Carrier 50TC-D rooftop air conditioner Installation Instructions
The 50TC-D is a single package rooftop cooling only unit with Puron (R-410A) refrigerant. It's designed for 50Hz applications and comes in sizes 17, 20, 24, 28, and 30. This document provides step-by-step instructions for installing the unit, including planning, support, ductwork, electrical connections, and accessories.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
50TC---D
Single Package Rooftop, 50Hz
Cooling Only
with Puronr (R---410A) Refrigerant
Sizes: 17, 20, 24, 28, 30
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . .
2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 -- Plan for Unit Location . . . . . . . . . . . . . . . . . .
Roof Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2 -- Plan for Sequence of Unit Installation . . . . .
9
13
9
9
Curb--Mount Installation
Pad--Mount Installation
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
Frame--Mount Installation . . . . . . . . . . . . . . . . . . .
Step 3 -- Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 4 -- Provide Unit Support
Roof Curb Mount
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
Slab Mount (Horizontal Units Only)
Alternate Unit Support
(In Lieu of Curb or Slab Mount)
. . . . . . . . . .
. . . . . . . . . . . . .
13
Step 5 -- Field Fabricate Ductwork . . . . . . . . . . . . . . .
For Units with Accessory Electric Heaters
Step 6 -- Rig and Place Unit
Positioning on Curb
Step 7 -- Horizontal Duct Connection
. . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
14
14
14
14
15
Step 8 -- Install Outside Air Hood — Factory Option . .
16
Step 9 -- Check Pulley Alignment and Belt Tension
Pulley Alignment
. . .
. . . . . . . . . . . . . . . . . . . . . . . . .
17
17
13
13
13
13
13
13
13
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
Step 10 -- Install External Condensate Trap and Line . .
18
Step 11 -- Make Electrical Connections . . . . . . . . . . .
Units without Factory--Installed Disconnect . . . .
Units with Factory--Installed Disconnect
All Units
. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory--Option Thru--Base Connections . . . . . .
18
19
19
19
20
Units without Thru--Base Connections . . . . . . . . .
Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . .
20
20
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit without Thru--Base Connection Kit
Heat Anticipator Settings
. . . . . . .
. . . . . . . . . . . . . . . . . . .
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low--Voltage Control Connections . . . . . . . . . . . .
PremierLinkt (Factory Option) . . . . . . . . . . . . . . .
Supply Air Temperature (SAT) Sensor . . . . . . . . .
Outdoor Air Temperature (OAT) Sensor
EconoMi$er2
. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Connections
Space Sensors
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect Thermostat . . . . . . . . . . . . . . . . . . . . . . .
Configure the Unit for Thermostat Mode . . . . . .
Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Air Quality (CO
2
) Sensor
Outdoor Air Quality Sensor
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
Smoke Detector/Fire Shutdown (FSD) . . . . . . . . .
Filter Status Switch . . . . . . . . . . . . . . . . . . . . . . . .
Supply Fan Status Switch
Remote Occupied Switch
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
Power Exhaust (output) . . . . . . . . . . . . . . . . . . . . .
Space Relative Humidity Sensor
CCN Communication Bus
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
RTU Open Control System . . . . . . . . . . . . . . . . . . .
Supply Air Temperature (SAT) Sensor . . . . . . . . .
Outdoor Air Temperature (OAT) Sensor . . . . . . .
EconoMi$er2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . .
Space Temperature (SPT) Sensors . . . . . . . . . . . .
Indoor Air Quality (CO
2
) Sensor
Outdoor Air Quality Sensor
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
Connecting Discrete Inputs . . . . . . . . . . . . . . . . . .
29
30
32
32
28
28
28
29
27
28
28
26
26
27
27
32
33
33
33
34
34
24
24
26
21
22
24
24
20
20
21
21
Communication Wiring -- Protocols
General
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RTU Open Troubleshooting . . . . . . . . . . . . . . . . .
Outdoor Air Enthalpy Control
Differential Enthalpy Control
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . .
Return Air Sensor Tube Installation . . . . . . . . . . .
Test/Rest Magnet . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Application Data . . . . . . . . . . . . . . . . .
Step 12 -- Adjust Factory--Installed Options . . . . . . . .
Step 13 -- Install Accessories . . . . . . . . . . . . . . . . . . .
39
39
42
42
37
37
38
38
35
35
36
36
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . .
43
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes for special requirements. In absence of local codes, it is recommended that the USA standard ANSI/NFPA 70, National Electrical
Code (NEC), be followed.
It is important to recognize safety information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning units.
2
Fig. 1 -- Unit Dimensional Drawing – 17 and 20 Size Units
3
C101023
Fig. 1 -- Unit Dimensional Drawing – 17 and 20 Size Units (cont.)
C11328
4
Fig. 2 -- Unit Dimensional Drawing – 24 and 28 Size Units
5
C101025
Fig. 2 -- Unit Dimensional Drawing – 24 and 28 Size Units (cont.)
C11329
6
Fig. 3 -- Unit Dimensional Drawing – 30 Size Units
7
C11225
Fig. 3 -- Unit Dimensional Drawing – 30 Size Units (cont.)
C11235
8
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes or the U.S.A. National
Electrical Code (Ref: ANSI/NFPA 70, [American National Standards Institute/National Fire Protection Association], latest revision) for special installation requirements
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 4.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on
Class A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 10 — Install External
Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
2438 mm
(96 in)
914 mm
(36 in)
1067 mm
(42 in)
1067 mm
(42 in)
914 mm
(36 in)
50TC---D
Base Unit
Economizer
Curb
356 mm/14---in
610 mm/24---in
17
820 (1808)
111 (245)
95 (210)
132 (290)
Fig. 4 -- Service Clearance Dimensional Drawing
Table 1 – Operating Weights
20
827 (1823)
111 (245)
UNIT KG (LB)
24
895 (1973)
111 (245)
95 (210)
132 (290)
112 (246)
140 (308)
28
952 (2098)
111 (245)
112 (246)
140 (308)
30
998 (2196)
111 (245)
123 (270)
155 (342)
C101074
9
Fig. 5 -- Roof Curb Details – 17 and 20 Size Units
10
C09139A
Fig. 6 -- Roof Curb Details – 24 and 28 Size Units
11
C09140A
Fig. 7 -- Roof Curb Details – 30 Size Unit
12
C11251
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb.
Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb
Install field--fabricated ductwork inside curb
Install thru--base service connection fittings (affects curb and unit)
Rig and place unit
Remove top skid
Install outside air hood
Install smoke detector tube
Install condensate line trap and piping
Make electrical connections
Install other accessories
Pad--mounted installation —
Prepare pad and unit supports
Rig and place unit
Remove duct covers and top skid
Install Return Air smoke detector sensor tube
Install field--fabricated ductwork at unit duct openings
Install outside air hood
Install condensate line trap and piping
Make electrical connections
Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Locate the carton containing the outside air hood parts; see Fig. 9 and 13. Do not remove carton until unit has been rigged and located in final position.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in
Figs. 5, 6 and 7. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Figs. 5, 6 and 7. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in
Fig. 8. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
C
A
MAXIMUM ALLOWABLE
DIFFERENCE MM (IN.)
B
A-B
6 (0.25”)
B-C
12 (0.5”)
Fig. 8 -- Unit Leveling Tolerances
A-C
12(0.5” )
C09386
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. Thru--the--base power connection must be installed before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan, remove knockouts in basepan located in control box area of access panel; see Figs. 1, 2 or 3 for basepan knockout locations. Attach the service connections to the basepans.
Hood Carton Location
(rear access panel)
Control Box
Access Panel
Filter and
Indoor Coil
Access Panel
Indoor Blower
Access Panel
Electric Heat
Access Panel Compressor
(each side)
C11155
Fig. 9 -- Typical Access Panel and Compressor Locations
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of
152 mm (6–in.) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support
(In Lieu of Curb or Slab Mount) —
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 102 mm x 102 mm (4--in. x 4--in.) pads on each side. Locate pads so that they support the rails. Make sure to avoid the fork openings.
