Valor 535XAP Installation And Owner's Manual

Valor 535XAP Installation And Owner's Manual

The Valor 535XAP is a direct vent gas fireplace heater designed for use with propane gas. It features a high-efficiency design that provides warmth and ambiance to your home. You can install it in a bedroom or a bed-sitting room as it's approved for such locations. It has multiple venting options, including horizontal and vertical terminations, making it adaptable to various configurations. You can also choose optional features like a circulating fan for improved heat distribution and a conversion kit for natural gas usage.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Valor 535XAP Installation And Owner's Manual | Manualzz
DIRECT VENT GAS FIREPLACE HEATER
MODEL 535 XAN (Natural Gas)
MODEL 535XAP (Propane)
Installation and Owner’s Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
-WHAT TO DO IF YOU SMELL GAS
•
•
Do not try to light any appliance.
Do not touch any electrical switch: do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
PLEASE READ THIS MANUAL BEFORE
INSTALLING AND OPERATING THIS
APPLIANCE.
This appliance may be installed in an
aftermarket permanently located,
manufactured (mobile) home, where not
prohibited by local codes.
The appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.
This appliance is a domestic room-heating
appliance. It must not be used for any
other purpose such as drying clothes etc.
This appliance is suitable for installation in a
bedroom or bed sitting room.
Massachusetts: the piping and the final
gas connection must be performed by a
licensed plumber or gas fitter in the State
of Massachusetts. See Carbon Monoxide
Detectors requirement on page 4.
Manufactured by
MILES INDUSTRIES LTD.
British Columbia, Canada
4000309-08
CONTENTS
1.
2.
SAFETY INFORMATION........................................................................................................................................................................ 3
OPTIONS..................................................................................................................................................................................................... 6
2.1.
Optional features................................................................................................................................................................................ 6
2.2.
Venting options................................................................................................................................................................................... 6
3. GENERAL ................................................................................................................................................................................................... 8
3.1.
Approvals & codes ............................................................................................................................................................................. 8
3.2.
Ratings................................................................................................................................................................................................. 8
3.3.
Wall Thickness .................................................................................................................................................................................. 8
4. LOCATION ................................................................................................................................................................................................. 9
4.1.
Framing ............................................................................................................................................................................................... 9
4.2.
Horizontal rear termination ........................................................................................................................................................... 10
4.3.
Horizontal side termination ............................................................................................................................................................ 11
4.4.
Horizontal side or rear snorkel termination ................................................................................................................................. 11
4.5.
Corner location, horizontal termination, 45° pipe bend.............................................................................................................. 11
4.6.
Through the roof termination*....................................................................................................................................................... 12
4.7.
Offset and through the roof termination*..................................................................................................................................... 12
4.8.
Vent location ..................................................................................................................................................................................... 13
5. SUPPLY GAS ............................................................................................................................................................................................ 14
6. PACK CONTENTS .................................................................................................................................................................................. 14
7. APPLIANCE PREPARATION............................................................................................................................................................... 16
7.1.
Window Removal ............................................................................................................................................................................ 16
7.2.
Ignition Spark Check....................................................................................................................................................................... 16
7.3.
# 817VAK Pipe Adapter Fitting .................................................................................................................................................... 17
7.4.
Top Heat Shield & Stand-off Fitting.............................................................................................................................................. 17
7.5.
Support Angle Fitting ...................................................................................................................................................................... 17
7.6.
Attaching Air Restrictors................................................................................................................................................................ 18
7.7.
Attaching Rear Ceramic Support .................................................................................................................................................. 18
7.8.
Attaching to the Framing ................................................................................................................................................................ 18
8. INSTALLATIONS WITH HORIZONTAL TERMINATION – INSTALLING TO WALL.......................................................... 19
8.1.
Wall Opening.................................................................................................................................................................................... 19
8.2.
Valor Terminal #551DVK - Preparing Wall Plates ..................................................................................................................... 19
8.3.
Dura-vent Terminals – Installing to wall ...................................................................................................................................... 20
9. INSTALLATIONS WITH THROUGH THE ROOF VERTICAL TERMINATION ..................................................................... 21
10. REMOTE CONTROL INSTALLATION............................................................................................................................................. 22
11. GAS SUPPLY INSTALLATION & AERATION SETTING ............................................................................................................. 23
11.1.
Gas Supply Installation ................................................................................................................................................................... 23
11.2.
AERATION SETTING CHECK .................................................................................................................................................. 23
12. CERAMIC FUEL BED INSTALLATION ........................................................................................................................................... 24
12.1.
Ceramic Walls Installation ............................................................................................................................................................. 24
12.2.
Ceramic Logs Installation ............................................................................................................................................................... 24
13. WINDOW REFITTING & CHECKING .............................................................................................................................................. 25
14. OPERATION CHECKS.......................................................................................................................................................................... 25
15. FRONT INSTALLATION ...................................................................................................................................................................... 26
15.1.
Additional Optional 3 or 4 Sided Trims ........................................................................................................................................ 26
15.2.
#601SFB Standard Metal Front ..................................................................................................................................................... 26
15.3.
#602CFB Cast Iron Front ............................................................................................................................................................... 26
16. OWNERS INFORMATION ................................................................................................................................................................... 27
16.1.
Operating Your Fire ........................................................................................................................................................................ 27
16.2.
Cleaning............................................................................................................................................................................................. 28
16.3.
Checks ............................................................................................................................................................................................... 29
16.4.
Servicing............................................................................................................................................................................................ 29
16.5.
General servicing.............................................................................................................................................................................. 29
17. LIGHTING INSTRUCTIONS................................................................................................................................................................ 30
18. APPROVED VENTING SUPPLIERS................................................................................................................................................... 31
19. WARRANTY REGISTRATION............................................................................................................................................................ 33
2
1. SAFETY INFORMATION
Keep curtains, clothing, furniture, and other
flammable materials a safe distance from all parts of
the appliance and its vent system.
WARNING: Do not operate the appliance with the
glass front removed, cracked, or broken. Replacement
of the glass should be done by a licensed or qualified
service person.
(The whole window unit may be temporarily removed
by the owner for cleaning the interior of the firebox,
etc.)
Only the authorized Valor replacement window unit
listed in the repair parts booklet must be fitted - never
use substitutes.
If the glass is damaged, search inside and adjacent to
the appliance for any glass fragments.
Keep the appliance area well clear and free from
combustible materials, gasoline and other flammable
vapors and liquids.
Never attempt to burn paper or any other material in
the appliance.
The venting terminal must not be recessed into a wall
or siding.
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
The vent terminal on the outside wall must be kept
free from obstructions. No objects should be placed
within 2 feet (60cm) of the vent terminal. The terminal
is hot during operation and requires a guard if it is
accessible to any person. An approved Valor guard is
available from your dealer.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to
avoid burns or clothing ignition.
During extreme weather conditions ensure that the
vent outlet is free from ice and snow before attempting
to light.
Young children should be carefully supervised when
they are in the same room as the appliance.
Clothing or other flammable material should not be
placed on or near the appliance.
Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the
control system and any gas control, which has been
under water.
