The barbas Unilux-6 45 is a wood-burning insert appliance designed for cozy evenings. It's ideal for smoke control areas and features a factory-installed modified air slider for compliance with smoke emission requirements. This manual provides detailed instructions for installation, operation, and annual maintenance.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Barbas Unilux-6 45 Installation Manual - Download & View Online | Manualzz
INSTALLATION INSTRUCTIONS &
MANUAL FOR ANNUAL MAINTENANCE
UNILUX-6 45
Wood-burning insert appliance
Barbas wishes you many cosy evenings with your new fire
This document is an essential part of your fire.
Read it carefully before installation and maintenance
of the gas fire and keep it in a safe place!
Version number: 04 - 344230
Serial number:
Date: 17-06-2019
Production date:
UNILUX-6 45
Declaration of Performance
According to regulation (EU) 305/2011
No. 1.818.080-2 - CPR-2013/07/01
1.
Unique identification code of the product-type
Unilux-6 45
2.
Intended use or uses of the construction product, in
accordance with the applicable harmonised technical
specification, as foreseen by the manufacturer
Room heater without hot water supply
3.
Name, registered trade name or registered trade mark Barbas Bellfires BV; Hallenstraat 17; 5531 AB Bladel; The Netherlands
and contact address of the manufacturer as required
pursuant to Article 11(5)
4.
Where applicable, name and contact address of the
Not applicable
authorised representative whose mandate covers the
tasks specified in Article 12(2)
System or systems of assessment and verification of
System 3
constancy of performance of the construction product
as set out in Annex V
5.
6.
In case of the declaration of performance concerning a
construction product covered by a harmonised
standard
7.
Declared performance
Harmonized technical specification
Essential characteristics
Fire safety
Distance to combustible materials
Risk of burning fuel falling out
Emission of combustion products
Surface temperature
Electrical safety
Cleanability
Release of dangerous substances
Maximum operating pressure
Flue gas temperature at nominal heat output
Mechanical resistance (to carry a chimney/flue)
Thermal output
Nominal heat output
Room heating output
Water heating output
Energy efficiency
8.
The notified laboratory SGS Nederland BV, No. 0608 performed the
determination of the product type on the basis of type testing under system 3
and issued test report EZKA/2017-01/00016-1
EN13229:2001/A2:2004/AC:2007
Performance
Pass
Minimum distances, in mm
Insulation thickness rear =
100
Insulation thickness sides =
100
Insulation thickness ceiling =
100
Front =
800
Insulation thickness floor =
100
Pass
CO = 0.09 vol%
Pass
Pass
Pass
NPD
Not applicable
T = 302 °C
NPD
Pass
6 kW
6 kW
- kW
75.8 %
The performance of the product identified in point 1 is in conformity with the declared performance in point 7.
This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 3.
Signed for and on behalf of the manufacturer by:
Danny Baijens, CEO
(Name and function)
Bladel; September 18, 2018
(place and date of issue)
Installation instructions
………………………………………………………………………..
(Signature)
3
UNILUX-6 45
4
Installation instructions
UNILUX-6 45
TABLE OF CONTENTS
Page
1
Introduction
1.1 General ................................................................................................
1.2 Safety and installation instructions ......................................................
7
8
Placing
2.1 Included ...............................................................................................
2.2 Preparation for positioning ...................................................................
2.3 Accessories .........................................................................................
2.4 Hearth requirements ............................................................................
10
10
14
15
Installation
3.1 Instructions ...........................................................................................
3.2 Flue gas channel ..................................................................................
3.3 Fitting ...................................................................................................
3.4 Preparation / Function check ...............................................................
17
17
18
26
4
Operation ....................................................................................................
27
5
Annual maintenance ...................................................................................
28
6
Replacement parts ......................................................................................
30
7
Dimensions .................................................................................................
35
8
Technical data .............................................................................................
40
9
Warranty terms ...........................................................................................
41
2
3
Installation instructions
5
UNILUX-6 45
6
Installation instructions
UNILUX-6 45
1
INTRODUCTION
1.1 GENERAL
The appliance must be positioned and connected by a Barbas dealer/specialist in
accordance with the following installation instructions, nationally and locally applicable
regulations. This manual contains directions for both positioning the appliance and for
its environmentally-friendly use. It also contains technical data for the appliance, parts
information and directions in the event of problems.
