Tyco TY-FRB Series, TY2231, TY3231, TY4131, TY4231, TY4831 Manual

Tyco TY-FRB Series, TY2231, TY3231, TY4131, TY4231, TY4831 Manual

Add to My manuals
12 Pages

Tyco TY-FRB Series are quick response, standard coverage, decorative sprinkler heads ideal for light or ordinary hazard commercial occupancies like banks, hotels, and shopping malls. They are designed for use in areas with finished ceilings and offer both pendent and upright configurations for flexibility in installation.

advertisement

Tyco TY-FRB Series Sprinkler Manual -  Quick Response & Standard Coverage | Manualzz
Worldwide
www.tyco-fire.com
Contacts
Series TY-FRB – 2.8, 4.2, 5.6, and 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp171
General
Description
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers
described in herein are quick response,
standard coverage, decorative 3 mm
glass bulb-type spray sprinklers. They
are designed for use in light or ordinary
hazard, commercial occupancies such
as banks, hotels, and shopping malls.
The sprinkler, where applicable, is
intended for use in areas with a finished
Page 1 of 12
ceiling. This recessed pendent sprinkler uses one of the following recessed
escutcheons:
• Two-piece Style 10 (1/2 in. NPT)
or Style 40 (3/4 in. NPT) Recessed
Escutcheon with 1/2 in. (12,7 mm) of
recessed adjustment or up to 3/4 in.
(19,1 mm) of total adjustment from
the flush pendent position.
• Two-piece Style 20 (1/2 in. NPT)
or Style 30 (3/4 in. NPT) Recessed
Escutcheon with 1/4 in. (6,4 mm) of
recessed adjustment or up to 1/2 in.
(12,7 mm) of total adjustment from
the flush pendent position.
The adjustment provided by the
recessed escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
what would be obtained when exposed
to corrosive atmospheres. Although
corrosion-resistant coated sprinklers
have passed the standard corrosion
tests of the applicable approval agencies, the testing is not representative
of all possible corrosive atmospheres.
Consequently, it is recommended that
the end user be consulted with respect
to the suitability of these coatings for
any given corrosive environment. The
effects of ambient temperature, concentration of chemicals, and gas/
chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which
the sprinklers will be exposed.
An intermediate level version of the
Series TY-FRB Pendent Sprinklers
is detailed in technical data sheet
TFP356. Sprinkler guards are detailed
in technical data sheet TFP780.
NOTICE
The Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards of the National Fire Protection Association (NFPA), in addition to
DECEMBER 2022
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
NFPA 13 prohibits installation of 1/2 in.
NPT sprinklers with K-factors greater
than 5.6 in new construction. They are
intended for retrofit in existing sprinkler
systems only.
Sprinkler
Identification
Number (SIN)
TY1131 . . . Upright 2.8K, 1/2 in. NPT
TY1231 . . Pendent 2.8K, 1/2 in. NPT
TY2131 . . . Upright 4.2K, 1/2 in. NPT
TY2231 . . Pendent 4.2K, 1/2 in. NPT
TY3131 . . . Upright 5.6K, 1/2 in. NPT
TY3231 . . Pendent 5.6K, 1/2 in. NPT
TY4131 . . . Upright 8.0K, 3/4 in. NPT
TY4231 . . Pendent 8.0K, 3/4 in. NPT
TY4831 . . . Upright 8.0K, 1/2 in. NPT
TY4931 . . Pendent 8.0K, 1/2 in. NPT
TFP171
TFP171
Page 2 of 12
* Temperature rating
** Pipe thread connections per
is indicated on
Deflector.
ISO 7-1 can be provided on
special request.
ESCUTCHEON
PLATE SEATING
SURFACE
1 - Frame
2 - Button
3 - Sealing
5 - Compression
Assembly
Screw
4 - Bulb
6 - Deflector *
7 - Bushing
7
1
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
3
2-1/4"
(57,2 mm)
2
4
1-9/16"
(39,7 mm)
5
6*
1/2" NPT **
WRENCH
FLATS
UPRIGHT
PENDENT
STYLE 10 or 20
RECESSED
ESCUTCHEON
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 IN. NPT
* Temperature rating
** Pipe thread connections per
is indicated on
Deflector.
ISO 7-1 can be provided on
special request.
5 - Compression
3 - Sealing
Assembly
Screw
4 - Bulb
6 - Deflector *
1
2
2-3/16"
(55,6 mm)
4
1-1/2"
(38,1 mm)
WRENCH
FLATS
UPRIGHT
1 - Frame
2 - Button
3
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
1/2" NPT **
ESCUTCHEON
PLATE SEATING
SURFACE
PENDENT
STYLE 10 or 20
RECESSED
ESCUTCHEON
5
6*
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 IN. NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and NYC Approved
EAC Approved
Note: For complete approval information,
including corrosion-resistant status, see
Tables A, B, C and D.