This appliance must be installed and repaired by a
qualified service person. The appliance should be
inspected before use and at least annually by a
professional service person. More frequent cleaning
may be required due to excessive lint from carpeting,
bedding material, etc. It is imperative that control
compartments;
burners
and
circulating
air
passageways of the appliance are kept clean.
Should you encounter an operational problem, call
your dealer immediately. Do not try to repair the unit
as you may cause an injury or damage the fireplace.
NOTE
When operating your new fireplace for the first time, some vapors may be released due to the burning of curing compounds
used in the manufacture of the appliance. They may cause a slight odor and could cause the flames to be the full height of the
firebox, or even slightly higher, for the first few hours of operation. It is also possible that these vapors could set off any
smoke detection alarms in the immediate vicinity. These vapors are quite normal on new appliances. You may wish to open
windows into the room to reduce the vapor/odor build up. After a few hours use the vapors will have disappeared and the
flames will be at their normal height.
During the first hour of use, the ceramic firebox walls may go a smoky color. This is not soot. It is a temporary effect lasting
only while the ceramic material becomes stabilized. The walls will revert to their initial color after your fire has been used for
one or two hours.
State of California. Proposition 65 Warning. Fuels used in gas, wood-burning or oil fired appliances, and the
products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects
and other reproductive harm. California Health & Safety Code Sec. 25249.6.
3
State of Massachusetts Carbon Monoxide Detector/Vent Terminal Signage Requirements
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side
wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In
addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
4
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for
venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the
manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with
the appliance or equipment at the completion of the installation.
5
2. OPTIONS
Heater engine unit #535XAN is used with all natural gas
installations.
Heater engine unit #535XAP is used with all propane
installations.
2.2. Venting options
2.2.1.
2.1. Optional features
Circulating fan
Having variable speeds and
temperature control, it is
designed to boost the natural
convection process through the
appliance. It may be fitted
before the fireplace is installed
or retrofitted at a later date –
Kit #755CFK
Natural Gas
Conversion kit
For conversion from propane to
natural gas. Intended primarily
for post installation conversion
in areas where natural gas was
not available at the time of
initial installation.
– Kit #608NGK
Direct vent installations
A list with approved vent suppliers and venting
accessories is shown at the end of this manual.
6
Mantle depth “A”
1”
(25mm)
2”
(51mm)
3”
(76mm)
Mantle clearance
“B”
7”
8”
9”
(178mm) (203mm) (229mm)
4”-5”
(102mm127mm))
10”
(254mm)
6”
(152mm)
7”
(178mm)
11”
(279mm)
12”
(305mm)
8”–12”
(203mm-305mm)
max.
14”
(356mm)
Figure 1 Major dimensions & clearances without optional trims (Shown with #601SFB Front)
3 sided trims
4 sided trims
Figure 2 #601SFB Front with optional trims
3 sided trims
Figure 3 #602CFB Front with optional trims
4 sided trims
7
3. GENERAL
3.1. Approvals & codes
These appliances are certified by C.S.A. for use in Canada and the USA. These appliances are for installation directly venting
through an outside wall or through the roof.
Model 535XAN is for use with natural gas.
Model 535XAP is for use with propane. It can be converted for use with natural gas with kit #608NGK.
These appliances comply with CGA P.4.1, Testing method for measuring annual fireplace efficiencies.
The installation must conform with local codes or, in the absence of local codes with the National Fuel Gas Code, ANSI
Z223.1or the Canadian installation code CAN/CGA-149. Only qualified licensed or trained personnel should install these
appliances.
These appliances, when installed, must be electrically grounded in accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1.
3.2. Ratings
535AN
535AP
Model
Gas
Natural
Propane
Altitude (Ft)
0-4500 1
Input Max. (Btu/h)
30,000
28,000
Input Min (Btu/h)
6,500
14,500
Manifold pressure (in.w.c.)
3.5-3.9
10.3-10.7
Min. Supply pressure (in. w.c.)
5.0
11.0
Max. Supply pressure (in. w.c.)
10.5
14.0
1
Tested to CAN/CGA - 2.17 Gas fired appliances for use at high altitudes. In the USA, installations may require deration over
2000ft - Check local codes.
3.3. Wall Thickness
The vent system (when horizontally terminated) is approved to pass through combustible wall construction of up to 14”
(36cm) thick.
A non-combustible wall can be any thickness up to the maximum horizontal run of vent pipe allowed for the particular
installation – See section 4.
8
4. LOCATION
4.1. Framing
The framing dimensions are shown
in figure 4.
• A non-combustible hearth is
not necessary in front of this
appliance.
• Note that the unit is installed at
the framing stage and fixed to
the framing using the support
angles. Wall finish (cement
board above) is then installed
over the support angels up to
the black frame on the unit.
• Be aware of the area 9” x 35½”
(23cm x 90.2cm) immediately
above the opening area shown
hatched in figure 4 which must
be constructed with noncombustible materials (such as
cement board).
Figure 4 Framing
9
4.2. Horizontal rear termination
See figure 5.
Can be used with either #551DVK standard vent kit or another
terminal cap and accessories.
Adapter #817VAK, one 90° vent elbow and pipe lengths will be
required.
(See venting options section of this manual).
The location requirements are shown in the table and graph
below and figure 5.
A: From floor to top of
vent duct
B: Frame front face to
outside wall
C: Frame front face to
inside wall
D: Vertical pipe run
between vent adaptor
and elbow
E: Horizontal pipe run
(including terminal
pipe) from elbow.
Figure 5
For installations with a horizontal rear termination, the
combination of horizontal and vertical vent pipes must be
within the allowed area shown in Graph 1. A minimum
vertical pipe run of 6” is necessary.
Example a: If a vertical rise of 2ft 3” is required, the
horizontal run must not be more than 11ft 6”.
Example b: If a horizontal run of 3ft 6” is required, the
vertical run must be at least 1ft 3”.
F: Clearance to
combustible materials
above horizontal pipe
run inside building
(Outside wall
shields/thimbles)
G: Clearance to
combustible materials
below horizontal pipe
run
H: Clearance to
combustible materials
all round vertical pipe
run and at sides of
horizontal pipe run
Minimum
3ft 7 9/16”
(111cm)
16”
(40.6cm)
6”
(152mm)
-
5”
(12.7cm)
Maximum
9ft 19/16”
(278cm)
17ft 4”
(528cm)
6ft
(183cm)
16ft
(488cm) with
no elbows in
horizontal run
-
15/16”
(3.3cm)
-
2”
(5.1cm)
-
The horizontal vent pipe run may be
redirected by using elbows up to a total of
180º but the maximum horizontal run (E in
figure 5 & graph 1) is reduced by 18” for
every 45º. For example if two 90º elbows are used
as in figure 5a the maximum horizontal run is
reduced by 3ft per elbow –
Total reduction = 6ft.
Figure 5a
(See page 16 graph 2 for restrictor installation detail)
Graph 1
10
4.3.
Horizontal side termination
See figures 5 &6.
Can be used with either #551DVK standard vent kit
or another terminal cap and accessories.
Adapter #817VAK, one 90° vent elbow and pipe
lengths will be required.
