Autonics TS4M Instruction Manual
The Autonics TS4M is a dual-indicator temperature controller designed for precise temperature control in various applications. Featuring a 4-digit display, touch switch settings, and a variety of control methods (ON/OFF, P, PI, PD, PID), the TS4M provides versatile control options. It accommodates various input sensors, including thermocouples and RTDs, for a wide range of temperature measurement needs. Additionally, the unit offers alarm outputs for monitoring critical temperature thresholds.
PDF
Download
Document
Advertisement
Advertisement
Dimensions Specificatio Caution 1. When connecting the power input and relay output, use AWG 20(0.50mm2) cable or over and tighten the terminal screw with a tightening torque of 0.74~0.90N.m. When connecting the sensor input and communication cable without dedicated cable, use AWG 28~16 cable and tighten the terminal screw with a tightening torque of 0.74~0.90N.m. Failure to follow this instruction may result in fire or malfunction due to contact failure. 2. Use the unit within the rated specifications Failure to follow this instruction may result in fire or product damage. 3. Use dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in electric shock or fire. 4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidit , direct sunlight, radiant heat, vibration, impact, or salinity may be present. Failure to follow this instruction may result in fire or explosion. 5. Keep metal chip, dust, and wire residue from flowing into the unit Failure to follow this instruction may result in fire or product damage. S 4 M 2 4 R Control output Power supply Sub output Size Digit Setting type Item 1. Present temperature (PV) display (Red) 1) RUN mode: Present temperature (PV) display 2) Parameter setting mode: Parameter display 2. Set temperature (SV) display (Green) 1) RUN mode: Set temperature (SV) display 2) Parameter setting mode : Parameter setting value display 8 3. Control/Alarm output display indicator 1) OUT: It turns ON when the control output is ON. During SSR drive output type in CYCLE/ 2 PHASE control, this indicator turns ON when 7 MV is over 3.0%. 2) AL1/AL2: It turns ON when the alarm output is ON. 4. Auto tuning indicator AT indicator flashes by every 1 sec during operating auto tuning. 1 3 4 5 5. 6 P Wiring method No-mark Bolt wiring method P Connector plug connection method 1 R Relay contact + SSR drive output 2 2 4 24VAC 50/60Hz, 24-48VDC 100-240VAC 50/60Hz 2 Alarm1 + Alarm2 output M C H B DIN W48 × H48mm DIN W72 × H72mm DIN W48 × H96mm DIN W96 × H96mm 4 9999 (4 digit) S Dual display type, set by touch switch T Temperature controller Input Sensor and Temperature Range Input sensor K(CA) J(IC) Thermocouple L(IC) T(CC) R(PR) S(PR) DPt100Ω RTD Cu50Ω Display KCaH KCaL JIcH JIcL LIcH LIcL TCcH TCcL RPR SPR DPtH DPtL CUsH CUsL Temperature range(ºC) -50 to 1200 -50.0 to 999.9 -30 to 800 -30.0 to 800.0 -40 to 800 -40.0 to 800.0 -50 to 400 -50.0 to 400.0 0 to 1700 0 to 1700 -100 to 400 -100.0 to 400.0 -50 to 200 -50.0 to 200.0 44.8 67.5 45 91.5 Terminal cover(sold separately) RMA-COVER(72×72mm) 70 68.5 41.5 5 18 TS4C, TS4H, TS4B Series 9.8 13 31 20 D 48.6 45 B TS4M Series A 22 Panel cut-out 22.5 C RLA-COVER(96×96mm ) RHA-COVER(48×96mm) A B C TS4M Min. 65 TS4C Min. 90 12 TS4H 23.9 TS4B D Min. 65 45 0.6 0 45 00.6 Min. 90 68 00.7 68 00.7 Min. 65 Min. 115 45 00.6 92 00.8 Min. 115 Min. 115 92 00.8 92 00.8 91.5 Size Series 3 94 13 55 4 47.2 46 15 21 3 64 91.5 64.5 RSA-COVER(48×48mm) 56 Parameter Groups Connections TS4M TS4C 1 RelayOUT: 250VAC3A1a RTD TC 2 B' 3 B 5 SENSOR 7 SSROUT: 12VDC±2V 20mAMax. 