Veris Industries AG01E Installation Manual

Veris Industries AG01E Installation Manual

VERIS INDUSTRIES AG01E is a carbon monoxide (CO) sensing element designed for use with Veris GWN Series gas platform units. It provides reliable monitoring of CO levels, essential for safety in areas where potential sources of CO, such as gasoline engines or generators, are present. The sensor is factory calibrated and requires no field calibration, ensuring accuracy and ease of use.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

AG01E Installation Manual - Veris Industries | Manualzz
Installation Guide
Accessories
TM
AG01E
Carbon Monoxide Sensing Element
Product Overview
The AG01E carbon monoxide (CO) sensing element is designed to work with the Veris GWN Series gas platform unit
to provide monitoring of CO levels. Common sources of CO include automobile exhaust from gasoline engines,
gasoline powered furnaces, gasoline powered water heaters, and gasoline generators. The sensor is calibrated at
the factory, so no field calibration is needed. The AG01E is warranted to meet accuracy specifications for one year
after the date of manufacture.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Specifications
Sensor Type
Measurement Range
Accuracy
Analog Output Scaling
Resolution
Sensor Warranty
Electrochemical
0-500 ppm
±5% of range
0-200 ppm
1 ppm
1 year from manufacture date
Low Level Setpoint
25 or 35 ppm (switch selectable)
High Level Setpoint
180 ppm (fixed)
Operating Temperature Range
-20° to 50°C (-4° to 122°F)
Operating Humidity Range
0-90% RH non-condensing
The AGxx sensors work only with Veris GWN Series gas platform devices.
Z207061-0A
Page 1 of 2
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0415
AG01E Installation Guide
Installation
TM
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect and lock out all power sources before beginning the installation of the sensor.
2. Install the GWN Series gas platform according to the instructions included with that device.
3. Remove the front cover from the GWN Series gas platform device.
4. Use the grooves on the sides of the AG01E to correctly position the sensor with respect to the GWN unit.
5. Press the connector block on the sensor onto the connector pins on the GWN unit.
Use these grooves to position the sensor
properly before pressing the sensor into the
pin connector on the GWN board.
6. The low relay setpoint value of the AG01E sensor is selectable (either 25 or 35 ppm). Use the setpoint selection switch on the
GWN board to choose LO (for 25 ppm) or HI (for 35 ppm).
The AG01E high setpoint value is fixed.
7. Replace the GWN front cover. Reconnect power.
Z207061-0A
Page 2 of 2
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0415

advertisement

Key Features

  • CO sensing element
  • 0-500 ppm measurement range
  • Factory calibrated
  • Low level setpoint selection (25 or 35 ppm)
  • High level setpoint (180 ppm)
  • Electrochemical sensor type
  • GWN Series compatibility

Frequently Answers and Questions

What is the AG01E sensor's accuracy?
The AG01E sensor has an accuracy of ±5% of range.
What is the sensor's high setpoint value?
The high setpoint value is fixed at 180 ppm.
What is the operating temperature range of the AG01E sensor?
The operating temperature range is -20° to 50°C (-4° to 122°F).