(See venting options section of this manual).
All vent length dimensions and clearance limits are
as section 4.2.
The minimum floor location is shown in figure 6.
Figure 6
4.4. Horizontal side or rear
snorkel termination
The dimensional requirements in sections
4.2 and 4.3 apply.
Adapter #817VAK, one 90° vent elbow and
pipe lengths will be required.
A thimble kit may also be necessary.
(See venting section of this manual).
4.5. Corner location, horizontal
termination, 45° pipe bend
See figures 5 & 7.
Can be used with either #551DVK standard
vent kit or another terminal cap and
accessories.
Adapter #817VAK, one 90° vent elbow and
pipe lengths will be required. (See venting
Figure 7
section of this manual).
All vent length dimensions and clearance
limits are as section 4.2.
The minimum corner location is shown in fig. 7.
11
4.6. Through the roof termination*
See figure 8.
Adapter #817VAK, pipe lengths, a vertical vent terminal, and
roof flashing will be required. Various other ceiling or roof
items may be necessary depending on the particular
installation. (See venting options section of this manual).
4.7. Offset and through the roof termination*
See figure 9.
For situations where offset is necessary in an attic to avoid
obstructions or allow useful space.
Adapter #817VAK, two 45° vent elbows, wall straps, a
vertical vent terminal, roof flashing and pipe lengths will be
required. Various other ceiling or roof items may be
necessary depending on the particular installation. (See
venting options section of this manual).
*Note
1. The distance from the roof to the lowest terminal
discharge opening depends on the roof pitch and must be
in accordance with the manufacturer’s instructions
supplied with the termination unit.
2. The venting system for these appliances is considered to
be a Special Venting System. The rule in the Installation
Code CAN/CGA–B149 requiring a minimum vent
height of 2ft above any portion of a building within 10ft
does not, therefore, apply.
Figure 8
Figure 9
12
4.8. Vent location
• The vent terminal must be located on an outside wall or through the roof.
• This direct vent appliance is designed to operate when an undisturbed airflow hits the outside vent terminal from any
direction.
• The minimum clearances from this terminal that must be maintained when located on an outside wall are shown in figure
10. Any reduction in these clearances could result in a disruption of the airflow or a safety hazard. Local codes or
regulations may require greater clearances.
• The vent terminal must not be recessed into a wall or siding.
• The vent terminal should be positioned where it will not be covered by any snowdrifts.
Fig. 10 Vent terminal locations
KEY
A
B
C
D
E
F
G
H
I
J
K
L
M
Note:
VENT TERMINAL LOCATIONS - MINIMUM DISTANCES
See figure 10
Clearance above grade, verandah, porch, deck or balcony
Clearance to window or door that may be opened
Clearance to permanently closed window (recommended to prevent
condensation on window)
Vertical clearance to ventilated soffit located above the terminal within a
horizontal distance of 2 feet (60 cm) from the center-line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Horizontal clearance to center-line of meter/regulator assembly located
within 15 feet below the terminal
Clearance to service regulator vent outlet
Clearance to non-mechanical air supply inlet to the building or the
combustion air inlet to any other appliance
Clearance to a mechanical air supply inlet
Clearance above paved sidewalk or a paved driveway located on public
property.
Note: A vent must not terminate directly above a sidewalk or paved
driveway, which is located between two single-family dwellings
and serves both dwellings.
Clearance under a verandah, porch, deck or balcony
Only permitted if veranda, porch, deck, or balcony is fully open on a
minimum of 2 sides beneath the floor.
Local codes and regulations may require different clearances.
13
MINIMUM CLEARANCE
Ins
Cms
12
30
12
30
12
30
18
46
12
12
12
36
30
30
30
90
36
12
90
30
72
84
180
210
12
30
5. SUPPLY GAS
Heater engine unit #535XAN is used with all natural gas installations.
Heater engine unit #535XAP is used with all propane installations.
The supply pressure must be between the limits shown in section 3.2 of this manual.
The supply connection is 3/8’’NPT.
The opening for the gas supply line is at the rear left corner of the appliance. See figure 11
6. PACK CONTENTS
#535XAN or #535XAP Engine unit
1 Appliance engine unit fitted with window
1 Ceramic ash bed
5 Ceramic logs
1 Firebox ceramic rear wall
2 Firebox ceramic sidewalls
1 Port cover
2 Frame side fixing brackets
1 Ash bed rear support
2 Restrictor plates for horizontal termination
installations
2 Restrictor plates for through the roof termination
installations
1 Gas inlet pipe connection adapter
1 Top heat shield panel
1 Frame top support angle
2 Stand-off brackets
2 Screws for wall switch plate
4 Screws for frame side fixing brackets
2 Screws for top heat shield panel
3 Screws for frame top support angle
6 Screws for standoff brackets
2 Screws for vent fixing
4 Woodscrews for fixing appliance to studding
1 Deluxe remote control
#551DVK Standard horizontal through the wall vent
kit (Alternative to Dura-vent unit)
1 Vent pipe & terminal unit
2 Wall plates
2 Wall shields (Supplied flat)
12 Thread cutting screws
1 Styrofoam cutting support do-nut
8 Wood screws
8 Wall plugs
#755CFK Circulating fan kit (Additional option)
Details are with the kit
#603FSK Black or #604 Champagne Additional
optional 3 sided trims
1 Top trim
2 Side trims
2 Trim fixing brackets
2 Corner connection plates
8 Grub screws for corner connections
10 Screws for side trims & engine attachment
#605FSK Black or #606FSK Champagne Additional
optional 4 sided trims
2 Top & bottom trims
2 Side trims
2 Trim fixing brackets
4 Corner connection plates
16 Grub screws for corner connections
10 Screws for side trims & engine attachment
#601SFB Standard metal front (Alternative)
1 Upper louver unit
1 Lower louver unit
2 Side channels
2 Hinge studs
2 Hinge spacers
2 Magnet counter plates
#602CFB Cast iron front (Alternative)
1 Top casting unit
1 Bottom casting unit
Take care when removing the contents from the packaging to prevent damage. Check that all the contents are in the packs and
are undamaged.
14
15
7. APPLIANCE PREPARATION
7.1.
Window Removal
See figure 12.
• Turn the top three spring loaded window bolts through 900 to release the window
from the firebox.
• Remove the bottom three spring-loaded window bolts.
• Detach the chain from the top right corner of the window.
• Carefully lift the window away. Keep the window and bolts in a safe place.
7.2. Ignition Spark Check
The pilot burner and electrode unit is at the left end of the burner.
Push in the lighting knob and turn counter-clockwise through the “IGN” position to
“PILOT”. A spark should flash across from the pilot electrode to the pilot burner shield.
See figure 13.
Figure 12 Window removal
Figure 13 Ignition spark check
16
7.3.
# 817VAK Pipe Adapter Fitting
Fit the adapter #817VAK securely over the outer vent collars. See figure 15. Drill through the
adapter outer tube and the appliance outer collar for two #6 screws supplied. Make sure that the
drill does not penetrate the inner tubes. Secure with the screws.
