Neles ND800PA Installation Maintenance And Operating Instructions

Neles ND800PA Installation Maintenance And Operating Instructions

Neles ND800PA is a fieldbus powered valve position controller designed for use with pneumatic actuators, suitable for both rotary and linear valves. Its control algorithm adjusts the pilot pressure to achieve the desired valve position based on an input signal from a Profibus PA network. The controller features automatic and manual calibration for accurate positioning and self-tuning for optimized control performance. The user interface includes a local keyboard and display for configuration and monitoring, and the device also supports configuration through Simatic PDM (Process Device Manager).

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Neles ND800PA Installation, Maintenance & Operation Manual | Manualzz
VALVE CONTROLLER
ND800PA
Rev. 1.0
Installation, Maintenance and
Operating Instructions
7 ND 72 en
4/02
2
Table of Contents
1
2
3
4
5
6
7
8
9
10
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Principle of operation . . . . . . . . . . . . . . . . . . . . 3
1.3 Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Technical specifications . . . . . . . . . . . . . . . . . . . 3
1.5 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . 5
MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Mounting on Metso Automation actuators
with VDI/VDE mounting face (S1) . . . . . . . . . 5
2.3 Mounting on EC and EJ actuators (S4) . . . . . . 6
2.4 Mounting on linear actuators with Metso
Automation or IEC 60534 mounting face . . . 7
2.5 Piping of supply air. . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Electrical connections . . . . . . . . . . . . . . . . . . . . 7
USER INTERFACE . . . . . . . . . . . . . . . . . . . . 9
3.1 Keyboard and display . . . . . . . . . . . . . . . . . . . . 9
3.2 Keyboard functions . . . . . . . . . . . . . . . . . . . . . . 9
3.3 HW write protection . . . . . . . . . . . . . . . . . . . . 9
CONFIGURATION. . . . . . . . . . . . . . . . . . . 11
4.1 Zero and range . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Position control . . . . . . . . . . . . . . . . . . . . . . . . 11
4.3 Control valve related settings. . . . . . . . . . . . . 12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . 13
5.1 Prestage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2 Spool valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Circuit board pack . . . . . . . . . . . . . . . . . . . . . . 14
5.4 Position sensor . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.5 Pressure sensor . . . . . . . . . . . . . . . . . . . . . . . . 15
ERROR MESSAGES. . . . . . . . . . . . . . . . . . . 16
TROUBLE SHOOTING . . . . . . . . . . . . . . . 17
TOOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ORDERING SPARE PARTS . . . . . . . . . . . . 17
ND800PA/K06B (WITH LIMIT SWITCHES). 18
10.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
10.1.1 General description . . . . . . . . 18
10.1.2 Markings . . . . . . . . . . . . . . 18
10.1.3 Technical specifications . . . . . . . 18
10.1.4 Safety precautions . . . . . . . . . 18
10.2
10.3
10.4
10.5
11
12
13
14
Installing ND800PA/K06B on a valve controller. 19
Electrical connections. . . . . . . . . . . . . . . . . . . . 19
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Removal of the limit switch ND800PA/K06B
for accessing the valve controller . . . . . . . . . . 19
10.6 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . 19
10.7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10.8 Ordering spare parts . . . . . . . . . . . . . . . . . . . . 19
DRAWINGS AND PARTS LISTS . . . . . . . 20
11.1 Exploded view and parts list . . . . . . . . . . . . . . 20
11.2 Exploded view and parts, ND800PA/K06B . . . 21
11.3 Mounting parts for B1C/B1J 6-20 actuators . 22
11.4 Mounting parts for B1C/B1J 25-50,
B1C 502 and B1J322 actuators. . . . . . . . . . . . 22
11.5 Mounting parts for Quadra-Powr®, ST,
SP and Valv-Powr® actuators . . . . . . . . . . . . . 23
11.6 Mounting parts for EC07-14 actuators,
rising signal opens valve . . . . . . . . . . . . . . . . . . 23
11.7 Mounting parts for EC05 actuators,
rising signal opens/closes valve . . . . . . . . . . . . 24
11.8 Mounting parts for EC07-14 actuators,
rising signal closes valve . . . . . . . . . . . . . . . . . . 24
11.9 Mounting parts for EJ05-14 actuators . . . . . . 25
11.10 Mounting parts for D/R linear actuators . . . . 26
11.11 Mounting parts for linear actuators
with IEC 60534 mounting face . . . . . . . . . . . . 27
11.12 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.12.1Connection diagram for ND800PA/K06B 28
11.12.2Device gland receptacles . . . . . . 29
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . 30
CONTROL DRAWINGS . . . . . . . . . . . . . . 31
13.1 FMRC control drawing for ND84_/MU . . . . 31
13.2 CSA control drawing for ND84_/XU . . . . . . 33
TYPE CODING . . . . . . . . . . . . . . . . . . . . . . 35
READ THESE INSTRUCTIONS FIRST!
These instructions provide information about safe handling and operation of the valve controller
If you require additional assistance, please contact the manufacturer or manufacturer’s representative.
Addresses and phone numbers are printed on the back cover.
SAVE THESE INSTRUCTIONS!
Subject to change without notice.
All trademarks are property of their respective owners.
3
1
INTRODUCTION
1.1
General
1.3
These instructions describe the digital Metso Automation
ND800PA valve position controller. The ND800PA can be used
with either cylinder or diaphragm type pneumatic actuators for
rotary or linear valves.
1.2
Principle of operation
The ND800PA is a fieldbus powered microcontroller-based valve
controller. The ND800PA configuration can be done either using
local push buttons, Simatic PDM (Process Device Manager) or some
other suitable Profibus PA configurator.
Using push buttons or PDM the configuration parameters can be
set according to the actuator and valve in question. Then auto-calibration can be started via push buttons or PDM. A three-digit display
with text labels describes the operation.
In control service the microcontroller (µC) reads data from the input
signal (Profibus PA), position sensor (α) and pressure sensor (p). A
change in input signal will be detected by control algorithm inside
the µC. The microcontroller will change the pilot current to one of
the prestage (PR) coils. A prestage valve lowers the pilot pressure
at the end of the spool valve (SV). The spool moves in the direction
of low pressure to open the flow in to the top of the actuator
cylinder and out from the other side of the piston. The increasing
pressure difference over the piston moves the piston and rotates
the feedback shaft. A position sensor ( a) measures the rotation for
the µC. Using a control algorithm the microcontroller adjusts the
pilot current until a new position of the actuator proportional to the
input signal is reached. In the steady state, the spool valve (SV) and
prestage (PR) valves are closed.
The valve controller is equipped with an identification plate
sticker (Fig. 2). Identification plate markings from top to bottom are:
Type designation of the valve controller
Revision number
Enclosure class
Input signal
Maximum supply voltage
Supply pressure range
Operational temperature
Manufacturing series numbers
CE mark
Fig. 2.
Optional plate
PR
1.4
µC
C2
α
P
C1
1 2 3 4
S
Profibus PA
Fig. 1.
Identification plate
Alternative markings on the optional plate (Fig. 3):
Filter-regulator (-K)
Operational temperature of regulator
Conduit entries (-L, -I or -NJ)
Fig. 3.
SV
Markings
Schematic diagram
Technical specifications
General
The ND800PA valve controller is suitable for rotary and sliding stem valves.
Actuator connection In accordance with VDI/VDE 3845
standard (S1) or as an option
compatibility with other NE-series (S2).
To replace an existing NE/NP positioner,
specify existing valve assembly
Action:
Double or single acting
Turning angle:
min 60°, max 95°
Environmental influence
Operational temp.: -20 - +85 °C (-4 - +185 °F)
option
-40 - +85 °C (-40 - +185 °F)
Influence of temperature on valve position
< 0.05 % / °C
Influence of vibration on valve position
< 1 % under 2g 5-150 Hz and
1g 150-300 Hz
0.5g 300-2000 Hz
4
Enclosure
Material:
Anodized aluminium alloy
Protection class:
IP65, NEMA 4 and 4X
Mechanical position
indicator:
on cover
Pneumatics ports:
1/4 NPT
Electrical connection: Screw terminals internals for 2.5 mm2
and 1 PG 13.5 conduit entry
(1/2 NPT, M20x1.5 and R 1/2 as option,
see optional plate)
Weight:
2.1 kg (4.6 lbs)
Pneumatics
Supply pressure:
Effect of supply
pressure:
Air quality:
Capacity:
Consumption:
2.5-8 bar (36-115 psi)
< 0.2 %/10 kPa (0.14%/psi)
As defined by ISA S7.3 standard
Max 30 Nm3/h (18 scfm)
at 4 bar (60 psi) supply
0.4 Nm3/h (0.24 scfm)
at 4 bar (60 psi) supply
Electronics
Power supply:
Bus voltage:
Taken from bus
9 to 32 VDC
Reverse polarity protection permits
connection of the bus cables in any order
Typical operating current at 24 V supply voltage:
21.8 mA
Operating current over full ambient
temperature and supply voltage range:
20.1-23.45 mA
Max. current in Failure (FDE Current):
27.0 mA
Performance with moderate constant load actuators
Hysteresis + dead band:< 1 %
Linearity error :
< 2%
Local keypad functions
Calibration:
Automatic / Manual
Control feedback:
0.0-3.0 (d and b)
Gain configuration: 0.1-3.0 (gain)
Mode Selection:
Auto/Man/Off
Positioner Fail Action, PFA:
- close (default)
- open
Position Sensor Rotation, ROT:
- clockwise (default)
- counterclockwise
Dead Angle Compensation, A0:
acc. to valve (0 % default)
Valve Type Selection, TYP:
- rot (rotary valve), default
- lin (linear valve)
Setpoint Cut-off CLOSE, CLO:
- 0-100 % (2 % default)
Setpoint Cut-off OPEN, CHI:
- 0-100 % (100 % default)
Lower Limit Valve Position, RLO:
- 0-100 % (0 % default)
Upper Limit Valve Position, RHI:
- 0-100 % (100 % default)
Profibus slave address, ADR:
- 0-126, default 126
Electrical connections
Input signal:
Profibus PA
according to IEC 61158-2
Approvals
Temp. ≤ +75 °C (+67 °F):
Cenelec EEx ia IIC T5/T6 (pending),
Temp. ≤ +50 °C (+122 °F):
CSA Class I, Divisions 1 and 2,
Groups A, B, C and D (pending)
FM Class I, Divisions 1 and 2,
Groups A, B, C and D (pending)
Sensors
Position sensor
linear range:
110 °
Actuator pressure
sensor linear range: 7 bar (100 psi) (differential pressure)
User interfaces
Local:
3 keys + LCD display
Simatic PDM functions:
Flow characterization: Linear, equal percentage, quick opening,
custom
Identification information:
HW/SW rev., serial numbers, actuator type etc.