This appliance is recommended as suitable for use in smoke control areas when
burning wood logs. The appliance, when sold into the UK market, include a factoryinstalled modified air slider to ensure compliance with smoke emission requirements
within smoke control areas.
Study this manual carefully before using the fireplace. We recommend you keep this
manual in a safe place for reference purposes.
The pictures in this Installation Instructions are made from a variant of this appliance.
Although the dimensions of the appliance on the pictures may differ from reality, the
actions and instructions shown are fully valid for the appliance described here.
See the “Instructions for use” for the operation of the appliance
The “Instructions for use” is provided separately by the appliance.
“The Clean Air Act 1993 and Smoke Control Areas”
Under the Clean Air Act local authorities may declare the whole or part of the district of
the authority to be a smoke control area. It is an offence to emit smoke from a chimney
of a building, from a furnace or from any fixed boiler if located in a designated smoke
control area. It is also an offence to acquire an “unauthorised fuel” for use within a
smoke control area unless it is used in an “exempt” appliance (“exempted” from the
controls which generally apply in the smoke control area).
In England appliances are exempted by publication on a list by the Secretary of State
in accordance with changes made to sections 20 and 21 of the Clean Air Act 1993 by
section 15 of the Deregulation Act 2015.
In Scotland appliances are exempted by publication on a list by Scottish Ministers under
section 50 of the Regulatory Reform (Scotland) Act 2014.
In Northern Ireland appliances are exempted by publication on a list by the Department
of Agriculture, Environment and Rural Affairs under Section 16 of the Environmental
Better regulation Act (Northern Ireland) 2016.
In Wales appliances are exempted by regulations made by Welsh Ministers.
Further information on the requirements of the Clean Air Act can be found here:
https://www.gov.uk/smoke-control-area-rules.
Your local authority is responsible for implementing the Clean Air Act 1993 including
designation and supervision of smoke control areas and you can contact them for
details of Clean Air Act requirements.
Installation instructions
7
UNILUX-6 45
1.2 SAFETY AND INSTALLATION INSTRUCTIONS
• Do not place flammable objects within 100 cm of the appliance. Pay special attention
to furnishings and ornaments around the appliance.
• During installation of the appliance, a clearance of 3 mm should be maintained on all
sides of the appliance to allow for expansion of the appliance during operation.
• When you use your appliance, the exterior will become hot. Always wear the glove
or use the accessories supplied when filling etc.
Protect yourself and others (especially children!) from burns. Do not leave children
unattended when the appliance is burning.
• Watch your clothing. Synthetic clothing in particular can easily catch fire and burn
intensely.
• Do not approach the appliance with flammable materials or liquids. Any work with
solvents, adhesives etc. in the space heated by the appliance can be very
dangerous.
• It is not allowed to connect the appliance to a flue which is already connected to
another appliance.
• Check the chimney. Cracks in the chimney may not only lead to damp, staining
of walls and leaking of smoke, they can also impair the carrying off of smoke.
• Prevent your chimney being soiled from above (birds’ nests etc.) by fitting a suitable
cap to the chimney pot.
• Avoid chimney fires! Have your chimney swept at least once per year - more often
if you use your fire a lot. Prevent excessive deposits of soot inside the chimney by
not burning freshly-cut wood. Instead, burn clean, dry chopped wood.
• Follow the instructions issued by your local fire brigade.
The appliance can be taken in operation if national and local regulations are satisfied.
The required constructive adaptations should be satisfied as well.
• It is essential that the appliance, the flue and combustion air supply are cleaned and
inspected annually by a Barbas dealer/specialist.
The safe operation of the appliance will thus remain guaranteed.
• The appliance is suitable and approved for periodical use.
• The appliance may only be set up if the appliance and location meets the
- national and local installation regulations;
- local fire brigade regulations and required architectural provisions.
8
Installation instructions
UNILUX-6 45
• Ensure that the room in which the appliance is situated has adequate ventilation.
• Wood and wood briquettes may be stoked in the appliance.
Do not use any coal and liquid fuels or fuel gel in the appliance. The appliance is
not intended for use of this fuels and can be dangerous and lead to damage to your
health and may seriously damage the appliance.
• Never use the appliance to burn rubbish.
• Please read all instructions / stickers on and around the appliance.
• Read the “Directions for use” before using the appliance for the first time. When you
first fire up your appliance, there are a number of extra points you should take into
account.