7.4. Top heat shield & Stand-off Fitting
See figures 16 & 17
•
Remove the screws at the top rear corner of the case sides.
Figure 15 #817VAK
•
Locate the heat shield over the vent pipe adapter.
Adapter
•
Support the front of the shield on the two angle supports.
•
Secure the shield to the case sides by refitting the two screws at the top rear corners and by two screws from the pack
fitted near the front.
•
Bend the two top rear stand-offs and fit to the heat shield with three screws each – see figure 17.
7.5. Support Angle Fitting
See figure 18
The distance from the wall angles to the front face of the heater case is adjustable between 3/8” (10mm) and 13/16” (30mm) to
allow for a range of wall finish material thicknesses (e.g. tile etc).
•
Fit the top angle support to the case top with three screws.
•
Fit the two side angle supports with two screws each. Fit the screws from inside the heater case.
Figure 17 Top & rear
Stand-offs
Figure 16 Heat shield
Figure 18 Support angles
17
7.6. Attaching Air Restrictors
There are two types of restrictor supplied with each
#535 engine unit. One type is for installations with
horizontal vent termination and the other is for
installations with through-the-roof termination.
Figure 19 identifies them.
The restrictors cover part of the openings in the
firebox rear wall ports – See figure 20.
To fit the restrictors, remove the center screws
from the rear ports and fit the restrictors using
these screws. To set the restrictors at maximum
port opening, slacken the bottom screws in the
ports, slide the restrictors down as far as possible
and tighten the screws over the restrictors.
To set the restrictors at minimum port opening,
Figure 19. Restrictor identification
slide the restrictors up as far as possible and tighten
the screws.
7.6.1.
Installations with Horizontal Termination
Do not fit restrictors if the vertical rise is less than 3ft.
Do not fit restrictors if the horizontal run is more than 4ft.
For installations with a horizontal run of 4ft or less and having a
vertical rise of 3ft or more fit the restrictors at maximum port opening
position. See Graph 2.
On models 535 the horizontal type restrictors are never set at any
position except maximum port opening.
Figure 20 Restrictor fitting
Figure 21 Rear ceramic support
Graph 2
7.6.2.
Installations with Through-the-roof Termination
For vent heights up to 20ft. Fit the restrictors at maximum port
opening position.
For vent heights above 20ft Fit the restrictors at minimum port
opening position.
7.7. Attaching Rear Ceramic Support
Fit the rear ceramic support to the firebox back panel with three
screws. See figure 21.
7.8. Attaching to the Framing
•
•
•
Figure 21a Adjustment for wall finish
Place the heater in position in the framing.
Secure the side support angles to the side studding through
two holes each side with the woodscrews supplied. The top support angle should abut the cement board but is not fixed
to the framing.
Check the wall finish requirements with the homeowner. If necessary, adjust the position of the heater so that the
distance from the front of the heater case to the angles is suitable for the thickness of the wall finish (e.g. tile, etc.) – see
figure 21a.
18
8. INSTALLATIONS WITH HORIZONTAL TERMINATION – INSTALLING
TO WALL
Important Installer Notice – Weather Sealing & Vapor Barriers
It is the installer’s responsibility to ensure that vent installations through exterior walls are caulked and weatherproofed in
such a manner as to:
•
Prevent rain water from entering the wall from the weather side by adequately caulking the outer vent plate to the
exterior wall surface.
•
Prevent moisture inside the home from penetrating into the wall structure by ensuring the inside wall plate is
adequately sealed to the inside vapor barrier.
•
Prevent rain water and moisture from entering the walls by sealing the joints between the outer vent tube and the inner
and outer wall plates.
We recommend the use of a high quality polyurethane sealant.
See section 4 for full range of horizontal termination applications.
8.1. Wall Opening
• Fit all the required pipes and elbows up to the wall to check the wall
opening position. See the manufacturer’s instructions supplied with
the sections.
• Make Wall Opening.
If the wall is constructed of solid non-combustible materials and has no
combustible surface cladding (including wood) inside or outside then
the wall plates or thimbles will not be required.
If the wall has combustible material, mark the wall for a 10”x10”
square. If the wall is totally non-combustible (e.g. masonry block or
concrete) mark for a 7” circular hole. In both cases, the center of the
hole should line up with the centerline of the horizontal vent. (see
figure 24)
8.2. Valor Terminal #551DVK - Preparing Wall Plates
The wall plates are not used for 7” hole in non-combustible walls.
1. Bend the wall shields and screw to the inside of the wall plates with
Figure 24
6 thread cutting screws per plate. See figure 22.
2. Bend the inner wall plate tab as shown in figure 23 so that the seam
on the terminal tube will pass
clearly through the plate with
the wall shield at the top. Place
the inner wall plate over the
terminal unit.
3. Slide the terminal into the wall.
Make sure that the drain hole is
at the bottom – the seam will be
through the notch in the wall
plates – See figure 24.
4. Slide the inner wall plate up to
the wall. Mark the four holes
for the wall screws. Slide the
plate away.
5. Drill and plug the wall.
6. Screw the plate to the wall with
Figure 23
4 screws provided.
Figure 22
7. Bend the outer wall plate tab as
shown in figure 23.
8. Place the outer wall plate over the terminal unit. Slide the wall plate up to the wall. Mark the four holes for the wall
screws. Slide the plate away.
9. Drill and plug the wall.
10. Screw the plate to the wall with 4 screws provided.
See figure 24.
19
8.3. Terminals – Installing to wall
Unless the wall is totally non-combustible, fit wall
thimbles.
Install as detailed in the manufacturer’s instructions
supplied with the pipes.
Figure 24B
Figure24C
Figure 24A
20
9. INSTALLATIONS WITH THROUGH THE ROOF VERTICAL
TERMINATION
• Check the roof pitch to determine which roof flashing will be needed see vent accessories section 2.4.
• The distance from the roof to the lowest terminal discharge opening
(“H” in figure 25) depends on the roof pitch and must be in accordance
with the Dura-vent instructions supplied with the termination unit.
Note: The venting system for these appliances is considered to be a
Special Venting System. The rule in the Installation Code requiring a
minimum vent height of 2ft above any portion of a building within 10ft
does not therefore apply.
• The minimum clearances to combustible materials all round the vent
pipes must be in accordance with the dimensions shown in section 4 of
this manual.
• Drop a plumb from the ceiling to the center of the appliance vent
opening. Mark the position on the ceiling. Drill a small hole at the
marked position.
• Determine the position where the vent will pass through the roof. If
directly above the position where it penetrates the ceiling, drop a plumb
from the roof to the small hole in the ceiling and mark the roof at this
spot.
If rafters or other obstructions will prevent a vertical exit or if clear attic
space is desired, the roof outlet can be offset using 45º elbows - see fig.
25.
Drill a small hole at the marked position.
• A ceiling fire stop must be installed at the second floor and higher
floors.
A ceiling support should be used below the flat ceiling.
To install the fire stop & support cut and frame a 10” (254mm) square
hole centered on the small hole previously drilled - see fig. 26.
• Fit vent accessory elbows and pipe lengths as required up through
ceiling support boxes and fire stops.
