- Industrial & lab equipment
- Electrical equipment & supplies
- GESTRA
- TRS 5-6
- Installation Guide
- 24 Pages
GESTRA TRS 5-6 Installation Instructions Manual
GESTRA TRS 5-6 is a high-integrity temperature switch used for safety monitoring in steam boilers and hot-water systems. It features a self-monitoring logic unit and two channels to ensure reliable operation. This device is designed for use with resistance thermometers TRG 5-53, TRG 5-54, TRG 5-55 or TRG 5-57 and provides fail-safe protection against a first fault. The TRS 5-6 can be mounted on a supporting rail or a mounting panel and is easy to install and wire.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
24
GESTRA Steam Systems TRS 5-6 EN English Installation Instructions 810378-05 Temperature Switch TRS 5-6 Contents Page Important Notes Usage for the intended purpose...............................................................................................................4 Safety note..............................................................................................................................................4 Danger....................................................................................................................................................4 Attention..................................................................................................................................................4 LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)........................................................4 ATEX (Atmosphère Explosible)..................................................................................................................4 Note........................................................................................................................................................4 Explanatory Notes Scope of supply.......................................................................................................................................5 Description..............................................................................................................................................5 Function..................................................................................................................................................5 Design.....................................................................................................................................................5 Technical Data TRS 5-6...................................................................................................................................................6 Corrosion resistance................................................................................................................................7 Name plate/ marking...............................................................................................................................7 Dimensions..............................................................................................................................................8 Design TRS 5-6...................................................................................................................................................9 Key........................................................................................................................................................11 Functional Elements TRS 5-6.................................................................................................................................................10 Key........................................................................................................................................................11 Installation TRS 5-6.................................................................................................................................................12 Attention................................................................................................................................................12 Tools......................................................................................................................................................12 Key........................................................................................................................................................12 Examples of Installation.........................................................................................................................13 Contents - continued Page Wiring TRS 5-6.................................................................................................................................................14 Attention................................................................................................................................................14 Note......................................................................................................................................................14 Tools......................................................................................................................................................14 Key........................................................................................................................................................14 Wiring diagram......................................................................................................................................15 Basic Settings Adjusting temperature limit....................................................................................................................16 Example 1 ............................................................................................................................................16 Example 2 ............................................................................................................................................16 Example 3 ............................................................................................................................................16 Tools . ...................................................................................................................................................16 Code switch settings ............................................................................................................................17 Commissioning Check wiring.........................................................................................................................................18 Apply mains voltage..............................................................................................................................18 Performance test TRS 5-6.................................................................................................................................................18 Operation Temperature limiter, safety temperature switching controller.................................................................18 Note......................................................................................................................................................18 Operation Malfunctions Danger..................................................................................................................................................19 Faultfinding list for troubleshooting.......................................................................................................19 Decommissioning Danger..................................................................................................................................................20 Disposal................................................................................................................................................20 Annex Note on the Declaration of Conformity / Declaration by the Manufacturer . .......................................21 Important Notes Usage for the intended purpose The temperature switch TRS 5-6 serves as safety device in plants requiring official approval and is used in conjunction with resistance thermometers TRG 5-53, TRG 5-54, TRG 5-55 and TRG 5-57. Use the temperature switch only for signalling temperature limits. Safety note The equipment must only be installed and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who – through adequate training – have achieved a recognised level of competence. Danger The terminal strip of the equipment is live during operation. This presents the danger of electric shock. Cut off power supply before mounting or removing the terminal strips and the housing cover. Attention The name plate specifies the technical features of the equipment. Note that any piece of equipment without its specific name plate must neither be commissioned nor operated. LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility) The equipment meets the requirements of the Low Voltage Directive 2006/95/EC and the EMC Directive 2004/108/EC. ATEX (Atmosphère Explosible) According to the European Directive 94/9/EC the equipment must not be used in potentially explosive areas. Note The temperature sensors TRG 5-53, TRG 5-54, TRG 5-55 and TRG 5-57 are simple items of electrical equipment as defined in EN 60079-11 section 5.7. According to the European Directive 94/9/EC the equipment must be equipped with approved Zener barriers if used in potentially explosive areas. Applicable in Ex zones 1, 2 (1999/92 EC). The equipment does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate document. Explanantory Notes Scope of supply TRS 5-6 1 Temperature switch TRS 5-6 1 Installation manual Description High-integrity self-monitoring temperature switch with periodic self-checking routine to be used in conjunction with a resistance thermometer type TRG 5-53, TRG 5-54, TRG 5-55 or TRG 5-57. The equipment operates as a safety temperature monitor, or in combination with an external lock-out in accordance with VDE 0116 as a safety temperature limiter. An alarm is given as soon as the tempera­ ture exceeds a preset limit. Application in steam boilers and pressurized hot-water plants operating without constant supervision (TRD 604) as well as any other kind of heat generating units. Function The temperature switch type TRS 5-6 is a two channel unit provided with an automatic periodic selfchecking logic unit, in accordance with DIN 3440/VDE 0116 (regulations on protection circuits for firing equipment of furnaces). The two channels are designed to monitor the operation of each other. The integrity of the resistance thermometer is continuously monitored by the TRS 5-6. Unless it finds a fault, this internal test does not interfere with the output contacts of the temperature switch and therefore the plant operation is not interrupted. A manual test push button is also provided. When the push button “Test I” is pressed, it simulates a fault in the resistance thermometer There is also a toggle switch “Test II / Inspection” for checking the function of the self-checking circuitry. The output contact relays of the temperature switch are of the normally close type and will therefore signal alarm condition in the event of a mains failure. The temperature switch can signal the following three operating conditions: n Normal operation (temperature within permissible range) n Alarm (limit temperature exceeded) n Alarm (fault in temperature switch or resistance thermometer) A green LED indicates Power ON. Two red LEDs are illuminated if the temperature limit is exceeded or if there is a system malfunction. The failure of one channel (loss of redundancy) is signalled