4 A 6 11 ALM2OUT: 250VAC1A1a ALM1OUT: 8 250VAC1A1a 13 1. All Parameter SSROUT: 12VDC±2V 20㎃Max. RelayOUT: 250VAC3A 1a 10 SOURCE: 100-240VAC 5VA50/60㎐, ※1 SOURCE: 100-240VAC 5VA50/60㎐, 24VAC5VA50/60㎐, 24-48VDC3W TS4M- AL2OUT: 250VAC 1A1a 4 , SV setting 10 11 5 12 6 13 7 14 AL2 OUT 250VAC 1A 1a B' B A SOURCE※2 ※TS4 Series has selectable control output; Relay output, and SSR drive output. AC/DC voltage type does not have SSRP function. ※1: 12VDC±2V 20mA Max. ※2: AC voltage type: 100-240VAC 5VA 50/60Hz AC/DC voltage type: 24VAC 5VA 50/60Hz 24-48VDC 3W ※Use crimp terminals or teminals of size specified below. (unit: mm) a c <Crimp terminal> Terminal a number 6 b 1 to 8 b a b a b <Round> c Max. 1.7 Max. 3.7 9 to 11 6 to 8 Max. 2.1 Max. 4.2 12 to 14 6 to 8 Max. 1.5 Max. 3.5 <Forked> Min. 3.0 Max.5.8 TC Run mode Please any key among 9 B' RTD TC B , 2sec. , Parameter 1group PAR2 AL1 alarm termerature Input sensor Temperature unit Input correction Input digital filter IN-Tㅑㅜ UNIT IN-Bㅑㅜ MAvF Control type Control output operation SV highlimit value SV low-limit value C-MD O-FT H-SV L-SV Control output type SSR drive output method※1 Control cycle AL1 alarm operation mode AL1 A AL2 SENSOR Auto tunung AT Proportional band P I RelayOUT: 250VAC3A 1a ※1 SOURCE: 100-240VAC 5VA50/60㎐, 24VAC5VA50/60㎐, 24-48VDC3W 1 2 3 4 5 6 7 Parameter 2group PAR1 Integral time SSROUT: 12VDC±2V 20㎃Max. 4sec. AL2 alarm termerature AL1 OUT 250VAC 1A 1a Relay OUT 250VAC 3A 1a Min. 3.0 Max.5.8 AL1OUT: 250VAC 1A1a 2 TS4H/B -P SSR OUT※1 a b 8 1 3 9 RTD Temperature range(℉) -58 to 2192 -58.0 to 999.9 -22 to 1472 -22.0 to 999.9 -40 to 1472 -40 to 999.9 -58 to 752 -58.0 to 752.0 32 to 3092 32 to 3092 -148 to 752 -148.0 to 752.0 -58 to 392 -58.0 to 392.0 6 86 96 64.5 Bracket key Used when entering into parameter groups, returning to RUN mode, moving parameter, and saving setting values. 6. Adjustment Used when entering into set value change mode, digit moving and digit up/down. 7. Digital input key keys for 3 sec. to operate the set function Press (RUN/STOP, alarm output reset, auto tuning) in digital input key [DI-T]. 8. Temperature unit (ºC/℉) indicator It shows current temperature unit. 1: Only for TS4M model. 2: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle control, phase control) is available to select. ※The above specifications are subject to change and some models may be discontinued without notice. ※Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, homepage). 6 48.4 At room temperature(23ºC±5ºC) - Below 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit - Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit - Termocouple L (IC), RTD Cu50Ω is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit Out of room temperature range - Below 200ºC of thermocouple R(PR), S(PR) is (PV ±1.0% or ±6ºC, select the higher one) ±1 digit - Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±5ºC, select the higher one) ±1 digit - Thermocouple L(IC), RTD Cu50Ω is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit For TS4M- -P, add ±1℃ by accuracy standard. 2: The weight includes packaging. The weight in parentheses is for unit only. Environment resistance is rated at no freezing or condensation. Ordering Information T TS4B Series 48 1: Unit Description 64.5 86 1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in fire, personal injury, or economic loss. 2. Install on a device panel to use. Failure to follow this instruction may result in electric shock or fire. 3. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in electric shock or fire. 4. Check 'Connections' before wiring. Failure to follow this instruction may result in fire. 5. Do not disassemble or modify the unit. Failure to follow this instruction may result in electric shock or fire. 6 91.5 Warning 72 11.5 13 ※The symbols used on the product and instruction manual represent the following symbol represents caution due to special circumstances in which hazards may occur. TS4H Series 3.3 ※Safety considerations are categorized as follows. Warning Failure to follow these instructions may result in serious injury or death. Caution Failure to follow these instructions may result in personal injury or product damage. 