Biamp | 301E | Electrical Inspection Asset Data Priority Condition Inspection

NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
School:
P.S. 19 - STATEN ISLAND, 780 POST AVENUE, STATEN ISLAND, NY, 10310
InspectionId
Inspection Type
804 ELECTRICAL
Time In
Last Edited
2013-12-23 09:05AM
2013-12-26 11:54AM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Public Address System (Amplifier Only), Partial Motor
Starters, Library Lighting Retrofit, Toilet Rooms
Lighting Retrofit, Interior Fluorescent Lighting
1998
Smart Boards
Years:
Systems:
Years:
Systems:
Years:
Systems:
2010
Battery Pack Emergency Lighting, Battery Pack Exit
Lighting, Emergency Light/Exit Light Panel
2003
LAN
Years:
Systems:
2009
Security Lights
Years:
Systems:
Years:
Systems:
1998, 2006, 2009
Partial Molded Case Circuit Breakers Type Panel
Boards
1998, 2008
Intrusion Alarm System
Years:
Systems:
2004
IPDVS/CCTV System, Telephone System
Years:
2012
Below Ground
Type of Service
DEDICATED INTERCOMS IN FIRE RESCUE AREAS
Question
Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms
in your building?
Response
No
Priority Condition
No condition recorded
Inspection
Question
Response
ELECTRICAL
ATHLETIC FIELD
Does not exist
AUDITORIUM
Inspected
Instance
1st Floor
HOUSE LIGHTING
Inspected
No
Instance on 1st Floor
Does a Chandelier Exist?
Lighting Fixture - Fluorescent
Inspected
Instance on 1st Floor
Pendant Mounted
Does not exist
Instance on 1st Floor
Recessed Mounted
Does not exist
Instance on 1st Floor
Surface Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Instance on 1st Floor
Lighting Fixture - Incandescent
Inspected
Instance on 1st Floor
Mobile Validity Version 2.0 (P)
Page 1 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
AUDITORIUM
HOUSE LIGHTING
Lighting Fixture - Incandescent
Pendant Mounted
Does not exist
Instance on 1st Floor
Recessed Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BEYOND USEFUL LIFE
25
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Surface Mounted
Does not exist
Instance on 1st Floor
LOCAL SOUND SYSTEM
Instance on 1st Floor
Inspected
Instance Condition
5- Poor
Deficiency
Deficiency Quantity
AMPLIFIER NOT OPERATIONAL
1
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
PROJECTION SYSTEM
Does not exist
Instance on 1st Floor
THEATER LIGHTING SYSTEM
Inspected
Instance on 1st Floor
Dimming System
Does not exist
Instance on 1st Floor
Theater Lighting
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BEYOND USEFUL LIFE
23
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Quantity
LIGHTING FIXTURE NOT OPERATIONAL
2
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
AUXILIARY SIGNAL/BELL SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
CAFETERIA
Instance
Mobile Validity Version 2.0 (P)
1st Floor
Page 2 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
CAFETERIA
LIGHTING
Inspected
Instance on 1st Floor
Lighting Fixture - Fluorescent
Inspected
Instance on 1st Floor
Pendant Mounted
Does not exist
Instance on 1st Floor
Recessed Mounted
Does not exist
Instance on 1st Floor
Surface Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Instance on 1st Floor
Lighting Fixture - Incandescent
Does not exist
Instance on 1st Floor
LOCAL SOUND SYSTEM
Instance on 1st Floor
Inspected
Instance Condition
5- Poor
Deficiency
Deficiency Quantity
AMPLIFIER NOT OPERATIONAL
1
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Projection System
Does not exist
Instance on 1st Floor
Inspected
CITY FIRE ALARM SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE
Inspected
LIGHTING
Does a Chandelier Exist?
No
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
3- Fair
Condition
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BALLAST DEFECTIVE
5
EACH
REPLACE BALLAST
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Quantity
LIGHTING FIXTURE LAMP NOT OPERATIONAL/MISSING
2
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Recessed Mounted
Does not exist
Surface Mounted
Does not exist
Does not exist
Lighting Fixture - HID
Mobile Validity Version 2.0 (P)
Page 3 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE
LIGHTING
Does not exist
Lighting Fixture - Incandescent
Inspected
SMART BOARD
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
COMPUTER LAB
Instance
Room 123
Has LAN/Modem access
Yes
Power Panel?
