- Home
- Domestic appliances
- Climate control
- Bryant
- HRVBBLVU High Efficiency
- Instruction manual
- 24 Pages
Bryant HRVBBLHU Conventional, HRVBBSVU Compact, HRVBBLVU High Efficiency Heat Recovery Ventilator Instruction manual
The HRVBBLHU, HRVBBSVU, and HRVBBLVU are heat recovery ventilators used to exchange indoor stale air with outside fresh air. The units are equipped with a special heat recovery core which transfers sensible heat between the fresh incoming air and stale exhaust air. To ensure comfort, these models can be applied as independent or standalone units. The HRV should be located in a conditioned space and in close proximity to a fused power source. It should be easily accessible for routine maintenance.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
installation, start-up, and operating instructions
HEAT RECOVERY
VENTILATOR
Cancels: New
NOTE: Read the entire instruction manual before starting the installation.
Index Page
SAFETY CONSIDERATIONS .....................................................2
INTRODUCTION ..........................................................................2
LOCATION....................................................................................2
Inspect Equipment ....................................................................2
Select Location..........................................................................2
UNIT INSTALLATION .............................................................2-3
Mount Unit................................................................................2
Independent System Application..............................................2
Forced-Air Application.............................................................3
Connect Ducts to HRV.............................................................3
Condensate Drain......................................................................3
Locate and Install Exterior Hoods ........................................3-4
COMPONENT DESCRIPTION ....................................................5
WALL CONTROL .....................................................................4-6
Location .................................................................................6-7
Basic Control Operation ...........................................................6
Standard Control Operation......................................................6
Automatic Control Operation ...................................................6
Wiring........................................................................................7
Humidity Selector .....................................................................7
ELECTRICAL CONNECTIONS...............................................7-8
115-vac Wiring .........................................................................7
12-vdc Wiring ...........................................................................8
ACCESSORIES ..........................................................................8-9
Interlock Relay..........................................................................8
20 Minute Timer.......................................................................8
60 Minute Adjustable Timer ....................................................8
BALANCING HRV................................................................10-11
Balancing Dampers.................................................................10
Flow Collars ......................................................................10-11
VENTILATION EVALUATION...........................................12-13
Method 1 .................................................................................13
Method 2 .................................................................................13
CONTROL BOARD OPERATION ............................................13
Board Function........................................................................13
Defrost.....................................................................................13
Off and Intermittent/Off Mode...............................................13
High-Speed Air Exchange ......................................................13
Low-Speed Air Exchange.......................................................13
CARE AND MAINTENANCE..............................................13-14
Door.........................................................................................13
Filter ........................................................................................14
Blower Motor and Wheel .......................................................14
Cleaning the Core ...................................................................14
TROUBLESHOOTING ..........................................................14-17
Wall Control............................................................................14
Control Board..........................................................................14
Blower Motor..........................................................................14
Blower Speed Selection..........................................................14
Defrost................................................................................14-16
Control Module Jumpers ........................................................16
Error Signaling ..................................................................16-17
WIRING DIAGRAMS ...........................................................18-19
DIMENSIONAL DRAWINGS ..............................................20-22
—1—
HRVBBLHU,
HRVBBSVU,
HRVBBLVU
Fig. 2—HRVBBSVU Compact Unit
II HRV-71-2
5-00
Fig. 1—HRVBBLHU Conventional Unit
A99271
A92268
Fig. 3—HRVBBLVU High Efficiency Unit
A92377
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
INTRODUCTION
The Heat Recovery Ventilator (HRV) is used to exchange indoor stale air with outside fresh air. The HRV unit is equipped with a special heat recovery core which transfers sensible heat between the fresh incoming air and stale exhaust air.
It is recommended, but not required to locate the HRV in a conditioned space. Special attention should be given to condensate drain, duct application, balancing HRV, and locating unit for easy access and routine maintenance.
The cross-flow design core allows entering and leaving air streams to transfer heat energy without mixing. (See Fig. 15, and 18 through 25.)
LOCATION
I.
INSPECT EQUIPMENT
Move carton to final installation location. Remove HRV from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete. Check to make sure HRV unit matches Fig. 1 through 3 and
7 through 9.
II.
SELECT LOCATION
The HRV should be located in a conditioned space and in close proximity to a fused power source. It should be easily accessible for routine maintenance.
If HRV is installed independent of a forced-air system, unit should be located near the center of the air distribution system. If HRV is installed in conjunction with a forced-air system, unit should be located next to (or close to) the indoor equipment.
I.
UNIT INSTALLATION
CAUTION: Do not install HRV in a corrosive or contaminated atmosphere.
MOUNT UNIT
The HRV can be suspended from floor joists using chains and 4 springs. Attach metal hanging bracket to all 4 sides of cabinet. (See
Fig. 4.) Unit should always be installed as level as possible.
A92269
Fig. 4—Chain Spring Installation
II.
INDEPENDENT SYSTEM APPLICATION
In the absence of a forced-air system and a typical duct system layout, the HRV can be applied as an independent or stand alone unit. To ensure comfort, this type of application involves running both fresh-air, and return-air registers (or stale-air pickup registers) throughout the home.
CAUTION: Do not install return-air registers (or staleair pickup registers) in same room as gas furnace or water heater.
Fresh-air registers are normally located in bedrooms, dining room, living room, and basement. It is recommended that registers be placed 6 to 12 in. from the ceiling on an interior wall and airflow directed toward ceiling. If registers are floor installed, airflow should be directed toward the wall.
Return-air (or stale-air pickup registers) are normally located to draw from kitchen, bathroom, basement, or other rooms where stale-air can exist.
Proper size and type of registers must be used to minimize pressure drop. The velocity of airflow through register should not be above
400 ft/minute.
Maximum length of duct for the system should be designed according to the highest speed of the unit. Refer to specifications listed in unit Product Data Digest for ventilation capacities.
—2—
III.
FORCED-AIR APPLICATION
Most HRV applications will be installed in conjunction with new or existing forced-air system. To operate properly, the fresh-air supply and stale-air return from HRV connect directly to return-air duct system. This is how the HRV distributes fresh air and removes stale air from inside of building. (See Fig. 7.) For these installations, furnace or fan coil blower must be interlocked and operate continuously whenever HRV is energized.
Interlock relay kit Part No. KVAAC0101FIR is available and designed to interlock HRV with indoor equipment blower. When
HRV is energized, R and G circuit inside of furnace or fan coil will energize. See Fig. 13 and interlock relay kit for additional information and Installation Instructions.
NOTE: The fresh air from HRV is introduced into return-air duct at a point no less than 6 ft upstream of furnace or fan coil. This connection should be direct. (See Fig. 7.) This is to allow incoming fresh-air to mix before entering indoor equipment.
IV.
CONNECT DUCTS TO HRV
CAUTION: If HRV duct work is installed in an unconditioned space, insulated flexible duct is required.
Insulated flexible duct is required on both fresh-air inlet and
exhaust-air outlet ducts connecting to exterior wall. When using insulated flexible duct, the vapor barrier of the flexible ducts must be taped very tight to prevent condensation problems. To reduce pressure drop, stretch the flex duct and support it in a proper manner to avoid reduced airflow.