If installation includes offset, support the offsetting pipes every 3 feet
(1m) with wall straps (fig. 25).
• Cut a hole in the roof centered on the small hole. The hole
must allow for the minimum clearances to combustible
materials - see section 4.
• Fit pipe lengths through the roof. Fit roof flashing
securing it with roofing nails.
• Fit storm collar and termination cap.
Fig 25 Through the roof installation
Fig 26 Fire stop hole
21
10. REMOTE CONTROL INSTALLATION
Caution! Don’t connect the batteries to the remote control receiver until the wires are
connected to the burner control unit, as short circuit could result in destruction of the
electrical components.
When installing the remote please refer to figures 37 and 38 below.
•
•
•
•
•
•
•
Connect the wiring harness to the receiver box, by pushing the wire connector on to the receiver circuit
board. The plug will only go on one way so please ensure that the wires are pointing up and slot in the
board is inline with the tab on the wiring harness plug
Connect wires “A” (with the “L” terminals)
to the connectors “B” on the control valve
Please note that the connectors are
“D”
different sizes, the smaller one fits to the
lower connection on the valve.
Connect the wires “C” to the connectors
“B”
“D” on the control valve. (Either wire can
be fitted to either connector).
Remove the remote control receiver lid.
Fit four 1.5V batteries.
Place the remote control receiver on the
“Velcro” pad.
Fit the 9V battery to the handset
transmitter
Remote control operating instructions are on
page 31 of this manual and are supplied with
the remote control kit.
Figure 37 Valve connections
“A”
“C”
Figure 38
22
11. GAS SUPPLY INSTALLATION & AERATION SETTING
11.1. Gas Supply Installation
• The gas supply pipe should enter the appliance case through the opening at the rear left side. The supply pipe should be
connected to the appliance gas inlet pipe situated at the left side of the control unit. Supply line connection to the inlet
pipe is 3/8”NPT.
If the circulating fan is to be installed, be aware that the supply pipe run inside the case should be at the same height
as the appliance inlet pipe in order to clear the fan. If intending to fit an internal isolating valve, check that it will be
clear of the fan.
• Use only new black iron or steel pipes or copper tubing if acceptable - check local codes. Note that in USA copper tubing
must be internally tinned for protection against sulfur compounds.
• Unions in gas lines should be of ground joint type.
• The gas supply line must be sized and installed to provide a supply of gas sufficient to meet the maximum demand of the
appliance without undue loss of pressure.
• Sealant used must be resistant to the action of all gas constituents including LP gas. Sealant should be applied lightly to
male threads to ensure excess sealant does not enter gas lines.
• The supply line should include a manual shut-off valve to allow the appliance to be disconnected for servicing.
• A plugged 1/8”NPT tapping must be installed in the line. The tapping must be accessible for test gauge connection and be
immediately upstream of the gas supply connection to the appliance.
• Pressure test the supply line for leaks.
f The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of ½psig (3.5kPa).
f The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than ½psig (3.5kPa).
f Failure to either disconnect or isolate the appliance during pressure testing may result in regulator or valve damage.
Consult your dealer in this case.
• The minimum supply pressure is given in section 3 of this manual.
• All piping and connections must be tested for leaks after installation or servicing. All leaks must be corrected
immediately.
• When testing for leaks:
f Make sure that the appliance is turned off.
f Open the manual shut-off valve.
f Test for leaks by applying a liquid detergent or soap
solution to all joints. Bubbles forming indicate a gas
leak. Never use an open flame to check for leaks.
f Correct any leak detected immediately.
• The pressure test tapping locations are shown in figure 34. A
built-in non-adjustable regulator controls the burner
manifold pressure. The correct pressure range is shown in
the table in section 3 of this manual. The pressure check
should be made with the burner alight and the thermostat at
its highest setting. See lighting instruction section for full
Figure 34 Pressure test tappings
operating details.
11.2. AERATION SETTING CHECK
Aeration is factory set.
The setting is non-adjustable for LP appliances.
For natural gas appliances, the shutter is factory set at an aeration gap that
will give optimum performance for the vast majority of installations.
However, in a few unusual installations performance may be improved by
adjusting the aeration. The need for adjustment should be determined by
operating the appliance with the ceramic fuel effects and window installed.
See the “Final checks” section in this manual for adjustment details.
Adjust the aeration by slackening the aeration plate screw and sliding the
plate. In an extreme circumstance, the plate can be totally removed. See
figure 35.
Figure 35 Aeration setting
23
12. CERAMIC FUEL BED INSTALLATION
12.1. Ceramic Walls
Installation
1. Locate the ceramic rear wall
in the channel at back of the
firebox and flat against the back of
the firebox. See figure 36.
2. Locate the sidewalls against
the sides of the firebox. Make sure
that they are behind the raised
edges of the burner module base at
the back corners. See figure 37.
3. Remove two screws from
under the top front of the firebox.
Using these screws fit the port
cover. See figure 38.
12.2. Ceramic Logs
Installation
1.
Place the ash bed in
position. The projections
at the front of the ash bed
locate against the sloping
metal stops immediately
behind the burner. See
figure 39.
2.
Place the rear log
in position locating the
two top projections in the
ash bed into the holes in
the rear log. See figure 40.
3.
Place the front log
at the front of the firebox
as shown in figure 41.
4.
Place the right side
center log in position
locating it on the two
locating pins on the left
hand side of the ash bed
with its “nose” resting at
the center of the ash bed
as shown in figure 42.
Figure 38 Port cover
Figure 37 Side walls
Figure 36 Rear wall
Figure 41 Front log
Figure 40 Rear log
Figure 42 left centre log
Figure 39 Ash bed
5.
Place the right side center log in position
locating on the two pins on the right hand side of the
ash bed with its nose” resting at the center of the ash
bed as shown in figure 43.
6.
Place “branch end” of the cross log on the pin
located on the center of the rear log and the other end in
the locating pocket on the left side of the front log as
shown in figure 44.
Figure 43 right centre log
24
Figure 44 Cross log
13. WINDOW REFITTING & CHECKING
•
•
•
•
Refit the window with the bottom three bolts. The bolts should be screwed in securely.
Refit the chain to the top right corner of the window.
Refit the top three bolts securing by turning them through 90º.
Pull the top of the window forward and release to check that it opens slightly and
returns in the event of a delayed ignition explosion. See figure 44.
• Similarly check the bottom of the window by pulling it forward and releasing. See
figure 45.
Figure 45
14. OPERATION CHECKS
• Check ignition, pilot stability, burner flames, and the full range of the thermostat settings using the rotary switch inside
the appliance and all other controls (wall switch, remote hand unit). See owner’s lighting instructions further on in this
manual for full details.
• Aeration adjustment
As described in section 11, for natural gas appliances, the burner aeration is adjustable. For the vast majority of installations,
no adjustment will be necessary. However, in a very few instances, performance may be improved by sliding the shutter to
adjust the aeration by (See figure 35). Evaluate the aeration only after the unit has warmed up – approximately 15 minutes.
Increasing aeration will cause the flame to appear more transparent and blue making the ceramic fuel effects glow more.
