DIEL AT200 Installation And Instruction Manual
DIEL AT200 is a control unit designed for monitoring and managing ventilation systems. This device features two independent ventilation lines, each with its own current monitoring capabilities. It also includes two PTC inputs for monitoring motor temperatures. The AT200 can be operated in 3 modes: automatic, manual, and scan. The automatic mode allows for remote control of the fan systems, while the manual mode allows for direct operator control, and the scan mode cycles between monitoring the two channels.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
AT200 MANUALE DI INSTALLAZIONE ED USO INSTALLATION AND INSTRUCTIONS MANUAL ITALIANO MONTAGGIO Eseguire nel pannello un foro da 91X91 mm, fissare la centralina con i ganci in dotazione. ALIMENTAZIONE E COLLEGAMENTI ELETTRICI Morsetti 1-2-3: Collegamento per 2 sonde PTC, morsetto 1 sonda PTC1, morsetto 2 sonda PTC2, morsetto 3 comune. Morsetti 4-5: Controllo remoto, alla chiusura del contatto, in caso di funzionamento automatico, si abilitano le linee di ventilazione. Morsetti 6-7-8: Relè fault, normalmente diseccitato (6-7 chiuso) durante il funzionamento della centralina, in caso di allarme per mancanza o eccessivo assorbimento da parete del carico il relè si eccita (6-8 chiuso). Morsetto 9-10-11: Uscita Motore 1, controllo e comando della prima linea di ventilazione (max 5A 220÷240 ±10% V AC 50-60 Hz). 3 ITALIANO Morsetti 12-13-14: alimentazione centralina AT100, con tensione alternata (220÷240 ±10% V AC 50-60 Hz). Morsetto 15-16-17: Uscita Motore 2, controllo e comando della seconda linea di ventilazione (max 5A 220÷240 ±10% V AC 50-60 Hz). PANNELLO FRONTALE Visualizza la funzione o il canale e il relativo valore in esecuzione Segnala il funzionamento automatico (acceso), manuale (spento), scansione (lampeggiante). Segnala che almeno un ventilatore è in marcia. Segnala che la centralina è nel menu di programmazione. Segnala assorbimenti di correnti superiori al set di calibrazione iniziale in almeno un canale. Dettagli disponibili nel menu di consultazione. Segnala assorbimenti di correnti inferiori al set di calibrazione iniziale in almeno un canale. Dettagli disponibili nel menu di consultazione. Segnala errore di sovra temperatura in almeno un motore. 4 ITALIANO Consente la commutazione tra le funzioni AUTOMATICA, MANUALE e SCANSIONE. >> Paragrafo SET AUTO/MAN/SCAN In fase di programmazione consente la conferma di un dato inserito, altrimenti effettua test dei led e display TASTI DI NAVIGAZIONE (DOWN/UP): Consentono lo scorrimento delle diverse pagine di menu e l’incremento decremento dei valori di programmazione. CAL: Effettua l’autocalibrazione della centralina. >> Paragrafo FUNZIONE CAL PROGRAM: Si entra nella funzione di programmazione della centralina >> Paragrafo FUNZIONE PROGRAM RESET: Effettua il reset degli allarmi >> Paragrafo FUNZIONE RESET FUNZIONAMENTO DELLA CENTRALINA La centralina AT200 serve a monitorare le correnti assorbite di due linee indipendenti di ventilazione e, dopo un processo di taratura iniziale, segnalare situazioni di eccessivo o ridotto assorbimento di corrente. È dotata anche di due ingressi PTC per rilevare la temperatura dei motori. Il funzionamento può essere in modalità manuale o automatica se collegata ad una centralina di comando remoto (tipo MT200, ME100). In caso di assorbimento anomalo di corrente rispetto alle soglie di allarme impostate, il relè FAULT (NO) commuta. 5 ITALIANO FUNZIONE CAL Si accede con la pressione contemporanea e prolungata di entrambi i tasti, ed effettua l’auto calibrazione della centralina con lettura e memorizzazione delle correnti assorbite dai ventilatori come riferimento per la gestione degli allarmi. Il funzionamento è totalmente automatico in tutte le sue fasi per una durata massima di circa 2 minuti. Fase 1: Lettura e memorizzazione delle correnti del canale 1. Esempio (Canale 1 - 0.25 A). I ventilatori sono in marcia. Fase 2: Lettura e memorizzazione delle correnti del canale 2. Esempio (Canale 2 - 0.30 A). I ventilatori sono in marcia. Termine della procedura di calibrazione. La centralina si porta nello stato di funzionamento automatico. FUNZIONE PROGRAM Serve per impostare i parametri di configurazione della centralina. Si accede con la pressione contemporanea e prolungata di entrambi i tasti, si seleziona la configurazione desiderata e si conferma con ENTER/TEST. UTILIZZO TASTI DI NAVIGAZIONE ED ENTER: Utilizzare il tasto ENTER per confermare i valori proposti nei vari menu, DOWN e UP per modificarli 6 ITALIANO UTILIZZO SENSORI PTC: Abilitazione degli ingressi per i sensori PTC: 0 = Non abilitati, 1 = Abilitati (Default = 0) SCOSTAMENTO CORRENTE: Scostamento percentuale della corrente attuale rispetto a quella di calibrazione. Un valore rilevato oltre questa soglia commuta il relè di FAULT. (Default = 10 %.) DELAY INIZIALE: Impostazione del tempo dopo lo start dei ventilatori prima di analizzare eventuali allarmi.