Distortion
Signal to Noise
Overload
Weight
120 Watt Power Amplifier
24v DC supply
Mother board address strapping (120 address positions)
Continuous fault monitoring
Volume override output
Test tone input
Data selectable 4 channel input (balanced)
Tone generator synchronisation input
Indication (power on - green, power shutdown - yellow, amp or line fault - red, overload - red)
Minimum cable size 2.5mm²
24 VDC
175mA
8100mA
120 Watts
100 VAC RMS
210Hz to 14.5kHz (±1dB)
< 0.2% at full load
77 dB
100 VRMS + 10%
1160 grams
240 Watt Power Amplifier
••
••
••
••
••
••
••
••
24v DC supply
Mother board address strapping (120 address positions)
Continuous fault monitoring
Volume override output
Test tone input
Data selectable 4 channel input (balanced)
Tone generator
Indication (power on - green, power shutdown - yellow, amp or line fault - red, overload - red)
Minimum cable size 4mm²
Voltage
Quiescent current
Max current
Max output power
Output voltage
Freq. Response
Distortion
Signal to Noise
Overload
Weight
480 Watt Power Amplifier
www.ampac.net
154-0001
480 Watt Power Amplifier
••
154-0077
24 VDC
350mA
16200mA
240 Watts
100 VAC RMS
210Hz to 14.5kHz (±1dB)
< 0.2% at full load
77 dB
100 VRMS + 10%
2320 grams
24 VDC
700mA
32400mA
480 Watts
100 VAC RMS
210Hz to 14.5kHz (±1dB)
< 0.2% at full load
77 dB
100 VRMS + 10%
4640 grams
154-0002
www.ampac.net
36 Alarm Systems
37
EV3000 Emergency Control Panel - Add Ons
Emergency Alarm Intiating Device (EAID)
Remote Paging Console
••
••
••
••
••
••
Connects to S004 WIP
2 wires for WIP & EAID
Compatible with 219-0015
Emergency Alarm Initiating Device (EAID)
213-0068
••
••
Provides a point to initiate a non-emergency voice announcement via the EV3000
Provides a pre-announcement tone
Easy keypad operation to broadcast voice announcements to selected zones, or group
of zones
Connects to EV3000 via RS485
Derives power from the EV3000 panel
Size
Supply voltage
Current
Communication
Weight
Warden Intercom Phone- 2 Wire (S0004)
••
••
••
••
Remote Paging Console
2 Wire WIP/EAID wiring
High quality WIP audio
Complies with AS4428.4
Suitable for models manufactured after July 2010
Operating Voltage
Line Voltage
Current draw
Line Impedance
Line Level
Cabling
Dimensions
Weight
27 VDC (line driven)
On hook - 25 VDC max
Off hook - 14 VDC max
On hook - 5 mA max
Off hook - 35 mA max
360 ohm balanced
0 dB (± 3dB)
2 wire - 2.5mm² max.
215H x 85W x 62D mm
380 grams
Warden Intercom Phone – 2 Wire (S0004)
WIP Enclosure Metal Surface Mounted
••
••
The fibre modem network interface kit offers the user a method of interconnecting
two (2) or more EV3000 Emergency Warning and Intercom System (EWIS) using fibre
optic cable as an alternative to copper. The modems convert hardwired data and
audio, to a common fibre optic
compatible output.
219-0015
291-0054
The fibre optic modems are full duplex and have 4-channels to carry both data and
two (2) audio signals. Two (2) channels are required – emergency public address and
warden intercom audio signals.
Fibre Optic Network Interface for EV3000
EV3000 2 Core Single Mode Fibre Network Interface
EV300 Single Core Multi Mode Fibre Network Interface
EV300 Single Core Singe Mode Fibre Network Interface 154-0074
154-0271
154-0272
154-0273
The WIP is installed remote to the ECP
Provides intercommunication between users at the WIP and Emergency Control Panel
This feature is only available when the Emergency Warning Intercom facility has been
incorporated in the control panel
Made of high impact red ABS plastic
Compatible with most EV3000 systems manufactured before July 2010
Operating Voltage
Line Voltage
Current draw
Line Impedance
Line Level
Cabling
Dimensions
Weight
Warden Intercom Phone – 3 Wire
WIP Enclosure Metal Surface Mounted
www.ampac.net
154-0005
Fibre Optic Network Interface for EV3000
Warden Intercom Phone - 3 Wire
••
••
••
80H x 300W x 220D mm
12 VDC
400 mA
RS 485
1160 grams
27 VDC (line driven)
On hook - 25 VDC max
Off hook - 14 VDC max
On hook - 5 mA max
Off hook - 35 mA max
360 ohm balanced
0 dB (± 3dB)
3 wire - 2.5mm² max.
215H x 85W x 62D mm
380 grams
219-0007
291-0054
www.ampac.net
38 Graphics Package
39
Smart GraphicsHD
Product Overview
AMPAC’s SmartGraphicsHD System unleashes the full power of FireFinder (fire detection) and the EV3000 (alarm and intercom)
by creating a robust and versatile hub for controlling your fire detection, alarm and intercom systems with one fully integrated
package. Flexible and intuitive in its design, SmartGraphicsHD puts the command of your systems at your fingertips.
••
••
••
••
••
••
••
••
••
••
••
Fire Status Indication
Main Screen
Interfaces to the FireFinder fire detection panel and the EV3000 emergency warning and intercom system
Clearly shows on the building floor plan the start and spread of the fire and the status of the emergency warning and intercom system
Has capabilities of e-mailing maps to emergency service organisations and key stakeholders
Supports the latest 1920x1080 HD computer technology
Able to operate over existing IT infrastructure
Can be expanded to incorporate multi-site facilities into one central monitoring package
Historic data log on the activity of the fire detection system and alarm system
Three level password protection
Detailed Egress Pathways
Building Information (like hazardous materials) and mustering point displayed on maps
Disable and Control
Item Numbers
SmartGraphics HD License Kit
SmartGraphics HD PC System Complete
SmartGraphics HD Touch PC System Complete
USB-RS232 Converter Kit
USB-RS485/422 Converter Kit
SmartGraphics 19” Rack PC with Touch Screen
4100-0002
4100-0003
4100-0004
4100-0006
4100-0007
4100-0009
Access Map
www.ampac.net
History Page
www.ampac.net
40 Detection & MCP’s
41
Series 65 Detection
Series 65 Optical Smoke Detector
The Series 65 Optical Smoke Detector incorporates a pulsing LED located within the
housing of the detector. The external detector moulding is identical to that of the
ionisation detector but has an indicator LED which is clear in quiescent state but
produces red light in alarm.
••
••
••
Responds well to slow-burning, smouldering fires
Well suited for bedrooms and escape routes
Unaffected by wind or atmospheric pressure
Series 65 Optical Smoke Detector
4106-1001
Series 65 Ionisation Smoke Detector
The Series 65 Ionisation Smoke Detector uses a low activity radioactive foil to detect
fires by irradiating the air in the smoke chambers and causing a current flow. If smoke
enters the chamber, the current flow is reduced leading to an alarm.
••
••
Responds well to fast-burning, flaming fires
Designed to operate in a variety of environments
Series 65 Ionisation Smoke Detector
4106-1002
Series 65 Integrating Ionisation Smoke Detector
Ionisation Detectors use a low activity radioactive foil to detect fires by irradiating the
air in the smoke chambers and causing a current flow. If smoke enters the chamber,
the current flow is reduced leading to an alarm. Circuitry in the Ionisation Smoke
Detector protects against transient levels of smoke above the normal threshold for up
to 20 seconds.
•• Responds well to fast-burning, flaming fires
•• Designed to operate in environments where transient levels of smoke may be expected
Product Overview
Series 65 Integrating Ionisation Smoke Detector
Series 65 incorporates well-proven sensing technologies together with advances in materials and electronics. Developed from
the highly successful Series 60 range of detectors, Series 65 includes a chip (integrated circuit) based on that used in XP95
analogue addressable detectors. The range consists of ionisation, integrating ionisation and optical smoke detectors, four
grades of heat detector and a range of bases.
Series 65 Heat Detector
••
••
••
••
••
••
••
••
••
Wide operating voltage
Advanced electronic technology
Flashing LED option
Magnetic test switch option
Can be used on security systems
Electrically and mechanically compatible with Series 60
Proven detection performance
Optical
Ionisation
Integrating Ion
Operating voltage
9 to 33 V dc
Quiescent current
50μA at 24 V dc
Alarm current
52mA at 24 V dc
Operating temp (no icing)
-20°C to +60°C
Relative humidity
100mm
Height
50mm
Weight inc base
IP Rating
Approvals
150 grams
15 grams
131 grams
IP23D (EN60529)
AS240-7
Can be used for applications where smoke detectors are unsuitable
Ideal in environments that are dirty or smoky under normal conditions
Series 65 A1R Standard Rate-of-Rise – MAT 50°C, MSRT 65°C
Series 65 BR Standard Rate-of-Rise – MAT 65°C, MSRT 85°C
Series 65 CR Standard Rate-of-Rise – MAT 80°C, MSRT 100°C
Series 65 CS Standard Static – MAT 80°C, MSRT 100°C
AS240-5
The Series 65 Standard Base has been designed to enable detectors to be fitted
without the need for force – particularly useful when fitting to suspended ceilings. All
Series 65 bases have a one way fit and can be locked into place by a grub screw using
a 1.5mm hexagonal screwdriver.
••
••
••
••
••
Detector locking mechanism
One way fit
Easy to wire
Contains an earth connector
Contains no electrical parts
Series 65 Standard Base
www.ampac.net
4106-1004
4106-1005
4106-1006
4106-1007
Series 65 Standard Base
-20°C to +90°C
153 grams
The Series 65 Heat Detector monitors temperature by using a dual thermistor network
which provides a voltage output proportional to the external air temperature. There
are four classes of heat detectors in the Series 65 range designed to suit a wide variety
of operating conditions.
Heat
0 to 95% (non condensing)
Diameter
4106-1003
4106-1008
www.ampac.net
42 Detection & MCP’s
43
Heat Detection
Orbis Detection
Type E Detector Type E Detector
The Type E Heat Detector is a thermal sensitive switch. It is a fixed temperature device
with a factory pre-set temperature in the range 60 °C to 240 °C. The detectorcomprises
a pair of normally open electrical contacts mounted within a stainless steel Probe
••
••
••
••
••
Resetting Type Heat Detector
Rate Compensation & Fast Response
Wide Temperature Range
Gold Plated Electrical Contacts
Corrosion & Shock Resistant
Contacts
Operating Current
Applied Voltage DC at 0.25A Operating Temp Set-point
Ambient Temp Range
IP rating
Weight
Sensitivity & Accuracy
Approvals
Normally open, close on temp set-point
0.25 A max
32 V max
+60°C to +240°C
-40°C to +180°C
IP67
140 grams
+/- 5% or degrees
AS1603-1 (CSIRO)
Type E Heat Detector Dual Thread
Type E Heat Detector Single Thread 223-0002
223-0003
Product Overview
Thermal Type B Sealed Cool Room Detector (Hoc)
The conventional Type B Cool Room Heat Detector is a 60°C fixed temperature
waterproof detector. The detector uses a bi-metallic strip to sense temperature
change,therefore consuming minimal standby current and providing high reliability.
••
••
••
••
Waterproof Design – rated to IP67
No Mounting Base Required
Low Current Consumption
CSIRO Approved to AS1603.1
Operating Voltage
15 to 30 V dc (Nominal 24 V dc)
Max Alarm Current
50 mA at 24 V dc
Remote LED Current
4mA at 5V
Dimensions
98 mm Dia x 45 mm H
Operating temperature
-10°C to +40°C
ColourIvory
IP rating
IP67
Weight
80 grams
ApprovalsAS1603-1
Type B Cool Room Heat Detector
202-0023
Orbis is a range of conventional detectors which has been developed with sophisticated technology previously only found in
intelligent detectors. Orbis is a range with modern styling and incorporates a mounting base wihich saves installation time.
••
••
••
••
••
••
••
••
••
••
••
Automatic drift compensation with DirtAlert® warning
Patented FasTest® which reduces the time taken to test detectors
SensAlert® uses a flashing LED to indicate that the sensor is not operating correctly
StartUpTM for fast commissioning
Attractive and compact design
Electrically compatible with Series 60 and Series 65
Wide voltage and operating temperature ranges
Algorithms for transient rejection
Flashing LED option
360° visibility of LEDs
Insect resistant
Optical
Multisensor
Operating voltage
8.5 to 33 V dc
Quiescent current
95μA at 24 V dc
Alarm current
40mA at 24 V dc
Operating temp
-40°C to +70°C (no icing)
Relative humidity
0 to 98% (non condensing)
Diameter
97mm
Height inc base
46mm
57mm
51mm
Weight inc base
135 grams
140 grams
130 grams
IP Rating
Approvals
www.ampac.net
Heat
IP23D (EN60529)
AS7240-7
AS7240-5
www.ampac.net
44 Detection & MCP’s
45
Orbis Detection
Manual Call Points
Optical Smoke Detector
Manual Call Point – ACP-04
The Orbis Optical Smoke Detector works using the well established light scatter
principle, however, the sensing technology is radically different in design from
previous optical detectors and significantly reduces false alarms.
••
••
••
••
••
••
••
••
Current Rating
Size
Switch Type
Cable termination
In-Line Resistor
Material
Operating Temperature
Humidity
IP rating
Weight
Responds well to slow-burning, smouldering fires
Performs well in black and white smoke
Extra confirmation of smoke before alarm signal is given
Reduced incidence of false alarms
Sensing chamber keeps out dust and other airborne contaminants
Operates over a broad range of voltages at extremes of temperature
Orbis Optical Smoke Detector 4106-1051
Multisensor Smoke Detector
The Orbis Multisensor Detector benefits from the same false alarm reduction
technology as the optical detector. It is a thermally enhanced smoke detector and so
will not give an alarm from heat alone.
••
••
••
••
••
••
Responds well to slow-burning, smouldering fires
Performs well in black and white smoke
Extra confirmation of smoke before alarm signal is given
Reduced incidence of false alarms
Sensing chamber keeps out dust and other airborne contaminants
Operates over a broad range of voltages at extremes of temperature
Orbis Multisensor Detector
4106-1052
Heat Detector
The Orbis Heat Detector monitors temperature by using a single thermistor network
which provides a voltage output proportional to the external air temperature. There
are seven classes of heat detectors in the Orbis range designed to suit a wide variety
of operating conditions.
••
••
••
••
Can be used for applications where smoke detectors are unsuitable
Ideal in environments that are dirty or smoky under normal conditions
Reduced incidence of false alarms
Increased reliability of detection
Orbis A1R (50°C) Heat Detector Rate of Rise
Orbis A2S (50°C) Heat Detector (Type B) Static Orbis BR (65°C) Heat Detector (Type A) Rate of Rise
Orbis BS (65°C) Heat Detector Static
Orbis CR (80°C) Heat Detector (Type C) Rate of Rise
Orbis CS (80°C) Heat Detector (Type D) Static 4106-1053
4106-1054
4106-1055
4106-1056
4106-1057
4106-1058
Orbis TimeSaver Relay Base
To support the Orbis detectors a range of bases are available. Each base has two slots
for fixing screws at a spacing of 51mm to 69mm. The detectors fit into the base one
way only and require minimal force in a clockwise rotation. The TimeSaver Relay base
incorporates a single pole voltage-free changeover contact for switching external
equipment. The relay is energised when the detector changes to alarm state and
deactivates when the detector is reset. The relay is capable of switching up to 30V at
1A. The Orbis Adaptor base enables the detector to be fitted to a Series 60/65 base.