13
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed 87 Pa (0.5 in. wg) with economizer or without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 458 mm (18 in.) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
For Units with Accessory Electric Heaters —
Minimum clearance is not required around ductwork.
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could cause personal injury.
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90--degree turn in the return ductwork between the unit and the conditioned space. If a 90--degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90--degree elbow.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 (on page 7) and Fig. 10 for additional information.
Lifting holes are provided in base rails as shown in
Fig. 10. Refer to rigging instructions on unit.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck when packaging is removed.
Before setting the unit onto the curb, recheck gasketing on curb.
Positioning on Curb —
Position unit on roof curb so that the following clearances are maintained: 6 mm ( 1 /
4 in.) clearance between the roof
( curb and the base rail inside the right and left, 12 mm
1 /
2 in.) clearance between the roof curb and the base rail inside the front and back. This will result in the distance between the roof curb and the base rail being approximately equal to Detail A and Detail B in Figs. 5, 6 and 7.
Do not attempt to slide unit on curb after unit is set. Doing so will result in damage to the roof curb seal.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove rigging skids and shipping materials.
14
"B"
1371 mm
(54")
MINIMUM
SEE DETAIL A
"C"
PLACE ALL SEAL STRIP
IN PLACE BEFORE PLACING
UNIT ON ROOF CURB.
DUCT END
DETAIL A
"A"
UNIT
50TC---D17
50TC---D20
50TC---D24
50TC---D28
50TC---D30
MAX WEIGHT
KG
1011
1017
1033
1145
1295
LB
2228
2243
2277
2525
2849
MM
3249
3249
3595
3595
4007
A
IN
127.8
127.8
141.5
141.5
157.8
DIMENSIONS
B
MM IN
1491
1491
1816
1816
2040
58.7
58.7
71.5
71.5
80.3
MM
1328
1328
1328
1532
1532
C
NOTES:
1. Dimensions in ( ) are in inches.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
IN
52.3
52.3
52.3
60.3
60.3
Fig. 10 -- Rigging Details
C11378
Step 7 — Horizontal Duct Connection
Refer to Figs. 1, 2 and 3 for locations and sizes of the horizontal duct connections. Note that there are two different return air duct connection locations – one for unit without an economizer (on back side of unit) and a different one for unit equipped with an economizer (on left end, under the economizer hood). The supply air duct connection is on the back side. See Fig. 11 for top view depicting typical horizontal duct arrangements.
Field--supplied 19 mm (3 /
4
--in) flanges should be attached to horizontal duct openings (see Fig. 11) and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Horizontal
Supply Air
Supply
Location Back
Height --- mm (In.) 402 (15 7 /
8
)
Width --- mm (in.) 756 (29 3 /
4
)
Return Air Duct without
Economizer
Return without
Economizer
Back
1253 (49 3 /
8
)
593 (23 3 /
8
)
Return Air Duct with Economizer
C10740
Return with
Economizer
Left end
467 (18 3 /
8
)
1564 (61 5 /
8
)
Fig. 11 -- Horizontal Duct Opening Dimensions
15
Step 8 — Install Outside Air Hood — Factory
Option
The outside air hood for factory--option economizer and two--position damper is shipped in knock--down form and requires field assembly. The panel for the hood top is shipped on the end of the unit (see Fig. 12). The remaining parts for the hood assembly (including side panels, filters and tracks) are shipped in a carton that is secured to the rear of the blower assembly. Access the carton location through rear panel (see Fig. 13).
Hood Top
Shipping
Position
Hood
Package
Fig. 12 -- Hood Top – Shipping Position
C09134
Fig. 13 -- Hood Package – Shipping Location
C09133
To remove the hood parts package:
1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage any wiring.
3. Carefully lift the hood package carton through the back blower access opening.
See Fig. 14 for identification of the various parts of the hood assembly.
Apply Seal Strip to the front of this flange
7
Apply Seal Strips to the back of these surfaces
3
7
Apply Seal Strip to the front of this flange
Apply Seal Strips to the back of these flanges
2
4
4
4
4
Apply Seal Strip to the back of this flange 1
5 6
Seal Strips
Item # Description
1 Angles
2 Side Plates
3 Hood
4
5 Side Filter Supports
1
2
6
7
Qty
4
2
2
2
C09079
Fig. 14 -- Hood Part Identification and Seal Strip
Application Areas
To assemble the outside air hood:
1. Remove hood top panel from shipping position on unit end.
2. Install four angles to the upper end panel using the screws provided
3. Apply seal strip to mating flanges on the side plates of the hood (see Fig. 14).
4. Secure side plates to panel using the screws provided.
5. Apply seal strip to mating flange of the hood (see
Fig. 14).
6. Secure top flange using screws provided in kit.
7. Install outdoor air screens by sliding them into the channel formed by the four angles installed in step 2.
Make sure that the screens extend across the entire length of the hood.
8. Install side filter supports using the screws provided
9. Install side drip angles using the screws provided.
10. Run a continuous length of seal strip across the hood covering the engagement holes in the lower hood.
11. Install top diverter using the screws provided.
12. On units with barometric relief, remove screws at bottom of relief damper. Do not discard damper door.
2
5
6
Fig. 15 -- Hood Assembly – Completed
C09090
16
Step 9 — Check Pulley Alignment and Belt Tension
Pulley Alignment —
The motor pulley is an adjustable--pitch type that allows implementation of changes in fan wheel speed to match as--installed ductwork systems. The pulley consists of a fixed flange side that faces the motor (secured to the motor shaft) and a movable flange side that can be rotated around the fixed flange side that increases or reduces the pitch diameter of this driver pulley. (See Fig. 16.)
Belt Tension —
Check belt tension by using a spring--force tool (such as
Browning’s Part Number “Belt Tension Checker” or equivalent tool); tension should be between 2.3--4.5 kg
(5--10 lbs) with 13.3 mm ( 5 /
8 in.) deflection when measured at the centerline of the belt span. This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft.
NOTE: Without the spring--tension tool, place a straight edge across the belt surface at the pulleys, then deflect the belt at mid--span using one finger to a 12.7 mm ( deflection.
1 /
2 in.)
Adjust the belt tension by loosening the four motor rail mounting nuts and bolts where the motor rails bolts to the blower rails. There are two jack bolts and nuts that are used to slide the motor rails to either increase or decrease belt tension. There are locking nuts on the jack bolts that need to be loosened at the motor rail. Turn the jack bolts clockwise or counter clockwise until the correct belt tension is achieved. Ensure the fan shaft and motor shaft are parallel prior to tightening motor plate nuts. (see Fig. 17.)
C07075
Fig. 16 -- Checking Pulley Alignment
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting
3. Tighten fan pulley setscrews and motor mounting bolts to torque specifications.
4. Recheck belt tension.
Step 1: Loosen motor rail bolts
Step 2: Loosen jack bolt lock nuts
Step 3: Loosen or tighten jack bolts until proper belt tension is achieved
Fig. 17 -- Adjusting Belt Tension
C11447
17
Step 10 — Install External Condensate Trap and
Line
The unit has one 19 mm (3 /
4
-in.) condensate drain connection on the end of the condensate pan (see Fig. 18).
See Figs. 1, 2 and 3, item “E”, in the view labeled “BACK
(HORIZONTAL DISCHARGE W/O ECON)” for the location of the condensate drain connection.
CONDENSATE
DRAIN
CONNECTION
Fig. 18 -- Condensate Drain Pan Connection
C10729
The piping for the condensate drain and external trap can be completed after the unit is in place. Hand tighten fittings to the drain pan fitting. Provide adequate support for the drain line. Failure to do so can result in damage to the drain pan. See Fig. 19.
