EnergAir metacentre DX Box Technical Manual
The EnergAir metacentre DX Box is a device that allows you to connect two air compressors together, effectively grouping them as a single unit for control. It can work with compressors of different capacities, allowing you to manage the load efficiently, especially when meeting fluctuating demand. The DX Box also offers additional functionalities such as local pressure sensor connectivity and an optional remote output.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
31
MANY0702A.GB – Metacentre DX Box Technical Manual bar TM DX Box Metacentre DX Box Index 1.0 Safety Precautions 1.1 Installation 1.2 Operational 1.3 Maintenance and Repair 2.0 Introduction 2.1 Management System Connectivity 2.2 Basic Function 2.3 Operation 3.0 Installation 3.1 Guidelines 3.2 Location 3.3 Power Supply 3.4 RS485 Connection 3.5 Compressor Interface PCB 3.6 System Pressure Sensor 3.7 Delivery Pressure Sensor (Option) 3.8 Auxiliary Fault Inputs (Option) 3.9 Remote Output (Option) 4.0 Commissioning 4.1 Commissioning Procedure 4.2 System Management Unit 4.3 Menu Navigation 4.4 Menu Items and Settings 4.5 Diagnostics 5.0 Operation 5.1 User Interface 5.2 Display 5.3 Status Symbols 5.4 Indications 5.5 Compressor Identification 5.6 Operation 5.7 Power Failure Auto-Restart 5.8 Failure Modes 5.9 Compressor Fault 5.10 DX Box Fault 5.11 Pressure Sensor Fault 6.0 Parts List 7.0 Technical Data 8.0 Wiring Connection Diagram Page 1 Technical Manual 1. Safety Precautions The product must only be operated at the supply voltage and frequency for which it is designed. ALWAYS EMPLOY SAFE WORKING PRACTISE AND PROCEDURES When mains power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit. WARNING: Risk of Danger WARNING: Risk of Electric Shock WARNING: Risk of High Pressure WARNING: Consult Manual When installing, commissioning, operating or carrying out service or maintenance on a product, personnel must use safe working practise and observe all relevant local health and safety requirements and regulations. Attention of users in the UK is drawn to the Health and Safety at Work Act, 1974, and to the Regulations and Recommendations of the Institution of Electrical Engineers (IEE). Lethal voltages are used within the product. Use extreme caution when carrying out electrical checks. Isolate the power supply before starting any maintenance work. It is not possible to anticipate every circumstance that might represent a potential hazard. If the user employs an operating procedure, an item of equipment or a method of working which is not specifically recommended the user must ensure the product will not be damaged or made unsafe and that there is no risk to persons or property. Failure to observe safety precautions or implement safe working practises may be considered dangerous practice or misuse of the product. 1.2 Installation Installation work must only be carried out by a competent person under qualified supervision. A fused isolation switch must be fitted between the main power supply and the product. The product should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times. If raised platforms are required to provide access to the product they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides. Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. This work must only be carried out by a qualified electrician or technician equipped with the correct tools and appropriate protection against electrical hazards. All air compressors and/or other machine equipment connected too, and controlled by, the product should have a warning sign attached stating ‘THIS UNIT MAY START WITHOUT WARNING' next to the display panel. If an air compressor and/or other machine equipment connected too, and controlled by, the product is to be started remotely, attach warning signs to the machine stating ‘THIS UNIT CAN BE STARTED REMOTELY’ in a prominent location, one on the outside of the machine, the other inside the machine control compartment. 1.3 Service Maintenance and Repair Service, maintenance, repairs or modifications must only be carried out by competent personnel under qualified supervision. If replacement parts are required use only genuine parts from the original equipment manufacturer, or an alternative approved source. Carry out the following operations before opening or removing any access panels or carrying out any work on the product :• • Isolate from the main electrical power supply. Lock the isolator in the 'OFF' position and remove the fuses. Attach a label to the isolator switch and to the product stating ‘WORK IN PROGRESS - DO NOT APPLY VOLTAGE'. Do not switch on electrical power or attempt to start the unit if such a warning label is attached. Ensure that all instructions concerning operation and maintenance are strictly followed and that the complete product, with all accessories and safety devices, is kept in good working order. The accuracy of sensor devices must be checked on a regular basis. They must be renewed when acceptable tolerances are exceeded. Always ensure any pressure within a compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device. The product must only be operated by competent personnel under qualified supervision. The product must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis. Never remove or tamper with safety devices, guards or insulation materials fitted to the unit. Do not paint the control facial or obscure any indications, controls, instructions or warnings. 1.3 Operation Page 2 Metacentre DX Box 2. INTRODUCTION The DX Box is designed to connect two load/unload air compressors to a system management unit, using a 2-wire RS485 data cable up to 500m (1650ft) in length. The DX Box is designed specifically to ‘group’ two compressors together as a single coherent unit. The system management unit will detect and manipulate the two compressors as a single multiple step or variable output compressor unit. The DX Box is able to manipulate two identical capacity compressors to form a single ‘group’ that will act in an identical manner as a 3-step compressor. The DX Box is also able to manipulate two differential capacity compressors providing demand matched control and sequence to form a single ‘group’ that will act in an identical manner as a variable stepping output, compressor. This functionality provides the ability to: a) Group two adjacent air compressors together as a single coherent unit. b) Combine two similar capacity compressors together to form a threestep variable output group acting as a single coherent variable output unit. c) Take advantage of a small or minimal capacity compressor, grouped together with a medium or higher capacity compressor, to form a high capacity, variable output, group acting as a single variable output ‘top-up’ compressor. d) Exceed the maximum compressor control capability of a system management unit by combining compressors together as one. Two single pressure switch control type air compressors can be connected to the DX Box using a 6-wire cable and a compressor interface PCB (i-PCB). The ‘i-PCB’ connections are identical to an system management unit. The DX Box also provides optional ‘local pressure sensor’ connections. The compressor delivery pressures, local system pressure and air treatment differential pressures can be displayed. The monitored local pressure is available on the system network and can be utilised by an system management unit for advanced pressure related functions. Any number of DX Boxes can be connected to an system management unit as long as the total number of single compressors and/or groups does not exceed the total number of compressors for the system management unit model. 2.1 Management System Connectivity DX Box 1 2 #1 3 #2 The DX Box connects to an ystem management unit using an industrial two wire RS485 data network (Multi485). 