Monitoring:
Valve travel setpoint, actual travel,
actuator pressure and device temperature
Diagnostics:
Travel deviation, travel duration, load factor,
operation time, valve/actuator travel counters,
failure information
Testing:
Step response, hysteresis loop
Module calibration: Position sensor, pressure sensor, temperature measurement
Electromagnetic protection
Protection standards: EN50081-1 and EN50082-2
IEC 801-2 ESD, level 4,
IEC 801-3 Electro Magnetic Field, level 3
IEC 801-4 Fast Transients, level 4
CE marking
Electromagnetic
compatibility:
89/336/EEC
5
1.5
Safety precautions
CAUTION:
Do not exceed the permitted values!
Exceeding the permitted values marked on the valve controller may cause damage to the controller and to equipment
attached to the controller and could lead to uncontrolled
pressure release in the worst case.
Damage to the equipment and personal injury may result.
CAUTION:
Do not remove or dismantle a pressurized controller!
Removing or dismantling a pressurized prestage, spool valve
or pressure sensor of an ND800PA leads to uncontrolled
pressure release. Always shut off the supply air and release
the pressure from the pipelines and equipment before removing or dismantling the controller.
Otherwise personal injury and damage to equipment may result.
CAUTION:
During automatic or manual calibration the valve operates between open and closed positions. Make sure that
the operation does not endanger people or processes!
EXi CAUTION:
Make sure that the complete installation and wiring
is intrinsic safe before operating the device!
EXi CAUTION:
Make sure that that the power source (e.g. segment
coupler, link or fieldbus power supply) is EXi certified apparatus!
EXi CAUTION:
Make sure that all the devices which are connected
to the fieldbus segment are EXi certified devices!
2
MOUNTING
2.1
General
NOTE:
The mounting must be in accordance with the installation
guidelines IEC-EN 60079-10.
If the ND800PA is supplied with valve and actuator the tubes are
mounted and the ND800PA adjusted in accordance with the
customer’s specificatons. If the controller is ordered separately, the
mounting parts for the assembly must be ordered at the same time.
Sample order: (B1C13)-Z-ND826/S1.
The controller is equipped with both the new Metso Automation
mounting face, for connection according to VDI/VDE 3845 (S1),
The mounting code for EC and EJ actuators is S4.
Shaft alternatives for the controller for Metso Automation rotary
actuators are shown in Fig. 4.
For mounting parts for Metso Automation actuators, see Sections
10.2-10.6.
2.2
Mounting on Metso Automation actuators
with VDI/VDE mounting face (S1)
See Sections 10.2, 10.4
Run the actuator until the piston is in the top position (spring
return actuators in the position determined by the spring).
Set the direction arrow in the direction of the valve closure
member and attach the draught piece (2) to the indicator
cover in the position shown in Fig. 4. Secure the screw of
the draught piece e.g. with Loctite and tighten it sufficiently.
Attach the bracket (1) to the ND800PA.
Attach the bracket (1) to the actuator. The shaft (40) of
the ND800PA must fit into the draught piece (2) shown
in Fig. 4. See also drawings in Section 10.2.
Note the differences in installation between the B1C, B1J and B1JA
actuators.
EXi CAUTION:
Do not remove the protective cover within hazardous area!
Shaft alternatives
S1
S2
mark
EXi NOTE (FM):
The installation must be in accordance with the FM Control
drawing. See 13.1 FM Control drawing.
40
40
mark = yellow dot
C2
EXi NOTE (CSA):
The installation must be in accordance with the CSA Control
drawing. See 13.2 CSA Control drawing.
NOTE:
Avoid earthing a welding machine in close proximity to an
ND800PA valve controller.
Damage to the equipment may result.
S
C1
Fig. 4.
The mark on the shaft must
stay in this sector
Mounting on Metso Automation actuator with
VDI/VDE mounting face
6
2.3
Mounting on EC and EJ actuators (S4)
See Sections 11.6-11.9
Mount the O-rings (38) into the air connections in the
bottom of the controller.
Place the valve controller on top of the actuator so that
the yellow mark is located in the position shown in Fig. 5.
See also Fig. 15.
Fasten the screws (4). Two of the screws are located at
the front edge and two inside the controller housing.
Painted
mark
Fig. 5.
Table 1.
6
9
11
13
17
20
25
32
40
50
502
B1J
B1JA
8
10
12
16
20
25
32
322
QP
1
2
3
4
5
6
EC
05
07
10
12
14
EJ
05
07
10
12
14
Mounting on EC and EJ actuators
Piping
Actuator
B1C
O-rings
Stroke vol.
dm3/in3
0.3/18
0.6/37
1.1/67
2.3/140
4.3/262
5.4/330
10.5/610
21/1282
43/2624
84/5126
195/11900
Stroke vol.
dm3/in3
0.9/55
1.8/110
3.6/220
6.7/409
13/793
27/1648
53/3234
106/6468
Stroke vol.
dm3/in3
0.62/37
1.08/66
2.18/133
4.34/265
8.7/531
17.5/1068
Stroke vol.
dm3
0.09
0.2
0.5
1.2
3.0
Stroke vol.
dm3
0.18
0.4
1
2.4
6
Piping
NPT
1/4
1/4
1/4
3/8
3/8
1/2
x
x
x
Plastic/Cu/SS (")
3/8
x
x
x
x
x
x
x
x
(x)
(x)
1/2
3/4
3/4
1
1
NPT
1/4
3/8
x
3/8
3/4
1
(x)
(x)
x
x
x
1/2
x
x
x
x
x
6/4
10/8
(x)
(x)
x
x
x
12/10
x
x
x
x
x
x
(x)
1/2
1/2
Plastic/Cu/SS (mm)
6/4
10/8
12/10
3/8
(x)
(x)
x
x
1/2
x
x
x
x
x
6/4
10/8
(x)
(x)
x
x
12/10
NPT
1/4
3/8
3/8
3/8
3/8
3/8
3/4
G
x
x
1/4
1/4
1/4
1/4
1/4
G
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1/4
1/4
1/4
1/4
1/4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
x
x
x
x
x
x
x
x
x
x
Spool
valve
2
2
2
6
6
6
6
6
6
6
6
Spool
valve
21
61
61
61
61
61
61
61
Spool
valve
21
21
61
61
61
61
Spool
valve
1
1
2
2
6
Spool
valve
11
21
21
61
61
7
Table 2.
Spring rates
Actuator type
Spring rate (bar/psi)
B1JK
3/43
4.2/61
B1JSTD
B1JV
5.5/80
QPB
3/43
QPC
4.3/62
QPD
5.6/81
Adjust regulator pressure to a level which is max 1 bar (14.5
psi) + spring rate. If spring rate is less than 3 bar (43 psi)
then supply pressure 4 bar (58 psi) is recommended.
2.4
Mounting on linear actuators with Metso
Automation or IEC 60534 mounting face
See Sections 10.5, 10.6.
Connect an airset directly to the actuator and position the
actuator at its mid-stroke position (see serial plate for
actuator stroke length).
Attach the feedback arm on to the controller input shaft.
Make sure the lettering on the feedback arm faces up,
toward the controller.
Attach the controller mounting bracket loosely on to the
slotted leg of the actuator. Make sure the marks on the
shaft and feedback arm operate in the quadrant shown.
Measure the distance from the centre of the feedback
lever shaft to the slot on the feedback lever and mark this
distance with a pencil or other marking instrument. Use
the dimensions given in Sections 10.5 and 10.6.
Mount the controller loosely onto the controller mounting
bracket.
Adjust the controller mounting bracket and the controller
so that the controller is at 90° to the centre line of the
actuator and the controller feedback lever is horizontal
and at 90° to the centre line of the actuator.
Tighten the controller mounting bracket screws.
Adjust the controller on the controller mounting bracket so
that the measured distance is maintained between the centre
of the feedback lever shaft and the actuator pin (pre-measured mark on the feedback lever). Note the controller must
still conform to the specifications in previous steps.
Tighten all the mounting bolts and then re-check that the
controller complies with previous steps. Check that the
actuator pin does not touch the controller case throughout the entire stroke of the actuator. If the actuator pin is
too long it may be trimmed to length. (The pin must be
trimmed on stroke of 1.125" or less.)
Attach the spring on to the feedback arm as shown.
Apply grease (Molykote or equivalent) to the contact surfaces
of the actuator pin and the feedback lever to reduce wear.
Increase and/or decrease air pressure to the actuator to
stroke the actuator full stroke to check that nothing is
binding and that the rotation of the feedback lever is 70°
for a 1"-5" stroke and 60° for a 3⁄4" stroke. See Sections
10.5 and 10.6.
2.5
Piping of supply air
CAUTION:
Do not exceed the permitted supply pressure
of the ND800PA!
Table 1 provides the recommended tube sizes in accordance with
actuator sizes. Tube sizes are the minimum values allowed. For
supply air choose a tube one size bigger. Operating times can be
tested by the PDM.
Connect the air supply to S (1/4 NPT).
Connect C1 and C2 (1/4 NPT) to the actuator.
For the pipe threads liquid sealants, such as Loctite 577, are
recommended.