Orbis LX Base Orbis TimeSaver Relay Base
Orbis Adaptor Base
www.ampac.net
201-0545
201-0543
201-0544
Double terminal, wire protected connectors for independent input and output connections when looping to other devices
Protective film prevents glass from splintering when broken
3A @ 12/24 VDC
1.5A @ 48 VDC
88mm H x 88mm W x 59mm D (surface)
88mm H x 88mm W x 27mm D (flush)
Single pole micro
6 x 2.5mm2 screw
470Ω (N/O operation only)
High impact ABS
-5°C to +70°C
0 – 95% non-condensing
IP 24D (indoor use)
153 grams
Manual Call Point – ACP-04 Red
Manual Call Point – ACP-04 Yellow
Manual Call Point – ACP-04 White
Manual Call Point – ACP-04 Green
Manual Call Point – ACP-04 Protective Cover
Manual Call Point – ACP-04 Glass
213-0060
213-0061
213-0062
213-0063
213-0057
213-0058
Manual Call Point – Conventional Weatherproof
The Weatherproof Manual Call Point has been designed for use outdoors and in places
where moisture may be present. The Manual Call Point provides a simple single pole
changeover contact for use with older fire systems or in other applications requiring
switching at up to mains voltage.
Contact rating
3A at 24 VDC
Size
87mm H x 87mm W x 57mm D
Switch type
Single Pole
Material
High Impact ABS
Temperature range
-25°C to +70°C
IP rating
IP65
Weight220g
IP65 MCP Reset n/c n/o con
213-0045
Manual Call Point - Conventional Waterproof
The Conventional Waterproof Manual Call Point has been designed to work on
conventional systems. The Manual Call Point has an easilt resettalbe element rather
than a break glass.
Supply Voltage
Operatin Temperature Humidity (No condensation or icing)
IP Rating Alarm Resistance
Current (Alarm LED On)
Conventional Waterproof MCP
9-33VDC
-30o to 70o
0-95%
67
470-680 Ohms
80mA
4105-1002
www.ampac.net
46 Detection & MCP’s
47
Sampling Duct Units
Beam Detection
Product Overview
The FIRERAY 5000 motorised reflective, auto aligning infrared optical beam smoke detector can be installed with up to two
detector heads per system, thus saving on installation time and costs. In addition, each system controller houses two pairs of
fire and fault relays, one per detector. This innovative system has been designed from the ground up to include pioneering
technology that fully addresses the needs of the installer and user, both now and in the future.
Product Overview
The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into
the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which
causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back
into the air duct.
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than
560mm, three other lengths of sampling pipe are available.
••
••
••
••
••
••
••
••
Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier
The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel
Easily accessible wire clamping terminals ensure secure and fast termination
Clear cover hence the alarm LED on the detector is visible at all times
Integral smoke test port
Sampling pipes available in 4 lengths
Operates in air speeds of 0.5 m/s to 20 m/s
Volt free contacts
www.ampac.net
Allows for 2 Detectors per System Controller
Each Detector configurable from 8m to 100m
Separate Fire and Fault relays per Detector
Integral LASER alignment
Auto-Align Fast Automatic Beam Alignment
Building Movement and Contamination Compensation
Low Level System Controller
Logs the 50 most recent events per detector
Programmable Sensitivity and Fire Thresholds
20mm Cable Gland Knockouts on System Controller
2-wire interface from System Controller to Detector
Operating distance (separation)
Cable length – system controller to detector
Operating voltage (to system controller)
8-100 metres
100 metres
14VDC to 36VDC
Operating current with 1 detector
5 to 6 mA
Operating current with 2 detectors
7.5 to 8.5 mA
Operating temperature
Relative humidity
IP rating
-10°C to +55°C (no icing)
93% (non condensing)
IP54
Item Numbers
Item Numbers
Orbis Duct Sampling Unit inc Detector Base
Duct Probe 300mm to 750mm
Duct Probe 750mm to 1500mm
Duct Probe 1500mm to 3000mm
••
••
••
••
••
••
••
••
••
••
••
214-0052
214-0060
214-0061
214-0062
Reflective Beam System
Reflective Prism
Detector & Reflective Prism
Long Range Reflective Prism
Universal Bracket for Detector
Prism Plate (1)
Prism Plate (4)
Ceiling Pendant Mounting
Detector Protective Cage
4109-1003
220-0007
220-0009
220-0010
220-0011
220-0012
220-0013
220-0014
220-0015
www.ampac.net
48 Detection & MCP’s
49
XP95 Detection
XP95 Optical Smoke Detector
The XP95 Optical Smoke Detector works using the light scatter principle and is ideal
for applications where slow-burning or smouldering fires are likely.
®
••
••
••
Responds well to slow-burning, smouldering fires
Well suited for bedrooms and escape routes
Unaffected by wind or atmospheric pressure
XP95 Optical Smoke Detector
XP95 Optical (Black) Smoke
4106-2001
4106-2010
XP95 Ionisation Smoke Detector
The XP95 Ionisation Smoke Detector uses a low activity radioactive foil to detect fires
by irradiating the air in the smoke chambers and causing a current flow. If smoke
enters the chamber, the current flow is reduced leading to an alarm.
••
••
••
••
Responds well to fast-burning, flaming fires
Designed to operate in a variety of environments
Minimal effects from temperature, humidity, atmospheric pressure
Well protected against electromagnetic interference over a wide frequency range
XP95 Ionisation Smoke Detector
XP95 Ionisation (Black)
4106-2002
4106-2011
Product Overview
The XP95 range of intelligent fire detectors is advanced in design, improved in performance and has unique features that
benefit the installer and end user. The range features smoke detectors (ionisation and optical), standard and high temperature
heat detectors and a multisensor. Beam detectors, flame detectors, manual call points, audio visual signalling devices, interface units and isolators complete the range. XP95 has a ‘central intelligence’ system where all the decisions are made by the
control panel.
••
••
••
••
••
••
••
Alarm Flag for fast alarm reporting
Alarm Address for fast location of alarm
XPERT card addressing
Electronics-free base
Easy installation
Elegant design
Insect Resistant
Optical
Alarm current at 24 V dc
Operating temp (no icing)
Ionisation
Heat
280μA
250μA
500μA
4mA
2mA
2mA
3.5mA
-20°C to +60°C
-20°C to +70°C
-20°C to +70°C
XP95 Multisensor Detector
100mm
50mm
157 grams
161 grams
58mm
161 grams
150 grams
160 grams
IP23D (EN60529)
AS7240-5
-
The XP95 Multisensor Detector contains an optical smoke sensor and a thermistor
temperature sensor whose outputs are combined to give the final analogue value.
••
••
••
Sensitive to a wide range of fires
Well suited for environments such as hotel bedrooms
Unaffected by wind or atmospheric pressure
XP95 Multisensor Detector
www.ampac.net
4106-2003
4106-2013
-20°C to +60°C
0 to 95% (non condensing)
Height
Approvals
-20°C to +120°C
Ideal in environments that are dirty or smoky under normal conditions
Well suited for warehouses, loading bays and car parks
Unaffected by wind or atmospheric pressure
XP95 Heat Detector Standard – A2S
XP95 Heat A2S (Black) Detector
Multisensor
340μA
Diameter
IP Rating
High Heat
17 to 28 V dc
Relative humidity
Weight inc base
The XP95 Heat Detector monitors temperature by using a single thermistor network
which provides a count output proportional to the external air temperature. The XP95
range features two Heat Detectors, standard and high temperature. The standard
heat detector is classified as an A2S device and will report an alarm at 55°C. The high
temperature detector, classified as a CS device, will report an alarm at 90°C.
••
••
••
Operating voltage
Quiescent current at 24 V dc
XP95 Heat Detector
4106-2004
www.ampac.net
50 Detection & MCP’s
51
Discovery Detection
Discovery Optical Smoke Detector
The Discovery Optical Smoke Detector works using the light scatter principle and is
ideal for applications where slow-burning or smouldering fires are likely.
••
••
••
••
Responds well to slow-burning, smouldering fires
Well suited for bedrooms and escape routes
Unaffected by wind or atmospheric pressure
Remote test feature
Discovery Optical Smoke Detector
4106-2005
Discovery Multisensor Detector
The Discovery Multisensor Detector comprises optical smoke and thermistor
temperature sensors whose respective outputs can be split to deliver specific smoke
or thermal actions respectively. This capability can aid early Alarm warning routines
and other advanced detection techniques.
Discovery Multisensor Detector
Discovery Multisensor (Black)
4106-2008
4106-2012
Discovery Ionisation Smoke Detector
The Discovery Ionisation Smoke Detector uses a low activity radioactive foil to
irradiate the air in the smoke chamber causing a current flow. If smoke enters the
chamber, the current flow is reduced leading to an alarm.
Product Overview
Discovery is a range of high-specification, intelligent fire detectors developed to meet the requirements of sophisticated
systems while providing engineers with an additional dimension in fire protection capability. Discovery has a ‘distributed
intelligence system’ where decisions are made in the detector head as well as at the control panel. Drift compensation is also
incorporated into the detector, allowing it to adapt to dirty or dusty environments reducing false alarms.
••
••
••
••
••
••
••
••
••
••
Optical/Heat
Multisensor
Operating voltage
Quiescent current 24 V dc
300μA
400μA
-40°C to +70°C
58mm
Weight inc base
Discovery CO/Heat Multisensor Detector
400μA
-30°C to +70°C
50mm
300μA
-20°C to +55°C
60mm
50mm
-
-
IP44 (EN60529)
AS7240-7
AS7240-5
AS7240-7
4106-2007
Carbon
Monoxide
160 grams
IP Rating
www.ampac.net
CO/Heat
Multisensor
100mm
50mm
4106-2006
Ideal in environments that are dirty or smokey under normal conditions
Well suited for warehouses, loading bays and car parks
Unaffected by wind or atmospheric pressure
Remote test feature
Discovery Heat Detector
0 to 95% (non condensing)
Diameter
Approvals
••
••
••
••
3.5mA
Relative humidity
Height inc base
300μA
Discovery Ionisation Smoke Detector
The Discovery Heat Detector, distinguishable by the low airflow resistant case, uses a
single thermistor to sense the air temperature around the detector.
17 to 28 V dc
Alarm current 24 V dc
Operating temp (no icing)
Ionisation
Responds well to fast-burning, flaming fires
Designed to operate in a variety of environments
Remote test feature
Discovery Heat Detector
Rejection of transient signals
Flashing LED option
Five response modes for ease of optimisation to changing environments
Drift compensation to ensure constant sensitivity
Four bytes of non-volatile memory for user data
Alarm flag for fast alarm reporting
Conventional alarm facility during control panel processor fault
360° visibility in alarm
Compatible with XP95 systems
Insect resistant
Optical
••
••
••
The Discovery CO/Heat Multisensor Detector is good at detecting deepseated
smouldering fires which give off a lot of CO as well as flaming fires. They are ideal for
use in hotel bedrooms where steam may be present, dusty environments or even
where simulated smoke may be present.
••
••
••
••
••
Enhanced detection capability
Early response to hot fires
Ideal for smouldering fires
Less susceptible to false alarms caused by steam than smoke alarms
Five response modes
Discovery CO/Heat Multisensor Detector
4106-2009
www.ampac.net
52 Detection & MCP’s
53
Discovery Detection
Manual Call Points
Discovery Carbon Monoxide Detector
Intelligent Manual Call Point (New)
The Discovery Carbon Monoxide (CO) Detector is good at detecting deep-seated
fires. Please note that CO detectors do not detect smoke particles or heat and are not
universal replacements for smoke detectors.
The Intelligent Manual Call Point has a highly visible alarm indicator which can be
seen from up to 10 metres away. When activated, the manual call point interrupts the
polling cycle for a fast response. A combined LED indicator and front reset mechanism
allows for a quick and simple reset.
••
••
••
••
••
Enhanced detection capability
Early response to hot fires
Ideal for smouldering fires
Less susceptible to false alarms caused by steam than smoke alarms
Five response modes
Discovery Carbon Monoxide Detector
201-0102
All detectors in the XP95 range fit the Intelligent Detector Base. It is a low insertion
force base with stainless steel contacts for the detector terminals.
XPERT addressing
One way fit of detector
Locking feature to prevent unauthorised removal
XP95/Discovery Detector Base
XP95/Discovery Detector Base (Black)
201-0004
201-0093
XP95/Discovery Isolating Base
The new style Isolating Base senses and detects short-circuit faults on XP95 loops and
spurs.
••
••
Up to 20 devices may be installed between isolating bases
High brightness LED
XP95/Discovery Isolating Base
201-0125
The Low Power Relay Base incorporates a low power relay to control field equipment
such as automatic door closers.
Gives a set of voltage free contacts controlled by the remote output of a detector
Draws negligible current
Capable of switching up to 30V at 1A
XP95/Discovery Low Power Relay
www.ampac.net
4105-2005
4105-2003
4105-2004
Waterproof Manual Call Point (New)
The Waterproof Addressable Manual Call Point has a highly visible alarm indicator
which can be seen from up to 10 metres away. When activated, the manual call point
interrupts the polling cycle for a fast response and has a combined LED indicator and
front reset mechanism allowing for a quick and simple reset.
Voltage
Quiescent current
Alarm current
Size (surface mount)
Operating temperature
Relative humidity
IP rating
Weight
Waterproof Manual Call Point
Transparent Cover
Pack of 10 Reset Keys
17-28 VDC
100μA
4mA
110H x 110W x 74D mm
-30°C to +70°C
0-95% RH
IP67
180 grams
4105-2002
4105-2003
4105-2004
Addressable XP95 Manual Call Point
XP95/Discovery Intelligent Low Power Relay Base
••
••
••
17-28 VDC
100μA
4mA
87H x 87W x 54D mm
-40°C to +70°C
0-95% RH
45
180 grams
Inetlligent Manual Call Point with Isolator
Transparent Cover
Pack of 10 Reset Keys
XP95/Discovery Intelligent Detector Base
••
••
••
Voltage
Quiescent current
Alarm current
Dimensions (surface mount)
Operating temperature
Humidity
IP rating
Weight
201-0014
The XP95 Manual Call Point has been designed to operate on a loop of intelligent
addressable fire detection devices. The address of each call point is set at the
commissioning stage by means of a seven segment DIL switch. The device features
plug and play terminal connections and a resettable element.
Voltage
Quiescent current
Alarm current
Address method
Size (surface mount)
Operating temperature
Relative humidity
IP rating
Weight
XP95 Manual Call Point (Surface)
XP95 Manual Call Point Protective Cover
Intelligent Waterproof Manual Call Point
17-28 VDC
100μA at 24VDC
4mA
7 segment DIL switch
93mm H x 89mm W x 59.5mm D
-20°C to +60°C (no icing)
0-95% (non condensing)
IP24D (indoor use)
160 grams
213-0050
213-0064
213-0066
www.ampac.net
54 Detection & MCP’s
55
Duct Sampling Unit
Flame Detection
Product Overview
Product Overview
The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second. The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into
the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which
causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back
into the air duct.
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than
560mm, three other lengths of sampling pipe are available.