2.2 Basic Function The DX Box is a ‘Duel unit eXtension’ to a system management unit providing the ability to group two individual air compressors together in to one duel ‘group’ acting as a single coherent unit. The DX Box provides additional ‘i-PCB’ connectivity. The DX Box can also be used to provide ‘iPCB’ connectivity at a remote location beyond the maximum distance specification of direct system management unit connection. 2.3 Operation 2.3.1 Timer Rotation Mode (Tr) A #1 50% 1 2 B #2 50% = 100% A B B A Timer Rotation should be used when the two compressors have the same (50:50), or very similar, output capacity. The DX Box will assign one compressor as ‘Duty’ and the other as ‘Standby’. The duty compressor will always be loaded first and the standby used as and when required to meet demand. The duty and standby assignment will be changed at every ‘Interval Time’ (adjustable). Page 3 Technical Manual 2.3.2 Automatic Mode (Ar) A B #1 65% 0% 35% 65% 100% #2 35% = 100% A A B B Automatic mode can be used when the compressor capacities are different. The DX Box will utilise each compressor as required to match output to demand. This mode enables the compressor ‘group’ to behave in the same manner as a single (multiple step) variable output unit. The set ‘Interval Time’ is ignored in this mode, the DX Box will continuously evaluated utilisation to match demand. For example: If demand can be satisfied by the smaller of the two compressors (demand < 36%) the DX Box will utilise the lower capacity compressor (B). If demand increases above the output capacity of the smaller compressor, but within the capacity of the larger capacity compressor, the DX Box will utilise the larger capacity compressor (A). If demand exceeds to capacity of the larger capacity compressor the DX Box will load the larger compressor continuously and utilise the smaller capacity compressor to regulate as required. 2.3.3 Management System Integration When integrated with a system management unit the DX Box compressor ‘group’ will respond in ‘Top-Up’ mode or ‘Base-Load’ mode as dictated by the management unit. The assigned mode of response will change from time-to-time dependant on the set sequencing mode of the management unit. In Top-Up’ mode the DX Box will allow variable capacity control (as described above) dependant on demand. In ‘Base-Load’ mode the DX Box will fully load both compressors to provide full base-load capacity output. Page 4 The DX Box ‘group’ unit should be set as a variable output unit on the management system. The management system will fully utilise the variable output capacity capability of the DX Box ‘group’ and report the percentage of utilisation of the ‘group’ in the same manner as a single variable output compressor. 2.3.4 Percentage Capacity The capacity of each compressor is expressed, and set, as a percentage of the combined output capacity of both compressors. For example: If the larger compressor #1 (A) has an output capacity of 13.0m3/min, and the smaller #2 (B) compressor an output capacity of 7.0m3/min, the total combined output of the DX Box ‘group’ equates to 20.0m3/min. Total Capacity (20.0m3/min.) = 100% Compressor #1 (A) = 65% Compressor #2 (B) = 35% 2.3.5 Compressor Failure Mode If one compressor in the DX Box ‘group’ suffers a shutdown failure, or is manually stopped, the DX Box will indicate an ‘Alarm’ condition. The remaining compressor will continue to function and the DX Box will continue to operate at reduced capacity. If both compressors suffer a shutdown failure, or are manually stopped, the DX Box will indicate a shutdown ‘Trip’ condition. Metacentre DX Box 3. Installation 3.1 Guidelines It is recommended that installation and commissioning be carried out by an authorised and trained product supplier. 3.2 Location The DX Box is wall mounting using conventional screw fixings. The DX Box can be located remote from the compressor units but within 100m (330ft) cable length from each compressor and within 100m (330ft) cable length from any pressure sensor option (if applicable). 3.3 Power Supply A fused switching isolator must be installed to the main incoming power supply, external to the DX Box. The isolator must be fitted with a fuse of the correct rating to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations). XPM-TAC24 1 2 3 1 4 2 3 4 X04 N L E E RS485 Note: Polarity is important. RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use earth shielded cables, securely bonded to a known good earth at one end. In addition, give careful consideration to cable routing during installation. 1) Never route an RS485 data communications or low voltage signal cable alongside a high voltage 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle. 2) If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor unit to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield. VOLTAGE SELECT X01 N L E L1 L2 28 27 X07 26 25 230Vac 1 2 3 4 X04 VOLTAGE SELECT 115Vac 3) Where possible, never route an RS485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna). Check the input voltage select link wires on the DX Box power supply PCB, adjust if necessary. 3.4 System RS485 Connection The DX Box is intended to operate as part of a managed system. Connection to the system management unit is two-wire, twisted pair, earth shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07. Page 5 Technical Manual 3.5 Compressor Interface PCB An ‘i-PCB’ is designed for connection to an DX Box controller using a six-wire (earth shielded) cable no greater than 100m (330ft) in length. Each compressor in the system must be assigned an identification number from 1 up to the number of compressors in the system. The identification number should be clearly indicated on each compressor for operational reference. The DX Box can be connected to any two compressors in an system management unit network. The compressor identification numbers will need to be re-designated to reflect that the two compressors are now in a single coherent group and will be regarded by the management system as a single unit. The ‘i-PCB’ of the first compressor (#1 or ‘a’) to be connected to the DX Box must be connected to the six terminals dedicated for compressor reference #1. The ‘i-PCB’ of the second compressor (#2 or ‘b’) to be connected to the DX Box must be connected to the six terminals dedicated for compressor reference #2. C01 C02 i-PCB C04 #2 C03 1 2 3 4 5 6 LED 1 LED 2 X02 DX Box 7 8 9 10 11 12 Interface PCB (i-PCB): C01 C02 i-PCB C04 #1 C03 1 2 3 4 5 6 LED 1 LED 2 X01 The ‘i-PCB’ is a DIN rail mountable unit designed to be installed within the compressor control or switchgear area and connected to the DX Box using a six-wire cable. Each air compressor must be equipped with a load/unload regulation system and, if not regulated with a single electro-mechanical pressure switch, have a facility for a remote load/unload control with the ability to accept a volt-free switching contact input for remote load/unload. Note: consult the air compressor manual or your air compressor supplier/specialist for details before installing the DX Box unit. DX Box 1 2 Page 6 3 4 5 6 The ‘i-PCB’ uses a 12V to 250V ac/dc input voltage detection system and universal relay contact control outputs (250Vac/dc @ 5A maximum). Integrated directly into the circuits of an air compressor, the ‘i-PCB’ avoids the need for additional relays or remote inputs. The ‘i-PCB’ also acts as an electrical barrier between the compressor and the DX Box providing protection and voltage isolation. Metacentre DX Box 3.5.1 Input Functions Ready Input, Alternative Connection Method: The ‘i-PCB’ is fitted with a six-pin terminal C04 for compressor monitoring. The ‘i-PCB’ uses two inputs (Ready and