NOTE:
Too much sealant may cause faulty operation of the controller.
Sealing tape is not recommended.
Ensure the cleaniness of the air piping.
The supply air must be clean, dry and oil-free instrument air, e.g.
according to standard ISA S7.3-81.
2.6
Electrical connections
The bus cable is led through a PG13,5 cable gland. Connect the
conductors to the terminal strip according to Fig. 6.
Reverse polarity protection permits connection of the bus cables in
any order.
Depending on the plant grounding policy, either Equipotential
Bonding or Capacitive grounding can be used. See "PROFIBUS - PA
User and Installation Guideline". In the case of Equipotential Bonding,
connect the cable shield to earth connection screw. In the case of
Capacitive grounding, connect the cable shield to terminal strip 1.
Earth connection
Profibus PA
Fig. 6.
Terminals
8
C2
DOUBLE-ACTING ACTUATOR
S
C1
1. Self closing.
Default setting:
PFA = CLO
ROT = cC (close valve to c lockwise)
A0 = % (acc. to valve type)
cLo = 2 %
NOTE: EC05 actuator requires a coupling plate
C2
2. Self opening.
S
C1
Setting:
PFA = OPE
ROT = cC (close valve to c lockwise)
A0 = % (acc. to valve type)
cLo = 2 %
NOTE: EC07...EC14 actuators require external piping
EC05 actuator requires a coupling plate (reverse action)
C2
SINGLE-ACTING ACTUATOR (SPRING TO CLOSE)
S
C1
3. Self closing.
Spring to close valve.
Default setting:
PFA = CLO
ROT = cC (close valve to c lockwise)
A0 = % (acc. to valve type)
cLo = 2 %
C2
S
C1
4. Self opening
Spring to open valve.
Setting:
PFA = OPE
ROT = ccC (close valve to c ounterclockwise)
A0 = % (acc. to valve type)
cLo = 2 %
CAUTION: Valve closes exceptionally counterclockwise.
Unsuitable for Q-, R-, T5-, F- and L-series valves.
C2
SINGLE-ACTING ACTUATOR (SPRING TO OPEN)
S
C1
5. Self opening.
Spring to open valve.
Setting:
PFA = OPE
ROT = cC (close valve to c lockwise)
A0 = % (acc. to valve type)
cLo = 2 %
After self-tuning the default parameters are as follows:
Gain
d
d
b
= 1.0 (for enhanced control use Gain=1.2)
= 0.0 for double acting actuators (factory set)
= 1.0 for single acting actuators (factory set)
= 1.0
In order to achieve symmetrical operation, always use filter regulator in connection with spring return actuators. See Table 2.
RA and DA actuators: use spool 21A.
RB, RC, RD, RE and DB, DC, DE actuators: use spool 61A.
NOTE: Use QP values for diapharagm-pneumatic linear actuators.
Use B1J values for spring-return cylinder actuators. Use B1C values for double-acting cylinder actuators
If operational conditions change considerably, perform self-tuning for optimum performance.
Fig. 7.
Operation directions and air connections
9
The keyboard and the display of the ND800PA are shown in Fig.
8. Only applicable information is shown on the display in each mode.
Operations and display are controlled by +, - and r keys.
Four setting functions are available: m, g, d or
c. Each of these names refers to the function to be adjusted
or changed.
In a or M mode the display indicates 0-100 % as the valve
travel. In o mode the display shows two dashes (--) instead of
digits. By pressing the r key the display shows the analog output
block output value (A0.OUT) within about 5 seconds. In other
situations the display indicates the adjustable parameter value
selected.
MODE: AUTO MAN OFF
GAIN
DB
CALIB
d includes positioner feedback parameters d and b. By pressing
the r key you can select one of the above parameters with the +
and - keys. Confirm your choice with the r key and change values
with + and - keys. Confirm the value with r. Default values are
listed in Fig. 7.
The next setting to move to with the + key is c. By pressing
the r key you can start zero and travel range calibration and
self-tuning. More detailed information about c is given in
Section 4.1.
Within different options you can move forward with the + key and
with the - key backward.
In addition, there are nine control valve related configuration
parameters: PFA. rot, A0, t4P, cLO, chi , rLo, rhi and Adr which are
explained in Section 4.3
You can return to the operation state from any setting by pressing
+ and - keys simultaneously for less than 1 second, repeating if
necessary.
3.3
3.2
Keyboard functions
See keyboard operations (Fig. 11).
The keyboard setting state is initiated by pressing the + and - keys
for 5 seconds. The blinking text item m and one of the
previously selected operation modes, a, M or o, will
be shown on the display. If you want to change the operation mode,
press r first. a, M or o will start to blink showing that
the mode-changing function is enabled. Choose the desired mode,
a, M or owith the + or - key. After the mode has
been selected, press the r key.
The m function provides three alternative ND800PA operation modes:
a:
During a mode the ND800PA controls the valve position
according to the analog output block (AO) output signal. This mode
is used during normal process control service.
M:
During this mode the valve position can be manually controlled from
the keyboard + or - keys. The position of the manually driven valve
is not saved in the non-volatile memory of the ND800PA, i.e. the
valve does not return to the same position after power failure.
However, the valve can be driven back into position after power
failure by the + and - keys.
o:
When the o mode is activated the ND800PA closes the valve
and does not respond to incoming signal.
Accept the selected mode by pressing the r key which returns you
automatically to the setting state.
ON OFF
DIP 2
DIP 1
2
LCD-display and keyboard
The ND800PA is delivered from the factory with HW write
protection OFF as the default setting. Reading and changing parameters is thus allowed. Write protection can be enabled with a switch
(DIP1) located on the circuit board (Fig. 9). DIP2 is not in use.
Write protection protects all acyclic write access to all writeable
parameters of the device. Changing the parameters from the local
keyboard or PDM is thus not allowed.
ON
Fig. 8.
HW write protection
2
Keyboard and display
1
3.1
Move to the next setting by pressing the + key. g starts to
flash. The positioner gain required for different size of actuators is
set with the g parameter. g is set automatically by
self-tuning procedure during a/ M calibration. Pressing the
r key allows you to change the gain value shown on the display with
the + and - keys. Accept a changed value with r key, which returns
you automatically to the setting state.
ON
USER INTERFACE
Fig. 9.
DIP switch
1
3
Operation
state
10
%
>5s
Setting state
&
= Analog output block output signal (%)
>5s
>5s
&
PREVIOUS SETTING
(FACTORY = 90˚)
KEYSTROKES
&
&
&
Fig. 10.
Keyboard operations
&
= Escape < 1 s
&
&
11
4
CONFIGURATION
4.1
Zero and range
The ND800PA position sensor operational range is factory adjusted
to suit Metso Automation actuators. If the ND800PA is to be fitted
into another manufacturer’s actuator, the sensor may need to be
readjusted as explained in Section 5.4.
Connect the air supply and fieldbus cable.
Select the c function from the keyboard according to 3.2.
Now you can select the a or M calibration mode
from the display by pressing the + or - key.
CAUTION:
Automatic calibration drives the valve against the
mechanical open and closed travel limits of the
valve-actuator assembly and a self-tuning procedure is performed. Make sure that these procedures can be safely executed.
Self-tuning procedure:
This is performed automatically during a or M
calibration.
As a result of self-tuning the g is set = 1 and b is set = 1.
d is originally factory set as explained in Fig. 7.
a calibration function:
For safety reasons the r key needs to be pressed for 5
seconds to activate the a calibration function. During
calibration the display shows the text CAL. After calibration
the ND800PA returns automatically to the setting function.
A self-tuning procedure is performed.
At any time you may interrupt the calibration sequences
by pressing the + and - keys simultaneously.
After the a calibration sequence is finished press the
+ and - keys simultaneously to get back to the operation
state. If this sequence has ended and an error message Err
appears on the display, see Chapter 6.
Now the ND800PA will work with basic settings including 2 ± 0.5 %
signal cutoff margins to secure full closing of the valve.
If you cannot drive the valve into a fully open position or if there is
no mechanical limit stop, proceed as follows:
M calibration function:
After selecting the M calibration function from the
display press the r key to activate the procedure.
With the + or - keys drive the valve manually to the
closed (0 %) position and then press the r key.
If you cannot drive the valve into the open position, you
may skip this sequence by pressing the + and - keys
simultaneously. Now the ND800PA assumes that the
maximum valve opening is the latest calibrated value. The
factory setting is 90°.
Drive the valve into the desired maximum opening position (100 %) with the + and - keys and press the r key.
A self-tuning procedure is performed.
If an error message Err appears on the display, see
Chapter 7.
Press the + and - keys simultaneously to return to the
operation state.
Now the valve controller will work with basic settings including
2 ± 0.5 % signal cutoff margins.
4.2
Position control
g is the gain parameter, d is the actuator pressure feedback
parameter and b is the valve velocity feedback parameter. The
default values after self-tuning are given in Fig. 7. Values are defined
for the control valve in question during self-tuning. However,
because of the large range of pressure drop and temperature for
the different processes, variations in supply air pressure and the great
variety of valve constructions, actuator load may differ considerably
from the default value. For this reason g, d and b may have to
be adjusted to ensure optimum control performance for special
cases. Use the following guidelines to adjust g, d and b.
Check that d value is according to Fig. 7.
Perform a or M calibration.
For enhanced control increase the g to value 1.2
If the valve is unstable, lower g until the valve is stable
at a constant input signal. If higher g is needed, increase
d to dampen instability with spring-return actuators.
If the valve is slow, increase g. If the valve is overshooting, decrease g. Adjust g for slight overshooting and then increase b to dampen it.
If the deviation between input signal and actual valve
position is high, increase g to decrease deviation.
However, avoid unstable operation.
g setting:
Select the g function from the keyboard according
to Section 3.2.
Now the display should indicate the current parameter
value. If you want to change it, press the r key.
Increase the parameter value by pressing the + key or
decrease its value by pressing the - key.
Press the r key when the desired value appears on the display.