Decreasing aeration will cause the flames to appear more yellow or orange making the fuel effects glow less. Too little
aeration may result in black carbon forming and dropping into the firebox.
25
15. FRONT INSTALLATION
15.1. Additional
Optional 3 or 4
Sided Trims
• Slide a corner
connection plate into the
channels in the top trim
and a side trim. Butt the
two trims together. Fit
four grub screws and
Figure 46 Trim bracket attachment
tighten to secure the trims Figure 45 Trims & corner plate
attachment
and corner plate. See
figure 45.
• Repeat for the other corner(s).
• Attach the two trim fixing brackets to the side trims with three screws each side. The brackets
must butt up to the edges of the corner connection plates. See figure 46.
• Attach the complete trim unit to the
firebox with four screws as shown in figure
47.
15.2. #601SFB Standard Metal
Front
• Fit the lower louver unit using the hinge
studs and hinge spacers as shown in figure 48.
• Fix the two adhesive backed magnet
counter plates to the tabs at the firebox sides,
which line up with the magnets on the lower
louver. See figure 48.
• Fit the two side channels by hooking into
the openings at the sides of the firebox as
shown in figure 49.
• Attach the upper louver by hooking over
the tabs near the top of the firebox sides. See
figure 50.
Figure 47 Trim unit
installation
15.3. #602CFB Cast Iron Front
• Attach the bottom-casting unit by
hooking over the lower tabs at the firebox
Figure 48 Lower louver & magnet counter plate
sides. See figure 51.
installation
• Attach the top-casting unit by hooking
over the four tabs at the firebox sides as shown in figure 52.
Figure 49 Side channel
installation
Figure 50 Upper louver installation
Figure 51 Bottom casting installation
Figure 52 Top casting installation
26
16. OWNERS INFORMATION
Please read the safety information and notes on page 3.
16.1. Operating Your Fire
The operating instructions are also on a chained plate inside the control access door.
1. For your safety, this appliance is fitted with a flame supervision device, which will shut off the gas supply if, for any
reason, the pilot flames go out. This device incorporates a fixed probe, which senses the heat from the pilot flame. If the
probe is cool, the device will prevent any gas flow unless the burner control knob is kept pushed in at the PILOT position.
See full lighting instructions on next page.
2. The Valorstat Programmable Remote Control
Your Valor Remote Control helps you get the comfort, convenience and aesthetics you want from your Valor Gas Fireplace.
The first thing to do is to set the time:
1. With your left thumb, hold down both the “AUTO” and the “TIMER” button until the temperature symbol flashes.
Let go.
2. Note the digital clock on the bottom right hand corner. The large “up” button (σ) sets the hour; the “down” (τ)
button sets the minutes. Set the time. Note: you must start setting the time while the temperature symbol is flashing.
If it stops flashing, go back to 1.
3. Let go and wait until the flashing stops. The remote tells you the time you set. It also tells you the current
temperature.
The “remote” controls your fireplace in three different ways.
Setting the Temperature
Use this setting when you come in and want to enjoy a certain temperature.
Here’s what you do:
1. Push the “AUTO” button until the temperature reading flashes. Let go.
2. While it is still flashing, push the up and down button to the temperature you want. Let it go.
3. Your Valor will reach that temperature and the remote will check the temperature every five minutes, adjusting the
amount of fuel needed to give you a steady, even heat.
Note: be patient with settings as it can take a few seconds.
Setting the Flame
Use this setting when you want a particular flame level. For instance, you want to watch flames burn at their highest level,
and you don’t mind if the room is too hot.
Here’s what you do:
1. Press either of the large “up” or “down” buttons.
2. The word “man” displays as well as an arrow in the left upper corner. Let go.
3. To raise the flame, press and hold the “up” button until you come to the flame level you want. Let go.
4. To lower the flame, press and hold the down button until you come to the flame you want. Let go.
5. The flame level will remain just as you set it.
Programming Time and Temperature
You can set your Valor to come on before you waken and turn after you leave home and turn on again just before you come
home and turn off after going to bed. You can leave it like this for the heating season.
Here’s what you do:
1. Decide what temperature you want your Valor to be at; also decide what time you want your Valor to turn on and
off; then decide what time you want it to come back on and off in the afternoon or evening. For the first few times
you set the timer, it’s handy to write these times down.
2. Set the temperature (just as you did in the section on “setting the temperature.”
3. Press the “timer” button and hold until “P1*” appears and flashes. Let go. While flashing, push the “up” button to
the hour you want your Valor to turn on in the morning and the “down” to the minute.
4. Press “timer” to P1 (moon) and proceed as in step 3, to turn off time.
5. Press “timer” again, and you get “P2*” to set the time to come back on in the afternoon. Set the time.
6. Press “timer” again to get P2 (moon) to set the time for your Valor to go off in the evening.
7. Do nothing else, and your Valor will give you steady, even heat at the temperatures and times you set.
8. Note: If you want to set your Valor for only 1 time on and off, set P2 for the same times as P1.
9. To temporarily override the timer setting, just press “auto” or “manual”. Press “timer” when you want to go back to
your settings.
When first turned on, the decorative flames will appear predominantly blue. After approximately 15 minutes the
flames will turn yellow.
27
16.2. Cleaning
It will be necessary to clean the glass periodically. During startup, condensation, which is normal, forms on the inside of the
glass and causes dust, lint etc. to cling to the glass surface. Initially paint, while curing, may deposit a slight film on the glass.
We therefore recommend that, during the first few weeks of use, the glass is cleaned two or three times with non-abrasive
common household cleaners and warm water. Ammonia based cleaners should not be
used. Subsequently the glass should be cleaned two or three times a season depending
on the circumstances. Do not clean the glass while it is hot.
Always close the window securely before lighting
16.2.1. To Clean the Inside of the Glass
•
Louver Fronts: Lift and unhook the top louver – see figure 59. Lift and unhook
the two side channels – see figure 60. Open the bottom louver – It does not need to be
Figure 59 Louver removal
removed.
•
Cast Iron Fronts: Lift up and unhook the upper casting. The bottom casting does
not need to be removed. See figure 61.
•
Push in the three spring loaded bolts at the top of the window and make a quarter turn so
that the slots in the bolt heads are horizontal. This will release the top of the window. Swing the
top of the window open as far as the chain will allow. The window should be open enough to let
you clean the inside of the glass. See figure 62.
Always securely fasten the window before lighting.
16.3. Clean the Ceramic Fuel Effects, Firebox Walls & Burner
Dust, etc. can be brushed from the ceramic fuel effects and firebox walls after removing the
front unit and completely removing the window.
Dust etc. can also be removed from the burner using a soft brush after removing the ceramic fuel
effects.
• Louver Fronts: Lift and unhook the top louver. Open the bottom louver – It does not need
to be removed. See figure 59.
Cast Iron Fronts: Lift up and unhook the upper casting. Lift up and unhook the bottom
casting. See figure 61.
•
Push in the three spring loaded bolts at the top of the window and make a quarter
turn so that the slots in the bolt heads are horizontal. This will release the top of
the window. See figure 62.