• In transit, some parts of the appliance may have moved from their original place.
Check that the door opens and closes, the baffle plates are fitted correctly to the
brackets at the top of the appliance and the heat-resistant panels are fixed to the
walls. Check if there are no foreign objects in the appliance.
• Avoid over-loading (white burning glow), caused, for example, by lengthy burning
with primary air (combustion air supply slider all the way to “ + ”) or by burning too
much wood in one go. The appliance can then become over-heated.
• Ask for the local building regulations, before commensing the installation of the
appliance.
Installation instructions
9
UNILUX-6 45
2
LOCATION
2.1
INCLUDED
Set documentation
•
•
Directions for use
Installation instructions
Attributes
•
•
Glove (Heat resistant up to max. 95°C)
Operating hook / Poker
N.B. If any part is missing, please contact your dealer.
2.2
PREPARATION FOR POSITIONING
Check all functions of the appliance before fitting.
• Check the opening and closing operation of the door.
Turn the handle all the way down:
Door is locked.
10
Installation instructions
UNILUX-6 45
Handle forwards:
The door releases from its lock and can be opened forwards.
For this, use the operating hook supplied.
• Check whether the 2 baffle plates are located correctly in the supports.
• Check the operation of the slider for the regulation of the combustion air intake
(middle below the window).
Installation instructions
11
UNILUX-6 45
• Check whether the ashtray is completely empty.
• Report any defects immediately to your dealer.
• Remove enclosed documents and components from the appliance.
•
12
Important:
Decide how to install the appliance.
There are many possibilities !
See also chapter 3.3 Fitting.
Dependent on the type of fireplace where
the appliance is located /installed.
Installation instructions
UNILUX-6 45
Connection Possibilities:
I
Mounting as insert in an existing fireplace.
In these situations the combustion air inlet is at the front of the appliance.
Ventilate the chimney
breast, when it is totally
empty, by placing vents in
the top and bottom of the
chimney breast.
II
Installing as a build-in appliance in an existing or new fireplace.
In this situation it is possible to fit the appliance with a combustion air supply from
the outside through the back or the underside of the appliance.
Ventilate the chimney breast, when it is totally empty.
Installation instructions
13
UNILUX-6 45
•
= Closed
(“break away” discs)
= Open
(“break away” discs)
= Grate
Ventilation openings chimney breast
= Grate
Combustion air supply via wall outlet
Ventilation casing / chimney.
Ensure that the casing/chimney has sufficient ventilation openings (See
Chapter 3 and 4).
Have the suitability of the area in which the fire is to be fitted (and the chimney)
approved by a specialist. The space into which the appliance is to be fitted must in no
way be damaged. The appliance must have its own chimney, constructed in compliance
with current legislation.
2.3
ACCESSORIES
The following accessories can be supplied by your dealer:
14
Art. nr.
Accessorie
344174
Built-in frame
344175
Deepened frame
344173
Classic frame
309872
310178
Grate ventilation chimney
Fitting box for grate ventilation chimney
Installation instructions
UNILUX-6 45
2.4
HEARTH REQUIREMENTS
The appliance must be placed on a constructional hearth made of solid non-combustible
material, such as concrete or masonry, at least 125 mm thick, including the thickness of
any non-combustible floor and/or decorative surface. Combustible material should not
be placed beneath the constructional hearths unless there is an air-space of at least
50 mm between the underside of the hearth and the combustible material, or the
combustible material is at least 250 mm below the top of the hearth.
A
B
150 mm
150 mm
Min
. 50
M
seein. de
dia pth
gra
0m
m
m
A = Superimposed hearth
B = Constructional hearth
Figure 1: Minimum dimensions appliance
The minimum depth of the constructional hearth is 500 mm. A superimposed hearth on
top of the constructional hearth must have a minimum depth of 225 mm and must be
free of any combustible material. The actual depth of a superimposed hearth is dependent on the installation height of the appliance. The higher the appliance is installed the
deeper the superimposed hearth should be to avoid scorched floor coverings. On the
diagram below the minimum depth of the superimposed hearth in relation to the height
of the appliance can be determined.
Installation instructions
15
UNILUX-6 45
Figure 2: Minimum depth of the superimposed hearth in relation to the height
of the appliance
The constructional hearth and a superimposed hearth must have a width extending at
least 150 mm from each side of the appliance.