(Default = 10 sec.) DELAY ALLARME: Impostazione del tempo di permanenza errore prima di attivare un allarme.(Default = 5 sec.) CANALE 1: Abilitazione della gestione del canale 1: 0 = Non abilitato, 1 = Abilitato. (Default = 1) CANALE 2: Abilitazione della gestione del canale 2: 0 = Non abilitato, 1 = Abilitato. (Default = 1) FUNZIONE RESET Serve per azzerare tutti gli allarmi rilevati dalla centralina. Si effettua con la pressione contemporanea e prolungata di entrambi i tasti. VISUALIZZAZIONE VALORI Premendo i tasti di navigazione è sempre possibile visualizzare i valori rilevati dalla centralina. 7 ITALIANO SET CORRENTE: Indica il SET iniziale memorizzato in sede di calibrazione, premendo UP il valore relativo al canale 1. MAX SOVRACORRENTE: Indica la massima sovracorrente raggiunta, premendo UP, il relativo valore al canale 1 SCOSTAMENTO CORRENTE: ==>> FUNZIONE PROGRAM=> SCOSTAMENTO CORRENTE DELAY INIZIALE: ==>> FUNZIONE PROGRAM=> DELAY INIZIALE DELAY ALLARME: ==>> FUNZIONE PROGRAM=> DELAY ALLARME UTILIZZO SENSORI PTC ==>> FUNZIONE PROGRAM=> UTILIZZO SENSORI PTC SET AUTO-MAN-SCAN Consente la scelta del funzionamento tra AUTOMATICO, MANUALE e SCANSIONE. AUTOMATICO: L’accensione e lo spegnimento dei ventilatori è effettuata da un sistema remoto (es. centralina MT200) collegata ai morsetti 4 e 5. Il Display indicherà la sigla iniziale AUT ed il led AUTO rimarrà acceso. Verrà visualizzato il canale con assorbimento più alto e alternativamente lo scostamento percentuale rispetto al valore di calibrazione. 8 ITALIANO MANUALE: I ventilatori saranno accesi e spenti manualmente dall’operatore. Il Display indicherà la sigla iniziale MAN ed il led AUTO rimarrà spento. Per comandare l’accensione dei ventilatori 1 e 2 premere il tasto ENTER/ TEST, il led PROGRAM lampeggierà, e verrà proposto il ventilatore 1, con i tasti UP/DOWN commutare in on/off, premere nuovamente il tasto ENTER/TEST per passare al ventilatore 2, con i tasti UP/DOWN commutare in on/off. Premere un’ultima volta il tasto ENTER/TEST per ritornare in visualizzazione normale. SCAN: L’accensione e lo spegnimento dei ventilatori è effettuata da un sistema remoto (es. centralina MT200) collegata ai morsetti 4 e 5. Il Display indicherà la sigla iniziale SCAN ed il led AUTO resterà lampeggiante. Verranno visualizzati alternativamente ed in modo automatico sia i valori del canale 1 che del canale 2. ERRORI OVERCURRENT: Indica assorbimenti di corrente superiori rispetto al valore rilevato in sede di calibrazione. Il relè FAULT commuta. La linea di ventilazione viene arrestata. UNDERCURRENT: Indica assorbimenti di corrente Inferiori rispetto al valore rilevato in sede di calibrazione. Il relè FAULT commuta. La linea di ventilazione non viene arrestata. OVERTEMP: Segnala errore di sovra temperatura in almeno un motore. Il relè FAULT commuta. La linea di ventilazione viene arrestata. 9 ITALIANO CARATTERISTICHE ELETTRICHE • Contenitore 90X90X130 mm incluse morsettiere. • Pannello frontale 96x96 mm. • Peso 0.5 Kg. • Contenitore in ABS auto estinguente. • Alimentazione 220÷240 ±10% V AC 50-60 Hz. • Collegamenti elettrici su morsettiere estraibili polarizzate. • Rilevamento e controllo della corrente assorbita dai motori dei ventilatori su due linee indipendenti. • Autocalibrazione della corrente nominale assorbita da ciascuna linea di ventilazione. • Generazione allarmi per assorbimento di corrente superiori o inferiori rispetto alla corrente nominale determinata in fase di auto calibrazione, sovratemperatura di almeno un motore. • Modalità di funzionamento automatica (attraverso controllo remoto del sistema di ventilazione), manuale, a scansione dei canali. • Uscite: relè di fault 250 VAC, 5 A massimi resistivi, un contatto di scambio. • Massima flessibilità di gestione e facilità di programmazione. • Temperatura di lavoro centralina da -40 °C a +60 °C. • Costruzione in accordo alle normative • Umidità ambiente ammessa massima 90% non condensante. • Memorizzazione permanente per più di dieci anni dei valori programmati. • Rigidità dielettrica 2.5 KVAC per 60”. 