Run) to determine compressor status. An Alarm input can be used if compressor alarm indication is available and required. The Alarm input is optional and is not necessary for system control. In instances where a convenient voltage signal for a compressor ready condition is not available the ‘Ready’ input can be connected directly to a constant compressor control system power supply voltage (12V to 250Vac or dc). This will signal the DX Box that the compressor is ready and available at all times when power is applied to the compressor. The DX has a built-in function to determine when a compressor is not responding, or is in a shutdown condition, regardless of a constant ready signal. If the DX Box requests a compressor to run/load, but fails to detect a RUN signal within 60 seconds, the DX Box will regard the compressor as ‘not ready’ and indicate the compressor as not available. If a RUN signal is detected at any time, the DX Box will automatically reset the compressor ‘not ready’ condition and re-establish control. Ready Input: The ‘Ready’ connection is intended to indicate that the compressor is in a ‘started’ state, has no operational inhibiting fault condition and is ready to respond to DX Box regulation without manual intervention. READY LAMP 0V +V +Vac F1 ALARM RUN READY C04 0Vac The READY input will accept 12V to 250V ac (50/60Hz) or dc. Caution: Do not connect a voltage greater than 250Vac/dc to this input. This input must be connected to the terminals of a ‘ready’ or ‘operational’ lamp, or other circuit of the compressor control system, that will be energised when the compressor is in started (standby or running) condition. The voltage to this input must de-energise when the compressor is stopped and unavailable to produce air upon a load signal, or the Emergency Stop button is pressed, or when the compressor experiences a fault that prevents the compressor from running. READY Safety: Never connect the READY input positive connection directly to the output of a control system transformer, always connect after a fuse or circuit breaker. If a normally closed contact of an Emergency Stop button is included in the compressor power supply circuit, connect after the Emergency Stop button contacts. This will instantly indicate a compressor ‘not ready’ condition if the Emergency Stop button is activated. When the compressor ready lamp, or other control circuit, is energised the ‘i-PCB’ will detect the voltage and signal the DX Box that the compressor is ready and available to load and produce air when a load request signal is given. Note: The ‘i-PCB’ input common terminal must always be connected to the neutral, common or 0V line of the applied input Page 7 Technical Manual Run Input: MAIN (LINE) CONTACTOR 0V Note: The ‘i-PCB’ input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage. +V Alarm Input: The ‘i-PCB’ is equipped with an alarm (or warning) input that can be used to detect alarm or warning conditions. ALARM READY RUN C04 The RUN input will accept 12V to 250V ac (50/60Hz) only (DC cannot be used). Caution: Do not connect a voltage greater than 250V to this input. Note: A fault, that stops the compressor, and/or prevents the compressor from running, is determined from the ‘Run’ and ‘Ready’ inputs; Alarm detection is optional and is not a requirement. Alarm Lamp 0V +V 12V to 250Vac must be applied to the ‘Run’ terminals when the compressor motor is running. This input can be connected to the control terminals A1 and A2 (coil) of the main starter contactor of the compressor. When the compressor control system energises the main contactor, the ‘i-PCB’ will detect the voltage across the contactor coil terminals and signal the DX Box that the compressor is running. Alternatively, if the main contactor coil voltage is greater than 250Vac, a contactor auxiliary switch can be used to apply a suitable voltage to the ‘Run’ input terminals. MAIN (LINE) CONTACTOR +V Run Ready C04 The Alarm input will accept 12V to 250V ac (50/60Hz) or dc. Caution: Do not connect a voltage greater than 250Vac/dc to this input. This input can be connected to the terminals of an alarm lamp or other accessible part of the control circuit that is energised when the compressor is in an alarm condition. 0V +V 0V AUXILIARY SWITCH ALARM RUN If an alarm condition is experienced the compressor alarm lamp, or alarm circuit, will energise. The ‘i-PCB’ will detect the voltage and signal the DX Box that an alarm has occurred. If the compressor has no accessible alarm circuit, or this function is not required, the ‘i-PCB’ alarm terminals can be ignored. READY C04 In instances where a motor starter contactor is not available or accessible, any part of a compressor control circuit that is energised when the compressor is running can be monitored. For example: fan contactor or voltage signal to a remote starter. Page 8 Alarm Note: The ‘i-PCB’ input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage. Metacentre DX Box 3.5.2 Output Functions The DX Box will control the ‘i-PCB’ load/unload relay outputs in accordance with the set system load and unload pressure set points. The ‘i-PCB’ load/unload relay contacts can be used for compressor controllers that have ‘pressure switch’ load/unload regulation. ‘i-PCB’ Internal Output Circuits Note: The local pressure settings of all compressors in the system should be set in a cascaded manner such that the system will operate normally in the event of system management unit inoperability. Note: The NC (normally closed) and NO (normally open) terminal references of the ‘iPCB’ are related to internal connection functions and should not be referenced to the connections of a compressor pressure switch (which will generally be in reverse order). C OUT NO 1 Load C Seq IN NO OUT C 0V 2 IN NC LOAD Relay 3 SEQ Relay 1&2 Two Wire Pressure Switch Connections: IN C 3 OUT NC Lethal voltages may be present on the terminals of the air compressor pressure switch. Isolate the air compressor power supply before starting any work. +V LOAD SOLENOID Contacts :250Vac/dc @ 5A maximum C03 C NC IN OUT 24Vac The C01 and C02 terminal functions of the ‘iPCB’ are intended to control load and unload regulation of the compressor. NO +20V C DI2 NC DI1 NO SEQ LOAD GND CONT UNL C02 Three Wire Pressure Switch Connections: Pressure Switch Regulation: NC C NO NC RUN-ON TIMER C When connected the pressure switch remains in circuit. If the DX Box is stopped or experiences a failure or loss of power, pressure control will automatically revert back to the pressure switch and the compressor will continue to operate in ‘Local’ mode. 0V +V NO For air compressors fitted with an electromechanical pressure switch a six-pin terminal C02 has been provided to enable connection to a pressure switch that has a two wire or three-wire connection. LOAD SOLENOID IN OUT C02 Page 9 Technical Manual Remote Load/Unload Regulation: For air compressors controllers fitted with ‘Remote/Local Pressure Regulation’ digital inputs, a 4-pin connector C01 has been provided. This terminal provides volt free contact closure for load control and also provides volt free contact closure for remote pressure control enable. A remote load enable input provides the facility to change the compressor load regulation from internal control to a remote switching source. For Example: If the compressor controller ‘Local/Remote Pressure Control’ input is a normally open type; Remote when closed, but the ‘Remote Load’ input is a normally closed type; load when open, the ‘i-PCB’ pressure switch terminal contacts can be used to achieve the correct switching logic. C02 NO OUT NC NO IN Note: Compressors that use electronic pressure detection but are not equipped with a remote pressure control enable feature will not automatically revert to local control if