56 1.7 4 ※Please observe all safety considerations for safe and proper product operation to avoid hazards. 6 37.5 40.5 Safety Considerations 48 60 16 Thank you for choosing our product. Please read the following safety considerations before use. 6 TS4C Series 96 INSTRUCTION MANUAL 48 36 TS4 SERIES (unit: mm) TS4M - -P TS4M Series 44.9 DUAL INDICATOR TEMPERATURE CONTROLLER Series TS4M TS4C TS4H TS4B AC Power 100-240VACᜠ 50/60Hz Power supply AC/DC Power 24VACᜠ 50/60Hz, 24-48VDCᜡ Allowable voltage range 90 to 110% of rated voltage AC Power Max. 5VA(100-240VAC 50/60Hz) Power consumption AC/DC Power Max. 5V(24VAC 50/60Hz), Max. 3W(24-48VDC) Display method 7 segment (PV: red, SV: green), other display part(green, red) LED method 7.0×15.0mm 9.5×20.0mm 7.0×14.6mm 11.0×22.0mm Character PV(W×H) size SV(W×H) 5.0×9.5mm 7.5×15.0mm 6.0×12.0mm 7.0×14.0mm RTD DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire) Input type TC K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) RTD At room temperature(23ºC ± 5ºC): (PV ± 0.5% or ±1ºC, select the higher one) ± 1 digit Display accuracy Out of room temperature range: (PV± 0.5% or ±2ºC, select the higher one)± 1digit 1 TC For TS4M- -P, add ±1℃ by accuracy standard. Relay 250VACᜠ 3A 1a Control output SSR 12VDCᜡ±2V 20mA Max. Alarm output AL1, AL2 Relay: 250VACᜠ 1A 1a Control method ON/OFF control, P, PI, PD, PID control Hysteresis 1 to 100℃/℉ (0.1 to 50.0℃/℉) Proportional band(P) 0.1 to 999.9ºC/℉ Integral time(I) 0 to 9999 sec. Derivative time(D) 0 to 9999 sec. Control period(T) 0.5 to 120.0 sec. Manual reset 0.0 to 100.0% Sampling period 100ms 2000VAC 50/60Hz 1min.(between input terminal and power terminal) Dielectric AC power strength AC/DC power 1000VAC 50/60Hz 1min.(between input terminal and power terminal) Vibration 0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times Relay life OUT: Over 200,000 times(250VAC 3A resistive load) cycle Electrical AL1/2: Over 300,000 times(250VAC 1A resistive load) Insulation resistance Min. 100MΩ(at 500VDC megger) Square-wave noise by noise simulator(pulse width 1㎲) ±2KV R-phase and S-phase Noise Memory retention Approx. 10 years (when using non-volatile semiconductor memory type) Environ Ambient temp. -10 to 50ºC, Storage: -20 to 60ºC -ment Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH Double insulation or reinforced insulation (mark: , dielectric strength between Insulation type the measuring input part and the power part : AC power 2kV, AC/DC power 1kV) Approval Approx. 147g Approx. 203g Approx. 194g Approx. 275g Weight 2 (approx. 100g) (approx. 133g) (approx. 124g) (approx. 179g) 8 AL1OUT: 250VAC 1A1a 9 AL2OUT: 250VAC 1A1a TC RTD B' B A SENSOR 10 11 12 Derivative time D OUT SSrM T AL-1 LBA detection band LBA monitoring time Alarm output hysteresis AL2 alarm operation mode LBaㅠㅠB LBaT AHYS AL-2 Manual reset REST Digital input Control output MV in case key of input break error Hysteresis DI-K ErMV Parameter lock LOC HYS 13 14 3sec. 3sec. Press key over 3 sec in any parameter group, it saves the set value and returns to RUN mode. (Exception: Press key once in SV setting group, it returns to RUN mode). If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter is not be saved. Press key again within 1 sec. after returning to RUN mode, it advances of the first parameter of previous parameter group. Press key to move next parameter. Parameter marked in might not be displayed depending on other parameter settings. Set parameter as 'Parameter 2 group → Parameter 1 group → Setting group of set value' order considering parameter relation of each setting group. 