Step 11 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with local electrical codes or in absence of local codes, it is recommended that the U.S.A.
standard ANSI/NFPA 70, National Electrical Code
(NEC), be followed.
NOTE: Field--supplied wiring shall conform with the limitations of minimum 33_C (63_F) rise.
Field power wires are connected to the unit at line--side pressure lugs on the terminal block (see Fig. 20 or the wiring diagram label for control box component arrangement) or at factory--installed option non--fused disconnect switch. Use copper conductors only.
BLK
YEL
BLU
LOAD
SIDE
MINIMUM PITCH
25 mm (1 in.) PER
3m (10 ft.) OF LINE
BASE RAIL
OPEN
VENT
76 mm
(3 in.)
MIN
TO ROOF
DRAIN
SEE NOTE
ROOF
CURB
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static difference. A 102 mm (4 in.) trap is recommended
C11354
Fig. 19 -- Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 102 mm (4-in.) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from
( the unit at 25 mm in 3 m (1-in. per 10 ft) of run. Do not use a pipe size smaller than the unit connection of 19 mm
3 /
4
-in.).
LINE
SIDE
SEE
DETAIL A
L1
L2
L3
DETAIL
A
CONTROL BOX
Fig. 20 -- Location of TB1
C11181
NOTE: Make field power connections directly to line connection pressure lugs only.
The unit is factory wired for the voltage shown on the nameplate. Refer to unit label diagram for additional information.
18
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and air conditioning unit. Use only copper wire. (See Fig. 21.)
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
Units Without Disconnect Option
11
TB
12 13
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 21 -- Disconnect Switch and Unit
Units Without Factory--Installed Disconnect —
When installing units, provide a disconnect switch of adequate size per local or national wiring code.
Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes.. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
Units with Factory--Installed Disconnect —
The factory--installed option disconnect switch is located in the main control box. The manual switch handle is accessible on the corner post adjacent to the control box access panel.
All Units --
All field wiring must comply with local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 22 for power wiring connections to the unit power terminal block and equipment ground.
Maximum wire size is 70.0 mm 2 (2/0 AWG) per pole.
Provide a ground--fault and short--circuit over--current protection device (fuse or breaker) per local code (or U.S.A.
NEC Article 440). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. On
3--phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance = 100 x max voltage deviation from average voltage average voltage
C09103
Disconnect per
NEC
L1 L2
400-3-50
L3
Units With Disconnect Option
Factory
Wiring
T1 T2 T3
L1
Optional
Disconnect
Switch
L2 L3
L1 L2 L3
Fig. 22 -- Power Wiring Connections
C11381
19
Table 2 – American/European Wire Conversions
Industry
Standard Size
AMERICAN
American Conversion
Size (mm 2 )
20 AWG
18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
3 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
21.14
26.65
33.61
42.39
53.49
67.42
85.00
107.9
0.52
0.82
1.30
2.08
3.30
5.25
6.36
13.29
EUROPEAN
Industry Standard
Size (mm 2 )
25.0
—
35.0
50.0
—
70.0
95.0
120.0
4.0
6.0
10.0
16.0
0.5
1.0
1.5
2.5
Factory--Option Thru--Base Connections —
All units are equipped with the ability to bring utilities through the base.
The electrical entrance is located in the control box area can can be accessed through the control box access panel. An embossed area is provided with three knock outs. High voltage is brought through the multi knock out by removing the appropriate size for the size of the fitting required. A 22 mm ( 7 /
8
--in.) knock out is provided for low voltage. An additional 22 mm ( 7 /
8
--in.) knock out is provided for a 115 volt line which is used when the unit is equipped with the non--unit powered convenience outlet option.
All required fittings are field supplied. Install fittings when access to both top and bottom of the base pan is available.
Units without Thru--Base Connections —
1. Install liquid tight conduit between disconnect and control box.
2. Pull correctly rated high voltage wires through the conduit.
3. Install power lines to terminal connections as shown in Fig. 22.
Field Control Wiring —
The 50TC--D unit requires an external temperature control device. This device can be a thermostat (field--supplied) or a
PremierLink controller (available as factory--installed option or as field--installed accessory, for use on a Carrier Comfort
Network or as a stand alone control) or the RTU Open for
Building Management Systems using non--CCN protocols
(RTU Open is available as a factory--installed option only).
Thermostat —
Select a Carrier--approved accessory thermostat. When electric heat is installed in the 50TC unit, the thermostat must be capable of energizing the G terminal (to energize the Indoor Fan Contactor) whenever there is a space call for heat (energizing the W1 terminal). The accessory thermostats listed on the unit price pages can provide this signal but they are not configured to enable this signal as shipped.
Install the accessory thermostat according to installation instructions included with the accessory.
Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.
If the thermostat contains a logic circuit requiring 24--v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24--v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.
For wire runs up to 15 m (50 ft.), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum).
For 15 to 23 m5 (0 to 75 ft.), use no. 16 AWG insulated wire (35_C minimum). For over 23 m (75 ft.), use no. 14
AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Typical
Thermostat
Corrections
Central
Terminal
Board
C
G
W2
X
C
See
Caution
G
W2
X
C
G
W2
20
W1
O/B/Y2
(see Note)
Y1
W1
Y2
W1
Y2
R
Y1
R
T–STAT
Y1
R
Note: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2.
Field Wiring
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may cause a short circuit.
Carefully check the connection of control coductor for indoor fan control at terminal G. Connecting the indoor fan lead to terminal C will cause a short circuit condition which can cause component damage inside the unit or at thermostat.
C10731
Fig. 23 -- Typical Low--Voltage Control Connections
Unit without Thru--Base Connection Kit —
Correctly rated low voltage wire can be routed through the rubber grommet located on the corner post adjacent to the control box access panel. Route wire through the grommet and then route the wire behind the corner post utilizing the factory provided wire ties secured to the control box. This will insure separation of the field low voltage wire and the high voltage circuit. Route the low voltage wire to the central terminal board. See Fig. 24.
NOTE: If utilizing the through the base connections, route the low voltage wire through the wire ties to the central terminal board.
Configure for Electric Heat: To configure the factory--approved thermostat, open the Advanced Setup menu, scroll down to ELECTRIC HEAT and change
RANGE value from OFF to ON. Consult the thermostat installation instructions for full details.
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second--stage heating.
Rubber
Grommet
Corner
Post
Indoor Blower
Access Panel
Main Control
Box
Filter
Area
Heater
Module
Fig. 26 -- Typical Component Location
C10632
Electric Heater
Tracks
Wire
Ties
Thru the Base
Connection
Fig. 24 -- Field Control Wiring Raceway
C10734
Electric Heaters
50TC--D units may be equipped with field--installed accessory electric heaters. The heaters are modular in design.
Heater modules are installed in the compartment below the indoor blower access panel. Access is through the electric heat access panel. Heater modules slide into the compartment on tracks along the bottom of the heater opening. See
Fig. 25 Fig. 26 and Fig. 27. Refer to the Electric Heater Kit
Installation Instructions for complete details.
Control Box
Access Panel
Filter and
Indoor Coil
Access Panel
Indoor Blower
Access Panel
Electric Heat
Access Panel
C10631
Fig. 25 -- Typical Access Panel Location
Not all available heater modules may be used in every unit. Use only those heater modules that are approved for use in a specific size unit. Refer to the label on the unit cabinet for the list of approved heaters.
Electric Heater
Opening
Fig. 27 -- Electric Heater Compartment\
(Cover Removed)
C09142
Low--Voltage Control Connections —
Locate the plug assembly in the electric heater section of the main unit. Connect the plug with the mating low voltage plug located on the heater.