Maximum Working Pressure
See Table E
Discharge Coefficient
K=2.8 gpm/psi½ (40,3 Lpm/bar½)
K=4.2 gpm/psi½ (60,5 Lpm/bar½)
K=5.6 gpm/psi½ (80,6 Lpm/bar½)
K=8.0 gpm/psi½ (115,2 Lpm/bar½)
Temperature Rating
See Tables A and B
Finishes
Sprinkler: See Table D
Recessed Escutcheon: Signal or Pure White,
Grey Aluminum, Jet Black, Chrome Plated,
or Natural Brass
Physical Characteristics
Frame �������������������������������������������������������Bronze
Button������������������������������������������� Brass/Copper
Sealing Assembly. . Beryllium Nickel w/TEFLON
Bulb������������������������������������������������������������� Glass
Compression Screw���������������������������������Bronze
Deflector������������������������������������� Copper/Bronze
Bushing (K=2.8)�����������������������������������������Bronze
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers are
intended for fire protection systems
designed in accordance with the standard installation rules recognized by
the applicable Listing or Approval
agency, such as UL Listing based on
the requirements of NFPA 13 and FM
Approval based on the requirements
of the FM Global Loss Prevention Data
Sheets. Use only the style 10, 20, 30,
or 40 recessed escutcheon, as applicable, for recessed pendent installations.
TFP171
Page 3 of 12
* Temperature rating
** Pipe thread connections per
is indicated on
Deflector.
ISO 7-1 can be provided on
special request.
1
2
2-3/16"
(55,6 mm)
2-3/16"
(55,6 mm)
WRENCH
FLATS
UPRIGHT
5 - Compression
3 - Sealing
Assembly
Screw
4 - Bulb
6 - Deflector *
3
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
1/2" NPT**
ESCUTCHEON
PLATE SEATING
SURFACE
1 - Frame
2 - Button
4
1-1/2"
(38,1 mm)
5
STYLE 10 or 20
RECESSED
ESCUTCHEON
PENDENT
6*
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 IN. NPT
* Temperature rating
** Pipe thread connections per
is indicated on
Deflector.
ESCUTCHEON
PLATE SEATING
SURFACE
ISO 7-1 can be provided on
special request.
1 - Frame
2 - Button
3 - Sealing
5 - Compression
Assembly
Screw
4 - Bulb
6 - Deflector *
1
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
3
2-5/16"
(58,7 mm)
2-1/4"
(57,2 mm)
3/4" NPT **
WRENCH
FLATS
UPRIGHT
2
4
1-9/16"
(39,7 mm)
PENDENT
5
STYLE 30 or 40
RECESSED
ESCUTCHEON
6*
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
CROSS SECTION
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 IN. NPT
CEILING PLATE
SEATING SURFACE
1
3
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
1/2" NPT **
UPRIGHT
2-1/4"
(57,2 mm)
2
4
1-9/16"
(39,7 mm)
5
6 *
WRENCH
FLATS
PENDENT
1 - Frame
2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *
* Temperature rating is
indicated on Deflector.
** Pipe thread connections
per ISO 7-1 can be
provided on special
request.
CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 IN. NPT
TFP171
Page 4 of 12
Installation
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings. A leak-tight
1/2 in. NPT sprinkler joint should
be obtained by applying a minimum-to-maximum torque of 7 ft-lb
to 14 ft-lb (9,5 N·m to 19,0 N·m). A
leak tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 ft-lb to 20 ft-lb (13,4 N·m to
26,8 N·m). Higher levels of torque can
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler. Do not attempt to compensate for
insufficient adjustment in the escutcheon plate by under or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Series TY-FRB Recessed Pendent
Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accordance with the following instructions:
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Step 1. After installing the Style 10, 20,
30, or 40 Mounting Plate, as applicable, over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Care must be taken to avoid damage
to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. For more information, see
Installation section.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench as shown
in Figure 15. Apply the sprinkler wrench
to the sprinkler wrench flats as shown
in Figure 1 to 4.
Step 3. After the ceiling is installed
or the finish coat is applied, slide on
the Style 10, 20, 30, or 40 closure over
the Series TY-FRB Recessed Pendent
Sprinkler and push the closure over the
mounting plate until its flange comes in
contact with the ceiling.
Care and
Maintenance
Step 1. Install pendent sprinklers in the
pendent position. Install upright sprinklers in the upright position.
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section. Before closing a fire