1: It is not displayed for AC/DC power model ( TS4 -22R). 2. Parameter 2group or Parameter Display Input sensor IN-T Temperature unit UNIT Input correction IN-B Input digital filter MAvF SV low-limit value L-SV SV high-limit value H-SV Control output operation O-FT Control type ㅊC-MD Control output type OUT SSR drive output ㄴㄴㄴSSrM method Control cycle AL1 alarm operation mode ㅅT key: Moves parameter and saves the set, key: Changes the set Description Setting range: Refer to ' Input Sensor And Temperature Range'. If changing input sensor, SV, IN-B, H-SV, L-SV, AL1, AL2, LBaT, LBaB, AHYS parameter values are initialized. ?C ?F If changing temperature unit, SV, IN-B, H-SV, L-SV, AL1, AL2, LBaT, LBaB, AHYS parameter values are initialized. Setting range ● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH:-999 to 999℃/℉ ● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: -199.9 to 999.9℃/℉ Setting range: 0.1 to 120.0 sec. Setting range: Within the rated temperature range by input sensor[ L-SV (H-SV-1digit)] When changing SV lower limit value, if SV ㅣL-SV, SV is initialized as L-SV. In case of changing input sensor type[IN-T], it changes automatically as min. value of the changed input sensor. Setting range: Within the rated temperature range by input sensor[ H-SV (L-SV+1digit)] When changing SV higher limit value, if SV H-SV, SV is initialized as H-SV. In case of changing input sensor type [IN-T], it changes automatically as max. value of the changed input sensor. COOL제어 HEAT When changing control output operation, ErMV is initialized. PID ONOF ㅈ어제ㅈㄻㅇㄴㄻㅇ When changing control type, ErMV is initialized (control output MV is below 100%) and DI-T turns OFF automatically. SSR RLY CYCL PHAS STND It is displayed when selecting control output [OUT] as [SSR]. It is not displayed for AC/DC power model (TS4 -22R). Setting range: 0.5 to120.0 sec. In case of Relay drive output [RLY] of control output [OUT], it is set as 20.0 sec. In case of SSR drive output [SSR] of that, it is set as 2.0 sec. T is not displayed when SSR drive output [SSR.M] method is set as CYCL, PHAS. 경보AM)_ AL-1 AM!A AM@A AM^A SBaB AM!A AL2 alarm operation mode AL-2 Alarm output hysteresis ㅁAHYS LBA monitoring time LBaT LBA monitoring range Digital input key LBaB DI-K Control output MV in case of input break error ErMV Parameter lock LOC 3. Parameter 1 group Parameter Display AL1 alarm temp. AL1 AL2 alarm temp. AL2 Auto tuning AT Proportional band ㅖP Integral time I Derivative time D Manual reset REST Hysteresis HYS key: Moves digit, AM!B AM!C SBaA SBaA AM!D LBaA LBaB AM!E L ㅣ BaA AM!F For more details refer to Functions 6. Alarm. Black: Flashes, Gray: Fixed When changing AL1, AL2 alarm operation mode, AL1, AL2 alarm temperature value are initialized. Setting range: Refer to Functions 4. Alarm output hysteresis. HYS is not displayed when AL1, AL2 alarm operation mode [AL-1, A AL-2] is set as [AM0._, SBa , LBa ]. Setting range: 0 to 9999 sec. '0' is set, loop break alarm function is OFF. BaT is displayed when AL1, AL2 alarm operation mode [AL-1, L AL-2] is set as LBa . Setting range: 0 to 999(0.0 to 999.9) , '0' is set, loop break alarm function is OFF. BaB is displayed when AL1, AL2 alarm operation mode [AL-1, L AL-2] is set as LBa and LBaT is not '0'. 