CTB
CONTL
BOARD
2 VIO
3 ORN
12
Field
Connections
BRN
ORN
Plug
Assembly
1
VIO
VIO
2
BRN
3
VIO BRN BRN
Elec Htr
VIO HR2 BRN
VIO HR1 BRN
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
C09149
Fig. 28 -- Accessory Electric Heater Control Connections
21
PremierLinkt (Factory--Option)
C08199
Fig. 29 -- PremierLink Controller
The PremierLink controller (see Fig. 29) is compatible with Carrier Comfort Networkr (CCN) devices. This control is designed to allow users the access and ability to change factory--defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilott, Touch Pilott and
Service Tool. (Standard tier display tools Navigatort and
Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the
50TC--D unit’s main control box to the right of the
Control Terminal Board (CTB) (see Fig. 30). Factory wiring is completed through harnesses connected to the
CTB thermostat. Field connections are made at a 16--pole terminal block (TB3) located at the top of the unit control box in front of the PremierLink controller. The factory--installed PremierLink control includes the supply--air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$ert2 package.
The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to PremierLink Configuration instructions for Operating
Mode.
C10635
Fig. 30 -- 50TC--D Control Box Component Locations
22
Fig. 31 -- PremierLink Wiring Schematic
23
C101075
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 50TC--D unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 152 mm
(6--inches) in length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is mounted in the fan deck (see Fig. 32). It can be removed or remounted per local codes.. Drill or punch a 13 mm (1/2--in.) hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. Insure that the sensor wires do not contact the hot surface of the electric heaters.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR RETURN AIR
ROOF
CURB
Fig. 32 -- Mounting Location for Supply Air
Temperature (SAT) Sensor on 50TC--D Units
C10733
NOTE: Refer to Form 33CS--68SI for complete
PremierLink configuration, operating sequences and troubleshooting information. Have a copy of this manual available at unit start--up.
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.
EconoMi$er2 —
The PremierLink control is used with EconoMi$er2
(option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
2 sensor
Outdoor air CO
2 sensor
Refer to Table 3 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices are made at the 16--pole terminal block (TB3, see Fig. 31) located on the control box top in front of the PremierLink control . Some input devices also require a 24--vac signal source; connect at CTB terminal R at “THERMOSTAT” connection strip for this signal source. See connections figures on following pages for field connection locations
(and for continued connections at the PremierLink board inputs).
Table 4 provides a summary of field connections for units equipped with Space Sensor. Table 5 provides a summary of field connections for units equipped with Space Thermostat.
Table 3 – PremierLink Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
Differential Dry Bulb
Temperature with
PremierLink
(PremierLink requires
4---20 mA Actuator)
Single Enthalpy with
PremierLink
(PremierLink requires
4---20mA Actuator)
Differential Enthalpy with PremierLink
(PremierLink requires
4---20mA Actuator)
Included ---
CRTEMPSN001A00
Included ---
Not Used
Included ---
Not Used
Required ---
33ZCT55SPT or equivalent
---
---
---
Requires ---
33CSENTHSW
Requires ---
33CSENTHSW or equivalent
NOTES:
CO
2
Sensors (Optional):
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO
2
33ZCT55CO2 --- Space temperature and CO
33ZCT56CO2 --- Space temperature and CO
2
2 room sensor.
room sensor with override.
room sensor with override and setpoint.
24
RETURN AIR
ENTHALPY SENSOR
---
---
Requires ---
33CSENTSEN or equivalent
Table 4 – Space Sensor Mode
LEGEND:
T55
T56
CCN
CMPSAFE
FILTER
TB3 TERMINAL
1
2
3
6
7
4
5
12
13
14
10
11
8
9
15
16
FIELD CONNECTION
T55---SEN/T56---SEN
RMTOCC
T55---SEN/T56---SEN
CMPSAFE
T56---SET
FSD
LOOP---PWR
SPS
IAQ---SEN
FILTER
IAQ---COM/OAQ---COM/RH---COM
CCN + (RED)
OAQ---SEN/RH---SEN
CCN Gnd (WHT)
AUX OUT(Power Exhaust)
CCN --- (BLK)
--- Space Temperature Sensor
--- Space Temperature Sensor
--- Carrier Comfort Network (communication bus)
--- Compressor Safety
--- Dirty Filter Switch
FSD --- Fire Shutdown
IAQ --- Indoor Air Quality (CO
OAQ --- Outdoor Air Quality (CO
2
RH --- Relative Humidity
2
)
)
SFS --- Supply Fan Status
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
Analog (10k thermistor)
Discrete, 24VAC
Analog (10k thermistor)
Discrete, 24VAC
Analog, 24VDC
Discrete, 24VAC
Analog, 4---20mA
Discrete, 24VAC
Analog, 4---20mA
Digital, , 5VDC
Analog, 4---20mA
Digital, 5VDC
(Output)Discrete 24VAC
Digital, 5VDC
Table 5 – Thermostat Mode
TB3 TERMINAL
1
4
5
2
3
10
11
12
13
8
9
6
7
14
15
16
FIELD CONNECTION
RAT SEN
G
RAT SEN
Y1
Y2
LOOP---PWR
W1
IAQ---SEN
W2
IAQ---COM/OAQ---COM/RH---COM
CCN + (RED)
OAQ---SEN/RH---SEN
CCN Gnd (WHT)
AUX OUT (Power Exhaust)
CCN --- (BLK)
LEGEND:
CCN --Carrier Comfort Network (communication bus)
G --Thermostat Fan
IAQ --Indoor Air Quality (CO
2
)
OAQ --Outdoor Air Quality (CO
2
RAT --Return Air Temperature
)
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
Analog (10k thermistor)
Discrete, 24VAC
Discrete, 24VAC
Analog, 24VDC
Discrete, 24VAC
Analog, 4---20mA
Discrete, 24VAC
Analog, 4---20mA
Digital, 5VDC
Analog, 4---20mA
Digital, 5VDC
(Output) Discrete 24VAC
Digital, 5VDC
RH --- Relative Humidity
W1 --- Thermostat Heat Stage 1
W2 --- Thermostat Heat Stage 2
Y1 --- Thermostat Cool Stage 1
Y2 --- Thermostat Cool Stage 2
25
Space Sensors —
The PremierLink controller is factory--shipped configured for Space Sensor Mode. A Carrier T--55 or T--56 space sensor must be used. T--55 space temperature sensor provides a signal of space temperature to the PremierLink control. T--56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants.
1 2 3 4 5 6 RED(+)
WHT(GND)
BLK(-)
SEN
SW1
BRN (GND)
BLU (SPT)
CCN COM
SENSOR WIRING
C08201
Fig. 33 -- T--55 Space Temperature Sensor Wiring
Connect T--55: See Fig. 33 for typical T--55 internal connections. Connect the T--55 SEN terminals to TB3 terminals 1 and 3 (see Fig. 34).
SEN
TB3
1
PL
J6-7
SEN 3
Fig. 34 -- PremierLink T--55 Sensor
J6-6
C10023
Connect T--56: See Fig. 35 for T--56 internal connections.
Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to TB3 terminals 1, 3 and 5 (see Fig. 36).
1 2 3 4 5 6 RED(+)
WHT(GND)
BLK(-)
SW1
SEN SET
BLK
(T56)
BRN (GND)
BLU (SPT)
Cool Warm
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Fig. 35 -- T--56 Internal Connections
C08202
SEN
SEN
TB3
1
TB3
3
PL
J6-7
PL
J6-6
Jumper
SET
SET 5
Fig. 36 -- PremierLink T--56 Sensor
J6-5
C10022
Connect Thermostat —
A 7--wire thermostat connection requires a 24--v power source and a common connection. Use the R and C terminals on the CTB’s THERMOSTAT connection strip for these. Connect the thermostat’s Y1, Y2, W1, W2 and
G terminals to PremierLink TB3 as shown in Fig. 37.
If the 50TC--D unit is equipped with factory--installed smoke detector(s), disconnect the factory BLU lead at
TB3--6 (Y2) before connecting the thermostat. Identify the
BLU lead originating at CTB--DDC--1; disconnect at
TB3--6 and tape off. Confirm that the second BLU lead at
TB3--6 remains connected to PremierLink J4--8.