Press the + and - keys simultaneously to return to the
operation state.
d setting:
The d parameters can be adjusted in the same manner.
(See Fig. 10).
The ND800PA stays in the selected operation mode during the
g and d settings.
12
Control valve related settings
Table 3.
The basic factory settings of the ND800PA assume a positioner fail
action to be closing the valve and a clockwise closing direction for
the position sensor. The setpoint cut-off CLOSE is set to 2 ± 0.5 %
to guarantee full closing of the valve against mechanical travel stops.
Valve size
4.3
Dead angle as percentage
Valve series
MBV MBV D
QMBV QMBV
1)
mm in
100%
OUTPUT
Dead Angle
Compensation
0%
INPUT
Setpoint Cut-Off CLOSE
Lower Limit Valve Position
Fig. 11.
100%
Setpoint Cut-Off OPEN
Upper Limit Valve Position
The input signal modifications accomplished using
Dead Angle compensation, Cut-Off and Limit functions
Following parameters are possible to change during setting state by
pressing + or - keys until the parameter in question appears on
the display.
Positioner fail action (PFA)
2)
The next application-specific parameter rot defines the relationship
between position sensor rotation and valve action.
Once rot is displayed press the r key and the current
parameter value will be shown on the display. Now you
may select between two values by pressing the + or key. The value cC means clockwise rotation for closing the
valve and ccC means counterclockwise to close.
After the desired value is displayed, press the key r to
conclude the operation. See default values and tubing sizes
in Fig. 7 and functions in Fig. 10.
α0 setting (dead angle, A0)
The α0 setting is made for Metso Automation segment and ball
valves. This setting takes into account the “dead angle” α0 of the
ball valves. The entire signal range is then used for effective valve
opening 90° - α0 (Figure 12 and Table 3). Use 0 % as the “dead
angle” for the valves not mentioned in Table 3.
After selecting A0 on the display, press the r key and the
parameter value currently selected appears as a percentage (%) on the display.
3)
Dead angle as %
25.5 19.5
1
14 24.5 12.5
1 1⁄2 12 10 9
13.5 24.5 12.5
2
2 1⁄2 9
8.0
18.0
10
8
12.0
3
8.5
16.5
10
8
12.0
4
12
5
10 8
11.5 16.0 9.0
6
7
8.5 12.0 6.5
9
8
9
7
7.5 13.5
10
8
6
6.5 9.5
12
6
6.0 14
5
5.5 9.5(14")
16
6.0 7.5(16")
18
6.0
20
5.5
24
7.0
26
7.0
28
6.0
30
32
5.5
36
1)
Seat supported 2) Trunnion 3) S/G seat
25
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
650
700
750
800
900
Configuration of the action taken during the loss of the power
(supply pressure is available). This action takes place also when the
positioner software notices a fatal device failure. In these both cases
the spool valve feeds C1 and releases C2 pressure, see Fig. 7.
When the letters PFA appear on the display you may read the
current value by first pressing the r key and then selecting either
the CLO or OPE values by pressing the + and - keys.
To conclude press the r key when the desired value is
shown on the display. See default values in Fig. 7 and
functions in Fig. 10.
Position sensor rotation (rot)
T5, QX- T25, QX- R,
QT5 T5 QT25 T25 QR
18.0
16.5
16.0
12.0
13.5
9.5
9.5
7.5
8.0
8.5
9.0
6.5
15
12
17
13
9
8
8
8
7
7
6
5
5
α0 = dead angle
Fig. 12.
Dead angle
Modify the parameter value by pressing + or - keys
alternately until the desired value appears on the display.
Press the r key to finalize your selection and return to the
setting state. See Fig. 10 for functions.
13
Valve type selection (t4P)
To compensate for nonlinearity of the position feedback caused by
the actuator linkage mechanism of a linear control valve, the
appropriate selection must be made at the t4P display.
After selecting t4P on the display, press the r key and select
between two values rot and Li n using the + and - keys.
The value rot indicates a rotary valve and Li n a linear valve.
To conclude press the r key when the desired value is
shown on the display.
Setpoint cut-off CLOSE (cLo)
When cLo appears on the display, press the r key and the
current default value as a percentage (%) appears on the
display. The Metso Automation’ standard default value is
2 % (2.0). Now modify this value to the desired number
and press the r key to return to the setting state. See Fig.
10 for functions.
When input signal goes below the defined value, the valve
is driven to the CLOSED position, see Fig. 11.
Setpoint cut-off OPEN (chi )
When chi appears on the display, press the r key and the
current default value as a percentage (%) appears on the
display. The Metso Automation’s standard default value is
100 % (1 00). Now modify this value to the desired number
and press the r key to return to the setting state. See Fig.
10 for functions.
When input signal goes above the defined value, the valve
is driven to the OPEN position, see Fig. 11.
Lower limit valve position (rLo)
When rLo appears on the display, press the r key and the
current default value as a percentage (%) appears on the
display. The Metso Automation’s standard default value is
0 % (0.0). Now modify this value to the desired number
and press the r key to return to the setting state. See Fig.
10 for functions.
Valve position is never allowed to go below this value.
The only exception is fail-safe situation. See Fig. 11.
Upper limit valve position (rhi )
When rhi appears on the display, press the r key and the
current default value as a percentage (%) appears on the
display. The Metso Automation’s standard default value is
100 % (1 00). Now modify this value to the desired number
and press the r key to return to the setting state. See Fig.
10 for functions.
Valve position is never allowed to go above this value.
The only exception is fail-safe situation. See Fig. 11.
NOTE:
The setpoint cut-off function overrides the limit function. If
setpoint cut-off CLOSE is greater than 0 %, the lower limit
Valve position is not applied (has value 0 %). Correspondingly,
if setpoint cut-off OPEN is smaller than 100 %, the upper limit
valve position is not applied (has value of 100 %).
Profibus slave address, (Adr)
When Adr appears on the display, press r key and the
current value appears on the display. The default is 126.
Now modify this value to desired number and press r key
to return the setting state. see Fig. 10 for instructions.
When all the control valve-related parameters are correctly set, return to operation state by pressing the + and
- key simultaneously for a short time.
5
MAINTENANCE
The maintenance requirements of the ND800PA valve controller
depend on the service conditions, for instance, the quality of instrument
air. In normal service conditions no regular maintenance is required.
The best reliability is achieved by following these instructions.
In the following text the numbers in parenthesis ( ) correspond to
the part numbers on the expoded view in Chapter 11, unless
otherwise stated.
The ND800PA valve controller includes the following interchangeable modules: prestage (3), spool valve (4), circuit board pack (5),
position sensor (6), and differential pressure sensor (7).
The modules are located underneath a protective cover (46) which
is attached with M3-screws (48, 4 pcs.). If a module fails it must be
changed. The module retrofit must be made in a clean, dry
environment. After replacement apply thread-locking compound
(for instance, Loctite 243) and tighten the screws firmly.
5.1
Prestage
NOTE:
The prestage must be handled very carefully. In particular the moving
parts on both ends of the prestage should not be touched when
the prestage is functioning and the protective cover is not in place.
Disassembly
Unplug the prestage (3) wire connectors from the circuit
board (5). Unscrew the M4 screws (92, 2 pcs.) and
remove the prestage module.
Reassembly
Place the O-rings (91) in the respective grooves and press
the prestage into place. Make sure that the nozzles are
properly guided on top of the O-rings. The screws guide
the prestage body into the correct position.
Push the prestage 2-pole wire connectors into the sockets on
the circuit board. Make sure that the wires do not cross each
other. The wire connectors can only be fitted in the correct way.
Tighten the screws (92) evenly with a torque of approx.
0.8 Nm (0.6 ft.lb).
Set the protective cover (46) carefully in place and tighten
the screws (48).
14
5.2
Spool valve
5.3
Before removing the spool valve (4) the prestage (3) must be taken
off. (See Section 5.1)
Disassembly
Unscrew the M4 screws (99, 4 pcs.) and remove the spool
valve assembly.
The spool valve can be cleaned by following especially clean and
careful procedures. The seal (106), filter (105), restriction (104)
and spring (100) are located at the ends of the spool valve (102,
103). The spool (97) can also be removed for cleaning.
NOTE:
Each spool valve body has an individual matching spool which
cannot be replaced by any other spool. Never change the orientation of the spool or the location of the individual spool springs.
Reassembly
Place a new gasket (98) in the location determined by the fitting
screw holes. Fit the spool valve into its corresponding position
on top of the seal and tighten the M4 screws (99) evenly.
The O-rings must be mounted first in their grooves located in
the spool valve unit. During mounting the O-rings must be
compressed because the sealing is done radially. Make sure that
the O-rings are evenly compressed and that they are fully inside
the grooves. The O-rings must be in perfect condition; no
defects are allowed. If a tool is used it must be blunt.
Mount the prestage unit directly onto the spool valve unit.
The ends of the nozzles will guide the prestage unit to the
right location. The prestage unit must fit by pushing gently
with no excessive force. Ensure that the spool valve unit
and the prestage unit have an even surface connection
before tightening the screws.
102
96
Circuit board pack
Disassembly
Loosen the M8 screw (66) and turn the position indicator (65) outwards from the feedback shaft.
Unplug all wire connectors from the circuit board (5) and
the signal wires from the terminal block (35).
Remove the M3 screws (111, 5 pcs.).
NOTE:
Ground yourself on the body of the device before touching
the circuit board pack.
Take hold of the sides of circuit board and lift it directly
upwards and outwards. Handle the board carefully, touching only the sides.
Reassembly
Remount the circuit board pack carefully. Do not let the
feedback shaft touch the circuit board.
Locate the pins of the pressure sensor on the matching
connections on the board.
Tighten the M3 screws (111) evenly.
Push the rubber grommet into the slot located on the
intermediate wall of the body and connect the wires to
the terminal block as shown in Fig. 14. Plug the prestage
wire connectors into the board making sure that the wires
do not cross each other. Plug the position sensor (6) wire
connector into the board.
Mount the protective cover (46).
