Precision Cooling
For Business-Critical Continuity™
Liebert InteleCool ®2
Complete, Packaged Telecom Shelter Air Conditioning
Flexible Air Conditioning Designed For The
Needs Of Today’s Telecommunications Shelters
Choose The Cooling Solution
That’s Right For Your
Shelter Location
Liebert®, the first name in protection for sensitive
systems, has created the Liebert InteleCool®2
specifically for shelter air conditioning
applications. More than just a shelter air
conditioner, the Liebert InteleCool2 is a custom
configured cooling system that fits your exact
needs and budget. Designed with the flexibility to
match the needs of today’s telecommunications
industry, you pick the level of protection your
application requires and Liebert will configure a
Liebert InteleCool2 for you.
Higher Availability:
R-407C refrigerant meets new
government requirements.
High efficiency scroll compressor.
Optional aluminum exterior panels for
enhanced weather resistant cabinet.
Heavy-duty, double-width blower system.
Now You Can Custom-Configure Shelter Air
Conditioning To Your Exact Needs and Budget
Maximum Flexibility Designed To Meet All Your Shelter
Cooling Requirements
Painted steel or
aluminum cabinets
Heavy-duty double
width blower
Optional Economizer
with spring-return
actuator
Compressor placement
on right or left
side of unit
Copper-tube,
aluminum fin coils
Copper-tube, aluminum fin coils.
Designed for operation in low
ambient conditions.
Flexibility:
Five capacities ranging from 2 to 5 tons.
Easy service access — Compressor
locatedon either left or right side.
Low Total Cost Of Ownership:
A Perfect Match For Many Critical Applications
In addition to a wide range of telecommunications shelter
applications, the Liebert InteleCool2 can be used at
virtually any site that requires reliable cooling in a small,
lightweight package:
Economizer option utilizes outside air for
cooling to save energy.
Cellular
PCS Services
Radio Paging
Mobile/Modular
Self-contained unit minimizes
installation time.
Microwave/Satellite
Electronic Equipment
Earth Stations
Structures
2
Scroll Compressor
The scroll compressor is ideal in applications where noise is a factor thanks to its low noise and
vibration. The compressor may be located on either the right or left side of the unit to make it
easier to service dual installations.
Fresh Air Damper
If required by your application, this feature allows the introduction of outside air into the
shelter by means of a field-adjustable damper.
Controls
For the highest levels of reliability — and to minimize site downtime — critical shelters can be
equipped with two Liebert InteleCool® 2 units and an autochangeover system that balances
runtime and automatically switches from one unit to another unit if required.
Swift, Simple Installation
Economizer Option
However you configure the Liebert InteleCool 2, it comes
from the Liebert factory wired, piped, charged with R-407C
refrigerant and factory-tested as a complete system. Each
standard unit is shipped with a Nationally Recognized Testing
Laboratory (NRTL) listing. If the wall openings and electric
service are in place, the Liebert InteleCool 2 can be installed
in as little as 30 minutes.
The Liebert InteleCool 2 can be equipped with an economizer
system that uses modulating dampers to draw in filtered,
outside ambient air for cooling when the exterior temperature
drops below a pre-set level. These outside air temperature
settings are field adjustable. The economizer saves energy
and reduces component wear.
Installation time is minimized
with Liebert InteleCool2’s
self-contained packaging.
Industry-standard
evaporator supply and
return openings allow the
unit to be placed quickly.
No Economizer
When outside
temperatures
are warmer than
the inside air, the
Economizer is
closed and indoor
air is recirculated
to maintain
proper cooling.
Full Economizer
The Economizer takes
advantage of low
outdoor ambients,
drawing on this cool
air to maintain indoor
temperatures. The
result is cooling at lower
energy costs, also saving
wear on components.
Modulated
In Modulated
mode, the
Economizer
draws cool
outside air and
recirculates indoor
air, reducing
compressor
run time.
3
Specifications
Emerson Network Power
60Hz Models 95°F Outdoor Ambient, Net Capacity
Model
ET024
80°F DB/67°F WB (26.7°C DB/19.4°C WB)
Total BTU/H
21,400
Total kW
6.3
Sensible BTU/H
16,900
Sensible kW
5.0
75°F DB/62.5°F WB (23.9°C DB/16.9°C WB)
Total BTU/H
19,900
Total kW
5.8
Sensible BTU/H
16,400
Sensible kW
4.8
Weight
(Standard Unit) lbs.(kg)
330 (150)
(Unit w/Economizer) lbs.(kg)
350 (159)
ET036
ET048
ET060
32,900
9.6
23,800
6.9
45,600
13.4
34,600
10.2
53,800
15.8
37,700
11.1
30,700
9.0
23,100
6.8
42,300
12.4
34,100
10.0
49,800
14.6
36,900
10.8
330 (150)
350 (159)
470 (213)
490 (222)
470 (213)
490 (222)
50Hz Models 95°F Outdoor Ambient, Net Capacity
Model
ET035
80°F DB/67°F WB (26.7°C DB/19.4°C WB)
Total BTU/H
26,600
Total kW
7.8
Sensible BTU/H
20,700
Sensible kW
6.1
75°F DB/62.5°F WB (23.9°C DB/16.9°C WB)
Total BTU/H
24,700
Total kW
7.2
Sensible BTU/H
20,400
Sensible kW
6.0
Weight
(Standard Unit) lbs.(kg)
330 (150)
(Unit w/Economizer) lbs.(kg)
350 (159)
Model
Wu
Ws
Wf
A
B
E
ET047
ET059
38,300
11.2
29,300
8.6
46,600
13.6
32,400
9.5
35,500
10.4
28,400
8.4
43,600
12.7
31,600
9.2
470 (213)
490 (222)
470 (213)
490 (222)
F
G
37-1/8 17-3/4 38-3/4
20
20
8
20-3/4
12
25-1/16
2 Ton
(943) (451) (984) (508) (508) (203) (527) (305)
(638)
37-1/8 17-3/4 38-3/4
28
28
8
18
14
26
3 Ton
(943) (451) (984) (711) (711) (203) (457) (356)
(660)
41
22-1/2 42-3/4 30-1/4 29-7/8 9-7/8
30
15-7/8 25-25/64
4/5 Ton
(1041) (572) (1086) (768) (759) (251) (762) (403)
(645)
Wu= unit width
Wf=width to flange edges
J
H
69-3/4
(1772)
69-3/4
(1772)
83
(2108)
A=height to top of flange
Wu
E
F
G
A
SUPPLY
B
RETURN
H
Wf
Emerson Network Power
Caribbean and Latin America
Office – United States of America
+1-954-984-3452 Phone
Ask.Cala@Emerson.com
Emerson Network Power European Headquarters
Office – Italy
+39 049 9719 111 Phone
+39 049 5841 257 FAX
Marketing.EMEA@EmersonNetworkPower.com
Emerson Network Power
Asia Pacific
Office – Phillipines
+63 2 687 6615
+63 2 730 9572 FAX
Marketing.AP@Emerson.com
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2012 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-19500 (R11/12)
Printed in USA
Business-Critical Continuity, Emerson Network Power and the
Emerson Network Power logo are trademarks and service marks
of Emerson Electric Co.
©2012 Emerson Electric Co.
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Industrial Power
Ws
J
Liebert Corporation World Headquarters
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
United States Of America
800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Contact@EmersonNetworkPower.com
Shaded areas indicate a
recommended clearance of
34” (864mm) in front and
30” (762mm) each side or
36” (914mm) each side when
mounted adjacent to another
unit or component access.
For recommended minimum
clearances refer to the
installation manual.
Infrastructure Management & Monitoring