EMC Mission-Critical Business Continuity for SAP

EMC Mission-Critical Business Continuity for SAP
White Paper
EMC MISSION-CRITICAL BUSINESS
CONTINUITY FOR SAP
EMC VPLEX, Symmetrix VMAX, VNX, VMware vSphere HA,
Brocade Networking, Oracle RAC, SUSE Linux Enterprise
• Simplified management for high availability and business continuity
• Resilient mission-critical SAP deployments
• Active/active data centers
EMC Solutions Group
Abstract
This white paper describes the transformation of a traditional SAP deployment
to a mission-critical business continuity solution with active/active data
centers. The solution is enabled by EMC® VPLEXTM Metro, EMC Symmetrix®
VMAXTM, EMC VNXTM, VMware vSphere® HA, Oracle RAC, Brocade networking,
and SUSE Linux Enterprise Server for SAP Applications.
June 2012
Copyright © 2012 EMC Corporation. All Rights Reserved.
EMC believes the information in this publication is accurate as of its
publication date. The information is subject to change without notice.
The information in this publication is provided “as is.” EMC Corporation makes
no representations or warranties of any kind with respect to the information in
this publication, and specifically disclaims implied warranties of
merchantability or fitness for a particular purpose.
Use, copying, and distribution of any EMC software described in this
publication requires an applicable software license.
For the most up-to-date listing of EMC product names, see EMC Corporation
Trademarks on EMC.com.
VMware, VMware vSphere, ESXi, vCenter, and vMotion are registered
trademarks or trademarks of VMware, Inc. in the United States and/or other
jurisdictions.
Brocade, DCX, MLX, VCS, and VDX are registered trademarks of Brocade
Communications Systems, Inc., in the United States and/or in other countries.
All other trademarks used herein are the property of their respective owners.
Part Number H9542.1
EMC Mission-Critical Business Continuity for SAP
2
Table of contents
Executive summary ............................................................................................................................. 5
Business case .................................................................................................................................. 5
Solution overview ............................................................................................................................ 5
Key benefits ..................................................................................................................................... 6
Introduction ....................................................................................................................................... 7
Purpose ........................................................................................................................................... 7
Scope .............................................................................................................................................. 7
Audience.......................................................................................................................................... 7
Terminology ..................................................................................................................................... 7
Solution overview ............................................................................................................................... 9
Introduction ..................................................................................................................................... 9
Solution architecture...................................................................................................................... 10
Protection layers ............................................................................................................................ 14
Database and workload profile ...................................................................................................... 15
Hardware resources ....................................................................................................................... 15
Software resources ........................................................................................................................ 16
EMC VPLEX Metro infrastructure ....................................................................................................... 17
Introduction ................................................................................................................................... 17
VPLEX consistency groups .............................................................................................................. 19
VPLEX Metro solution configuration................................................................................................ 20
VPLEX Witness configuration .......................................................................................................... 22
VPLEX performance monitoring ...................................................................................................... 23
VMware virtualized infrastructure ..................................................................................................... 24
Introduction ................................................................................................................................... 24
VMware deployments on VPLEX Metro ........................................................................................... 25
VMware stretched cluster configuration ......................................................................................... 27
VMware vSphere HA configuration ................................................................................................. 29
VMware vSphere DRS configuration ............................................................................................... 31
EMC Virtual Storage Integrator and VPLEX ...................................................................................... 31
SAP system architecture ................................................................................................................... 33
Introduction ................................................................................................................................... 33
SAP system configuration............................................................................................................... 34
SUSE Linux Enterprise High Availability Extension configuration .................................................... 35
EMC Mission-Critical Business Continuity for SAP
3
Oracle database architecture ............................................................................................................ 43
Introduction ................................................................................................................................... 43
Oracle RAC and VPLEX .................................................................................................................... 44
Oracle ACFS configuration .............................................................................................................. 44
Oracle Extended RAC on VPLEX Metro............................................................................................. 45
Oracle ASM disk group configuration ............................................................................................. 46
Oracle database migration process ................................................................................................ 46
Brocade network infrastructure......................................................................................................... 53
Introduction ................................................................................................................................... 53
IP network configuration ................................................................................................................ 55
SAN network configuration ............................................................................................................. 56
EMC storage infrastructure ............................................................................................................... 57
Introduction ................................................................................................................................... 57
Symmetrix VMAX configuration ...................................................................................................... 58
VNX5700 configuration .................................................................................................................. 59
High availability and business continuity – testing and validation .................................................... 60
Introduction ................................................................................................................................... 60
SAP enqueue service process failure .............................................................................................. 60
SAP ASCS instance virtual machine failure ..................................................................................... 62
Oracle RAC node failure.................................................................................................................. 64
Site failure ..................................................................................................................................... 65
VPLEX cluster isolation ................................................................................................................... 68
Conclusion ....................................................................................................................................... 71
Summary ....................................................................................................................................... 71
Findings ......................................................................................................................................... 71
References ....................................................................................................................................... 73
EMC ............................................................................................................................................... 73
Oracle ............................................................................................................................................ 73
VMware .......................................................................................................................................... 73
SUSE .............................................................................................................................................. 74
SAP ................................................................................................................................................ 74
Appendix – Sample configurations ................................................................................................... 75
EMC Mission-Critical Business Continuity for SAP
4
Executive summary
Business case
Global enterprises demand always-on application and information availability to
remain competitive. The EMC solution described in this white paper offers a business
continuity and high-availability strategy for mission-critical applications such as
SAP ERP.
Recovery point objectives (RPOs) and recovery time objectives (RTOs) are key metrics
when planning a mission-critical business continuity strategy. They answer two
fundamental questions that businesses pose when they consider the potential
impact of a disaster or failure:
•
How much data can we afford to lose (RPO)?
•
How fast do we need the system or application to recover (RTO)?
Mission-critical business continuity for SAP demands aggressive RPOs and RTOs to
minimize data loss and recovery times. The main challenges that the business must
consider when designing such a strategy include:
•
Minimizing RPO and RTO
•
Eliminating single points of failure (SPOFs)—technology, people, processes
•
Maximizing resource utilization
•
Reducing infrastructure costs
•
Managing the complexity of integrating, maintaining, and testing multiple point
solutions
This white paper introduces an EMC solution that addresses all these challenges for
SAP ERP applications with an Oracle Real Applications Clusters (RAC) 11g database layer.
The solution demonstrates an innovative active/active deployment model for data
centers up to 100 km apart. This transforms the traditional active/passive disaster
recovery (DR) model to a highly available business continuity solution, with 24/7
application availability, no single points of failure, and near-zero RTOs and RPOs.
Solution overview
EMC® VPLEXTM Metro is the primary enabling technology for the solution. VPLEX
Metro is a storage area network-based (SAN) federation solution that delivers both
local and distributed storage federation. Its breakthrough technology,
AccessAnywhereTM, enables the same data to exist in two separate geographical
locations, and to be accessed and updated at both locations at the same time. With
VPLEX Witness added to the solution, applications continue to be available, with no
interruption or downtime, even in the event of disruption at one of the data centers.
The white paper demonstrates how the following technologies create this innovative
business continuity solution:
•
EMC VPLEX Metro provides the virtual storage layer that enables an
active/active Metro data center.
•
EMC VPLEX Witness supports continuous application availability, even in the
event of disruption at one of the data centers.
EMC Mission-Critical Business Continuity for SAP
5
Key benefits
•
EMC Symmetrix® VMAXTM and EMC VNXTM arrays, with proven five 9s
availability, support for Fully Automated Storage Tiering (FAST), and a choice of
replication technologies, provide the enterprise-class storage platform for the
solution.
•
Migrating from a single instance database to Oracle RAC on Extended Distance
Clusters removes single points of failure at the database layer, across distance.
•
VMware vSphere® virtualizes the SAP application components and eliminates
these as single points of failure. VMware® High Availability (HA) protects the
virtual machines in the case of physical server and operating system failures.
•
SUSE Linux Enterprise Server for SAP Applications, with SUSE Linux Enterprise
High Availability Extension and SAP Enqueue Replication Server (ERS), protects
the SAP central services (message server and enqueue server) across two
cluster nodes to eliminate these services as single points of failure.
•
Brocade Ethernet fabrics and MLXe core routers provide seamless networking
and Layer2 extension between sites.
•
Brocade DCX 8510 Backbones provide redundant SAN infrastructure, including
fabric extension.
The solution increases the availability for SAP applications by:
•
Eliminating single points of failure at all layers in the environment to build a
distributed and highly available SAP system
•
Providing active/active data centers that support near-zero RPOs and RTOs and
mission-critical business continuity
Additional benefits include:
•
Fully automatic failure handling
•
Increased utilization of hardware and software assets:

Active/active use of both data centers

Automatic load balancing between data centers

Zero downtime maintenance
•
Simplified SAP high-availability management
•
Simplified deployment of Oracle RAC on Extended Distance Clusters
•
Reduced costs by increasing automation and infrastructure utilization
EMC Mission-Critical Business Continuity for SAP
6
Introduction
Purpose
This white paper describes a solution that increases availability for SAP applications
by creating active/active data centers in geographically separate locations and
eliminating single points of failure at all layers in the environment.
In SAP environments, business disruption can result from technical, logical, or
logistical failures. This solution addresses business continuity from the technical
perspective.
Scope
The scope of the white paper is to:
•
Introduce the key enabling technologies
•
Describe the solution architecture and design
•
Describe how the key components are configured
•
Describe the steps used to convert an Oracle single instance database to a
four-node Oracle RAC cluster on Oracle Automatic Storage Management (ASM)
•
Present the results of the tests performed to demonstrate the elimination of
single points of failure at all layers in the environment
•
Identify the key business benefits of the solution
Audience
This white paper is intended for SAP Basis Administrators, Oracle DBAs, storage
administrators, IT architects, and technical managers responsible for designing,
creating, and managing mission-critical SAP applications in 24/7 landscapes.
Terminology
This white paper includes the terms in Table 1.
Table 1.
Terminology
Term
Description
ABAP
ACFS
ASCS
ASM
CIFS
CNA
CRM
DI
DPS
DRS
dvSwitch
DWDM
ERP
ERS
FAST VP
FCoE
FEC
SAP Advanced Business Application Programming
Oracle ASM Cluster File System
ABAP SAP Central Services
Oracle Automatic Storage Management
Common Internet File System
Converged network adapter
Cluster resource manager
Dialog instance
Dynamic Path Selection
VMware vSphere Distributed Resource Scheduler
vSphere distributed switch
Dense wavelength division multiplexing
Enterprise resource planning
Enqueue Replication Server
Fully Automated Storage Tiering for Virtual Pools
Fibre Channel over Ethernet
Forward Error Correction
EMC Mission-Critical Business Continuity for SAP
7
Term
Description
FRA
HA
HAIP
HBA
IDES
ISL
LACP
LAG
LLDP
LUW
MCT
MPLS
MPP
NAS
NFS
NL-SAS
OCR
Oracle Extended RAC
RAC
RFC
RMAN
RPO
RTO
SAN
SBD
SFP
SLES
SLE HAE
SMT
SPOF
STONITH
TAF
ToR
VCS
vLAG
vLAN
VMDK
VMFS
VMHA
VNX OE
VPLS
VPN
VRF
VSI
Flash Recovery Area
High availability
Highly available virtual IP
Host bus adapters
SAP Internet Demonstration and Evaluation System
Inter-Switch Link
Link Aggregation Control Protocol
Link Aggregation Group
Link Layer Discovery Protocol
Logical unit of work
Multi-Chassis Trunking
Multi-Protocol Label Switching
Multipathing plug-in
Network-attached storage
Network File System
Nearline SAS (Serial Attached SCSI)
Oracle Cluster Registry
Oracle RAC on Extended Distance Clusters
Real Application Clusters
Remote function call
Oracle Recovery Manager
Recovery point objective
Recovery time objective
Storage area network
STONITH block device
Small Form-Factor Pluggable
SUSE Linux Enterprise Server
SUSE Linux Enterprise High Availability Extension
Subscription Management Tool
Single point of failure
Shoot The Other Node In The Head
Transparent Application Failover
Top-of-Rack
Virtual cluster switch
Virtual Link Aggregation Group
Virtual LAN
Virtual disk
Virtual Machine File System
VMware High Availability
VNX Operating Environment
Virtual Private LAN Service
Virtual private network
Virtual Routing and Forwarding
Virtual Storage Integrator
EMC Mission-Critical Business Continuity for SAP
8
Solution overview
Introduction
SAP implementations – the challenge and the solution
Traditional SAP implementations have several single points of failure (SPOFs),
including:
•
Central Services
•
Database server
•
Enqueue server*
•
Single site deployment
•
Message server*
•
Local disk storage
* In this solution, the enqueue and message servers are implemented as services within the
ABAP SAP Central Services (ASCS) instance.
This white paper presents a solution for increasing availability for SAP applications.
The architecture and components of the solution create an active/active clustered
solution for the entire SAP stack to enhance reliability and availability while
simplifying the deployment and management of the environment. This provides the
following benefits:
•
Eliminates single points of failure at all layers in the environment to build a
highly available SAP system
•
Provides active/active data centers to enable mission-critical business
continuity
Figure 1 illustrates the single points of failure in a SAP environment and the solution
components used to address them.
The Challenge
The Solution
SAP single points of failure
High availability and business continuity
Figure 1.