••
••
••
••
••
••
••
••
Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier
The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel
Easily accessible wire clamping terminals ensure secure and fast termination
Clear cover hence the alarm LED on the detector is visible at all times
Integral smoke test port
Sampling pipes available in 4 lengths
Operates in air speeds of 0.5 m/s to 20 m/s
Volt free contacts
Item Numbers
Duct Sampling Unit inc XP95 Detector Base
Duct Probe 300mm to 750mm
Duct Probe 750mm to 1500mm
Duct Probe 1500mm to 3000mm www.ampac.net
214-0051
214-0060
214-0061
214-0062
Flame detectors are effective in protecting areas where flaming fires may be expected. There is a choice of detection techniques - Ultra Violet and Infra-red, or a combination of both. UV Flame Detectors are generally used in engine rooms, factories
and warehouse applications. Infra-red Flame Detectors are able to tolerate dirtier environments which may block UV radiation
and are generally used in applications such as waste handling, colour printing and paper manufacturing.
••
••
••
••
••
••
Detects a wide range of open fires
Insensitive to wind
Transient voltage protection
Three types of detector
Lockable security fitting
White finish
UV Base
IR2 Base
IR3 Base
Operating voltage
Quiescent current at 24 V dc
Field of view
Operating temp (no icing)
IR3 Flame
17-28 V DC
2.3mA
2.8mA
2.2mA
2.2mA
2.2mA
90° cone
90° cone
90° cone
90°
90°
-40°C to +55°C
Relative humidity
Dimensions
IR2 Flame
-10°C to +55°C
0 to 95% (non condensing)
100D x 48H mm
Weight
210g
IP Rating
IP66
142W x 108H x 82D mm
1 kg
2 kg
IP65
www.ampac.net
56 Detection & MCP’s
57
Flame Detection
Intelligent Base Mounted UV Flame Detector
Intelligent Dual IR Flame Detector
The Intelligent Base Mounted UV Flame Detector is designed to protect internal areas
where open fires may be expected. The detector has a single UV sensor with a narrow
spectral response in order to discriminate between flames and most spurious sources
of radiation.
The Intelligent Dual Infra-Red (IR²) Flame Detector is designed for use in areas
where flaming fires may be expected. The detector has two sensors which respond
to different IR wavelengths to discriminate between flames and spurious sources
of radiation. Applications include aircraft hangars, coal handling and paper
manufacturing plants and woodworking environments.
••
••
••
••
••
Responds to stationary flames with no flicker
Sensitive to UV radiation emitted by flames during combustion
Compact flame detector which can fit into Discovery or XP95 bases
Loop-powered
Increased reliability of detection
XP95 Base Mounted UV Flame Detector
XP95 Dual IR2 Flame Detector
201-0130
201-0169
Intelligent Triple IR Flame Detector
The Intelligent Triple IR Flame Detector (IR³) is designed to protect areas where open
flaming fires may be expected. It is sensitive to low frequency, flickering infra-red
radiation emitted by flames during combustion.
XP95 Triple IR3 Flame
201-0188
Intelligent Base Mounted UV IR² Flame Detector
The Intelligent Base Mounted UV IR² Flame Detector is designed to protect areas
where open flaming fires may be expected. The detector has a UV and dual IR sensors
responding to different wavelengths in order to discriminate between flames and
spurious sources of radiation.
•• Responds to stationary flames with no flicker
•• Sensitive to UV and low-frequency flickering IR radiation emitted by flames during combustion
•• Compact flame detector which can fit into Discovery or XP95 bases
•• Loop-powered
•• False alarms due to electrical discharges from lightning or arc welding and flickering sunlight are minimised
XP95 Base Mounted UV IR² Flame Detector
Base Mounted Flame Detector Bracket
The Flame Detector Bracket is an optional accessory for the Intelligent Flame
Detectors. It is a stainless steel mounting bracket adjustable in two axis.
Bracket for Base Mounted Flame Detectors
201-0186
201-0131
Flame Detector Bracket
The Flame Detector Bracket is an optional accessory for the Intelligent Flame
Detectors. It is a stainless steel mounting bracket adjustable in two axis. Not suitable
for Base Mounted Flame Detectors.
Flame Detector Bracket
Intelligent Base Mounted IR³ Flame Detector
201-0189
The Intelligent Base Mounted IR³ Flame Detector is designed to protect areas where
open flaming fires may be expected. The detector has three IR sensors that respond to
different IR wavelengths in order to discriminate between flames and spurious sources
of radiation.
•• Responds to stationary flames with no flicker.
•• Sensitive to low-frequency flickering IR radiation emitted by flames during combustion.
•• Compact flame detector which can fit into Discovery or XP95 bases.
•• Loop-powered.
•• False alarms due to factors such as flickering sunlight are avoided by a combination of filters and signal processing techniques.
XP95 Flameproof IR³ Flame Detector
www.ampac.net
Flame Detector Weather Shield
The Flame Detector Weather Shield protects the device from inclement conditions.
S/Steel Weather Shield for Standard Flame Detector
201-0190
201-0132
www.ampac.net
58 Detection & MCP’s
59
Hazardous Area Detection
Orbis I.S. Optical Smoke Detector
The Orbis I.S. Optical Smoke Detector works using the light scatter principle, and is
ideal for applications where slow burning or smouldering fires are likely.
®
TM
••
••
••
••
••
Reduces false alarms
Recommended for early warning of fire in most areas
Improved sensitivity to black smoke
Compensation for slow changes in sensitivity
Algorithms for reliability of alarm
Orbis I.S. Optical Smoke Detector
201-0604
Orbis I.S. Multisensor Detector
The Orbis I.S. Multisensor Detector benefits from the same false alarm reduction
technology as the optical detector. It is a thermally enhanced smoke detector and so
will not give an alarm from heat alone.
••
••
••
••
••
Reduces false alarms
Sensitive to fast burning, flaming fires
Improved sensitivity to black smoke
Compensation for slow changes in sensitivity
Algorithms for reliability of alarm
Orbis I.S. Multisensor Detector
201-0605
Orbis I.S. Heat Detector
Product Overview
Ampac offers a range of Intrinsically Safe detectors in both conventional and addressable. Orbis IS ia a range with modern
styling and is electronically compatible with Apollo Series 60 intrinsically safe conventional detectors. XP95 Intrinsically Safe
range is a development of the well established intelligent XP95 range from Apollo specifically for use in hazardous areas and
are set by means of the patented XPERT card.
Optical
Operating voltage
Quiescent current 24 V dc
••
••
••
••
340μA
300μA
300μA
20°C to +60°C (no icing)
Relative humidity
0 to 95% (non condensing)
Dimensions inc base
Can be used for applications where smoke detectors are unsuitable
Ideal in environments that are dirty or smoky under normal conditions
Reduced incidences of false alarms
Increased reliability of detection
Orbis I.S. A1R Heat Detector- Rate of Rise
Orbis I.S. A1S Heat Detector- Static
Orbis I.S. A2S Heat Detector- Static
Orbis I.S. BR Heat Detector- Rate of Rise
Orbis I.S. BS Heat Detector- Static
Orbis I.S. CR Heat Detector- Rate of Rise Orbis I.S. CS Heat Detector- Static
Heat
14 to 22 V dc
Operating temp range
Weight inc base
Ionisation
The Orbis IS Heat Detector monitors temperature by using a single thermistor network
which provides a voltage output proportional to the external air temperature. There
are seven classes of heat detectors in the Orbis IS range designed to suit a wide variety
of operating conditions.
100Dia x 50H mm
157 grams
161 grams
IP Rating
IP23D (EN60529)
Category
II IG Ex ia IIC T5 -20°C≤Ta≤45°C (T4≤60°C) Ga
Certificate
IECEx BAS 12.0091X, BAS02ATEX 1289
161 grams
Orbis I.S. TimeSaver Base
The Orbis IS TimeSaver Base is a completely new design that provides installers with
an open working area with fixing holes shaped to allow a simple mounting procedure.
••
••
••
••
Grouped terminals to make wiring easy
Two fixing centres
LED alignment mark
Detector locking mechanism
Orbis I.S. TimeSaver Base
www.ampac.net
201-0134
201-0135
201-0601
201-0600
201-0607
201-0602
201-0603
201-0606
www.ampac.net
60 Detection & MCP’s
61
Hazardous Area Detection
XP95 I.S. Ionisation Smoke Detector
Conventional Galvanic Barrier
The XP95 I.S. Ionisation Smoke Detector uses a low activity radioactive foil to detect
fires by irradiating the air in the smoke chambers and causing a current flow. If smoke
enters the chamber, the current flow is reduced leading to an alarm.
The Conventional Galvanic Barrier is installed in the safe area and ensures system
integrity
••
••
••
••
••
••
••
Detects super heating and flaming combustibles
Dual chamber technology
Wind resistant smoke inlets.
Transient voltage protection
Fine gauze insect protection
Lockable security fitting
Must be connected to a suitable safety barrier and protocol translator
XP95 I.S. Ionisation Smoke Detector
201-0103
The XP95 I.S. Optical Smoke Detector works using the light scatter principle and is
ideal for applications where slow-burning or smouldering fires are likely.
Detects a wide range of fires
Insensitive to wind
Transient voltage protection
Fine gauze insect protection
Simple construction allows detection chamber to be cleaned
Lockable security fitting
Must be connected to a suitable safety barrier and protocol translator
XP95 I.S. Optical Smoke Detector
Supply Voltage
30V DC
Dimensions
93mm H x 89mm W x 59.5mm D
MaterialABS
4105-3014
Conventional Intrinsically Safe Call Points
201-0104
The XP95 I.S. Heat Detector operates by measuring heat levels with a single thermistor
network which gives a count output proportional to the external air temperature.
Rate of rise and fixed temperature alarm point
Single thermistor technology
Transient voltage protection
Resettable operation
Lockable security fitting
Must be connected to a suitable safety barrier and protocol translator
XP95 I.S. Heat Detector
The conventional IS manuall call point has been designed to aperate on contenctional
instrinsically safe fire detection systems. designed specifically for use in atmospheres
which explosivemixures are or may be present.
Conventional Indoor I.S. MCP Red (470 ohm)
XP95 I.S. Heat Detector
••
••
••
••
••
••
201-1061
201-0198
Conventional Indoor I.S. MCP Red (470 ohm)
XP95 I.S. Optical Smoke Detector
••
••
••
••
••
••
••
Orbis I.S. Galvanic Barrier Singel Channel
Orbis I.S. Galvanic Barrier Dual Channel
201-0105
XP95 I.S. Mounting Base
The range of conventional manual call points include break glass, push button
and tool reset versions which are approved for Zone 0, 1, 2, 21 and 22 requiring
intrinsically safe equipment for the control of fire and gas alarm systems
Supply Voltage
Dimensions
Material
Aluminium
IP Rating
Approvals
IS Break Glass Call Point, Red
IS Push Button Call Point, Red
IS Tool Reset Call Point, Red
I.S. Break Glass Call Point
I.S. Push Button Call Point
I.S. Tool Reset Call Point
24V DC (28 max)
98mm H x 95mm W x 76mm D
Marine grade copper free LM6
IP66
ATEX, IECEx, Inmetro, GOST-R
4105-3007
4105-3008
4105-3009
4105-3010
4105-3011
4105-3012
The XP95 I.S. Mounting Base has been designed to accept only IS products. This
ensures that standard detectors cannot inadvertently be fitted into an intrinsically safe
system. XPERT cards are supplied with all bases.
••
••
••
••
••
••
••
••
Wide cable entry
Contains no electronic parts
‘One way only’ fit
Low insertion force
Large terminations
Lockable security fitting
White finish.
Must be connected to a suitable safety barrier and protocol translator
XP95 I.S. Mounting Base
www.ampac.net
201-0106
www.ampac.net
62 Detection & MCP’s
63
Hazardous Area Detection
IP65 I.S. Manual Call Points
Conventional BEx Flameproof Call Points
The XP95 IS Manual Call Point is based on the standard weatherproof model. It
features an ‘interrupt’ facility to provide fast response to an alarm.
The range of conventional manual call points include break glass, push button and
tool reset versions which are approved for Zone 1, 2, 21 and 22 hazardous areas for the
control of fire and gas alarm systems.
Voltage
14 to 22 VDC
Quiescent current
300uA
Alarm current
2mA (alarm LED On)
Size
124mm H x 124mm W x 60mm D
Operating temperature
–20°C to +40°C (T5)
–20°C to +60°C (T4)
Humidity
0 to 95%
IP rating
IP67
Weight
400 grams
Classification
E Ex ia IIc T5
ApprovalsEN54-11
XP95 Intrinsically Safe Manual Call Point
Supply Voltage
24V DC (28 max)
Dimensions
98mm H x 95mm W x 76mm D
Material
Marine grade copper free LM6
Aluminium
Colour
Red (RAL3000)
Operating Temperature
Ta = -40°C to +50°C
IP Rating
IP66
Weight800g
Approvals
ATEX, IECEx, GOST-R
BEx Break Glass Call Point, Red, 470R Fire, 3K3 EOL
BEx Push Button Call Point, Red, 470R Fire, 3K3 EOL
BEx Tool Reset Call Point, Red ,470R Fire, 3K3 EOL
BEx Break Glass Call Point, Red, 470R Fire
BEx Push Button Call Point, Red, 470R Fire
BEx Tool Reset Call Point, Red, 470R Fire
BEx Push Button Call Point, Yellow, 470R Fire, 3K3 EOL
201-0107
XP95 I.S. Protocol Translator and Galvanic Barrier
The Protocol Translator and Galvanic Barrier are installed in the safe area ensuring
integrity of communication between control equipment and field devices and safety
within the limits of BASEEFA approvals
••
••
••
••
••
Enables IS detectors to be connected to a standard loop driver
Loop powered
DIN-Rail mounting
Maximum of 20 XP95 IS devices per channel
Translators must be connected to detectors via a suitable safety barrier
XP95 Protocol Translator Single Channel XP95 Protocol Translator Dual Channel XP95 I.S. Galvanic Barrier
4105-3001
4105-3002
4105-3003
4105-3004
4105-3005
4105-3006
4105-3013
Intelligent Flameproof Triple IR Flame Detector
The Intelligent Triple IR Flame Detector (IR³) is designed to protect areas where open
flaming fires may be expected. It is sensitive to low frequency, flickering infra-red
radiation emitted by flames during combustion.
201-0108
201-0155
201-0109
••
••
••
••
••
••
Loop-powered
Sensitive to flickering IR radiation
Detects through films of oil, dust, water and ice
Responds to flickering flames, including those invisible to the naked eye
False alarms due to lighting or flickering sunlight are minimised
Compatible with Discovery and XP95 protocols
XP95 Flameproof IR³ Flame Detector
201-0187
DIN-Rail Interface Enclosures
DIN-Rail Interface Enclosures are available and can be used for housing intrinsically
safe (IS) barriers or DIN-Rail mounted interfaces. A multi-purpose label that features a
section for use with IS systems is supplied. For non-IS systems, the part referring to IS
can simply be removed.
XP95 IS DIN Rail Interface Enclosure (4 units)
I.S. DIN Rail Interface (10 Units)
201-0142
201-0153
Intelligent Flameproof Dual IR Flame Detector
The Intelligent Dual Infra-Red (IR²) Flame Detector is designed for use in areas
where flaming fires may be expected. The detector has two sensors which respond
to different IR wavelengths to discriminate between flames and spurious sources
of radiation. Applications include aircraft hangars, coal handling and paper
manufacturing plants and woodworking environments.