When connecting the HRV to a return-air duct system, insulated flexible duct can be used. However, when metal or rigid ducts are applied use approximately 18-in. of flexible duct at HRV ports for fresh-air supply, and stale-air return. When using metal duct from fresh-air supply to system duct work, the metal duct should be insulated. (See Fig. 5.) This can act as a silencer when connecting ducts to return-air duct system. This should eliminate transmission of noise or vibration from unit to main duct system.
NOTE: Balancing dampers should be installed in stale air exhaust and fresh air intake ducts before connecting to the HRVBBSVU and the HRVBBLVU units. The balancing dampers are provided in the HRVBBLHU units (see balancing HRV section).
V.
CONDENSATE DRAIN
To connect condensate drain, proceed as follows:
1. Insert sleeved grommets into bottom of unit using the gasket washer and nut. (see Fig. 6).
2. Cut two sections of plastic tubing, about 12" long and attach them to each drain.
3. Join the two short sections of plastic tubing to the "T" connector and the main tube as shown.
4. Make a loop in the tubing below the "T" connector to create a trap to prevent sewer gases from entering the ventilation system. (See Fig. 6.)
5. Connect unit drain to building’s main drain. Provide slight slope from unit for run-off.
VI.
LOCATE AND INSTALL EXTERIOR HOODS
IMPORTANT: To prevent condensation problems, insulated flexible ducts are required on both fresh-air inlet and exhaust-air outlet ducts connecting between HRV and exterior wall.
Fresh-air intake and stale-air exhaust must be separated by at least
6 ft. Fresh-air intake must be positioned at least 10 ft from nearest dryer vent, furnace exhaust, driveway, gas meter, or oil fill pipe.
Fresh-air intake must be positioned as far as possible from garbage containers and potential chemical fumes. When possible, it is advised to locate the intake and exhaust hoods on same side of house or building. The intake and exhaust hoods should never be located on interior corners or in dead air pockets. (See Fig. 7.) Both intake and exhaust hoods must be 18 in. from ground and at least
12 in. above anticipated snow level.
After selecting proper hood locations make appropriate size hole through exterior wall, pass flexible duct through hole and insert hood tube into duct. Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely.
FLEXIBLE
DUCT
FRESH-AIR
SUPPLY
STALE-AIR
RETURN
DUCTS CONNECTING TO
RETURN-AIR DUCT SYSTEM
Fig. 5—Flexible Duct Fit-Up
A98382
Fig. 6—Condensate Drain With Loop Trap
A99268
—3—
8
6 FEET
18 IN.
FURNACE 6 IN.
6 IN.
HRV
INSULATED DUCT CONNECTING
FRESH AIR & EXHAUST TO
OUTSIDE
NOTE: SUPPLY & EXHAUST DUCTS TO HAVE
BALANCING DAMPERS (ON COLD SIDES)
(SEE STEP 4-CONNECT DUCTS TO HRV)
REAR
INLET HOOD
6 FEET
NOTE: ALL DUCT WORK TO BE FIELD SUPPLIED.
EXHAUST HOOD
18 IN.
Fig. 7—Exhaust Ventilation
A99265
—4—
6
3
6 4
2
4
5
6
3
2
1
14
12
11
13
1
10
8
4
9
7
A99283
Fig. 8—HRVBBLHU Conventional Horizontal Unit
7 8 9 10
A98408
Fig. 9—HRVBBSVU Compact Unit
COMPONENT DESCRIPTION
The following listed items are components of HRVBBLHU. (See
Fig. 8)
1. Stale air return from building connected to return-air duct system.
2. Fresh air intake connected to outdoor air inlet hood.
3. Exhaust air connected to outdoor air exhaust hood.
4. Mechanical filters trap dust contained in the air.
5. Heat recovery core is either a cross-flow type for compact models, or a counter-flow type for high efficiency models.
The core transfers heat between the 2 air streams.
6. Blowers bring in fresh air from outside and exhaust stale air to outside.
7. Electronic control circuit ensures proper unit operation.
8. Fresh air supply from HRV connected to return air duct of forced air system.
9. Terminal connector block for wiring wall and timer controls.
10. Electrical cord connects to standard 115-v outlet.
12 1
14
3
6
7
9
10
A98409
Fig. 10—HRVBBLVU Compact
High-Efficiency Unit
The following listed items are components of HRVBBSVU and HRVBBLVU. (See Fig. 9 and 10)
1. Stale air return from building connected to return-air duct system.
2. Fresh air intake connected to outdoor air inlet hood.
3. Exhaust air connected to outdoor air exhaust hood.
4. Dampers are used to control air exchange with outdoor air during defrost mode.
5. Mechanical filters trap dust contained in the air.
6. Heat recovery core is either a cross-flow type for compact models, or a counter-flow type for high efficiency models.
The core transfers heat between the 2 air streams.
7. Blowers bring in fresh air from outside and exhaust stale air to outside.
8. Capacitor required for motor operation.
9. Condensation tray collects condensate from heat recovery core.
10. Drainage tubes connects to sleeved grommets
11. Electronic control circuit ensures proper unit operation.
12. Fresh air supply from HRV connected to return air duct of forced air system.
13. Terminal connector block for wiring wall and timer controls.
14. Electrical cord connects to standard 115-v outlet.
8
11
13
2
4
5
—5—
WALL CONTROL
I.
LOCATION
The HRV wall controls are unique to HRV and must be installed for proper unit operation.
Three wall control options are available:
1. Basic Control
2. Standard Control
3. Automatic Control
II.
BASIC CONTROL OPERATION
The basic control contains a 3 position slide switch which is used to manually select OFF, LOW, and HIGH speed blower operation.
The unit operates continuously when LOW or HIGH is selected.
(See Table 1.)
III.
STANDARD CONTROL OPERATION
The standard control contains an adjustable dehumidistat, and a 3 position slide switch which is used to manually select between
OFF, LOW, and INTERMITTENT modes. There are 2 LEDs on the control to indicate operating mode. (See Table 2.) This control offers 2 modes of operation:
1. With switch off, HRV is inoperative and both LEDs are out.
(See Fig. 14.)
2. With switch on LOW, HRV continuously exchanges air with outside. If dehumidistat is satisfied, blower will run in low speed, otherwise, blower will run on high speed. Both
LEDs are illuminated all the time.
3. With switch on INTERMITTENT, the HRV exchanges air with outside on high-speed blower, and unit shuts down when dehumidistat is satisfied. The ON LED is illuminated all the time, and AIR EXCHANGE LED is illuminated only when unit is running. This mode is ideal for maintaining proper humidity levels when no one is home.
IV.
AUTOMATIC CONTROL OPERATION
This control contains an adjustable dehumidistat and push button switch to cycle between 3 modes of operation. There are 5 LEDs to indicate mode of operation. (See Table 3.)
NOTE: This control is designed to be used primarily with installations which are independent of a forced air system (models
HRVBBSVU and HRVBBLVU only).
1. Initially the switch is off. All LEDs are off and HRV is inoperative.
2. First push of mode button puts HRV into intermittent mode.
The HRV operates at high speed when there is a call for dehumidification. Intermittent and exchange LEDs are illuminated. When dehumidistat is satisfied, HRV shuts down and exchange LED goes out.
3. Next push of mode button puts system in continuous mode.
Continuous and exchange LEDs remain on. The HRV operates at high-speed blower during calls for dehumidification and low speed when dehumidistat is satisfied.
4. Next push of mode button puts system in circulation mode.
HRV operates in high speed at all times. Circulation LED remains on. When there is a call for dehumidification, exchange LED is on and HRV exchanges air with outside.