the DX Box is stopped or experiences a fault or loss of power. C Local/Remote common Remote Load common C NC Examine the ‘i-PCB’ internal output circuit diagram to establish any desired switching logic that may differ from normal practise. Load and Sequence Connection: COMPRESSOR CONTROLLER INPUTS Local/Remote or Remote Load Enable Remote Load Inputs Common C SEQ C LOAD C01 Note: Compressor controller inputs common voltage may be 0V or +V. The local/remote pressure regulation input and/or remote load input logic of some electronic pressure sensor type controllers are reversed, in this instance the ‘pressure switch’ outputs (terminal C02) can be used to establish alternative logic control connections. Page 10 Do not attempt to utilise the Load/Seq ‘Electronic Pressure Control’ (terminal C01) and the ‘Pressure Switch Control’ (terminal C02) output connections at the same time. These two output functions are internally connected and a short circuit condition and/or malfunction may result. Note: The ‘i-PCB’ connection examples shown in this manual are intended to provide a guide for the majority of compressor control systems in use. Some compressors have variations in operation and/or function; consult your compressor supplier/specialist for advice. Metacentre DX Box 3.5.3 Service Maintenance Switch: (Optional) The ‘i-PCB’ is equipped with a volt-free input (terminal C05) that can be used to remove the compressor from DX Box control without generating a fault condition during maintenance or servicing periods. The DX Box ‘group’ will continue to operate at reduced maximum output capacity. If both compressors are set for service/maintenance the DX Box will indicate to the system management unit that the DX Box ‘group’ is in maintenance mode; the system management unit will remove the DX Box ‘group’ from the sequence strategy and substitute with an alternative available compressor if necessary. C05 1 2 When the ‘Service Maintenance Switch’ input terminal pins are connected together, using a volt-free switching contact, the DX Box will detect that the compressor is in maintenance mode and unavailable for utilisation. When the ‘Service Maintenance Switch’ inputs are open circuit again the compressor will automatically be accepted back in to DX Box control. The use of a ‘key switch’ is recommended for this purpose in order to prevent the switch contacts being inadvertently left in the closed circuit condition after service maintenance is complete. DO NOT connect any external voltage source to the pins of terminal C05. Note: If both compressors are switched to maintenance mode at the same time the responce of the system management unit will be dependant on model; only models equipped with ‘Service Maintenance Switch’ functionality will recognise the maintenance mode. Activating the ‘Service Maintenance’ function with an system management unit that is not equipped for the function will result in a DX Box ‘group’ fault indication. Page 11 Technical Manual 3.7 Delivery Pressure Sensor (optional) 3.6 System Pressure Sensor Required for DX Box operation. A pressure sensor input is available for monitoring local ‘system’ or ‘dry-side’ pressure downstream of local air treatment or other potential restrictions to air flow. This input is intended for a 4-20mA type pressure sensor. The ‘Compressor Delivery’ pressure option can provide local over-pressure protection and air treatment differential monitoring. P1 Ps #1 The pressure sensor should be installed in such a manner as to be able to sample atmospheric pressure during routine calibration procedures. It is recommended that a valve be used that will allow the sensor to be removed without de-pressurisation of the air system. Connect the pressure sensor to the ‘System’ (REF) pressure sensor input terminals of the DX Box. The pressure sensor must be connected to the DX box using a 2-wire, earth shielded, cable that is no longer than 100m (330ft) in length. 26 25 - - + + X05 DP#1 P2 #2 DP#2 Compressor Delivery Pressure: A pressure sensor input is available for each compressor connected to the DX Box. This input is intended for a 4-20mA type pressure sensor that is installed to monitor the ‘delivery’ pressure of the applicable compressor. It is recommended the pressure sensor should be installed up-stream of (before) any isolation valve and in such a manner as to be able to sample atmospheric pressure during routine calibration procedures. Connect the pressure sensor to the correct DX Box terminals for the applicable compressor. The pressure sensor must be connected to the DX box using a 2-wire, earth shielded, cable that is no longer than 100m (330ft) in length. Polarity is important. - Some types of pressure sensor are not suitable for direct exposure to water (e.g. rain, condensate, steam or excess moisture) or direct sunlight. In this instance the sensor must be protected from the environment if it is to be mounted in a location exposed to climatic or adverse conditions. X05 + 24 #2 #1 23 22 21 - - + + #1 Polarity is important. Page 12 #2 + Metacentre DX Box 3.8 Auxiliary Fault Inputs (Option) 3.9 Remote Output (Option) The DX Box is equipped with two auxiliary ‘Fault’ inputs, one dedicated to each compressor. The input(s) can be used to detect a compressor ‘Alarm’ or ‘Shutdown Trip’ condition. The input(s) can also be used to detect a ‘Fault’ condition of auxiliary equipment associated with the compressor. Remote Output R4 The function of each ‘Fault’ input can be selected in the DX Box menu: 1: Alarm The system management unit will display the fault as a compressor ‘Alarm’ condition; the compressor will continue to run and be utilised as required. 2: Trip The system management unit will display the fault as a compressor ‘Shutdown Trip’ condition; the compressor will be removed from sequence and will not be utilised. The DX Box is equipped with a remote relay contact output; terminal X03. The function of the output can be defined in the DX Box menu. The contacts of the remote relay output can be used to switch an external devise or signal a remote condition or fault condition. The remote relay contacts are rated for 24Vac/dc @ 5A maximum. Alarm Beacon: An Alarm Beacon kit is available that can be connected to the DX Box remote output to provide a highly visible fault indication from a distance. X03 XPM-TAC24 24Vac 2 1 X04 18 #2 #1 17 16 15 X03 Fault Comp #1 R2 14 13 - 24Vac + Beacon Fault Comp #2 As default the auxiliary ‘Fault’ input(s) are normally open, Fault on closed circuit condition. If required this can be reversed in the DX Box menu to be normally closed, Fault on open circuit. The unused 24Vac @ 1A power supply output of the XPM-TAC24 power supply PCB (terminal X03) can be used to provide the beacon 24Vac supply. Note: Pin ‘1’ of X03 (0vac) is bonded to earth on the XPM-TAC24 module PCB. Note: The maximum cable length for an Auxiliary ‘Fault’ input is 100m (330ft). Page 13 Technical Manual 4. COMMISSIONING 4.1 Commissioning Procedure 4.2 System Management Unit Carry out the following procedures before attempting to apply power and start. Ensure the connection type for the DX Box ‘group’ is defined as “I-485” (RS485 network communication) in the system management unit configuration. It is recommended that an authorised and trained product supplier carry out commissioning. 