16
Installation instructions
UNILUX-6 45
3
INSTALLATION
3.1 INSTRUCTIONS
When fitting one of these appliances local and/or national regulations relating to fire
safety must be followed. In case of doubt, consult the fire safety department of the local
fire brigade, particularly if the fire is to be fitted in a home with walls and/or floors
containing flammable material.
The connection of several appliances to a single flue/chimney is not allowed.
3.2 CHIMNEY
If no chimney is immediately available, have one fitted by a recognised specialist only.
The chimney must be compliant with local regulations and is particularly important because it has a significant bearing on the function of the appliance.
Basic rules:
• A chimney for an open appliance is not, by definition, suitable for a closable model
(i.e. an appliance with doors). As a closed appliance draws in much less (cold) air,
the smoke is hotter. Please have your chimney inspected to see whether it is suitable
for a closable appliance.
• The chimney opening must be at least 5 metres above the top of the door opening of
your appliance.
• The chimney must protrude at least 40 cm above the apex of a sloping roof and at
least 1 metre above a flat roof. In short, the chimney must always end in an area with
a negative air pressure. Contact your local chimney sweep
for the exact dimensions of the chimney opening.
• The internal diameter must not be less than that of the appliance at any point (even
at the end of the pipe).
• Avoid bends at all costs. The maximum deviation from the perpendicular is 45°.
Never use more than 2 bends.
• Both the dimensions and the construction must meet stringent construction
standards. Your recognised specialist will be pleased to assist.
• Contact your fire insurer to make sure that your policy is in order.
Installation instructions
17
UNILUX-6 45
3.3 FITTING
The appliance can be fitted in the newly-built or existing chimney breast of an open fire.
When fitting, both fire safety and operational safety must be safeguarded. The fitter is
responsible for this.
General guidelines:
• If there is a wooden beam above the fitting location, heat must not radiate directly
onto it. An insulation plate must be hung below the beam, leaving an air gap between
it and the beam of at least 1 cm.
• Always use (white) unbound ceramic insulation wool. Bound material (yellow), such
as glass and rock wool, spreads an irritating smell on heating, causes excess smoke
and is unsuitable for high temperatures.
Insulation requirements:
• temperature resistance ≥ 700°C.
• density ≥ 80 kg/m3
• Before fitting, remove the door to protect the glass.
3.3.1 Positioning of the appliance
The appliance must be positioned on a concrete surface. If such a surface is not
immediately available, a sufficiently solid pedestal of noninflammable material should
be built from the creeping space.
Ventilate the empty space in the chimney, by placing ventilation openings at the top and
bottom of the chimney breast.
The total ventilation openings should be at least 450 cm2 at the bottom of the chimney
breast and also at least 450 cm2 at the top of the chimney breast.
(Total ventilation openings: 900 cm2.)
Attention! :
18
Smaller ventilation openings than prescribed here may
cause damage to the chimney breast.
Always maintain the minimum dimensions of the
ventilation openings!
Installation instructions
UNILUX-6 45
The ventilation openings at
the top should be at least
50 cm below the ceiling
Ventilation openings
Figure 3: Use of ventilation of chimney
Examples installation possibilities.
A
Appliance as an insert-appliance in an existing chimney.
Legend page 20
Installation instructions
19
UNILUX-6 45
B
Appliance as an insert-appliance in an existing or a new chimney.
Fitted with ventilation of the chimney.
C
Appliance as a build-in appliance in an existing or a new chimney.
Fitted with ventilation of the chimney.
External combustion air supply through the back or underside of the appliance.
Legend page 20
20
Installation instructions
UNILUX-6 45
Appliance:
1
Inlet opening combustion air (front of appliance)
2
Inlet opening combustion air (bottom / rear of appliance, Ø80 mm)
with the aid of the air supply adapter (pre-mounted)
3
Flue connection (topside of appliance, Ø128 mm external)
4
Insulation material, noninflammable ‼! (for example ceramic fibre) (sides and top
of appliance)
Schouw/Schouwlichaam:
5
Inlet opening chimney-ventilation air (grate, bottom of chimney)
6
Outlet opening chimney-ventilation air (grate, top of chimney)
Buitenmuur:
7
Inlet opening combustion air (grate, exterior wall)
Installation instructions
21
UNILUX-6 45
3.3.2 Aeration / ventilation
Combustion air is needed to keep the combustion going by drawing in air from the
room, of directly from outside, due to the natural draught of the chimney.
