Rockwell Automation Allen-Bradley 140U Installation Instructions Manual
Rockwell Automation Allen-Bradley 140U N-Frame Circuit Breakers and Molded Case Switches are designed for reliable protection of electrical circuits. These devices are UL-listed and conform to IEC standards. Featuring integral trip units, they offer up to 1600 Amps of continuous current rating and provide a variety of protection functions including overload, short circuit, and ground fault protection. The trip units utilize microprocessor-based technology for accurate current sensing, adjustable pick-up and time delay settings allow for precise circuit coordination. The 140U series is suitable for various applications such as industrial machinery, power distribution systems, and building automation.
Advertisement
Advertisement
Bul. 140U Installation Instructions for Bul. 140U N-Frame Circuit Breakers and Molded Case Switches DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES. ALLEN-BRADLEY IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS. The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment as well as general and local health and safety laws, codes and procedures. The recommendations and information contained herein are based on Rockwell experience and judgement, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Rockwell for further information or instructions. 1. INTRODUCTION The N-Frame Circuit Breaker (Figure 1-1) are 690VAC maximum rated devices, 600V for UL applications, and have integral trip units. Available current ratings are up to 1600 Amp, 1200 for UL applications. I N-Frame Circuit Breakers and molded case switches are listed in accordance with Underwriters Laboratories, Inc. Standard UL-489 and satisfy the requirements of the International Electrotechnical Commission Recommendations No. IEC 60947-2. The Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. The primary function of the Trip Unit is circuit protection. This is achieved by analyzing the secondary current 40752-195 (1) Effective 2/2011 Figure 1-1 N-Frame Circuit Breaker signal received from the circuit breaker current sensors and initiating trip signals to the circuit breaker shunt trip when pre-set current levels and time delay setting are exceeded. Low level ground fault protection with an adjustable time delay is supplied when appropriate trip types are selected. In open air at 40º C, a N-Frame Circuit Breaker with a Trip Unit will carry continuously up to 1200 amperes without exceeding a 50º C rise at the terminals. The calibration of the trip unit is insensitive to ambient temperatures over a range of -20º to +55º C. However, the trip unit contains thermal temperature protective circuitry that initiates a trip operation for self-protection if the internal ambient temperature at the printed circuit board (PCB) reaches approximately 90º C. For ambient conditions above 40º C, derating of the circuit breaker should be considered to avoid exceeding a safe terminal temperature operation range. Consult Allen-Bradley for recommendations. 1 Molded Case Switches: The Molded Case Switch (MCS) is similiar to the Circuit Breaker except that it has a differtrip at 15,000 Ampere but there is no overload short delay or ground fault trip. As a result sections 2.6, 4.5, 6.8 and 7 are not applicable. In the remaining sections the term circuit breaker shall also include the molded case switch. Overload Trip: In accordance with standards requirements, the trip unit initiates a trip of the circuit breaker within two hours of an overload of 135 percent, and a trip in less time for higher overloads. A “Thermal Memory” effect prevents the breaker from being reenergized immediately after an overload. A “cooling off” period of up to 5 minutes is required, which allows time for the cabling to cool off. Short delay/Instantaneous Trip: For short circuit conditions that exceed the short delay pick-up settings, the trip units initiate a trip after a delay prescribed by the I²t response time delay action is provided by trip unts designated LSI and LSIG unless the instantaneous (I) setting is selected. Table 