When dehumidistat is satisfied, HRV dampers close which recirculates indoor air. The exchange LED goes off.
5. The maintenance light illuminates every 3 months to indicate filter should be cleaned. It is reset by opening the door to the HRV.
NOTE: The standard and automatic controls sense humidity not temperature. Either control must be located in an area where it will continually monitor fresh air circulating within the home. Install
HRV wall control as close as possible to main system thermostat and follow same guidelines as installing a thermostat, (locate approximately 5 ft. [60 in.] above floor, mount on an inside partitioning wall, etc).
—6—
MODE
Off
Low
High
OPERATION
Off
Air Exchange
With Outside
Air Exchange
With Outside
TABLE 1—BASIC CONTROL
DAMPER POSITION
Closed To Outside
Open To Outside
Open To Outside
FAN SPEED
Off
Low
High
MODE
Off
Low
Intermittent
DEHUMIDISTAT POSITION
Any
Satisfied
Call for dehumidification
Satisfied
Call for dehumidification
TABLE 2—STANDARD CONTROL
OPERATION
Off
Off
Air exchange with outside
Air exchange with outside
Air Exchange with Outside
DAMPER POSITION FAN SPEED
Closed to outside
Open to outside
Open to outside
Closed to outside
Open to outside
Off
Low
High
Off
High
ON
LED
Off
On
On
On
On
AIR EXCHANGE
LED
Off
Off
On
Off
On
TABLE 3—AUTOMATIC CONTROL
MODE
Off
Intermittent
Continuous
Recirculation
Any
DEHUMIDISTAT POSITION
Any
Satisfied
Call for dehumidification
Satisfied
Call for dehumidification
Satisfied
Call for dehumidification
Any
OPERATION
Off
Air exchange with outside
Air exchange with outside
Air exchange with outside
Air exchange with outside
Recirculation
Air exchange with outside
Any
DAMPER POSITION FAN SPEED
Closed to outside
Open to outside
Open to outside
Open to outside
Open to outside
Closed to outside
Open to outside
Off
Off
High
Low
High
High
High
Any
INDICATOR
LEDS
OFF
Intermittent ON
Intermittent and Exchange ON
Continuous and Exchange ON
Continuous and Exchange ON
Recirculation ON
Recirculation and Exchange ON
Maintenance (open door)
TABLE 4—RECOMMENDED HUMIDITY LEVELS
50° F
32° F
14° F
-4° F
-22° F
OUTSIDE TEMPERATURE
10° C
0° C
-10° C
-20° C
-30° C
DOUBLE-PANE
WINDOWS
55 percent
45 percent
35 percent
30 percent
25 percent
TRIPLE-PANE
WINDOWS
65 percent
55 percent
45 percent
45 percent
35 percent
If the level of humidity falls too low in the winter months while operating in the continuous exchange mode, a humidifier may be integrated into the system. Intermittent exchange mode may also be selected for short periods of time to increase the level of humidity.
V.
WIRING
Remove top cover assembly from wall control and pass thermostat wire through hole located on back of control before attaching to wall. Connect Y, R, G, and B (yellow, red, green and black) between wall control and HRV circuit board. Following color code. (See Fig. 11 and 12.) Replace top cover assembly.
NOTE: HRV wall control and circuit board operate on 12vdc.
VI.
HUMIDITY SELECTOR
The humidity selector is a built-in dehumidistat designed to properly control the level of humidity in the house during the winter months. This control helps avoid condensation problems in upper northern regions where indoor humidity is a problem during the winter season.
NOTE: This control is not to be confused with a dehumidistat used during the summer months to control high relative indoor humidity.
Table 4 recommends humidity levels to avoid condensation.
Y R G B
YELLOW
RED
GREEN
BLACK
ELECTRICAL CONNECTIONS
I.
115-VAC WIRING
The HRV operates on 115vac. It comes with a power cord attached to unit and ready to plug into a fused outlet. Unit must be grounded for proper operation.
All electrical connections must comply with National and Local
Electrical Codes, or other ordinances that might apply.
Fig. 11—Typical Wall Control
A98383
—7—
WALL CONTROL
MODE
AIR EXCHANGE
´
70
60
MAINTENANCE
50
% HUM. RELATIVE HUM.
40
30
55%
45%
35%
30%
EXT. TEMP. EXT.
10
°
C/50
°
F
0
°
C/32
°
F
–10
°
C/14
°
F
–20
°
C/–4
°
F
25
20
80
BLACK
GREEN
RED
YELLOW
CONTROL
CONNECTOR
A98410
CAUTION: Do not use an extension cord as a power source for operating the HRV.
II.
12-VDC WIRING
The HRV circuit board, wall control, and accessories operate on
12vdc. See Wall Control section, item Wiring and Fig. 11 and 12 for more information.
ACCESSORIES
I.
INTERLOCK RELAY
The interlock relay kit, Part No. KVAAC0101FIR is required when installing HRV into a forced-air heating and cooling system.
(See Fig. 13.) For additional information, refer to Installation
Instructions supplied with interlock relay kit.
The purpose of interlock relay kit is to energize indoor system equipment (furnace or fan coil) blower whenever HRV is calling.
If HRV is energized, and indoor system equipment is not, interlock relay will energize and make R and G at indoor equipment. This will insure fresh air distribution throughout the building via the central duct system.
Fig. 12—Control Connections
II.
20 MINUTE TIMER
A push button timer can be used to override the wall control and put the HRV into high speed for 20 minutes. Connect switches in parallel and connect leads to HRV terminals I, OC, and OL. (See
Fig. 14.) Push button locations are ideal in special activity areas, such as, bathrooms or kitchen, where high-speed exhaust operation is needed for a short period of time.
NOTE: The 20 minute timer will not function properly unless
HRV wall control is applied and working correctly. Timing function is internal to electronic circuit board, it is activated by a momentary contact between OC and OL. The I connection is to illuminate the push button. The maximum number of push button timers that can be applied is 5.
III.
60 MINUTE ADJUSTABLE TIMER
A 60 minute adjustable timer can also be used to override wall control and put HRV into high-speed operation for a select amount of time. Connect timer in parallel with push button timers, or to
HRV terminals OC and OL. (See Fig. 14.)
The 60 minute timer will provide a minimum of 30 minutes, and a maximum of 80 minutes of ventilation at high speed. When adjustable timer expires, an additional 20 minutes will remain as a result of the internal timer of HRV electronic circuit board.
—8—
W
THERMOSTAT
TERMINALS
R G Y
9-PIN AMP PLUG
3
6
9
2
5
8
1
4
7
BLK
WHT
BLK
WHT
FOUR WIRE
TWO-WIRE
HEATING ONLY
GND
115V FIELD-
SUPPLIED
FUSED
DISCONNECT
FURNACE
AUXILIARY
J-BOX
GND
NOTE: Connect Y-terminal as
shown for proper operation.