••
••
••
••
••
••
••
Sensitive to flickering IR radiation
Detects through films of oil, dust, water and ice
Responds to flickering flames, including those invisible to the naked eye
Compatible with Discovery and XP95 protocols
Remote optical self-test function
90° field of view
Up to 40m coverage
XP95 Flameproof IR² Flame Detector
www.ampac.net
201-0191
www.ampac.net
64 Detection
Audio Visual
& MCP’s
& Interafaces
65
Marine Detection
TM
Orbis Marine Optical Smoke Detector
The Orbis Marine Optical Smoke Detector works on the well established light scatter
principle. However, the sensing technology is radically different in design from
previous optical detectors and significantly reduces false alarms.
Orbis Marine Optical Smoke Detector
201-0654
Orbis Marine Multisensor Detector
The Orbis Marine Multisensor Detector benefits from the same false alarm reduction
technology as the optical detector. It is a thermally enhanced smoke detector and so
will not give an alarm from heat alone.
Orbis Marine Multisensor Detector
201-0655
Orbis Marine Heat Detector
The Orbis Marine Heat Detector uses a single thermistor to sense the air temperature
around the detector. There are six classes of heat detectors in the Orbis Marine range
designed to suit a wide variety of operating conditions.
Orbis Marine A1R Heat Detector- Rate of Rise
Orbis Marine A2S Heat Detector- Static
Orbis Marine BR Heat Detector- Rate of Rise
Orbis Marine BS Heat Detector- Static
Orbis Marine CR Heat Detector- Rate of Rise
Orbis Marine CS Heat Detector- Static
201-0162
201-0651
201-0650
201-0657
201-0652
201-0653
Orbis Marine TimeSaver Base
The Orbis Marine TimeSaver Base is a completely new design that provides installers
with an open working area with fixing holes shaped to allow a simple mounting
procedure.
Orbis Marine TimeSaver Base
www.ampac.net
201-0656
www.ampac.net
66 Detection & MCP’s
Xpander Wireless Detection
67
XPander Heat Detector and Mounting Base
There are two heat detectors in the Xpander range designed to suit a wide variety of
operating conditions. A static heat detector (CS) which responds only when a fixed
temperature has been reached and a rate-of-rise detector (A1R) which has a fixed
upper limit, but in addition, measures the rate of increase in temperature
Voltage (regulated from radio base)
Size inc base
Operating temperature
Relative humidity
IP rating
Weight inc base
3VDC
105mm D x 80mm H
-10°C to +50°C (no icing)
0 to 95% (non condensing)
IP23D
400 grams
XPander A1R Heat Detector and Mounting Base
XPander CS Heat Detector and Mounting Base
4106-5301
4106-5302
XPander Optical Smoke Detector and Mounting Base
The Xpander Optical Smoke Detector works on the light scatter principle and is ideal
for applications where slow-burning or smouldering fires are likely.
Voltage3VDC
Size inc base
100mm D x 75mm H
Operating temperature
-10°C to +50°C (no icing)
Relative humidity
0 to 95% (non condensing)
IP rating
IP23D
Weight inc base
500 grams
XPander Optical Smoke Detector and Mounting Base
4106-5303
Xpander Combined Sounder & Detector
The Xpander Combined Sounder and Detector is wireless and designed to proved one
point notification and detection.
Product Overview
••
••
••
••
Traditionally, fire detection systems in industrial and commercial applications have used hard wired installations. These
systems are generally installed at the time of construction or refurbishment, making the laying of cables not a great issue.
However, certain applications do not lend themselves to this approach, such as occupied buildings, heritage sites, architecturally sensitive buildings and annexes. This is where wireless systems provide the ideal solution.
Xpander is a system in which individual detectors, call points and alarm devices communicate with the XP95 loop by radio
signals.
••
••
••
••
••
••
••
••
Easy to install.
XPERT card addressing.
Self-monitoring.
Proven technology.
915MHz radio channels.
Up to 31 devices per interface.
Up to 5 interfaces per loop (max devices per loop 126 inc interface)
All detectors within the Xpander range are supplied complete with mounting bases.
www.ampac.net
Wireless
Avaliable with a choice of Xpander detectors
Bi-directional (monitored) radio platform
A choice of 4 Tones including Temporal T3
XPander Sounder Heat A1R Combined Detector & Base
XPander Sounder Heat CS Combined Detector & Base
XPander Sounder Optical Combined Detector & Base
4111-1301
4111-1302
4111-1303
Xpander Combined Sounder Visual Indicator and Detector
The Xpander Combined Sounder Visual Indicator and Detector is wireless and
designed to privide a one point notification and detection.
••
••
••
••
Wireless
Avaliable with a choice of Xpander detectors
Bi-directional (monitored) radio platform
A choice of 4 tone including Temporal T3
XPander Sndr VI Red Heat A1R Combined Detector & Base
XPander Sndr VI Red Heat CS Combined Detector & Base
XPander Sndr VI Red Optical Combined Detector & Base
XPander Sndr VI Clear Heat A1R Combined Detector & Base
XPander Sndr VI Clear Heat CS Combined Detector & Base
XPander Sndr VI Clear Optical Combined Detector & Base
4111-1401
4111-1402
4111-1403
4111-1501
4111-1502
4111-1503
www.ampac.net
68 Detection & MCP’s
69
Xpander Wireless Detection
XPander Sounder Red and Red Mounting Base
Xpander Hub & Cluster
The Xpander Sounder and Sounder Base is wireless and designed to be used with
Xpander detectors and manual call points.
The Xpander Hub and Cluster System comprises of Radio Hub capable of receiving
information from a maximum of 31 Radio Cluster Communicators (RCCs). The RCCs
are each capable of receiving information from up to 31 wireless detection and alarm
devices from the Xpander range.
Voltage3VDC
Alarm tones (selectable)
includes Temporal T3
IP rating
IP21C
Sound output
100dB(A)
XPander Sounder Red and Red Mounting Base
XPander Sounder White and White Mounting Base
4107-8301
4107-8302
XPander Sounder Beacon
The Xpander Sounder Beacon and Sounder Base is wireless and designed to be used
with Xpander detectors and manual call points.
Voltage3VDC
Alarm tones (selectable)
includes Temporal T3
IP rating
IP21C
Sound output
100dB(A)
XPander Sounder Beacon Red and Red Mounting Base
XPander Sounder Beacon Amber and White Mounting Base
XPander Sounder Beacon Clear and White Mounting Base
4107-8303
4107-8304
4107-8305
Xpander Manual Call Point
The Xpander Manual Call Point is compliant with AS7240-11 and is powered by two
independent packs of three AA alkaline batteries with a typical five year life.
Voltage
Size inc base
Operating temperature
Relative humidity
IP rating
Weight inc base
Regulated 3V from radio circuiting
105mm D x 80mm H
-10°C to +50°C (no icing)
0 to 95% (non condensing)
IP23D
500 grams
XPander Manual Call Point
Transparent Hinged Cover for Manual Call Point
Operating Temperature
Humidity
Operating Voltage
Power Requirements
Radio Hub
RCC
Battery Backup:
Radio Hub
RCC
Battery Standby Time:
Radio Hub
RCC
Material:
Dimensions and Weight of Interface
4105-5001
213-0064
www.ampac.net
4110-2001
N/A
1 x 6V 4Ah
N/A
72 Hours
ABS - IP54
270mm width x 205mm height x 85mm
depth, 950 grams
4110-2004
4110-2005
Xpander Input/Output Unit
The Xpander Input/Output Unit is a radio based interface and offers two monitored
input circuts and two relay outputs. It can be used for controlling fire doors, fire
dampers, smoke vents and other fire engineering applications.
Supply Voltage
Relay Rating
Material
Dimensions Operating Temperature
Humidity
IP rating
3VDC +
2A at 30VDC
ABS grey plastic
120mm W x 240mmH x 60mm D
-10°C to +55°C
0% to 95% relative humidity
(no condensation)
65
XPander Input/Output Unit
XPander Dual Input/Output Unit
The Xpander Diversity Loop Interface Unit is connected to the detection loop and
provides bi-directional communications from the LoopSense and FireFinder control
panels to the wireless devices.
XPander Diversity Interface Module with Isolator
40mA at 24V DC
Mains Powered 220-240VAC, 50Hz
Xpander Radio Hub
Xpander Radio Communications Cluster
Xpander Diversity Loop Interface Unit
Voltage
24VDC + voltage pulses
Operating Current
15mA
Mechanical Isolation
Isolator included as standard
MaterialABS
Dimension
270mmW x 205mmH x 85mmD
Operating temperature
-10°C to +55°C
Humidity
0% to 95% relative humidity
(no condensation)
-10°C to 50°C (ambient)
Up to 95% non-condensing
17 to 28V DC
4110-2002
4110-2003
Site Survey Kit
The Xpander Survey Tool is used at the site survey stage to ascertain if a site is suitable
for an Xpander installation. A site survey must be carried out before Xpander can be
installed.
••
••
Indicates the suitability of proposed device location.
Tests for radio signal strength.
XPander Site Survey Kit
Power Supply for Site Survey Kit (4112-1001)
4112-1001
4112-1002
www.ampac.net
70 Detection & MCP’s
Aspirating Smoke Detection -Wagner Titanus Family
Product Overview
TITANUS PRO•SENS® is a universal air sampling device suitable for a broad range of applications. The high degree of modularity of the device makes it possible to achieve a cost-effective solution – customised to suit the specific needs of the customer.
An additional price advantage comes with the optional equipping of the device with a second detector module.
The base TITANUS PRO•SENS® unit with 2 detector heads fitted (TITANUS PRO•SENS® 2) can be used for separate zone detection of a room and its equipment, or configured as a double knock tripping system. Each detector is completely separate, with
no switching or leak between detection zones
Robust & Efficient High Pressure Light Source (HPLS) Detection Technology
••
••
••
••
••
••
••
••
••
••
••
••
LOGIC·SENS Fire Pattern Recognition Technology
Freezer Version Operates in -40Deg to +60DegC with No Heater Boxes Required
A Powerful & Efficient Aspirator Allowing up to 560m of Pipework
A BlowFree System for Programmed or Automated On-Demand Pipe Clearing
Modular Plug In Detector Heads for a Customised & Cost Effective Solution & Maintenance
Dual Detector Ability Allows Separate Monitoring & Reporting of Room & Equipment with One Unit
Time Saving Installation & Commissioning Via Plug & Play Setup
Large Capacity 3-Stage Filters with Selectable 1-15 Micron Ratings
A Large Range of Fittings, Pipework and Sampling Points
XP95 Interfacing to FireFinderTM and LoopSenseTM Fire Control Panels
FIP Bar Graph Display Module Available & SmartGraphicsHD Display Integration
Cost Effective Solutions for Every Application Type
www.ampac.net
71
Specifications
Power Supply
Detector Unit :
PRO·SENS
®PRO·SENS® 2
Number of Sensor Modules Fitted :
1
2
Max. Number of Sampling Holes :
32
64
Max. Total Pipe Length Capable :
300m*
560m*
Weight:
1460g1560g
Current – Start Up Maximum:
300mA
320mA
Current - Quiescent (at 24 VDC)
200mA
220mA
Current - Alarm (at 24 VDC)
210mA
240mA
Operating Voltage:
24 VDC (14 - 30 VDC)
Tapered Pipe Connectors:
1 x 25mm
2 x 25mm
Detector Dimensions (W x H x D) :
200 x 292 x 113mm
Housing Colour:
RAL 9018, Papyrus White
Cabinet Type, Rating :
ABS Plastics IP20 (Optional IP52)
Temperature-Standard Version:
-20 °C to + 60 °C
Temperature-DeepFreeze Version:
-40 °C to + 60 °C
Humidity (Permanent)
10-95% Rel. Non-Condensing
Cable Entries:
5 x M20, 2 x M25
Sensor Head Sensitivities:
0.5%, 0.1% and 0.015%
Interface Types
XP95 Addressable Loop, Conventional Circuit , Relays
Alarms
4 Adjustable Threshold Levels: - Alert, PreAlarm, Alarm & Alarm2
Fault Signals
Air Flow Low, Air Flow High, Processor/Hardware Fail,
Ventilator Fail Air Stabilising
Alarm & Fault Relay (CLI Version)
1A, 30 VDC max.
Front Panel Control & Indications:
Collective Fault - Yellow Operation – Green
APID & CLI Versions:
Reset & Isolate Controls
Detector Isolation – Yellow X 2
Noise level
Standard & Freezer - 45 dB(A),
Silent Version - 23dB(A)
Remote BarGraph Display:
Panel Mounted Display Module
*The maximum permissible length is pipe branch shape dependant.
Item Numbers
ProSens Base Unit-APID
ProSens Base Unit-CLI
ProSens Base Unit- OEM ProSens- 40 Base Unit- APID ProSens-40 Base Unit- CLI
ProSens-40 Base Unit- OEM
ProSens Detector 0.5%
ProSens Detector 0.1% ProSens Detector 0.015% ProSens -40 Detector 0.5%
ProSens -40 Detector 0.1%
ProSens -40 Detector 0.015%
Wagner Filter Box LF-AD
Wagner Filter Element LF-AD-E
Wagner Filter Box LF-AD-1
Wagner Filter Element LF-AD-ES
Wagner Filter Box LF-AD-2
Wagner Filter Element LF-AD-E2 M
*Wagner Filter Pipe SF-400 Short
*Wagner Filter Element SF-400
*Wagner Filter Pipe SF-650 Long
*Wagner Filter Element SF-650
Bar Graph Display - Titanus (panel kit)
Bar Graph Display - Titanus (add on kit)
Remote Bar Graph Display cw Enclosure
*Allows full flow right up until 100% Capacity. Special order only.
7010-1000
7010-1010
7010-1020
7010-1100
7010-1110
7010-1120
AD-10-5130
AD-10-5100
AD-10-5115
AD-10-5200
AD-10-5190
AD-10-5195
AD-10-1960
AD-10-0330
AD-10-1963
AD-10-0335
AD-10-1966
AD-10-0332
AD-10-2010
AD-10-1930
AD-10-2000
AD-10-1920
159-0280
4310-0088
4310-0089
www.ampac.net
72 Detection & MCP’s
73
High Sensitivity Detection System
Aspirating Smoke Detection - FastSense
Product Overview
FastSense is an aspirating system that adopts laser technology making it extremely
sensitive, thus providing the earliest warning to the slightest traces of smoke. FastSense
is available in 3 models: FastSense 25, FastSense 100, FastSense PLUS. The FastSense
25 accommodates sampling pipe up to 25 metres in length while the FastSense 100
and FastSense PLUS has total sampling pipe capacity of 100 metres and 200 metres
respectively.
••
••
••
••
••
••
Advanced Laser Technology
ClassiFire Artificial Intelligence software
Patented ‘Wastegate’ system
In-built bar-graph and smoke level display; and programming
(Available only with the FastSense PLUS)
Apollo Protocol Interface Card Interface (APIC) provides portal for indication and control of FastSense detectors at Ampac’s FireFinder Fire Alarm Control Panel
FASTSENSE Models
Voltage
Quiescent current
Dimensions (mm)
Height Width
Depth
High Sensitivity Detection System
The HIgh Sensitivity detectors are complemented by a range of light grey fittings intended to ensure that the system will suit
most applications.
••
••
••
••
••
••
Pipes, printed with red markings, have ‘bell’ ends for easy fit to the next pipe, thus saving time and material (less need for coupling for pipe joins).
T-piece is available with friction or lock fitting.