On delivery, the appliance is prepared for a combustion air supply from the living room
or a combustion air supply directly from the outside, through the underside or through
the back of the appliance.
• Combustion air from the living-room:
The air inlet openings are located under the operating flap. When using the
appliance, please ensure there is a sufficient supply of fresh air: use a grate with a
minimum net opening in the outer wall of 50 cm2.
Make sure that the ventilation supply is open; this is particularly important with
today’s airtight dwellings.
If the dwelling has mechanical ventilation that creates under pressure in the room
where the appliance is located, it is necessary to fit a flue gas fan.
The type of flue gas fan is dependent on the capacity of the mechanical ventilation
system. Always consult your fitter about this.
In dwellings with an operating extractor hood, this should be turned to the lowest
setting or turned off altogether. If the extractor hood remains in use, additional
ventilation must be provided in compensation. This will not only avoid poor
combustion, but will also prevent flue gases being sucked from the appliance into
the room.
Should creating an extra ventilation opening prove insufficient, it is then necessary
to fit a flue gas fan.
• Combustion air directly from outside:
The appliance draws the required air from outside the room, which allows it to
operate independently of the surrounding air in the room where the appliance is
located.
The combustion air supply can be connected to the back or the underside of the
appliance. To do this, use combustion air connection Ø80 mm (exterior) for the back
or underside. Install a fixed or flexible pipe of Ø80 mm in the wall/floor between this
air supply connection and outside air supply inlet. We recommend that this pipe is
fitted with a sealing valve in order to prevent condensation in the appliance when it
is not in use.
22
Installation instructions
UNILUX-6 45
3.3.3 Fitting in an existing chimney
Do not use masking tape on the appliance when
installing and plastering.
Tape can damage the finish of the appliance.
• Remove the existing fire basket or stoking stones and remove the shut-off flap.
The chimney must be intact and must not be damaged during fitting.
The chimney breast opening must be big enough for a gap of 1 - 3 cm to be left all
round the appliance. Clad the chimney breast opening from the inside with a ceramic
wool fireblanket or similar (see section 3.3).
• Extend the existing chimney so that it ends at the appliance’s smoke outlet. To do
this, use a flexible, double-walled stainless steel chimney, for example.
• Slide the appliance into the chimney breast opening. Seal the smoke outlet where it
joins the chimney so that no soot can accumulate above the appliance under any
circumstances. See 3.3.4.
• Level off the appliance so that the cover does not catch on the base.
• Fill any gaps around the appliance with a ceramic insulation wool fireblanket and
position the frame (where supplied).
3.3.4 Fitting in a newly-built chimney
Do not use masking tape on the appliance when
installing and plastering.
Tape can damage the finish of the appliance.
• Clad the appliance on the top, sides and rear up to the front edge with an approx.
10 cm thick ceramic isolation wool fireblanket. Leave a few centimetres clearance
between the front of the chimney and the appliance.
• Level off the appliance.
• Make a good seal between the smoke outlet from the appliance to the chimney.
See also 3.3.5.
Ensure that the entire flue is gas-tight.
Installation instructions
23
UNILUX-6 45
• Ventilate the chimney, by placing ventilation openings at the top and bottom of the
chimney.
The total ventilation openings should be at least 450 cm2 at the bottom of the
chimney breast and also at least 450 cm2 at the top of the chimney breast.
(Total ventilation openings: 900 cm2.)
Attention! :
Smaller ventilation openings than prescribed here may
cause damage to the chimney breast.
Always maintain the minimum dimensions of the
ventilation openings!
• Close up the front.
Available BARBAS grids (option) for ventilating the chimney:
CLEAR OPENING (cm2)
COLOUR
DIMENSION (cm)
Brass or white
(incl. fitting)
13.5 x 13.5
75
Brass or white
(incl. fitting)
27.0 x 13.5
150
Convection air fan (white)
43.0 x 22.0
550
• During installation of the appliance, a clearance of 3 mm should be maintained on all
sides of the appliance to allow for expansion of the appliance during operation.
• If the appliance is to be placed against a bearing wall or against a wall containing
flammable material, an air gap of at least 20 mm should first be created.
Before it a false wall, 100 mm thick, must be built of masonry or aerated concrete.
