Dossena 9DER3/2IM Quick Start Manual
Dossena 9DER3/2IM is a residual current device (RCD) designed for use in LV AC networks of TT and TN types. This device offers a wide range of adjustment for the I∆n threshold, reaching up to 30A, and for the delay time, up to 10 seconds. With its various functionalities, it provides ease of use, high reliability, and efficient installation. The clear display shows all measurement values and parameters, while the color variation of the background indicates the device's working status.
PDF
Download
Document
Advertisement
Advertisement
DER3 MU 1140 R .7 EV Codice Ordinazione/ Order Code: 9DER3/2IM - 9DER3/2I – 9DER3/2D- 9DER3/1I- 9DER3/1D- 9DER3/2IMRS485 - 9DER3/2IRS485 –9DER3/2DRS485 CARATTERISTICHE TECNICHE/ TECHNICAL CHARACTERISTICS Alimentazione ausiliaria/ Auxiliary power supply Us Tensione di alimentazione/ Auxiliary power supply 48 ÷ 400 Vca/ac -15/+10% (@50/60Hz ) Uimp 4kV Categoria sovratensione/ Overvoltage category Consumo max/ Max consumption ≤ 4VA Grado inquinamento/ Pollution degree Circuito controllato (in abbinamento a toroidi Dossena) / Monitored circuit (by using Dossena toroids) Tipo di MRCD/ Type of MRCD A, AC Norme di riferimento/ Standards Un Tensione nominale/ rated voltage <1000Vca/ac (@50/60Hz) Uimp Sistema di distribuzione/ Distribution system TT, TN Icw Tipo di Misura/ Measurement type Campo di regolazione IΔn/ Adjustment range IΔn Collegamenti toroide-relè/ Connections toroidMRCD In Massima corrente nominale/ Maximum rated current IEC 60947-2:2019 8kV 80kA (0.5s) Continua /variabile Tipo di regolazione/ Adjustment Continuously/ variable Campo di regolazione Δt/ Adjustment range Δt Inst./ 0,06 ÷ 10Sec. Categoria sovratensione/ Overvoltage category CAT III Grado inquinamento/ Pollution degree 2 TRMS 0,03 ÷ 30A Cavi schermati twistati/ Shielded twisted cables D35 480A D60 720A D80 1020A CAT II 2 D110 1560A D160 1860A D210 2160A D60A 720A D110A 1560A D160A 1860A D210A 2460A Involucro/ Housing Classe di isolamento/ Insulation class Grado di protezione/ Protection degree Contatti uscita/ Output contacts Tipo di Interfaccia seriale/ Serial interface Terminazione linea seriale/ Serial line termination Isolamento galvanico seriale/ Serial line insulation Massima altitudine/ Maximum altitude II sul frontale/ II on the front Tenuta al fuoco/ Fire resistance IP40 frontale/ front panel IP20 morsetti/ terminals Altre caratteristiche/ Other features 2 NA-C-NC 250Vca/ac 5A (P.F.= 1)/ Sezione max morsetti/ Max. terminals section 30Vcc/dc 3A RS485 Modbus RTU Spellatura conduttori/ Cable strip 120Ω <1kV @50Hz 2000m Coppia di serraggio/ Tightening torque Temp.di funzionamento/ Operation temperature Temp. di stoccaggio/ Storage temperature Involucro in classe: V0 Housing class: V0 2,5mm2 7mm 0,6Nm -10 ÷ +55°C -20 ÷ +80°C Generalità: I relè differenziali di tipo A, AC della gamma DER3 Dossena, perfettamente conformi alla normativa vigente IEC 60947-2:2019, possono essere impiegati su reti BT in corrente alternata di tipo TT e TN. Essi consentono di realizzare un'adeguata selettività della protezione differenziale grazie all'ampia regolazione della soglia della corrente di dispersione (fino a 30A) e della soglia di ritardo dell'intervento (fino a 10sec). La gamma, ricca di funzionalità, garantisce semplicità di utilizzo, grande affidabilità, facilità di installazione e rapidità di programmazione. Sull’ampio display sono visualizzate in modo chiaro le grandezze e i parametri. La variazione del colore di fondo indica con immediatezza lo stato di funzionamento dello strumento (Verde= Vigilanza, Azzurro= Programmazione, Rosso= Allarme/Intervento). PRECAUZIONI DI SICUREZZA E ISTRUZIONI DI INSTALLAZIONE Tutte le operazioni di installazione e manutenzione devono essere eseguite da personale qualificato in assenza di tensione ed in totale regime di sicurezza elettrica, nel rispetto delle normative vigenti. 1) Prima di alimentare l’apparecchiatura DER3 verificare di aver eseguito correttamente tutti i collegamenti necessari. 