W
R
2
HN61KK041 HONEYWELL
PILOT DUTY RELAY 125V
3
120V FROM
HRV
1
G
C
Y
FURNACE
24V
TERMINAL BLOCK
TWO
WIRE
Fig. 13—Interlock Relay Wiring Layout
CONDENSING
UNIT
A92460
J3
ELECTRONIC CONTROL
BOARD
9
8
7
OL
OC
I
6
5
4
3
THE WIRES FROM THE SWITCH
YELLOW – INDICATOR, (J3-3)
BLACK – COMMON, (J3-4)
RED – SWITCH, (J3-5)
RED
BLACK
YELLOW
J1
1
2
3
4
5
6
7
8
9
(OPTIONAL)
60 MINUTE TIMER (OPTIONAL)
PUSH BUTTON SWITCHES
(5 SWITCHES MAXIMUM)
(OC)
BLACK – (J3-4)
COMMON
TERMINAL
STRIP
(I)
YELLOW – (J3-3)
INDICATOR
TERMINAL STRIP
RED – (J3-5)
SWITCH
TERMINAL STRIP
(OL)
BACK OF PUSH BUTTON SWITCH
Fig. 14—Push Button Timer Wiring Layout
—9—
A98386
TEMPORARY
FLOW COLLAR
BALANCING
DAMPER
STALE AIR
TO OUTSIDE
FRESH AIR SUPPLY
TO BUILDING
BALANCING
DAMPER
FRESH AIR
FROM OUTSIDE
STALE AIR RETURN
FROM BUILDING
FLOW
COLLAR
Fig. 15—Balancing HRVBBLHU
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
12
″
(300mm)
12
″
(300mm)
30
″
(760mm)
BALANCING
DAMPER
12
″
(300mm)
BALANCING
DAMPER
12
″
(300mm)
FRONT
TEMPORARY
FLOW COLLAR
TEMPORARY
FLOW COLLAR
FRONT
STALE AIR
TO OUTSIDE
12
″
(300mm)
BALANCING
DAMPER
TEMPORARY
FLOW COLLAR
A99266
RIGHT SIDE VIEW RIGHT SIDE VIEW
A98425
Fig. 16—Balancing HRVBBSVU and HRVBBLVU
BALANCING HRV
Balancing intake and exhaust airflow is very important for proper system operation and optimum performance when applying an
HRV. Unit balancing prevents a positive and/or negative pressure within the home. Balancing the HRV is done by applying temporary flow collars and permanent balancing dampers to the fresh air intake and stale air exhaust ducts. (See Fig. 15 and 16.)
Airflow is determined by connecting a magnehelic gage to the temporary flow collar. (See Fig. 17.) Both flow collars and magnehelic gage are included in the accessory start-up balancing kit.
If supply-air from outside is greater than exhaust-air from the house, an imbalance can result over pressurizing the home. If exhaust-air is greater than supply-air, combustion appliances may backdraft, bringing exhaust fumes into the house. A balanced condition will ensure optimum performance, provide satisfied customers, and avoid expensive callbacks.
Before proceeding with balancing, all windows, doors, and fireplace flues should be tightly closed. No exhaust systems such as range top exhausts, dryer exhaust, fume hoods, bath or roof fans should be in operation. The forced-air furnace (if used for circulation) should be operating in continuous fan mode for normal operating speed.
I.
BALANCING DAMPERS
Balancing dampers (some times called butterfly dampers) are provided with the HRVBBLHU. The dampers for the HRVBB-
SVU and HRVBBLVU are field supplied and should be permanently located in fresh-air intake and stale-air exhaust ducts between HRV and exterior wall. (See Fig. 15 and 16) Some field modification may be required to ensure proper installation of balancing dampers while located in flexible duct. Insulating over these dampers is strongly recommended after balancing is complete to prevent condensation problems.
II.
FLOW COLLAR
Flow Collars are temporary, and should be installed as close to
HRV as possible and in straightest sections of duct to ensure accuracy. (See Fig. 15.) If only 1 flow collar is available, install collar in stale-air duct of HRV, and record airflow. Next, install
—10—
collar in the fresh-air duct and record airflow. If 2 flow collars are available, it will be much easier to read airflow and properly adjust dampers to balance unit.
With speed control at maximum speed (high-speed operation) and continuous air exchange occurring with outside, connect hoses from flow collar to a magnehelic gage. (See Fig. 17.) The gage must be leveled and zeroed before use to read accurately. If needle falls below zero, reverse hose connections.
Measure exhaust air first, it is typically the lowest pressure due to nature of system and ductwork. Next, measure fresh air. If fresh air reading is higher than exhaust reading, adjust damper until reading is same. If reading is lower, return to exhaust damper and adjust to obtain same reading. You can use label on flow collar to convert static pressure into airflow.
Once HRV is balanced and dampers are adjusted to equalize airflow, use tape or drive screws to prevent damper blades from moving. Remove flow collars and secure ducts. This procedure should be repeated to ensure unit is balanced properly.
MAX
MAX
MIN
AIRFLOW
DIRECTION
FLOW
COLLAR
MIN
CONVERSION
CHART
ZEROING SCREW
A98400
Fig. 17—Magnehelic Gage
NOTE: The flow collar directional arrow (on flow collar) must be oriented in the airflow direction of unit.
NOTE: Some field modification may be required to ensure proper temporary installation of flow collar during balancing when insulated flexible duct is used.
STALE AIR
TO OUTSIDE
6
°
C
43
°
F
FRESH AIR
FROM OUTSIDE
0
°
C
32
°
F
STALE AIR
TO OUTSIDE
2
36
°
°
C
F
FRESH AIR
FROM OUTSIDE
0
°
32
C
F
STALE AIR
FROM BUILDING
22
72
°
C
F
FRESH AIR
TO BUILDING
16
°
C
61
°
F
STALE AIR
FROM BUILDING
22
°
C
72
°
F
A98403
Fig. 18—HRVBBLHU and HRVBBSVU
Cross Flow
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
FRESH AIR
TO BUILDING
20
68
°
°
C
F
Fig. 19—HRVBBLVU Counterflow
A98404
FRESH AIR
TO BUILDING
STALE AIR
FROM BUILDING
A99269
Fig. 20—HRVBBLHU Airflow During
Air Exchange
—11—
FILTERED AIR
TO BUILDING
Fig. 21 —HRVBBLHU Airflow
During Defrost
STALE AIR
FROM BUILDING
A99270
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO BUILDING
STALE AIR
FROM BUILDING
FILTERED AIR
TO BUILDING
STALE AIR
FROM BUILDING
Fig. 22—HRVBBSVU Airflow During
Air Exchange
FRESH AIR
TO BUILDING
STALE AIR
FROM BUILDING
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
A92382
A92383
Fig. 23—HRVBBSVU Airflow During
Recirculation and Defrost
FILTERED AIR
TO BUILDING
STALE AIR
FROM BUILDING
A92384
Fig. 24—HRVBBLVU Airflow During
Air Exchange
VENTILATION EVALUATION
CAUTION: DO NOT use HRV during construction of a house or when sanding drywall. This type of dust may damage system.
When ventilation requirement is determined, use Product Data
Sheets to reference unit airflow delivery and performance.
—12—
A92385
Fig. 25—HRVBBLVU Airflow During
Recirculation and Defrost
The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required. These methods are derived from the Canadian National Building Code
1995 version and the CSA F326.1 revision.
The following 2 methods can be used to evaluate the approximate ventilation needs of a house. Accuracy of calculations are dependent upon the information available and knowing critical measurements of the structure. (See Fig. 26.)