SAP implementations – the challenge, the solution
EMC Mission-Critical Business Continuity for SAP
9
Solution
architecture
The following sections describe the solutions implemented at each layer of the
environment to provide high availability and business continuity, as shown in
Figure 2.
Figure 2.
The journey to high availability – logical view
Storage layer high availability
All the storage required by each server in the environment was moved
to enterprise-class storage arrays (Symmetrix VMAX and VNX).
Brocade 8510 Backbones were deployed to provide a redundant SAN
fabric for storage access.
This takes advantage of the proven five 9s uptime provided by the
arrays and the SAN Backbones, including their advanced
manageability and business continuity features.
Figure 3.
Storage HA
Database high availability
The database server is the data repository for the SAP application.
For this solution, the backend database server was converted
from an Oracle single instance database to a four-node
Oracle RAC database on Oracle ASM. This eliminates the
database server as a single point of failure.
Figure 4.
Database HA
EMC Mission-Critical Business Continuity for SAP
10
SAP application high availability
The SAP application servers were fully virtualized using
VMware ESXiTM 5.0. Each of the SAP virtual machines
was deployed using SUSE Linux Enterprise Server for
SAP Applications 11 SP1 as the guest operating
system.
SUSE Linux Enterprise High Availability Extension and
SAP Enqueue Replication Server (ERS) were also
deployed to protect both the SAP message server and
enqueue server. This eliminates the ABAP SAP Central
Services (ASCS) as a single point of failure.
Figure 5.
SAP application HA
Data center high availability
The high-availability cluster solution described above protects SAP within the data
center. For high availability between data centers, the solution uses EMC VPLEX Metro
storage virtualization technology, as shown in Figure 6. The unique VPLEX Metro
Access Anywhere active/active clustering technology allows read/write access to
distributed volumes across synchronous distances. By mirroring data across
locations, VPLEX enables users at both locations to access the same information at
the same time.
Figure 6.
Data center HA
This solution combines VPLEX Metro with SUSE Linux Enterprise High Availability
Extension (at the operating system layer) and Oracle RAC (at the database layer) to
remove the data center as a single point of failure and provide a robust business
continuity strategy for mission-critical applications.
EMC Mission-Critical Business Continuity for SAP
11
Oracle RAC on Extended Distance Clusters over VPLEX provides these benefits:
•
VPLEX simplifies management of Extended Oracle RAC, as cross-site high
availability is built in at the infrastructure level.
To the Oracle DBA, installation, configuration, and maintenance are exactly the
same as for a single site implementation of Oracle RAC.
•
VPLEX eliminates the need for host-based mirroring of ASM disks and the host
CPU cycles that this consumes.
With VPLEX, ASM disk groups are configured with external redundancy and are
protected by VPLEX distributed mirroring.
•
Hosts need to connect to their local VPLEX cluster only and I/O is sent only once
from that node. However, hosts have full read-write access to the same
database at both sites.
With host-based mirroring of ASM disk groups, each write I/O must be sent
twice, once to each mirror.
•
There is no need to deploy an Oracle voting disk on a third site to act as a
quorum device at the application level.
•
VPLEX enables you to create consistency groups that will protect multiple
databases and/or applications as a unit.
The solution uses VPLEX Witness to monitor connectivity between the two VPLEX
clusters and ensure continued availability in the event of an inter-cluster network
partition failure or a cluster failure. VPLEX Witness is deployed on a virtual machine at
a third, separate failure domain (Site C).
Network high availability
In each data center, an Ethernet fabric was built using Brocade virtual cluster switch
(VCS) technology, which delivers a self-healing and resilient access layer with all
links forwarding. Virtual Link Aggregation Groups (vLAGs) connect the VCS fabrics to
the Brocade MLXe core routers that extend the Layer 2 network across the two data
centers.
Figure 7 shows the physical architecture of all layers of the solution, including the
network components.
EMC Mission-Critical Business Continuity for SAP
12
Figure 7.
Solution architecture
EMC Mission-Critical Business Continuity for SAP
13
Protection layers
Table 2 summarizes the high availability (HA) layers that the solution uses to
eliminate single points of failure.
Table 2.
Local high availability
Local high availability
Protection
Site
Components protected
VMware HA and VMware DRS
Sites A & B
SAP virtual machines
SUSE Linux Enterprise HAE and
SAP Enqueue Replication Server
Sites A & B
SAP enqueue server, SAP message server
Multiple SAP Dialog Instances
Sites A & B
SAP work processes (DIA, UPD, UP2, SPO)
VMware
Sites A, B, & C
Server virtualization
Oracle RAC
Sites A & B
Oracle database
Oracle Clusterware
Sites A & B
SAP shared file system
Oracle ACFS
Sites A & B
SAP Oracle Home, SAP global directory,
SAP transport directory, SAP ASCS directory
EMC Symmetrix VMAX
Site A
Local storage, RAID, multipath
EMC VNX
Site B
Local storage, RAID, multipath
VPLEX Metro then extends the high availability with a clustering architecture that
breaks the boundaries of the data center and allows servers at multiple data centers
to have read/write access to shared block storage devices. This data center
transformation takes traditional high availability to a new level of mission-critical
business continuity.
Figure 8 illustrates this high-availability design, with VPLEX Witness and Cross-Cluster
Connect deployed to provide the highest level of resilience.
Figure 8.
Local HA, with VPLEX enabling multisite business continuity
EMC Mission-Critical Business Continuity for SAP
14
Each of the technologies shown in Figure 8 is explored in more detail in the relevant
sections of the white paper.
Database and
workload profile
Hardware
resources
Table 3 details the database and workload profile for the solution.
Table 3.
Database and workload profile
Profile characteristic
Details
Number of databases
1
Database type
SAP OLTP
Database size
500 GB
Database name
VSE
Oracle RAC
4 physical nodes
Workload profile
SAP custom order-to-cash processes
Table 4 details the hardware resources for the solution.
Table 4.
Solution hardware environment
Purpose
Quantity
Configuration
Storage (Site A)
1
EMC Symmetrix VMAX, with:
• 2 engines
• 171 x 450 GB FC drives
•
Storage (Site B)
1
52 x 2 TB SATA drives
EMC VNX5700, with:
• 30 x 2 TB NL-SAS drives
• 79 x 600 GB SAS drives
Distributed storage federation
2
VPLEX Metro cluster, with:
• 2 x VS2 engines
Oracle RAC database servers
4
4 x eight-core CPUs, 128 GB RAM
VMware ESXi servers for SAP
4
2 x four-core CPUs, 128 GB RAM
VMware ESXi server for VPLEX
Witness
2
2 x two-core CPUs, 48 GB RAM
Network switching and routing
platform
2
Brocade DCX 8510 Backbone, with:
• Fx8-24 FC extension card
• 2 x 48-port FC Blades with 16 Gb FC line
speed support
Brocade MLXe Router
4
Brocade VDX 6720 in VCS mode
EMC Mission-Critical Business Continuity for SAP
15
Software resources Table 5 details the software resources for the solution.
Table 5.
Solution software environment
Software
Version
Purpose
EMC Enginuity™
5875.198.148
Symmetrix VMAX operating
environment
EMC VPLEX GeoSynchrony
5.1
VPLEX operating environment
EMC VPLEX Witness
5.1
Monitor and arbitrator component for
handling VPLEX cluster failure and
inter-cluster communication loss
EMC VNX OE for block
05.31.000.5.715
VNX operating environment
EMC VNX OE for file
7.0.52.1
VNX operating environment
EMC UnisphereTM
1.1
VNX management software
SUSE Linux Enterprise Server
for SAP Applications,
including SUSE Linux
Enterprise High Availability
Extension
11 SP1
Operating system for all servers in
the environment
VMware vSphere
5.0
Hypervisor hosting all virtual
machines
Oracle Database 11g (with
Oracle RAC and Oracle Grid
Infrastructure)
Enterprise
Edition 11.2.0.3
Oracle database and cluster software
SAP ERP
6.04
SAP ERP IDES system
EMC Mission-Critical Business Continuity for SAP
16
EMC VPLEX Metro infrastructure
Introduction
Overview
This section describes the VPLEX Metro infrastructure for the solution, which
comprises the following components:
•
EMC VPLEX Metro cluster at each data center (Site A and Site B)
•
EMC VPLEX Witness in a separate failure domain (Site C)
EMC VPLEX
EMC VPLEX is a storage virtualization solution for both EMC and non-EMC storage
arrays. EMC offers VPLEX in three configurations to address customer needs for high
availability and data mobility, as shown in Figure 9:
•
VPLEX Local
•
VPLEX Metro
•
VPLEX Geo
Figure 9.
VPLEX topologies
For detailed descriptions of these VPLEX configurations, refer to the documents listed
in References on page 73.
EMC VPLEX Metro
This solution uses VPLEX Metro, which uses a unique clustering architecture to help
customers break the boundaries of the data center and allow servers at multiple data
centers to have read/write access to shared block storage devices. VPLEX Metro
delivers active/active, block-level access to data on two sites within synchronous
distances with a round-trip time of up to 5 ms.
EMC VPLEX Witness
VPLEX Witness is an optional external server that is installed as a virtual machine in a
separate failure domain to the VPLEX clusters. VPLEX Witness connects to both VPLEX
clusters using a Virtual Private Network (VPN) over the management IP network; it
requires a round trip time that does not exceed 1 second.
By reconciling its own observations with information reported periodically by the
clusters, VPLEX Witness enables the cluster(s) to distinguish between inter-cluster
EMC Mission-Critical Business Continuity for SAP
17
network partition failures and cluster failures and to automatically resume I/O at the
appropriate site.
VPLEX Witness failure handling semantics apply only to distributed volumes within a
consistency group and only when the detach rules identify a static preferred cluster
for the consistency group (see VPLEX consistency groups on page 19 for further
details).
EMC VPLEX Management Interface
You can manage and administer a VPLEX environment with the web-based VPLEX
Management Console or you can connect directly to a management server and start a
VPlexcli session (VPLEX command line interface).
EMC VPLEX High Availability
VPLEX Metro enables application and data mobility and, when configured with VPLEX
Witness, provides a high-availability infrastructure for clustered applications, such as
Oracle RAC. VPLEX Metro enables you to build an extended or stretch cluster as if it
was a local cluster, and removes the data center as a single point of failure.
Furthermore, as the data and applications are active at both sites, the solution
provides a simple business continuity strategy.
An even higher degree of availability can be achieved by using a VPLEX Cross-Cluster
Connect configuration. In this case, each host is connected to the VPLEX clusters at
both sites. This ensures that, in the unlikely event of a full VPLEX cluster failure, the
host has an alternate path to the remaining VPLEX cluster.
VPLEX logical storage structures
VPLEX encapsulates traditional physical storage array devices and applies layers of
logical abstraction to these exported LUNs, as shown in Figure 10.
Figure 10.
VPLEX logical storage structures
A storage volume is a LUN exported from an array and encapsulated by VPLEX. An
extent is the mechanism VPLEX uses to divide storage volumes and may use all or
part of the capacity of the underlying storage volume. A device encapsulates an
EMC Mission-Critical Business Continuity for SAP
18
extent or combines multiple extents or other devices into one large device with a
specific RAID type. A distributed device is a device that encapsulates other devices
from two separate VPLEX clusters.
At the top layer of the VPLEX storage structures are virtual volumes. These are created
from a top-level device (a device or distributed device) and always use the full
capacity of the top-level device. Virtual volumes are the elements that VPLEX exposes
to hosts using its front-end ports. VPLEX presents a virtual volume to a host through a
storage view.
VPLEX can encapsulate devices across heterogeneous storage arrays, including
virtually provisioned thin devices and traditional LUNs.
VPLEX consistency groups
Consistency groups aggregate virtual volumes together so that the same detach rules
and other properties can be applied to all volumes in the group. There are two types
of consistency group:
•
Synchronous consistency groups—These are used in VPLEX Local and VPLEX
Metro to apply the same detach rules and other properties to a group of
volumes in a configuration. This simplifies configuration and administration on
large systems.
Synchronous consistency groups use write-through caching (known as
synchronous cache mode) and with VPLEX Metro are supported on clusters
separated by up to 5 ms of latency. VPLEX Metro sends writes to the back-end
storage volumes, and acknowledges a write to the application only when the
back-end storage volumes in both clusters acknowledge the write.
•
Asynchronous consistency groups—These are used for distributed volumes in
VPLEX Geo, where clusters can be separated by up to 50 ms of latency.
Detach rules
Detach rules are predefined rules that determine I/O processing semantics for a
consistency group when connectivity with a remote cluster is lost—for example, in the
case of a network partitioning or remote cluster failure.
Synchronous consistency groups support the following detach rules to determine
cluster behavior during a failure:
•
Static preference rule identifies a preferred cluster
•
No-automatic-winner rule suspends I/O on both clusters
When a detach rule is set it is always invoked when connectivity is lost between
clusters. However, VPLEX Witness can be deployed to override the static preference
rule and ensure that the non-preferred cluster remains active if the preferred cluster
fails.
EMC Mission-Critical Business Continuity for SAP
19
VPLEX Metro
solution
configuration
Storage structures
Figure 10 shows the physical and logical storage structure used by VPLEX Metro in the
context of this solution.
Figure 11.
VPLEX physical and logical storage structures for solution
There is a one-to-one mapping between storage volumes, extents, and devices at
each site. The devices encapsulated at Site A (cluster-1) are virtually provisioned thin
devices, while the devices encapsulated at Site B (cluster-2) are traditional LUNs.