The friction fit sampling points are aesthetically designed and have an easy fit ‘finger twist’ lock nut.
Resilient snap-on conduit saddle clips and collars, are a boon for installers.
Sampling kits are available with either friction or locking TPiece and also includes a one (1) metre sampling tube and sampling point
Sampling pipe plug available for extending sampling point whilst being unobtrusive.
Item Numbers
Pipe (4M Length)
Pipe Coupling Std DX 40025
Pipe Coupling IP65 DX 43025 FitAncilliaries
Large 90o Bend - Standard
End Cap 25mm DX52125
Pipe Clip Saddle GW50603
Pipe Clip Mounting Rail GW50609
Label Sampling Pipe Roll
Sampling Point Kit 10mm - Friction Fit
Sampling Point Kit 10mm - Locking
Tube - 10mm (100 metre roll) natural
Wagner Reducer Film 2.0mmGrey Standard-Grey
Wagner Reducer Marking Tape
www.ampac.net
230-0061
230-0062
230-0063
230-0067
230-0068
230-0072
230-0074
230-0121
230-0081
230-0082
230-0112
01-10-9390
01-10-9330
Relay Outputs (All normally open 1 Amp)
Fire 1
Fire 2
Pre-Alarm
Auxiliary
Fault
25
27 VDC 250mA 100
27 VDC 400mA PLUS
27 VDC
400mA
215 220
372
140300427
859095
Optional
Optional
Optional
Optional
OptionalOptional
OptionalOptional
OptionalOptional
Fitted
Fitted
Fitted
Fitted
Fitted
No. of Pipe Inlets
1
2
4
Max. Pipe Length
25m
100m
200m
Sensitivity Range
Minimum
25%25%25%
Maximum
0.03%0.03%0.03%
Data Bus
1.2km1.2km1.2km
IP Rating
IP50IP50IP50
Operating temperature
-10°C to +60°C
Humidity0 to 90% non-condensing
Weight
1.7kg3.8kg5.2kg
ApprovalsAS1603.8
Item Numbers
FastSense 25 detector & docking station
FastSense 100 detector & docking station
FastSense PLUS detector
FastSense PLUS detector + command module
FastSense Range Apollo XP95 Interface (APIC)
FastSense 25/100 Dust Filter
FastSense Plus Dust Filter
230-0001
230-0002
230-0011
230-0012
230-0041
230-0147
230-0148
www.ampac.net
74 Audio Visual & Interafaces
75
Ampac Interfaces
Single Input/Output Device
The Ampac Single Input Output Device is designed to interface to a variety of plant
control equipment such as door contacts, sprinkler flow switches and fire fan control
systems.
••
••
••
••
••
••
••
••
••
Loop Powered
Monitored Input
Change Over Relay Output
Compatible with XP95 & Discovery Protocol
Built In Short Circuit Isolator
Low Power Consumption
Diagnostic LED Indications
Surface Mount Enclosure
DIN Rail Mount Option
Single Input Output Device DIN Mount Single Input Output Device Enclosed
Single Input Device DIN Mount
Single Input Device Enclosed
4210-0050
4210-0051
4210-0052
4210-0053
Three Input Output Device
The Ampac Three Input Output Device is designed to interface to a variety of plant
control equipment such as door contacts, sprinkler flow switches, gas valves and fire
fan control systems.
••
••
••
••
••
••
••
3 x Independent Monitored Inputs
3 x Change Over Relay Outputs
Loop Powered inc Short Circuit Isolator
Compatible with XP95 & Discovery Protocol
Low Power Consumption
Diagnostic LED Indications
Surface and DIN Mount Enclosures
Product Overview
Three Input Output Device DIN Mount Three Input Output Device Enclosed Three Input Device DIN Mount
Three Input Device Enclosed
Ampac offer an extensive range of addressable Interface devices which have a new uniform sleek design for ease of installation and commissioning. Designed for the monitoring and controlling of many types of essential plant equipment, the
Interface devices enable fire protection solutions to be engineered simply and effectively without the need for specialist
enclosures.
4210-0054
4210-0055
4210-0056
4210-0057
The range includes both single and 3 channel input output devices together with a zone input device that may be mounted in
bespoke enclosures, direct surface wall mounted or DIN rail mounted.
Input / Output
Input
Zone Input
Operating voltage
3 Input / Output
3 Input
17 to 28 V dc
Quiescent current at 24 V dc
1.25mA
1.25mA
7.5mA
1.31mA
1.25mA
Max loop current at 24 V dc
2mA
1.51mA
3.6mA
1.59mA
1.54mA
1A at 30V ac/dc
N/A
1A at 30V dc
1A at 30V ac/dc
N/A
Output rating
Operating temp
Relative humidity
-20°C to +70°C (no icing)
0 to 95% (non condensing)
Dimensions - DIN
110W x 75H x 25D mm
144W x 75H x 25D mm
Dimensions - Enclosed
150W x 200H x 52D mm
150W x 200H x 52D mm
IP Rating
www.ampac.net
IP44
Zone Input Device
The Zone Input Device is designed to allow up to 40 conventional detectors to be
interfaced to the Ampac range of Apollo analogue addressable control panels.
••
••
••
••
••
••
••
••
••
Conventional Monitored Input
Selectable EOL Monitoring Device
Loop Powered
Compatible with XP95 & Discovery Protocol
Built In Short Circuit Isolator
Low Power Consumption
Diagnostic LED Indications
Surface Mount Enclosure
DIN Rail Mount Option
Zone Input Device DIN Mount
Zone Input Device Enclosed
4210-0058
4210-0059
www.ampac.net
76 Audio Visual & Interafaces
77
XP95 Interfaces
Input/Output Unit with Isolator
The Input/Output unit with Isolator provides a voltage free, single, pole, change-over
relay output, a single, monitored switch input and an unmonitored, non-polarised
opto-coupled input.
••
••
••
••
••
••
It can report fault, switch open and switch closed levels
Three visible LEDs
Loop powered
Voltage free
Capable of switching up to 1A at 30V
Built-in short circuit isolator
Input Unit with Isolator
Output Unit with Isolator
201-0151
201-0152
Zone Monitor with Isolator
The Zone Monitor with Isolator powers and controls the operation of a zone of up to
20 Apollo Series 65 or Orbis fire detectors from a Discovery or XP95 Loop.
••
••
••
Loop powered
Visible LED
Built-in short circuit isolator
Discovery/XP95 Zone Monitor with Isolator
201-0126
Product Overview
There are a variety of XP95 interfaces available to suit a number of individual applications. Standard interfaces are fitted with
bi-directional short circuit isolators so that they are unaffected by a single short circuit on either loop input or output. The exception to this is the Main Input/Output Unit which is not isolated. DIN-Rail interfaces feature enclosures that clip to standard
35mm DIN rails or are screwed to the base of a larger enclosure. They enable fire system designers to create multi-purpose
interfaces for individual sites.
Input /
Output
Zone
Monitor
Sounder
Unit
Operating
voltage
Switch
Monitor
(inc Plus)
Mains Input /
Output
3 Input /
Output
Mini Switch
Monitor
Sounder Control Unit with Isolator
The XP95 Sounder Control Unit with Isolator is used to control the operation of a zone
of conventional sounders and report their status to the control panel.
••
••
Allows sounders to be operated continuously or be pulsed or be pulsed, 1 second on
1 second off
May be synchronized when in pulsed operation
Sounder Control Unit with Isolator
17 to 28 V dc
Quiescent
current at 24 V dc
1.25mA
4mA
+ detectors
1.95mA
1.25mA
1.25mA
3mA
200 μA
Max loop current
at 24 V dc
3.5mA
11mA
3.6mA
4.2mA
3.5mA
7.5mA
3.4mA
Output rating
1A at 30V dc
N/A
1A at 30V dc
1mA (opto)
5A at 250V ac 1A at 30V dc
Operating temp
-20°C to +70°C (no icing)
Relative humidity
0 to 95% (non condensing)
N/A
Three Channel Input/Output Unit with Isolator
The Three Channel Input/Output unit with Isolator provides three voltage free, single
pole, change-over relay outputs, and three monitored switch inputs.
Dimensions
150W x 90H x 48D mm
-
-
Weight
240 grams
621 grams
30 grams
IP Rating
IP54
IP54
-
••
••
••
••
Supervises one or more normally-open switches on each of the three inputs
Loop powered
Capable of switching up to 30V at 1A on each of the three outputs
Built-in short circuit isolator
Three Channel Input/Output Unit with Isolator
www.ampac.net
201-0127
201-0175
www.ampac.net
78 Audio Visual & Interafaces
79
XP95 Interfaces
Alarm Acknowledgement Facility
Mains Switching Input/Output Unit
The XP95 Loop Powered Mains Switching Input/ Output Unit provides a voltage free,
single pole charge- over relay output and a monitored switch input.
••
••
••
Supervises one or more normally-open switches connected to a single pair of cables
Three visible LEDs
Capable of switching 250 vac at up to 5 amps
Mains Switching Input/Output Unit
201-0180
Mini Switch Monitor with Isolator
The Mini Switch Monitor is an interface within an entirely new housing. This allows
the unit to be fitted onto a standard 35mm DIN-Rail (using a twist-click motion)
or mounted within an enclosure, for example a Manual Call Point. It is designed to
monitor the state of one or more single pole, volt-free contacts connected on a single
pair of cables and to report the status to the FireFinder or LoopSense addressable
control equipment.
••
••
••
••
••
The Alarm Acknowledgment Facility (AAF) is a loop powered addressable device that
helps reduce the costly consequence of an unwanted alarm.
Operating Voltage
Quiescent Current
Additional Operational Currents
Temperature
Humidity (Non Condensing)
Address Setting Alarm Current
Dimension
Weight
Compliance
21 to 28 VDC (loop powered)
900µAA at 24VDC
Ext “Hush” enabled +100µA
Poll LED “ON” steady +2mA
Alarm LED “ON” steady &
buzzer sounding– Ia = <8mA
-20°C to 70°C
0 to 95%
1 to 126
<8mA at 24VDC
Single gang Clipsal plate
45 grams
AS7240.2 and AS4428.1 amendment 1
Alarm Acknowledgement Facility AS7240
Alarm Acknowledgement Facility Horizontal AS7240
226-0002
226-0004
Designed for use where space is limited
Built in short circuit isolator
Interrupt/non interrupt in one unit
‘Pre-alarm’ status available
Three coloured LEDs giving clear status indication
XP95 Mini Switch Monitor with Isolator
201-0184
Apartment Module
The Apartment Module (AM) is a loop powered addressable device that helps reduce
the costly consequences of an unwanted alarm
Operating Voltage
Quiescent Current
Alarm Current
Zone Circuit
Zone EOL
Speaker Circuit
Address Setting
Dimension
Material
Weight
Apartment Module
www.ampac.net
21 to 28 VDC (loop powered)
4.9mA with 6k2Ω EOL
1.9mA with 10μF EOL
4.2mA + Zone alarm current of 14.5mA
10 detectors (max) with 6k2Ω EOL
(detector current < 1.2mA)
20 detectors (max) with 10μF EOL
(detector current < 2.4mA)
6k2Ω, 10μF
100Volt line, 6 W max, 47k EOL
1 to 126
Single gang PDL plate
High impact ABS (white)
45 grams
226-0003
www.ampac.net
80 Audio Visual & Interafaces
81
Conventional Audio Visual
Vantage Sounder
Vantage LED Beacons
The Vantage spatial sounder has been designed for general purpose, fire and security
applications and incorporates AS1670.4 compliant signal tones.
Designed as a general purpose LED beacon for fire, security and industrial
applications, the Vantage Beacon incorporates the latest in energy efficient LED
technology to provide maximum all-round visibility in an aesthetically pleasing body
with minimum power requirements.
Operating voltage
Volume setting
Current @ 24VDC
Sound output @ 1m (Tone 1)
Number of tones
IP Rating (shallow)
IP Rating (deep)
Operating temperature
Humidity
Dimensions (mm)
Weight
Approvals
21 - 28VDC
Low
Med High
9mA
18mA
36mA
86dBA
101dBA 106dBA
32
IP43
IP65
-20°C to +70°C (no icing)
0 to 95% (non condensing)
94Ø x 85H(shallow), 94Ø x 102H (deep)
200g (shallow), 220g (deep)
EN54-3, AI 2002, A2 2006
Vantage Sounder Red with Shallow Base
Vantage Sounder White with Shallow Base
Deep Base Only Red
Deep Base Only White
205-0062
205-0063
205-0064
205-0065
Operating Voltage
Supply Current
Flash Rate
Operating Temp.
Humidity
Material
Dimensions
Shallow Base
Deep Base
IP rating
Weight
20 - 35V DC
9mA
T3 Temporal (red & clear)
1Hz (amber)
-20°C +70°C
0 to 95% Non-condensing
ABS fire retardant plastic
94mm Ø x 60mm H
94mm Ø x 77mm H
IP43 (shallow), IP65 (deep)
145g (shallow), 165g (deep)
Red LED Beacon White Shallow Body
Amber LED Beacon White Shallow Body
Red LED Beacon White Deep Body
Amber LED Beacon White Deep Body Red LED Beacon Red Deep Body
Amber LED Beacon Red Deep Body
Clear Lens Red LED Beacon White Shallow Body
4107-1001
4107-1002
4107-1003
4107-1004
4107-1009
4107-1010
4107-1011
Vantage Combi
The Vantage Combi is a combined low profile electronic reflex horn sounder
incorporating a high output LED cluster strobe array. The Vantage Combi has been
designed for general purpose, fire and security applications and incorporates
AS1670.4 compliant signals.
Voltage
18 to 35 VDC
Volume setting
Low, Med & High
Current (mA @ 27VDC )
11 - 48mA
Sound Output (dB @ 1m)
85 - 100dB
SignalAS1670.4
Flash rate
1 per sec
Size (shallow)
93mm Dia x 90mm H
Size (deep)
93mm Dia x 107mm H
Temperature range
-20°C to +70°C
Humidity
0 to 95%
IP Rating (shallow base)
IP43
IP Rating (deep base)
IP65
Weight
223g & 253
ApprovalsAS1670.4
Deep Base Only Red
Deep Base Only White
Vantage Combi Red with Shallow Base Vantage Combi White with Shallow Base
Amber Sounder Beacon White Deep Body (VTB-32 Tone)
www.ampac.net
Vector Sounder
The Vector sounder has been designed for general purpose conventional fire
detection applications and incorporates AS1670.4 compliant signal tones. The Vector
sounder can be installed as a sounder base for Ampac conventional detectors or a
surface mount sounder when used in conjunction with the optional lid
Operating voltage
8 to 35 VDC
Supply current Evac
15mA @ 24VDC
Supply current Alert
8 mA @ 24VDC
Signal output
AS1670.4
Max. Output level
91 dBA @ 1 metre with detector
Evac
93 dBA @ 1 metre with lid
Volume control
-30dBA
IP rating
IP42
Temperature range
-20 to + 70°C
ConstructionABS
Dimension (mm)
106Ø x 35h (Sounder & lid only)
205-0064
205-0065
205-0066
205-0067
4107-5001
Vector Sounder Vector Sounder Lid
205-0077
205-0017
www.ampac.net
82 Audio Visual & Interafaces
83
Conventional Audio Visual
Remote Indicators
Vantage Dual LED Beacon
Fire Alarm Remote Indicator - Round
The Vantage Dual LED Beacons are designed for use with the EV3000 Emergency
Warning and Intercommunication Systems. Incorporating the latest in LED
technology, the Vantage beacon offers maximum all-round visibility in an aesthetically
pleasing body with minimum power requirements. The low current features of the
product allow installers to use a larger number of visual devices on the EV3000 which
negates the need for additional output circuits and power supplies.