SPACE
THERMOSTAT
R
G
Y1
Y2
W1
CTB
THERMOSTAT
R
TB3
2
4
6
8
PL
J4-12
J4-10
J4-8
J4-6
W2
C
10
C CTB
THERMOSTAT
J4-4
C10283
Fig. 37 -- Space Thermostat Connections
If the 50TC unit has an economizer system and free--cooling operation is required, a sensor representing Return Air
Temperature must also be connected (field--supplied and installed). This sensor may be a T--55 Space Sensor (see Fig.
33) installed in the space or in the return duct, or it may be sensor PNO 33ZCSENSAT, installed in the return duct.
Connect this sensor to TB3--1 and TB3--3 per Fig. 34.
Configure the Unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for
Operating Mode. Default setting is Sensor Mode (value
1). Change the value to 0 to reconfigure the controller for
Thermostat Mode.
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
26
Economizer Controls
Indoor Air Quality (CO
2
) Sensor —
The indoor air quality sensor accessory monitors space carbon dioxide (CO
2
) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
2 present in the space air.
The CO
2 sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO
2 typical CO
2 sensor wiring schematic.
sensor for electrical requirements and terminal locations. See Fig. 38 for
+
-
+
0-10VDC
SIG COM
4-20mA
NC ALARM
COM
NO
}
RELAY
CONTACTS
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 38. Connect the 4--20 mA terminal to terminal TB3--9 and connect the SIG COM terminal to terminal TB3--11. See Fig. 39.
IAQ Sensor
J4
4-20mA
SIG COM
TB3
9
TB3
11
PL
J5-5
J5-3
24 VAC
Fig. 39 -- Indoor CO
2
Sensor (33ZCSENCO2)
Connections
C11156
Refer to Form 33CS--68SI, PremierLink Installation,
Start--up, and Configuration Instructions, for detailed configuration information.
Outdoor Air Quality Sensor
(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
2 sensor is designed to monitor carbon dioxide (CO
2
) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 40. The outdoor air CO
2 economizer outside air hood.
sensor must be located in the
H G 24 VAC
+ -
OR
24 VDC
2 1
J3
8 7 6 5 4 3 2 1
J4
C08635
Fig. 38 -- Indoor/Outdoor Air Quality (CO
2
) Sensor
(33ZCSENCO2) -- Typical Wiring Diagram
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO
2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources.
Allow at least 0.9 m (3 ft) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.
COVER REMOVED SIDE VIEW
Fig. 40 -- Outdoor Air Quality Sensor Cover
C07135
Wiring the Outdoor Air CO
2
Sensor: A dedicated power supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect the 4 to 20 mA terminal to the TB3--13 terminal of the 50TC--D . Connect the SIG COM terminal to the TB3--11 terminal of the
50TC--D. See Fig. 41.
27
OAQ Sensor
4-20mA
SIG COM
TB3
13
TB3
11
PL
J5-2
J5-3
24 VAC
Fig. 41 -- Outdoor CO
2
Sensor Connections
C11157
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory--wired for PremierLink FSD operation when
PremierLink is factory--installed.
On 50TC--D units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The PremierLink communicates the smoke detector’s tripped status to the
CCN building control. See Fig. 31, The PremierLink wiring schematic.
Filter Status Switch —
This function is available only when PremierLink is configured for (Space) Sensor Mode.
PremierLink control can monitor return filter status in two ways: By monitoring a field--supplied/installed filter pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch according to switch manufacturer’s instructions, to measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--10. Setpoint for Dirty Filter is set at the switch. See Fig. 42.
Filter Switch (NO, close on rising pressure (high drop))
CTB
Thermostat
R
TB3
10
PL
J4-4
C10286
Fig. 42 -- PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter pressure drop increases (indicating dirt--laden filters), the input signal to PremierLink causes the filter status point to read “DIRTY”.
Using Filter Timer Hours: Refer to Form 33CS--68SI for instructions on using the PremierLink Configuration screens and on unit alarm sequence.
Supply Fan Status Switch —
The PremierLink control can monitor supply fan operation through a field--supplied/installed differential pressure switch. This sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation.
Install the differential pressure switch in the supply fan section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to close as pressure rises indicating fan operation.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT--R terminal. Connect the other side of the
NO contact set to TB3--8. Setpoint for Supply Fan Status is set at the switch. See Fig. 43.
Fan (Pressure) Switch (NO, close on rise in pressure)
CTB
Thermostat
R
TB3
8
PL
J4-6
C10287
Fig. 43 -- PremierLink Wiring Fan Pressure Switch
Connection
Remote Occupied Switch —
The PremierLink control permits a remote timeclock to override the control’s on--board occupancy schedule and place the unit into Occupied mode. This function may also provide a “Door Switch” time delay function that will terminate cooling and heating functions after a 2--20 minute delay.
Connect one side of the NO contact set on the timeclock to
CTB’s THERMOSTAT--R terminal. Connect the other side of the timeclock contact to the unit’s TB3--2 terminal (see
Fig 44).
Remote Occupied
LCTB
Thermostat
R
Time Clock
TB3
2
PL
J4-12
C10288
Fig. 44 -- PremierLink Wiring Remote Occupied
Refer to Form 33CS--68SI for additional information on configuring the PremierLink control for Door Switch timer function.
Power Exhaust (output) —
Connect the accessory Power Exhaust contactor coils(s) per Fig. 45.
Power Exhaust
PER VIO
TB3
15
CTB
THERMOSTAT
C
PL
J8-3
BRN
Fig. 45 -- PremierLink Power Exhaust Output
Connection
C11158
28
Space Relative Humidity Sensor —
The RH sensor is not used with 50Hz 50TC--D models at this time.
CCN Communication Bus —
The PremierLink controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins, and likewise, positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins.
Wiring connections for CCN must be made at the 3--pin plug.
At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft (1219 m), with no more than 60 total devices on any 1000--ft (305 m) section. Optically isolated RS--485 repeaters are required every 1000 ft
(305 m).
NOTE: Carrier device default is 9600 band.
Communications Bus Wire Specifications: The CCN
Communication Bus wiring is field--supplied and field--installed. It consists of shielded 3--conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.
See Table 6 for recommended cable.
Table 6 – Recommended Cables
MANUFACTURER
Alpha
American
Belden
Columbia
CABLE PART NO.
2413 or 5463
A22503
8772
02525
NOTE: Conductors and drain wire must be at least 20
AWG (American Wire Gage), stranded, and tinned copper.
Individual conductors must be insulated with PVC,
PVC/nylon, vinyl, Teflon, or polyethylene.
An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of --20_C to 60_C
(4_F to 140_F) is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.
The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).
Connecting CCN bus:
NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See
Table 7 for the recommended color code.
Table 7 – Color Code Recommendations
SIGNAL TYPE
+
Ground
---
CCN BUS WIRE
COLOR
Red
White
Black
CCN PLUG PIN
NUMBER
1
2
3
Connect the CCN (+) lead (typically RED) to the unit’s
TB3--12 terminal. Connect the CCN (ground) lead
(typically WHT) to the unit’s TB3--14 terminal. Connect the CCN (--) lead (typically BLK) to the unit’s TB3--16 terminal. See Fig. 46.
CCN Bus
+ (RED)
TB3
12
PL
J2-1
GND (WHT)
TB3
14 J2-2
– (BLK)
TB3
16 J2-3
Fig. 46 -- PremierLink CCN Bus Connections
C10290
29
RTU Open Control System
The RTU Open control is factory--mounted in the
50DC*D unit’s main control box, to the right of the CTB.