2) Installare SEMPRE il differenziale insieme ai toroidi serie D. 3) La sezione dei conduttori deve essere tale che la resistenza totale di ciascuna connessione DER3 ↔ trasduttore sia inferiore a 0,5Ω. 4) Ridurre al minimo la distanza dei collegamenti tra DER3 e trasduttore tenendoli il più lontano possibile da cavi di potenza; utilizzare cavi twistati (mantenere separato il circuito di misura da quello di prova) e schermati con lo schermo connesso a terra in un solo punto. STATO DI NORMALE VIGILANZA (display verde) (I∆): Visualizzazione in vero valore efficace (TRMS) della corrente di dispersione in A. (I∆n): Soglia di corrente di dispersione nominale impostata. ∆t= tempo limite di non intervento impostato. Istogramma: rappresenta graficamente la misura della corrente di dispersione del sistema in % di I∆n (solo per DER3/2D-2I-2IM). AL= visualizzazione grafica della soglia di allarme impostata (solo per DER3/2D-2I-2IM). Funzione dei pulsanti: ▲ ▼ = possibilità di regolare il contrasto del display. SET = premere per almeno 3 secondi per entrare nel SET UP. TEST = premere per eseguire il test – tenere premuto per circa 10 secondi per eseguire il TEST SPECIALE. RST = premere RST per eseguire il reset manuale (appare solo se impostato in modalità manuale “MAN”). TEST: Il test verifica l'intero sistema di protezione differenziale (DER3+ toroide serie D + B.A.). Premendo il tasto test, il display si colorerà di rosso, il relè di TRIP e il 2° relè cambieranno di stato. Compariranno lampeggianti il segnale di pericolo e la scritta TRIP. Se il riarmo è impostato su manuale (MAN) premere il tasto RESET per riarmare il differenziale. TEST SPECIALE: Il test speciale (unicamente con B.A.) verifica l'intero sistema di protezione differenziale (DER3 + toroide + B.A.) senza intervento della B.A. e viene eseguito solo ed esclusivamente con il relè di TRIP normalmente diseccitato ovvero impostato in N.De. Tenendo premuto il tasto di TEST per circa 10 secondi, viene avviato il test. Se alla fine del test il display risulta verde, compare la scritta TEST OK e lampeggia il segnale di pericolo, il test è andato a buon fine e nessun relè cambia di stato. Se invece il display diventa giallo/rosso lampeggiante e lampeggia il segnale di pericolo con scritta REL. BA il test è fallito e viene comandato il cambio di stato del 2° relè. Note: a seguito di forti anomale e sollecitazioni elettromagnetiche potrebbe accadere che sul display scompaia la simbologia; in tale caso premere semplicemente uno dei tasti▲ ▼ per ritornare alla normale visualizzazione. STATO DI SETUP (display azzurro) 1- premere per almeno 3 secondi il tasto SET per entrare nel SETUP(display apparirà azzurro). 2- premere rapidamente il tasto SET per passare da un parametro all’altro in modo ciclico (il parametro da modificare apparirà lampeggiante). 3- premere ▲▼per modificare il parametro selezionato. 4- premere SET per almeno 3 secondi per uscire dal SETUP, salvando i parametri impostati (display torna verde) Dopo circa 3 minuti di inattività il DER3 esce automaticamente dal SETUP senza salvare le modifiche. Note: I parametri di configurazione modificati saranno attivi solo dopo averli salvati e rimarranno tali anche nel caso in cui lo strumento perda l’alimentazione. Se intervengono allarmi durante la fase di programmazione,questi sono da associarsi alle impostazioni precedenti. PARAMETRI RANGE [DEFAULT] IΔn (A)= Soglia della corrente di dispersione nominale: valore al quale la ID provoca l'intervento del relè di TRIP . 0,03 ÷ 30A [0,03A] ΔT= Tempo limite di non intervento(s) ovvero il ritardo entro il quale una corrente differenziale più elevata di IΔn può fluire nel DER3 senza provocare l'intervento (se = “INST” il differenziale funzionerà senza ritardo). 0,06 ÷ 10sec. [0.060S] T – il 2° relè funziona come secondo relè di TRIP: cambio di stato contemporaneamente al relè di TRIP (la bobina di apertura deve comunque essere sempre collegata al relè di TRIP). A – il 2° relè funziona come relè di allarme: cambio di stato al superamento della soglia di allarme impostata (solo per DER3/2D-2I-2IM). T/ A [A] N.De.=indica lo stato di riposo del relè di TRIP. E’ normalmente diseccitato (N.De.) e si eccita quando la ID supera la IΔn. NE= indica lo stato di riposo del relè di TRIP. E’normalmente eccitato (N.E.) e si diseccita quando la ID supera la IΔn. Impostando NE (sicurezza positiva) esclude la vigilanza continua del funzionamento del circuito della bobina di apertura BA. N.De. - N.E.