Ampac offer a range of remote indicators which are designed for fire detection
systems requiring local indication of an individual or group of detection devices
located in concealed areas. Applications include floor and ceiling voids spaces, roof
spaces, lift shafts and escalator machine rooms.
Operating Voltage
Supply Current
Flash Rate
Operating Temp.
Humidity
Material
Dimensions
Flush
Surface IP rating
Weight
18 - 35V DC
9mA
T3 Temporal (red), 1Hz (amber)
-20°C +70°C
0 to 95% Non-condensing
ABS fire retardant plastic
Voltage
Current at 24v
Size
Weight
Remote Indicator – Fire Alarm in Concealed Space
Remote Indicator – Fire Alarm in Roof Space
Remote Indicator – Fire Alarm in Room
Remote Indicator – Fire Alarm in Duct
Remote Indicator – Fire Alarm in Cupboard
Remote Indicator – Fire Alarm Under Floor
Remote Indicator – Fire Alarm in Return Air
Remote Indicator – Fire Alarm in Exhaust Duct
Remote Indicator – Fire Alarm in Supply Air Duct
Remote Indicator – Fire Alarm in Ceiling
Remote Indicator – Fire Alarm Above
Remote Indicator – Fire Alarm
Remote Indicator – Detector Activated
188mm L x 94mm W x 62mm H
188mm L x 94mm W x 80mm H
IP43 (shallow), P65 (deep)
215g (shallow), 235g (deep)
Dual LED Beacon Shallow Base
Dual LED Beacon Deep Base 24 VDC
1.5mA
74mm Dia x 16mm H
26 grams
4107-1005
4107-1006
209-0004
209-0005
209-0006
209-0007
209-0008
209-0009
209-0010
209-0011
209-0012
209-0013
209-0014
209-0020
209-0023
Beacon / Strobe Sign Plate
The beacon / strobe sign plate mounts directly behind the single Beacon or Sounder/
Beacon and is generally located outside the main entrance to the building to attract
the attention of approaching fire fighters.
Indicator / Buzzer & Indicator / Buzzer with Mute
Fixing
Strobe / Beacons
Material
Size
••
••
••
••
Directly behind the Sonos Model
Painted metal 1mm
120mm W X 160mm H
Vantage Sounder / Beacon FIRE Legend Plate
ASL-86 Strobe FIRE Legend Plate
4210-0048
4210-0049
Xenon Strobes
AMPAC offer the flexibility of individual red and amber strobes or a combined red/
amber strobe unit, complete with mounting box and terminals.
Voltage
24 VDC
Current140mA
Rating
10 Watts
Size inc base
100Dia x 88H mm
Flash rate
75 per minute
Operating temperature
-20°C to + 60°C
IP rating
IP65
Weight – strobe
182 grams
Weight – combined unit
719 grams
24V Strobe Light Red ASL86
24V Strobe light Amber ASL86
24V Strobe Light Combined Red/Amber
www.ampac.net
Alarm activation indicator and buzzer
10mm red flashing LED
Buzzer (with mute facility)
Modern styling
Indicator / Buzzer
Voltage
24 VDC
Current at 24v
27mA
LED flash rate
45 per minute
Buzzer
3.8kHz @ 114dBA
Size
70H x 110W x 10D mm
Weight64g
Indicator / Buzzer with Mute
Voltage
24 VDC
Current at 24v
43mA
LED flash rate
45 per minute
Buzzer
3.8kHz @ 114dBA
Size
70H x 110W x 10D mm
Weight89g
Flashing Indicator / Buzzer
Flashing Indicator / Buzzer with Mute Switch
209-0017
209-0016
208-0007
208-0008
208-0011
www.ampac.net
84 Audio Visual & Interafaces
85
Bells
Warning Signs
Fire Alarm Bell 150mm
The Fire Alarm Bell is a motorised, maintenance free bell designed for fire alarm
applications. Its low current consumption, ease of installation incorporating diode
polarity suppression and universal recognisable bell sound, makes it an ideal choice
for fire alarm installations.
Voltage
Operating current
Size (without back box)
Sound level
Operating temperature
Weight
12V DC or 24V DC
55mA or 25mA
150mm Dia x 56mm D
92 dB @ 1m
-10°C to +55°C (no icing)
764 grams
AFB-63 Bell 150mm Red 24VDC
AFB-63 Bell 150mm Red 12VDC
206-0012
206-0011
Fire Alarm Bell 200mm
The Fire Alarm Bell incorporates a solenoid actuation mechanism and is designed for
fire alarm applications. Its low current consumption, ease of installation incorporating
diode polarity suppression and traditionally recognisable bell sound, makes it an ideal
choice for fire alarm installations.
Voltage
19-27 VDC
Operating current
100mA
Size (without back box)
200mm Dia x 70mm D
Sound Level
85 dB @ 3m
Operating temperature
-20°C to +70°C (no icing)
Weight1.25kg
Bell 200mm 24v dc Red
206-0011
Product Overview
The Ampac range of Warning Signs offer state of the art LED technology for a variety of applications in a highly aesthetic
design. The slimline enclosure can easily be adapted to surface or semi-flush mounting while a range of standard fascia plates
has been developed to suite Agent Release applications. A weatherproof version is also available along with custom legend
fascia plates.
A maximum of 6 Warning Signs can be connected to the output of each Agent Release module located within the ZoneSense,
FireFinder or LoopSense fire control panels.
••
••
••
••
••
••
••
••
••
••
••
Low Power Consumption
High Efficiency LED Indications
Aesthetically Pleasing
Two or Three Wire Connectivity
Single or Dual Level Operation
Continuous or Flashing LED Operation
Synchronisation between Signs
Integral Buzzer with Mute Facility
External Sounder Output
Surface or Semi-Flush Fixing
Waterproof Version
4210-0110
4210-0120
Operating Voltage
Power Consumption
Surface mounting of bell box designed for use with the 150mm and 200mm Bell.
Humidity
IP rating
Dimension (mm)
Level 1 & 2 active – 100mA at 24 Vdc
-20°C to +55°C
0% to 95% non condensing
4210-0110 – IP30
Material
Material
Cast Aluminium
FinishRed
Depth
40 mm
Weight
270 grams
www.ampac.net
Level 1 active – 50mA at 24 Vdc
Operating Temperature
Bell Back Box
Bell Back Box
17 Vdc to 29 Vdc
4210-0120 – IP65
ABS Enclosure / Acrylic Fascia
4210-0110 – 195H x 325W x 50D
4210-0120 – 212H x 338W x 67D
Item Numbers
206-0006
Warning Sign (no fascia plate)
Warning Sign IP65 (no fascia plate) ‘Fire Alarm - Do Not Enter’ (fascia plate only) ‘Fire Alarm - Evacuate Area’ (fascia plate only) ‘Do Not Enter - Gas Discharged’ (fascia plate only) ‘Fire Door Closing’ (fascia plate only) ‘Extinguishing System Inoperative’ (fascia plate only) Custom Legend (specify text)
Wall / Ceiling Mount Surround - Smart Term/Warning Sign
Dual Ceiling Mount Surround for Warning Sign
4210-0110
4210-0120
4210-0131
4210-0132
4210-0133
4210-0134
4210-0135
4210-0136
4210-0046
4210-0047
www.ampac.net
86 Audio Visual & Interafaces
87
Speakers
One-Shot Ceiling Speaker
Surface Speaker - 100mm
The 100mm and 200mm One Shot ceiling speakers are ideal for use in a wide range
of applications including Emergency Warning Systems (EWS), Background Music and
Public Address (PA) paging within shopping centres, offices and hotels. The One Shot
speaker units install in seconds. They simply snap fit to any 10-13mm thickness ceiling
by means of the 3 integral pressure clips.
The Surface Mount 100mm Speaker is an excellent choice for use in plant rooms,
warehouses, shopping centres and malls. The custom designed speaker and
transformer assembly has been engineered to meet Australian Fire Evacuation
Standards
Rated Power
Line Voltage
Frequency R esponse
SPL
Speaker Tap (watt)
Cut-out size
Dimensions
Weight
Driver
Power taps
SPL 1W @ 1m
Frequency response
Connection
5 watts
100 Volt
100 Hz to 15 kHz
98 dB (1 watt @ 0.5m)
0.33, 0.66, 1.25, 2.5, 5
140 mm Diameter
155 x 110 Hmm
850 grams
Ceiling Speaker – 100mm One-Shot (White)
Ceiling Speaker – 100mm One-Shot (Black)
Ceiling Speaker – 200mm One-Shot (White)
One Shot Combo Speakers (Box Qty 32)
One Shot Combo Grills (Box Qty 32)
Surface Speaker – 100mm
218-0026
218-0031
218-0032
4113-1001
4113-1002
The EasyFit range of Ceiling Speakers are lightweight, quick and easy to install, and
are finished in unobtrusive white with an attractive metal grille. The EasyFit Ceiling
Speaker offers a wide frequency range along with good sound dispersion ensuring
quality music reproduction and excellent speech intelligibility.
The 100mm speaker is ideal for use in a wide range of applications including
Emergency Warning Systems (EWS), Background Music and Public Address (PA)
paging within shopping centres, offices and hotels.
5 watts
100 Volt
100 Hz to 20 kHz
96 dB (1 watt @ 0.5m)
0.33, 0.66, 1.25, 2.5, 5
85 mm Diameter
100 x 105 Hmm
800 grams
Driver
Maximum/rated power
Power taps
Frequency Range
Axial sensitivity 1W/1m/1kHz
Opening Angle( -6dB)
Ceiling Speaker – 100mm Recessed
Low Profile Grill
218-0008
218-0003
The 200mm speaker is ideal for use in a wide range of applications including
Emergency Warning Systems (EWS), Background Music and Public Address (PA)
paging within shopping centres, offices and hotels.
Rated Power
Line Voltage
Frequency R esponse
SPL
Speaker Tap (watt)
Cut-out size
Dimensions
Weight
Ceiling Speaker – 200mm Recessed
Low Profile Grill
www.ampac.net
Ceiling cutout diameter
Overall dimensions
Safety
Ceiling Speaker - 200mm Recessed
5 watts
100 Volt
100 Hz to 20 kHz
96 dB (1 watt @ 0.5m)
0.33, 0.66, 1.25, 2.5, 5
190 mm Diameter
200 x 75 Hmm
1 kg
218-0022
EasyFit Ceiling Speakers
Ceiling Speaker – 100mm Recessed
Rated Power
Line Voltage
Frequency R esponse
SPL
Speaker Tap (watt)
Cut-out size
Dimensions
Weight
100mm (4”) dual cone
0.33, 0.66, 1.25, 2.5, 5W
90dB @ 1kHz (+/- 2dB)
100Hz-15kHz
4 way terminal block + 22uF bipolar capacitor
4 Inch 5 Watt
6 Inch 10 Watt
8 Inch 15 Watt
8 Inch 30 Watt
4”
6.5”
8”
8”
8W/5W
15W/10W
22W/15W
45W/30W
5, 2.5, 1.25, 0.66, 0.33W
10, 5, 2.5, 1.25W
15, 10, 5, 2.5, 1.25W
30, 15, 7.5, 3.75W
100Hz - 15kHz
60Hz - 20kHz
50Hz - 17kHz
50Hz - 17kHz
94dB SPL
91dB SPL
93dB SP
93dB SPL
144° / 93° at 1kHz / 4kHz
170° at 1kHz
165° at 1kHz
100° at 1kHz
140mm
195mm
238mm
238mm
170mm x 110mm
220mm x 115mm
273mm x 103mm
273mm x 115mm
acc to EN 60065
acc to EN 60065
acc to EN 60065
acc to EN 6006
Ceiling Speaker, Easyfit 5w 4” - EVAC
Ceiling Speaker, Easyfit 5w 5” - Brilliant White
Ceiling Speaker, Easyfit 5w 5” White
Ceiling Speaker, Easyfit 10w 6.5”
Ceiling Speaker, Easyfit 15w 8” White
Ceiling Speaker, Easyfit 30w 8” White
218-0041
218-0042
218-0043
218-0044
218-0045
218-0046
218-0009
218-0021
www.ampac.net
88 Audio Visual & Interafaces
89
Addressable Audio & Visual
Speakers
Horn Speaker - 10 Watt
Integrated Sounder Base
The Ampac 10 Watt/ 20 Watt Horn Speaker is specifically designed for distributed
Public Address (PA) and Emergency Warning Systems (EWS) with frequency response
characteristics ensuring clear speech reproduction during announcements.
The Integrated Sounder Base comprises a base sounder with integral mounting base
and is for use with Discovery or XP95 ranges. It is designed for indoor use.
Rated Power
Line Voltage
Frequency R esponse
SPL
Speaker Tap (watt)
Dispersion angle
Material
IP Rating
Dimensions
Weight
Horn Speaker – 10 Watt
Horn Speaker – 20 Watt
Horn Speaker Bracket Wurli-Gig
10 watts
100 Volt
250 Hz to 13 kHz
105 dB (1 watt @ 1m)
1.25, 2.5, 5, 7.5, 10
110°
UV stabilised plastic
IP65
150 Dia x 190 Dmm
1.4 kg
www.ampac.net
201-0110
201-0114
218-0028
218-0007
218-0040
Addressable Beacon Base
The High Efficiency Ampac 10 and 20 watt horn loudspeaker is specifically designed
for distributed Public Address (PA) and Emergency Warning Systems (EWS) with
frequency response characteristics ensuring clear speech reproduction during
announcements.
Horn Speaker Bosch Easy Fit 10W IP66 Grey
Horn Speaker Bosch Easy Fit 20W IP66 Grey
17-28 VDC
1.2mA
5mA
92dB(A)
-20°C to +60°C (no icing)
0 to 95% (non condensing)
IP21D
115Dia x 38H mm
140 grams
Integrated Base Sounder
White Cap
Horn Speaker - 10 Watt / 20 Watt
Rated input
Power handling
Power taps
SPL at Rated Power (10W @ 1m)
SPL at Rated Power (1W @ 1m)
Frequency Range (-10dB)
Dispersion Angle(-6dB)
Weight
Voltage (polarity sensitive)
Quiescent current
Max current (sounder operated)
Max sounder output
Operating temperature
Relative humidity
IP rating
Size
Weight
10 Watt
20 Watt
100V100V
10W20W
10, 7.5, 5, 2.5,
20, 15. 10,
1.257.5, 5W
119 dB
124 dB
108 dB
110 dB
300Hz - 13kHz
9kHz
140°@1kHz
90°@1kHz
1.3KG 2.1KG
218-0047
218-0048
The Beacon Base is a loop-powered beacon combined with a standard Intelligent
Mounting Base. It is used to signal a fire alarm in enclosed areas. The Beacon Base can
be used either with a detector fitted or with a cap for operation as a stand-alone alarm
device.
Voltage (polarity sensitive)
Quiescent current
Max current (sounder operated)
Max sounder output
Operating temperature
Relative humidity
IP rating
Size
Weight
Beacon Base
White Cap
17-28 VDC
300μA at 24V DC
3.1mA at 24V DC
92dB(A)
-20°C to +60°C (no icing)
0 to 95% (non condensing)
IP21D
115mm Dia x 31mmH
109 grams
201-0120
201-0114
www.ampac.net
90 Audio Visual & Interafaces
91
Addressable Audio & Visual
Sounder Beacon Base
Intelligent Open-Area Beacon
The Sounder Beacon Base is a loop-powered sounder and beacon combined with a
standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas.