protection system main control valve
for maintenance work on the fire protection system that it controls, obtain
permission to shut down the affected
fire protection systems from the proper
authorities and notify all personnel who
may be affected by this action.
Step 2. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench as shown in
Figure 14. Apply the sprinkler wrench
to the sprinkler wrench flats as shown
in Figure 1 to Figure 5.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Series TY-FRB Upright and Pendent
Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more information, see Installation section.
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections according to NFPA
25 should suffice. Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from
the floor level per NFPA. Inspection at
close range can better determine the
exact sprinkler condition and the longterm integrity of the corrosion-resistant
material, which can be affected by the
corrosive conditions present.
TFP171
Page 5 of 12
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1/8"
(3,2 mm)
MOUNTING
SURFACE
MOUNTING
SURFACE
CLOSURE
1/2" (12,7 mm)
SERIES
TY-FRB
1-5/16" (33,3 mm)
13/16" (20,6 mm)
CLOSURE
SERIES
TY-FRB
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 IN. NPT
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 IN. NPT
2-7/8" DIA.
(73,0 mm)
2-7/8" DIA.
(73,0 mm)
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1/8"
(3,2 mm)
MOUNTING
SURFACE
MOUNTING
SURFACE
CLOSURE
1/2" (12,7 mm)
SERIES
TY-FRB
1-1/4" (31,8 mm)
3/4" (19,1 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 IN. NPT
CLOSURE
SERIES
TY-FRB
1-1/4" (31,8 mm)
1" (25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 IN. NPT
TFP171
Page 6 of 12
2-7/8" DIA.
(73,0 mm)
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
3/4" (19,1 mm)
1/4" (6,4 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
1/2" (12,7 mm)
1/4" (6,4 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1/8"
(3,2 mm)
MOUNTING
SURFACE
MOUNTING
SURFACE
CLOSURE
1-1/4" (31,8 mm)
SERIES
TY-FRB
3/4" (19,1 mm)
CLOSURE
SERIES
TY-FRB
1-1/4" (31,8 mm)
1" (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN. NPT
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN. NPT
2-7/8" DIA.
(73,0 mm)
2-7/8" DIA.
(73,0 mm)
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
3/4" (19,1 mm)
1/4" (6,4 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
FACE OF
SPRINKLER
FITTING
1/2" (12,7 mm)
1/4" (6,4 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
MOUNTING
SURFACE
MOUNTING
SURFACE
CLOSURE
1/2±1/8"
(12,7±3,2 mm)
1-5/16" (33,3 mm)
SERIES
TY-FRB
13/16" (20,6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 IN. NPT
CLOSURE
SERIES
TY-FRB
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 IN. NPT
WRENCH
RECESS
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFP171
Page 7 of 12
K-Factor
Type
Pendent
(TY1231)
Upright
(TY1131)
2.8
1/2 in. NPT
Recessed
Pendent
(TY1231)a
Figure 6
Recessed
Pendent
(TY1231)b
Figure 7
Temperature
Bulb Liquid
Color
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
286°F (141°C)
Blue
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
286°F (141°C)
Blue
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
Sprinkler Finish 5
Natural
Brass
Chrome Plated
Polyesterc
1, 2, 3, 4
1, 2, 4
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 K-FACTOR SPRINKLERS
TFP171
Page 8 of 12
K-Factor
Type
Pendent
(TY2231)
Upright
(TY2131)
4.2
1/2 in. NPT
Recessed
Pendent
(TY2231)a
Figure 8
Recessed
Pendent
(TY2231)b
Figure 9
Temperature
Bulb Liquid
Color
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
286°F (141°C)
Blue
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
286°F (141°C)
Blue
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
135°F (57°C)
Orange
155°F (68°C)
Red
175°F (79°C)
Yellow
200°F (93°C)
Green
Sprinkler Finish3
Natural
Brass
Chrome Plated
Polyesterc
1, 2
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
4.2 K-FACTOR SPRINKLERS
TFP171
Page 9 of 12
K-Factor
Type
Pendent
(TY3231)
Upright
(TY3131)
5.6
1/2 in.
NPT
Recessed
Pendent
(TY3231)a
Figure 10
Recessed
Pendent
(TY3231)b
Figure 11
Temperature
Bulb Liquid
Color
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Sprinkler Finish 8
Natural Brass
Chrome Plated
Polyesterc
Lead
Coated
1, 2, 3, 4, 5, 6, 7
1, 2, 3, 5, 7
1, 2, 3, 5, 6, 7
1, 2, 3, 5, 7
1, 2, 4, 5, 7
N/Ad
1, 2, 3, 4, 5, 7
N/A
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