10 . ENGLISH ASSEMBLY Make a hole of 91X91 mm in the panel, attach the control unit using the supplied hooks. POWER SUPPLY AND ELECTRICAL CONNECTIONS Terminals 1-2-3: Connection for 2 PTC probes, terminal 1 PTC1 probe, terminal 2 PTC2 probe, terminal 3 common. Terminals 4-5: Remote control upon closing of the contact, in case of automatic operation the ventilation lines will be enabled. Terminals 6-7-8: Fault relay, normally de-energised (6-7 closed) when the control unit is running; the relay is energized (6-8 closed) if an alarm is triggered due to lack of or excessive consumption of charge by the wall. Terminal 9-10-11: Motor 1 Output, monitoring and control of the first line of ventilation (max 5A 220÷240 ±10% V AC 50-60 Hz). 11 ENGLISH Terminal 12-13-14: power supply to AT100 control unit, with alternating voltage (220÷240 ±10% V AC 50-60 Hz). Terminal 15-16-17: Motor 2 Output, monitoring and control of the second line of ventilation (max 5A 220÷240 ±10% V AC 50-60 Hz). FRONT PANEL Displays the function or the channel and the relative value during operation Reports the automatic function (on), manual function (off) or scan function (blinking) Reports that at least one fan is running. Indicates that the control unit is in the programming menu. Reports current consumptions greater than initial set points on at least one channel. Details available in the menu for consultation. Reports current consumptions smaller than initial set points on at least one channel. Details available in the menu for consultation. Indicates over temperature fault in at least one motor. 12 ENGLISH Enables switching between AUTOMATIC, MANUAL and SCAN functions. >> Section SET AUTO/MAN/SCAN During programming, it enables the user to confirm an entry, otherwise the system runs tests on LEDs and display NAVIGATION KEYS (DOWN/UP): Allow scrolling through the different menu pages and to increase/decrease the programming values. CAL: Runs the auto calibration of the control unit. >> Section CAL FUNCTION PROGRAM: You will enter the programming function of the control unit >> Section PROGRAM FUNCTION RESET: Resets the alarms >> Section RESET FUNCTION THE OPERATION OF THE CONTROL UNIT The control unit AT200 monitors the current consumption of two independent lines of ventilation and, after the initial calibration procedure, reports excessive or reduced current consumption situations. It also features two PTC inputs to measure the temperature of the motors. The operation can be either manual or automatic, if connected to a remote control unit (type MT200, ME100). In case of abnormal current consumption i.e. different than the alarm thresholds set, the FAULT relay (NO) switches. 13 ENGLISH CAL FUNCTION Activate it by pressing and holding both buttons simultaneously; it runs the auto calibration of the control unit, reading and saving the current consumption of the fans to use as reference for alarm management. The operation is completely automatic in all its phases for a maximum period of about 2 minutes. Phase 1. Reading and saving the current values in channel 1. Example (Channel 1 - 0.25 A). The fans are running. Phase 2: Reading and saving the current values in channel 2. Example (Channel 2 - 0.30 A). The fans are running. The end of the calibration procedure. The control unit goes into automatic operating mode. PROGRAM FUNCTION This function allows you ti set the configuration parameters of the control unit. It can be turned on by simultaneously pressing and holding down both keys; now you can select the desired configuration and confirm with ENTER/TEST. USE NAVIGATION KEYS AND ENTER: Use the ENTER key to confirm the values proposed in the various menus, DOWN and UP to change them 14 ENGLISH HOW TO USE THE PTC SENSORS: Enabling inputs for PTC sensors: 0 = Disabled, 1 = Enabled (Default = 0) CURRENT OFFSET: Measured offset value of the current, expressed as a percentage, compared to set point. If the