경보STOP AlRE AT OFF Press keys for 3 sec. and it executes the set function. For more information, refer to Functions 5. Digital input key. When control type [C-MD] is ONOF, AT is not displayed. Setting range 0.0 to 100.0% O nly 0.0, 100% are displayed when control type [C-MD] is set as ONOF. When changing PID control to ON/OFF control, if MV is below 100.0%, it is initialized as 0.0%. OFF LOC1 LOC2 LOC3 LOC1: Locks parameter 2 group, LOC2: Locks parameter 1, 2 group LOC3: Locks parameter 1, 2 group and SV setting Parameter setting values are still possible to check when parameter lock is set. Functions 1. Auto tuning [AT] Auto tuning measures the control subject’s thermal characteristics and thermal response rate, and then determines the necessary PID time constant. (When control type[C-MD] is set as PID, it is displayed.) Application of the PID time constant realizes fast response and high precision temperature control. If error [OPEN] occurs during auto tuning, it stops this operation automatically. To stop auto tuning, change the set as [OFF]. (It maintains P, I, D values of before auto tuning.) 2. Hysteresis [HYS] Heating operation In case of ON/OFF control, set between ON and OFF intervals ON OFF as hysteresis. (When control type [C-MD] is set as ONOF, it is displayed.) If hysteresis is too small, it may cause control Hysteresis output hunting (takeoff, chattering) by external noise, etc. [HYS] Temperature 3. SSR drive output selection(SSRP function) [SSrM] SV ● SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive output. ● Realizing high accuracy and cost effective temperature control as linear output(cycle control and phase control). ● Select one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at [SSrM] parameter of parameter 2 group. For cycle control, connect zero cross turn-on SSR or random turn-on SSR. For phase control, connect random turn-on SSR. Temperature controller (TS4 series) SSR drive output (12VDC) 4. SV setting You can set the temperature to control with keys. Setting range is within SV lower limit value [L-SV] to SV higher limit value [H-SV]. E.g.) In case of changing set temperature from 210ºC to 250ºC 1)Standard ON/OFF control mode [STND] A mode to control the load in the same way as Relay output type. (ON: output level 100%, OFF: output level 0%) Press any key among , Change SV by , , , , once. OUT ON OFF ON AM! Deviation high-limit alarm AM@ Deviation low-limit alarm AM# Deviation high/lowlimit alarm AM$ Deviation high/lowlimit reserve alarm 50Cycle 50Cycle 50% 80% 3)Phase control mode [ PHAS] A mode to control the load by controlling the phase within AC half cycle. Serial control is available. RANDOM Turn-on type SSR must be used for this mode. AC OUT 10% 50% 4. Alarm output hysteresis [AHYS] It displays alarm output ON and OFF interval and hysteresis is applied to both AL1 OUT and AL2 OUT. KCaH, JIcH, ㅣLIcH, TCcH, RPR, SPR, DPtH, ㅊCUsH: 1 to 100 KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: 0.1 to 50.0 E.g.)AL1 alarm operation[AL-1]: AM#A Temp. AL1 alarm operation[AL1]: 10ºC Alarm output hysteresis[AHYS]: 4 210ºC H SV 100℃ PV 110℃ OFF ON H OFF PV 90℃ SV 100℃ ON PV 90℃ High deviation: Set as 10℃ ON H SV 100℃ High deviation: Set as -10℃ If deviation between PV and SV as low-limit is higher than set value of deviation temperature, Lower deviation: Set as -10℃ the alarm output will be ON. ON Lower deviation: Set as 10℃ SV 100℃ H OFF PV 110℃ H OFF H PV 90℃ SV 100℃ PV 110℃ ON If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be ON. ON High/Lower deviation: Set as 10℃ H OFF PV 90℃ ON H SV 100℃ PV 110℃ OFF If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be OFF. High/Lower deviation: Set as 10℃ OFF H OFF ON PV 90℃ SV 100℃ H OFF Absolute-value Alarm: Set as 90℃ ON PV 90℃ SV 100℃ Absolute-value Alarm: Set as 90℃ If deviation between PV and SV as high-limit is higher than set value of deviation temperature, the alarm output will be ON. SV 100℃ H ON PV 110℃ Absolute-value Alarm: Set as 110℃ ON SV 100℃ H PV 110℃ If PV is higher than the absolute value, the output will be ON. Absolute-value Alarm: Set as 110℃ If PV is lower than the absolute value, the output will be ON. ON OFF LBa Loop break alarm It will be ON when it detects loop break. 