d. Not available (N/A).
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. Note the following exceptions:
• LPCB does not rate the thermal sensitivity of recessed sprinklers.
• The recessed pendent (TY3231) sprinklers with a 286°F (141°C) temperature rating are not LPCB Approved.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.)
7. EAC Approved.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where
Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLE C
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
TFP171
Page 10 of 12
K-Factor
Type
Pendent
(TY4231)
Upright
(TY4131)
8.0
3/4 in.
NPT
Recessed
Pendent
(TY4231)a
Figure 12
Recessed
Pendent
(TY4231)b
Figure 13
Pendent
(TY4931)
8.0
1/2 in.
NPT
Upright
(TY4831)
Temperature
Bulb Liquid
Color
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Sprinkler Finish9
Natural Brass
Chrome Plated
Polyesterc
Lead
Coated
1, 2, 3, 4, 5, 6, 7, 8
1, 2, 5, 8
1, 2, 5, 8
N/Ad
1, 2, 3, 5, 8
N/A
1, 2, 4, 5, 6, 8
1, 2, 5, 8
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
d. Not available (N/A).
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed
sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. EAC Approved.
9. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where
Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLE D
LABORATORY LISTINGS AND APPROVALS FOR
8.0 K-FACTOR SPRINKLERS
TFP171
Page 11 of 12
Sprinkler Finish
K-Factor
2.8
1/2 in.
NPT
4.2
1/2 in.
NPT
5.6
1/2 in.
NPT
8.0
3/4 in.
NPT
8.0
1/2 in.
NPT
Type
Pendent (TY1231)
and
Upright (TY1131)
Natural
Brass
Chrome
Plated
Polyester
Lead Coated
175 psi (12,1 bar)
N/A 2
175 psi (12,1 bar)
N/A
Recessed
Pendent (TY1231)
Pendent (TY2231)
and
Upright (TY2131)
Recessed
Pendent (TY2231)
Pendent (TY3231)
and
Upright (TY3131)
Recessed
Pendent (TY3231)
Pendent (TY4231)
and
Upright (TY4131)
250 psi (17,2 bar)
or 175 psi (12,1 bar)1
175 psi
(12,1 bar)
175 psi (12,1 bar)
Recessed
Pendent(TY4231)
Pendent (TY4931)
and
Upright (TY4831)
N/A
175 psi (12,1 bar)
175 psi
(12,1 bar)
NOTES
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in
Canada (C-UL); and, the Approval by the City of New York.
2. Not available (N/A).
TABLE E
MAXIMUM WORKING PRESSURE
TFP171
Page 12 of 12
P/N 57 – XXX – X – XXX
SPRINKLER
FINISH
SIN
TEMPERATURE
RATINGS
330
2.8K UPRIGHT (1/2 in. NPT)
TY1131
1
NATURAL BRASS
135
135°F (57°C)
331
2.8K PENDENT (1/2 in. NPT)
TY1231
3
PURE WHITE
POLYESTER (RAL9010)1
155
155°F (68°C)
340
4.2K UPRIGHT (1/2 in. NPT)
TY2131
4
SIGNAL WHITE
POLYESTER (RAL9003)
175
175°F (79°C)
341
4.2K PENDENT (1/2 in. NPT)
TY2231
5
JET BLACK
POLYESTER (RAL9005)2
200
200°F (93°C)
370
5.6K UPRIGHT (1/2 in. NPT)
TY3131
7
LEAD COATED
286
286°F (141°C)
371
5.6K PENDENT (1/2 in. NPT)
TY3231
9
CHROME PLATED
390
8.0K UPRIGHT (3/4 in. NPT)
TY4131
391
8.0K PENDENT (3/4 in. NPT)
TY4231
360
8.0K UPRIGHT (1/2 in. NPT)
TY4831
361
8.0K PENDENT (1/2 in. NPT)
TY4931
NOTES
1. Eastern Hemisphere sales only.
2. Available in only 2.8K, 4.2K, and 8.0K, 155°F (68°C) and 200°F (93°C); requires longer
lead time to manufacture.
TABLE F
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Limited
Warranty
Ordering
Procedure
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*)
For warranty terms and conditions, visit
www.tyco-fire.com.
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
* Refer to technical data sheet TFP770
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (Specify SIN),
(specify K-factor), (specify Pendent or
Upright) Sprinkler (specify) temperature
rating, (specify) finish or coating, P/N
(specify from Table F)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC

advertisement

Key Features

  • Quick Response
  • Standard Coverage
  • Decorative
  • Upright & Pendent
  • Recessed Pendent
  • Various K-Factors
  • Multiple Temperature Ratings
  • Corrosion-Resistant Options

Frequently Answers and Questions

What types of occupancies are Tyco TY-FRB Series sprinklers suitable for?
These sprinklers are designed for light or ordinary hazard commercial occupancies like banks, hotels, and shopping malls.
What types of installations are possible with Tyco TY-FRB Series sprinklers?
They offer upright, pendent, and recessed pendent configurations for flexibility.
Are there any restrictions on the use of Tyco TY-FRB Series sprinklers in new construction?
NFPA 13 prohibits installation of 1/2 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only.

Related manuals