MASTER
BEDROOM
WASH-
ROOM
#1
WASH-
ROOM
#2
BEDROOM
#3
BEDROOM
#4
BEDROOM
#5
1320 sq ft (125 sq m)
LIVING ROOM
#6
WASH-
ROOM
#7
LAUNDARY
ROOM
#8
KITCHEN
#9
FAMILY ROOM
#10
DINING ROOM
#11
1320 sq ft (125 sq m)
BASEMENT
1320 sq ft (125 sq m)
A98388
Fig. 26—Floor Plan Example
METHOD 1
To calculate approximate ventilation:
The sum of rooms X 10 CFM per room, plus 20 CFM for a master bedroom or basement.
Example: 11 rooms X 10 CFM + 2 X 20 CFM = 150 CFM.
NOTE: The master bedroom and basement are not included in first part of this equation, but figured in at second part of equation.
METHOD 2
To calculate approximate ventilation:
Referencing same example. (See Fig. 26.) Total cu ft X 0.3 per hr
= total. Take total and divide by 60 to get CFM.
Example:
1320 sq ft X 8 ft in height = 10560 cu ft per floor
10560 cu ft X 3 floors = 31680 total cu ft in house
31680 cu ft X 0.3 air change per hr = 9500 cu ft
9500 cu ft
÷
60 minimum per hr = 160 CFM
Conclusion: The total amount of airflow needed is 160 CFM. This falls within airflow range of a HRVBBLHU1150 size unit.
CONTROL BOARD OPERATION
I.
BOARD FUNCTION
NOTE: To ensure proper operation of HRV, configuration jumpers are located on electronic control board and must match configuration setup shown on Fig. 27 and 28 under Jumper Table.
Jumpers are factory set and do not require any changes unless control board is replaced. If control board is replaced, or you encounter unusual start-up operation, check jumpers to make sure they are located properly. (See Fig. 27 and 28.)
II.
DEFROST
The HRV continually monitors the outside air temperature. If the outside air is at or below 23°F(-5°C), the HRV will initiate a defrost cycle by closing the outside air damper and re-circulating warm indoor air through the heat recovery core. This happens approximately every hr with 5 minute defrost cycle. During this process, core is defrosted without the use of electric strip heat. At
5°F(-15°C), unit will defrost for 5 minutes every half hr. At
-22°F(-30°C), the unit will sense a need to defrost every 20 minutes with a 5 minute cycle. See the Troubleshooting section for a control logic explanation.
III.
OFF AND INTERMITTENT/OFF MODE
When HRV is Off, K1 relay is open, and K5 relay is energized which closes outside air damper. (See Logic Diagram in Fig. 27 and 28.)
IV.
HIGH-SPEED AIR EXCHANGE
When high-speed air exchange occurs, K1 and K2 relays are energized and K5 relay is de-energized. This opens low-speed contacts, and closes high-speed contacts on K2 relay. This also opens contacts on K5 relay which opens outside air damper. Then,
115vac is applied between orange and gray wires on Molex plug
(pins 1 and 6) and blower motor runs in high-speed operation.
Also, 115vac is applied across pins 5 and 7, this energizes interlock relay. (See Logic Diagram in Fig. 27 and 28.)
V.
LOW-SPEED AIR EXCHANGE
When low-speed air exchange occurs, K1 Relay is energized which closes the contacts. K2 and K5 relays are de-energized. This keeps low-speed contacts closed and high-speed contacts open on
K2 relay, and opens outdoor air damper. 120vac is applied between Red and Gray wires on Molex plug (pins 1 and 4) and blower motor runs in low-speed operation. Also, 115vac is applied across pins 5 and 7, this energizes interlock relay. (See Logic
Diagram in Fig. 27 and 28.)
I.
HRV door can be removed by unlatching brief case style latches, then slide door to the right and remove it from hinges. Door must be in place and secured shut for proper operation.
II.
FILTER
CARE AND MAINTENANCE
WARNING: ways turn off main power to system. There may be more than 1 disconnect switch. Electrical shock can cause personal injury or death.
CAUTION: the unit.
DOOR
Before installing or servicing system, al-
Although special care has been taken to minimize sharp edges in the construction of your unit, be extremely careful when handling parts or reaching into
Filters in HRV are washable and should be cleaned every 3 months. Use a vacuum cleaner to remove heaviest portion of accumulated dust, then wash in lukewarm water. Allow filter to completely dry before reinstalling. A dirty air filter will cause excessive strain on blower motor. Never operate unit without a filter. Vacuum out debris.
—13—
In addition, regularly check and clean screens on exterior intake and exhaust hoods when necessary.
CAUTION: DO NOT clean filters in a dishwasher and
DO NOT dry them with a heating appliance or permanent damage will result.
III.
BLOWER MOTOR AND WHEEL
HRV blower motors are factory lubricated for life. Lubricating bearings is not recommended. However, inspect and clean any accumulated dirt and grease from blower motor and wheel annually.
IV.
CLEANING THE CORE
HRV unit is equipped with special heat recovery core and must be handled with care. We recommend that it be washed once a year following the season of most intense use. This will ensure maximum efficiency of the plastic partitions within the core.
Allow heat recovery core to soak for 3 hr in a solution of warm water and mild soap. Rinse under heavy stream of water. Hot water and strong detergent will damage core and should NOT be used.
TROUBLESHOOTING
WARNING: Before installing or servicing system, always turn off main power to system. There may be more than 1 disconnect switch. Electrical shock can cause personal injury or death.
CAUTION: Although special care has been taken to minimize sharp edges in the construction of your unit, be extremely careful when handling parts or reaching into unit.
NOTE: Reference Table 5 Troubleshooting Chart
This can be a quick guide in resolving unit problems. It is also recommended to review and understand Wall Control Board
Operation and Care and Maintenance sections before continuing.
There are 3 main parts to focus on when troubleshooting HRV unit:
1. Wall control
2. Electronic control board
3. Blower motor
I.
WALL CONTROL
Typically the wall control is either good, or it is bad. Use Table 1,
2, or 3 to determine if wall control is operating correctly. Use Fig.
12 to check control wire connections.
NOTE: The electronic control board and wall control operate on
12vdc.
II.
CONTROL BOARD
Electronic control board must have wall control attached before unit will function properly. Also, configuration jumpers located on control board must match configuration setup shown on Fig. 28 under Jumper Table. In addition, outside air thermistor must be connected to control board for it to operate properly. See Table 6,
Temperature -vs- Ohm Chart, for valid temperature range.
III.
BLOWER MOTOR
The HRV blower motor operates on 115vac, with 2-speed operation.
The easiest way to check blower speed operation is to use the wall control and initiate a low-speed blower and high-speed blower operation.
—14—
NOTE: If there is a short circuit or an open circuit at thermistor,
CPU will go into a 5 minute defrost cycle every 20 minutes. This feature is not there on older board versions with 3pin jumpers.
OVERRIDE TEST
To use override test function, a thermistor must be connected to the control board. Unit must not be in defrost mode during an override test.
A.
High Speed
1. Disconnect HRV from 115vac.
2. Unplug wall control wires at control module terminal block inside HRV.
3. Plug HRV back to 115vac.
4. Attach a wire across J3-8 and J3-9 (B and G) on control module terminal block.
5. Push in door switch, this will initiate a high-speed exchange.
B.
Low Speed
1. Unplug HRV from 115vac.
2. Disconnect wall control wires at control module terminal block inside HRV.
3. Plug HRV back to 115vac.
4. Connect a 3.9 Kohm resistor between J3-8 and J3-9 (B and
G) on control module terminal block.