Yes
LIGHTING
Inspected
Instance on Room 123
Lighting Fixture - Fluorescent
Inspected
Instance on Room 123
Pendant Mounted
Instance on Room 123
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Instance on Room 123
Surface Mounted
Does not exist
Instance on Room 123
Lighting Fixture - HID
Does not exist
Instance on Room 123
Lighting Fixture - Incandescent
Does not exist
Instance on Room 123
RACEWAY WITH RECEPTACLES
Instance on Room 123
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
EMERGENCY DC STANDBY BATTERY POWER
Does not exist
EMERGENCY GENERATOR SET
Does not exist
EMERGENCY LIGHT/EXIT LIGHT PANEL
Inspected
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD COVER IS MISSING
Electrical Room
1
EACH
MAINTENANCE
PRIORITY 5
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
EMERGENCY LIGHTING
Inspected
BATTERY PACK
3- Fair
Condition
Deficiency
Deficiency Location/Instance
BATTERY NOT OPERATIONAL
Cafeteria, Gymnasium, 1st Floor Corridor near Auditorium, 3rd
Floor Corridor near Room 352
4
EACH
REPLACE BATTERY
PRIORITY 5
LEVEL 2
No violations recorded
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Mobile Validity Version 2.0 (P)
Page 4 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
EMERGENCY LIGHTING
Inspected
Non Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
EXIT LIGHT
Inspected
BATTERY PACK
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Non Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
EXIT/EMERGENCY LIGHT
Does not exist
FIRE ALARM SYSTEM
Inspected
AREA SMOKE DETECTOR
Does not exist
BELL/HORN
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
DUCT SMOKE DETECTOR
Does not exist
ELEVATOR RECALL
Does not exist
FAN SHUTDOWN CONTROL
Does not exist
FIRE ALARM DIGITAL COMMUNICATOR
Does not exist
FUSED CUTOUT PANEL
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
HEAT DETECTOR
Does not exist
MAGNETIC DOOR HOLDER CONTACTOR
Does not exist
MAIN PANEL
Inspected
Bell At Panel
Inspected
Condition
3- Fair
Deficiency
No deficiencies recorded
Fire Alarm Control Panel (Electronic)
Does not exist
Fire Alarm Control Panel (Standard)
Inspected
Instance
Boiler Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
ACME
N/A
4
Circuits
Inspector Estimate
1943
Documented
Deficiency
Deficiency Quantity
PANEL BEYOND USEFUL LIFE
66,000
S.F.
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Quantity
PANEL ID IS MISSING
1
EACH
MAINTENANCE
Quantity Uom
Potential Action
Mobile Validity Version 2.0 (P)
Page 5 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
FIRE ALARM SYSTEM
MAIN PANEL
Fire Alarm Control Panel (Standard)
Urgency of Action
Purpose of Action
Violations
PRIORITY 2
LEVEL 2
No violations recorded
Inspected
MANUAL PULL STATION
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
REMOTE ANNUNCIATOR
Display Monitor
Does not exist
Panel
Inspected
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Printer
Does not exist
Punch Register
Does not exist
SPRINKLER FLOW/AIR PRESSURE SWITCH
Does not exist
STROBE
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
SUB-PANEL
Does not exist
TAMPER FLOW SWITCH/CHAIN
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
GROUNDING SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
GYMNASIUM
Instance
3rd Floor
LIGHTING
Inspected
Instance on 3rd Floor
Lighting Fixture - Fluorescent
Does not exist
Instance on 3rd Floor
Lighting Fixture - HID
Inspected
Instance on 3rd Floor
Pendant Mounted
Does not exist
Instance on 3rd Floor
Recessed Mounted
Instance on 3rd Floor
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BEYOND USEFUL LIFE
19
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BALLAST DEFECTIVE
5
EACH
REPLACE BALLAST
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Mobile Validity Version 2.0 (P)
Page 6 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
GYMNASIUM
LIGHTING
Lighting Fixture - HID
Surface Mounted
Does not exist
Instance on 3rd Floor
Lighting Fixture - Incandescent
Inspected
Instance on 3rd Floor
Pendant Mounted
Does not exist
Instance on 3rd Floor
Recessed Mounted
Instance on 3rd Floor
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BEYOND USEFUL LIFE
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Surface Mounted
Does not exist
Instance on 3rd Floor
