Omron K6EL, K6EL-500 Manual

Omron K6EL, K6EL-500 Manual

Omron K6EL-500 is a high-speed, compact ground fault relay designed for use in low-voltage circuits. It features a selectable operating time of less than 0.1 seconds and is engineered for high reliability, even when working with inverter loads. The K6EL-500 offers flexibility with its switchable sensed current, allowing you to adjust sensitivity based on your specific application requirements. For remote monitoring, the automatic-reset models provide continuous fault detection and alert you to potential issues. The K6EL-500 is compatible with a range of through-type ZCTs (Zero-phase Current Transformers), simplifying installation and ensuring seamless integration into your electrical system.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Omron K6EL-500 - Ground Fault Relay User Manual | Manualzz
Ground Fault Relay
K6EL
Economical, Compact, High-performance,
DIN 48 u 48-mm Ground Fault Relay for Low
Voltages
• Performs continuous monitoring and detection of ground faults
in low-voltage circuits due to the deterioration of insulation in
electrical devices.
• Higher reliability ensured with improved resistance to high-frequency noise when used for inverter loads.
• Remote monitoring of cubicles is possible with automatic-reset
models.
• Ground Fault Relays and through-type ZCTs (zero-phase current transformers) are mutually compatible.
• The through-type ZCTs are equipped with test terminals, allowing operation tests for Ground Fault Relays to be performed with
ease.
• Series now includes K6EL-R50, which operates at
50 mA r10%.
Model Number Structure
■ Model Number Legend
K6EL-@@
1
2 3
1. Ground Fault Relay
2. Operating Time and Reset Method
None: 0.1 s manual reset
A:
0.3/0.8 s (switchable) manual reset
R:
0.5 s automatic reset
3. Sensed Current
30: 30 mA (fixed)
50: 50 mA/150 mA (switchable)
100: 100 mA/200 mA (switchable)
200: 200 mA/500 mA (switchable)
500: 500 mA/1,000 mA (switchable)
Ordering Information
■ List of Models
Manual-reset Ground Fault Relays
Type
Type
High-sensitivity
models
Sensed current
30 mA (fixed)
Operating time
Medium-sensitivity models
100 mA/200 mA
(switchable)
200 mA/500 mA
(switchable)
500 mA/1,000 mA
(switchable)
High-speed models
Less than 0.1 s
K6EL-30
K6EL-100
K6EL-200
K6EL-500
Delayed models
0.3/0.8 s (switchable)
---
K6EL-A100
K6EL-A200
K6EL-A500
Automatic-reset Ground Fault Relays
Type
Type
Operating time
Delayed models
Less than 0.5 s
Sensed current
High-sensitivity models
Medium-sensitivity models
50 mA/150 mA (switchable)
500 mA/1,000 mA (switchable)
---
K6EL-R500
K6EL-R50 (See note.)
---
Note: Operating Error
50-mA tap: r10%
150-mA tap: r20%
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1
K6EL
ZCTs (Zero-phase Current Transformers)
Type
Rated current
Indoor through-type models
Sensed current
Model
Indoor separate-type models
Diameter of through-hole
Model
Diameter of through-hole
50 A
OTG-L21
21 mm
---
---
100 A
OTG-L30
30 mm
---
22 mm
200 A
OTG-L42
42 mm
OTG-CN52
52 mm
400 A
OTG-L68
68 mm
OTG-CN77
77 mm
600 A
OTG-L82
82 mm
OTG-CN112
112 mm
1,000 A
OTG-L156
156 mm
---
---
■ Ground Fault Relay and ZCT Combinations
(OK: Compatible)
Ground Fault Relay
K6EL-30
K6EL-R50
ZCT
K6EL-100, -200, -500, -R500
K6EL-A100, -A200, -A500
OTG-L21 (50 A)
OK
OK
OTG-L30 (100 A)
OK
OK
OTG-L42 (200 A)
OK
OK
OTG-L68 (400 A)
---
OK
OTG-L82 (600 A)
---
OK
OTG-L156 (1,000 A)
---
OK
OTG-CN52 (200 A)
---
OK
OTG-CN77 (400 A)
---
OK
OTG-CN112 (600 A)
---
OK
Note: 1. “OK” indicates groupings that can be combined freely.
2. Combinations with the OTG-LA@@ are also possible.
■ Options
Flush Mounting Adapters
Front Cover
Model
Model
Y92F-30
Y92A-48B (Hard Cover)
Y92F-71
Y92A-48D(Soft Cover)
Specifications
■ Ground Fault Relay Ratings
Type
High-speed models
Delayed models
Item
Control power supply
100/110 VAC or 200/220 VAC, 50/60 Hz (same for all) (See note 1.)