All cluster-1 devices are mirrored remotely on cluster-2, in a distributed RAID 1
configuration, to create distributed devices. These distributed devices are
encapsulated by virtual volumes, which are then presented to the hosts through
storage views.
Consistency group
Consistency groups are particularly important for databases and their applications.
For example:
•
Write-order fidelity—To maintain data integrity, all Oracle database LUNs (for
example, data, control, and log files) should be placed together in a single
consistency group.
•
Transactional dependency—Often multiple databases have transaction
dependencies, such as when an application issues transactions to multiple
databases and expects the databases to be consistent with each other. All
LUNs that require I/O dependency to be preserved should reside in a single
consistency group.
EMC Mission-Critical Business Continuity for SAP
20
•
Application dependency—Oracle RAC maintains Oracle Cluster Registry (OCR)
and voting files within a set of disks that must be accessible to maintain
database availability. The database and OCR disks should reside in a single
consistency group.
For the solution, a single synchronous consistency group—Extended_Oracle_RAC_CG—
contains all the virtual volumes that hold the Oracle 11g database binaries, the
Oracle ASM disk groups, and the OCR and voting files. The detach rule for the
consistency group has cluster-1 as the preferred cluster.
Configuration process
For the solution, the VPLEX Metro logical storage structures are configured as follows
(Figure 12 to Figure 16 show extracts from the configuration wizards provided by the
VPLEX Management Console):
•
Storage volume—A storage volume is a LUN exported from an array and
encapsulated by VPLEX. Figure 12 shows several storage volumes created at
Site A, as displayed in the VPLEX Management Console.
Figure 12.
•
Extent—In the solution, there is a one-to-one mapping between extents and
storage volumes, as shown in Figure 12 and Figure 13.
Figure 13.
•
EMC VPLEX storage volumes (Site A)
EMC VPLEX Extent Creation wizard
Device—In the solution, there is a one-to-one mapping between devices and
extents. Figure 14 shows the option used to configure this one-to-one mapping.
Figure 14.
EMC VPLEX Device Creation wizard
EMC Mission-Critical Business Continuity for SAP
21
•
Distributed device—In the solution, the distributed devices were created by
mirroring a device remotely in a distributed RAID 1 configuration, as shown in
Figure 15.
Figure 15.
•
Virtual volume—In the solution, all top-level devices are distributed devices.
These devices are encapsulated by virtual volumes, which VPLEX presents to
the hosts through storage views. The storage views define which hosts access
which virtual volumes on which VPLEX ports.
•
Consistency group—Figure 16 shows the consistency group created for the
solution—Extended_Oracle_RAC_CG.
Figure 16.
VPLEX Witness
configuration
EMC VPLEX Device Creation wizard
EMC VPLEX Create Consistency Group wizard
The solution uses VPLEX Witness to monitor connectivity between the two VPLEX
clusters and ensure continued availability in the event of an inter-cluster network
partition failure or a cluster failure. This is considered a VPLEX Metro HA configuration
as storage availability is ensured at the surviving site.
VPLEX Witness is deployed at a third, separate failure domain (Site C) and connected
to the VPLEX clusters at Site A and Site B. Site C is located at a distance of less that
1 second latency from Sites A and B.
When a VPLEX Witness has been installed and configured, the VPLEX Management
Console displays the status of cluster witness components, as shown in Figure 17.
EMC Mission-Critical Business Continuity for SAP
22
Figure 17.
VPLEX
performance
monitoring
EMC VPLEX Witness components and status
VPLEX 5.1 delivers enhanced performance monitoring through the performance
monitoring dashboard. This dashboard provides a customizable view into the
performance of the VPLEX system and enables you to view and compare different
aspects of system performance, down to the director level.
Many different metrics are currently available, including:
•
Front-end Latency chart
•
Front-end Bandwidth chart
•
Front-end Throughput chart
•
CPU Utilization chart
•
Rebuild Status chart
•
WAN Link Performance chart
•
Back-end Latency chart
Figure 18 shows the front-end and CPU performance on cluster-1 (the Site A VPLEX)
when Oracle statistics were gathered on the SAP VSE database.
Figure 18.
VPLEX performance monitoring dashboard
EMC Mission-Critical Business Continuity for SAP
23
VMware virtualized infrastructure
Introduction
Overview
For the solution, the SAP application servers are fully virtualized using VMware
vSphere 5. This section describes the virtualization infrastructure, which uses these
components and options:
•
VMware vSphere 5.0
•
VMware vCenterTM Server
•
VMware vSphere vMotion®
•
VMware vSphere High Availability (HA)
•
VMware vSphere Distributed Resource SchedulerTM (DRS)
•
EMC PowerPath®/VE for VMware vSphere Version 5.7
•
EMC Virtual Storage Integrator for VMware vSphere Version 5.1
VMware vSphere 5
VMware vSphere 5 is the industry’s most complete, scalable, and powerful
virtualization platform, with infrastructure services that transform IT hardware into a
high-performance shared computing platform, and application services that help IT
organizations deliver the highest levels of availability, security, and scalability.
VMware vCenter Server
VMware vCenter is the centralized management platform for vSphere environments,
enabling control and visibility at every level of the virtual infrastructure.
VMware vSphere vMotion
VMware vSphere vMotion is VMware technology that supports live migration of virtual
machines across servers with no disruption to users or loss of service.
Storage vMotion is VMware technology that enables live migration of a virtual
machine’s storage without any interruption in the availability of the virtual machine.
This allows the relocation of live virtual machines to new datastores.
VMware vSphere High Availability
VMware vSphere High Availability (HA) is a vSphere component that provides high
availability for any application running in a virtual machine, regardless of its
operating system or underlying hardware configuration.
VMware vSphere Distributed Resource Scheduler
VMware vSphere Distributed Resource Scheduler (DRS) dynamically and
automatically balances load distribution and virtual machine placement across
multiple ESXi servers.
EMC Mission-Critical Business Continuity for SAP
24
EMC PowerPath/VE
EMC PowerPath/VE for VMware vSphere delivers PowerPath multipathing features to
optimize VMware vSphere virtual environments. PowerPath/VE installs as a kernel
module on the ESXi host and works as a multipathing plug-in (MPP) that provides
enhanced path management capabilities to ESXi hosts.
EMC Virtual Storage Integrator for VMware vSphere
EMC Virtual Storage Integrator (VSI) for VMware vSphere is a plug-in to the VMware
vSphere client that provides a single management interface for managing EMC
storage within the vSphere environment. VSI provides a unified and flexible user
experience that allows each feature to be updated independently, and new features
to be introduced rapidly in response to changing customer requirements.
When PowerPath/VE is installed on an ESXi host, VSI presents important multipathing
details for devices, such as the load-balancing policy, the number of active paths,
and the number of dead paths.
VMware
deployments on
VPLEX Metro
EMC VPLEX Metro delivers concurrent access to the same set of devices at two
physically separate locations and thus provides the active/active infrastructure that
enables geographically stretched clusters based on VMware vSphere. The use of
Brocade Virtual Link Aggregation Group (vLAG) technology enables extension of
VLANs, and hence subnets, across different physical data centers.
By deploying VMware vSphere features and components together with VPLEX Metro,
the following functionality can be achieved:
•
vMotion—The ability to live migrate virtual machines between sites in
anticipation of planned events such as hardware maintenance.
•
Storage vMotion—The ability to migrate a virtual machine’s storage without any
interruption in the availability of the virtual machine. This allows the relocation
of live virtual machines to new datastores.
•
VMware DRS—Automatic load distribution and virtual machine placement
across sites through the use of DRS groups and affinity rules.
•
VMware HA—A VPLEX Metro environment configured with VPLEX Witness is
considered a VPLEX Metro HA configuration, as it ensures storage availability at
the surviving site in the event of a site-level failure. Combining VPLEX Metro HA
with a host failover clustering technology such as VMware HA provides
automatic application restart for any site-level disaster. Figure 19 illustrates
this HA architecture.
EMC Mission-Critical Business Continuity for SAP
25
Figure 19.
•
VMware HA with VPLEX Witness – logical view
VPLEX Metro HA Cross-Cluster Connect—Protection of the VMware HA cluster
can be further increased by adding a cross-cluster connect between the local
VMware ESXi servers and the VPLEX cluster on the remote site.
Local data unavailability events, which VMware vSphere 5.0 does not
recognize, can occur when there is not a full site outage. Cross-connecting
vSphere environments to VPLEX clusters protects against this and ensures that
failed virtual machines automatically move to the surviving site.
VPLEX Cross-Cluster Connect is available for up to 1 ms of distance-induced
latency.
This solution uses VPLEX Metro HA with Cross-Cluster Connect to maximize the
availability of the VMware virtual machines, as shown in Figure 20. 1
1
For detailed information, see the EMC TechBook: EMC VPLEX Metro Witness Technology and
High Availability.
EMC Mission-Critical Business Continuity for SAP
26
Figure 20.
VMware stretched
cluster
configuration
VMware HA with VPLEX Witness and Cross-Cluster Connect – logical view
VMware and EMC support a stretched cluster configuration that includes ESXi hosts
from multiple sites 2. For the solution, a single vSphere cluster is stretched between
Site A and Site B by using a distributed VPLEX virtual volume with VMware HA and
VMware DRS. There are four hosts in the cluster, two at each site. VPLEX Metro HA
Cross-Cluster Connect provides increased resilience to the configuration.
In vCenter, it is easy to view the configuration of this cluster—SiteAandSiteB—and the
features enabled for it, as shown in Figure 21. This view also shows the memory, CPU,
and storage resources available to the cluster.
Figure 21.
2
vSphere cluster with HA and DRS enabled
For detailed requirements and scenarios, see the VMware Knowledge Base article 1026692:
Using VPLEX Metro with VMware HA
EMC Mission-Critical Business Continuity for SAP
27
Each ESXi server is configured with two 10 GbE physical adapters to provide network
failover and high performance. A vSphere distributed switch (dvSwitch) 3 provides a
single, common switch across all hosts. The 10 GbE physical adapters (also referred
to as uplink adapters) are assigned to the dvSwitch.
Two distributed port groups are assigned to the dvSwitch:
•
dvPortGroupSiteAB—for virtual machine network traffic
•
Management Network—for VMkernel traffic and, in particular, vMotion traffic
Figure 22 shows the dvSwitch configuration. As both vSphere 5.0 distributed
switches and Brocade VCS switches support Link Layer Discovery Protocol (LLDP), the
properties of the associated physical switches can also be easily identified from
vCenter.
Figure 22.
dvSwitch configuration and LLDP detail
Datastore EXT_SAP_VPLEX_DS01 was created on a 1 TB VPLEX distributed volume
and presented to the ESXi hosts in the stretch cluster. All virtual machines were
migrated to this datastore, using Storage vMotion, because they need to share virtual
disks or to be able to vMotion between sites. Figure 23 shows the configuration
details for the datastore.
3
A dvSwitch provides a network configuration that spans all member hosts and allows virtual
machines to maintain consistent network configuration as they migrate between hosts. For
further information, see the VMware vSphere Networking ESXi 5.0 document.
EMC Mission-Critical Business Continuity for SAP
28
Figure 23.
VMware vSphere
HA configuration
Datastore EXT_SAP_VPLEX_DS01 and associated hosts and virtual machines
Enabling VMware vSphere HA and VMware vSphere DRS
vSphere HA leverages multiple ESXi hosts, configured as a cluster, to provide rapid
recovery from outages and cost-effective high availability for applications running in
virtual machines. 4 vSphere HA protects application availability in the following ways:
•
It protects against a server failure by restarting the virtual machines on other
ESXi servers within the cluster.
•
It protects against application failure by continuously monitoring a virtual
machine and resetting it in the event of guest OS failure.
For the solution, both vSphere HA and DRS were enabled, as shown in Figure 24.
Figure 24.
vSphere HA wizard
4
For further information on vSphere HA, see the VMware vSphere Availability ESXi 5.0
document.
EMC Mission-Critical Business Continuity for SAP
29
VM Monitoring
VM Monitoring was configured to restart individual virtual machines if their heartbeat
is not received within 60 seconds.
Virtual machine restart options
The VM Restart Priority option for the four SAP virtual machines was set to High. This
ensures that these virtual machines are powered on first in the event of an outage.
Figure 25 shows this setting and the Host Isolation Response setting (default).
Figure 25.
VM Restart Priority and Host Isolation Response settings
Datastore heartbeating
When you create a vSphere HA cluster, a single host is automatically elected as the
master host. The master host monitors the state of all protected virtual machines and
of the slave hosts. When the master host cannot communicate with a slave host, it
uses datastore heartbeating to determine whether the slave host has failed, is in a
network partition, or is network isolated.
To meet vSphere HA requirements for datastore heartbeating, a second datastore—
EXT_SAP_VPLEX_HA_HB—was created on a 20 GB VPLEX distributed volume and
presented to all the ESXi hosts, as shown in Figure 26. In a production environment,
vCenter automatically selects two or more datastores for this purpose, based on host
visibility.
Figure 26.
vSphere HA Cluster Status – heartbeat datastores
EMC Mission-Critical Business Continuity for SAP
30
VMware vSphere
DRS configuration
VMware DRS host groups and virtual machine groups
DRS host groups and virtual machine groups simplify management of ESXi host
resources. These features were not required for this solution.