1.1: Trip Unit Types Trip Unit Functions Long Time Adjustable Ampere Rating with Adjustable Long Delay Short Time Adjustable Short Time Pick-up with Short Time Delay l²t Ramp LS Digitrip RMS 310+ Trip Unit LSI LSG LSIG • • • Adjustable Short Time Delay with Adjustable short Time Pick-up Instantaneous Fixed Instantaneous (Override) • • • • • MCS • • • • • Adjustable Ground Fault Pick-up • • Adjustable Ground Fault Time •③ • Using Trip unit with adjustable delay (LSI, LSIG), instantaneous pick-up is achieved when the lowest time delay setting (l) is selected for non-IMM trip units. Override setting fixed at frame withstand rating. ③ I2t response. Ground Fault 40752-195 (1) Effective 2/2011 2 Table 1.2: Trip Unit Function and Rating Sensing Trip Function Range/Setting Description ② Ampere Rating Adjustable with IR Switch Trip Unit Ampere Rating (IR) 1250 Amp ③ 1200 Amp 800 Amp Short Delay Pick-Up (Adjustable) In Multiples of amperes (In) with marks at 2-3-4-5-6-7-8-9x Short Delay Time (Adjustable) I²t ramp configuration Short Delay Time (Adjustable) Flat response with time delay settings at Instantaneous, ① 120ms and 300ms. Trip Unit Ampere Rating Trip Unit Setting Ground Fault 1200 Amp Pick-Up 800 Amp (Adjustable) Ground Fault Time Delay Flat Response with time settings of: Inst, 120ms and 300ms Occurs with short delay time adjustment set at 1. ① ② The Molded Case Switch has a fixed instantaneous setting. ③ Not UL Listed Ground Fault Protection: when selected, ground fault pick-up and time delay settings shown in Table 1.2 allow selective ground fault coordination with other circuit protection devices. Internal Accessories: Internal accessories mount in the breaker. A list of internal accessories and their instruction DC Application: N-Frame trip units are suitable for AC application only. Auxiliary Alarm Alarm (Signal)/Lockout (ASL) Switch 40752-094 Auxiliary Switch 40752-097 Shunt Trip 40752-095 Low Energy Shunt Trip Undervoltage Release Mechanism (Handle Reset) 40752-096 Field Testing: ing of the trip unit when connected to test kit. Note: Shunt trip and undervoltage accessories, if required, must be mounted in the left pole. Ground Fault Alarm: A ground fault alarm relay may be ordered that provides a contact closure when a ground fault trip occurs. - Note: Trip unit versions with ground fault protection are supplied with an auxiliary switch, mounted in the right pole of the trip unit. 3 40752-195 (1) Effective 2/2011 This instruction leaflet gives procedures for installation and field testing of N-frame circuit breakers and describes the different trip unit characteristics. For this publication, the term circuit breaker shall also include the molded case switch. 2. INSTALLATION The installation procedure consists of inspecting the circuit breaker, installing the accessories and terminals and, if required, mounting the circuit breaker, connecting the line and load conductors and accessory wiring, and adjusting trip settings. Circuit breakers, accessories, and terminals. may be supplied in separate packages. To install the circuit breaker, perform the following steps: 2.1 Inspection Make sure the circuit breaker is suitable for the intended installation by comparing nameplate date with existing equipment ratings and system requirements. Inspect the circuit breaker for completeness and check for damage before mounting. 2.2 Accessory Installation Note: If required, internal accessory installation in any type of circuit breaker should be done before the circuit breaker is mounted and connected. Refer to the individual accessory instruction leaflets listed above. Figure 2-2 Conductor Extensions (Purchased Separately) Terminals are not included. Terminals must be purchased separately. For bus connections use: M12 - 1.75 bolts for Metric Style front mounted bus connections, socket cap screws are recommended. Torque Table (Domestic) Terminal Cat. Wire Size No. MCM 140U-N-TLA2 #1-500 (2) 140U-N-TLA3 3/0-400 (3) 140U-N-TLA4 4/0-500 (4) 140U-N-TLA3A 500-750 (3) 140U-N-TLC2 2/0-500 (2) 140U-N-TLC3 3/0-5-- (3) 140U-N-TL4 3/0-400 (4) Cond. Mat'l CU/AL CU/AL CU/AL CU/AL CU ONLY CU ONLY CU ONLY Torq. Lb.