Rated current
Depends on the ZCT
Sensed current
50% to 100% of the rated sensed current (50 mAr10%, 150 mA r20%) (See note 2.)
Non-operating current
0% to 50% of the rated sensed current
Rated short-time current
2,500 A
Ground fault indication method
LED (red)
Test method
Relay operation confirmed using a test button. (Independent of ZCT connection.)
Reset method
Built-in
contacts
Manual
Either press the reset button or turn the control power supply OFF and ON again.
Automatic
Automatically resets when the ground fault is cleared.
Delayed high-sensitivity
models
100 VAC
Contact form
SPDT+SPST-NO
SPDT
Carrying current
5A
3A
Rated load
240 VAC
cosI = 1
cosI = 0.4 (L/R = 7 ms)
cosI = 1
5A
2A
220 VAC, 3 A
110 VDC
0.3 A
0.2 A
30 VDC
5A
3A
Power (VA) consumption
3 VA max.
Weight
Approx. 110 g
Note: 1. The K6EL-R50 requires a 100-VAC control power supply.
2. Only the K6EL-R50 can be switched between 50 mA r10% and 150 mA r20%.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
2
K6EL
■ Ground Fault Relay Characteristics
Item
Type
High-speed models
Delayed models
Operating time
Less than 0.1 s
0.3 s/0.8 s (switchable)
Inertial non-operating
time
---
0.1 s when set to 0.3 s
0.5 s when set to 0.8 s
Control power supply
range
80% to 110% of the control power supply voltage
Delayed high-sensitivity models
Less than 0.5 s
Operating temperature 10 to 55 qC (with no icing)
range
Operating humidity
range
45% to 85% (with no condensation)
Insulation resistance
5 M: min. at 500 VDC (between charged parts and the mounting panel)
Dielectric strength
1,500 VAC, 50/60 Hz for 1 min (between charged parts and the mounting panel)
Lightning impulse
dielectric strength
1.2/50 Ps, 7,000 V (between control power supply terminals)
Lightning impulse
operation failure
1.2/50 Ps, 7,000 V (primary side of ZCT)
Vibration resistance
Destruction: 16.7 Hz, 4-mm double amplitude for 1 min
Shock resistance
98 m/s2
Note: The range for an operating time of 0.3 s is 0.15 to 0.45 s and the range for an operating time of 0.8 s is 0.6 to 1.2 s.
■ ZCT (Zero-phase Current Transformer)
Item
Structure
Model
Indoor through-type models
OTG-L21
Indoor separate-type models
OTG-L30
OTG-L42
OTG-L68
OTG-L82
OTG-L156
OTG-CN52 OTG-CN77
OTGCN112
Rated current
50 A
100 A
200 A
400 A
600 A
1,000 A
200 A
400 A
600 A
Diameter of
through-hole
21 mm
30 mm
42 mm
68 mm
82 mm
156 mm
52 mm
77 mm
112 mm
Rated voltage
600 VAC max., 50/60 Hz, single-phase/three-phase
Output terminal
polarity
None (The ZCT’s output terminals k and l can be connected to either input terminals 3 or 4 of the Relay.) (See note.)
Insulation
resistance
100 M: min. (between charged metal parts and ground)
Dielectric strength
2,200 VAC, 50/60 Hz for 1 min (between charged metal parts and ground)
Ambient operating
temperature
10 to 60 qC (with no icing)
Weight
Approx.
90 g
Approx.
130 g
Approx.
230 g
Approx.
480 g
Approx.
700 g
Approx.
6.6 kg
Approx.
1.3 kg
Approx.
2.5 kg
Approx.
3.5 kg
Note: Do not connect ZCT output terminals k and l to ground. Doing so may result in damage to the Relay.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
3
K6EL
Internal Block Diagram
X/c
9
Note: 1. The K6EL-R50 does not
have terminals 6 and 7.
2. The K6EL-R500 and K6ELR50 do not have terminal 2.
(They cannot be used at 200/
220 V.)
Delayed models only
8
Operating time
selection switch
11
X/a
Operating time
setting circuit
6
(See note 1.)
Reset button
3
Input
protection
circuit
From OTG ZCT
4
Operating
value setting
circuit
Sensitivity
selection switch
(not provided on
the K6EL-30)
Amplifier
circuit
7
Switching
circuit
X
Ground fault
indicator (red)
Test button
Power
supply
circuit
Shock-wave
absorption
circuit
2
1
Operation at
200/220 V
(See note 2.)