4.1.1 Power Supply PCB Voltage Selector: Before applying power to the DX Box ensure that the power supply connections are correct and secure and that the operating voltage selector is set correctly for the power supply voltage in use; 115Vac or 230Vac (+-10%), 50/60Hz; see ‘Installation’. XPM-TAC24 1 2 3 1 4 2 3 4 Each DX Box ‘group’ connected to an system management unit must be assigned a unique compressor identification number (1 to 12). This number will be the ‘network address’ number for the DX Box ‘group’. This number, and the DX Box identification (‘A’ or ‘B’) should be clearly marked on the compressor for identification purposes; for example ‘3A’. When connecting a DX Box to a system always use the system management unit unique compressor identification number as the DX Box ‘network address’ number. X04 L N E E VOLTAGE SELECT X01 L N E DX Box 230Vac 1 2 3 4 X04 1 2 #1 3 #2 VOLTAGE SELECT 115Vac General Checks: Check and ensure all pressure sensor, ‘i-PCB’ and other connections are correctly installed and secure. Close the front panel of the DX Box and apply power. Indicate each compressor connected to the DX Box using the DX Box compressor identification number and the compressors local reference number #1 or #2. Example: Compressor #1 = network address 3(#1) Compressor #2 = network address 3(#2) The local DX Box reference numbers (#1 and #2) have no meaning for system management unit identification and referencing; it is not important for compressors to be connected to the DX Box in numerical order or sequentially. The management system will indicate both compressors as a single unit with one identification number. Page 14 Metacentre DX Box 4.3 Menu Navigation Access Code: Display Item Structure: Access to page list displays higher than page ‘P00’ is restricted by access code. To access menu mode pages press UP and DOWN together, an access code entry display is shown and the first code character will flash. Use PLUS or MINUS to adjust the value of the first code character then press ENTER. The next code character will flash; use UP or DOWN to adjust then press ENTER. Repeat for all four code characters. All value, parameter or option selection displays are grouped into menu lists. Items are assigned to a list according to type and classification. Items that can be used to select options or modify functions are assigned to ‘menu mode’ lists. Items that a User may require to view during routine operation, detected pressure for example, are assigned to the normal operational mode list. Lists are identified by page number; the normal User display list is page ‘P00’. All parameters and options are assigned to menu mode pages ‘P01’ or higher. All Page ‘P00’ items are view only and cannot be adjusted. Normal Operational Mode (Page P00): At controller initialisation, all display elements and LED indicators are switched on for three seconds, the display will then show the software version code for a further 3 seconds before initialisation is complete and the normal operating display (Page P0) is shown. In page P00 ‘normal operational display mode’ the main display will continuously show the detected delivery pressure and the Item display will show the first item of the ‘User’ menu. User menu ‘Items’ can be selected using the Up or Down buttons at any time. Pressing the Enter button will lock any selected Item display and inhibit return to the default display. When an Item display is locked the lock key symbol will slow flash. To unlock an Item display press Up or Down to view an alternative Item display or press Reset or Escape. No Item values, options or parameters can be adjusted in page ‘P00’. If a fault condition occurs the fault code becomes the first list item and the display will automatically jump to display the fault code. More than one active fault code item can exist at any one time. Page 0 If the code number is less than 1000 then the first code character will be 0(zero). To return to a previous code character press ESCAPE. When all four code characters have been set to an authorized code number press ENTER. An invalid code will return the display to normal operational mode; page ‘P00’. Access Code Timeouts: When in menu mode, if no key activity is detected for a period of time the display will automatically reset to the normal operational display; Page ‘P00’. Menu Mode Navigation: In menu mode the main value display will flash and show the Page number. To select a page press UP or DOWN. For each page the display will show the first Item of the page list. To view a page list press ENTER, the Page number will stop flashing and the Item display will flash. Press UP or DOWN to view the selected page list items. To select an Item value for modification press ENTER, the Item display will stop flashing and the Value display will flash. The value or option can now be modified by pressing UP(Plus) or DOWN(Minus). To enter a modified value or option in memory press ENTER; alternatively the modification can be abandoned, and the original setting maintained, by pressing ESCAPE. Page 1 Page 2 Item 1 Item 2 Item 3 Item 4 Item 5 Item 6 Value Value Value Value Value Value Page 3 Page 4 Page 5 Item 1 Item 2 Item 3 Item 4 Item 5 Value Value Value Value Value Page 15 Technical Manual Press ESCAPE at any time in menu mode to step backwards one stage in the navigation process. Pressing ESCAPE when the page number is flashing will exit menu mode and return the display to normal operational mode; page ‘P00’. Page 1 Page 0 Page 2 Item 1 Item 2 Item 3 Item 4 Item 5 Item 6 Value Value Value Value Value Value Page 3 Page 4 Page 5 Press and hold RESET for two seconds at any time to immediately exit menu mode and return to the normal operational mode display. Any value or option adjustment that has not been confirmed and entered into memory will be abandoned and the original setting maintained. A flashing Key symbol displayed with any Item indicates the Item is locked and cannot be modified. This will occur if the Item is view only (non adjustable) or in instances where the item cannot be adjusted while the DX Box is in ‘Remote Mode’. Page 16 Item 1 Item 2 Item 3 Item 4 Item 5 Value Value Value Value Value Metacentre DX Box 4.4 Menu Items and Settings Menu 1 – Comp #1 Settings 1 Pc Comp #1 Percent Capacity 2 D3 ‘i-PCB’ Alarm Input 0V/+V (Di3) 3 D6 Auxiliary Input (Di6) Menu 2 – Comp #2 Settings 1 Pc Comp #2 Percent Capacity 2 D5 ‘i-PCB’ Alarm Input 0V/+V (Di5) 3 D7 Auxiliary Input (Di7) Menu 3 – Configuration 1 Ad DX Box network Address 2 Mo Mode 3 Rt Rotation Interval time 4 St Start Delay time 5 P> Pressure display units 6 R4 Auxiliary Output Function (R4) Menu 4 – Regulation Control 1 C> Control percent (view only) 2 Pf P Factor 3 I Factor If Menu 5 – System Pressure Sensor 2 Po Offset Calibration 3 Pr Range Calibration Menu 6 – Comp #1 Pressure Sensor 1 PE Enable 2 PL Pressure Limit 3 Po Offset Calibration 4 Pr Range Calibration Menu 7 – Comp #2 Pressure Sensor 1 PE Enable 2 PL Pressure Limit 3 Po Offset Calibration 4 Pr Range Calibration 4.4.1 Menu items for compressor #1 Pc: Percent Capacity Set to the percentage output compared to the total output of the DX Box ‘group’. For example: If compressor #1 = 13.0 m3/min and compressor #2 = 7.0 m3/min then: Compressor #1 = 65% D3: ‘i-PCB’ Alarm Input NO/NC ‘i-PCB’ Alarm input configuration for compressor #1. As default the ‘i-PCB’ Alarm input (optional) will generate an Alarm condition when voltage (12V to 250V) is applied to the Alarm input terminals (‘no’). This configuration can be changed so that a constant voltage can be applied to the Alarm input terminals and an Alarm generated when the voltage is removed. (‘nc’). ‘no’ (normally open) – default Alarm when voltage applied. (normally closed) Alarm when voltage removed. ‘nc’ Set to default ‘no’ if not used. D6: Auxiliary Input Selects the function and operation of the ‘Auxiliary Input’: Menu 7 - Diagnostics See ‘Diagnostics’ Ano Access Code = Menu 1 – Compressor #1 0021 Anc Tno Tnc Alarm: (normally open) – default Alarm when closed Alarm: (normally closed) Alarm when open Trip: (normally open) Trip when closed Trip: (normally closed) Trip when open Set to default ‘Ano’ if not used. Page 17 Technical Manual 4.4.2 Menu 2 – Compressor #2 4.4.3 Menu 3 – Configuration Menu items for compressor #2 DX Box configuration items. Pc: Percent Capacity Ad: Network Address Set to the percentage output compared to the total output of the DX Box ‘group’. DX Box network address; must be set to the compressor identification number used by the system management unit controller for the DX Box ‘group’ (1 to 12). Each DX Box and/or compressor in a system must have a unique identification number. For example: If compressor #1 = 13.0 m3/min and compressor #2 = 7.0 m3/min then: Compressor #2 = 35% D5: ‘i-PCB’ Alarm Input NO/NC ‘i-PCB’ Alarm input configuration for compressor #2. Note: The DX Box network address number must be unique and must not be set the same as any other compressor or DX Box ‘group’ in a system. Mo: Mode (see: Operation) As default the ‘i-PCB’ Alarm input (optional) will generate an Alarm condition when voltage (12V to 250V) is applied to the Alarm input terminals (‘no’). 