VMware DRS affinity rules
DRS uses affinity rules to control the placement of virtual machines on hosts within a
cluster. DRS provides two types of affinity rule:
•
A VM-Host affinity rule specifies an affinity relationship between a group of
virtual machines and a group of hosts.
•
A VM-VM affinity rule specifies whether particular virtual machines should run
on the same host or be kept on separate hosts.
Table 6 and Figure 27 show the VM-VM affinity rule that the solution uses.
Table 6.
VMware DRS affinity rule
VM-VM affinity rule
SAPASCS - Separate
Figure 27.
EMC Virtual
Storage Integrator
and VPLEX
Keep virtual machines SAPASCS1 and SAPASCS2 on separate
hosts.
DRS VM-VM affinity rule for vplex_esxi_metro_HA cluster
EMC Virtual Storage Integrator (VSI) provides enhanced visibility into VPLEX directly
from the vCenter GUI. The Storage Viewer and Path Management features are
accessible through the EMC VSI tab, as shown in Figure 28.
In the solution, VPLEX distributed volumes host the EXT_SAP_VPLEX_DS01 Virtual
Machine File System (VMFS) datastore, and Storage Viewer provides details of the
datastore’s virtual volumes, storage volumes, and paths.
As shown in Figure 28, the LUNS that make up the datastore are four 256 GB
distributed RAID 1 VPLEX Metro volumes that are accessible via PowerPath.
EMC Mission-Critical Business Continuity for SAP
31
Figure 28.
VSI Storage Viewer – datastores
EMC Mission-Critical Business Continuity for SAP
32
SAP system architecture
Introduction
Overview
This section describes the SAP system architecture deployed for the solution in the
two data centers. The SAP application layer uses these SAP and SUSE components:
SAP application
Operating system
•
SAP Enhancement Package 4
for SAP ERP 6.0 IDES
•
SUSE Linux Enterprise Server for
SAP Applications 11 SP1
•
SAP NetWeaver Application Server
for ABAP 7.01
•
SUSE Linux Enterprise High
Availability Extension
•
SAP Enqueue Replication Server
The SAP system runs in a hybrid environment, with SAP services on virtual machines
and the database on physical servers. All SAP instances are installed on VMware
vSphere virtual machines with SUSE Linux Enterprise Server for SAP Applications as
the operating system. The underlying database is a physical Oracle RAC database on
ASM. The VMware and Oracle environments are described in separate sections of the
white paper (see VMware virtualized infrastructure and Oracle database ).
SAP ERP 6.0
SAP ERP 6.0, powered by the SAP NetWeaver technology platform, is a world-class,
fully-integrated enterprise resource planning (ERP) application that fulfills the core
business needs of midsize companies and large enterprises across all industries and
market sectors. SAP ERP 6.0 delivers a comprehensive set of integrated, crossfunctional business processes and can serve as a solid business process platform
that supports continued growth, innovation, and operational excellence.
SAP IDES (Internet Demonstration and Evaluation System) supports demos, testing,
and functional evaluation based on preconfigured data and clients. IDES contains
application data for various business scenarios, with business processes in that are
designed to reflect real-life business requirements and have access to many realistic
characteristics. This solution uses IDES to represent a model company for testing
purposes.
SUSE Linux Enterprise Server for SAP Applications
SUSE Linux Enterprise Server is a highly reliable, scalable, and secure server
operating system that is built to power physical, virtual, and cloud applications. It is a
preferred Linux platform for SAP.
SUSE Linux Enterprise Server for SAP Applications, based on the newest SUSE Linux
Enterprise Server technology, is optimized for all mission-critical SAP NetWeaver
software solutions and appliances. SAP and SUSE validate and certify SUSE Linux
Enterprise Server for SAP Applications jointly to eliminate potential software
incompatibilities. This partnership tightly integrates the application workload with
the operating system and eliminates the possibility of incompatibilities when patches
are applied to either the applications or the operating system.
EMC Mission-Critical Business Continuity for SAP
33
SUSE Linux Enterprise High Availability Extension
SUSE Linux Enterprise Server for SAP Applications includes SUSE Linux Enterprise
High Availability Extension, which offers high-availability service and application
clustering, file systems and clustered file systems, network-attached storage (NAS),
network file systems, volume managers, SAN and drivers, and the means to manage
of all these components working together. SUSE Linux Enterprise High Availability
Extension provides an integrated clustering solution for physical and virtual Linux
deployments, enabling the implementation of highly available Linux clusters and
eliminating single points of failure.
SAP system
configuration
SAP system architecture
The solution implements a high-availability SAP system architecture, as shown in
Figure 29.
Figure 29.
SAP system architecture
The enqueue server and message server are decoupled from the Central Instance and
implemented as services within the ASCS instance 5. SAP ERS is installed as part of
the HA architecture to provide zero application lock loss and further protect the
5
The enqueue server manages logical locks, its objective being to minimize the duration of a
database lock. Unlike database locks, an SAP lock can exist across several database LUWs.
The message server informs all servers (instances) in an SAP system of the existence of the
other servers. Other clients (for example, SAPlogon and RFC clients with load balancing) can
also contact it for information about load balancing.
EMC Mission-Critical Business Continuity for SAP
34
enqueue server 6. Two dialog instances are installed to provide redundant work
processes such as dialog (DIA), background (BGD), update (UPD), spool (SPO), and
gateway.
Key design considerations
The SAP system deployed for the solution implements these key design features:
SUSE Linux
Enterprise High
Availability
Extension
configuration
•
The ASCS instance is installed with a virtual hostname (SAPVIPE), to decouple it
from the virtual machine hostname.
•
The ERS instance is installed with a different instance number (01), to avoid
future confusion when both ASCS and ERS are under cluster control.
•
SAP patches, parameters, basis settings, and load balancing settings are all
installed and configured according to the SAP installation guide and the SAP
Notes listed on page 73.
•
VMware best practices for SAP are adopted in this solution 7.
•
SAP update processes (UPD/UP2) are configured on the additional application
server instances.
•
SAP ASCS instance profile, ERS instance and start profiles, and dialog instance
profiles are updated with ERS configurations. See Appendix – Sample
configurations for sample configurations.
•
SAP shared file systems, including /sapmnt/<SID> (available to all SAP
instances) and /usr/sap/<SID>/ASCS00 (available to SAP cluster nodes, ASCS
instance, and ERS instance), are stored on Oracle ASM Cluster File System
(ACFS) and mounted as Network File System (NFS) shares on the SAP virtual
machines. These shared file systems are presented as a highly available NFS
resource that is managed by Oracle Clusterware.
•
Some IDES functionality—for example, synchronization with the external GTS
system—is deactivated to eliminate unnecessary external interfaces that are
outside the scope of the solution.
•
The storage for the entire SAP environment is encapsulated and virtualized for
this solution. The storage is distributed across the two sites and made
available to the SAP servers through VPLEX Metro.
SAP virtual machine architecture with SUSE Linux Enterprise High Availability
Extension
The solution uses SUSE Linux Enterprise High Availability Extension to protect the
central services (message server and enqueue server) across two cluster nodes built
on VMware virtual machines. VMware High Availability (VMHA) protects the virtual
machines. Figure 30 shows this architecture.
6
SAP ERS provides a replication mechanism for the enqueue server by holding a copy of the
locking table within its shared memory segment. ERS installation for Linux is not part of the
standard SAPInst process. For installation instructions, see the SAP Enqueue Replication
Server help portal on help.sap.com.
7
For full details, see: SAP Solutions on VMware: Best Practices Guide.
EMC Mission-Critical Business Continuity for SAP
35
Figure 30.
SAP ASCS cluster architecture with SUSE Linux Enterprise HAE
The key components of SUSE Linux Enterprise High Availability Extension
implemented in this solution include:
•
OpenAIS 8/Corosync 9—a high-availability cluster manager that supports
multinode failover
•
Resource agents (virtual IP address, master/slave, and SAPInstance) to monitor
and control the availability of resources
•
High-availability GUI and various command line tools
Table 7 shows the configuration of the SAP virtual machines.
Table 7.
VM role
SAP virtual machines
Quantity
vCPUs
Memory (GB)
OS bootdisk (GB)
VM name
SAP ASCS
1
2
4
32
SAPASCS1
SAP ERS
1
2
4
32
SAPASCS2
SAP AAS
2
2
4
32
SAPDI1
2
4
32
SAPDI2
8
OpenAIS is an open implementation of the Application Interface Specification (AIS) provided
by the Service Availability Forum (SA Forum).
9
The Corosync Cluster Engine is a group communication system with additional features for
implementing high availability within applications.
EMC Mission-Critical Business Continuity for SAP
36
Installation and configuration process
The SUSE white paper Running SAP NetWeaver on SUSE Linux Enterprise Server with
High Availability – Simple Stack describes how to install and configure the SUSE
software and SAP NetWeaver.
Appendix – Sample configurations provides a sample configuration file that supports
the features and functionality validated by this solution. You should consider the
time values (timeout, intervals, and so on) here as “initial” values to be fine tuned
and optimized for your particular environment.
For the solution, SUSE Linux Enterprise High Availability Extension was installed and
configured using YaST and Pacemaker GUI. Here is a summary of the installation and
configuration process:
1.
Set up an internal SMT Server (for security purposes) to update all software
packages to the latest versions.
2.
In the YaST Software Management module, select Patterns > High Availability
to install the High Availability Extension, as shown in Figure 31.
Figure 31.
Installing SUSE Linux Enterprise High Availability Extension
EMC Mission-Critical Business Continuity for SAP
37
3.
In the YaST Cluster module, configure the cluster basic settings, as shown in
Figure 32.
Figure 32.
4.
Configuring cluster basic settings
In Pacemaker GUI, configure the global cluster settings, as shown in
Figure 33.
Figure 33.
Configuring global cluster settings
EMC Mission-Critical Business Continuity for SAP
38
5.
In Pacemaker GUI, open the Resources category and configure IPaddr2,
master/slave, and SAPInstance resources, as shown in Figure 34.
Figure 34.
6.
Configuring resources
In Pacemaker GUI, configure the dependencies of the resources, as shown in
Figure 35.
Figure 35.
Configuring resource dependencies
EMC Mission-Critical Business Continuity for SAP
39
7.
In Pacemaker GUI, start the cluster and check that the cluster and all resource
agents are operating normally, as shown in Figure 36.
Figure 36.
Checking the cluster status
Key design considerations
STONITH device configuration
SBD (STONITH block device) and STONITH (Shoot The Other Node In The Head) enable
fencing (isolating nodes) in a cluster via shared storage. This solution uses a partition
of a virtual disk (VMDK) as an SBD STONITH device. 10 Therefore, both cluster nodes
need simultaneous access to this virtual disk. The virtual disk is stored in the same
datastore as the SAP virtual machines. This is provisioned and protected by VPLEX
and is available on both sites.
By default, VMFS prevents multiple virtual machines from accessing and writing to
the same VMDK. However, you can enable sharing by configuring the multi-writer
option 11, as shown in Figure 37.
10
SBD is essential for handling split-brain scenarios in the cluster. A single SBD device is
configured for this solution. This single SBD device configuration is for testing purposes only;
for production configuration, see Running SAP NetWeaver on SUSE Linux Enterprise Server
with High Availability – Simple Stack.
11
For detailed information, see VMware Knowledge Base article 1034165: Disabling
simultaneous write protection provided by VMFS using the multi-writer flag.
EMC Mission-Critical Business Continuity for SAP
40
Figure 37.
Multi-writer option
Master/slave configuration
The SAPInstance resource agent controls the ASCS instance as well as the
appropriate ERS instance. It is configured as master/slave resource that extends the
roles of the resource from started and stopped to master and slave. A promoted
master instance starts the SAP ASCS instance. The demoted slave instance starts the
ERS instance. The master/slave mode ensures that an ASCS instance is never started
on the same node as the ERS.
Figure 38 shows the configuration of the SAPInstance resource agent.
Figure 38.
SAPInstance resource agent configuration
Figure 39 shows the configuration of the master/slave resource agent.
Figure 39.
Master/slave resource agent configuration
EMC Mission-Critical Business Continuity for SAP
41
Resource constraints
The ASCS instance and its virtual IP are bound together using appropriate order and
colocation constraints. Figure 40 shows the configuration of the Resource Colocation
and Resource Order constraints.
Figure 40.
Resource Colocation and Resource Order constraint configuration
Corosync token parameter configuration
In the Corosync configuration file—corosync.conf—the token timeout specifies the
time (in milliseconds) after which a token loss is declared if a token is not received.
This timeout corresponds to the time spent detecting the failure of a processor in the
current configuration. For this solution, the value of this parameter is set to
10,000 ms in order to cope with the switchover of the underlying layers without
unnecessary cluster service failover.
Polling concept
SUSE Linux Enterprise High Availability Extension can continuously monitor the status
of SAP processes on each cluster node and make the correct decisions to
promote/demote the ASCS instance and ERS instance respectively.
There is no need to implement SAP polling concept. Ensure that this feature is NOT
enabled in the ERS instance profile. For a sample ERS instance profile, see ERS
sample instance profile on page 76.
EMC Mission-Critical Business Continuity for SAP
42
Oracle database architecture
Introduction
Overview
This section describes the grid and database that underlies the SAP applications in
the solution. At each data center, the database originated as a physical Oracle
Database 11g single instance. To eliminate the database server as a single point of
failure, the single instance database was migrated to a four-node physical Oracle RAC
11g cluster with the Oracle database residing on ASM.