Operation at
100/110 V
10
Power supply indicator (green)
Nomenclature
POWER LEAKED
K6EL-A100
Power supply indicator (green)
Ground fault indicator (red)
EARTH LEAKAGE
RELAY
TEST RESET
Reset button (black)
(not provided on automatic-reset models)
Test button (red)
SENSITIVITY
Sensitivity selection switch
(not provided on the K6EL-30)
100
mA
200
mA
Operating time selection switch
(delayed models only)
0.3S
0.8S
OPERATING TIME
Connections
Ground Fault Relay
(from Pin Side)
Ground Fault Relay with P3GA-11
(from Terminal Side)
Ground Fault Relay with P2CF-11
(from Terminal Side)
(See note 1.)
From ZCT
5
5 6 7
4
8
9
3
2
10
1 11
From ZCT
4
From ZCT
3
2
6
7
8
8
9
1
Control power
supply
10 11
1
5
4
From ZCT
3
From ZCT
2
100 VAC
100 VAC
200 VAC
200 VAC
(See note 2.)
6
9
11 10
100 VAC
200 VAC
7
Control power supply
Note: 1. The K6EL-R50 does not have terminals 6 and 7.
2. The K6EL-R500 and K6EL-R50 do not have terminal 2. (They cannot be used at 200/220 V.)
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
4
K6EL
Connection Examples
Installation on the Electrical Path
Molded case
circuit-breaker
Installation on a Ground Bus Bar
Molded case
circuit-breaker
ZCT
Transformer
Load
Load
Transformer
kt
OTG ZCT
Y/b
lt
k
Y/b
OTG ZCT
Auxiliary relay
kt
l
Y
k
l
Auxiliary relay
lt
Y
ZCT
5 6 7
4
8
3
9
2
10
1 11
Alarm buzzer
BZ
Alarm buzzer
BZ
100/110 VAC
K6EL Ground
Fault Relay
Ground bus bar
K6EL
Ground
Fault Relay
5 6 7
4
8
3
9
2
10
1 11
200/220 VAC
Do not, under any circumstances, connect the k and l
lines to ground.
Note: When not using the kt and lt terminals (test terminals), leave
them unconnected. The Relay may not be able to attain its
performance characteristics if used with the kt and lt terminals
connected.
100/110 VAC
200/220 VAC
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Ground Fault Relay
1
78
6
63.7
0.7
13.6
44.8 × 44.8
48
Applicable Connecting Sockets
P2CF-11 Front Connecting Socket
P3GA-11 Back Connecting Socket
PL11 Back Connecting Socket
48
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
5
K6EL
Dimensions with Adapter Mounted
Y92F-30 Flush Mounting Adapter
(Sold Separately)
Panel
15
Mounting Hole
Cutout Dimensions
P3GA-11
Back Connecting Socket
R0.5 max.
58
45 +0.5
0
45 +0.5
0
Note: Recommended panel
thickness: 1 to 3.2 mm.
48
7
91.4
Panel
Y92F-71 Flush Mounting Adapter
(Sold Separately)
56
Mounting Hole
Cutout Dimensions
P3GA-11
Back Connecting Socket
R0.5 max.
45±0.2
58
68
45 +0.5
0
55 +0.5
0
91.4
45±0.2
Note: Recommended panel
thickness: 1 to 3.2 mm.
50±0.2
Dimensions for Socket Mounting
Y92F-30
P3GA-11
K6EL
+
Adapter
K6EL
103
77
Y92H-1 Hook
K6EL
91.4
7
P2CF-11 (sold separately)
16
PL11
(sold separately)
(sold separately)
Note: The same dimensions apply
when using the Y92F-71 Adapter.
Connecting Sockets
P2CF-11 Front Connecting Socket
3
Eleven, M3.5×7.5
sems screws
4.5
7.8
Terminal Arrangement
(Top View)
Mounting Holes
Two, 4.5-dia. holes
8 7 6 5
4
70 max.
40±0.2
35.4
Two, 4.5-dia.
holes
9
3
10 11 1 2
4
50 max.
31.2 max.
P3GA-11 Back Connecting Socket
27 dia.
Terminal Arrangement
(Top View)
45
25.6
5 6 7 8
4
3
9
2 1 11 10
45
http://www.ia.omron.com/
4.5 16.3 6.2
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
6
K6EL
PL11 Back Connecting Socket
4
3.5
1
Terminal Arrangement
(Bottom View)
Two, 3.5-dia. holes or
two, M3 socket mounting holes
5 6 7
30 dia.