Mount the position indicator (65) on the shaft and tighten
the M8 screw (66) temporarily. The final locking of the
position indicator occurs when the actuator is installed.
NOTE:
Changing a new circuit board pack requires updating the
module parameters using PDM communication. See the instructions provided with the new circuit board.
103
104
circuit board pack
105
106
Fig. 13.
108
109
97
100
101
107
Spool valve
Fig. 14.
Circuit board pack
grommet
15
5.4
Position sensor
5.5
Pressure sensor
Before loosening the position sensor (6) first loosen the circuit board
according to 5.3.
The position sensor assembly (6) consists of the MR-sensor (114),
which is fixed to the housing, and the spiral (117), which is fixed to
the main shaft.
Before removing the pressure sensor (7) you must loosen the circuit
board according to 5.3.
Disassembly
Loosen the M3 screws (116, 2 pcs.) and lift the sensor out
of the housing.
Remove the lock ring (119) from the shaft and open the
hexagonal socket screw (118, 2 pcs.). Mark the top of the
spiral before removing it. Slide the spiral out of the shaft.
Reassembly
Mount the O-rings (123, 2 pcs.) in their grooves in the
housing. Push the pressure sensor back into place, guided
by the O-rings. The final location is shown in Fig. 16.
Tighten the M3 screws evenly.
Replace the circuit board and the protective cover according to 5.3.
Reassembly
Mount the new sensor and spiral together as a pair. Slide
the spiral back onto the shaft and replace the lock ring on
the shaft. Turn the spiral and the shaft to the position
shown in the Fig. 15, corresponding to a 45° valve opening.
Tighten the M3 screws.
Install a 0,1 mm (0.004 in) thick gauge strip between the
sensor and the spiral. Press the sensor against the spiral,
without using unnecessary force, and tighten the screws
(116) evenly. Remove the strip.
Mount the circuit board and the protective cover (46) as
directed in 5.3.
Disassembly
Loosen the M3 screws (126, 2 pcs.) and lift out the
pressure sensor (7) holding it from the both ends.
NOTE:
Changing the pressure sensor requires updating of the calibration
values of the sensor using PDM communication. See the instructions in the ND800PA User’s guide.
NOTE:
Changing the new position sensor requires updating of the
calibration values of the sensor using PDM. See the instructions
in the ND800PA User’s guide.
Fig. 16.
Pressure sensor
Shaft alternatives
45˚
yellow
mark
mark
40
mark
40
40
mark
45˚
90˚
yellow
119
118
mark
40
114
116 117
screws of the
spiral at this
point
mark
45˚
yellow
mark = yellow dot
Fig. 15.
Position sensor
16
6
ERROR MESSAGES
When the ND800PA detects serious device failure (analogue
inputs, analogue outputs or electronics) it enters fail-safe mode
which drives the control valve into the position defined in the
parameter positioner fail action (PFA). Fail-safe mode is indicated by
the LCD as message Exx, where xx is a number between 1-99, or
by the PDM. The error message is displayed until the cause of error
is eliminated and the ND800PA unit is cold-started, i.e. the fieldbus
is momentarily disconnected. Cold-start can also be done using
PDM.
Table 4.
Error messages shown on LCD display
Error message
E41
E44
E51
E52
E61
E65
E81
E82
E91
When the ND800PA detects an error during travel calibration or
self-tuning, the error message Err is displayed. It disappears when
any key is pressed.
The ND800PA stores error messages in its non-volatile memory,
which saves the 20 most recent error codes. The memory can be
read out with PDM.
Table 4 lists the error messages shown on the LCD display and their
explanations.
Reason
Action
Pneumatic prestage valve 1 (VA1) control Check wires and connectors or change circuit board.
failure.
Resistance of the coil is approx. 100 Ω, measured from the prestage connectors.
Pneumatic prestage valve 2 (VA2) control Check wires and connectors or change circuit board.
failure.
Resistance of the coil is approx. 100 Ω, measured from the prestage connectors.
Position feedback ADC low limit failure. Check the mounting of controller; the mark on the shaft must stay in the
right sector, see Fig. 4.
Check wires, connector and position sensor rotation range or
change circuit board.
Rotate the position feedback shaft 10 degrees counterclockwise and
cold-start the device.
Position feedback ADC high limit failure. Check the mounting of controller; the mark on the shaft must stay in the
right sector, see Fig. 4.
Check wires, connector and position sensor rotation range or
change circuit board.
Rotate the position feedback shaft 10 degrees clockwise and
cold-start the device.
Memory (EEPROM) failure.
Change circuit board.
Memory (EEPROM) failure.
Change circuit board.
Memory (RAM) failure.
Change circuit board.
Memory (ROM) failure.
Change circuit board.
Processor failure.
Change circuit board.
Zero and travel calibration or
self-tuning fails.
Check range of position sensor or mechanical limits of actuator.
Check wires and connectors.
Check leakage.
Check that spool valve does not stick.
Check that prestage is not defective.
Err
ADC = analog/digital converter
17
7
TROUBLE SHOOTING
Mechanical/electrical defects
1. A change in the valve position setpoint does not affect the
position of the actuator
supply pressure too low
spool valve sticks
tubes between controller and actuator are incorrect, see
Fig. 7
actuator and/or valve jammed
signal wires incorrectly connected, no value on display
circuit board is defective
calibration has not been carried out (a or M)
ND800PA is either in M or o mode
prestage is defective
position sensor is defective
2. The actuator goes to the final position with a small change of
input signal
tubes between controller and actuator are incorrect, see
Fig. 7
the parameter settings PFA and rot are incorrectly selected.
See Figs. 7 and 10
3. Inaccurate positioning
spool valve dirty
dirt in the permanent magnet air gap
actuator too small
supply pressure too low
pressure sensor is defective
d and b parameters in the d mode do not comply with
recommendations shown in Fig. 7
g parameter is too small, perform a / M
calibration acc. to Section 4.2
4. Overshooting or positioning too slow
g is too high or too low, see Fig. 7
spool valve dirty
supply air tube too small or supply air filter dirty
valve sticks
check leakages in tubes between controller and actuator
check leakages in mechanical stop screws
5. Err is shown during calibration
position sensor is out of range, see Section 5.4
mechanical actuator travel exceeds position sensor linear
travel, i.e. 110°. If it fails in fully closed position, turn the spiral
(117) counterclockwise in 5° steps. If it fails in the fully open
position, turn the spiral (117) clockwise in 5° steps.
the parameter settings PFA and rot are incorrectly selected, see Section 4.3 and Fig. 7
the actuator did not move or was stuck during calibration
ND800PA/actuator mounting is incorrect, see Figs. 4, 5,
15 and Sections 10.2-10.6
spool valve sticks
prestage is defective
PDM trouble shooting is explained in the ND800PA User’s Guide.
8
TOOLS
No special tools needed.
9
ORDERING SPARE PARTS
Spare parts are delivered as modules. Available modules are shown
in Section 11.1.
When ordering spare parts, always include the following information:
controller type designation and serial number from the ID
plate
code of this manual, part number, part name and quantity
required
When ordering the circuit board, serial number of the
position sensor
18
10
ND800PA/K06B (WITH LIMIT SWITCHES)
10.1
Introduction
10.1.1
10.1.3
Technical specifications
10.1.3.1 ND800PA/K06B
General description
ND800 can be equipped with limit switches. ND800PA/K00B has
2 microswitches.
Limit switches are used for electrical position indication of the valves
and other devices.
The switching points can be chosen freely.
Microswitch type:
OMRON D2VW-01
(gold plated contacts)
Protection class IP67
Resistive load:
100 mA: 30 V DC/125 V AC (06)
Switch accuracy:
< 2°
Number of switches: 2
Protection class
of cover:
2 cams
(06)
Conduit entry:
terminal
2 microswitches
IP65 (DIN 40050, IEC 529)
PG 13.5
1/2 NPT = -L
M20x1.5 = -I
R 1/2 =
-NJ
Ambient temperature: -20 - +80 °C (-4 - +176 °F)
PG 13.5
earth
connection
Fig. 17.
10.1.2
ND800/K06B layout
Markings
The limit switch is provided with an identification plate sticker, see
Fig. 18. Identification plate markings from top to bottom are:
Type designation
Electrical values
Enclosure class
Temperature range
Conduit entry
Serial number
The type designation is described in Chapter 13.
Fig. 18.
Identification plate
Weight:
Approx. 0.8 kg (1.8 lbs) (limit switches only)
Materials:
Body:
Internal parts:
Sealing:
Aluminium alloy, epoxy-coated
Stainless steel and plastic
Nitrile and neoprene rubber
10.1.4
Safety precautions
CAUTION:
Do not exceed the limit switch performance limitations!
Exceeding the limitations marked on the limit switch may
cause damage to the limit switch, actuator and valve. Damage
or personal injury may result.
CAUTION:
Observe caution with the live parts of the limit switch!
The limit switches are fed with a voltage that, depending on
the system, may be lethal.
Do not touch any uncovered parts of the wires. Always
disconnect the wires before dismantling the limit switch.
19
10.2
Installing ND800PA/K06B on a valve
controller
The limit switch can be installed on an existing valve controller.
NOTE:
Do not install a ND800/K06B limit switch on a ND800/X valve controller!
If the valve controller is already mounted on an actuator/valve assembly, operate the actuator into the closed
or open position.
Remove the cover (2) and the pointer (65).
Turn the shaft (304) onto the shaft (40). Fasten the screw
(305) using a locking agent such as Loctite. Unfasten the
screws (331) in the cam discs (330).
Mount the housing (300) on the valve controller.
Turn the cam discs (330) to avoid contact with the
microswitches, if needed.
Mount the pointer (65) on the shaft (304).
Adjust the limit switch according to Section 10.4.
10.3
Electrical connections
Before connecting the power, make sure that the electrical specifications and the wiring meet the installation conditions. See the
diagram in Section 11.12. See also the information on the identification plate.