See Fig. 30. Factory wiring is completed through harnesses connected to the CTB. Field connections for
RTU Open sensors will be made at the Phoenix connectors on the RTU Open board. The factory--installed RTU Open control includes the supply--air temperature (SAT) sensor.
The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package.
The RTU Open controller is an integrated component of the
Carrier rooftop unit. Its internal application programming provides optimum performance and energy efficiency. RTU
Open enables the unit to run in 100% stand--alone control mode, Carrier’s I--Vu Open network, or a Third Party
Building Automation System (BAS). On--board DIP switches allow you to select your protocol (and baud rate) of choice among the four most popular protocols in use today:
BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 47.)
Refer to Table 8, RTU Open Controller Inputs and Outputs for locations of all connections to the RTU Open board.
Fig. 47 -- RTU Open Multi--Protocol Control Board
C10811
30
Fig. 48 -- RTU Open System Control Wiring Diagram
31
C101076
Table 8 – RTU Open Controller Inputs and Outputs
POINT NAME
Space Temp / Zone Temp
Supply Air Temperature
Outdoor Air Temperature
Space Temperature Offset Pot
Safety Chain Feedback
Compressor Safety Status
Fire Shutdown Status
Enthalpy Status
Humidistat Input Status
Indoor Air CO2
Outdoor Air CO2
Space Relative Humidity
Supply Fan Status*
Filter Status*
Door Contact Input*
Occupancy Contact*
Economizer Output
Supply Fan Relay State
Compressor 1 Relay State
Compressor 2 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Dehumidification Relay State
BACnet OBJECT
NAME
TYPE OF I/O
DEDICATED INPUTS zone_temp AI (10K Thermistor) sa_temp oa_temp
AI (10K Thermistor)
AI (10K Thermistor) stpt_adj_offset safety_status comp_status firedown_status enthalpy_status humstat_status
AI (100K Potentiometer)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC) iaq
CONFIGURABLE INPUTS
AI (4---20 ma) oaq space_rh sfan_status filter_status
AI (4---20 ma)
AI (4---20 ma)
DI (24 VAC)
DI (24 VAC) door_contact_status occ_contact_status
DI (24 VAC)
DI (24 VAC)
OUTPUTS econ_output sfan comp_1 comp_2 heat_1 heat_2 pexh dehum
AO (4---20ma)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC, 1A)
LEGEND
AI --- Analog Input
AO --- Analog Output
DI --- Discrete Input
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.
The RTU Open controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 50TC--D unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 152 mm
(6--in.) in length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to the supply--air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air opening or in the supply air duct (as required by local codes). Drill or punch a 13 mm (1 /
2
--in.) hole in the flange or duct. Use two field--supplied, self--drilling screws to secure the sensor probe in a horizontal orientation. See
Fig. 32.
CONNECTION PIN
NUMBER(S)
J20---1, 2
J2---1, 2
J2---3, 4
J20---3
J1---9
J1---2
J1---10
J2---6
J5---7
J4---2 or J4---5
J5---1 or J5---3 or
J5 5 or J5---7
J2---5
J1---4
J1---8
J1---7
J1---6
J1---5
J11---3
J11---7, 8
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.
EconoMi$er2 —
The RTU Open control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU Open control;
EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
2 sensor
Outdoor air CO
2 sensor
32
Field Connections
Field connections for accessory sensors and input devices are made the RTU Open, at plugs J1, J2, J4, J5, J11 and
J20. All field control wiring that connects to the RTU
Open must be routed through the raceway built into the corner post as shown in Fig. 24. The raceway provides the
UL required clearance between high-- and low--voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU Open. Connect to the wires to the removable
Phoenix connectors and then reconnect the connectors to the board.
Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Carrier, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone operation for back-up. Refer to the configuration section for details on controller configurations associated with space sensors.
S 33ZCT55SPT, space temperature sensor with override button (T--55)
S 33ZCT56SPT, space temperature sensor with override button and setpoint adjustment (T--56)
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and setpoint adjustment (T--59)
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 152 m (500 ft.)
Use a three--conductor shielded cable for the sensor and setpoint adjustment connections.
If the setpoint adjustment (slidebar) is not required, then an unshielded,
18 or 20 gauge, two--conductor, twisted pair cable may be used.
Connect T--55: See Fig. 33 for typical T--55 internal connections. Connect the T--55 SEN terminals to RTU
Open J20--1 and J20--2. See Fig. 49.
SEN J20-1
SEN J20-2
Fig. 49 -- RTU Open T--55 Sensor Connections
C08460
Connect T--56: See Fig. 35 for T--56 internal connections.
Install a jumper between SEN and SET terminals as illustrated. Connect T--56 terminals to RTU Open J20--1,
J20--2 and J20--3 per Fig. 50.
SEN
SEN J20-2
Jumper
SET
SET J20-3
Fig. 50 -- RTU Open T--56 Sensor Connections
C08461
Connect T--59: The T--59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 51 for internal connections at the T--59. Connect the SEN terminal (BLU) to RTU Open J20--1. Connect the COM terminal (BRN) to J20--2. Connect the SET terminal (STO or BLK) to J20--3.
BLK (STO)
J20-3
BRN (COM)
BLU (SPT)
J20-2
SENSOR
WIRING
J20-1
OR SET SEN
OPB COM- PWR+
J20-1
24 VAC
POWER
WIRING
NOTE: Must use a separate isolated transformer.
C10291
Fig. 51 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Indoor Air Quality (CO
2
) Sensor —
The indoor air quality sensor accessory monitors space carbon dioxide (CO
2
) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO
2 present in the space air.
The CO
2 sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO typical CO
2
2 sensor wiring schematic.
sensor for electrical requirements and terminal locations. See Fig. 38 for
To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return--air grille (if present) so it senses the concentration of CO
2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
33
Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources.
Allow at least 0.9 m (3 ft) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor, use two 2--conductor 18 AWG (American Wire Gage) twisted--pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the RTU Open control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 38. Connect the 4--20 mA terminal to
RTU Open J4--2 and connect the SIG COM terminal to
RTU Open J4--3. See Fig. 52.
IAQ Sensor
4-20mA J4-2
SIG COM J4-3
24 VAC
Fig. 52 -- RTU Open / Indoor CO
2
(33ZCSENCO2) Connections
Sensor
C10738
Outdoor Air Quality Sensor
(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
2 sensor is designed to monitor carbon dioxide (CO
2
) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 40. The outdoor air CO
2 sensor must be located in the economizer outside air hood.
Wiring the Outdoor Air CO
2
Sensor: A dedicated power supply is required for this sensor. A two--wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect the 4 to 20 mA terminal to RTU Open J4--5. Connect the SIG COM terminal to RTU Open J4--6. See Fig. 53.
OAQ Sensor/RH Sensor
4-20mA J4-5
SIG COM J4-6
24 VAC
Fig. 53 -- RTU Open / Outdoor CO
2
(33ZCSENCO2) Connections
Sensor
C10739
On 50TC--D units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open controller communicates the smoke detector’s tripped status to the BAS building control. See Fig. 48, the RTU
Open System Control Wiring diagram.
The Fire Shutdown Switch configuration,
MENU→Config→Inputs→input 5, identifies the normally open status of this input when there is no fire alarm.
Connecting Discrete Inputs —
Filter Status: The filter status accessory is a field--installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting
MENU→Config→Inputs→input 3, 5, 8, or 9 to Filter
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer to Fig. 47 and Fig. 48 for wire terminations at J5.
Fan Status: The fan status accessory is a field--installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting
MENU→Config→Inputs→input 3, 5, 8, or 9 to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer to Fig. 47 and Fig. 48 for wire terminations at J5.
Remote Occupancy: The remote occupancy accessory is a field--installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be configured for remote occupancy by setting
MENU→Config→Inputs→input 3, 5, 8, or 9 to Remote
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set MENU→Schedules→occupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 47 and Table 8 for wire terminations at J5.