The solution uses these Oracle components and options:
•
Oracle Database 11g Release 2 Enterprise Edition
•
Oracle Automatic Storage Management (ASM) and Oracle ASM Cluster File
System (ACFS)
•
Oracle Clusterware
•
Oracle Real Applications Clusters (RAC) 11g on Extended Distance Clusters
Oracle Database 11g R2
Oracle Database 11g Release 2 Enterprise Edition delivers industry-leading
performance, scalability, security, and reliability on a choice of clustered or single
servers running Windows, Linux, or UNIX. It provides comprehensive features for
transaction processing, business intelligence, and content management applications.
Oracle ASM and Oracle ACFS
Oracle ASM is an integrated, cluster-aware database file system and disk manager.
ASM file system and volume management capabilities are integrated with the Oracle
database kernel. In Oracle Database 11g R2, Oracle ASM has also been extended to
include support for OCR and voting files to be placed within ASM disk groups.
Oracle ACFS, a feature within ASM in Oracle Database 11g, extends ASM functionality
to act as a general-purpose cluster file system. Oracle database binaries can reside
on ACFS, as can supporting files such as trace and alert logs, and non-Oracle
application files such as SAP ERP. Non-Oracle servers can access ACFS volumes using
industry-standard NAS protocols such as NFS and Common Internet File System
(CIFS).
Oracle Clusterware
Oracle Clusterware is a portable cluster management solution that is integrated with
the Oracle database. It provides the infrastructure necessary to run Oracle RAC,
including Cluster Management Services and High Availability Services. A non-Oracle
application can also be made highly available across the cluster using Oracle
Clusterware.
Oracle Grid Infrastructure
In Oracle Database 11g R2, the Oracle Grid Infrastructure combines Oracle ASM and
Oracle Clusterware into a single set of binaries, separate from the database software.
This infrastructure now provides all the cluster and storage services required to run
an Oracle RAC database.
EMC Mission-Critical Business Continuity for SAP
43
Oracle Real Application Clusters 11g
Oracle RAC is primarily a high-availability solution for Oracle database applications
within the data center. It enables multiple Oracle instances to access a single
database. The cluster consists of a group of independent servers co-operating as a
single system and sharing the same set of storage disks. Each instance runs on a
separate server in the cluster. RAC can provide high availability, scalability, fault
tolerance, load balancing, and performance benefits, and removes any single point of
failure from the database solution.
Oracle RAC on Extended Distance Clusters
Oracle RAC on Extended Distance Clusters (Oracle Extended RAC) is an architecture
that allows servers in the cluster to reside in physically separate locations. This
removes the data center as a single point of failure.
Oracle Extended RAC enables all nodes within the cluster, regardless of location, to
be active. It provides high availability and business continuity during a site or
network failure, as follows:
•
Storage and data remain available and active on the surviving site.
•
Oracle Services load balance and fail over to the Oracle RAC nodes on the
surviving site.
•
Oracle Transparent Application Failover (TAF) allows sessions to automatically
fail over to Oracle RAC nodes on the surviving site.
•
Third-party applications placed under Oracle Clusterware control can load
balance and fail over to the Oracle RAC nodes on the surviving site—for
example, NFS or Apache httpd.
•
Oracle RAC nodes on the surviving site continue to process transactions.
Oracle recommends that the Oracle Extended RAC architecture fits best where the two
data centers are relatively close (no more than 100 km apart) 12.
Oracle RAC and
VPLEX
Oracle RAC is normally run in a local data center due to the potential impact of
distance-induced latency and the relative complexity and overhead of extending
Oracle RAC across data centers with host-based mirroring using Oracle ASM. With
EMC VPLEX Metro, however, an Oracle Extended RAC deployment, from the Oracle
DBA perspective, becomes a standard Oracle RAC install and configuration 13.
Oracle ACFS
configuration
This solution uses four ACFS volumes mounted across the Oracle RAC cluster, as
shown in Table 8. Three of these volumes, SAPMNT, USRSAPTRANS, and ASCS00,
were then exported as NFS shares to the SAP servers, using a virtual IP address and a
highly available NFS resource under control of Oracle Clusterware.
12
See the Oracle white paper: Oracle Real Application Clusters (RAC) on Extended Distance
Clusters.
13
See the EMC white paper: Oracle Extended RAC with EMC VPLEX Metro Best Practices
Planning.
EMC Mission-Critical Business Continuity for SAP
44
Table 8.
Oracle Extended
RAC on VPLEX
Metro
Oracle ACFS volumes and mount points
ACFS volume
Size (GB)
Mount point
Description
SAP_O_HOME
16
/oracle/VSE/112
ORACLE_HOME for database VSE –
shared on all Oracle RAC nodes
SAPMNT
16
/sapmnt/VSE
SAP global directory, which stores
kernels, profiles etc. – shared on all
SAP virtual machines
USRSAPTRANS
16
/usr/sap/trans
SAP transport directory, which
stores the transport files – shared
on all SAP Dialog Instance virtual
machines
ASCS00
16
/usr/sap/VSE/ASCS00
SAP ASCS instance directory, which
stores the instance-related files –
shared on SUSE Linux Enterprise High
Availability Extension cluster nodes
Figure 41 provides a logical representation of the deployment of Oracle Extended RAC
on VPLEX Metro for the solution.
Figure 41.
Oracle Extended RAC over EMC VPLEX Metro
EMC Mission-Critical Business Continuity for SAP
45
Oracle ASM disk
group
configuration
The storage ASM disk groups were configured to reflect the existing single-instance
Oracle database layout. Table 9 shows the ASM disk group layout and configuration.
Table 9.
Oracle ASM disk group size and configuration
ASM disk group*
No of disks
Disk group size (GB)
Redundancy
OCR
5
40
Normal
EA_SAP_ACFS
4
64
External
EA_SAP_DATA
16
2,048
External
EA_SAP_REDO
4
64
External
EA_SAP_REDOM
4
64
External
EA_SAP_FRA
4
256
External
* The EA_SAP_ prefix is used to uniquely identify the ASM disk groups related to the SAP
application in Extended Oracle RAC.
Oracle database
migration process
For the solution, the following two-step process was used to migrate the original
single instance database to an Oracle RAC cluster on ASM (see Figure 42):
1.
Migrate the database from file system to ASM, using the Oracle Recovery
Manager (RMAN) “duplicate from active database” method.
2.
Convert the database to Oracle RAC, using the Oracle rconfig utility.
Figure 42.
Two-step migration process for Oracle database
This two-step process follows the guidelines in these Oracle white papers:
•
Moving your SAP Database to Oracle Automatic Storage Management 11g
Release 2: A Best Practices Guide
•
Configuration of SAP NetWeaver for Oracle Grid Infrastructure 11.2.0.2 and
Oracle Real Application Clusters 11g Release 2: A Best Practices Guide
EMC Mission-Critical Business Continuity for SAP
46
Preparing the source and target systems for duplicating the database
Table 10 outlines how to prepare the source and target systems before duplicating
the database.
Table 10.
Steps for preparing the source and target systems
Preparation—source system
1
Ensure that key environment variables are set: ORACLE_SID, ORACLE_BASE and
ORACLE_HOME.
2
Ensure that a tnsnames.ora entry is configured for the source and target/auxiliary
databases for use during duplication.
3
Ensure that the Oracle password file is configured.
4
Ensure that the compatible parameter is set to 11.2.0.2.0 or later.
Preparation—target system
1
Ensure that Oracle Clusterware is available on the local Oracle RAC node and that
the ASM instance is accessible.
2
Ensure that key environment variables are set: ORACLE_SID, ORACLE_BASE, and
ORACLE_HOME.
3
Ensure that a tnsnames.ora entry is configured for the source and target/auxiliary
databases for use during duplication.
4
Ensure that the Oracle password file is configured.
5
Create an spfile on the target system for the duplication process. For this solution,
the following parameters were amended from the default settings:
*.db_domain='sse.ea.emc.com'
*.db_name='VSE'
*.db_create_file_dest='+EA_SAP_DATA'
*.db_create_online_log_dest_1='+EA_SAP_REDO'
*.db_create_online_log_dest_2='+EA_SAP_REDOM'
*.db_recovery_file_dest='+ES_SAP_FRA'
*.db_recovery_file_dest_size=53445918720
*.log_archive_format='VSEARC%t_%s_%r.dbf'
*.control_files='+EA_SAP_DATA/vse/cntrlVSE1.ctl',
'+EA_SAP_REDO/vse/cntrlVSE2.ctl',
'+EA_SAP_REDOM/vse/cntrlVSE3.ctl'
*.log_file_name_convert=
'/oracle/VSE/origlogA/log_g11m1.dbf','+EA_SAP_REDO',
'/oracle/VSE/mirrlogA/log_g11m2.dbf','+EA_SAP_REDOM',
'/oracle/VSE/origlogB/log_g12m1.dbf','+EA_SAP_REDO',
'/oracle/VSE/mirrlogB/log_g12m2.dbf','+EA_SAP_REDOM',
'/oracle/VSE/origlogA/log_g13m1.dbf','+EA_SAP_REDO',
'/oracle/VSE/mirrlogA/log_g13m2.dbf','+EA_SAP_REDOM',
'/oracle/VSE/origlogB/log_g14m1.dbf','+EA_SAP_REDO',
'/oracle/VSE/mirrlogB/log_g14m2.dbf','+EA_SAP_REDOM'
Note: archive logs are written to the FRA by default
EMC Mission-Critical Business Continuity for SAP
47
Preparation—target system
6
Start up the target instance in nomount mode:
SQL> connect sys/[email protected] as SYSDBA
Connected to an idle instance.
SQL> startup nomount
ORA-32004: obsolete or deprecated parameter(s) specified for
RDBMS instance
Oracle instance started
Total System Global Area
Fixed Size
Variable Size
Database Buffers
Redo Buffers
SQL>
10689474560 bytes
2237776
1644169904
8992587776
50479104
bytes
bytes
bytes
bytes
Migrating the database from file system to ASM
Migrating the database to ASM involves using RMAN to create a duplicate instance
under ASM on the target system:
1.
Start RMAN and connect both the source (target in RMAN) and target (auxiliary
in RMAN) databases as sys.
2.
Run the RMAN commands shown in Figure 43.
connect target sys/[email protected]
connect auxiliary sys/[email protected]
run {
ALLOCATE CHANNEL t1 DEVICE TYPE disk;
ALLOCATE CHANNEL t2 DEVICE TYPE disk;
ALLOCATE CHANNEL t3 DEVICE TYPE disk;
ALLOCATE CHANNEL t4 DEVICE TYPE disk;
ALLOCATE CHANNEL t5 DEVICE TYPE disk;
ALLOCATE CHANNEL t6 DEVICE TYPE disk;
ALLOCATE CHANNEL t7 DEVICE TYPE disk;
ALLOCATE CHANNEL t8 DEVICE TYPE disk;
ALLOCATE AUXILIARY CHANNEL a1 DEVICE TYPE disk;
duplicate target database
to VSE
from active database
nofilenamecheck;
}
Figure 43.
Sample RMAN duplicate script
In the solution environment, it took approximately 18 minutes to produce a duplicate
of the live single instance 500 GB database using this method, as shown in Figure 44.
EMC Mission-Critical Business Continuity for SAP
48
Recovery Manager: Release 11.2.0.3.0 - Production on Fri Mar 2
09:39:33 2012
...
..
.
contents of Memory Script:
{
Alter clone database open resetlogs;
}
executing Memory Script
database opened
Finished Duplicate Db at 02-MAR-2012 09:57:37
Figure 44.
Extract from log file of RMAN script
Validating the migration
When the migration is complete, it is important to validate the placement of data
files, online redo logs, and control files, and to ensure that no corruption occurred
during duplication. Figure 45 shows the RMAN script used to validate the database
migration for the solution.
run {
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
ALLOCATE
validate
Figure 45.
CHANNEL t1 DEVICE TYPE disk;
CHANNEL t2 DEVICE TYPE disk;
CHANNEL t3 DEVICE TYPE disk;
CHANNEL t4 DEVICE TYPE disk;
CHANNEL t5 DEVICE TYPE disk;
CHANNEL t6 DEVICE TYPE disk;
CHANNEL t7 DEVICE TYPE disk;
CHANNEL t8 DEVICE TYPE disk;
CHANNEL t9 DEVICE TYPE disk;
CHANNEL t10 DEVICE TYPE disk;
database;}
Sample RMAN database validation script
The processing time for this validation script was approximately five minutes. Figure
46 shows the output of the RMAN validation script for one of the cloned data files in
the VSE database.
File Status Marked Corrupt Empty Blocks Blocks Examined High SCN
---- ------ -------------- ------------ --------------- ---------18
OK
0
97439
1280000
21966205
File Name: +EA_SAP_DATA/vse/datafile/psapsr3.259.776893807
Block Type Blocks Failing Blocks Processed
---------- -------------- ---------------Data
0
786620
Index
0
347303
Other
0
48638
Figure 46.
Output from RMAN validate database command
Post duplication tasks
When duplication is complete and validated, a new spfile must be created on the
target system as part of the post duplication process. Figure 47 shows the creation of
the spfile for the solution—a single parameter points from the pfile to the spfile.
EMC Mission-Critical Business Continuity for SAP
49
SQL> alter system reset log_file_name_convert;
System altered.
SQL> create pfile='/home/oracle/initVSE.ora_gen' from memory;
File created.