-in. 375 375 375 450 300 300 275 Figure 2-1 Terminal Installation 40752-195 (1) Effective 2/2011 4 Torq. Nm.vv 42.4 42.4 42.4 50.9 33.9 33.9 31.1 0.312-18 (M8-1.25) Tap 6-Places 3.438 (87.31) 1.718 (43.64) CL Circuit Breaker CL Breaker 0.312-18 (M8-1.25) Tap 4-Places CL Circuit Breaker Load End 8.625 (219.65) 14.750 (374.65) CL Handle 1.906 (48.41) 2.50 R (6.35 R) CL Handle .188 R (4.76 R) 5.587 (141.91) 6.125 (155.57) 1.375 (34.92) 1.500 (38.10) 2.750 (69.85) 2.750 (69.85) 2.750 (69.85) Dimensions in Inches (Millimeters) 4-POLE 2- AND 3-POLE Figure 2-5 Breaker Mounting bolt Drilling Plan 3.187 (80.95) 6.375 (161.92) FRONT COVER CUTOUT Figure 2-6 Circuit Breaker Escutcheon Dimensions 2.3 Terminal Installation 1200A Front Connect CAUTION If not already installed, mount terminals. The terminal cover screws must first be loosened and the terminal covers removed. CIRCUIT BREAKER COVER CONSTRAINTS MOVING PARTS. DO NOT OPERATE THE BREAKER WITHOUT THE COVER INSTALLED. Figure 2-9 Securement of Cable (See caution note for bracing instruction) 5 40752-195 (1) CAUTION VOLTAGE IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE MOUNTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. 2.4 Mounting To mount the circuit breaker, perform the following steps: 1200A Front Connect Circuit Breakers OVERHEATING CAN CAUSE NUISANCE TRIPPING AND DAMAGE TO THE CIRCUIT BREAKER. WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE POSSIBILITY OF TERMINAL OVERHEATING. Connect line and load conductors and accessory leads. If the circuit breaker includes ground fault protection, connect the neutral current sensor and ground fault alarm unit as . CAUTION a. For individual surface mounting, drill mounting panel using the drilling plan shown in Figure 2-5. For dead front cover applications, cut out cover to correct escutcheon dimensions, see Figure 2-6. HAZARDOUS VOLTAGE CONDITIONS CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. MAINTAIN ORIGINAL ELECTRICAL CLEARANCE AND CREEPAGE SPACINGS AT TERMINATIONS . internal accessories, make sure the accessory wiring can be reached when the circuit breaker is mounted. After the circuit breaker is installed and all connections are made, check all mounting hardware and terminal connection hardware for torque loading. Torque values for line/ load terminal lugs are given on table in Figure 2-1. Torque mounting screws to 30-35 lb-ft. (41-47 Nm). Note: Labels with accessory connection schematic diagrams are provided on the side of the circuit breaker. A note should be made of the diagrams if the labels cannot be seen when the circuit breaker is mounted. c. Position the circuit breaker on the mounting surface. d. Secure the circuit breaker with the supplied hardware 2.5 Connecting Line and Load Conductors Re-install load end and line end covers and secure with pan head screws provided. Torque large screws to 35-45 lb.-in. (4.0-5.0 Nm) and small screws to 24-30 lb-in. (2.7-3.4 Nm). When using the terminals TA700NB1 or T700NB1, or when prospective fault currents of cabled installations exceed 65kA, (such as NDC applications), the conductors are to be braced in accordance with Figure 2-9. CAUTION UNSUPPORTED CABLES CAN CAUSE MINOR PERSONAL INJURY OR EQUIPMENT DAMAGE UNDER SHORT CIRCUIT CONDITIONS. Wrap conductor cables with 3/8” nylon or equivalent rope as shown in Figure 2-9, having a minimum tensile strength of 2000 lbs., at 6” from terminals and every additional 6” with 5 wraps or every additional 1” with 1 wrap. 2.6. Adjusting Trip Settings The N-frame circuit breakers have the trip unit built in as an integral part of the breaker. The trip unit is not field replaceable. The various trip unit settings are described in section 4. They should be adjusted as required at this point. 