LOCAL SOUND SYSTEM
Instance on 3rd Floor
Inspected
Instance Condition
5- Poor
Deficiency
Deficiency Quantity
AMPLIFIER NOT OPERATIONAL
1
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
SCOREBOARD
Does not exist
Instance on 3rd Floor
THEATER LIGHTING SYSTEM
Does not exist
Instance on 3rd Floor
INTERCOM SYSTEM
Does not exist
KITCHEN/WARMING PANTRY
Inspected
Instance
1st Floor
LIGHTING
Inspected
Instance on 1st Floor
Lighting Fixture - Fluorescent
Inspected
Instance on 1st Floor
Pendant Mounted
Does not exist
Instance on 1st Floor
Recessed Mounted
Instance on 1st Floor
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Surface Mounted
Does not exist
Instance on 1st Floor
Lighting Fixture - HID
Does not exist
Instance on 1st Floor
Lighting Fixture - Incandescent
Does not exist
Instance on 1st Floor
Mobile Validity Version 2.0 (P)
Page 7 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
LAN
Inspected
Inspected
LOCAL DISTRIBUTION FRAME (I/LDF)
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
MAIN EQUIPMENT RACK (MDF)
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
LIBRARY
Instance
Room 215
Has LAN/Modem access
Yes
LIGHTING
Inspected
Instance on Room 215
Lighting Fixture - Fluorescent
Inspected
Instance on Room 215
Pendant Mounted
Does not exist
Instance on Room 215
Recessed Mounted
Does not exist
Instance on Room 215
Surface Mounted
Instance on Room 215
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Quantity
LIGHTING FIXTURE BALLAST DEFECTIVE
1
EACH
REPLACE BALLAST
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Quantity
LIGHTING FIXTURE LAMP NOT OPERATIONAL/MISSING
2
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Lighting Fixture - HID
Does not exist
Instance on Room 215
Lighting Fixture - Incandescent
Does not exist
Instance on Room 215
Projection System
Does not exist
Instance on Room 215
RACEWAY WITH RECEPTACLES
Does not exist
Instance on Room 215
SMART BOARD
Instance on Room 215
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
LIGHTING - SECURITY LIGHTS
2- Between Good and Fair
Condition
Replacement Quantity
18
EACH
Replacement Uom
Deficiency
Deficiency Location/Instance
Deficiency Quantity
Mobile Validity Version 2.0 (P)
LIGHTING FIXTURE NOT OPERATIONAL
Roof
1
Page 8 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
LIGHTING - SECURITY LIGHTS
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
EACH
REPLACE
PRIORITY 4
LEVEL 3
No violations recorded
Deficiency
Deficiency Location/Instance
Deficiency Quantity
LIGHTING FIXTURE NOT OPERATIONAL
Exit 2
1
EACH
REPAIR
PRIORITY 4
LEVEL 3
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
LIGHTING FIXTURE PHOTOCELL NOT OPERATIONAL
East side of the building
1
EACH
REPLACE
PRIORITY 4
LEVEL 3
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
LIGHTNING PROTECTION
Does not exist
LOCKER ROOM
Does not exist
MOTOR CONTROL CENTER
Does not exist
MOTOR STARTER/CONTACTOR
Inspected
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
MOTOR STARTER BEYOND USEFUL LIFE
Fan Rooms, Boiler Room
12
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
MULTIPURPOSE ROOM
Does not exist
PANEL BOARD
Inspected
FUSED DISCONNECT SWITCH TYPE
Does not exist
FUSED KNIFE SWITCH TYPE
Inspected
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Fan Rooms, Boiler Room, Corridors near Rooms 207 and 307
5
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
FUSED TOGGLE SWITCH TYPE
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Electrical Room
1
EACH
REPLACE-UPGRADE
Quantity Uom
Potential Action
Mobile Validity Version 2.0 (P)
Page 9 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
PANEL BOARD
FUSED TOGGLE SWITCH TYPE
Urgency of Action
Purpose of Action
Violations
PRIORITY 1
LEVEL 2
No violations recorded
Inspected
MOLDED CASE CIRCUIT BREAKER TYPE
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Cafeteria, Kitchen, Corridors and Boiler Room
11
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD COVER IS MISSING
Boiler Room
1
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
PUBLIC ADDRESS SYSTEM
Instance
Room 203
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Model
Biamp Advantage 301e
Deficiency
Deficiency Location/Instance
Deficiency Quantity
SYSTEM BEYOND USEFUL LIFE
Room 203
66,000
S.F.