Power Exhaust (output): The relay used by the RTU
Open board to control power exhaust is a dry contact which means it does not have 24vac. This 24vac must be connected to the relay to allow it to operate the power exhaust relay in the PE accessory. A 24vac source must be provided to J11--2 on the RTU Open control board. This can be provided by the unit’s transformer from various sources. The “R” terminal on the unit’s low voltage terminal board (LVTB) is a logical source. Refer to Fig.
47 and Fig. 48 for wire terminations at J11.
Space Relative Humidity Sensor: The RH sensor is not used with 50Hz 50TC--D models at this time.
34
Communication Wiring -- Protocols
General —
Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different.
The RTU Open can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks.
Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to set the board’s network address. See Fig. 54 and 55 for protocol switch settings and address switches. The 3rd party connection to the RTU Open is through plug J19.
See Fig. 56 for wiring.
NOTE: Power must be cycled after changing the SW1--3 switch settings.
Refer to the RTU Open Controller Integration Guide
(Catalog No. 11--808--428--01) for more detailed information on protocols, 3rd party wiring, and networking.
PROTOCOL
BACnet MS/TP
(Master)
Modbus
(Slave)
N2
(Slave)
LonWorks
DS8
Unused
Unused
Unused
Unused
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
DS7
OFF
OFF
OFF
ON
BAUD RATE
9600
19,200
38,400
76,800
Baud Rate Selections
DS2
OFF
ON
OFF
ON
SW3 Protocol Selection
DS6
OFF
DS5
OFF
OFF
OFF
ON
ON
OFF
OFF
DS4
ON
ON
ON
ON
DS1
OFF
OFF
ON
ON
Fig. 54 -- RTU Open SW3 Dip Switch Settings
DS3
OFF
OFF
ON
OFF
DS2 DS1
Select Baud Select Baud
Select Baud Select Baud
OFF
OFF
OFF
OFF
C07166
Fig. 55 -- RTU Open Address Switches
C10815
Fig. 56 -- Network Wiring
C10816
35
Local Access —
BACview 6 Handheld: The BACview 6 is a keypad/display interface used to connect to the RTU Open to access the control information, read sensor values, and test the RTU, see Fig. 57. This is an accessory interface that does not come with the RTU Open controller and can only be used at the unit. Connect the BACview 6 to the RTU Open J12 local access port. There are two password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is idle. See Form
48--50HCTQ--01T, Appendix A for navigation and screen content.
Virtual BACview: Virtual BACview is a freeware computer program that functions as the BACview 6 Handheld. The
USB Link interface (USB--L) is required to connect a computer to the RTU Open board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld.
RTU Open Troubleshooting —
Communication LEDs: The LEDs indicate if the controller is speaking to the devices on the network. The
LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 9.
Cable
Access Port
P1 P1
J12
P5 P5
Protocol Selector
RTU Open
BACview 6 Local Access Cable
Fig. 57 -- BACview 6 Handheld Connections
C10812
36
Table 9 – LEDs
The LEDs on the RTU Open Control Board (see Fig. 47) show the status of certain functions:
If this LED is on...
Power
Rx
Tx
DO#
Status is...
RTU Open has power
RTU Open is receiving data from the network segment
RTU Open is transmitting data over the network segment
The digital output is active
If Run LED shows...
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
14 flashes per second
On
The Run and Error LEDs indicate control module and network status
And Error LED shows...
Off
2 flashes, alternating with Run LED
3 flashes, then off
4 flashes, then pause
Status is...
Normal
Five minute auto---restart delay after system error
Control module has just been formatted
On
On
Off
7 flashes per second, alternating with
Run LED
14 flashes per second, alternating with Run LED
Two or more devices on this network have the same ARC156 network address
Exec halted after frequent system errors or control programs halted
Exec start---up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
On
Brownout
Failure. Try the following solutions:
S
Turn RTU Open off, then on.
S
Format RTU Open.
S
Download memory to RTU Open.
S
Replace RTU Open.
NOTE: Refer to Catalog No. 48--50HCTQ--01T for complete configuration of RTU Open, operating sequences and troubleshooting information. Refer to RTU Open
Controller Integration Guide (Catalog No. 11--808--428--01) for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start--up.
Outdoor Air Enthalpy Control
(PNO 33CSENTHSW) --
The enthalpy control (33CSENTHSW) is available as a field--installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field--installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 58.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 58. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK
(connect to GND).
Enthalpy
Switch
24V
GND
RED
BLK
PL6-1 (24-V)
PL6-4 (COM)
LOW GRA 7 CTB ECON
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
Factory Wiring Harness
C11160
Fig. 58 -- Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor (see Fig. 59).
37
24V
– 4-20
Main
+ VDC
Out
GND
LOW
Outside Air
Enthalpy Switch
RED
BLK
GRA
PL6-1 (24-V)
7
PL6-4 (COM)
CTB ECON
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
Return Air Sampling Tube
(Shipping Location)
+ 24-36
VDC In
– 4-20 Main
Out
Return Air
Enthalpy
Sensor
C11161
Fig. 59 -- Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.
2. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (+) terminal on the enthalpy controller. Connect the BLK wire to (--) spade connector on the return air enthalpy sensor and the (--) terminal on the enthalpy controller.
Smoke Detectors
Smoke detectors are available as factory--installed options on 50TC--D models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical return configurations only. The unit is factory--configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.
Return Air Sensor Tube Installation –
The return air sampling tube is shipped in the unit’s supply fan section, attached to the blower housing (see Fig. 60). Its operating location is in the return air section of the unit (see
Fig. 61, unit without economizer, or Fig. 62, unit with economizer), inserted into the return air sensor module housing which protrudes through the back of the control box.
ROT
ATION
C09102
Fig. 60 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air Detector
Sampling Tube
Fig. 61 -- Return Air Sampling Tube Location
C09135 in Unit without Economizer
38
Return Air Detector
Sampling Tube
Fig. 62 -- Return Air Sampling Tube Location in Unit with Economizer
C09136
To install the return air sensor sampling tube:
1. Remove the tube from its shipping location.
2. Open the unit end to access the return air sensor (located on right--hand partition)
3. Orient the tube’s sampling holes into the return air flow direction. For vertical application, position the sampling holes on the bottom of the tube, facing into the bottom return duct opening. For horizontal application, position the sampling holes on the side of the tube, facing the unit’s end panel.
4. Insert the sampling tube into the return air sensor module’s forward or rear opening until the tube snaps into position.
5. Replace end panel or outside air hood.
Return Air Sensor Exhaust Tube Installation —
The exhaust tube is shipped in a bag located in the control box. The exhaust tube is 152 mm (6 inches) long with a base coupling and a gasket. Slip the gasket over the coupling end, then insert the connector into the rear opening in the sensor module until the tube snaps into location.
NOTE: The shipping bag contains a tube plug or cap.
This part is not used in this installation and may be discarded. Do NOT insert the plug into the exhaust tube.
Test/Reset Magnet —
The shipping bag also contains a magnet for testing and resetting smoke detectors. Do not discard this magnet.
Additional Application Data —
Refer to Catalog No. HKRNKA--1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.
39
Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data
ELEC. HTR { P.E.
NO P.E.