40752-195 (1) 2/2011 6 4X Ø.344 MTG HOLES Ø.703 CBORE X .453 DP .359 DP FROM BOTTOM 11.500 OF TERMIALS 7.000 8.625 14.750 OF MTG HOLES 16.000 OVER ALL LENGTH 9.250 REMOVABLE TERMINAL COVER 2.799 3.819 HANDLE 2.490 1.375 2.750 REMOVABLE TERMINAL COVER 4.125 8.250 Figure 3-1 Circuit Breaker Manual Controls 3.2 Circuit Breaker Reset 3. OPERATION 3.1 Manual Operation Manual operation of the circuit breaker is controlled by the circuit breaker handle and the Push-to-Trip button. The circuit breaker handle has three positions, two of which are shown on the cover raised lettering to indicate ON and OFF. On the handle, ON, OFF, and TRIP are also shown by a color-coded strip for each circuit breaker handle position: red for ON, white for TRIP, and green for OFF (See Figure 3-1). The Push-to-Trip button checks the circuit breaker tripping function and may be used to periodically exercise the operating mechanism. 7 After an automatic or accessory initiated trip, or a manual Push-to-Trip operation, the circuit breaker is reset by moving the circuit breaker handle to the extreme OFF position. CAUTION LACK OF ILLUMINATION OF THE STATUS LIGHT DOES NOT INDICATE THE TERMINALS OF THE BREAKER ARE DEENERGIZED. 40752-195 (1) Effective 2/2011 4-1 . Test Port - a test port is built into each trip unit to allow use of a functional test kit. The test kit performs a test of the Long Delay, Short Delay, and Ground Fault functions. 4. TRIP UNIT ADJUSTMENTS 6646 C06 H01 STATUS G 7 H 4 3 6646 C06 H01 Push to Trip IR D E F A 3 tR (s) LONG 10 12 15 G 7 H 4 5 6 A 3 6646 C06 H01 IR D E F A 3 tR (s) LONG 10 12 15 G 7 H 4 2 I sd (xIR ) SHORT 5 6 7 8 20 4 24 3 9 2 9 5 4 tsd (ms) SHORT 120 Inst. 300 A B C D E F G H I J 7 6646 C06 H01 STATUS TEST / ALARM C B 3 IR D E F A tR (s) I sd (xIR ) LONG SHORT 5 6 7 10 12 15 G 7 8 20 4 H 4 9 24 3 2 9 2 4 40752-195 (1) Effective 2/2011 B C D E F G H I J A 4-3 . IR - Continuous Current Setting. In accordance with standards requirements, the trip unit initiates a trip of the circuit breaker within 2 hours for an overload of 135% and will trip as a function of 12 t for higher currents. Continuous Current Values for each lettered setting are indicated by the chart on the right side of the trip unit. 4-5 . Isd - Setting in multiples of IR. For short circuit conditions that exceed the short delay pick-up setting, the trip unit initiates a trip after a predetermined delay. 4-6 . The - Ig (xIn) switch is the ground fault pick-up switch and is used on the LSIG & LSG styles to set the ground fault pick-up as a percentage of I (Frame current). For example, a 1200A frame with an Ig (xIn) setting of 0.4 will provide a ground fault pick-up at 480A. 3 10 2 4-2 . Test LED - to be used with a no trip functional test. This LED is a dual function light. As previously stated, the LED is used as a no trip indicator when using the test port. In normal modes, this LED indicates a high load alarm. It will light if the continuous current is 95% of the setting and must be present for a 38 second duration. 4-4 . tR - The number of seconds required to trip @ 6x. For example, IR - 800A, - 2 sec load current - 4800A (6x). The breaker will trip in 2 seconds. NOTE: The last two time settings vary according to the frame as follows: 1200A 20,24, 1250A\800A - 14,14, 1600A - 20,20. NOTE: There is a thermal memory capacitor that will affect the LDT time. If the breaker has tripped on LD, this capacitor must be discharged or it will self discharge after five minutes. If neither one of these choices has been done, the LD trip time will be shorter. 9 STATUS C B 11 2 B C D E F G H I J 10 TEST / ALARM Push to Trip I sd (xIR ) I g (xIn) tg (ms) SHORT GND GND 120 5 6 7 .6 .8 1.0 8 .4 20 4 9 .3 Inst. 300 24 3 2 .2 9 4 2 1 tg (ms) Inst. 120 300 K J L M N O P Q R 3 TEST / ALARM 11 tsd Inst. 120 (ms) 300 8 STATUS 11 Push to Trip 6 Settings 10 C B 1 5 4 2 1 2 * 6646 C05 H04 11 A I sd (xIR ) I g (xIn) tsd / tg (ms) SHORT / GND SHORT GND 5 6 7 .6 .8 1.0 M N O 20 4 8 .4 L P 24 3 K Q 9 .3 2 .2 J 9 R 6646 C05 H07 C B IR D E F * tR (s) LONG 10 12 15 TEST / ALARM A B C D E F G H 6646 C05 H10 Push to Trip 3 8A 6646 C05 H01 10 2 1 4-7 . For the LSI style, the Short Delay time is a flat response determined by the tsd/tg switch setting of INST, 120ms or 300ms. For the LS style, the short delay time is an 12t function. 