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
SPEAKER NOT OPERATIONAL
Rooms 125, 215, 303, 305 and 309
5
EACH
REPLACE
PRIORITY 5
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CLOCK NOT OPERATIONAL
Corridors and Classrooms
11
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
SCIENCE DEMO ROOM
Does not exist
SCIENCE LAB
Does not exist
Mobile Validity Version 2.0 (P)
Page 10 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
SCIENCE PREP ROOM
Does not exist
SECURITY
Inspected
Inspected
INTRUSION ALARM
Central Control Panel
Inspected
Instance
Room 101
5- Poor
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Model
Vista-128B
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL NOT OPERATIONAL
Room 101
1
EACH
REPAIR
PRIORITY 4
LEVEL 3
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Infrared Sensor
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Panic Switch
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Remote Annunciator
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Siren/Strobe
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
Ultrasonic Sensor
Inspected
IPDVS/CCTV SYSTEM
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
SERVICE SWITCH
Instance
Electrical Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Federal Pacific Electric
LIGHT. MAIN. SW. 800 A.
800
Amps
Nameplate
1972
Documented
Deficiency
Deficiency Quantity
SWITCH BEYOND USEFUL LIFE
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Instance
Electrical Room
3- Fair
Instance Condition
Mobile Validity Version 2.0 (P)
Page 11 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
SERVICE SWITCH
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Standard Switchboard
POWER 800 AMP MAIN SWITCH
800
Amps
Nameplate
1954
Documented
Deficiency
Deficiency Quantity
SWITCH BEYOND USEFUL LIFE
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Instance
Electrical Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Murray Electrical Products
T.C.U 1,2
200
Amps
Nameplate
2005
Documented
Deficiency
No deficiencies recorded
Instance
Electrical Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Murray Electrical Products
T.C.U 3,4
200
Amps
Nameplate
2005
Documented
Deficiency
No deficiencies recorded
SWIMMING POOL
Does not exist
SWITCHBOARD
Water Penetration In Electrical Room?
Number of Spares
Inspected
AIR CIRCUIT BREAKER TYPE
No
0
Does not exist
FUSED DISCONNECT SWITCH TYPE
Inspected
Instance
Electrical Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Metropolitan Electric
LT. DIST.
1400
Amps Total
1
Mobile Validity Version 2.0 (P)
Page 12 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
SWITCHBOARD
FUSED DISCONNECT SWITCH TYPE
Capacity/Size 2 UOM
Source of Capacity/Size
Section(s)
Nameplate
1972
Documented
Installation Year
Source of Installation Year
Deficiency
Deficiency Quantity
SWITCHBOARD BEYOND USEFUL LIFE
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Instance
Electrical Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Metropolitan Electric
POWER DIST.
1000
Amps Total
2
Section(s)
Nameplate
1972
Documented
Deficiency
Deficiency Quantity
SWITCHBOARD BEYOND USEFUL LIFE
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
FUSED KNIFE SWITCH TYPE
Does not exist
MOLDED CASE CIRCUIT BREAKER TYPE
Does not exist
Inspected
TELEPHONE
Inspected
PBX/INTERCOM
1- Good
Condition
Deficiency
No deficiencies recorded
STANDARD
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
TOILET ROOM - STAFF
Inspected
LIGHTING
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
3- Fair
Condition
Deficiency
No deficiencies recorded
Recessed Mounted
Does not exist
Surface Mounted
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Lighting Fixture - HID
Does not exist
Lighting Fixture - Incandescent
Does not exist
Inspected
TOILET ROOM - STUDENT
Mobile Validity Version 2.0 (P)
Page 13 of 14
Print Date: 6/20/2014
NYC Department of Education
Building Condition Assessment Survey 2013-2014
Electrical Inspection
R019
Question
Response
TOILET ROOM - STUDENT
Inspected
LIGHTING
Inspected
Lighting Fixture - Fluorescent
Inspected
Pendant Mounted
3- Fair
Condition
Deficiency
Deficiency Quantity
LIGHTING FIXTURE LAMP NOT OPERATIONAL/MISSING
2
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Recessed Mounted
Does not exist
Surface Mounted
Inspected
3- Fair
Condition
Deficiency
Deficiency Quantity
LIGHTING FIXTURE LAMP NOT OPERATIONAL/MISSING
1
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Lighting Fixture - HID
Does not exist
Lighting Fixture - Incandescent
Does not exist
TRANSFORMER
Does not exist
TV SYSTEM
Cable System Exist?
Master Antenna System Exist?
Operational?
Inspected
No
Yes
No
Inspected
MAIN EQUIPMENT RACK
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
SYSTEM NOT IN USE
Gymnasium Fan Room
1
EACH
NO ACTION
PRIORITY 1
LEVEL 1
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Mobile Validity Version 2.0 (P)
Page 14 of 14
Print Date: 6/20/2014