206 190 Description ㅁㅆㅁㅁㅁㅁAM .A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF. AM ㅁ.ㅜㅜㅠㅠㅠㄱㅠㅠㅠㅁB Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status. (Alarm output HOLD) AM .C Standby sequence 1 First alarm condition is ignored and from second alarm condition, standard alarm operates. When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition, standard alarm operates. AM .D Alarm latch If it is an alarm condition, it operates both alarm latch and standby sequence. When and standby power is supplied and it is an alarm condition, this first alarm condition is ignored and sequence 1 from the second alarm condition, alarm latch operates. AM .E Standby sequence 2 First alarm condition is ignored and from second alarm condition, standard alarm operates. When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON. After clearing alarm condition, standard alarm operates. AM .F Basic operation is same as alarm latch and standby sequence1. It operates not only by Alarm latch power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied and standby standby sequence and if it is alarm condition, alarm output does not turn ON. After sequence 2 clearing alarm condition, alarm latch operates. Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set temperature, alarm temperature (AL1, AL2) or alarm operation (AL-1, AL-2), switching STOP mode to RUN mode. 3)Sensor break alarm The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between standard alarm [SBaA] or alarm latch [SBaB]. 4)Loop break alarm(LBA) It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling control), when control output MV is 100%(0% for cooling control) and PV is not increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], or when control output MV is 0%(100% for cooling control) and PV is not decreased below than LBA detection band [LBaB] during LBA monitoring time [LBaT], alarm output turns ON. Time 194 OFF It does not use digital input key function. STOP Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm) except Control output operates as setting. Hold the digital input keys for 3 sec. to restart. Digital input key t t t t (t: over 3 sec.) keys AlRE ④Check SV AT STOP RUN STOP RUN Clears alarm output by force. (only when alarm option is alarm latch, or alarm latch and standby sequence 1/2 .) This function is applied when present value is out of alarm operation range but alarm output is ON. Alarm operates normally right after clearing alarm. Starts/Stops auto-tuning. This function is same as auto-tuning[AT] of parameter 1 group. (You can start auto-tuning [AT] of parameter 1 group and stop it by digital input key.) ※This parameter AT appears only when control method [C-MD] parameter 2 group is set as PID. When control method [C-MD] parameter 2 group is set as ONOF, this parameter is changed as OFF. Description HHHH Flashes if measured sensor input is higher than temperature range. When input is within the rated temperature range, this display Flashes if mesured sensor input is lower than temperature range disappears. LLLL Troubleshooting Flashes if input sensor is disconnected or sensor is not connected. Check input sensor state. Factory Default Parameter Default 0 Parameter Default AL1 1250 AL2 1250 Parameter Default AT OFF P 01)0 Parameter Default I 0000 D 0000 Parameter Default REST 05)0 HYS 002 3. Parameter 2 group ※ H: Alarm output hysteresis[AHYS] 2)Alarm opetion Time 210 Display OPEN 2. Parameter 1 group It will be ON when it detects sensor disconnection. - ·Manual reset [REST] by control result 7. Manual reset[REST] When selecting P/PD control mode, certain temperature Set below 50.0 as reset value difference exists even after PV reaches stable status because heater's rising and falling time is inconsistent due to thermal Offset SV characteristics of controlled objects, such as heat capacity, Offset heater capacity. This temperature difference is called offset and manual reset [REST] function is to set/correct offset. Set over 50.0 as reset value When PV and SV are equal, reset value is 50.0%. After control is stable, PV is lower than SV, reset value is over 50.0% or PV Measured value is higher than SV, reset value is below 50.0%. 