The Sounder Beacon Base can be used either with a detector fitted or with a cap for
operation as a stand-alone alarm device.
The Intelligent Open-Area Beacon has been developed for use in situations where
there is a risk that sounders will not be heard. It is weatherproof and can be used
outside.
Voltage (polarity sensitive)
Quiescent current + Beacon
Max current (sounder operated)
Max current (beacon only)
Max sounder output
Operating temperature
Relative humidity
IP rating
Size
Weight
17-28 VDC
300µA
8mA
3.1 mA
91dB(A)
-20°C to +60°C (no icing)
0 to 95% (non condensing)
IP21D
115Dia x 38H mm
160 grams
Sounder Beacon Base
Beacon Base
White Cap
17-28 VDC
333µA
3.1mA
1Hz
-10°C to +55°C (no icing)
0 to 95% (non condensing)
IP65
104Dia x 97.5H mm
205 grams
Intelligent Open Area Beacon (Red) Sonos
Intelligent Open Area Beacon (Clear) Sonos
208-0100
208-0101
201-0116
201-0120
201-0114
Loop-Powered Beacon
Intelligent Open-Area Sounder / Sounder Beacon
The Loop-Powered Beacon is a local-area beacon designed for indoor use. The beacon
has been developed as a supplement to sounders for use in situations where there is a
risk that sounders will not be heard.
The Intelligent Open-Area Sounder /Sounder Beacon has been designed for use in
open areas and can be connected to any Discovery or XP95 system.
Voltage (polarity sensitive)
Quiescent current
Max current (beacon operated)
Flash rate
Operating temperature
Relative humidity
IP rating
Size
Weight
17-28 VDC
150µA
3mA
1Hz
-20°C to +60°C (no icing)
0 to 95% (non condensing)
IP23D
115Dia x 38H mm
140 grams
Loop-Powered Beacon (Red)
Loop-Powered Beacon (Amber) Standard Flash
Loop-Powered Beacon (Clear Lens/Red Flash) Standard Flash
www.ampac.net
Voltage (polarity sensitive)
Quiescent current
Max current (beacon operated)
Flash rate
Operating temperature
Relative humidity
IP rating
Size
Weight
201-0118
201-0156
201-0157
SounderSounder/Beacon
Voltage (polarity sensitive)
17-28 VDC
Quiescent current
333µA
Max current
5mA8mA
(sounder/beacon operated)
Max sounder output
-
1Hz
Operating temperature
-10°C to +55°C (no icing)
Relative humidity
0 to 95% (non condensing)
IP rating
IP65
Size
104Dia x 97.5H mm
Weight
225 grams
260 grams
Intelligent Open Area Sounder (Red) Sonos
Intelligent Open Area Sounder (White) Sonos
ntelligent Open Area Sounder Beacon (Red) Sonos
Intelligent Open Area Sounder Beacon (Clear) Sonos
205-0100
205-0101 I
205-0102
205-0103
www.ampac.net
92 Audio Visual & Interafaces
93
Hazardous Area - Intrinsically Safe
Hazardous Area- Flameproof Equipment
Product Overview
The Intrinsically Safe range of products includes the compact I.S. Sounder, I.S. Beacon and I.S. Sounder / Beacon. The range is
suitable for all intrinsically safe signalling applications including fire, security and process control. Approvals include ATEX and
IECEx and GOST-R for Zone 0 applications and FM approval for Class I Division 1 and Class I Zone 0 applications. The I.S. Beacon
optimises the effectiveness of its six high output LEDs via a prismatic lens design.
The I.S. combined Sounder and Beacon requires only one Zener barrier or galvanic isolator to run both sounder and beacon
or alternatively the unit can be operated as individual signals. Power to the I.S. range should be via a certified zener barrier or
galvanic isolator whose output parameter is no greater than, Uo=28v dc, Io=93mA,and Po=660mw. The beacon is internally
input overload and reverse polarity protected and is end of line monitoring resistor certified.
••
••
••
••
••
Input Overload and Reverse Current Protection
End of Line Resistor Certified
ATEX and IECEx approval
2 x M20 clearance gland knockouts
Auto Synchronised Sound Output (exc. Beacon)
Voltage Range
25mA at 24V DC
-
Flash Rate
-
Number of Tones
Temperature range
Beacon
Sounder/Beacon
16-28Vdc via Zener barrier or galvanic isolator
Energy
Sound Output (nominal) at 1m +/- 3dB – Tone 2
The flameproof range of products is ideal for hazardous areas, specifically Zone 1 and 2 applications. The use of flameproof
technology ensures that engineers installing into hazardous areas need not fit an intrinsically safe barrier and the associated wiring requirements. Sound level outputs are up to 117dB(A) at 1 metre with a choice of 32 alarm tones and 3 remotely
selectable stages.
Housings are manufactured from corrosion proof, marine grade copper free LM6 aluminium which is phosphated and powder
coated. All models have two M20 cable entries, large termination areas and an ingress protection of IP66/67. Two entry points
for cabling are present for IN and OUT wiring, thus eliminating the requirement for additional flameproof junction boxes.
Sounder
Nominal Current Consumption
Product Overview
25mA at 24V DC
30mA at 24V DC
double flash at 2Hz and 1Hz
23cd
23cd
100dB(A)
100dB(A)
49
49
••
••
••
••
••
••
••
ATEX and IECEx approval
Rapid installation with no barrier requirements
Suitable for Zone 1 & 2 flameproof applications
Large termination area
Ratchet adjustable stainless steel ‘U’ bracket
Synchronisation on multi-sounder systems
Sounders have 32 synchronised tones available
Voltage Range
Nominal Current Consumption
-40 to +60°C
Beacon
Sounder
Sounder/Beacon
20-28V DC
20-28V DC
20-28V DC
300mA
265mA
565mA
Protection rating
IP65
Energy
5 joules (5Ws)
-
5 joules (5Ws)
Boxed weight
Red
Flash Rate
1Hz (60 fpm)
-
1Hz (60 fpm)
Body Colours
Red, Amber, Clear
Sound Output (nominal) at 1m +/- 3dB – Tone 2
-
110dB(A)
110dB(A)
Number of Tones
-
32
32
-50 to +70°C
-50 to +70°C
-50 to +70°C
Protection rating
P66/67
IP66/67 I
P66/67
Boxed weight
2.45Kg
3.2Kg
4.8Kg
Item Numbers
I.S. Sounder Red Body
I.S. Beacon Red Body, Red Lens
I.S. Beacon Red Body, Amber Lens
I.S. Beacon Red Body, Clear Lens
I.S. Sounder Beacon Red Body, Red Lens
I.S. Sounder Beacon Red Body, Amber Lens I.S. Sounder Beacon Red Body, Clear Lens
Sounder/Beacon Solenoid Driver Single Channel Sounder/Beacon Solenoid Driver Dual Channel
Sounder Circuit Zener Barrier
www.ampac.net
Temperature range
205-0114
208-0201
208-0202
208-0203
205-0111
205-0115
205-0116
205-0112
205-0117
205-0118
Body Colours
Red
Item Numbers
BEx Flameproof Sounder Red Body
BEx Flameproof Beacon Red Body, Red Lens
BEx Flameproof Sounder Beacon Red Body, Red Lens
205-0113
208-0200
205-0110
www.ampac.net
94 Cable
95
2 Core TPS Cable
Specifications
Item Number
9000-4201-0200
Cross Section
mm2
Conductor
Strands/ Dia
Core
Configuration
Stripe Colour
Overall Size
mm
Std Drum
Length
Std Drum
Length
0.75
7 / 0.37
Flat
-
6.2 x 4.0
200M
50
9000-4201-0500
0.75
7 / 0.37
Flat
-
6.2 x 4.0
500M
50
9000-4202-0200
0.75
7 / 0.37
Flat
White
6.2 x 4.0
200M
50
9000-4202-0500
0.75
7 / 0.37
Flat
White
6.2 x 4.0
500M
50
9000-4203-0200
0.75
7 / 0.37
Flat
Yellow
6.2 x 4.0
200M
50
9000-4203-0500
0.75
7 / 0.37
Flat
Yellow
6.2 x 4.0
500M
50
9000-4204-0200
0.75
7 / 0.37
Flat
Blue
6.2 x 4.0
200M
50
9000-4204-0500
0.75
7 / 0.37
Flat
Blue
6.2 x 4.0
500M
50
9000-4205-0200
1.0
7 / 0.43
Flat
White
7.1 x 4.2
200M
54
9000-4205-0500
1.0
7 / 0.43
Flat
White
7.1 x 4.2
500M
54
9000-4206-0200
1.5
7 / 0.505
Flat
-
8.0 x 5.0
200M
75
9000-4206-0500
1.5
7 / 0.505
Flat
-
8.0 x 5.0
500M
75
9000-4207-0200
1.5
7 / 0.505
Flat
White
8.0 x 5.0
200M
75
9000-4207-0500
1.5
7 / 0.505
Flat
White
8.0 x 5.0
500M
75
9000-5203-0200
1.5
7 / 0.505
Twisted
-
7.5 x 6.5
200M
80
9000-5203-0500
1.5
7 / 0.505
Twisted
-
7.5 x 6.5
500M
80
9000-6203-0200
1.5
7 / 0.505
Screened
-
7.6
200M
93
9000-6203-0500
1.5
7 / 0.505
Screened
-
7.6
500M
93
Product Overview
AMPAC Safety’s CableSAFE cables are manufactured and approved for use in Fire Detection and Emergency Warning Systems.
CableSAFE cables are available with coloured sheath stripes on Red Sheath to differentiate between detector and ancillary
circuits. A twisted version is available for use in addressable loop cabling when reduced line noise is essential.
••
••
••
••
••
••
••
Red Sheath for Fire Alarm Application as specified for Fire Alarm use
White, blue or yellow stripe on red sheath for fire related systems
StripEasy Sheath
Metre markings
Available in flat and twisted
AS/CAS008 compliant
200m and 500m rolls available
Approved to:
AS/NZS5000.2 Cable Construction
AS/CAS008 ACMA Compliance N31145
AS/NZS1125 Conductors
AS/NZS3808 Insulation & Sheath
Applications
Fire Systems
Warning Systems
••
••
••
••
••
••
••
••
••
••
••
Addressable Loop
Addressable Interfaces
Conventional Zones
Sounders & Bells
Door Holders
Remote Indicators
Agent Release
Warning Signs
www.ampac.net
Ceiling Speakers
Horn Speakers
Visual Warning Devices
Item Numbers
2 Core TPS Cable
TPS Flat 2c 0.75mm‚ - 200M
TPS Flat 2c 0.75mm‚ - 500M
TPS Flat 2c 0.75mm‚ White Stripe - 200M
TPS Flat 2c 0.75mm‚ White Stripe -500M
TPS Flat 2c 0.75mm Yelllow Stripe - 200M
TPS Flat 2c 0.75mm Yelow Stripe - 500M
TPS Flat 2c 0.75mm Blue Stripe - 200M
TPS Flat 2c 0.75mm Blue Stripe - 500M
TPS Flat 2c 1.0mm‚ White Stripe - 200M
TPS Flat 2c 1.0mm‚ White Stripe - 500M
TPS Flat 2c 1.5mm‚ - 200M
TPS Flat 2c 1.5mm‚ - 500M
TPS Flat 2c 1.5mm‚ White Stripe -200M
TPS Flat 2c 1.5mm‚ White Stripe - 500M
9000-4201-0200
9000-4201-0500
9000-4202-0200
9000-4202-0500
9000-4203-0200
9000-4203-0500
9000-4204-0200
9000-4204-0500
9000-4205-0200
9000-4205-0500
9000-4206-0200
9000-4206-0500
9000-4207-0200
9000-4207-0500
TPS Twisted 2c 1.5mm‚ - 200M
TPS Twisted 2c 1.5mm‚ - 500M
TPS Twisted Screen 2c 1.5mm‚ -200M
TPS Twisted Screen 2c 1.5mm‚ - 500M
9000-5203-0200
9000-5203-0500
9000-6203-0200
9000-6203-0500
2 Core TPS Cable Halogen Free
TPS Flat Hal Free 2c 1.5mm- 500M
TPS Twisted Hal Free 2c 1.5mm - 200M
9000-7203-0500
9000-8203-0500
www.ampac.net
96 Ancillaries
Ancillaries
97
Electro-Magnetic Door Holders
Electro Magnetic Door Retainer
The AMPAC Door Retainer enables doors to be held open under normal conditions
and released during a fire alarm condition. They are simple to install and commission
and are suited to a wide range of applications including Hospitals, Schools,
Manufacturing Plants and Office Buildings.
Operating Voltage
15 to 29 VDC
Operating Current
55mA @ 24 VDC
Holding Force
50kg
Housing
White High Temperature ABS
Operating Temperature
-10° to +55° C
Dimension (mm)
100h x 100w x 50d
IP rating
IP 51
Weight
750 g
ApprovalC-Tick
Ampac Door Holder 24VDC 50KG
212-0012
Surface Mount Door Holder
The Surface Mount Door Holders combine good looks, high performance and
economy in a low profile package. Designed to allow doors to be held open under
normal conditions and released during a fire alarm condition, the Surface Mount
Door Holders are simple to install and commission and are suited to a wide range of
applications including:
Product Overview
Ampac offers a wide range of Ancillary devices for use in conjunction with its range of intelligent and conventional detectors
and control panels. A versatile and functional range offering a huge choice for any application.
Products incude:
••
••
••
••
••
••
E lectro magnetic door retainters
MultiAmp PSU
Key Holders
Wall Boxes
Document cabinets
Sealed Rechargable Lead-Acid Batteries
www.ampac.net
4101-
1001/3/4 1002/5
Operating Voltage 24V dc 230V ac
Current 50mA 12mA
Dimensions (mm)
ABS
87 W x 95 H x 46 D
Steel
86 W x 86 H x 62 D
Manual Release Yes
Operating Temp. -10° to +50°C
IP rating IP51
Finish White Fire Resistant ABS
ApprovalsEN1155
Surface Mount 200N 24V ABS Case Door Holder
Surface Mount 200N 230V ABS Case Door Holder
Surface Mount 500N 24V ABS Case Door Holder
Surface Mount 200N 24V Steel Case Door Holder
Surface Mount 200N 230V Steel Case Door Holder
Adjustable Keeper Plate 4101-1001
4101-1002
4101-1003
4101-1004
4101-1005
4101-6004
www.ampac.net
98 Ancillaries
99
Electro-Magnetic Door Holders
Flush or Surface Mount- Metal Case
Universal Door Holder
The Flush Mount Door Holder is built around a robust fascia plate for flush mounting
on a back box. The Surface Mount unit is supplied with a back box incorporating
20mm knockouts. Designed to allow doors to be held open under normal conditions
and released during a fire alarm condition, the Door Holders are simple to install and
commission and are suited to a wide range of applications including:
The Universal Door Holder is designed for floor, ceiling or wall mount applications and
enables doors to be held open under normal conditions and released during a fire
alarm condition. The Universal Door Holder is simple to install and commission and is
suited to a wide range of applications including:
4101- 3001/1004
3005/1005
Operating Voltage 24V dc
230V ac
Current 50mA 12mA
Dimensions (mm)
Flush Mount
86 W x 86 H x 43 D
Surface Mount
86 W x 86 H x 62 D
Manual Release
Yes
Operating Temp
-10° to +50°C
IP rating
IP51
Finish
Nickel Coated Painted White
ApprovalsEN1155
Flush Mount 200N 24Vdc Door Holder
Flush Mount 200N 230Vac Door Holder
4101-3001
4101-3005
Universal Mount 500N Short Stand 24V Door Holder
Universal Mount 500N Long Stand 24V Door Holder
Universal Mount 1000N Short Stand 24V Door Holder
Universal Mount 1000N Long Stand 24V Door Holder
4101-4001
4101-4002
4101-4003
4101-4004
Floor Mount Door Holder
Decorative Flush or Surface Mount
The Floor Mount Door Holder features rugged cast aluminium housing, a holding
electromagnet with integral anti-residual ejection pin and a manual release switch.