• If the appliance is not placed against a bearing wall or a wall containing flammable
material, no false wall is necessary. Layers of insulation of at least 100-mm thickness
will then be sufficient (class A1, DIN 4102-compliant). See also section 3.3.
• After four weeks, your appliance will be ready for use.
24
Installation instructions
UNILUX-6 45
3.3.5 Connecting the smoke outlet
The appliance comes with a detachable smoke outlet connection, Ø130 mm (Ø128 mm
external). This connection is intended for steel pipes, double/single-skinned stainless
steel (insulated) flues or double/single-skinned flexible stainless steel flues.
After the appliance has been installed, it can be connected to the flue.
In order to be able to disassemble the smoke outlet connection, remove the baffle
plates first.
•
Disassembling the smoke outlet connection.
•
Pull the pipe of the appliance or the stainless steel (flexible) pipe downwards
through the appliance and secure it to the smoke outlet connection.
Fix with hose clamp (minimum 2 pieces per connection).
Installation instructions
25
UNILUX-6 45
• Push the smoke outlet connection back upwards and secure it in place.
• Replace the two baffle plates.
3.4
PREPARATION / FUNCTION CHECK
• Check the operation of the combustion air supply slider
• Check if the combustion air supply openings are open
26
Installation instructions
UNILUX-6 45
4
OPERATION
The appliance built into chimney
Figure 3: Operating
1
2
3
4
5
6
7
8
Handle
Ceramic heat-proof glass
Outlet opening (2x grate) (chimney breast) ventilation air chimney breast
Grate
Ashtray
Inlet opening (2x grate)(chimney breast) ventilation air chimney breast
Combustion air-supply slider (Combined operation for the primary, secondary and
tertiary combustion air-supply)
Inlet opening combustion air from Living-room, if there’s no direct outside air
supply. This is already decided during the installation of the appliance.
NEVER close off open air intakes.
Installation instructions
27
UNILUX-6 45
5
ANNUAL MAINTENANCE
It is essential that the appliance, the chimney and the
combustion air supply are cleaned and inspected
annually, by a Barbas-dealer/expert.
The safe operation of the appliance will thus remain
guaranteed.
Start with maintence 24 hours after the last burning period.
Recommended order for yearly maintenance:
•
Inside the appliance:
• Check the door seals. If necessary, replace the seals.
•
Temporarily remove the door, by opening it competely and lifting it upwards.
•
Remove the complete interior of the appliance and carefully clean all parts with
a hand brush.
Emptying the ashtray.
•
Clean the glass on the inside of the door with glass spray or ceramic hob
cleaner.
If the glass is broken or cracked, it must be immediately replaced before
operating the appliance again.
Broken ceramic heat-resistant glass
may not be thrown away in a glass
container, but must be included in
normal household waste.
•
•
Check the grate and all interior plates on cracks.
If necessary, replace the parts.
‚
Chimney/flue channel:
• Sweep and inspect chimney. Check for cracks, loose parts, flue gas leakage
and overall condition of the chimney.
When in doubt use an inspection camera !
ƒ
Combustion air supply appliance:
• Check the combustion air supply route from the outside up to the appliance.
• Clean the combustion air supply inlet openings.
28
Installation instructions
UNILUX-6 45
„
Outside appliance:
• Clean the outside of the appliance with a dry lint free cloth.
• Wait for the appliance to cool down sufficiently before cleaning. Never use
scouring powder, aggressive cleaners or fire polish on the appliance.
• Any lacquer damage can be repaired with a BARBAS heat resistant paint spray
can. (Pay atention that the appliance is sufficiently cooled down !)
…
Ventilation house:
• Check whether the room where the appliance is installed is sufficiently
ventilated according to national and local regulations and standards.
• Ensure that as little dust, and as few particles of cigarette smoke, candles and
oil lamps as possible pollute the air in the room in which the appliance is used.
Heating of these particles by the convection system of the appliance could lead
to discoloration of the walls and ceiling. It is therefore very important to ensure
that the room in which the appliance is located is sufficiently ventilated.
†
Last check appliance:
• In reversed order, place back all parts in the appliance.
• Place back the door on the appliance.
• Check the correct operation from the sliders and flaps. See Chapter 3.6:
Preparation / Function check.
‡
General:
• Parts:
Individual parts for replacement/accessories are available from your BARBAS
dealer. Use only original parts.