8. Input correction[IN-B] Controller itself does not have errors but there may be error by external input temperature sensor. This function is for correcting this error. E.g.) If actual temperature is 80ºC but controller displays 78ºC, set input correction value [IN-B] as '002' and controller displays 80ºC. As the result of input correction, if current temperature value (PV) is over each temperature range of input sensor, it displays 'HHHH' or 'LLLL'. 9. Input digital filte [MAvF] If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV and stable control is impossible. Therefore, digital filter function stabilizes current temperature value. For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4 sec and displays this values. Current temperature may be different by actual input value. 10. Error 1. SV setting OFF 3sec.) [DI-K] RUN Auto-tuning OFF Operation ③Completes SV setting Clear alarm Absolute value low limit alarm Description No alarm output PV AHYS: 4 190ºC RUN/STOP Absolute value high limit alarm Alarm operation - AHYS: 4 SV 200ºC AL1 OUT Alarm option Sensor break alarm AC OUT Set both alarm operation and alarm option by combining. Alarm outputs are two and each one operates individually. When the current temperature is out of alarm range, alarm clears automatically. If alarm option is alarm latch or alarm latch and standby sequence 1/2, press digital input key( + 3 sec., digital input key[DI-K] of parameter 2 group set as AlRE), or turn OFF the power and turn ON to clear alarm. SBa OFF 2)Cycle control mode [CYCL] A mode to control the load by repeating output ON / OFF according to the rate of output within setting cycle. Having improved ON / OFF noise feature by Zero Cross type. Parameter 5. Parameter reset Reset all parameters as factory default. Hold the front + + keys for 5 sec., to enter parameter reset [INIT] parameter. Select 'YES' and all parameters are reset as factory default. Select ‘NO’ and previous settings are maintained. If setting parameter lock [LOC] or processing auto-tuning, parameter reset is unavailable. Name - Option Name AC OFF ②SV setting mode Mode AM)_ AM^ When selecting phase or cycle control mode, the power supply for load and temperature controller must be the same. In case of selecting PID control type and phase [PHAS] / cycle [PHAS] control output modes, control cycle [T] is not allowed to set. For AC/DC power model ( TS -22R), this parameter is not displayed and it is available only standard control by relay or SSR. AM!A 1)Alarm operation Load Power 100-240VAC 50/60Hz 5. Digital input key ( + ①RUN mode SSR Module Alarm operation AM% key: Moves parameter and saves the set, key: Moves digit, or key: Changes the set Description Setting range: Deviation alarm(-F.S to F.S), Absolute value alarm(temperature range) In case alarm operation mode [AL-1, AL-2] of Parameter 2 group AMㅡ)_/ SBa / LBA , no parameters is displayed. ON Front AT indicator flashes during auto tuning operation. OFF Setting range: 0.1 to 999.9 Setting range: 0 to 9999 sec. Integral operation is OFF when set value is "0". Setting range: 0 to 9999 sec. Derivative operation is OFF when set value is "0". Setting range: 0.0 to 100.0%/ It is displayed in P/PD control. Setting range ● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH: 1 to 100 ● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: 0.1 to 50.0 It is displayed when control type [C-MD] of parameter 2 