* [N.De.] MAN/AUTO: Stato di funzionamento del RESET: in modalità MAN, a seguito di uno scatto per IΔ>IΔn, la scritta “SET” diventa “RESET” e permetterà quindi il RESET della condizione di TRIP (solo se IΔ<IΔn). MAN- AUTO [MAN] ◄ AL: Soglia di intervento allarme (% di IΔn): al superamento di tale soglia si genera una condizione di allarme (solo per DER3/2D-2I-2IM) 20% ÷ 80% [50%] <R: Valore percentuale d'isteresi rispetto alle soglie impostate. 30% ÷ 80% [80%] KCT= rapporto di trasformazione dei trasduttori. Per la “serie D” è 0,500 K. Modificare a 5 solo se si usano i trasduttori D80S e D300M. 0,001 ÷ 30 [0,500] NODE= Nodo di rete: assegnare ad ogni singolo DER3 un numero di nodo (solo per versioni dotate di uscita seriale RS485). BAUD= Configurazione velocità seriale (solo per versioni dotate di uscita seriale RS485). 1 ÷ 247 [1] 4800 ÷ 38400 [19200] *Attenzione: la condizione di N.E. (sicurezza positiva) è applicata solo ed esclusivamente al relè di TRIP e non al secondo relè, anche nel caso in cui fosse configurato come TRIP. Pag 2 di 4 Introduction: The residual current devices, type A, AC Dossena DER3 series, fully compliant with IEC 60947-2: 2019, can be used in LV network in AC ,TT and TN type. The series offers a wide range of adjustment of the I∆n threshold (up to 30 A) and of the delay time (up to 10 sec). DER3 guarantees ease of use, reliability, and speed of programming. The measures and parameters are clearly displayed. The variation of the background colour immediately indicates the instrument’s operating status (Green = residual current protection active, Blue = setup, Red = Alarm / Intervention). INSTALLATION SUGGESTIONS AND SAFETY PRECAUTION: All installation and maintenance operations must be carried out by qualified personnel in the absence of voltage and in a total electrical safety regime, in compliance with the safety regulations. 1) Before powering the DER3, check that all connections have been executed properly. 2) ALWAYS install DER3 combined with Dossena toroidal transducer D series. 3) The cross-section of the conductors must be such that the total resistance of each DER3 ↔transducer connection is less than 0.5Ω. 4) Minimize the distance connections between DER3 and transducer and keep them away from power cables; use twisted shielded cables with the shield connected to ground at one point only (keep the measurement circuit separate from test circuit). NORMAL VIGILANCE (GREEN DISPLAY) (I∆): Display in true rms value (TRMS) of the residual current in A. (I∆n): Set threshold of the nominal residual current. ∆t= Set the limiting non-actuating time. Histogram: represents the measurement of the residual current of the system in% of I∆n (only for models DER3/2D - 2I - 2IM). AL= Alarm threshold (only for models DER3/2D - 2I - 2IM). Keys functions: ▲ ▼ = possibility to adjust the display contrast. SET = press for at least 3 seconds to enter in SET UP. TEST = press to perform DER3 test, push for at least 10 seconds to start DER3 a special test RESET = Reset button, active only in the manual reset mode. TEST: The test checks the complete protection system (DER3+ toroid series D + T.C.). Push test button to start the test. Display becomes red. The TRIP relay and the 2nd relay change state. Danger signal and message “TRIP” appear flashing on display. Press “RESET” button to reset the device, if the reset mode is in manual mode (MAN). SPECIAL TEST: The special test (only possible with T.C.) checks the complete protection system without T.C. tripping; it can be executed only if the TRIP mode is set as normally de-energized N.De. Press the test button for 10 seconds to perform the special test. At the end of test, if the display will be green, the message "TEST OK" will appear and the danger signal will flash, the test has been successful. No relays switch. Otherwise, the test has failed when the display flashes red and yellow and the message “REL.BA” flashes, with the switching of the 2nd relay . Note: In case of strong electromagnetic disturbances the display may go blank or irregular: push the button ▲or ▼ to restore the normal