value measured exceeds this threshold, the FAULT relay will be triggered. (Default = 10 %.) INITIAL DELAY: Setting the time after the start of the fans before analyzing any alarms. (Default = 10 sec.) ALARM DELAY: Setting the error duration time before activating an alarm. (Default = 5 sec.) CHANNEL 1: Enabling channel 1 management: 0 = Disabled, 1 = Enabled. (Default = 1) CHANNEL 2: Channel 2 management enabling: 0 = Disabled, 1 = Enabled. (Default = 1) RESET FUNCTION This function is used to reset all alarms detected by the control unit. This operation can be done by simultaneously pressing and holding down both buttons. DISPLAYING THE VALUES By pressing the navigation keys you can always view the values measured by the controller. CURRENT SET: It indicates the initial SET stored upon calibration; pressing UP the value for channel 1. 15 ENGLISH MAX SURGE CURRENT: Indicates the maximum overcurrent reached, pressing UP, the value corresponding to channel 1 CURRENT OFFSET: ==>> PROGRAM FUNCTION=> CURRENT OFFSET INITIAL DELAY: ==>> PROGRAM FUNCTION=> INITIAL DELAY ALARM DELAY: ==>> PROGRAM FUNCTION=> ALARM DELAY HOW TO USE THE PTC SENSORS: ==>> PROGRAM FUNCTION => USING PTC SENSORS SET AUTO-MAN-SCAN The user can choose among AUTOMATIC, MANUAL and SCAN operating modes. AUTOMATIC: Fans are switched on and off via a remote system (i.e. MT200 control unit) connected to terminals 4 and 5. The Display will show the initial acronym AUT and the AUTO LED will remain lit. You will see the channel with the greatest current consumption and alternatively the offset percentage referred to the set point. MANUAL: The fans will be switched on and off manually by the operator. The Display will indicate the initial abbreviation MAN and the AUTO LED will remain off. To switch on the fans 1 and 2, press the ENTER / TEST key, the PROGRAM LED will flash, and the fan 1 will be proposed, use the UP / DOWN keys to switch on / off, press the ENTER / TEST key again to switch to fan 2, use the UP / DOWN keys to switch to on / off. Press the ENTER / TEST key one last time to return to normal view. 16 ENGLISH SCAN: Fans are switched on and off via a remote system (i.e. MT200 control unit) connected to terminals 4 and 5. The Display will show the initial acronym SCAN and the AUTO LED will flash. The display alternately and automatically shows the values of channel 1 and those of channel 2. ERRORS OVERCURRENT: Indicates current consumption greater than the value measured during calibration. The FAULT relay switches. The ventilation line stops. UNDERCURRENT: Indicates current consumption below the value measured during calibration. The FAULT relay switches. The ventilation line is not stopped. OVERTEMP: Indicates over temperature fault in at least one motor. The FAULT relay switches. The ventilation line stops. 17 ENGLISH ELECTRICAL PROPERTIES • Container 90X90X130 mm, including the terminals. • Front panel 96x96 mm. • Weight 0.5 Kg. • ABS self extinguishing container. • Power supply (220÷240) Volt AC ± 10% 50/60 Hz. • Electrical connections on removable polarized terminals. • Measurement and control of current absorbed by fan motors on two independent lines. • Auto-calibration of rated current absorbed by each ventilation line. • Generation of warning signals in case of current consumption greater or lower than the nominal current measured upon auto-calibration, overtemperature of at least one motor. • Operating mode (via remote control of ventilation system): automatic, manual or channel scan. • Outputs: fault relay 250 VAC, 5 A maximum resistive, one switch contact. • Maximum management flexibility and ease of programming. • Working temperature of the control unit from -40°C to + +60°C. • Manufactured according to regulations • Maximum permissible ambient humidity 90%, non-condensing. • Permanent storage of programmed values for more than ten years. • Dielectric strength 2.5 KVAC for 60”. 18 . TAB 1 19 20 21 22 Diel srl Via A. Pizzocaro, 9 - 36075 MONTECCHIO MAGGIORE (VI) ITALY Tel +39 0444 440977 - Fax +39 0444 448728 mail: [email protected] - www.diel-ed.it 2018_01
advertisement
Key Features
- Dual Ventilation Lines
- PTC Temperature Monitoring
- Automatic, Manual, and Scan Modes
- Current Consumption Monitoring
- Over-Temperature Protection
- Fault Relay
- Easy Configuration and Programming