5. Push in door switch, this will initiate a low-speed exchange.
IV.
BLOWER SPEED SELECTION
Three-speed blowers are factory connected to electronic control board on HIGH- and LOW-speed taps of blowers. Installer can easily change low-speed tap to medium-speed tap so electronic control will select between high and medium speed. Connections can be changed at motor location. (See Tables 7 and 8.)
To change low speed to medium speed, proceed as follows:
1. Unplug unit from 115vac.
2. Locate blower assembly.
3. Locate red wire and blue wire coming from blower assembly.
4. Unplug red wire from quick connect.
5. Unplug protecting cap quick connection from blue wire and put on red wire coming from blower. The cap is a safety insulator.
6. Connect red wire of main harness to blue wire.
7. Replace wires.
V.
DEFROST
Defrost cycle is controlled by a thermistor which is located in the fresh-air intake passage (the thermistor unit is connected to J4 of control module. See Fig. 27 and 28). When defrost temperature sensor detects the need for defrost, K5 relay will close for 6 minutes while K1 and K2 remain energized.
This closes the outdoor air damper while running HRV blower on high-speed. This process recirculates warm indoor air through heat recovery core which melts any frost that has formed. Water created in this process is collected by HRV and drained away. Frequency of the defrost cycle depends on outdoor temperature (see Table
10).
If defrost is not working properly, check for proper damper operation. To do this, turn unit to OFF position. Damper should close.
SAFETY FEATURE
This new control has an added safety feature. If microprocessor does not detect the thermistor or detects a short circuit, unit will automatically go into a 6 minute defrost cycle every 20 minutes.
SYMPTOMS
Air too humid
Unit not responding to wall control
Unit stops momentarily
Air from distribution register too cold
Unit makes annoying noise
Noise level too high at distribution registers when in high speed
TABLE 5—TROUBLESHOOTING CHART
CAUSES
Continuous exchange mode used in small houses
Defrost condition is in effect
Outdoor temperatue is below 23°F
Broken control wire
Electrical supply interrupted
Improper calibration of air flow
Ventilation wheel out of adjustment
SOLUTIONS
Use Intermittent Mode
Check humidity level settings
Unit will operate when not in defrost mode.
Defrost cycle is based on outdoor ambient (see
Table 10)
Test wall control
Check connections
Check thermistor
Check units circuit breaker
Check calibration of flow rates
Remove the motor and screw wheel on properly
Air duct system too short
TABLE 6—TEMPERATURE/OHM RELATIONSHIP
98
100
102
104
106
108
86
88
90
92
94
96
110
112
114
116
118
120
74
76
78
80
82
84
62
64
66
68
70
72
TEMP F°
30
32
34
36
50
52
54
56
58
60
38
40
42
44
46
48
8,042
7,668
7,310
6,993
6,661
6,368
6,085
5,811
5,571
5,313
5,088
4,869
14,530
13,790
13,090
12,480
11,860
11,270
10,750
10,250
9,750
9,300
8,840
8,432
4,660
4,450
4,268
4,019
3,918
3,750
OHMS
34,480
32,630
30,760
29,220
27,470
26,020
24,680
23,320
22,070
20,910
19,830
18,820
17,870
16,920
16,160
15,260
Install a duct silencer
TABLE 7—FACTORY SET BLOWER CONNECTION HIGH
CONTROL
MODULE
J1-6
No Connection
J1-4
OR LOW SPEED
MAIN ELECTRICAL
HARNESS CABLE
Orange
No Connection
Red
BLOWER
WIRE
SPEED
Orange High
Blue + Cap Medium
Red Low
TABLE 8—MODIFY BLOWER CONNECTION HIGH
OR MEDIUM SPEED
CONTROL
MODULE
J1-6
J1-4
No Connection
MAIN ELECTRICAL
HARNESS CABLE
Orange
Red
No Connection
BLOWER
WIRE
Orange
Blue
Red + Cap
SPEED
High
Medium
Low
TABLE 9—TEMPERATURE AND VOLTAGE
TEMPERATURE
°F (°C)
-22 (-30)
-4 (-20)
5 (-15)
14 (-10)
32 (0)
41 (5)
50 (10)
68 (20)
A.
Defrost Check
VOLTAGE DC
VOLTS (J4)
3.5
2.7
2.3
2.0
1.4
1.1
0.9
0.6
1. Make sure defrost cable is properly connected into J4.
2. Make sure thermistor assembly is correct. Measure thermistor temperature reading with multimeter. Select multimeter DC measurement scale 0-20v. At connector J4
(without removing thermistor cable), measure voltage between pins of thermistor cable. Depending on temperature of outside air intake, values should correspond with those in
Table 9.
If reading is not correct (reading 0v for short circuit or 5v for open circuit), change thermistor assembly.
3. If thermistor is good, do a RESET and see if defrost works.
If defrost still does not work, change circuit board.
B.
Advanced Debugging
Defrost can be simulated using the following procedures:
1. Unplug unit from 115vac.
2. Disconnect thermistor assembly from J4.
3. Replug unit in 115vac and select high-speed exchange.
4. Defrost should start within 2 minutes after high-speed exchange has been initiated.
—15—
OUTSIDE TEMPERATURE °F
Above 23°F
23°F to 5°F
4°F to -17°F
Below -18°F
TABLE 10—DEFROST CYCLE
STANDARD DEFROST (AS
SHIPPED)
No Defrost
6 Minute Defrost/60Minute Exchange
6 Minute Defrost/32 Minute Exchange
6 Minute Defrost/20 Minute Exchange
EXTENDED DEFROST
(JUMPER JU1-F REMOVED)
No Defrost
10 Minute Defrost/30 Minute Exchange
10 Minute Defrost/20 Minute Exchange
10 Minute Defrost/15 Minute Exchange
JU1A
MODEL
HRVBBLHU1150
HRVBBLHU1250
HRVBBSVU1150
HRVBBSVU1250
HRVBBLVU1150
HRVBBLVU1200
HRVBBLVU1330
JU1B JU1C
UNIT IDENTIFICATION
JU1A
OUT
OUT
IN
IN
IN
IN
IN
5. After test unplug unit.
6. Connect thermistor cable to J4.
7. Replug unit back in 115vac.
VI.
CONTROL MODULE JUMPERS
TABLE 11—JU1 JUMPER DEFINITION
JU1D JU1E
Reverse Damper Operation
In = Normal
Out = Inverse
TABLE 12—JUMPER LOCATIONS
JU1B
IN
IN
OUT
OUT
OUT
OUT
OUT
Jumpers on the control module give exact configuration to HRV micro-controller. If there is a mistake in the jumper configuration,it can cause improper unit operation. This control has a simplified jumper selection mode. Jumper selection is done by the presence or absence of jumper at specific location (See Tables 11 and 12.)
WARNING: to making any jumper change. If unit is not disconnected, micro-controller will never see jumper change. Failure to follow this warning could result in electrical shock or death.
Always disconnect unit from 115vac prior
JU1C
IN
IN
OUT
OUT
OUT
OUT
OUT
JUMPER TABLE
JU1D
OUT
OUT
OUT
OUT
OUT
OUT
OUT
JU1E
IN
IN
IN
IN
IN
IN
IN
JU1F
Factory Set
Always In
JU1F
IN
IN
IN
IN
IN
IN
IN
JU1G
Factory Set
Always In
JU1G
IN
IN
IN
IN
IN
IN
IN
VII.