51 max. 40
4
3
2
3.9
1 11
Two, 2-dia. holes
35 max.
Mounting Holes
8
9
10
31 dia.
holes
40±0.3
Approx. 20.5
Front Cover
Model
Y92A-48B (Hard Cover)
Y92A-48D (Soft Cover)
ZCT
9.3
Indoor Through-type Models
OTG-L21 (50 A)
11
50
20
13
6
Mounting Hole
Cutout Dimensions
Terminal symbols
(protrude 0.3 mm)
Nameplate
kt
k
l
lt
Label and caution
66
21 dia.
6
Two, 5.5-dia. holes or
two, M5 screw holes
64
74
5.2
20
64
OTG-L30 (100 A)
9.3
11
20
13
63
Mounting Hole
Cutout Dimensions
Terminal symbols
(protrude 0.3 mm)
6
kt
k
l
lt
Nameplate
Two, 5.5-dia. holes or
two, M5 screw holes
79
30 dia.
76
6
86
5.2 20
76
OTG-L42 (200 A)
11
9.3
5.2
Mounting Hole
Cutout Dimensions
17
88
42 dia.
Two, 5-dia. holes or
two, M4 screw holes
109
97
97
(mounting pitch)
107
OTG-L68 (400 A)
25
11
9.3
6.1
17
118
Mounting Hole
Cutout Dimensions
68 dia.
Two, 5-dia. holes or
two, M4 screw holes
136
131
13
(mounting pitch)
143
http://www.ia.omron.com/
31
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
7
K6EL
11
OTG-L82 (600 A)
9.3
6.2
138
17
Mounting Hole
Cutout Dimensions
82 dia.
Two, 5-dia. holes or
two, M4 screw holes
158
160
28
160 (mounting pitch)
172
OTG-L156 (1,000 A)
33
156 dia.
L
M5 terminal screws
Mounting Hole
Cutout Dimensions
263
Four, 8.5-dia. holes or
four, M8 screw holes
138
90
230
270
3.2
60
230
9
90 130
20
40
Indoor Separate-type Models
OTG-CN52 (200 A)
52 dia.
K
M4 terminal screws
Mounting Hole
Cutout Dimensions
Two, 6.5-dia. holes or
two, M6 screw holes
141
K
79
170
170
30
7
http://www.ia.omron.com/
200
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
8
K6EL
OTG-CN77 (400 A)
77 dia.
M4 terminal screws
K
Mounting Hole
Cutout Dimensions
157
Four, 6.5-dia. holes or
four, M6 screw holes
84
K
53
195
195
70 53
7
230
112 dia.
OTG-CN112 (600 A)
K
M4 terminal screws
Mounting Hole
Cutout Dimensions
Four, 6.5-dia. holes or
four, M6 screw holes
200
107
K
53
225
225
70 53
7
260
■ Maximum Wire Sizes for ZCTs
Wire/cable
Model
Rated
current
600-V vinyl-insulated wire (IV)
Through-hole
diameter
2-wire
OTG-L21
50 A
21 dia.
22 mm2
14 mm2
OTG-L30
100 A
30 dia.
2
2
OTG-L42
200 A
OTG-L68
OTG-L82
60 mm
Cable (VVR)
3-wire
38 mm
2-wire
8 mm2
38 mm
5.5 mm2
2
38 mm2
42 dia.
100 mm
2
100 mm
2
100 mm
400 A
68 dia.
400 mm2
325 mm2
325 mm2
600 A
82 dia.
500 mm2
500 mm2
400 mm2
OTG-L156
1,000 A
156 dia.
500 mm
2
500 mm
2
OTG-CN52
200 A
52 dia.
200 mm
2
200 mm
2
OTG-CN77
400 A
77 dia.
500 mm
2
400 mm
2
OTG-CN112
600 A
112 dia.
500 mm2
500 mm2
http://www.ia.omron.com/
3-wire
2
1,000 mm
60 mm2
250 mm2
400 mm2
2
1,000 mm2
150 mm
2
100 mm2
400 mm
2
325 mm2
1,000 mm2
1,000 mm2
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
9
K6EL
Test Circuit
Switch
200 mA: 500 :, 50 W
500 mA: 200 :, 100 W
1,000 mA: 100 :, 200 W
100 VAC
Slidac
mA
Ammeter
K6EL
kt
k
l
lt
OTC
R
Select the resistance R shown in the test circuit diagram according to
the K6EL’s rated sensed current. Change the current using the slidac
and ascertain the K6EL’s operating value each time by reading the
ammeter.