SQL> REM check and change Oracle instance parameters as required
SQL> !vi /home/oracle/initVSE.ora_gen
SQL> create SPFILE='+EA_SAP_DATA/VSE/spfileVSE.ora' from
pfile='/home/oracle/initVSE.ora_gen';
File created.
Figure 47.
Recreating the spfile
Converting the single instance database to Oracle RAC
With the duplicate database, spfile, and pfile created, and the database not yet
registered with Oracle Clusterware, the single instance database was started with
sqlplus, ready for rconfig to convert it to Oracle RAC:
1.
Create an rconfig instruction file for the conversion.
For the solution, the ConvertToRAC_AdminManaged.xml template (located in
the $ORACLE_HOME/assistants/rconfig/sampleXMLs directory) was used to
create this file. Table 11 lists the required parameter values.
Table 11. rconfig instruction file parameter values
Parameter
Value
Convert verify
"YES"
SourceDBHome
/oracle/VSE/112
TargetDBHome
/oracle/VSE/112
SourceDBInfo SID
“VSE”
User
Sys
Password
xxxxxxxxx
Role
Sysdba
Node name
<n:NodeList>
<n:Node name="sse-ea-erac-n01"/>
<n:Node name="sse-ea-erac-n02"/>
<n:Node name="sse-ea-erac-n03"/>
<n:Node name="sse-ea-erac-n04"/> </n:NodeList>
InstancePrefix
VSE00*
SharedStorage type
“ASM”
* This prefix meets SAP requirements for Oracle instance naming.
2.
Run rconfig as the Oracle user.
EMC Mission-Critical Business Continuity for SAP
50
The processing time to convert the database and deploy the four instances across the
cluster was 11 minutes. Figure 48 shows the rconfig output.
[email protected]:~> rconfig ./VSE.xml
Converting Database "VSE.sse.ea.emc.com" to Cluster Database. Target
Oracle Home: /oracle/VSE/112. Database Role: PRIMARY.
Setting Data Files and Control Files
Adding Database Instances
Adding Redo Logs
Enabling threads for all Database Instances
Setting TEMP tablespace
Adding UNDO tablespaces
Adding Trace files
Setting Fast Recovery Area
Updating Oratab
Creating Password file(s)
Configuring Listeners
Configuring related CRS resources
Starting Cluster Database
<?xml version="1.0" ?>
<RConfig version="1.1" >
<ConvertToRAC>
<Convert>
<Response>
<Result code="0" >
Operation Succeeded
</Result>
</Response>
<ReturnValue type="object">
<Oracle_Home>
/oracle/VSE/112
</Oracle_Home>
<Database type="ADMIN_MANAGED" >
<InstanceList>
<Instance SID="VSE001" Node="sse-ea-erac-n01" >
</Instance>
<Instance SID="VSE002" Node="sse-ea-erac-n02" >
</Instance>
<Instance SID="VSE004" Node="sse-ea-erac-n03" >
</Instance>
<Instance SID="VSE003" Node="sse-ea-erac-n04" >
</Instance>
</InstanceList>
</Database>
</ReturnValue>
</Convert>
</ConvertToRAC></RConfig>
Figure 48.
Output from rconfig showing the new instances created
Standardizing Oracle RAC for SAP
After the database was converted, SAP requirements for the Oracle database were
met by making the changes shown in Table 12.
EMC Mission-Critical Business Continuity for SAP
51
Table 12.
Matching SAP requirements for Oracle database
Description
Instance name
Changes applied
Online redo log group
VSE001
Redo log groups 11 – 14
VSE002
Redo log groups 21 – 24
VSE003
Redo log groups 31 – 34
VSE004
Redo log groups 41 – 44
VSE001
PSAPUNDO
VSE002
PSAPUNDO_002
VSE003
PSAPUNDO_003
VSE004
PSAPUNDO_004
Undo tablespace naming
Listener.ora
Add the following line to the listener.ora on each node,
where VSE00x is the instance name for that node:
SID_LIST_LISTENER =
(SID_LIST=(SID_DESC=(SID_NAME=VSE00x)
(ORACLE_HOME=/oracle/VSE/112)))
Connecting to Oracle RAC from SAP
To enable SAP to connect to the newly created RAC database, tnsnames.ora on each
of the SAP virtual machines (SAPDI1 and SAPDI2) was amended to use the new
database, as shown in Figure 49. The SAP services were then restarted.
VSE.WORLD=
(DESCRIPTION =
(LOAD_BALANCE = OFF)
(FAILOVER = ON)
(ADDRESS_LIST =
(ADDRESS =
(PROTOCOL = TCP)
(HOST = sse-ea-erac-scan-c01.sse.ea.emc.com)
(PORT = 1521)
)
)
(CONNECT_DATA =
(SERVICE_NAME = VSE.sse.ea.emc.com)
(FAILOVER_MODE =
(TYPE = SELECT)
(METHOD = BASIC))
)
)
Figure 49.
Sample tnsnames.ora file entry for the Oracle RAC database
Transparent Application Failover (TAF) is a client-side feature that allows clients to
reconnect to surviving instances if a database instance fails. TAF can be configured
using either a client-side specified connect string or server-side service attributes.
In the solution, database service VSE.sse.ea.emc.com was configured for TAF on
Oracle RAC. It was also configured on the client side to enable SAP to use TAF. TAF
was set to establish connections at failover time and to enable users with open
cursors to continue fetching on them after failure of select operations.
EMC Mission-Critical Business Continuity for SAP
52
Brocade network infrastructure
Introduction
Overview
This section describes the IP and SAN networks deployed for the solution in the two
data centers, and the Layer 2 extension between the data centers. The network
infrastructure is built using these Brocade components:
•IP network
SAN
•
Brocade VDX 6720 Data Center Switches
•
Brocade DCX 8510 Backbones
•
Brocade MLX Series routers
•
Brocade 825 HBAs
•
Brocade 1020 CNAs
Brocade VDX 6720
The Brocade VDX 6720 Data Center Switch is a high-performance, ultra-low latency,
wire-speed 10 GbE fixed port switch. It is specifically designed to improve network
utilization, maximize application availability, increase scalability, and dramatically
simplify network architecture in virtualized data centers. With a rich set of Layer 2
features, the Brocade VDX 6720 is an ideal platform for traditional Top-of-Rack (ToR)
switch deployments.
By delivering Brocade VCS Fabric technology, the Brocade VDX 6720 enables
organizations to build data center Ethernet fabrics—revolutionizing the design of
Layer 2 networks and providing an intelligent foundation for cloud-optimized data
centers.
Brocade MLX Series
Brocade MLX Series routers are designed to enable cloud-optimized networks by
providing industry-leading 100 GbE, 10 GbE, and 1 GbE wire-speed density; rich IPv4,
IPv6, Multi-VRF, Multiprotocol Label Switching (MPLS), and carrier Ethernet
capabilities; and advanced Layer 2 switching.
By leveraging the Brocade MLX Series, mission-critical data centers can support more
traffic, achieve greater virtualization, and provide high-value cloud-based services
using less infrastructure—thereby simplifying operations and reducing costs.
Moreover, the Brocade MLX Series can reduce complexity in large campus networks
by collapsing core and aggregation layers, as well as providing connectivity between
sites using MPLS/VPLS. All of the Brocade MLX Series routers help reduce power and
cooling costs with the lowest power consumption and heat dissipation in their class.
Designed for non-stop networking, the Brocade MLX Series features Multi-Chassis
Trunking (MCT), which provides more than 30 TB/s of dual-chassis bandwidth, full
active/active routing links, and uninterrupted traffic flow in the event of node failover.
Organizations can achieve high resiliency through fully redundant switch fabrics,
management modules, power supplies, and cooling systems. To further ensure
network and application availability, the Brocade IronWare operating system features
hitless management failover and software upgrades.
EMC Mission-Critical Business Continuity for SAP
53
Brocade DCX 8510 Backbone
Networks need to evolve in order to support the growing demands of highly
virtualized environments and private cloud architectures. Today, Fibre Channel (FC) is
the de facto standard for storage networking in the data center. The introduction of
16 Gb/s Fibre Channel extends the life of this robust, reliable, and high-performance
technology. This enables organizations to continue leveraging their existing IT
investments as they solve their most difficult business challenges.
Brocade DCX 8510 Backbones are the industry’s most powerful 16 Gb/s Fibre
Channel switching infrastructure, and provide the most reliable, scalable, highperformance foundation for private cloud storage and highly virtualized
environments. They are designed to increase business agility while providing nonstop access to information and reducing infrastructure and administrative costs.
The 16 Gb FC capability of the Brocade DCX 8510 offers significant benefits for data
center to data center SAN Metro connectivity:
•
16 Gb provides the maximum throughput and lowest latency FC for
deployments utilizing Fibre connections between data centers.
•
Optional 10 Gb FC line speed for optimal line utilization if a DWDM network is
deployed between sites. This feature requires a license.
•
Optional frame-level Inter-Switch Link (ISL) Trunking that enables high
utilization compared to standard DPS trunking. This feature requires a license.
•
Optional compression for the ISLs between the data centers. This provides
added bandwidth for deployments where the number of site-to-site
connections are limited.
•
Optional data in-flight encryption for the ISLs between the data centers for
deployments requiring very high levels of data security.
•
Buffer credit loss detection and recovery.
•
Automatic Forward Error Correction (FEC), which proactively corrects up to 11 bit
errors per 2112-bit FC frame.
•
Diagnostic mode for the ISL ports between data centers can be used on any
(offline) ISL port and offers the following features:

Electrical and optical loopback tests

Link saturation testing

Link distance measurement accuracy within 5 m when used with 8 Gb SFP+
and 50 m when used with 10 GbE SFP+.
EMC Mission-Critical Business Continuity for SAP
54
IP network
configuration
For the solution, the IP network in each data center is built using two Brocade VDX
6720 switches in a VCS configuration. All servers are connected to the network using
redundant 10 GbE connections provided by Brocade 1020 CNAs.
The two Brocade VDX switches at each site are connected to a Brocade MLX Series
router using a Virtual Link Aggregation Group (vLAG). The Brocade MLX Series routers
extend the Layer 2 network between the two data centers.
Note
A vLAG is a fabric service that enables a Link Aggregation Group (LAG) to
originate from multiple Brocade VDX switches. In the same way as a standard
LAG, a vLAG uses the Link Aggregation Control Protocol (LACP) to control the
bundling of several physical ports together to form a single logical channel.
Oracle RAC relies on a highly available virtual IP (the HAIP or RAC interconnect) for
private network communication. With HAIP, interconnect traffic is load balanced
across the set of interfaces identified as the private network. For the solution, a
separate VLAN—VLAN 10—is used for the interconnect. VLAN 20 handled all public
traffic.
All traffic between Site A and Site B is routed through the Brocade MLX routers using
multiple ports configured as a LAG.
Figure 50 shows the IP network infrastructure.
Figure 50.
The solution IP networks
EMC Mission-Critical Business Continuity for SAP
55
SAN network
configuration
The SAN in each data center is built with Brocade DCX 8510 Backbones, as shown in
Figure 51. All servers are connected to the SAN using redundant 8 Gb connections
that are provided by Brocade 825 HBAs.
The VPLEX to VPLEX connection between the data centers uses multiple FC
connections between the Brocade DCX 8510 Backbones. These are used in
active/active mode with failover.
Figure 51.
The solution SAN networks
EMC Mission-Critical Business Continuity for SAP
56
EMC storage infrastructure
Introduction
Overview
This section describes the storage infrastructure for the solution:
•
A Symmetrix VMAX array provides the storage platform at Site A
•
An EMC VNX5700 array provides the storage platform at Site B
The two storage arrays are deployed with a matching LUN configuration.
EMC Symmetrix VMAX
EMC Symmetrix VMAX is a high-end storage array based on Intel Xeon processors and
optimized for the virtual data center. Intel Stop and Scream detects poison packets in
PCIe, and enables enhanced error isolation in a multiblade, highly-available
environment. This results in shorter downtime, faster problem diagnosis, and
simplified repair process, enabling the IT manager to optimize the virtual data center.
Built on the strategy of simple, intelligent, modular storage, the Symmetrix VMAX
incorporates a highly scalable Virtual Matrix Architecture that enables it to grow
seamlessly and cost-effectively from an entry-level configuration into the world’s
largest storage system. The VMAX supports Flash, FC, and SATA drives within a single
array, and an extensive range of RAID types. EMC Fully Automated Storage Tiering for
Virtual Pools (FAST VP) automates tiered storage strategies.
The EMC Enginuity operating environment provides the intelligence that controls all
components in a VMAX array.
EMC VNX5700
The VNX5700 is a member of the VNX series next-generation storage platform, which
is designed to deliver maximum performance and scalability for mid-tier enterprises,
enabling them to dramatically grow, share, and cost-effectively manage multiprotocol
file and block systems. VNX supports Flash, SAS, and NL-SAS drives within a single
array and an extensive range of RAID types. FAST VP provides automated storage
tiering across all drive types.
The VNX series utilizes the Intel Xeon 5600 series processors, which help make it 2-3
times faster overall than its predecessor. The VNX quad-core processor supports
demands of advanced storage capabilities such as virtual provisioning, compression,
and deduplication. Furthermore, performance of the Xeon 5600 series enables EMC
to realize its vision for FAST on the VNX, with optimized performance and capacity,
without tradeoffs, in a fully automated fashion.