ERROR SIGNALING
Two types of error can be signaled by the wall control (automatic wall control only). In case of error, indicators on wall control will flash.
When error occurs, set dehumidistat at 80 percent position. This will enable you to properly troubleshoot problems.
TYPE 1—LOSS OF MEMORY (AUTO MODEL ONLY)
All indicators flash rapidly (rate of about once every sec). When this occurs, reset power and check if problem still exists. If indicators are still flashing, check red wire for shorting on another component. If error still exists, wall control has lost its memory.
Replace wall control.
The defective wall control still works even when flashing, it is working in backup mode. Original modes of wall control are replaced by backup mode. (See Table 13.)
MODES
OFF
1
2
3
TABLE 13—BACK MODE
WALL CONTROL
BACKUP MODE
OFF
INTERMITTENT
LOW-SPEED EXCHANGE
HIGH-SPEED EXCHANGE
—16—
J3-9
J3-8
J3-7
J3-6
TABLE 14—SYSTEM WIRING COLORS AND CONNECTIONS
CONTROL MODULE
WALL CONTROL
WIRE
WALL CONTROL
Terminal Block No.
Terminal Block
Identification
B
G
R
Y
Color
Black
Green
Red
Yellow
Terminal No.
J1-4
J1-3
J1-2
J1-4
Terminal Identification
B
G
R
Y
TYPE 2—COMMUNICATION PROBLEM OR UNSUP-
PORTED MODE (AUTO MODEL ONLY)
All indicators flashing at a rate of about once every 8 sec.
Communication is not properly entered or is not working.
A.
Case 1
User changes the mode on wall control and HRV responds to command (OFF, LOW, or HIGH speed). Check all wires to wall control particularly red wire. (See Table 14.)
B.
Case 2
User changes the mode but, HRV does respond. All indicators flash at a rate of about once every 8 sec. Check all wires to wall control particularly green wire. If problem still exists, test wall control with 5 ft of wire from HRV. If this works, change wall control module inside HRV.
C.
Reset
To reset HRV, proceed as follows:
1. Unplug HRV from 115vac.
2. Wait 15 sec.
3. Plug HRV into 115vac.
—17—
CONNECTION DIAGRAM
BLK
G
R
Y
WALL CONTROL
WALL CONTROL
WALL CONTROL
WALL CONTROL
NOTE 1, 5
OVERRIDE SWITCH
OVERRIDE SWITCH
OVERRIDE LED
OPTIONAL
NOTE 5
120V 60Hz
FROM MAIN
S1
LOGIC DIAGRAM
J1 3
A1
J1 6
K1
RELAY
J1 4
K2
RELAY
RELAY K5 J1 9
NEUTRAL
J1 2
MED
NC
HIGH
M1
FAN
MOTOR
LOW
M2
DAMPER
MOTOR
J1 1
J1 8
DEFROST
TEMPERATURE
SENOR
A1
NOTE 4
ELECTRONIC ASSEMBLY
R1
T1
GY
R
GY
O
G
NC
1
2
3
R
X1
GY
O
G
BL
R
(NOTE 2)
M1
NEUTRAL
HIGH
FAN MOTOR
MEDIUM
LOW
BN
BN
C1
ELECTRONIC ASSEMBLY W BK O
BL Y
MAIN EARTHING
POINT
NOTES
1. CONTROLS AVAILABLE. SEE INSTALLATION MANUAL.
( LOW VOLTAGE ONLY 12 VOC.).
2. FACTORY SET WIRING FOR SLOWER SPEED SELECTION IS HIGH AND
LOW. MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED.
DISCONNECT RED WIRE FROM THE MOTOR RED TAP. AND CONNECT
TO THE MOTOR BLUE TAP.
3. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED.
USE THE SAME OR EQUIVALENT WIRE.
4. USE FACTORY SUPPLIED PROTECTIVE TUBING.
5. FIELD WIRING MUST COMPLY WITH APPLICABLE CODES,
ORDINANCES AND REGULATIONS.
BK
COM NO
DOOR INTERLOCK
SWITCH
S1
NEUTRAL
LINE
LINE VOLTAGE
LOW VOLTAGE
AND FIELD WIRE
Y
BL
M2
X2
1
BL
2
BL
DAMPER
MOTOR
R
V
W
Y
BN
NC
G
W
BK
W1
120 V 60 HZ
NEMA-15P
5-15 PLUG
COLOR CODE
RED
VIOLET
WHITE
YELLOW
BROWN
NO CONNECTION
BK
BL
GY
O
G
BLACK
BLACK
GREY
ORANGE
GREEN
JU1A
OUT
JUMPER TABLE
JU1
A B C D E F G
2
1
JU1B JU1C JU1D JU1E JU1F JU1G
OUT IN IN OUT IN IN
MODEL
TYPE
HRVBBLHU1150
OUT OUT IN IN OUT
NO
CHANGE
NO
CHANGE
NO
CHANGE
NO
CHANGE
NO
CHANGE
IN IN
OUT
NO
CHANGE
HRVBBLHU1250
EXTENDED DEFROST
ALL TYPES
A
A
A
D E F RO S T T I M E
(DEFROST/VENTILATION)
M I N U T E S
23
°
F
-5
°
C
6/32
5
°
-15
F
°
6/32
-22
C -30
°
°
F
C
6/20
6/32
10/30
6/32
10/20
6/20
10/15
FUNCTION TABLE
A
MODE
Intermittent
Exchange Low
Exchange High
K1
0
Circulation low
Circulation high
Defrost Cycle
Off
1
0
0 = Relay coil is de-energized
1 = Relay coil is energized
NS = Not supported
1
1
1
1
RELAY
K2
0
0
1
0
1
1
0
K4
0
1
1
1
1
1
0
K5
0
0
0
1
1
0
0
Fig. 27—Wiring Diagram for Models: HRVBBLHU1150, and HRVBBLHU1250
A00035
DEFROST
TEMPERATURE SENOR
-t
CONNECTION DIAGRAM
NOTE 1 OPTIONAL
120VAC
DOOR
INTERLOCK
SWITCH
J1 3
K1
RELAY
J1 4
K2
RELAY
J1 6
LOGIC DIAGRAM
LOW
HIGH
FAN
MOTOR
2
MED
(NOTE 5)
LOW
HIGH
FAN
MOTOR
1
MED
(NOTE 5)
J1 2
NEUTRAL
J1 1
POWER CONTROL BOARD W
GY
BK O
R
BL Y
BK
DOOR INTERLOCK SWITCH
GY
O
R
GY
O
R
1
2
NC
1
2
NC
GY
O
BL
R
FAN MOTOR 2 (NOTE 3)
GY
O
BL
R
NEUTRAL
HIGH
MEDIUM
LOW
BN
BN
MOTOR
CAPACITOR
G
FAN MOTOR 1
NEUTRAL
HIGH
MEDIUM
LOW
BN
BN
MOTOR
CAPACITOR
G
(OPTIONAL)
TO J1 PIN 7
TO J1 PIN 5
INTERLOCK RELAY KIT
24 VAC TO
INDOOR
EQUIPMENT
Y
BL
1
2
DAMPER MOTOR 2
Y
BL
(NOTE 4)
DAMPER MOTOR 1
1
Y
2
BL
W
COM
NO
BK
NEUTRAL
G
LINE
NEMA-15P
120VAC 60HZ
LINE VOLTAGE
LOW VOLTAGE
AND FIELD WIRE
OPTIONAL
R
V
W
Y
BN
NC
COLOR CODE
RED
VIOLET
WHITE
YELLOW
BROWN
NO CONNECTION
BK
BL
GY
O
G
BLACK
BLACK
GREY
ORANGE
GREEN
K5
RELAY
J1 9
CONTROL BOARD
IN
IN
IN
IN
JU1A
IN
JUMPER TABLE
JU1
A B C D E F G
2
1
JU1B JU1C JU1D JU1E JU1F JU1G
OUT OUT OUT IN IN IN
MODEL
HRVBBSVU1150
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
HRVBBSVU1200
HRVBBLVU1150
HRVBBLVU1200
HRVBBLVU1330
NOTES
1 - THREE CONTROLS AVAILABLE. SEE THE INSTALLATION MANUAL
(LOW VOLTAGE ONLY 12 VDC).