0: 1: This configuration can be changed so that a constant voltage can be applied to the Alarm input terminals and an Alarm generated when the voltage is removed. (‘nc’). 1 to 24 Hours (24hrs default) ‘no’ (normally open) – default Alarm when voltage applied. (normally closed) Alarm when voltage removed. ‘nc’ Timer Rotation Automatic (default) Rt: Rotation Interval Time The time interval between ‘Top-Up’ and ‘BaseLoad’ rotation of the compressors connected to the DX Box. Note: Only applicable in ‘Timer Rotation’ mode. St: Start Delay Time Set to default ‘no’ if not used. D7: Auxiliary Input Selects the function and operation of the ‘Auxiliary Input’: Ano Anc Tno Tnc Alarm: (normally open) – default Alarm when closed Alarm: (normally closed) Alarm when open Trip: (normally open) Trip when closed Trip: (normally closed) Trip when open Set to default ‘Ano’ if not used. Page 18 If it is necessary for the DX Box to ‘start’ the main motors of both compressors together, compressor #2 will not be started until the start delay time has expired after compressor #1 has been started. Set to the ‘star/delta’ time of the largest compressor in the group. P>: Pressure Units Selects the display pressure units: 0: 1: 2: bar (default) psi kPa Metacentre DX Box R4: Auxiliary Output Function Example % Control Functions: Selects the function of the auxiliary relay contact output R4. Control Fno: Compressor Fault N/O Energised if a compressor Alarm or Trip fault is detected. Fnc: Compressor Fault N/C De-energised if a compressor Alarm or Trip fault is detected. C1r: Compressor #1 Running Energised when compressor #1 is detected as running. C2r: Compressor #2 Running Energised when compressor #2 is detected as running. Crr: Compressor Running Energised if compressor #1 and/or compressor #2 is detected as running. On: Metacentre ON Energised when Metacentre management system is regulating to achieve or maintain pressure (Off when in standby or stopped). AC: Metacentre Active Energised when Metacentre management system is actively maintaining control of compressors inclusive of Standby (Off when stopped; unless management system set to force compressors offload when stopped) rPC: Remote Pressure Control Energised when in ‘Remote Mode’ – System management unit control. CS: Compressor(s) in Maintenance Mode Energised when one, or both, compressors have been switched to Service/Maintenance mode. 50:50% 100.0 % 90.0 ‘x’ 80.0 75.0% 70.0 ‘x’ 60.0 50.0 50% 40.0 ‘y’ 30.0 25.0% 20.0 ‘y’ 10.0 0.0 Display: A A+B 50% 100% 65:35% Control 100.0 % ‘x’ 90.0 82.5% 80.0 ‘x’ 70.0 65% 60.0 50.0 ‘y’ 50.0% ‘y’ 4.4.4 C>: Menu 4 – Regulation Control Control percent (view only) The DX Box uses a P&I pressure control algorithm to determine compressor utilization. The control algorithm produces a percentage value that is compared to the percentage settings of each compressor. The ‘control percentage’ will increase and decrease in response to changes in local system pressure ‘SP’. When the DX Box is operating in conjunction with a system management unit the algorithm ‘target’ response is automatically manipulated to match the system requirements. Pf: If: 40.0 35% 30.0 ‘z’ 20.0 10.0 17.5% ‘z’ 0.0 Display: A B A+B 35% 65% 100% Do not adjust the ‘P’ and/or ‘I’ factor setting(s) unless you are familiar with the P&I control response and the function of these settings within the P&I control algorithm. P Factor (default 40) I Factor (default 10) Page 19 Technical Manual 4.4.5 Menu 5 – System Pressure Sensor The (Ps) ‘System Pressure Sensor’ is a requirement of DX Box operation and must be installed and commissioned. The ‘System’ or ‘Reference’ pressure sensor (Ps) input is intended for monitoring system, or ‘dry-side’ pressure downstream of local air treatment or other potential airflow restriction that may cause a pressure differential. P1 Pr: Pressure Range Calibration The value can be adjusted for any sensor range between 1.0bar (15psi) and 630bar (9135psi). Default = 16.0bar (232psi). If the sensor does not have a 0(zero) bar offset, the range value must be the same as the ‘maximum’ pressure value of the sensor. For example: if the sensor is a –1.0bar (minus 1.0bar) to 15bar type then: Offset = -1.0bar Ps #1 DP#1 P2 #2 Range = 15.0bar The ‘range’ value can be used for calibration: expose the senor to a known accurate pressure and adjust the ‘range’ value until the display pressure matches the applied pressure. The main display value will show the actual detected pressure when this menu item is selected. 4.4.6 Menu 6 – Comp#1 Pressure Sensor DP#2 P1 P1 Ps #1 #1 DP#1 DP#1/2 #2 P2 The ‘System’ pressure is broadcast on the network and can be used for advanced System management unit pressure control. Po: Pressure Offset Calibration The value can be adjusted between –1.5bar (minus 1.5bar) and +1.0bar (-15 to +22psi). Default = 0.0bar (0psi). The ‘offset’ value can be used for atmospheric (0bar-g) calibration; expose the senor to atmosphere and adjust until the display pressure shows 0(zero)bar. The main display value will show the actual detected pressure when this menu item is selected. Note: For sensors with ‘minus’ offset values any detected pressure below 0(zero)bar will be displayed, and transmitted on the network, as 0(zero)bar. Page 20 The ‘Compressor #1’ pressure sensor (P1) input is intended for monitoring the ‘delivery’ pressure of compressor #1 prior to any isolation valve and air treatment or other potential air flow restriction that may cause a pressure differential. PE: Pressure Sensor Option Enable 4-20mA auxiliary pressure sensor enable: 0: 1: Disable (default) Enable A compatible ‘4-20mA’ type pressure sensor must be connected to the DX Box compressor #1 pressure sensor input. When enabled the pressure will be displayed with compressor #1 status. Metacentre DX Box PL: Pressure Limit When pressure detection is enabled, and the pressure sensor used to detected compressor delivery, or ‘wet-side’ pressure, this function can be implemented. The maximum pressure limit function is intended to protect the compressor from local excess pressure conditions when pressure is being regulated remotely; for example, from the system management unit that is using system, or ‘dryside’ pressure for regulation control. If the set ‘pressure limit’ is exceeded the compressor will be unloaded, regardless of remote load command. For example: if the sensor is a –1.0bar (minus 1.0bar) to 15bar type then: Offset = -1.0bar Range = 15.0bar The ‘range’ value can be used for calibration: expose the senor to a known accurate pressure and adjust the ‘range’ value until the display pressure matches the applied pressure. The main display value will show the actual detected pressure when this menu item is selected. 