The VNX Operating Environment (VNX OE) allows Microsoft Windows and Linux/UNIX
clients to share files in multiprotocol NFS and CIFS environments. At the same time, it
supports Internet SCSI (iSCSI), FC, and Fibre Channel over Ethernet (FCoE) access for
high-bandwidth and latency-sensitive block applications.
EMC Mission-Critical Business Continuity for SAP
57
Symmetrix VMAX
configuration
Storage layout
For the solution, VPLEX Metro, Oracle Extended RAC, and SAP volumes are laid out
using Virtual Provisioning. This configuration places the Oracle data files and log files
in separate thin pools and allows each to use distinct RAID protection. The data files
reside in a RAID 5 protected pool and the redo logs in a RAID 1 protected pool.
Figure 52 is a logical representation of how the storage layout corresponds to the
Oracle ASM disk groups.
Figure 52.
Storage groups and ASM disk groups
Storage was not pre-allocated to any devices, except for the Oracle REDO log devices.
EMC recommends that these devices are fully pre-allocated on creation, using
persistent allocation. This ensures that their storage is available up front and, if a
zero space reclaim is run on the pool at any stage, their pre-allocated capacity is not
returned to the pool’s free space.
Device tables
Table 13 shows the size and number of devices configured for each ASM disk group.
Table 13.
Device sizes
Storage group
Number of devices
Device size (GB)
OCR
5
8
FRA
4
16
REDO
8
16
DATA
16
128
ACFS
4
16
EMC Mission-Critical Business Continuity for SAP
58
Table 14 shows the size and number of devices configured for VPLEX Metro.
Table 14.
VNX5700
configuration
Size and number of devices configured for VPLEX Metro
VPLEX Device
Number of devices
Device size (GB)
VPLEX metadata
2
80
VPLEX log volume
2
20
VPLEX metadata backup
2
80
For the solution, VPLEX Metro, Oracle Extended RAC, and SAP volumes on the
VNX5700 array at Site B were laid out using traditional RAID groups and LUNs,
whereas these volumes were laid out on the VMAX at Site A using Virtual
Provisioning. Similar EMC best practices apply to both provisioning methods, and the
same ASM disk groups were created on the VNX and VMAX.
On the VNX, this configuration places the Oracle data files and log files in separate
RAID groups and allows each to use distinct RAID protection. The data files reside in a
RAID 5 protected RAID group and the redo logs in a RAID 10 protected RAID group. The
FRA disk group resides on NL-SAS drives with RAID 6 protection.
The LUNs created on the VNX match the number and size of the thin devices created
on the VMAX, as shown in Figure 52, Table 13, and Table 14. Figure 53 shows the
layout of the RAID groups on the VNX.
Figure 53.
VNX RAID group layout
EMC Mission-Critical Business Continuity for SAP
59
High availability and business continuity – testing and validation
Introduction
SAP enqueue
service process
failure
The EMC validation team initially installed and validated the environment without any
high-availability or business continuity protection schemes. We then transformed the
environment to the mission-critical business continuity solution described in this
white paper. We carried out the following tests to validate the solution and
demonstrate the elimination of all single points of failure from the environment:
•
SAP enqueue service process failure
•
SAP ASCS instance virtual machine failure
•
Oracle RAC node failure
•
Site failure
•
VPLEX cluster isolation
Test scenario
This test scenario validates that, if the enqueue service process fails, the SUSE Linux
Enterprise High Availability Extension cluster promotes the SAP ERS instance to a fully
functional ASCS instance and takes over the lock table without end user interruption.
To test this failure scenario, we terminated the enqueue process on the active ASCS
node by running the kill command:
kill -9 <process id>
System behavior
The system responds to the enqueue service process failure as follows:
1.
The SAPInstance resource agent detects and reports the failure, as shown in
Figure 54.
Figure 54.
SAPInstance resource agent detects and reports failure
EMC Mission-Critical Business Continuity for SAP
60
2.
The master/slave resource agent promotes the previous slave node
(SAPASCS1) to the master node, which hosts the ASCS services, and starts
the ERS as a slave on the other node (SAPASCS2) when it rejoins the cluster
(see Figure 55).
Figure 55.
3.
Master/slave resource agent switches the master and slave nodes
The replicated lock table is restored, as shown in Figure 56.
Figure 56.
Replicated lock table restored
Result
The end user does not notice the enqueue process failure, unless an enqueue
operation is running. In this case, the end user experiences a longer transaction
response time during the switchover. New users can log into the system immediately
after the message server switchover. No administrative intervention is required.
EMC Mission-Critical Business Continuity for SAP
61
SAP ASCS instance Test scenario
virtual machine
This test scenario validates that, in the event of an unexpected ESXi server outage
failure
(which is equivalent to a virtual machine failure), the High Availability Extension
cluster promotes the SAP ERS instance to a fully functional ASCS instance and takes
over the lock table, without end-user interruption.
To test this failure scenario, we powered off (via DRAC) the ESXi server that hosts the
SAP ASCS instance virtual machine. We then rebooted the server without entering
maintenance mode.
System behavior
The system responds to the virtual machine failure as follows:
1.
SAPASCS2 becomes unavailable from vSphere Client (see Figure 57).
Figure 57.
2.
Virtual machine fails
The SAPInstance resource agent detects and reports the failure (see Figure 58).
Figure 58.
SAPInstance resource agent detects and reports failure
EMC Mission-Critical Business Continuity for SAP
62
3.
VMHA restarts the failed virtual machine (SAPASCS2) on the surviving ESXi
host (see Figure 59).
Figure 59.
4.
VMHA restarts the failed virtual machine
The master/slave resource agent promotes the previous slave node
(SAPASCS1) to the master node, which hosts the ASCS services, and starts
the ERS as a slave on the other node (SAPASCS2) when it rejoins the cluster
(see Figure 60).
Figure 60.
Master/slave resource agent switches the master and slave nodes
EMC Mission-Critical Business Continuity for SAP
63
5.
The replicated lock table is restored (see Figure 61).
Figure 61.
Replicated lock table restored
Result
The end user does not notice the enqueue process failure, unless an enqueue
operation is running. In this case, the end user experiences a longer transaction
response time during the switchover. New users can log into the system immediately
after the message server switchover. No administrative intervention is required.
Oracle RAC node
failure
Test scenario
This test scenario validates that, in the event of an unexpected RAC node failure, the
SAP instances automatically connect to other RAC nodes. End users can continue
their transactions without interruption, unless uncommitted transactions (at the
database level) are being executed on the failed RAC node.
To test this failure scenario, we rebooted the server to cause an Oracle node failure.
System behavior
The system responds to the RAC node failure as follows:
1.
The RAC node goes offline and instance VSE003 is unavailable, as shown in
Figure 62.
[email protected]:~> srvctl status database -d VSE
Instance VSE001 is running on node sse-ea-erac-n01
Instance VSE002 is running on node sse-ea-erac-n02
Instance VSE004 is running on node sse-ea-erac-n03
Instance VSE003 is not running on node sse-ea-erac-n04
Figure 62.
2.
RAC node goes offline
The SAP instance work process connects to another RAC instance, as shown
in Figure 63.
EMC Mission-Critical Business Continuity for SAP
64
.
Figure 63.
SAP instance connects to another RAC node
Result
The end user experiences a longer transaction response time when the dialog
instance work process reconnects to another RAC node. Uncommitted transactions
are rolled back at the database level to guarantee the data consistency. The end user
receives a system error message (short dump) and needs to restart the transaction.
No administrative intervention is required.
Site failure
Test scenario
This test scenario validates that, in the event of a complete site failure, the surviving
RAC nodes preserve database operations.
To test this failure scenario, we simulated a complete failure of Site A, including
VPLEX cluster, ESXi server, network, and Oracle RAC node components. The VPLEX
Witness remained available on Site C. On Site B, VPLEX cluster-2 remained in
communication with the VPLEX Witness.
Figure 64 shows the status of the environment before the site failure.
EMC Mission-Critical Business Continuity for SAP
65
Figure 64.
Status of environment prior to Site A failure
System behavior
The system responds to site failure as follows:
•
When Site A fails, VPLEX Witness ensures that the consistency group’s detach
rule, which defines cluster-1 as the preferred cluster, is overridden and that the
storage served by VPLEX cluster-2 on Site B remains available.
•
RAC nodes sse-ea-erac-n03 and sse-ea-erac-n04 on Site B remain available.
•
When the ESXi servers on Site A fail, VMHA restarts SAPASCS1 and SAPDI1 on
Site B. SAPASCS1 is restarted on a different ESXi host to SAPASCS2, as
prescribed by the defined VM-VM affinity rule.
•
SUSE Linux Enterprise High Availability Extension detects the failure of cluster
node SAPASCS1. Because the ERS was running on this node, the cluster takes
no action except to restart the ERS when SAPASCS1 rejoins the cluster. The lock
table is preserved and operational all the time.
•
End users on SAPDI1 lose their sessions due to the ESXi server failure. During
the restart process, new users are directed to SAPDI2. When SAPDI1 restarts on
Site B, users can log into SAPDI1 again.
EMC Mission-Critical Business Continuity for SAP
66
Figure 64 shows the status of the environment after the site failure.
Figure 65.
Environment status after Site A failure
Result
Table 15 shows the expected and observed behaviors of the system when Site A fails.
Table 15.
Oracle RAC nodes
(database VSE)
ESXi server
Virtual machine
Expected and observed behaviors
System
Status prior to
test
sse-ea-erac-n01 (Site A)
Available
Ejected
Ejected
sse-ea-erac-n02 (Site A)
Available
Ejected
Ejected
sse-ea-erac-n03 (Site B)
Available
Available
Available
sse-ea-erac-n04 (Site B)
Available
Available
Available
sse-ea-r710a (Site A)
Available
Unavailable
Unavailable
SAPASCS1
sse-ea-r710b (Site A)
SAPDI1
sse-ea-r710c (Site B)
SAPDI2
sse-ea-r710d (Site B)
SAPASCS2
Available
Expected behavior
VMHA restart Site B
Unavailable
Available
Available
VMHA restart Site B
Available
Available
Available
Available
Available
Available
Available
Available
Observed behavior
VMHA restart Site B
Unavailable
VMHA restart Site B
Available
Available
Available
Available
EMC Mission-Critical Business Continuity for SAP
67
VPLEX cluster
SAP services
System
Status prior to
test
VPLEX1 – Site A – cluster-1
Available
Unavailable
Unavailable
VPLEX2 – Site B – cluster-2
Available
Available
Available
Enqueue Replication Server
Available
Unavailable
Unavailable
SLE HAE restart after
reboot on Site B
SLE HAE restart after
reboot on Site B
Available
Available
Enqueue/Message Server
VPLEX cluster
isolation
Available
Expected behavior
Observed behavior
Test scenario
This test scenario validates that, in the event of isolation of a VPLEX cluster, the SAP
applications and database continue operation on the surviving site without
interruption.
To test this failure scenario, we simulated isolation of the preferred cluster on Site A,
with both the external Management IP network and the VPLEX WAN communications
network partitioned. The LAG network remains available. VPLEX Witness remains
available on Site C. On Site B, VPLEX cluster-2 remains in communication with VPLEX
Witness.
System behavior
The system responds to the VPLEX cluster isolation as follows:
•
When the VPLEX on Site A becomes isolated, the VPLEX Witness ensures that
the consistency group’s detach rule, which defines cluster-1 as the preferred
cluster, is overridden and that the storage served by VPLEX cluster-2 on Site B
remained available.
•
RAC nodes sse-ea-erac-n03 and sse-ea-erac-n04 on Site B remain available and
RAC nodes sse-ea-erac-n01 and sse-ea-erac-n02 on Site A are ejected.
•
The ESXi servers on Site A remain available and virtual machines SAPASCS1
and SAPDI1 remain active due to the use of VPLEX Metro HA Cross-Cluster
Connect.
Figure 64 shows the status of the environment after VPLEX isolation on Site A.
EMC Mission-Critical Business Continuity for SAP
68
Figure 66.
Environment status after isolation of VPLEX on Site A
Result
Table 16 shows the expected and observed behaviors of the system when the VPLEX
at Site A is isolated.
Table 16.
Oracle RAC nodes
(database VSE)
ESXi server
Virtual machine
Expected and observed behaviors
System
Status prior to
test
sse-ea-erac-n01 (Site A)
Available
Ejected
Ejected
sse-ea-erac-n02 (Site A)
Available
Ejected
Ejected
sse-ea-erac-n03 (Site B)
Available
Available
Available
sse-ea-erac-n04 (Site B)
Available
Available
Available
sse-ea-r710a (Site A)
Available
Available
Available
SAPASCS1
sse-ea-r710b (Site A)
SAPDI1
sse-ea-r710c (Site B)
SAPDI2
sse-ea-r710d (Site B)
SAPASCS2
Available
Available
Available
Available
Available
Available
Available
Expected
behavior
Available
Available
Available
Available
Available
Available
Available
Observed
behavior
Available
Available
Available
Available
Available
Available
Available
EMC Mission-Critical Business Continuity for SAP
69
VPLEX cluster
SAP services
System
Status prior to
test
Expected
behavior
Observed
behavior
VPLEX1 – Site A – cluster-1
Available
Unavailable
Unavailable
VPLEX2 – Site B – cluster-2
Available
Available
Available
Enqueue Replication Server
Available
Available
Available
Enqueue/Message Server
Available
Available
Available
EMC Mission-Critical Business Continuity for SAP
70
Conclusion
Summary
This solution demonstrates the transformation of a traditional active/passive SAP
deployment to a highly available business continuity solution with active/active data
centers and always-on application availability.