5 8 H04 A Ii(xIn) INST 7 8 10 6 12 4 2.5 Maintenance Mode * TEST / ALARM tR (s) IR D E F C B A Isd (xIR) Ig (xIn) tsd /tg (ms) Settings tg (ms) LONG SHORT GND SHORT / GND 120 300 Inst. 10 12 15 5 6 7 .6 .8 1.0 M N O J K L 20 4 G 7 8 .4 L P tsd 50ms M N O 120 24 3 H 4 K Q 9 .3 (ms) P Q R 300 2 2 .2 J 9 R * 12 6646 B C D E F G H I J STATUS 6646 Push to Trip C06 Remote MM C05 H01 13 response determined by the tsd/tg switch settings of INST, 120ms or 300ms. This switch is a dual switch that also determines the ground fault time settings of INST, 120ms or 300ms. As an example, if the tds/tg switch is set at a position J, then both short delay time ond example would be to set the tsd/tg switch The LSIG label (see balloon 8A) should be used in conjuction with the tsd/tg switch to set any one of nine possible combinations of short 14 label should be applied to the right side breaker trip unit nameplate. 4P 4d STATUS TEST / ALARM tR (s) IR D E F 4P 3dn/2 4P 3d C B LONG 10 12 15 G H A 20 4 24 3 7 4 2 * Isd (xIR) Ig (xIn) tsd /tg (ms) Settings tg (ms) SHORT GND SHORT / GND 120 300 Inst. 5 6 7 .6 .8 1.0 M N O J K L 8 .4 L P tsd Inst. M N O 120 K Q 9 .3 (ms) P Q R 300 2 .2 J 9 R * 14 B C D E F G H C05 A is set by the tg switch. For the LS style, the short time is an I2t function. 6646 6646 Push to Trip C06 H02 H01 4-9 . For the LSG style, the short delay time is 4-10 . Status LED - A green status light indicates the operational status of the trip unit. If the load current is approximately 20% of the maximum current rating (In) of the breaker, the status light will blink on and off once each second. 4-11 . Mechanical Push to Trip. 4-12 . The Maintenance Mode and adjustable INSTantaneous features are only available on LSI and LSIG styles. Please refer to the labeling to the left of the test kit connector. The Maintenance Mode consists of the two lowest settings of the INST switch: 2.5x and 4.0x. For example, a 1200A (In) NG breaker with the switch set to 2.5x would trip instantaneously when the current exceeded 3000A. 4-13 . The adjustable INSTantaneous (Ii) Mode has four settings from 6x to 9x. For example, a 800A (In) NG breaker with the (Ii) switch set to 7x would trip instantaneously with the current at or above 5600A. The last setting on the (Ii) switch can be one of three values depending on the frame current: 800A=28, 1200A=12, 1600A=9. 4-14 . On a breaker without Maintenance Mode, the lowest labeled SDT setting is labeled INSTaneous. The lowest SDT setting with Maintenance Mode is labeled as 50ms. 9 40752-195 (1) Effective 2/2011 4-15 . The Remote Maintenance Mode is enabled by applying 24VDC to the two wire cable that exists the left side of the breaker. The wires are color coded as follows: Yellow=+24V and Black=common ground. A blue colored LED on the left side of the breaker is the Maintenance Mode section of the trip unit. The lighted blue LED indicates that the lowest setting of the Maintenance Mode is enabled. This setting corresponds to 2.5x of In. Turning the adjustable switch on the trip unit has no affect on either the Maintenance Mode or the INST Mode settings while the blue LED is lit. In addition to the blue colored LED, a relay contact (C, NO) is available. The wires for this contact exit the left hand side of the breaker and are color coded as follows: Blue=C, and Red=NO. NO NC - 4-16 . The High Load Alarm Relay option will provide a SPST contact closure when the trip unit current equals or is greater than 95% of In for a period of 38 seconds. If the current drops below the 95% value, the contact will open. The yellow and green wires that exit the right side of the breaker are the common (C) and nor mally (NO) of this relay. + 4-17 . The Ground Fault Relay option will provide a SPST contact closure immediately before the breaker will trip on a ground fault over current detect. This closure is momentary (50ms) and the customer must provide the necessary external circuitry in order to latch this signal. The yellow and green wires that exit the right side of the breaker are the common (C) and normally (NO) of this relay. NOTE: Either the high Load Alarm Relay or the Ground Fault Alarm Relay option can be selected but not