Decorative Door Holders are particularly suitable for installation in prestigious projects
such as Hotels, Offices, Historical Buildings and Museums. Built around a robust fascia
plate for flush mounting and supplied with a back box, the Door Holders are available
in Bright Chrome, Lacquered Brass or Stainless Steel finish with matching Decorative
Keeper Plate.
4101-
2001/3 4 1002/4
Operating Voltage
24V dc Current 45mA
90mA
Dimensions (mm)
110 W x 95 H x 96 D
Manual Release Yes
Operating Temp.
-10° to +50°C
IP rating
P51
Finish
Aluminium White
Housing
Zinc Plated Magnet
Approval EN1155
Floor Mount 200N 24V Cast Aluminium Door Holder
Floor Mount 500N 24V Cast Aluminium Door Holder
Floor Mount 200N 24V Vandal Proof Door Holder
Floor Mount 500N 24V Vandal Proof Door Holder
www.ampac.net
4101-
4001 / 02 4003 / 04
Operating Voltage
24V dc
Current 43mA
76mA
Stand Length (mm)
Floor Mount H1
183 / 282
Steel
250 / 350
Manual Release
Yes
Operating Temp
-10° to +50°C
IP rating
IP51
Finish
Nickel Coated Painted White
ApprovalEN1155
* For product specifications, please refer to the Product Data Sheet.
4101-2001
4101-2002
4101-2003
4101-2004
4101- Operating Voltage Current Dimensions (mm)
Flush Mount Surface Mount
Manual Release Operating Temp. IP rating Approval 3002/03/04
24V dc
50mA
3006/07/08
230V ac
12mA
86 W x 86 H x 24 D
86 W x 86 H x 62 D
Yes
-10° to +50°C
IP51
EN115
Chrome Flush Mount 24V Door Holder
Brass Flush Mount 24V Door Holder
Stainless Steel Flush Mount 24V Door Holder
Chrome Flush Mount 230V Door Holder
Brass Flush Mount 230V Door Holder
Stainless Steel Flush Mount 230V Door Holder
Chrome Surface Mount Kit
Brass Surface Mount Kit
Stainless Steel Surface Mount Kit
Brass Keeper Plate
Stainless Steel Keeper Plate
Bright Chrome Keeper Plate
4101-3002
4101-3003
4101-3004
4101-3006
4101-3007
4101-3008
4101-6005
4101-6006
4101-6007
4101-6008
4101-6009
4101-6010
www.ampac.net
100 Ancillaries
101
Electro-Magnetic Door Holders
Power Supplies
Weatherproof IP65
MultiAmp-DH
The Weatherproof Door Holder is ideal for most applications in all types of buildings
while its high level of ingress protection means it is particularly suited to use outdoors
and in marine type applications.
Remotely releases fire doors held open by electro magnetic door holder.
Operating Voltage Current Dimensions (mm)
Assembly
Keeper Plate
Magnet Weight
Manual Release
Operating Temp. IP rating Finish IP65 Protected 1200N 24Vdc
IP65 Protected 1200N 230Vac
4101-5001
24V dc 300mA 4101-5002
230V ac
45mA
Ø 102 x 45
Ø 89 x 42
2.0kg
No
-10° to +50°C
IP65
Zinc Plated Steel
Material
High Impact ABS
FinishWhite
Dimension
(Recessed)
91mm H X 149mm W x 40mm D
(Surface)
91mm H X 149mm W x 53mm D
Weight
400g packed
Mains Supply Voltage
230 VAC +/- 10% @ 47-63Hz
Door Holder Output Voltage
24 VDC @ 250mA
Operating Temperature
-5° to +45° C
Relative Humidity
25% to 95%
MultiAmp-DH 250MA Flush Mount
MultiAmp-DH 250MA Surface Mount
4510-1100
4510-1101
4101-5001
4101-5002
Floor Mount Bracket
A floor mounting bracket is available for the Surface Mount Door Holders. With this
the Door Holder can be mounted in any convenient position on the floor to suit the
door. It is supplied in a white finish with mounting instructions and is compatible with
standard conduit back boxes.
Floor Mounting Bracket
4101-6001
Remote Door Release
Remotely releases fire doors held open by electro magnetic door holder.
Remote Door Release Plate Vertical Screen
Remote Door Release Plate Horizontal Screen
268-0003
268-0010
Chain Keeper Plate
The Chain Keeper enables a wall mounted electromagnetic door holder to be used
even when the door will not open fully to meet the magnet. It is a very flexible
solution to awkward mounting. A one metre length of chain is supplied as standard.
Keeper Plate and Mounting with 1M Chain
4101-6002
Document Cabinets
AMPAC offers ABS and metal document cabinets designed to complement the range
of AMPAC’s fire control panels. The cabinets can hold in excess of 100 A4 sheets of fire
and security information relevant to the premises.
Low Profile Keeper Plate
The non-adjustable, slim style keeper plate is for use with 200N Door Holders. It is
an alternative to the standard adjustable keeper design where the gap between the
door and the magnet needs to be kept to a minimum.
Low Profile Keeper Plate 200N
www.ampac.net
4101-6003
Dimensions
IP Rating
Weight
Document Cabinet ABS Document Cabinet Metal Cool Grey
Document Cabinet Metal White
ABS – 300mm H x 360mm W x 100mm D
Metal – 295mm H x 356mm W x 92mm D
IP30
ABS – 1kg
Metal – 3kg
4210-0010
4210-0020
4210-0021
www.ampac.net
102 Ancillaries
103
Power Supplies
Batteries
Sealed Rechargeable Lead-Acid Batteries
Ampac sells a comprehensive battery range for all applications requiring a reliable
rechargeable power source. The wide range of sizes coupled with good cycling ability
make them perfect for critical systems such as fire alarm and emergency warning
systems. Designed using VRLA technology, negating the need to add water, these
batteries can be applied in many critical systems requiring reliable reserve power.
Available as 12V or for very large systems 2 volt cells (x12).
Extra large 12 Volt (consideration of battery cabinet space required)
Product Overview
The MultiAmp PSU range of power supplies has been specifically designed for Fire System Installations and features intelligent
battery charging and monitoring with remote fault signalling. Available in 2A, 5A or 10A versions, the MultiAmp PSU range of
switch mode power supplies has been specifically designed for use with compliant fire detection and alarm systems.
The units include intelligent battery charging using efficient EcoCharge technology, possess mains & battery monitoring with
independent voltage free relay outputs. The units also feature battery deep discharge protection in the event of a prolonged
mains failure. The inclusion of LED indicators provides quick diagnostics of the status of the power supply, while a variety of
enclosures offer the installer a choice of standby battery backup options.
••
••
••
••
••
••
••
27.6V dc output
Energy efficient operation
Cost effective switch mode technology
Intelligent battery charging and monitoring technology with Deep discharge protection
Mains AC transient protection
Remote fault signalling
Space for addressable loop interface module
Output (mains on)
27.6Vdc
Load Output
2.0, 5.0 & 10.0 Amps
Mains Supply
110V ac to 230V ac @ 50Hz
Environment
-10°C to 40°C @ 75%RH
Dimensions (mm)
12Ahr Enclosure
330W x 280H x 121D
38Ahr Enclosure
425W x 400H x 216D
65Ahr Enclosure
425W x 680H x 216D
IP rating
IP30
Material
1.6mm Mild Steel
Finish
Power coated - Surf Mist
Approval
Complies with AS7240.4
www.ampac.net
210-0008
210-0006
210-0016
210-0010
210-0003
210-0012
210-0013
210-0015
210-0004
12V 100AH SLA Battery
12V 160AH SLA Battery
12V 150AH SLA Battery
12V 230AH SLA Battery
210-0002
210-0022
210-0017
210-0011
2V 250AH SLA Battery
2V 300AH SLA Battery
2V 500AH SLA Battery
210-0018
210-0019
210-0020
Test Equipment
Detector Test Equipment
••
••
••
••
Item Numbers
2 Amp PSU - Space for 2 x 12Ahr Batts
2 Amp PSU - Space for 2 x 38Ahr Batts
5 Amp PSU - Space for 2 x 38Ahr Batts
10 Amp PSU - Space for 2 x 38Ahr Batts
5 Amp PSU - Space for 2 x 65Ahr Batts 10 Amp PSU - Space for 2 x 65Ahr Batts 12V 1.3AH SLA Battery
12V 3.2AH SLA Battery
12V 7AH SLA Battery
12V 12AH SLA Battery
12V 18AH SLA Battery
12V 26AH SLA Battery
12V 40AH SLA Battery
12V 65AH SLA Battery
12V 75AH SLA Battery 4510-8102
4510-8202
4510-8205
4510-8210
4510-8305
4510-8310
Access poles are used with interchangeable heads that fit onto the end of the pole.
The equipment is suitable for use on a wide range of detectors.
Poles are telescopic, nonconductive, toughened fibreglass.
Light weight and simple to use
Telescopic Pole 2.5M To 4 mtrs
Single Extension Pole - 1.13M
Universal Detector Removal Tool
Smoke Detector Test Dispenser
Heat Detector Tester 240V AC
Heat Detector Tester - cordless (head only)
Smoke Detector Test Set - 8.2 metre
Smoke & Mains Heat Tester Set - 6 metre
Smoke & Cordless Heat Tester Set - 4.5 metre
Battery Baton for Cordless Heat Tester
Smoke Detector Test Gas 250ml Aerosol Test Gas
Can Smoke 150ML (Handheld)
Carbon Monoxide Smoke Can Detector Tester (Test Pole)
204-0001
204-0002
204-0003
204-0004
204-0005
204-0017
204-0009
204-0010
204-0018
204-0021
204-0014
204-0015
204-0020
www.ampac.net
104 Ancillaries
105
Test Equipment
Ancillary Equipment
Smoke Pen
Wall Boxes
The Smoke Pen kit has been designed to provide a smooth, thin, non-volatile smoke
stream and is ideal for testing High Sensitivity Smoke Detectors promoted by Ampac.
The Smoke Pen incorporates a purpose designed dispenser which safely retains the
smoke stick for easy use during serving and commissioning of aspirating systems.
Each kit comes complete with five (5) smoke sticks offering over 4 hours of smoke
stop/re-start usage)
••
••
••
Smoke Pen
204-0030
Used for flush mounting devices such as manual call points and sounders
Suitable for MCP models ACP-01 & FP2
Suitable for ‘Vara’ sounder
Size Metal
Plastic
Weight Metal
Plastic
Wall Box Metal 25mm Deep for MCPs
Wall Box Plastic 35mm Deep for MCPs
268-0002
268-0009
Detector Base – Mounting Block
Flame Sensor Test Unit and Case
The Flame Sensor Test Kit is a tool which is designed to test flame detectors without
the need of real flames.
Flame Sensor Test Unit and Case
72mm H x 72mm W x 47mm D
72mm H x 72mm W x 35mm D
153 grams
47 grams
29600-226
•• The mounting block is recommended for use when detectors are installed on uneven surfaces
•• The mounting block ensures the correct fit with the base and the detector, improves reliability and ensures that the mounting tags on the base are not overtightened
•• Used with Base Mounted Flame Detector
Mounting Block For S65 / XP95 Base
201-0192
Void Fire Detector Holder
The Void Fire Detector Holder allows the installation of a fire detector within a sealed
ceiling space at variable heights. The holder enables easy inspection and maintenance
of the fire detector located within the ceiling void space from below ceiling level.
Discovery Programmer
The Discovery Programmer is a portable test and configuration tool for Discovery
smoke and heat detectors
Discovery Programmer
53832-030 EUR
Three models are available to suit various ceiling void heights from 0.6 metres to 3
metres.
••
••
••
••
Adjustable mounting tubes
Aesthetically pleasing
Fixing brackets included
Removable ceiling plate
Void Detector Holder 1 Metre
Void Detector Holder 2 Metre
Void Detector Holder 3 Metre
Key Holder – D2
Wilco Detector Bracket
••
••
••
••
••
The Willco Detector Bracket has been designed to allow installation of fire detectors
within a concealed ceiling space at variable heights. The bracket assembly enables
easy inspection and maintenance of the fire detector from below ceiling level.
Installation is quick and easy using the existing designated false ceiling hanger along
with readily available 20mm electrical conduit (not supplied).
Provides a visible place to locate a key used for emergency access
Red finish
Instructions on glass
Break glass operation similar to a manual call point
Suitable for indoor use
Size
100mm Dia x 32mm D
FinishRed
Weight
130 grams
Break Glass Key Holder D2
D2 Key Box Holder Spare Glass KP-308
www.ampac.net
4112-2001
4112-2002
4112-2003
••
••
••
215-0003
215-0004
Adjustable mounting heights
3 x Height adjustment brackets included
Manufactured from Galvanised Steel
Wilco Detector Bracket 4112-2008
www.ampac.net
106 Ancillaries
107
Ancillary Equipment
Deckhead Mounting Boxes
The Deckhead Mounting Box gives extra protection to devices to be fitted in areas
where there is the possibility of moisture or condensation ingressing through the rear
of the base. The new version is suitable for a wider range of detector bases as well as
Apollo’s AV bases.
••
••
••
Protects against water ingress.
Improved performance.
Available in polycarbonate or metal.
Deckhead Mounting Box
Metal Deckhead Mounting Box with PG16 Access Ports
Metal Deckhead Mounting Box with M20 Access Ports
Deckhead Adaptor
(for use with 29600-196 - converts cable glands from PG16 to M20)
201-0193
201-0195
201-0194
27249-005
Head Office - Perth
Ampac Technologies Pty Ltd
7 Ledgar Road, Balcatta, Western Australia, 6021
Telephone: +618 9201 6100
Fax: +618 9201 6101
Email: [email protected]
Web: www.ampac.net
Australia
New South Wales & Australian Capital Territory
Unit B, 28–32 Egerton Street, Silverwater, New South Wales,
2128
T: +612 8866 6200
F: +612 9648 4932
E: [email protected]
Northern Territory
2/10 Cato St, Winnellie, Northern Territory, 0820
T: +618 8911 1260
F: +618 8911 1261
E: [email protected]
Queensland
1/53 Parramatta Road, Underwood, Queensland, 4119
T: +617 3462 5700
F: +617 3208 9355
E: [email protected]
South Australia
63 Grange Road, Welland, South Australia, 5007
T: +618 8246 3800
F: +618 8340 4218
E: [email protected]
Victoria & Tasmania
345 Darebin Road, Thornbury, Victoria, 3071
T: +613 8459 3300
F: +613 8459 3301
E: [email protected]
As part of Ampac’s commitment to continuous improvement, specifications may change without notice. Version 15/09/15