The solution combines EMC, VMware, Oracle, SUSE, and Brocade high-availability
components to:
•
Eliminate single points of failure at all layers in the environment
•
Provide active/active data centers that support near-zero RPOs and RTOs
•
Enable mission-critical business continuity for SAP applications
Each single point of failure was identified and mitigated by using fault-tolerant
components and high-availability clustering technologies. Resource utilization was
increased by enabling active/active data access. Failure handling was fully
automated to eliminate the final and often most unpredictable SPOF from the
architecture—people and processes.
In addition, the use of management and monitoring tools such as the vSphere Client,
EMC Virtual Storage Integrator, and the VPLEX performance tools simplifies
operational management and allows monitoring and mapping of the infrastructure
stack.
Oracle RAC on Extended Distance Clusters over VPLEX provides these benefits:
Findings
•
Simplified management of deployment—installation, configuration, and
maintenance are the same as for a single site RAC deployment.
•
Hosts connect only to their local VPLEX cluster, but have full read-write access
to the same database at both sites.
•
No need to deploy Oracle voting disk and Clusterware on a third site.
•
Eliminates the costly host CPU cycles consumed by ASM mirroring—I/O is sent
only once from the host to the local VPLEX.
•
Ability to create consistency groups that protect multiple databases and/or
applications as a unit.
To validate the solution, the EMC validation team ran the following tests and noted
the behaviors indicated:
•
Simulate a SAP enqueue service process failure
 Application continues without interruption
•
Simulate a SAP ASCS instance virtual machine failure
 Application continues without interruption
•
Simulate an Oracle RAC node failure
 Application continues without interruption
EMC Mission-Critical Business Continuity for SAP
71
•
Simulate a total site failure
 Application continues without interruption
•
Validate VPLEX Witness functionality during simulated isolation of a VPLEX cluster
 Application continues without interruption
The testing demonstrates how VMware, SAP, SUSE, and Oracle high-availability
solutions eliminate single points of failure at the local level.
It also demonstrates how VPLEX Metro, combined with SUSE Linux Enterprise High
Availability Extension, Oracle Extended RAC, and Brocade networking, extends this
high availability to break the boundaries of the data center and allow servers at
multiple data centers to have read/write access to shared block storage devices.
VPLEX Witness and Cross-Cluster Connect provide an even higher level of resilience.
Together, these technologies enable transformation of a traditional
active/passive data center deployment to a mission-critical business continuity
solution with active/active data centers, 24/7 application availability, no single
points of failure, and near-zero RTOs and RPOs.
EMC Mission-Critical Business Continuity for SAP
72
References
EMC
Oracle
VMware
For additional information, see the following EMC documents (available on EMC.com
and on the EMC online support website):
•
EMC VPLEX Metro Witness Technology and High Availability
•
Using VMware vSphere with EMC VPLEX Best Practices Planning
•
Conditions for Stretched Hosts Cluster Support on EMC VPLEX Metro
•
Oracle Extended RAC with EMC VPLEX Metro Best Practices Planning
•
EMC VPLEX with GeoSynchrony 5.0 Configuration Guide
•
Implementation and Planning Best Practices for EMC VPLEX – Technical Notes
•
EMC VPLEX with GeoSynchrony 5.0 and Point Releases CLI Guide
•
EMC Simple Support Matrix for EMC VPLEX and GeoSynchrony
•
Validating Host Multipathing with EMC VPLEX – Technical Notes
For additional information, see the following Oracle documents:
•
Moving your SAP Database to Oracle Automatic Storage Management 11g
Release 2: A Best Practices Guide
•
SAP with Oracle Real Application Clusters 11g Release 2 and Oracle Automatic
Storage Management 11g Release 2: Advanced Configurations & Techniques
•
Configuration of SAP NetWeaver for Oracle Grid Infrastructure 11.2.0.2 and
Oracle Real Application Clusters 11g Release 2: A Best Practices Guide
•
Oracle Real Application Clusters (RAC) on Extended Distance Clusters
•
Oracle Database Upgrade Guide Upgrade to Oracle Database 11g Release 2
(11.2): UNIX For Oracle Patch Set Release 11.2.0.2 and 11.2.0.3
For additional information, see the following VMware documents:
•
VMware vSphere Networking ESXi 5.0
•
VMware vSphere Availability ESXi 5.0
•
VMware Knowledge Base article 1026692: Using VPLEX Metro with VMware HA
•
VMware Knowledge Base article 1034165: Disabling simultaneous write
protection provided by VMFS using the multi-writer flag
•
SAP Solutions on VMware vSphere: High Availability
•
SAP Solutions on VMware: Best Practices Guide
EMC Mission-Critical Business Continuity for SAP
73
SUSE
SAP
For additional information, see the following SUSE documents:
•
SUSE Linux Enterprise High Availability Extension – High Availability Guide
•
Running SAP NetWeaver on SUSE Linux Enterprise Server with High Availability
– Simple Stack
•
SAP Applications Made High Available on SUSE Linux Enterprise Server 10
•
Protection of Business-Critical Applications in SUSE Linux Enterprise
Environments Virtualized with VMware vSphere 4 and SAP NetWeaver as an
Example
For additional information, see the following SAP documents:
•
SAP Note 1552925 – Linux High Availability Cluster Solutions
•
SAP Note 1431800 – Oracle 11.2.0 Central Technical Note
•
SAP Note 105047 – Support for Oracle Functions in the SAP Environment
•
SAP Note 1550133 – Oracle Automatic Storage Management (ASM)
•
SAP Note 527843 – Oracle RAC Support in the SAP Environment
•
SAP Note 989963 – Linux: VMware Timing Problem
•
SAP Note 1122388 – Linux: VMware vSphere Configuration Guidelines
•
SAP Note 1310037 – SUSE Linux Enterprise Server 11: Installation notes
•
SAP Installation Guide for SAP ERP 6.0 – EHP 4 Ready ABAP on Linux: Oracle Based on SAP NetWeaver 7.0 including Enhancement Package 1
•
SAP Enqueue Replication Server Setup help portal
EMC Mission-Critical Business Continuity for SAP
74
Appendix – Sample configurations
CRM sample
configuration
node SAPASCS1 \
attributes standby="off"
node SAPASCS2 \
attributes standby="off"
primitive rsc_IP_VSE_SAPVIPE ocf:heartbeat:IPaddr2 \
operations $id="rsc_IP_VSE_SAPVIPE-operations" \
op monitor interval="10s" timeout="20s" on_fail="restart" \
params ip="xxx.xxx.xxx.xxx" \
meta is-managed="true"
primitive rsc_SAP_VSE_ASCS00_SAPVIPE ocf:heartbeat:SAPInstance \
operations $id="rsc_SAP_VSE_ASCS00_SAPVIPE-operations" \
op monitor interval="120" enabled="true" role="Master" timeout="60" start_delay="5" \
op start interval="0" timeout="180" \
op stop interval="0" timeout="240" \
op promote interval="0" role="Master" timeout="320" start_delay="0" \
op demote interval="0" role="Slave" timeout="320" start_delay="0" \
params InstanceName="VSE_ASCS00_SAPVIPE"
ERS_InstanceName="VSE_ERS01_SAPASCS2" AUTOMATIC_RECOVER="true"
START_PROFILE="/sapmnt/VSE/profile/START_ASCS00_SAPVIPE"
ERS_START_PROFILE="/sapmnt/VSE/profile/START_ERS01_SAPASCS2" \
meta target-role="Started"
primitive sbd_stonith stonith:external/sbd \
meta target-role="started" \
op monitor interval="15" timeout="15" start-delay="15" \
params sbd_device="/dev/sdb1"
group grp_sap_VSE rsc_IP_VSE_SAPVIPE \
meta is-managed="true" target-role="started"
ms msl_sap_VSE_ASCS00_SAPVIPE rsc_SAP_VSE_ASCS00_SAPVIPE \
meta globally-unique="true" target-role="Started" clone-node-max="1" master-max="1"
notify="true"
colocation colocation_IP_ASCS inf: grp_sap_VSE:Started
msl_sap_VSE_ASCS00_SAPVIPE:Master
order ord_VSE_IP_Master : grp_sap_VSE msl_sap_VSE_ASCS00_SAPVIPE:promote
symmetrical=false
property $id="cib-bootstrap-options" \
dc-version="1.1.5-5bd2b9154d7d9f86d7f56fe0a74072a5a6590c60" \
cluster-infrastructure="openais" \
expected-quorum-votes="2" \
last-lrm-refresh="1329421965" \
default-resource-stickiness="1000" \
no-quorum-policy="ignore" \
stonith-timeout="120s"
ASCS sample
instance profile
SAPSYSTEMNAME = VSE
SAPSYSTEM = 00
INSTANCE_NAME = ASCS00
DIR_CT_RUN = $(DIR_EXE_ROOT)/run
DIR_EXECUTABLE = $(DIR_INSTANCE)/exe
SAPLOCALHOST = SAPVIPE
#----------------------------------------------------------------------# SAP Message Server parameters are set in the DEFAULT.PFL
#----------------------------------------------------------------------ms/standalone = 1
EMC Mission-Critical Business Continuity for SAP
75
ms/server_port_0 = PROT=HTTP,PORT=81$$
#----------------------------------------------------------------------# SAP Enqueue Server
#----------------------------------------------------------------------enque/table_size = 4096
rdisp/enqname = $(rdisp/myname)
enque/snapshot_pck_ids = 100
ipc/shm_psize_34 = 0
enque/server/replication = true
enque/server/max_requests = 1000
enque/enrep/stop_timeout_s = 0
enque/enrep/stop_retries = 0
ERS sample
instance profile
SAPSYSTEM = 01
SAPSYSTEMNAME = VSE
INSTANCE_NAME = ERS01
#-------------------------------------------------------------------# Special settings for this manually set up instance
#-------------------------------------------------------------------DIR_EXECUTABLE = $(DIR_INSTANCE)/exe
DIR_CT_RUN = /usr/sap/VSE/SYS/exe/run
#-------------------------------------------------------------------# Settings for enqueue monitoring tools (enqt, ensmon)
#-------------------------------------------------------------------enque/process_location = REMOTESA
rdisp/enqname = $(rdisp/myname)
#-------------------------------------------------------------------# standalone enqueue details from ASCS instance
#-------------------------------------------------------------------ASCSID = 00
ASCSHOST = SAPVIPE
enque/serverinst = $(ASCSID)
enque/serverhost = $(ASCSHOST)
#-------------------------------------------------------------------# HA polling
#-------------------------------------------------------------------#enque/enrep/hafunc_implementation = script
#enque/enrep/poll_interval = 10000
#enque/enrep/hafunc_init =
#enque/enrep/hafunc_check = $(DIR_EXECUTABLE)/enqtest.sh
ERS sample START
profile
SAPSYSTEMNAME = VSE
SAPSYSTEM = 01
INSTANCE_NAME = ERS01
#----------------------------------------------------------------------# Special Settings for this manually set up instance
#----------------------------------------------------------------------ASCSID = 00
DIR_CT_RUN = /usr/sap/VSE/SYS/exe/run
DIR_EXECUTABLE = $(DIR_INSTANCE)/exe
_PF = $(DIR_PROFILE)/VSE_ERS01_SAPASCS2
SETENV_00 = LD_LIBRARY_PATH=$(DIR_EXECUTABLE)
SETENV_01 = PATH=$(DIR_INSTANCE)/exe:%(PATH)
#----------------------------------------------------------------------# Copy SAP Executables
EMC Mission-Critical Business Continuity for SAP
76
#----------------------------------------------------------------------_CPARG0 = list:$(DIR_EXECUTABLE)/ers.lst
Execute_00 = immediate $(DIR_EXECUTABLE)/sapcpe$(FT_EXE) $(_CPARG0) pf=$(_PF)
#----------------------------------------------------------------------# Start enqueue replication server
#----------------------------------------------------------------------_ER = er.sap$(SAPSYSTEMNAME)_$(INSTANCE_NAME)
Execute_01 = immediate rm -f $(_ER)
Execute_02 = local ln -s -f $(DIR_EXECUTABLE)/enrepserver $(_ER)
Restart_Program_00 = local $(_ER) pf=$(_PF) NR=$(ASCSID)
DI sample instance SAPSYSTEMNAME = VSE
SAPSYSTEM = 00
profile
INSTANCE_NAME = D00
DIR_CT_RUN = $(DIR_EXE_ROOT)/run
DIR_EXECUTABLE = $(DIR_INSTANCE)/exe
exe/saposcol = $(DIR_CT_RUN)/saposcol
rdisp/wp_no_dia = 10
rdisp/wp_no_btc = 3
exe/icmbnd = $(DIR_CT_RUN)/icmbnd
icm/server_port_0 = PROT=HTTP,PORT=80$$
SAPFQDN = sse.ea.emc.com
SAPLOCALHOSTFULL = $(SAPLOCALHOST).$(SAPFQDN)
ipc/shm_psize_10 = 136000000
ipc/shm_psize_40 = 112000000
rdisp/wp_no_vb = 1
rdisp/wp_no_vb2 = 1
rdisp/wp_no_spo = 1
enque/process_location = REMOTESA
enque/serverhost = SAPVIPE
enque/serverinst = 00
enque/deque_wait_answer = TRUE
enque/con_timeout = 2000
enque/con_retries = 60
EMC Mission-Critical Business Continuity for SAP
77