10.4
Adjustment
The pointer (65) need not be removed for adjustment.
When the limit switch is ordered together with the valve and the
actuator, the valve controller switches are factory-adjusted.
The limits can be adjusted by changing the position of the cam discs
(330) on the shaft. The lower switch is activated at the closed limit
and the upper switch at the open limit.
With the actuator in the open or closed position, find the switching
point by turning the cam disc so that the switch changes about 5°-6°
before the limit.
After re-installation of the actuator, first adjust its mechanical limits
according to the valve, then the valve controller, and finally the limit
switch.
When adjustment is completed, turn the pointer (65) so that
the yellow line is parallel with the valve closure member.
LS1 16
15
13
12
K
A
LS2
ND800/K00B
Fig. 19.
Limit switch adjustment, ND800/K06B
10.5
Removal of the limit switch ND800PA/K06B
for accessing the valve controller
Before the protective cover (46) can be removed the limit switch
must be detached.
Remove the cover (2) and the pointer (65).
Loosen the screws (302) and remove the housing (300).
Detach the shaft (304) with cam discs (330).
Proceed with the valve controller as applicable.
Re-install the limit switch according to Section 10.2 and check the
adjustment according to Section 10.4.
10.6
Circuit diagrams
The internal circuitry of the limit switch is shown in the connection
diagram in Section 11.12 and on the sticker inside the cover.
10.7
Maintenance
Regular maintenance of the limit switch is not necessary.
10.8
Ordering spare parts
NOTE:
Always use original spare parts to make sure that the limit
switch functions as intended.
When ordering spare parts, always include the following information:
limit switch type designation (from the name plate or
switch documents)
number of the spare parts list or number of this manual,
part number, part name and quantity required
20
11
DRAWINGS AND PARTS LISTS
11.1
Exploded view and parts list
2
64
66
65
92
3
46
7
107
99
91
97
106
4
103, 104, 105
101 100
126
48
116
109
5
111
96
6
118
123
119
108
102, 104, 105
98
35
1
31
32
44
40
54
52
Item
Qty
Description
Recommended spare
1
2
3
4
5
6
7
31
32
35
40
44
46
48
51
52
54
64
65
66
91
92
1
1
1
1
1
1
1
1
2
4
1
1
1
4
1
1
1
4
1
1
2
2
Housing
Cover
Prestage unit *
Spool valve assembly *
Circuit board pack
Position sensor *
Differential pressure sensor *
Exhaust cover
Screw
Terminal block
Shaft assembly
Washer
Protective cover
Screw
Ear
Screw
Couplings jacket
Screw
Pointer
Screw
O-ring
Screw
x
51
Item
Qty
Description
96
97
98
99
100
101
102
103
104
105
106
107
108
109
111
116
118
119
123
126
1
1
1
4
2
1
1
1
2
2
2
4
1
1
5
2
2
1
2
2
Spool valve body **
Spool **
Gasket
Screw
Spring **
Back stop **
End piece I **
End piece II **
Restriction **
Filter **
Gasket **
Screw **
Adjustable back stop **
O-ring **
Screw
Screw
Screw
Lock ring
O-ring
Screw
x
*) delivered as a module
**) part of the spool valve assembly
Recommended spare
x
21
11.2
Exploded view and parts,
ND800PA/K06B
64
2
361
363
330
331
66
360
302
65
304
305
300
Item
Qty
Description
2
64
65
66
300
302
304
305
312
315
316
330
331
360
361
363
380
1
4
1
1
1
4
1
1
6
2
2
2
2
2
2
2
Cover
Screw
Pointer
Screw
Housing
Screw
Shaft
Screw
Terminal block
End stop
Screw
Cam disc
Screw
Microswitch
Screw
Spring washer
Wire
Recommended spare
316
312
315
380
22
11.3
Mounting parts for B1C/B1J 6-20
actuators
S1
11.4
S2
Item
Qty
Description
Item
Qty
Description
1
2
3
4
28
29
36
1
1
4
4
4
1
1
Mounting bracket
Ear
Washer
Screw
Screw
Screw
Coupling jacket
1
2
3
4
13
14
28
29
1
1
4
4
2
2
4
1
Mounting bracket
Draught piece
Washer
Screw
Screw
Hexagon nut
Screw
Screw
Mounting parts for B1C/B1J 25-50,
B1C 502 and B1J322 actuators
Item
Qty
Description
1
2
3
4
27
28
1
1
4
4
4
4
Mounting bracket
Draught piece
Washer
Screw
Washer
Screw
23
11.5
11.6
Mounting parts for Quadra-Powr®, ST,
SP and Valv-Powr® actuators
Item
Qty
Description
1
2
4
28
29
30
35
1
1
4
4
1
4
1
35
1
36
1
Mounting bracket
Ear
Screw
Screw
Screw
Screw
Adapter plug
(QP II 1/S- 6/S only)
Adapter plate
(QP II 2B/K thr. 6_/K)
Coupling jacket
Item
Qty
Description
1
2
3
4
5
6
7
8
9
10
1
2
1
4
4
1
4
4
4
4
Mounting bracket
Coupling half
Adapter
Screw
Hex nut
Screw
Screw
Washer
Screw
Washer
Item
Qty
Description
4
38
4
2
Screw
O-ring
Mounting parts for EC07-14 actuators,
rising signal opens valve
EC07-14
4
38
ND800/S4
24
11.7
Mounting parts for EC05 actuators,
rising signal opens/closes valve
EC05
9
39
Item
Qty
Description
4
9
28
38
39
4
2
2
4
1
Screw
Screw
Screw
O-ring
Coupling plate (acc. to action)
Item
Qty
Description
4
38
244
245
4
2
2
2
Screw
O-ring
Plug
O-ring
28
4
38
ND800/S4
11.8
Mounting parts for EC07-14 actuators,
rising signal closes valve
4
244, 245
38
tubing
EC07-14
25
11.9
Mounting parts for EJ05-14 actuators
ND800/S4
4
38
244, 245
Item
Qty
Description
4
38
244
245
4
2
1
1
Screw
O-ring
Plug
O-ring
26
11.10 Mounting parts for D/R linear actuators
5
4
3
LEVER ARM IN MID-STROKE POSITION
DISTANCE FROM THE CENTER OF FEEDBACK ARM
TO THE CENTER OF ACTUATING PIN
2
9
3.57
2.87
7
1
2.50
1.00" UP TO 5.00"
STROKE @ 70° ROTATE
1.61
6
11
1.07
0.80
10
35°
0.71
3.50
8
60°
ROTATE
FOR 3/4"
STROKE 30°
12
13
1"
3/4"
1-1/8" 1-1/2"
3/4"
1-1/8" 1-1/2"
2-1/4"
3-1/2"
2-1/4"
3-1/2"
STROKE
3-1/2"
3-1/2"
3-1/2"
3-1/2" IN INCHES
70° 1.00 1.13
1.50
2.25
5.00
1"
14
0.75 STROKE
MAKE SURE THIS MARK ON THE
LEVER ARM IS IN THE SAME
QUADRANT AS THE MARK ON
THE FLAT OF THE SHAFT.
0.65
FOR
3/4" STROKE
LEVERARM SPRING POSITION
TO BE AGAINST ACTUATOR PIN
1"
3/4"
3/4"
1-1/8" 1-1/2"
2-1/4"
3-1/2"
4"
5"
1-1/8" 1-1/2"
2-1/4"
3-1/2"
4"
5"
STROKE
IN INCHES
1"
CL
ACTUATOR
90°
1"
3/4"
3/4"
1-1/8" 1-1/2"
2-1/4"
3-1/2"
4"
5"
STROKE
1-1/8" 1-1/2"
2-1/4"
3-1/2"
4"
5"
IN INCHES
4.00
MID STROKE
1"
Item
Qty
Description
1
2
3
4
5
6
7
9
10
11
12
13
14
1
2
2
2
2
1
4
1
1
2
4
4
4
Mounting bracket
Screw
Flat washer
Lock washer
Hex nut
Positioner lever arm
Linkage arm spring
Positioner pin
Screw
Lock washer
Screw
Lock washer
Flat washer
12
11
14
1
11
3
6 5
19
18
15
17
8
7
2
4
16
14.3 (20 mm)
21.4 (30 mm)
28.6 (40 mm)
Distance from shaft center to carrier
bolt according to stroke.
Scale
71.4 (100 mm)
64.3 (90 mm)
57.1 (80 mm)
50 (70 mm)
Stroke 60 - 100 mm
Stroke 20 - 60 mm
35.7 (50 mm)
42.8 (60 mm)
The mark on the shaft should stay in this sector!
70°
9
Feedback lever in horizontal position at mid travel of stroke.
27
11.11 Mounting parts for linear actuators
with IEC 60534 mounting face
(20 - 100 mm)
Stroke
28
11.12 Connections
11.12.1 Connection diagram for ND800PA/K06B
LIMIT SWITCH (.../K06B)
RD
A
VALVE
CONTROLLER
(ND800)
BU
12
WH
BK
13
GY
BU
15
YE
BK
16
BN
A = Open (LS2)
RD
K
K = Closed (LS1)
LS1
LS2
ND84../X./K06BX only
PG13,5
ND84../../K06B
With limit switch OMRON D2VW-01 micro switches
Connection diagram shows limit switch when actuator is in intermediate position.
Switch A (upper) is activated at the open limit of the travel and switch K (lower) at the closed limit.