•
Modifications:
Introduced modifications to the appliance are not permitted.
Installation instructions
29
UNILUX-6 45
6
REPLACEMENT PARTS
Pos no
Article no
Description
1
340637
Baffle plate stainless steel
2
339977
Stone baffle plate
3
340264
Stone side left
4
343281
Stone rear
5
340378
Bottom
6
340377
Combustion grate
7
340263
Stone side right
8
340379
Wood rack
9
344169
Ceramic glass
When ordering, please give the serial number.
30
Installation instructions
UNILUX-6 45
6.1
SEQUENCE FOR REPLACING THE INTERIOR OF THE APPLIANCE
• Remove the grate and the ashtray.
Although the heat resistant panels have been manufactured with the
greatest care, there is the possibility that some sharp parts may stick
out, possibly causing injuries. We therefore urgently recommend
wearing safety gloves when handling the panels.
• Remove the rear bottom plate.
Installation instructions
31
UNILUX-6 45
• Unscrew the locking pin with the aid of an Allen key and a wrench. You can now
remove the top baffle plate by pulling it forward slightly and then tipping it downwards
The baffle plate can now be pulled forwards and out.
• Remove the bottom baffle plate by lifting it slightly and removing it sloping to
one side.
32
Installation instructions
UNILUX-6 45
• Remove carefully the left-hand side panel.
• Remove carefully the right-hand side panel.
• Remove carefully the rear panel, by lifting it upwards and remove it diagonally
forward.
Installation instructions
33
UNILUX-6 45
• Finally, remove the wood rack.
The entire interior is now disassembled.
The interior is reassembled in the reverse order.
Make sure, when reassembling the interior to start with the wood rack.
34
Installation instructions
UNILUX-6 45
7
DIMENSIONS
7.1
•
without frame
Installation instructions
35
UNILUX-6 45
7.2
36
•
with built-in frame
Installation instructions
UNILUX-6 45
7.3
•
with classic frame
Installation instructions
37
UNILUX-6 45
7.4
38
•
45° - with classic frame
Installation instructions
UNILUX-6 45
7.5
•
with deepened frame
Installation instructions
39
UNILUX-6 45
8
TECHNICAL DATA
Combustion:
Measured in compliance with
EN 13229 : 2001 and EN 13229 - A2 : 2004
Fuel
Nominal output
Efficiency
Wood
6 kW
76%
Emissions (dry, at 13% O2, 273 K, 1013 hPa):
Carbon monoxide (CO)
0.09%; 1171 mg/m3
Dust
20 mg/Nm3
Total hydrocarbons (CxHy)
110 mg/m3
Nitrogen oxides (NOx)
104 mg/m3
Flue gas mass flow
Flue temperature
Chimney draught
Flue gas connection
Weight
6.3 g/s
302°C
0.12 mbar
Ø122 mm (Ø128 mm ext.)
87 kg
Inside:
Interior side panels
Interior bottom
Inner lining
Bottom baffle plate
Top baffle plate
Heat-resistant panels 1400 kg/m3, 1300°C
Steel (heat-resistant and rust-proof)
Steel (heat-resistant and rust-proof)
Heat-resistant panel 2000 kg/m3, 1300°C
Stainless steel
Outside:
Construction
Doors
Sheet-steel casing.
Flat door opening to left.
Shutter with fixed handle.
Operation:
• Handle for opening the door.
• Combustion air supply slider
Single combined slide for controlling the
primary, secondary and tertiary air supply.
Ash collection:
Ashtray with grate.
Combustion air supply:
At least 50 cm2 opening in the room where the
fire is located or a outside air supply opening of
Ø80 mm in wall/floor.
40
Installation instructions
UNILUX-6 45
9
WARRANTY TERMS
Barbas Bellfires
Warranty terms
Barbas Bellfires B.V. guarantees the quality of the supplied Barbas appliance and the
quality of the materials used. All Barbas appliances are developed and manufactured
according to the highest possible quality standards. If, despite all this, something should
prove amiss with the Barbas appliance you have purchased, Barbas Bellfires B.V. offers
the following manufacturer’s warranty.
Article 1: Warranty
1.1. If Barbas Bellfires B.V. determines that the Barbas appliance you have purchased
is defective as a result of a flaw in the construction or material, Barbas Bellfires B.V.
guarantees to repair or replace the appliance free of charge, without charging any
costs for labour or spare parts.