•
Remove the bottom three spring-loaded window bolts. See figure 62.
•
Detach the chain from the top right corner of the window. See figure 62.
•
Carefully lift the window away. Keep the window and bolts in a safe place.
Always completely remove the window before removing the ceramic fuel effects.
When cleaning, make sure that no particles are brushed into the slots in the burner.
Always securely replace the window securely before lighting.
Figure 60 Side channel
removal
Figure 61 Cast top front removal
Figure 62 Window opening & removal
28
16.4. Checks
• A periodic check of the pilot and burner flames should be made. Check
after the fire has been on for at least 30 minutes. The pilot flame must cover
the tip of the thermocouple probe. The main burner flame pattern will vary
from appliance to appliance depending on the type of installation and climatic
conditions. See figures 63 & 64.
• The appliance area must always be kept clear and free from combustible
materials, gasoline and other flammable vapors and liquids.
• Inspect the vent terminal outdoors regularly to make sure that dirt, snow,
insects, leaves etc, do not obstruct it.
• Examine the whole vent system regularly. We recommend annually.
16.5. Servicing
All appliances use four 1.5V AA batteries for thermostat control.
For Appliances with Wall switch only the batteries are
accessible by opening the bottom access panel.
For Appliances with Remote Control the batteries are accessible
by opening the bottom access panel and removing the lid of the
remote control receiver. The handset has a 9V battery.
Figure 63 Pilot flame
16.6. General servicing
If you require any attention to your appliance, contact your
supplier quoting the model number. It will be helpful if the
appliance serial number can also be quoted. This is on the rating
plate, which is on a chained, plate accessible by opening the
bottom access panel.
The repair parts are shown in the separate repair parts leaflet.
Please always quote part number and description when
requesting spare parts.
Figure 64 Main flames
29
17. LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage,
personal injury or loss of life.
A.This appliance has a pilot which must be lighted by hand. When lighting , follow these instructions exactly. To save
gas, turn the pilot off when not using the appliance.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS:
-Do not try to light any appliance.
-Do not touch any electric switch; do not use any phone in your building.
-Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot
reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the control knobs. Never use tools. If the controls will not push in or turn by
hand, don’t try to repair them, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the control system and any gas control which has been under
water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above
2. Set the thermostat as far clockwise
as possible*.
3. Turn the gas control knob clockwise to OFF.
NOTE: The knob cannot be turned from PILOT to OFF unless it is pushed in
partially. Do not force.
4. Wait five (5) minutes to clear out any gas. then smell for gas, including near the floor. If you smell gas, STOP!
Follow “B” in the safety information above. If you don’t smell gas, go to the next step.
5.
Find the pilot. It is at the left side.
6.
Push in and turn the gas control knob counterclockwise until resistance is felt just before the “IGN” position.
7.
Keep pushed in for a few seconds to allow gas to flow then, keeping knob depressed, turn to “PILOT” to light
pilot. Hold knob in for a further 10 seconds then release. The knob should pop back out. Pilot should remain lit. If
pilot goes out repeat steps 3 through 7. If knob does not pop out when released, stop and immediately call your
service technician or gas supplier; If pilot lights but will not stay lit after several tries, turn the gas control knob
to “OFF” and call your service technician or gas supplier.
8.
When pilot is lit, partially depress the knob and turn to “ON” position (Burner alight). Do not leave knob set
between “PILOT” and “ON”.
9.
Set thermostat to desired setting*.
TO TURN OFF GAS TO APPLIANCE
1.
Set the thermostat as far clockwise as possible*
2.
Push in gas control knobb slightly and turn clockwise to “OFF”. Do not force.
*The flame height can be increased or decreased by depressing the remote control
hand set button.
30
18. APPROVED VENT SUPPLIERS
APPROVED ALTERNATIVE VENT SUPPLIERS FOR
530, 534, 535 AND 739 MODELS
VERTICAL
TERMINATION CAPS
HORIZONTAL
CO-AXIAL KIT,
26" LONG
STANDARD CO-AXIAL
984
HIGH WIND
CO-AXIAL
985
STANDARD CO-AXIAL
980
HIGH WIND
CO-AXIAL
991
EXTENDED
CO-AXIAL
930
4DT-HC
SV4CHC
4DT-VC
VENT ADAPTERS /
COUPLERS
ADJUSTABLE PIPE LENGTH 4" x 6-5/8"
3PDVCV
982
4DT-ST14
SNORKEL, 36" Rise
981
4DT-ST36
UNIVERSAL ADAPTER 3"
FLEX COUPLER
2150
CO-LINEAR FLEX
CONNECTOR
923F
CO-AXIAL TO COLINEAR ADAPTER
923GCL
CO-LINEAR TO CO-AXIAL
ADAPTER
923GK
3” DIAMETER
2280 SERIES
12" TO 17"
17" TO 24"
4" TO 10"
Galvanized
911
Black
Galvanized
Black
Galvanized
911B
912
912B
917
Black
Galvanized
917B
Black
Galvanized
1-1/2" TO 6"
Black
1-1/2" TO
12"
1-1/2" TO
24"
HSDV4658-1313
SV4CGV
SNORKEL, 14" Rise
11" TO
14-5/8"
MILES
INDUSTRIES
551DVK
CO-LINEAR
ALUMINUM
FLEXIBLE
LINER
RLH
INDUSTRIES
SECURE VENT
SELKIRK
VENTING PARTS DESCRIPTION
SIMPSON
DURAVENT
VENTING PARTS CODE / AVAILABILITY BY MANUFACTURER
HS-C33U-99
HS-C33F-1313
559CLT
556CLA
3” AFCL
NOTE: 2-PLY LINER APROVED TO CAN/ULC S635
SUITABLE FOR VENTING GAS APPLIANCES. AS
MANUFACTURED BY Z-FLEX.