29
11.12.2 Device gland receptacles
1:
3:
4:
+Voltage, brown
- Voltage, blue
Shield, black
ND84.../...P1 = male type WEIDMÜLLER 945565, PG13.5/M12
1:
3:
4:
+Voltage, brown
- Voltage, blue
Shield, grey
ND84.../...P2 = male minifast type TURCK RSFV48/13.5
30
12
DIMENSIONS
ND800PA/S1
1/4NPT
23
33
1.30 0.90
117
4.60
C2
F05-Ø50(VDI/VDE3845)
23
0.90
M6/10
(35.4)
(35.4)
(1.39)
(1.39)
4
0.16
C1
M6x12
(3)
23.5
(0.12) 25 0.93
0.98
33
1.30
S
PG13.5
21
0.83
ND800PA/S1/K00B
F05-ø50
33
1.30
(35.4)
(1.39)
26.8
1.05
172
6.77
33
1.30
55
2.16
S
PG13.5
C2
13.9
0.55
23.5
0.93
38
1.49
C1
70
2.76
46
1.81
M6 / 10
23
0.90
ø6
ø0.24
PG13.5
(35.4)
(1.39)
1/4 NPT
47.5
1.87
S
4
0.16
C1
39.5
1.55
137
5.39
5
0.20
23
0.90
C2
44
1.73
29
1.14
ø15
ø0.59
2
0.08
ND800A
13
0.51
5.6
0.22
137
5.39
ND800/S4
(26)
10.5
0.41
S
C1
= 1/2 NPT
= M20x1.5
= R1/2
(1.02)
C2
-L
-I
-NJ
G1/4
M5 / 18
(VDI/VDE 3845)
21
0.83
ND800/S1
31
13
CONTROL DRAWINGS
13.1
FMRC control drawing for ND84_/MU
(ND84_/NU)
HAZARDOUS (CLASSIFIED) LOCATION
Class I, Divisions 1 and 2, Groups A, B, C, D
Class I, Zone 0, AEX ia, Group IIC T5/T6
T5: Ta = -40...65 C
T6: Ta = -40...50 C
METSO Field Systems OY:
ND83_ /MU or ND84_ /MU
Fieldbus Valve Controller
Entity Parameters:
Ui ≤ 22,5 V
Ii ≤ 380mA
Pi ≤ 5,32W
Ci < 5nF
Li < 10 H
NONHAZARDOUS LOCATION
FMRC approved associated
apparatus with applicable division
and group or zone and group
approval e.g.:
Fieldbus IS barrier
Segment coupler with
integrated barrier
Entity Parameters:
Uo ≤ Ui
Io
≤ Ii
Co ≤ Ci + Ccable
Lo ≤ Li + Lcable
Notes:
1. For installation in a Division 1 hazardous (classified) location, the wiring must be in accordance with the
National Electrical Code Article 504-20. For installation in a Zone 0 hazardous (classified) location, the
wiring must be in accordance with the National Electrical Code Article 505.
2. The Entity Concept allows interconnection of intrinsically safe and associated apparatus not specifically
examined in combination as a system when the approved values of Voc ( or Uo) and Isc (or Io) for the
associated apparatus are less than or equal to Vmax (or Ui) and Imax (or Ii) for the intrinsically safe
apparatus and the approved values of Ca (or Co) and La (or Lo) for the associated apparatus are greater
than Ci + Ccable, Li + Lcable, respectively for the intrinsically safe apparatus.
3. Note associated apparatus with only Zone 1 approved connections limits the mounting of the valve
controller to Zone 1. Also associated apparatus with Group IIB connections or if in minimum one device at
the fieldbus cable is specified only with IIB limits the complete fieldbus segment to IIB.
4. The metallic enclosure of the ND800 valve controller must be grounded and bonded in accordance with
the National Electrical Code ANSI / NFPA 70, Article 250
5. The cover of the ND800 enclosure may be removed in hazardous location for reading the display and
operating the push buttons. The internal cover of the electronic circuits must not be removed in hazardous
areas.
6. The valve controllers ND83_/NU and ND84_/NU are non-incendive for Class I, Division 2, Groups A,B,C
and D; Class I, Zone 2, Groups IIC, IIB, IIA T5 / T6 hazardous (classified) locations and need to be
connected to an associated apparatus with a max. output voltage of 22,5V.
32
Control Drawing for Installations according to the FISCO Model:
This concept may only be applied if all devices at the fieldbus line are approved and specified for
the FISCO model, also the barrier of Segment coupler must be specified for the FISCO model.
HAZARDOUS (CLASSIFIED) LOCATION
NONHAZARDOUS LOCATION
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 0, AEX ia, Group IIB/IIC T5/T6
T5: Ta = -40...65 C
T6: Ta = -40...50 C
METSO Field Systems OY:
ND83_ /MU or ND84_ /MU
Fieldbus Valve Controller
Entity Parameters:
Ui ≤ 22,5V
Ii ≤ 380mA
Pi ≤ 5,32W
Ci < 5nF
Li < 10 H
FMRC approved associated
apparatus with applicable zone and
group approval which is specified for
the FISCO model e.g.:
Fieldbus IS barrier
Segment coupler with
integrated barrier
Entity Parameters:
Uo ≤ Ui
Io
≤ Ii
Po ≤ Pi
Notes:
7. For installation in a Division 1 hazardous (classified) location, the wiring must be in accordance with the
National Electrical Code Article 504-20. For installation in a Zone 0 hazardous (classified) location, the
wiring must be in accordance with the National Electrical Code Article 505.
8. The Entity Concept together with the FISCO model allows interconnection of intrinsically safe and
associated apparatus not specifically examined in combination as a system when the approved values of
Uo and Io and Po for the associated apparatus are less than or equal to Ui and Ii and Pi for the
intrinsically safe apparatus. If the cable is specified with the following parameters:
R = 15 .150 O hm / km
L = 0,4 1mH / km
C = 80 .200n F / km (inclusive shielding)
A max. cable length of 5000m is allowed if all devices connected to the cable are approved and specified
to the FISCO model.
9. Note associated apparatus with only Zone 1 approved connections limits the mounting of the valve
controller to Zone 1. Also associated apparatus with Group IIB connections or if in minimum one device at
the fieldbus cable is specified only with IIB limits the complete fieldbus segment to IIB.
10.The metallic enclosure of the ND800 valve controller must be grounded and bonded in accordance with
the National Electrical Code ANSI / NFPA 70, Article 250
11.The cover of the ND800 enclosure may be removed in hazardous location for reading the display and
operating the push buttons. The internal cover of the electronic circuits must not be removed in hazardous
areas.
33
13.2
CSA control drawing for ND84_/XU
(ND84_/ZU)
HAZARDOUS (CLASSIFIED) LOCATION
Class I, Divisions 1 and 2, Groups A, B, C, D
Class I, Zone 0, AEX ia, Group IIC T5/T6
T5: Ta = -40...65 C
T6: Ta = -40...50 C
METSO Field Systems OY:
ND83_ /XU or ND84_ /XU
Fieldbus Valve Controller
Entity Parameters:
Ui ≤ 22,5V
Ii ≤ 380mA
Pi ≤ 5,32W
Ci < 5nF
Li < 10 H
NONHAZARDOUS LOCATION
CSA approved associated apparatus
with applicable division and group or
zone and group approval e.g.:
Fieldbus IS barrier
Segment coupler with
integrated barrier
Entity Parameters:
Uo ≤ Ui
Io
≤ Ii
Co ≤ Ci + Ccable
Lo ≤ Li + Lcable
Notes:
1. For installation in a Division 1 hazardous (classified) location or a Zone 0 / 1 hazardous (classified)
location, the wiring must be in accordance with the Canadian Electrical Code CSA C22.1 Part 1.
2. The Entity Concept allows interconnection of intrinsically safe and associated apparatus not specifically
examined in combination as a system when the approved values of Voc ( or Uo) and Isc (or Io) for the
associated apparatus are less than or equal to Vmax (or Ui) and Imax (or Ii) for the intrinsically safe
apparatus and the approved values of Ca (or Co) and La (or Lo) for the associated apparatus are greater
than Ci + Ccable, Li + Lcable, respectively for the intrinsically safe apparatus.
3. Note associated apparatus with only Zone 1 approved connections limits the mounting of the valve
controller to Zone 1. Also associated apparatus with Group IIB connections or if in minimum one device at
the fieldbus cable is specified only with IIB limits the complete fieldbus segment to IIB.
4. The metallic enclosure of the ND800 valve controller must be grounded and bonded in accordance with
the Canadian Electrical Code CSA C22.1
5. The cover of the ND800 enclosure may be removed in hazardous location for reading the display and
operating the push buttons. The internal cover of the electronic circuits must not be removed in hazardous
areas.
6. The valve controllers ND83_/ZU and ND84_/ZU are non-incendive for Class I, Division 2, Groups A,B,C,
and D; Class I, Zone 2, Groups IIC, IIB, IIA T5 / T6 hazardous (classified) locations and need to be
connected to an associated apparatus with a max. output voltage of 22,5V.
34
Control Drawing for Installations according to the FISCO Model:
This concept may only be applied if all devices at the fieldbus line are approved and specified for
the FISCO model, also the barrier of Segment coupler must be specified for the FISCO model.
HAZARDOUS (CLASSIFIED) LOCATION
NONHAZARDOUS LOCATION
Class I, Divisions 1 and 2, Groups A, B, C, D
Class I, Zone 0, AEx ia, Group IIB/IIC T5/T6
T5: Ta = -40...65 C
T6: Ta = -40...50 C
METSO Field Systems OY:
ND83_ /XU or ND84_ /XU
Fieldbus Valve Controller
Entity Parameters:
Ui ≤ 22,5V
Ii ≤ 380mA
Pi ≤ 5,32W
Ci < 5nF
Li < 10 H
CSA approved associated
apparatus with applicable zone and
group approval which is specified for
the FISCO model e.g.:
Fieldbus IS barrier
Segment coupler with
integrated barrier
Entity Parameters:
Uo ≤ Ui
Io
≤ Ii
Po ≤ Pi
Notes:
7. For installation in a Division 1 hazardous (classified) location or a Zone 0 / 1 hazardous (classified)
location, the wiring must be in accordance with the Canadian Electrical Code CSA C22.1 Part 1.
8. The Entity Concept together with the FISCO model allows interconnection of intrinsically safe and
associated apparatus not specifically examined in combination as a system when the approved values of
Uo and Io and Po for the associated apparatus are less than or equal to Ui and Ii and Pi for the
intrinsically safe apparatus. If the cable is specified with the following parameters:
R = 15 .150 O hm / km
L = 0,4 1mH / km
C = 80 .200n F / km (inclusive shielding)
A max. cable length of 5000m is allowed if all devices connected to the cable are approved and specified
to the FISCO model.