group is set ONOF. 6. Alarm Start control When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT]. to to The status of changing control output MV (LBA monitoring time is reset.) to When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB] during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time. to Control output MV is 0% and loop break alarm (LBA) turns and maintains ON. to The status of changing control output MV (LBA monitoring time is reset.) to When control output MV is 100% and PV is not increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time. to When control output MV is 100% and PV is increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time. to The status of changing control output MV (LBA monitoring time is reset.) hen executing auto-tuning, LBA detection band[LBaB] and LBA monitoring time are automatically set W based on auto tuning value. When alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA) [LBa ], LBA detection band [LBaB] and LBA monitoring time [LBaT] parameter is displayed. Parameter Default Parameter Default Parameter Default Parameter Default IN-T KCaH H-SV 1200 T 02)0 LBaB 0002 UNIT ?C O-FT HEAT AL-1 AMiA DI-K STOP IN-B 0000 C-MD PID LA-2 Am@A ErMV 00)0 MAvF 00)1 OUT RLY AHYS 001 LOC OFF L-SV -050 SSrM STND LBaT 0000 The AC/DC voltage models do not have SSR drive output method[SSrM]. In case of control output [ OUT] , if set as SSR, it supports only ON/OFF output. Installation TS4M(48×48mm) Series Other Series Insert product into a panel, fasten bracket by pushing with tools as shown above. Cautions during Use 1. Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents. 2. Check the polarity of the terminals before wiring the temperature sensor. For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length. For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire. 3. Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise. 4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power. 5. Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller. 6. When changing the input sensor, turn off the power first before changing. After changing the input sensor, modify the value of the corresponding parameter. 7. 24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device. 8. Make a required space around the unit for radiation of heat. For accurate temperature measurement, warm up the unit over 20 min after turning on the power. 9. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power. 10. Do not wire to terminals which are not used. 11. This unit may be used in the following environments. ①Indoors (in the environment condition rated in 'Specifications') ②Altitude max. 2,000m ③Pollution degree 2 ④Installation category II Major Products Photoelectric Sensors Temperature Controllers Fiber Optic Sensors Temperature/Humidity Transducers Door Sensors SSRs/Power Controllers Door Side Sensors Counters Area Sensors Timers Proximity Sensors Panel Meters Pressure Sensors Tachometer/Pulse (Rate) Meters Rotary Encoders Display Units Connector/Sockets Sensor Controllers Switching Mode Power Supplies Control Switches/Lamps/Buzzers I/O Terminal Blocks & Cables Stepper Motors/Drivers/Motion Controllers Graphic/Logic Panels Field Network Devices Laser Marking System (Fiber, Co₂, Nd: YAG) Laser Welding/Cutting System ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Dual-indicator display
- Touch switch setting
- Various control methods
- Multiple input sensors
- Alarm outputs
Frequently asked questions
The Autonics TS4M supports ON/OFF, P, PI, PD, and PID control methods.
The TS4M can accept thermocouples (K, J, L, T, R, S) and RTDs (Pt100Ω, Cu50Ω).
The temperature range is determined by the type of sensor you use. Refer to the 'Input Sensor and Temperature Range' table in the instruction manual.