display. SETUP (BLU DISPLAY) 1 -push SET button for at least 3 seconds to enter in SETUP(display becomes blue) 2- push quickly SET button to select cyclically the parameter to modify (it will appear flashing) 3- push ▲▼ buttons to modify the selected parameter 4- push SET button for at least 3 seconds to exit from SETUP and save the parameters (display returns green). DER3 automatically exits from SETUP without saving modification after 3 minutes of inactivity. Note: The new setup parameters will be operative only after saving, and they remain the same even in case of loss the power supply. If an alarm occurs in setup, it is caused by the previously set parameters. PARAMETERS RANGE [DEFAULT] I∆n (A)= Threshold of the nominal residual current: when IΔ exceeds I∆n TRIP relay switches. 0,03 ÷ 30A [0,03A] ΔT= Limiting of non-actuating time. If you set it to "INST", the tripping mode becomes instantaneous. 0,06 ÷ 10sec [0.06S] nd T – The 2 relay can work as a TRIP relay: it switches at the same time of TRIP relay (the trip coil must be always connected to TRIP relay). A – The 2nd relay can work as an alarm relay. It switches when set alarm threshold is exceeded (only for models DER3/2D-2I-2IM). T/ A [A] N.de. = Trip relay is normally de-energized (N.De.) and it energizes when IΔ exceeds set I∆n NE= Trip relay is normally energized (N.E.) and it de-energizes when IΔ exceeds set I∆n. Setting TRIP as normally energized N.E. (positive security/fail safe) disables the permanent control of T.C. and its power. N.De. - N.E.* [N.De.] MAN/AUTO: Reset mode: manual or automatic. After a trip for IΔ> IΔn, the written "SET" becomes "RESET" and will therefore allow the RESET of the TRIP condition (only if IΔ <IΔn). MAN- AUTO [MAN] ◄ AL: Threshold of Alarm (% of IΔn). ): when this threshold is exceeded, an alarm condition is generated (only for models DER3 / 2D-2I-2IM) 20% ÷ 80% [50%] <R: Hysteresis: threshold in percentage value of IΔn. 30% ÷ 80% [80%] KCT= transformation ratio of toroid. For "Series D" it is 0.500 K, no changes values admitted. Set to 5 only with the use of toroids D80S and D300M. 0,001 ÷ 30 [0,500] NODE= Configuration network node: assign to each DER3 a node number (only for versions equipped with serial output RS485) BAUD= Serial baudrate configuration (only for versions equipped with serial output RS485) 1 ÷ 247 [1] 4800 ÷ 38400 [19200] * Warning: the safety condition N.E, is applied exclusively to the TRIP relay and not to the second relay, even if it is set in TRIP condition. Pag 3 di 4 ALLARMI: Il simbolo di pericolo è sempre visibile sul display/ ALARMS: the danger symbol is always visible on display MSG COLORE/ COLOR ALA lampeggiante giallo/rosso (Solo per: flashing Only for: yellow/red 2I/2IM/2D) BA lampeggiante giallo/rosso EVENTI/ EVENTS CAUSA/ CAUSE Il 2° relè cambia di stato (solo se impostato come relè di allarme). Incremento dell'istogramma. Incremento del valore di corrente I∆. ALLARME B.A.: Possibile problema della BA (disconnessa o assenza tensione) o interruttore non armato. ATTENZIONE: Se l’impianto non fa uso della BA occorre disabilitare tale controllo (vedere sotto in “NOTE SPECIALI”). B.A. ALARM: Possible T.C. problem (disconnection, no voltage) or no armed circuit breaker. WARNING: Disable this monitoring if no TC is used in the system(see below in “SPECIAL NOTES”). Il 2° rele cambia di stato. The 2nd relay switches. rosso fisso Red Alarm thereshold exceeded: The residual current I∆ is greater than the set alarm threshold The 2nd relay switches (only if it set as alarm relay). Increasing of histogram. Increasing I∆ current value . flashing yellow/red TRIP Superamento soglia allarme La corrente di dispersione I∆ ha superato la soglia di allarme Il rele di Trip e il 2° rele cambiano stato. Incremento dell'istogramma. Blocco della visualizzazione sul valore di corrente per cui è avvenuto l'intervento. ALLARME DI TRIP La corrente di dispersione I∆ ha superato almeno l'85% della soglia I∆n. TRIP ALARM (I∆n) The residual current I∆ has exceeded at least 85% of threshold I∆n. The Trip relay and the 2nd relay change state. The increasing of histogram The visualization is blocked on current value for which DER3 has tripped. TORO