2 - FAN MOTOR 2 IS USED ONLY WITH HRVBBLHU1250, HRVBBLVU1200,
AND HRVBBLVU1330.
3 - DAMPER MOTOR 2 IS USED ONLY WITH HRVBBLVU1200 AND
HRVBBLVU1330.
4 - IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE
REPLACED, USE THE SAME OR EQUIVALENT WIRE.
5 - FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND
LOW. MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED.
DISCONNECT RED WIRE FROM MOTOR(S) RED TAP AND CONNECT TO
MOTOR(S) BLUE TAP.
A
A
A
A
A
DAMPER
MOTOR
1
DAMPER
MOTOR
2
J1 8
FUNCTION TABLE
A
MODE
Intermittent
Exchange Low
Exchange High
Circulation low
K1
0
1
Circulation high
Defrost Cycle
1
1
Off 0
0 = Relay coil is de-energized
1 = Relay coil is energized
NS = Not supported
1
1
RELAY
1
1
1
0
0
K2
0
0
1
1
0
1
1
K5
1
0
A00090
Fig. 28—Wiring Diagram for Models: HRVBBSVU1150, HRVBBSVU1200, HRVBBLVU1150, HRVBBLVU1200, and HRVB-
BLVU1330
2 3
⁄
16 †
(56.2)
4 PLCS
2 5
⁄
16 †
(58.7)
G
4 3
⁄
4
†
(120.6)
1 †
(25.4)
2 PLCS
5 7 ⁄
8 † DIA
(149.2)
4 PLCS
4 1
D
20 †
(508.0)
18 1
⁄
8 †
(460.4)
16 7 ⁄
8 †
(428.6)
15 †
(381.0)
2 3
C
F
A
B
30 1 ⁄
4 †
(768.3)
E
NOTES:
1. FRESH AIR FROM OUTSIDE TO HRV
2. FRESH AIR FROM HRV TO HOUSE
3. STALE AIR FROM HOUSE TO HRV
4. STALE AIR FROM HRV TO OUTSIDE
A99263
A
MODEL NO.
in.
mm in.
HRVCBBLHU1150 15-1/8 384.2
4-1/16
B
HRVBBLHU1250 19 mm
104 in.
C mm in.
D mm in.
E mm
5-5/8 143.3
14-1/2 368.9
11-3/8 288.9
in.
4-3/8
F mm in.
G mm
111.3
7-3/4 196.9
483 5-13/16 147.7
5-1/16 128.1
14-1/2 368.9
11-3/16 254.0
5-13/16 401.6
9-5/16 236.6
Fig. 29—Dimensional Drawing HRVBBLHU
1
4 9 ⁄ 16
″
[115.9)]
5 7 ⁄
8
″
DIA
[149.2]
2 PLCS
3
F DIA
2 PLCS
3 3 ⁄
16
″
[81.0]
2 C
5 3 ⁄
4
″
[146.0]
4
B
D
19 3 ⁄
4
″
[501.7]
1 15 ⁄
16
″
[23.8]
2 3 ⁄
16
″
[55.6]
4 PLCS
1
″
[25.4]
2 PLCS
POWER
CORD
WALL
CONTROL
WIRING
3 ⁄
8
″
DIA
[9.5]
27
″
[685.8]
NOTES:
1. FRESH AIR FROM OUTSIDE TO HRV
2. FRESH AIR FROM HRV TO HOUSE
3. STALE AIR FROM HOUSE TO HRV
4. STALE AIR FROM HRV TO OUTSIDE
A
22 1 / 16
″
[560.4]
15 11 ⁄
16
″
[398.5]
DRAINS
11 ⁄
16
″
DIA.
[17.5]
2 PLCS
E
G
A98003
A B C D E F G
MODEL NO.
in.
mm in.
mm in.
mm in.
mm in.
mm in.
mm in.
mm
HRVBBSVU1150 18-1/2 469.9
4-11/16 119.1
13-5/16 388.2
15-7/16 392.1
13-9/16 344.5
5-7/8 149.2
19-15/16 506.2
HRVBBSVU1200
HRVBBLVU1150
24-1/2 622.2
8-3/16 208.0
19-5/16 490.6
14-9/16 369.9
16-15/16 430.2
6-7/8 174.6
19-15/16 506.2
Fig. 30—Dimensional Drawing HRVBBSVU and HRVBBLVU
1 1 ⁄
2
″
[38.1]
2 PLCS
24 1 ⁄
16
″
[611.2]
4
2
8 1 ⁄
8
″
DIA
[206.4]
2 PLCS
5 7 ⁄
8
″
DIA
[148.2]
2 PLCS
43
″
(1092.2)
17 9 ⁄
16
″
[446.9]
3
5 13 ⁄
16
″
[147.6]
4 3 ⁄
4
″
[120.6]
15 1 ⁄
2
″
[393.7]
NOTES:
1. FRESH AIR FROM OUTSIDE TO HRV
2. FRESH AIR FROM HRV TO HOUSE
3. STALE AIR FROM HOUSE TO HRV
4. STALE AIR FROM HRV TO OUTSIDE
18 5 ⁄
16
″
[465.1]
1
″ [
25.4]
2 PLCS
6 15 ⁄
16
″
[176.2]
1
2 3 ⁄
16
″
[55.6]
2 PLCS
7 1 ⁄
8
″
[181.0]
POWER
CORD
41
″
[1041.4]
12 3 ⁄
4
″
[323.9]
WALL
CONTROL
WIRING
3 ⁄
8
″
DIA
[9.5]
23 15 ⁄
16
″
[608.0] 22 3 ⁄
8
″
[568.3]
DRAIN
11 ⁄
16
″
DIA.
[17.5]
2 PLCS
19 1 ⁄
16
″
[484.2]
8 3 ⁄
16
″
[208.0]
7 3 ⁄
16
″
[182.6]
Fig. 31—Dimensional Drawing HRVBBLVU1200 or HRVBBLVU1330
A98001
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
—23—
© 2000 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —24— Printed in U.S.A.
hrv712 Catalog No. 13HR-VB3
advertisement
Key Features
- Heat Recovery Ventilator
- Fresh air exchange
- Heat recovery core
- Independent or standalone use
- Conditioned space installation
- Easy access for maintenance
- Adjustable humidity control
- Defrost cycle
- Three-speed blower
- Washable air filters