4.4.7 Menu 7 – Comp#2 Pressure Sensor P2 The compressor will be inhibited from loading again until the detected pressure has reduced below the set limit, and remains below the set limit, for longer than 10 seconds. If, after reloading, pressure exceeds the limit again, the cycle is repeated. #2 DP#2 To deactivate adjust to 0(zero) – default. The ‘Compressor #2’ pressure sensor (P2) input is intended for monitoring the ‘delivery’ pressure of compressor #2 prior to any isolation valve and air treatment or other potential air flow restriction that may cause a pressure differential. Po: Pressure Offset Calibration PE: Pressure Sensor Option Enable The value can be adjusted between –1.5bar (minus 1.5bar) and +1.5bar (-22 to +22psi). Default = 0.0bar (0psi). 4-20mA auxiliary pressure sensor enable: When pressure exceeds the set limit the ‘excess pressure symbol’ will flash in the appropriate compressor status display. This indication will remain until manually reset. The ‘offset’ value can be used for atmospheric (0bar-g) calibration; expose the senor to atmosphere and adjust until the display pressure shows 0(zero)bar. The main display value will show the actual detected pressure when this menu item is selected. Note: For sensors with ‘minus’ offset values any detected pressure below 0(zero)bar will be displayed, and transmitted on the network, as 0(zero)bar. Pr: Pressure Range Calibration The value can be adjusted for any sensor range between 1.0bar (22psi) and 630bar (9135psi). Default = 16.0bar (232psi). If the sensor does not have a 0(zero) bar offset, the range value must be the same as the ‘maximum’ pressure value of the sensor. 0: 1: Disable (default) Enable A compatible ‘4-20mA’ type pressure sensor must be connected to the DX Box compressor #2 pressure sensor input. When enabled the pressure will be displayed with compressor #2 status. PL: Pressure Limit When pressure detection is enabled, and the pressure sensor used to detected compressor delivery, or ‘wet-side’ pressure, this function can be implemented. The maximum pressure limit function is intended to protect the compressor from local excess pressure conditions when pressure is being regulated remotely; for example, from the system management unit that is using system, or ‘dryside’ pressure for regulation control. Page 21 Technical Manual If the set ‘pressure limit’ is exceeded the compressor will be unloaded, regardless of remote load command. The compressor will be inhibited from loading again until the detected pressure has reduced below the set limit, and remains below the set limit, for longer than 10 seconds. If, after reloading, pressure exceeds the limit again, the cycle is repeated. When pressure exceeds the set limit the ‘excess pressure symbol’ will flash in the appropriate compressor status display. This indication will remain until manually reset. To deactivate adjust to 0(zero) – default. Po: Pressure Offset Calibration The value can be adjusted between –1.5bar (minus 1.5bar) and +1.5bar (-22 to +22psi). Default = 0.0bar (0psi). The ‘offset’ value can be used for atmospheric (0bar-g) calibration; expose the senor to atmosphere and adjust until the display pressure shows 0(zero)bar. The main display value will show the actual detected pressure when this menu item is selected. Note: For sensors with ‘minus’ offset values any detected pressure below 0(zero)bar will be displayed, and transmitted on the network, as 0(zero)bar. Pr: Pressure Range Calibration The value can be adjusted for any sensor range between 1.0bar (22psi) and 630bar (9135psi). Default = 16.0bar (232psi). If the sensor does not have a 0(zero) bar offset, the range value must be the same as the ‘maximum’ pressure value of the sensor. For example: if the sensor is a –1.0bar (minus 1.0bar) to 15bar type then: Offset = -1.0bar Range = 15.0bar The ‘range’ value can be used for calibration: expose the senor to a known accurate pressure and adjust the ‘range’ value until the display pressure matches the applied pressure. The main display value will show the actual detected pressure when this menu item is selected. Page 22 Metacentre DX Box 4.5 Diagnostics The DX Box controller is equipped with comprehensive diagnostic functions. Each input can be examined individually and each output can be manually activated or manipulated individually. EX Box Controller Diagnostics: Menu P06 - Diagnostics D1 Digital Input 1 D2 Digital Input 2 ON D3 Digital Input 3 D4 Digital Input 4 OFF D5 Digital Input 5 Pulsing D6 Digital Input 6 D7 Digital Input 7 D8 Digital Input 8 ------------------------------------------------------------R1 Relay Output 1 R2 Relay Output 2 OFF R3 Relay Output 3 R4 Relay Output 4 ON R5 Relay Output 5 R6 Relay Output 6 ------------------------------------------------------------A1 Analogue Input 1 bar <> mA A2 Analogue Input 2 bar <> mA A3 Analogue Input 3 bar <> mA Relay Outputs: Each relay output can be energised and deenergised manually by selecting the item. Use PLUS and MINUS to adjust ‘on’ (1) or ‘off (0) and then ENTER. Analogue Inputs: The item will alternate between the detected value and the electrical measurement on the input terminals. An independent measuring device can be used to check the displayed electrical measurement. A1: A2: A3: Comp #1 Pressure 4-20mA Comp #2 Pressure 4-20mA System Pressure 4-20mA Digital Inputs: D2, D3, D4 and D5 (connected to the ‘iPCB’s’) are the only digital inputs that will detect a pulsing signal. D2/4: i-PCB Compressor Ready/Run Status OFF Not Ready ON Ready Pulsing Running D3/5: i-PCB Compressor Load/Maintenance OFF Alarm (unless reversed in menu) ON OK (unless reversed in menu) Pulsing Service Maintenance The pulse signal is 24VDC at 50/60Hz. A DC voltage meter will detect this as 12VDC +-4V. Page 23 Technical Manual 5. OPERATION 5 9 6 2 BAR 3 7 When viewing the status or pressure information for a compressor the ‘network address’ and DX Box identification will be show on the upper display (for example, “C.03.1” indicates that the compressor is connected to the DX Box as compressor #1 and the DX Box is represented on the system management unit as compressor number “03”). The status of the compressor will also be show using the ‘Run’ and ‘Load’ symbols. 4 1 8 10 5.1 User Interface 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 5.2 LCD Display No function (unit always ON) No function No function ESCAPE Button UP, PLUS Button DOWN, MINUS Button ENTER Button DX Box Active Indicator FAULT Indicator Display The upper display will continuously show the The detected ‘System’ pressure and the lower display will show the percentage load of the DX Box ‘group’. If the ‘Delivery’ pressure sensor option for a compressor has not been enabled the lower display line will not be shown and the ‘differential’ pressure item will not be available. User Menu Iems: P.-C>: C#1-P>: C#1- P: C#2-P>: C#2- P: 5.3 ‘System’ Pressure. and % Output ‘Delivery’ pressure compressor #1 ‘Differential’ Pressure #1 ‘Delivery’ pressure compressor #2 ‘Differential’ Pressure #2 Status Symbols DX Box Status (C>): Press UP and DOWN to view the status, ‘Delivery’ pressure (if enabled) and ‘Differential’ pressure (if applicable) for each compressor in the ‘group’. Power Failure Auto Restart (always on) Communicating with the System Management Controller (Remote Mode) Flashing - No Communications with the System Management Controller (Local Mode) One, or both, Compressors are Loaded One, or both, compressors are switched to ‘Service Maintenance’ mode. One, or both, compressors have exceeded the set Pressure Limit 1: Compressor Alarm 2: Auxiliary Alarm input active 3: Delivery Pressure Sensor fault (display “- - - -“) 1: Compressor Not Available 2: Auxiliary Trip input active Page 24 Metacentre DX Box Compressor Status: 5.6 Operation Compressor Running Compressor On Load Flashing - Not Responding, Compressor Not Running When required to load. Service Maintenance function active The DX Box is always active (started) and cannot be stopped. The DX Box will automatically switch between ‘Remote’, when under system management unit control, or ‘Local’ mode. 5.7 Power Failure Auto-Restart Pressure Limit Exceeded 1: Compressor Alarm 2: Auxiliary Alarm input active 3: Pressure Sensor fault (display “- - - -“) The DX Box will always automatically start when power is re-applied after a power supply disruption or failure. 