For example, R could take the values shown below:
30 mA: 3.3 k:, 6 W
100 mA: 1 k:, 20 W
Safety Precautions
■ Correct Use
Switching the Operating Time
Installation and Wiring
• Do not, under any circumstances, connect the ZCT’s output terminals k and l to ground. Doing so may result in damage to the
Relay’s internal circuits.
• Pass the primary conductor through the ZCT once.
• The Relay detects ground faults in internal wiring of devices due to
insulation deterioration and so install the ZCT as close to the power
supply side as possible.
1. With the K6EL-A100, A200, and A500, the operating time can be
switched using a flat-bladed screwdriver.
2. The operating time for the K6EL-30, 100, 200, 500, R50, and
R500 is fixed and hence cannot be switched.
ZCT Installation
• Install the ZCT at an outdoor cable inlet or on a ground bus bar at a
location allowing easy inspection.
• When installing on the electrical path, use a ZCT with a value
greater than the electrical path’s rated current.
• If the secondary lines run in parallel to a circuit carrying a large current, either separate the lines as far as possible or use a shield line.
Run the secondary lines
close to each other.
Sensed current selection switch
Operating time selection switch
Testing
ZCT
K6EL
Primary conductor
Separate by 20 cm min.
Circuit carrying large current
• When installing a separate-type ZCT with current flowing along the
primary conductors, short the secondary terminals using clips or
some other method.
Switching the Sensed Current
• If the ground fault indicator (red) lights when the Relay’s test button
is pressed, it means that the internal circuits are operating normally.
• To make an overall test, run a simulated ground fault current.
Resetting
• Once manual-reset models operate, they continue to operate until
they are reset. Reset them either by pressing the reset button
(black) or by turning the control power supply OFF and ON again.
• Automatic-reset models reset automatically when the ground fault
is cleared (i.e., the current drops below the sensed current).
1. With the K6EL-@100, 200, 500, R50, and R500, the sensed current can be switched using a flat-bladed screwdriver.
2. The sensed current for the K6EL-30 is fixed and hence cannot be
switched.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
10
K6EL
Q&A
Q: How does the K6EL operate when used for inverter loads (e.g., inverter motors and inverter air conditioners)?
A: The influence of high-frequency noise generated by the inverter has been reduced by combining a special ground
fault relay IC and a capacitor for cutting out high-frequencies. The possibility of malfunctions due to the influence
of the inverter is much less than with the existing ESA Ground Fault Relay.
R
S
M
Inverter
T
Rg
K6EL
Q: What connection method should be used for ungrounded electrical paths?
A: With ungrounded electrical paths, connect the capacitor or resistor for detection in the way shown in the diagram.
The table shows the formulas for calculating the resistance or capacitance as well as the formulas for calculating
ground currents for complete ground faults. (Depending on the location, the allowable ground fault current may be
restricted. In this case, use values of R and C that do not exceed the restrictions.)
Connection method
OTG ZCT
Y/b
kt
Resistor (R) or
capacitor (C)
l
k lt
Rg
K6EL
Y
Ig
It: Ground Fault
Relay’s set
value
V: Line voltage
2
f: Frequency
P= 5V (W)
R
P: Allowable
power for the
resistor used
Capacitor:
(A tolerance is
C= 2It (F)
included in the
2πfV
formulas on the
Dielectric strength left.)
> 2 V (V)
Formula for ground
current
Formula for
safety ground
fault
Resistor:
Isolating
transformer
Load
Singlephase
electrical
path
Formula for resistor or capacitor
R= V (Ω)
2It
Ig=
Ig=
V
(A)
2Rg + R
V
1
(2Rg) + ( 2πfC )2
Ig= V (A)
R
(A)
Ig = 2πfCV (A)
2
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
11
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.
This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.
2007. 3
OMRON Corporation
In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.

advertisement

Key Features

  • High-speed operation
  • Compact design
  • Inverter compatibility
  • Switchable sensed current
  • Automatic reset

Frequently Answers and Questions

What are the different operating times available for the K6EL-500?
The K6EL-500 offers a fixed operating time of less than 0.1 seconds. This ensures quick and efficient detection of ground faults.
Can the K6EL-500 be used with inverter loads?
Yes, the K6EL-500 is designed to work reliably with inverter loads, such as inverter motors and inverter air conditioners. It features improved resistance to high-frequency noise.
How do you reset a manually-reset K6EL-500 after a ground fault?
To reset a manually-reset K6EL-500, press the reset button (black) or turn the control power supply off and on again.