both. The High Load Alarm Relay can only be selected with LS and LSI trip unit styles. If the trip unit is a Ground Fault style, the Alarm A Relay, by default, will be selected. NOTE: The contact rating of the relay is: 2A, 30 VDC resistive load. The coil resistance is approximately 1600 ohms. (Max switching voltage: 220 VDC, Max switching current: 2A). The coil resistance is about 1600 ohms. 40752-195 (1) Effective 2/2011 LEFT SIDE OF BREAKER BLACK YELLOW - + 24 VOLT DC BLUE RED 10 Polarity Markings .59 (14.98) 2.75 (69.85) 1.062 (26.97) M12-1.75 Tapped Holes 4-Places 4.375 (111.13) 2.188 (55.58) 3.12 (79.25) 1.69 (42.93) .50 (12.7) 5.80 (147.32) 2.75 (69.85) Figure 5-1 Neutral Sensor Outline White Grey Figure 5-2 Connection Diagrams Ground Fault Breaker - Figure indicates normal feed installation. Neutral sensor is wired identically for reverse feed applications. 11 40752-195 (1) Effective 2/2011 5. Ground Fault Ground fault circuit breakers detect ground fault currents through residual sensing (they are not designed to use source ground or zero sequence ground fault sensing methods). If the system neutral is grounded, but no phase to neutral loads are used, the neutral current sensor is not necessary. If the system neutral is grounded and phase or neutral loads are used, then the neutral current sensor (see Figure 5-1) must be used. It should be connected to the breaker according to Figure 5-2. The neutral sensor has the same ratio as the breaker current sensors. Note: The polarity of the sensor connections is critical. Always observe the polarity markings on the installation drawings. To insure correct ground fault equipNational Electric Code requirements under article 23095(C). See section 7 for testing instructions. 6. INSPECTION AND FIELD TESTING Inspection Circuit breaker should be inspected periodically. This inspection can be best done during normal equipment maintenance periods when no voltage to the equipment is available. The inspection should include the following checks 6-1 through 6-8. 6.1 Remove dust, dirt, soil, grease, or moisture from the surface of the circuit breaker using a lint-free dry cloth, brush, or vacuum cleaner. Do not blow debris into the circuit breaker. If contamination is found, look for the source and eliminate the problem. 6.2 Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind. If mechanical linkages are not free, replace circuit breaker. 6.3 With the circuit breaker in the ON position, press the PUSH-TO-TRIP button to mechanically trip the circuit breaker. Trip, reset, and switch circuit breaker ON several times. If mechanism does not reset each time the circuit breaker is tripped, replace the circuit breaker. 6.4 Check base, cover, and operation handle for cracks, chipping, and discoloration. Circuit breakers should be replaced if cracks or severe discoloration is found. 6.5 Check terminals and connectors for looseness or signs of overheating. Overheating will show as discoloration, melting, or blistering of conductor insulation, or as pitting or melting of conductor surface due to arcing. If there is no evidence of overheating or looseness, do not disturb or tighten the connections. If there is evidence of overheating, terminatons should be cleaned or replaced. Before re-energizing the circuit breaker, all terminations and cable should be refurbished to the same condition as when originally installed. 6.6 Check circuit breaker mounting hardware, and tighten if necessary. 6.7 Check area where circuit breaker is installed for any VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM. MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION AND THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. Exposure to certain types of chemicals can cause deterioration of electrical connections. 