9. Note associated apparatus with only Zone 1 approved connections limits the mounting of the valve
controller to Zone 1. Also associated apparatus with Group IIB connections or if in minimum one device at
the fieldbus cable is specified only with IIB limits the complete fieldbus segment to IIB.
10.The metallic enclosure of the ND800 valve controller must be grounded and bonded in accordance with
the Canadian Electrical Code CSA C22.1
11.The cover of the ND800 enclosure may be removed in hazardous location for reading the display and
operating the push buttons. The internal cover of the electronic circuits must not be removed in hazardous
areas.
35
14
TYPE CODING
VALVE CONTROLLER ND800
LIMIT SWITCH (ND800/K00 or ND800/I00)
1.
2.
1.
2.
3.
4.
5.
ND
8
4
2
-
sign
PRODUCT GROUP
ND
Valve controller
sign
SERIES CODE
6.
/
S1
8
3.
4.
5.
sign
INPUT SIGNAL
4
Profibus PA
Bus voltage 9-32 VDC
Transmission system acc. to IEC 1158-2. Normative parts
acc. to EN 50170 Vol. 2.
sign
SPOOL VALVE
CONNECTIONS
(S, C1, C2)
1
Ø 1 mm, double acting, available
only with EC actuators
1/4 NPT, G 1/4 (S4)
2
Ø 2 mm, double acting
1/4 NPT
6
Ø 6 mm, double acting
1/4 NPT
11
Ø 1 mm, 3-way spool valve,
single action, available only with
EJ actuators
1/4 NPT, G 1/4 (S4)
21
Ø 2 mm, 3-way spool, single action
1/4 NPT
61
Ø 6 mm, 3-way spool, single action
1/4 NPT
sign
ACTION
-
Double action, without sign. 4th sign should be 1, 2 or 6.
In connection with B_CU6 to B_CU11, EC10 and EC12 actuators
4th sign must be 2. In connection with EC5 and EC07 actuators
4th sign must be 1.
Single action, without sign. 4th sign should be 21 or 61.
In connection with B_JU8, QP1, QP2, EJ07 and EJ10 actuators
4th sign should be 21. In connection with EJ05 4th sign must be 11.
Not appplicable with double acting actuators.
A
6.
Single action, linear motion, applicable to Metso Automation
D/R series diaphragm actuator. Not applicable to attachment face
according to VDI/VDE 3845 (6th sign S1).
21A is for RA and DA.
61A is for RB, RC, RD, RE and DB, DC, DE.
Also applicable to linear actuators acc. to IEC 60534-6-1
with own linkage set. 4th sign 21 or 61 acc. to stroke volume
for single action. Specify the stroke (20-60 mm or 60-100 mm).
sign
OPTIONS
-
Standard, IP 65 enclosure, NEMA 4 and 4X. Built-in display and
local keypad. PG 13,5 conduit entry. Without sign.
Temperature range -20 ˚C... +85 ˚C / -4 ˚F... +185 ˚F.
Supply voltage 9-32 VDC. Operating current over full ambient
temperature and supply voltage range is 20.1-23.45 mA.
At 24 VDC typical operating current is 21.8 mA
C
Low temperature, -40 ˚C / -40 ˚F.
X
Intrinsically safe construction acc. to EN 50014, EN 50020
and EN 50284.
II 1G (Zone 0), EEx ia IIC T5/T6
Ex nL IIC T5/T6
Ex nC IIC T5/T6
Temperature range T5; -20 ˚C...+65 ˚C / -4 ˚F...+149 ˚F,
T6; +50 ˚C / +122 ˚F.
Ui = 17.5 VDC, Ii = 360 mA (pending).
XU
CSA Class I, Divisions 1 and 2, Groups A, B, C and D.
CSA Class I, Zone 0, AEx ia, Group IIC T5/T6.
Temperature range T5; -20 ˚C...+65 ˚C / -4 ˚F...+149 ˚F,
T6; +50 ˚C / +122 ˚F.
1/2 NPT conduit entry. Not available with any limit switches 7. sign I or K.
Ui = 17.5 VDC, Ii = 360 mA (pending).
7.
8.
—
7.
8.
9.
K
06B
-
ZU
CSA Class I, Division 2, Groups A, B, C and D.
CSA Class I, Zone 2, AEx ia, Group IIC T5/T6.
Temperature range T5; -20 ˚C...+65 ˚C / -4 ˚F...+149 ˚F,
T6; +50 ˚C / +122 ˚F
1/2 NPT conduit entry. Not available with any limit switches 7. sign I or K
Ui = 17.5 VDC, Ii = 360 mA (pending).
MU
FM Class I, Division 1, Groups A, B, C and D.
FM Class I, Zone 0, AEx ia, Group IIC T5/T6.
Temperature range T5; -20 ˚C...+65 ˚C / -4 ˚F...+149 ˚F,
T6; +50 ˚C / +122 ˚F.
1/2 NPT conduit entry.Not available with any limit switches 7.sign I or K.
Ui = 17.5 VDC, Ii = 360 mA (pending).
NU
FM Class I,Division 2,Groups A,B,C and D.
FM Class I, Zone 2, AEx ia, Group IIC T5/T6.
Temperature range T5; -20 ˚C...+65 ˚C / -4 ˚F...+149 ˚F,
T6; +50 ˚C / +122 ˚F.
1/2 NPT conduit entry. Not available with any limit switches 7. sign I or K.
Ui = 17.5 VDC, Ii = 360 mA (pending).
S1
Valve controller attachment face acc. to standard VDI/VDE 3845,
equipped with an H-clip. When valve controllers are separate
deliveries, VDI/VDE 3845 ear is supplied. Not applicable to linear
actuators (5th sign A).
S4
Valve controller attachment face only for EC/EJ actuators
without tubings. Pneumatic connections C, S1, S2; G 1/4.
A
Pressure gauges, scale bar/psi/kPa, basic material brass, nickel plated,
housing stainless steel, glycerine filled. 5th sign always defined.
Temperature range -40 ˚C... +70 ˚C / -40 ˚F... +158 ˚F.
P1
Connection plug male , Weidmüller 945565, PG13.5/M12.
Not available with accessories L, I, NJ.
P2
Connection plug male minifast, Turck RSFV48 /13.5.
Not available with accessories L, I, NJ.
Y
Special construction, to be specified.
sign
LIMIT SWITCH CODE
K
Micro swithes, defined with 8. sign
sign
LIMIT SWITCH TYPE
Micro switches, 2 pcs.
9.
06B
OMRON D2VW-01, gold plated contacts 30 VDC, I < 100 mA.
Bus powered, no external power needed. Temperature range
-40 ˚C ... +80 ˚C / -40 ˚F ...+176 ˚F. When option of ND84
valve controller is X (6. sign) then 9. sign always be X.
Temperature range according to valve controller.
sign
OPTION OF LIMIT SWITCH
-
Standard IP 65 enclosure.NEMA 4 and 4X.PG 13.5 conduit entry (4 pcs).
Temperature range according to switch type.
X
Intrisically safe construction. DEMKO EEx ia IIC T6
certification (EN 50014, EN 50020).
Temperature range according to valve controller type.
P
Connection plug according to DIN 43650A/ISO 4400 (PG11).
Not available with ND82, ND83, ND84 valve controllers
options X, XU, ZU, MU, NU and accessories L, I, NJ.
Y
Special construction, to be specified.
EXTERNAL CONNECTION
PARTS
K
Filter regulator for supply air, type BELLOFRAM 51FR. Pressure
gauge, scale bar/psi/kPa, basic material bras, nickel plated, housing
stainless steel, glycerine filled. Specified on the option sticker. Filter
size 5 µm. Temperature range -18 ˚C... +52 ˚C / 0 ˚F... +125 ˚F.
Filter regulator with higher capacity needed for actuators
BC40 and BJ32.
L
PG13.5 / 1/2 NPT conduit entry.
Specified in the option sticker
I
PG13.5 / M20x1,5 conduit entry.
Specified in the option sticker.
NJ
PG13.5 / R1/2 (PF1/2) conduit entry.
Specified in the option sticker.
Metso Field Systems Inc.
Europe, Levytie 6, P.O.Box 310, 00811 Helsinki, Finland. Tel.int +358 20 483 150. Fax int. +358 20 483 151
North America, 42 Bowditch Drive, P.O. Box 8004, 01545 Shrewsbury, USA. Tel. int +1-508-852-3567. Fax int. +1-508-852-3562
Latin America, Av. Central, 181- Chácaras Reunidas, 12238-430, São Jose do Campos, SP BRAZIL.
Tel. int. +55 12 335-3500, Fax int. +55 12 335-3535
Asia Pacific, 501 Orchard Road, #05-09 Wheelock Place, 238880 Singapore. Tel. int. +65 735 5200. Fax int. +65 735 4566
www.metsoautomation.com

advertisement

Key Features

  • Fieldbus powered
  • Profibus PA compatible
  • Automatic calibration
  • Self-tuning
  • Local keyboard & display
  • Simatic PDM support

Frequently Answers and Questions

How do I calibrate the ND800PA?
You can calibrate the ND800PA either automatically or manually using the local keyboard. The procedure involves moving the valve to its open and closed positions and then pressing the 'r' key to initiate self-tuning.
What is the function of the 'g' parameter?
The 'g' parameter represents the gain of the control algorithm. It affects the speed of response and the degree of overshooting. You can adjust 'g' to fine-tune the control performance, but ensure it remains stable.
What type of actuators are compatible with the ND800PA?
The ND800PA can be used with either cylinder or diaphragm type pneumatic actuators for rotary or linear valves. The instruction manual provides details on mounting the controller for different actuator types.

Related manuals

Download PDF

advertisement