1.2. Repair or replacement of the Barbas appliance will be undertaken by Barbas
Bellfires B.V. or by a Barbas dealer as designated by Barbas Bellfires B.V.
1.3. This warranty is supplementary to the existing legal national warranty of Barbas
dealers and Barbas Bellfires B.V. in the country of purchase and is not intended to
restrict your rights and claims based on the applicable legal provisions.
Article 2: Warranty conditions
2.1. Should you wish to claim under the warranty, please contact your Barbas dealer.
2.2. Complaints should be reported as quickly as possible after they have manifested
themselves.
2.3. Complaints will only be accepted if they are reported to the Barbas dealer,
together with the serial number of the Barbas appliance which is stated on the front
of the instructions for use.
2.4. In addition, the original receipt (invoice, receipt, cash receipt) showing the date of
purchase must also be submitted.
2.5. Repairs and replacements during the warranty period do not give any entitlement
to an extension of the warranty period. After a repair or replacement of warranty
parts, the warranty period shall be deemed to have started on the date of
purchasing the Barbas appliance.
2.6. If a certain part is eligible for the warranty and the original part is no longer
available, Barbas Bellfires B.V. shall ensure that an alternative part of at least the
same quality shall be provided.
Article 3: Warranty exclusions
3.1. The warranty on the Barbas appliance ceases to be in effect if:
a. it is not installed according to the supplied installation instructions, and to
national and/or local regulations;
b. it has been installed, connected or repaired by a non-Barbas dealer;
Installation instructions
41
UNILUX-6 45
c.
d.
e.
3.2.
it has not be used or maintained according to the instructions for use;
it has been changed, neglected or roughly treated;
it has been damaged as a result of external causes (outside the appliance
itself), for example, lightning strike, water damage or fire;
In addition, the warranty lapses if the original purchase receipt shows any
change, deletion, removal or if it is illegible.
Article 4: Warranty area
4.1. The warranty is only valid in those countries where Barbas appliances are sold
through an official dealer network.
Article 5: Warranty period
5.1. This warranty will only be granted during the warranty period.
5.2. The body of the Barbas appliance is guaranteed for a period of 10 years against
construction and/or material faults, starting from the moment of purchase.
5.3. For other parts of the Barbas appliance, a similar warranty applies from the moment
of purchase for a period of one year.
5.4. For user parts such as glass, glass (cord), thermocouple and the interior of the
combustion chamber, a similar guarantee is given until after the first burning.
Article 6: Liability
6.1. A claim granted by Barbas Bellfires B.V. under this warranty does not automatically
imply that Barbas Bellfires B.V. also accepts liability for any possible damage.
The liability of Barbas Bellfires B.V. never extends further than that stated in these
warranty conditions. Any liability of Barbas Bellfires B.V. for consequential damage
is expressly excluded.
6.2. That stated in this provision is not valid if and to the extent that is derives from
a mandatory provision.
6.3. All agreements entered into by Barbas Bellfires B.V. are, unless specifically
stated otherwise in writing and to the extent that they are permitted based on
applicable law, subject to the FME-CWM general sales and delivery conditions
for the technology industry.
Barbas Bellfires B.V.
Hallenstraat 17
5531 AB Bladel
The Netherlands
Tel: +31-497339200
Email: [email protected]
Carefully retain the instructions for use; they show the serial number of the appliance.
You will need this if you wish to claim under the warranty.
42
Installation instructions
Your Barbas dealer
04 - 170619 - 344230

advertisement

Key Features

  • Wood-burning insert appliance
  • Smoke control area compliant
  • Factory-installed modified air slider
  • Detailed installation instructions
  • Annual maintenance guide
  • Replacement parts list
  • Technical data

Frequently Answers and Questions

What type of fuel can I use in the Unilux-6 45?
This appliance is designed for burning wood and wood briquettes. Do not use coal, liquid fuels, or fuel gel.
How often should I clean and inspect my Unilux-6 45?
It is essential to clean and inspect the appliance, chimney, and combustion air supply annually by a Barbas dealer/expert.
What is the minimum distance required between the appliance and combustible materials?
The minimum distance required is 100 mm for the rear, sides, and ceiling, and 800 mm for the front. See the Declaration of Performance for specific details.