4DT-ADJ
4DT-ADJ(B)
SV4LA
SV4LBA
Galvanized
Black
Galvanized
SV4LA12
SV4LBA12
SV4LA24
Black
SV4LBA24
31
DV 90°
ELBOWS
945
Black
945B
945G
945BG
Galvanized Swivel
Black Swivel
Galvanized
Black
Galvanized Swivel
Black Swivel
PIPES 4" x 6 5/8" ( ID x OD )
6" LONG
9" LONG
12" LONG
18" LONG
FLASHINGS
Black
990
990B
990G
990BG
908
908B
SV4EBR90
4DT-EL90
4DT-EL90(B)
4DT-06
4DT-06(B)
Galvanized
907
4DT-09
Black
907B
906
906B
4DT-09(B)
4DT-12
4DT-12(B)
4DT-18
Galvanized
Black
Galvanized
SV4E90
SV4EB90
SV4L6
SV4LB6
SV4L12
SV4LB12
4DT-18(B)
Black
4DT-24
4DT-24(B)
4DT-36
4DT-36(B)
SV4L24
SV4LB24
SV4L36
SV4LB36
Black
902
902B
4DT-48
4DT-48(B)
SV4L48
SV4LB48
ROOF FLASHING
0/12-6/12
943
4DT-AF6
SV4FA
ROOF FLASHING
7/12-12/12
943S
4DT-AF12
SV4B
WALL THIMBLE
943F
942
4DT-WT
SV4F
SV4RSM
24" LONG
36" LONG
Galvanized
Black
Galvanized
Black
Galvanized
FLAT ROOF FLASHING
STORM COLLAR
953
4DT-SC
SV4AC
DECORATIVE PLATE
940
4DT-CS
SV4PF
CATHEDRAL CEILING
SUPPORT
941
4DT-CCS
CEILING FIRESTOP/ FLOOR
SUPPORT
963
4DT-FS
SV4BF
SV4SD
988
950
989
984SG
4DTWS
4DT-VS
4DT-OS
SV4VS
WALL STRAP
VINYL SIDING STANDOFF
ELBOW STRAP
TERMINAL GUARD
MILES
INDUSTRIES
SV4EBR45
SV4E45
SV4EB45
RLH
INDUSTRIES
4DT-EL45
4DT-EL45(B)
904
904B
903
903B
48" LONG
VARIOUS VENTING SYSTEM
PARTS
Galvanized
SECURE
VENT
Galvanized
SELKIRK
DV 45°
ELBOWS
VENTING PARTS
DESCRIPTION
SIMPSON
DURAVENT
VENTING PARTS CODE / AVAILABILITY BY MANUFACTURER
835TG
NOTES: 1) SIMPSON DURA-VENT CO-AXIAL PIPE AND FITTINGS REQUIRE VALOR 817VAK STARTER ADAPTER TO FIT
VALOR SMOOTH COLLARS. ALL OTHER ABOVE MANUFACTURERS' COLLARS WILL FIT DIRECTLY TO SIMPSON DURA-VENT
OR VALOR SMOOTH COLLAR; 2) FOLLOW INSTRUCTIONS PACKAGED WITH EACH MANUFACTURER'S COMPONENTS.
3) UNLESS OTHERWISE SPECIFIED, ALL THE PARTS AND ASSEMBLIES FROM THE ABOVE TABLE ARE TO BE USED
WITH 4" x 6-5/8" PIPES; 4) TERMINATION CAPS MANUFACTURED BY RLH INDUSTRIES ARE FROM HOMESTYLE CHIMNEY
COLLECTION AND CAN BE ORDERED IN ONE OF THE FOLLOWING FINISHES: a) ALUMINIUM; b) BLACK POWDER COATED;
c) SOLID COPPER.
32
17. WARRANTY FOR VALOR BRAND PRODUCTS
17.1.1. If you have a problem with this unit, please contact your dealer or supplier immediately. Under no
circumstances should you attempt to service the unit in any way by yourself. The warranties in
paragraphs 1 and 2 are provided only to the first purchaser/user of this unit, are not transferable
and are subject to the conditions and limitations in paragraphs 3, 4 and 5. Please review the
conditions and limitations carefully and strictly follow their requirements.
17.1.2. Lifetime Limited Parts Warranty
During the lifetime of the first purchaser/user, (subject to paragraph 6) Miles Industries Ltd. (the “Company”) or its appointed distributor will at its option
pay for the repair of, or will exchange the following parts or components which are found to be defective in material or workmanship under normal
conditions of use and service:
Part or Component
Defect Covered
•
Exterior steel casing
Corrosion
•
Glass
Loss of structural integrity
•
Burners and connecting pipes
Corrosion (but not discolouration) causing loss of structural integrity
•
Cast iron parts
Corrosion
•
Fire box and heat exchanger
Corrosion (but not discolouration) causing loss of structural integrity
17.1.3. Two-Year Parts Warranty
For a period of two years from the date of purchase (subject to paragraph 6,) the Company, at its option, will repair or exchange all parts or components of
this unit (other than those listed in paragraph 1) which are found to be defective in material or workmanship.
17.1.4. Travel Time / Shipping Not Covered By Warranty
Travel time by a repairer to perform warranty work or replace a part and any shipping charges incurred in respect of an exchange or replacement of a part
shall be paid for by the owner of the unit.
17.1.5. Conditions and Limitations
1.1
The warranty enrolment card must be completed by the first purchaser/user and countersigned by the dealer or a licensed, competent service
contractor and returned to the Company within 90 days of purchase. Registration can also be completed online at www.valorfireplaces.com.
1.2
Installation and maintenance must be performed by a licensed Valor dealer or a licensed, competent service contractor. Installation must comply
with the enclosed installation instructions and all local and national gas appliance installation and building codes.
1.3
Owner must comply with all operating instructions.
1.4
This warranty is only valid under normal non-commercial conditions of use and service. This warranty is void if there is evidence of misuse,
abuse, alteration, improper installation, accident or lack of maintenance.
1.5
This warranty is void where installation of the unit does not conform to all applicable codes including national and local gas appliance installation
codes and building and fire codes.
1.6
This warranty does not cover damage to the unit by:
•
Improper or inadequate installation, or operational or environmental conditions including improper chimney installation.
•
Inadequate ventilation or competition for air in the home from household equipment or appliances.
•
Damage caused by chemicals; dampness; condensation; or sulphur in the fuel supply lines which exceeds acceptable industry standards.
1.7
This warranty does not extend to or cover glass or log breakage due to misuse, accident, mishandling or lack of maintenance; brass which is
damaged by chemicals or down draft conditions; chipping of enamel or painted surfaces or damage to the unit while in transit.
1.8
The Company does not authorize anyone, including its dealers, to extend or alter this warranty in any way and assumes no responsibility for
direct, indirect or consequential damages caused by this unit. The laws of the state or province in which the first purchaser/user lives may give the first
purchaser/user specific rights which extend this warranty and in that event, the Company’s sole obligation under this warranty is to provide labour and/or
materials in accordance with those laws.
17.1.6. Discharge of Liability
After two years from the date of purchase, the Company may, at its option, fully discharge all obligations under this warranty by paying to the first
purchaser/user the wholesale price of any defective part.
17.1.7. No Obligation to Pay Labour Costs
The Company shall not be responsible for the cost of labour to remove any defective part nor to reinstall any replacement or repaired part. Repair work will
be done at the place where the unit is installed or in the repairer’s shop, at the repairer’s option.
17.1.8. No Other Warranty
The entire obligation to repair this unit is set forth in this warranty. Some States or Provinces may specifically mandate additional warranties on the part of
manufacturers, but in the absence of any such specifically mandated legislation, there is no other warranty or obligation expressed or implied
33

advertisement

Key Features

  • Propane gas
  • Direct vent
  • High efficiency
  • Bedroom/bed-sitting room
  • Horizontal & vertical venting
  • Circulating fan (optional)
  • Natural gas conversion kit (optional)
  • C.S.A. certified

Frequently Answers and Questions

Can I install the Valor 535XAP in a bedroom?
Yes, this appliance is approved for installation in a bedroom or a bed-sitting room.
What type of gas does the Valor 535XAP use?
It's designed for propane gas, but you can convert it to natural gas using the optional conversion kit.
What kind of venting options are available?
You can choose between horizontal and vertical terminations for venting the appliance.

Related manuals

Download PDF

advertisement