1: Compressor Not Available 2: Auxiliary Trip input active 5.8 Failure Modes 5.4 Indicators Run Indicator (Green LED) OFF ON DX Box Fault condition Active Fault Indicator (Red LED) OFF – No fault Slow Flash: 1: Compressor Alarm 2: Pressure Sensor fault (display “- - - -“) Fast Flash: 1: Compressor Not Available If communications with the system management unit is disrupted, the DX Box will switch to ‘Local’ mode and pressure regulation control is maintained using the set pressure set points. The DX Box will automatically switch back to ‘Remote’ mode when communications with the system management unit are re-established, or the DX Box fault is reset. If a fault occurs with the DX Box, or power to the DX Box is disrupted, pressure regulation control is automatically transferred back to each compressor. The compressor(s) will continue to operate using the pressure settings programmed or set in the individual compressor controller(s). 5.5 Compressor Identification Each compressor connected to the DX Box will have an assigned compressor identification number #1 or #2. DX Box 1 2 #1 3 #2 The DX Box ‘group’ will also have a single unique system address identification and will be represented on the system management unit as a single entity using the ‘address’ identification number. The identification number will be unique for the system. For example, “C.03.1” indicates that the compressor is connected to the DX Box as compressor #1 and the DX Box is represented on the system management unit as compressor number “03”. The design of some air compressor control systems may inhibit automatic transfer of pressure regulation control to local operation mode. In this instance the compressor will not continue production of compressed air – consult the air compressor manual or your air compressor supplier / specialist for details before installing the DX Box unit. 5.9 Compressor Fault If a compressor fault condition is detected the ‘status’ display will show an ‘Alarm’ condition. The ‘status’ display associated with the compressor will also indicate a fault condition (see Status Symbols). The DX Box ‘Fault’ indicator (10) will flash to attract attention. Compressor fault conditions will also be communicated to the system management unit controller. Page 25 Technical Manual 5.10 DX Box Fault The DX Box has two ‘shutdown’ fault conditions: E:0821 Short Circuit Condition Detected, check all DX Box controller inputs and outputs. E:0115 BAR System Pressure Sensor Fault. If one of these fault conditions occur the DX Box will switch ‘off. The ‘Run Indicator’ (9) will also switch off and the ‘Fault Indicator’ (10) will fast flash. 5.11 Pressure Sensor Fault (Option) If a ‘Delivery’ pressure sensor fault is detected (if the pressure sensor option is enabled) the DX Box will indicate a compressor ‘Alarm’ condition and the associated pressure display will show “- - - -“ dashes. The DX Box will continue to operate normally without interruption. Page 26 Metacentre DX Box 6.0 Parts List Metacentre DX Box Item Part No. 1 2 3 4 Description Y07ENER10.00 Y07CM14.00 Y07CM20.00 Y05CM31.00 KPY0617.00C Y07CM49.00 Unit, DX Box Manual, User CD Controller, S1 DX Unit, XPM-TAC24 PCB, Terminal EX Gland, Set - Pg13.5 XPM -TA C24 2 3 Required For Each Compressor: AirMaster S1 Item Part No. Description 1 4 5 Y04CM59.00 Unit, i-PCB Optional Accessories: Item Part No. 5 Y04CM29.00 7 Y01ENER35.00 7 11 24 14 12 A2 A1 Sensor, Pressure 4-20mA, 0-16.0bar Module, Relay 24Vac 7.0 Technical Data Installation and Mounting Dimensions Metacentre DX Box Power Temperature Humidity 6 Description 6 Dimensions Weight Mounting Enclosure Supply i-PCB 21 22 291mm x 241mm x 152mm 6.5kg (14lb) wall, 4 x screw fixings IP54, NEMA 12 230Vac +/- 10% 115Vac +/- 10% 50VA 0°C to 45°C (32°F to 112°F) 30% to 90% RH non-condensing 24mm 238mm 24mm 236mm 188mm 8mm Ø 286mm Page 27 Technical Manual X07 C007 C008 X06 not used C006 C005 C008 Ao RS485 X04 8 7 6 5 4 3 2 1 C+ C009 L1 C010 L2 C011 C012 C013 C004 C003 C002 C001 - Ai3 4-20mA System Press. X05 C007 A-GND - Ai2 4-20mA + C006 Ai3 Pressure #2 - Ai1 4-20mA + C005 +VDC Pressure #1 C015 C016 X04 C014 C019 C024 C025 X03 X06 L1 Multi485 L2 L1 Multi485 L2 C004 Ai2 X07 C009 C010 29 30 31 32 +VDC 15 16 17 18 19 20 X05 C003 27 28 C002 Ai1 21 22 23 24 25 26 C001 +VDC 13 14 S1-10-R4-333 Controller DX Box 8.0 Wiring Diagram C011 C017 C017 C018 C018 C019 +C Di6 Aux Fault #1 +C Di7 Aux Fault #2 not used C028 C029 C026 C030 C022 2 3 4 5 6 24Vac 2 1 X03 10k C013 C031 0Vac X01 XPM-TAC24 X02 2 1 L N E E L N E C029 C027 C014 +20VDC i-PCB 2 R4 X01 24Vac C032 Page 28 C023 C021 2 1 C025 C016 C031 6 Di4 Ready/Run 5 Di5 Alarm/Serv. 4 3 - GND 2 R3 LOAD 1 R1 SEQ 6 Di2 Ready/Run 5 Di3 Alarm/Serv. 4 3 - GND 2 R2 LOAD 1 R1 SEQ i-PCB 1 C023 R4 Aux Output +20VDC X02 C015 C024 230Vac 10% 115Vac 10% C011 10k X01 C022 V2 7 C021 V1 1 X03 R3 R2 R1 C020 8 9 10 11 12 C027 Metacentre DX Box XPM-TAC24 BLACK BLUE ORANGE BROWN WHITE RED GREEN VIOLET 1 T3.15A T1.6A T1.6A T1.0A FH4 FH3 FH2 FH5 2 3 4 X04 1 VOLTAGE SELECT 2 3 4 230V +-10% 230V 115V 115V +-10% IEC 5x20mm T1.0A X02 X03 2 24Vac/2 earthed 1 1 2 3 4 N L E E X01 2 24Vac/1 isolated FH1 NL E Page 29 Technical Manual DX Commissioning Form Customer Contact Customer Ref: Phone Internal Ref: Installation/Site Commission Date Commission Engineer Ser No. Software 3 #1 bar m /min kW VA Hz Comp #1 Manufacturer Comp #1 Model/Type Comp #1 Working Pressure Comp #1 Full Load Capacity bar/psi m3/min #2 bar m3/min kW VA Hz Comp #2 Manufacturer Comp #2 Model/Type Comp #2 Working Pressure Comp #2 Full Load Capacity bar/psi m3/min P01 P01 P01 Pc D3 D6 Comp #1 Percent Capacity ‘i-PCB’ Alarm Input Auxiliary Input P02 P02 P02 Pc D5 D7 Comp #2 Percent Capacity ‘i-PCB’ Alarm Input Auxiliary Input P03 P03 P03 P03 P03 P03 Ad Mo Rt St P> R4 Network Address Mode Rotation Time Start Delay Time Pressure Display Units Auxiliary Output Function (R4) P04 P04 Pf If ‘P’ factor ‘I’ factor P05 P05 Po Pr System Pressure 'Offset' System Pressure 'Range' P06 P06 P06 P06 PE PL Po Pr Comp #2 Pressure Enable Comp #2 Pressure Limit Comp #2 Pressure 'Offset' Comp #2 Pressure 'Range' 0 P07 P07 P07 P07 PE PL Po Pr Comp #2 Pressure Enable Comp #2 Pressure Limit Comp #2 Pressure 'Offset' Comp #2 Pressure 'Range' 0 Page 30 % no Ano nc Anc no nc Ano Anc Tno Tnc % 1 Ar 2 3 Tr Tno 4 5 Tnc 6 7 8 9 10 11 12 hrs sec bar Fno psi Fnc C1r C2r Crr Eon Eac rPC CS bar /psi bar /psi 1 bar /psi bar /psi bar /psi 1 bar /psi bar /psi bar /psi
advertisement
Key Features
- Compressor grouping
- Variable output control
- System pressure monitoring
- Remote output option
- Compressor failure indication
- Maintenance mode
Frequently Answers and Questions
How many compressors can I connect to a single DX Box?
The DX Box is designed to group two compressors together.
What is the maximum distance between the DX Box and the compressors?
The DX Box can be located up to 100m (330ft) away from each compressor.
What happens if one of the compressors in the group fails?
If one compressor fails, the DX Box will indicate an alarm condition and continue to operate at reduced capacity using the remaining compressor.
How do I set the compressor capacity percentages?
The capacity of each compressor is expressed and set as a percentage of the combined output capacity of both compressors. This information is detailed in the manual.