rosso fisso Red Il rele di Trip cambia stato. Il 2° rele cambia di stato (solo se impostato come secondo relè di trip). TheTrip relay switches. The 2nd relay switches (only if it is set as second trip relay). TEMP rosso fisso Red ALLARME TOROIDE Problema toroide: o è scollegato (controllare i collegamenti con il DER3) o possibile presenza di cortocircuiti nei suoi avvolgimenti. TOROID ALARM Toroid problem: either it is disconnected (check the wirings between toroid and DER3) or there is a short in its windings. ALLARME TEMPERATURA Eccessiva temperatura interna TEMPERATURE ALARM Excessive internal temperature NOTE SPECIALI FUNZIONALITA’ MEMORIA DI INTERVENTO (SOLO PER DER3/2IM): Il DER3/2IM è in grado di indicare il proprio intervento anche in mancanza di alimentazione. Premendo il primo tasto partendo da sinistra ▼se il display si illumina di rosso il DER3/2IM è intervenuto. Il DER3/2IM necessita di restare acceso almeno 10 minuti per attivare la memorizzazione di intervento. Attenzione: il DER3/2IM sarà in grado di mantenere la memoria dell’intervento fino ad un massimo di 4 giorni e tale tempo si ridurrà dopo ogni consultazione. SPECIAL NOTES: MEMORY INTERVENTION FEATURE (ONLY FOR DER3/2IM): It is possible to know if the DER3/2IM tripped even when it is not powered: by pressing the first button from the left ▼ , if the screen lights up in red DER3/2IM tripped. Storage is only possible if the DER3/2IM device has been turned on for at least 10 minutes. Warning: the DER3/2IM will be able to keep the memory of the trip up to a maximum of 4 days, and it will be reduced after every consultation. DISATTIVAZIONE ALLARME BA: Per disattivare l’allarme BA: 1. Premere per circa 20 secondi il pulsante ▼. 2. Entrare in Set-up premendo il tasto SET per almeno 3 secondi (display azzurro). 3. Uscire dal Set-up premendo il tasto SET per almeno 3 secondi (display verde). 4. Spegnere il differenziale. 5. Accendere il differenziale. Il controllo della BA è disattivo. 6. Ripetere dal punto 1 per riattivare la funzionalità. T.C. ALARM DISABLING: Follow the instructions below to disable the T.C. alarm: 1. Press at least 20 seconds the button ▼. 2. Enter in setup by pressing SET for at least of 3 sec (blue display). 3. Exit from setup by pressing SET for at least of 3 sec (green display). 4. Power off the MRCD. 5. Power on the MRCD. The T.C alarm is disabled. 6. Repeat the procedure to enable again the TC alarm REGOLAZIONE CONTRASTO DISPLAY: Per modificare il contrasto del display premere ▲o▼ quando lo strumento è in stato di normale vigilanza (display verde) DISPLAY CONTRAST ADJUSTMENT: Press ▲or ▼ to modify the display contrast when the device is in normal vigilance mode (green display) Pag 4 di 4 ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Residual Current Device (RCD)
- Type A, AC
- Wide Adjustment Range I∆n (0.03-30A)
- Adjustable Delay Time (0.06-10s)
- Clear Display
- Visual Status Indication (Green, Blue, Red)
- RS485 Modbus RTU Interface (for certain models)
Frequently asked questions
Ensure all necessary connections are made correctly. Install the device with the Dossena D series toroidal transducers. The conductor cross-section must be sufficient to keep the total resistance of each connection under 0.5Ω. Minimize the distance between the device and the transducer, use shielded twisted cables, and connect the shield to ground at one point only.
'I∆n' stands for the threshold of the nominal residual current. It represents the current value at which the residual current exceeds the set threshold, causing the TRIP relay to switch.
'ΔT' refers to the limiting non-actuating time. If it is set to 'INST', the tripping mode becomes instantaneous, meaning there is no delay. It allows you to control the delay time before the device trips.
Press the 'TEST' button to begin the test. The display will turn red, the TRIP relay and the second relay will change state. The danger signal and the message 'TRIP' will flash. Press the 'RESET' button if the reset mode is set to 'MAN'.
The 'BA' alarm indicates a possible problem with the T.C. (disconnection, no voltage) or an un-armed circuit breaker. If the system doesn't use the T.C., disable this monitoring.