by the lighting-up of one red LED. The combination of TRG 5-... and TRS 5-6 provides fail-safe protection against a first fault, i.e. the system will still continue to provide the safety function even after the occurrence of a first fault. Design TRS 5-6 Plug-in unit in plastic case for installation in contol cabinets. The terminals in the case are accessible after loosening two screws and unplugging the unit from its base. Thanks to the code plug the equipment cannot be connected inadvertently to wrong GESTRA equipment. The equipment may be clipped onto a 35 mm supporting rail or screwed into position on a mounting panel. Technical Data TRS 5-6 Type approval DIN · STW (STB) · 985 07S Input 3 terminals for the connection of one resistance thermometer (Pt 100): TRG 5-5..., PN 40-160, Tmax 400 °C – 540 °C Output 2 volt-free relay contacts. Max. contact rating with switching voltages of 24 V, 115 V and 230 V AC: 4 A resistive, 0.75 A inductive at cos ϕ 0.5. Max. contact rating with a switching voltage of 24 V DC: 4 A. Contact material: silver, hard-gold plated. Temperature range 30 °C to 540 °C, adjustable in steps of 2 °C via code switch. Switching hysteresis –3 °C Indicators and adjustors 2 LED “Alarm”, 1 LED “Power”, 1 button “Test 1”, 1 toggle switch “Test 2 / Inspection”, 8 LEDs and 1 code switch for setting the temperature limit Mains supply 230 V +/– 10 %, 50/60 Hz. Special voltages 115 V +/– 10 %, 50/60 Hz or 24 V +/– 10 %, 50/60 Hz. Power consumption 5 VA Protection TRS 5-6 b: IP 20 to DIN EN 60529 Admissible ambient temperature TRS 5-6 b: 0 °C to 55 °C Body materials TRS 5-6 b: Base ABS, black. Cover: Polystyrol, highly shock resistant, stone grey. Front panel: Aluminium. Weight TRS 5-6 b: approx. 1.0 kg Approvals EC prototype approval TÜV type approval / DIN CERTCO PED Pressure Equipment Directive 97/23/EC, EN 12952-11, EN 12953-09: Requirements made on limiting equipment for boilers. VdTÜV Bulletin “Wasserstand 100” (= Water Level 100) / DIN EN 14597 Requirements made on temperature conrollers, temperature monitors and temperature limiters. DIN registration number STW (STB) 985 07 S. VdTÜV Bulletin 985. Technical Data - continued Corrosion resistance If the unit is used for the intended purpose, its safety is not impaired by corrosion. Name plate/ marking Equipment designation Mains supply Protection External fuse Fig. 1 Technical Data - continued - 158 95 Dimensions 106 37.5 75 Fig. 2 Fig. 3 7 Design TRS 5-6 7 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 6 Fig. 4 2 5 Fig. 5 4 1 TRS 5-6 °C °C 30 T0 2 T1 4 T2 8 T3 16 T4 32 T5 64 T6 128 T7 2 min Inspection Test II Alarm Test I °C MAX 256 T8 MADE BY GESTRA Fig. 6 1 Functional Elements TRS 5-6 MAX 55 C 9 0 ! § ON 1 2 3 4 5 6 7 8 " Fig. 7 10 $ % MAX 95% IP 20 Design / Functional Elements Key 1 Cover screws 2 Base 3 Upper part of the housing 4 Mounting clip 5 Cable entry (flexible) 6 Cable entry (housing) 7 Fixing holes d = 4.3 mm 8 Supporting rail TS 35 x 15 DIN EN 50022 9 Toggle switch “TEST II / INSPECTION” 0 LED “Alarm” ! Button “TEST I” " LED “Operation” § LED “MAX Temperature” $ Code switch, 8 poles 11 Installation TRS 5-6 On supporting rail 1. Clip temperature switch onto supporting rail. 2. Loosen cover screws 1 and detach cover 3 from its base 2. 3. Select cable entry 5 and remove corresponding seal. On mounting panel 1. Loosen cover screws 1 and detach cover 3 from its base2. 2. Unscrew mounting clip 4. 3. Drill hole 7 marked in the base to ∅ 4.3 mm. 4. Select cable entry 5 / 6 and remove corresponding seal. 5. Fix base with two M4 screws onto mounting panel. Attention To provide sufficient ventilation, ensure a minimum spacing of 20 mm between ­adjacent units. Tools Screwdriver (5.5 / 100) Key 1 Cover screws 2 Base 3 Upper part of the housing 4 Mounting clip 5 Cable entry (flexible) 6 Cable entry (housing) 7 Fixing holes d = 4.3 mm 8 Supporting rail TS 35 x 15 DIN EN 50022 12 Installation - continued Examples of Installation 4 2 C 5 6 3 6 TRS 5-6 °C °C 30 T0 2 T1 4 T2 8 T3 16 T4 32 T5 64 T6 128 T7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 8 2 min Inspection Test II Alarm Test I °C MAX 256 T8 MADE BY GESTRA MAX 55 C 1 7 Fig. 8 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 % MAX 95% IP 20 Fig. 9 13 Wiring TRS 5-6 Note that screened four-core cable, e. g IIY(St)Y 2 x 2 x 0.8 or LIYCY 4 x 0.5 mm2 is required. Attention To protect the switching contacts fuse circuit with T 2.5 A or according to TRD regulations (1A for 72h operation). The screen must not make any other electrical contact. Note Connect screen only to terminal 13 of the temperature switch. The loop resistance must be below 10 Ω. The rated voltage is indicated on the name plate. When switching off inductive loads, voltage spikes are produced that may impair the operation of control and measuring systems. Inductive loads should be provided with commercial arc suppressor RC combinations, e.g. 0.1 µF/100 W. Tools Screwdriver for slotted screws, size 2.5 completely insulated according to DIN VDE 068001 Key % External wire link & Burner-protection circuit of the installation / Mains ( Terminal, red ) Terminal, red = Terminal, black a Terminal, black b Terminal, red c Terminal, red d Terminal, yellow 14 Electrical Connection - continued Wiring diagram TRS 5-6 % °CMAX L N / & & Pt 100 IEC 751 TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57 Fig. 10 = ( 3 6 5 ) d 3 6 c 5 2 a b Fig. 11 Fig. 12 TRG 5-53, TRG 5-55, TRG 5-57 TRG 5-54 15 Basic Settings Adjusting temperature limit The rear of the upper part of the housing is provided with a code switch (8 poles) for setting the temperature limit. Example 1 A temperature limit is to be set at Tmax = 176 °C. The code switch indicates eight values between 2 and 256. The basic temperature is 30 °C. Set the switches 2, 16 and 128 to the right