CRHEATER***A00
VERTICAL
283A00
284A00
NONE
282A00
283A00
284A00
NONE
284A00
NONE
282A00
283A00
284A00
NONE
282A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
HORIZONTAL
274A00
275A00
NONE
273A00
274A00
275A00
NONE
275A00
NONE
273A00
274A00
275A00
NONE
273A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
Nom
(kW)
FLA MCA
LRA
253
253
262
262
262
262
262
249
253
253
253
253
253
253
249
249
249
249
253
253
240
240
240
240
253
253
249
249
249
303
285
285
285
285
262
262
262
303
303
303
285
285
285
285
326
326
326
326
FLA
69
98
51
51
66
95
54
92
48
48
66
95
51
51
44
44
63
92
48
48
43
43
62
90
66
95
44
44
63
106
55
55
66
95
54
69
98
61
61
77
58
58
69
98
66
66
77
106
FUSE or
HACR
BRKR
80
100
60
60
80
100
60
90
60
60
80
100
60
60
50
50
70
90
60
60
50
50
70
90
80
100
50
50
70
110
60
60
80
100
60
80
100
70.0
70
90
60
60
80
100
80
80
90
110
34.7
52.1
---
17.4
34.7
52.1
---
52.1
---
17.4
34.7
52.1
---
17.4
---
17.4
34.7
52.1
---
17.4
---
17.4
34.7
52.1
34.7
52.1
---
17.4
34.7
52.1
---
17.4
34.7
52.1
17.4
34.7
52.1
---
17.4
34.7
---
17.4
34.7
52.1
---
17.4
34.7
52.1
FLA
50.1
75.2
---
25.1
50.1
75.2
---
75.2
---
25.1
50.1
75.2
---
25.1
---
25.1
50.1
75.2
---
25.1
---
25.1
50.1
75.2
50.1
75.2
---
25.1
50.1
75.2
---
25.1
50.1
75.2
25.1
50.1
75.2
---
25.1
50.1
---
25.1
50.1
75.2
---
25.1
50.1
75.2
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
75.4
88.0
48.8
48.8
72.1
84.7
51.4
80.7
45.6
45.6
72.1
84.7
48.2
48.2
42.4
42.4
68.1
80.7
45.6
45.6
41.4
41.4
66.9
79.5
72.1
84.7
42.4
42.4
68.1
96.2
52.7
52.7
72.1
84.7
51.4
75.4
88.0
58.0
58.0
83.6
55.3
55.3
75.4
88.0
61.9
61.9
83.6
96.2
DISC. SIZE
MCA w/ P.E. (pwrd fr/unit)
DISC. SIZE
FUSE or
HACR
BRKR
90
100
60
60
80
100
70
100
60
60
80
100
60
60
60
60
80
100
60
60
60
60
80
90
80
100
60
60
80
110
70
70
80
100
70
90
100
80
80
100
80
80
90
100
80
80
100
110
FLA
76
105
58
58
73
102
61
99
55
55
73
102
58
58
51
51
70
99
55
55
50
50
69
98
73
102
51
51
70
113
62
62
73
102
61
76
105
68
68
84
65
65
76
105
73
73
84
113
LRA
265
265
274
274
274
274
274
261
265
265
265
265
265
265
261
261
261
261
265
265
252
252
252
252
265
265
261
261
261
315
297
297
297
297
274
274
274
315
315
315
297
297
297
297
338
338
338
338
83.1
95.7
55.0
55.0
79.9
92.5
57.6
88.5
51.8
51.8
79.9
92.5
54.4
54.4
48.6
48.6
75.9
88.5
51.8
51.8
47.6
47.6
74.6
87.2
79.9
92.5
48.6
48.6
75.9
104.0
58.9
58.9
79.9
92.5
57.6
83.1
95.7
64.2
64.2
91.4
61.5
61.5
83.1
95.7
68.1
68.1
91.4
104.0
NOTE: See page 41 for table legend and notes.
40
CRHEATER***A00
VERTICAL
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
NONE
282A00
283A00
284A00
Legend and Notes for Table 10
LEGEND:
BRKR --Circuit breaker
DISC --Disconnect
FLA --Full load amps
IFM --Indoor fan motor
LRA --Locked rotor amps
MCA --Minimum circuit amps
PE --Power exhaust
HORIZONTAL
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
NONE
273A00
274A00
275A00
Nom
(kW)
---
17.4
34.7
52.1
---
17.4
---
17.4
34.7
52.1
34.7
52.1
Table 10 -- Unit Wire/Fuse or HACR Breaker Sizing Data (cont)
ELEC. HTR { P.E.
NO P.E.
w/ P.E. (pwrd fr/unit)
DISC. SIZE DISC. SIZE
FLA
---
25.1
50.1
75.2
---
25.1
---
25.1
50.1
75.2
50.1
75.2
FLA MCA
3.1
3.1
3.1
70.7
70.7
83.6
96.2
71.1
71.1
64.1
64.1
75.4
88.0
84.1
96.7
FUSE or
HACR
BRKR
90
90
90
110
90
90
80
80
80
100
90
110
LRA
374
374
374
374
392
392
333
333
333
333
392
392
FLA
75
75
77
106
75
75
67
67
69
98
77
106
MCA
70.3
70.3
83.1
95.7
76.9
76.9
91.4
104.0
77.3
77.3
91.9
104.5
FUSE or
HACR
BRKR
90
90
100
110
90
90
90
90
90
100
100
110
FLA
82
82
84
113
83
83
75
75
76
105
85
113
LRA
386
386
386
386
404
404
345
345
345
345
404
404
{ Heater capacity (kW) is based on heater voltage of 400 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
NOTES:
1. In compliance with NEC requirements (U.S.A. Standard) for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2. MCA calculation for units with electric heaters over 50 kW =
(1.25 x IFM amps) + (1.00 x heater FLA).
41
Economizer 2 Position Damper
Unit Without Economizer or
2 Position Damper
C10645
Fig. 63 -- EconoMi$ert IV Wiring
Step 12 — Adjust Factory--Installed Options
EconoMi$er IV Occupancy Switch —
Refer to Fig. 63 for general EconoMi$er IV wiring.
External occupancy control is managed through a connection on the Central Terminal Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to complete the installation.
Step 13 — Install Accessories
Available accessories include:
Roof Curb
Thru--base connection kit (must be installed before unit is set on curb)
Manual outside air damper
Two--Position motorized outside air damper
EconoMi$er IV (with control and integrated barometric relief)
EconoMi$er2 (without control/for external signal and integrated barometric relief)
Power Exhaust
Differential dry--bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
Electric Heaters
Single Point kits
Thermostat / Sensors
CO
2 sensor
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information on installing these accessories.
Pre--Start and Start--Up
This completes the mechanical installation of the unit.
Refer to the unit’s Service and Maintenance manual for detailed Pre--Start and Start--up instructions.
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A.
Edition Date: 08/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
42
Catalog No: 50TC---C06SI
Replaces: 50TC--- C05SI
I.
PRELIMINARY INFORMATION
MODEL NO.:
DATE:
START-UP CHECKLIST
(Remove and Store in Job File)
SERIAL NO.:
TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
j VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE j VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT j REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS j VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS j CHECK REFRIGERANT PIPING FOR INDICATIONS OF LEAKS; INVESTIGATE AND REPAIR IF NECESSARY j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS j CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE j VERIFY THAT UNIT INSTALLATION IS LEVEL j CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
III. START-UP (REFER TO UNIT SERVICE/MAINTENANCE MANUAL FOR START--UP
INSTRUCTIONS)
ELECTRICAL
SUPPLY VOLTAGE
CIRCUIT 1 COMPRESSOR AMPS
CIRCUIT 2 COMPRESSOR AMPS
INDOOR-FAN AMPS
L1-L2
L1
L1
L2-L3
L2
L2
L3-L1
L3
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
PRESSURES (Cooling Mode)
REFRIGERANT SUCTION, CIRCUIT 1
REFRIGERANT SUCTION, CIRCUIT 2
REFRIGERANT DISCHARGE, CIRCUIT 1
REFRIGERANT DISCHARGE, CIRCUIT 2
DB
DB
DB kPa kPa kPa
OR kPa
WB
WB
WB
PSIG
PSIG
PSIG
PSIG
_ C
_ C
_ C
OR
_ C
_ F
_ F
_ F
_ F j VERIFY THAT 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION.
j VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS
(IF EQUIPPED)
43
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A.
Edition Date: 08/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
Catalog No: 50TC---C06SI
Replaces: 50TC--- C05SI