7. PERFORMANCE TESTING FOR GROUND FAULT CIRCUIT BREAKERS 7.1 Code Requirements The National Electric Code under Article 230-95-C requires that any ground-fault protection system be SOME COMMERCIAL CLEANING AGENTS WILL DAMAGE THE NAMEPLATES OR MOLDED PARTS. MAKE SURE THAT CLEANING AGENTS OR SOLVENTS USED TO CLEAN THE CIRCUIT BREAKER ARE SUITABLE FOR THE JOB. 40752-195 (1) Effective 2/2011 12 The test shall be conducted in accordance with approved instructions provided with the equipment. A written record of this test shall be made and shall be available to the authority having inspection jurisdiction. Figure 7-1a. This should cause the breaker to trip in less than 1 second, and if an alarm indicatior is supplied, it should operate. Reset the breaker and the alarm indicator. Repeat the test on the other two phases. 7.3.5 If the system is a 4-wire system with a neutral current sensor, apply the same current as described in paragraph 7.3.4 above through one phase of the breaker, returning As a follow-up to the basic performance requirements stipulated by the N.E.C. as stated above in 7.1, UL Standard through the neutral sensor, as shown in Figure 7-1b. The breaker should not trip and the alarm indicator, if supNo. 1053 requires that certain minimum instructions must plied, should not operate. Repeat the test on the other two accompany each ground fault protection system. These phases. following statements plus a copy of the test record form are shipped with each N-Frame ground fault circuit breaker. 7.3.6 If the system is a 3-wire system with no neutral current sensor, apply the same current as described in para7.3 General Test Instructions graph 7.3.4 above through any two phases of the breaker, with the connections exactly shown in Figure 7-1c. the 7.3.1 The interconnected system shall be evaluated in acbreaker should not trip, and the alarm indicator, if supplied, cordance with the equipment assembler’s detail instruction should not operate. 7.2 UL Standards Requirements 7.3.2 The polarity of the neutral sensor connection (if used) must agree with equipment assembler’s detailed instructions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler. Repeat the test using the other two combinations of breaker phases. 7.3.3 The grounding points of the system shall be veri- FIELD TESTING SHOULD BE USED FOR FUNCTIONAL TESTING AND NOT FIELD CALIBRATION. bypass the sensors. High-Voltage testers and resistance bridges may be used. THERE IS A HAZARD OF ELECTRICAL SHOCK OR BURN WHENEVER WORKING IN OR AROUND ELECTRICAL EQUIPMENT. ALWAYS TURN OFF POWER SUPPLYING BREAKER BEFORE CONDUCTING TESTS. CAUTION ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE. 7.3.7 The results of the test are to be recorded on the test form provided with the equipment. Note: Since the ground fault circuit breakers derive their operating power from the phase current, and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature. 7.3.4 Using a low voltage (0-24V), high current, AC source, apply a test current of 125% of the ground fault pick-up setting through one phase of the circuit breaker, as shown in 13 40752-195 (1) Effective 2/2011 Low Voltage Source Source L Low Voltage Source Source C Load R N Current Limiting Resistor (if required) Figure 7-1a Connections for Ground Fault Trip Test 40752-195 (1) Effective 2/2011 L Low Voltage Source Source C Load R N L C R Current Limiting Resistor (if required) Current Limiting Resistor (if required) Figure 7-1b Connections for Ground Fault No-Trip Test with a Four Wire System Figure 7-1c Connections for Ground Fault No-Trip Test with a Three Wire System 14 NOTES 15 40752-195 (1) Effective 2/2011 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information recommendations, descriptions and safety notations in this document are based on Rockwell Automation's experience and judgement and may not cover all contingencies. should be consulted. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MECHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF ROCKWELL. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. PRINTED IN USA 40752-195 (1) Effective 2/2011 16 ">

Download
Advertisement
Key features
- Integral trip units
- Up to 1600 Amps rating
- UL-listed
- IEC compliant
- Overload, short circuit, and ground fault protection
- Microprocessor-based technology
- Adjustable pick-up and time delay settings
- Internal accessories
- Field-testable