by using a small screwdriver. The sum of the values gives a temperature of 146 °C. Plus 30 °C basic temperature makes the requested limit temperature Tmax = 176 °C. Fig. 13 Example 2 A temperature limit is to be set at Tmax = 446 °C. Set the switches 32, 128 and 256 to the right by using a small screwdriver. The sum of the values gives a temperature of 416 °C. Plus 30 °C basic temperature makes the requested limit temperature Tmax = 446 °C. Example 3 A temperature limit is to be set at Tmax = 79 °C. Set the switches 16 and 32 to the right by using a small screwdriver. The values add up to a temperature of 48 °C. Plus 30 °C basic temperature makes the requested limit temperature Tmax = 78 °C. Note that temperatures can only be adjusted in steps of 2 °C. Fig. 14 Tools n Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680 16 Basic Settings - continued Code switch settings 30 S1 S2 S3 S4 S5 S6 S7 S8 ON OFF OFF ON OFF OFF ON OFF Fig. 13 (Example 1) °C 2 4 8 16 32 64 128 256 176 30 S1 S2 S3 S4 S5 S6 S7 S8 OFF OFF OFF ON ON OFF OFF OFF °C 2 4 8 16 32 64 128 256 78 Fig. 14 (Example 3) 17 Commissioning Check wiring Make sure that the TRS 5-6 is wired to its associated temperature sensor as indicated in the wiring diagram. Fig. 10, Fig. 11, Fig. 12 Apply mains voltage Apply mains voltage to temperature switch TRS 5-6. Performance test TRS 5-6 1. When switching on the mains voltage the green LED " must be permanently illuminated. 2. Raise temperature in the heat generator until the permissible temperature limit is exceeded. The two red LEDs 0 of the temperature switch must light up. 3. After lowering the temperature the two red LEDs 0 must extinguish. 4. To simulate a temperature alarm press button “Test I”. When pushing the button, the two red LEDs 0 must light up. 5. To test the self-checking routine of the temperature switch proceed as follows: Set switch “Test II / Inspection” in the direction of the arrow. After max. two minutes the two red LEDs 0 should signal a temperature alarm. Note that the button “Test I” must not be operated during this test nor must the adjusted limit temperature be exceeded! After a successful test set the switch back into its original position. Both LEDs 0 must extinguish after the response delay. Operation Temperature limiter, safety temperature switching controller Operation only in conjunction with temperature sensors TRG 5-53, TRG 5-54, TRG 5-55 or TRG 5-57 in (pressurized) hotwater and steam plants to TRD 401, TRD 602, TRD 604, EN 12952, EN 12953. Note To analyse and remedy malfunctions occurring during the commissioning procedure refer to section Operational Malfunctions. 18 Operation Malfunctions Danger The terminal strip of the equipment is live during operation. This presents the risk of severe cases of electric shock! Cut off power supply before mounting or removing the terminal strips and the housing cover. Faultfinding list for troubleshooting Normal operation - Temperature switch triggers an alarm Fault: The temperature switch triggers an alarm during normal operation. Remedy: Make sure that the green LED " is illuminated. If this is not the case check whether the equipment is supplied with mains voltage. Remedy: Check whether the cable leading to the resistance thermometer is damaged. Remedy: Check whether the resistance thermometer gives correct readings (basic values of ­measuring resistors to DIN EN 60751 for Pt 100). Fault: The test “Test II / Inspection” was not successful, because after two minutes only one or none of the red LEDs 0 is illuminated. Remedy: Replace temperature switch. If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country. 19 Decommissioning Danger The terminal strip of the equipment is live during operation. This presents the risk of severe cases of electric shock! Cut off power supply before mounting or removing the terminal strips and the housing cover. Disposal Dismantle the equipment and separate the waste materials, using the material specification as a reference. Electronic component parts such as the circuit board must be disposed of separately! For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. 20 Annex Note on the Declaration of Conformity / Declaration by the Manufacturer For details on the conformity of our equipment according to the European Directives see our Declaration of Conformity or our Declaration of Manufacturer. The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under www.gestra.de/documents or can be requested from us. 21 For your notes 22 For your notes 23 Agencies all over the world: www.gestra.de 810378-05/04-2010cm (808392-05) · GESTRA AG · Bremen · Printed in Germany 24
advertisement
Key Features
- Self-monitoring
- Two channels
- Fail-safe
- Adjustable temperature limit
- LED indicators
- Easy installation
- DIN-compliant
- TÜV type approval
- PED compliant
Frequently Answers and Questions
What is the purpose of the GESTRA TRS 5-6 temperature switch?
The TRS 5-6 is a safety device designed to monitor and signal temperature limits in steam boilers and hot-water systems. It is used in conjunction with resistance thermometers TRG 5-53, TRG 5-54, TRG 5-55 or TRG 5-57.
How do I adjust the temperature limit on the TRS 5-6?
The temperature limit is adjustable in steps of 2 °C using the code switch located on the rear of the device. Refer to the manual for instructions on how to set the code switch.
What are the outputs of the TRS 5-6?
The TRS 5-6 has two volt-free relay contacts that can be used to signal an alarm condition when the temperature limit is exceeded or a fault is detected.
How do I perform a performance test on the TRS 5-6?
Refer to the manual for detailed instructions on how to perform a performance test. The test includes verifying LED functionality, simulating a temperature alarm, and checking the self-checking routine.