Tyco TY-FRB Series, TY2231, TY3231, TY4131, TY4231, TY4831 Manual 12 Pages
Tyco TY-FRB Series are quick response, standard coverage, decorative sprinkler heads ideal for light or ordinary hazard commercial occupancies like banks, hotels, and shopping malls. They are designed for use in areas with finished ceilings and offer both pendent and upright configurations for flexibility in installation.
advertisement
▼
Scroll to page 2
of
12
Worldwide www.tyco-fire.com Contacts Series TY-FRB – 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Scan the QR code or enter the URL in a web browser to access the most up-to-date electronic version of this document. Data rates may apply. docs.jci.com/tycofire/tfp171 General Description The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described in herein are quick response, standard coverage, decorative 3 mm glass bulb-type spray sprinklers. They are designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, and shopping malls. The sprinkler, where applicable, is intended for use in areas with a finished Page 1 of 12 ceiling. This recessed pendent sprinkler uses one of the following recessed escutcheons: • Two-piece Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush pendent position. • Two-piece Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) Recessed Escutcheon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the recessed escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond what would be obtained when exposed to corrosive atmospheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/ chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level version of the Series TY-FRB Pendent Sprinklers is detailed in technical data sheet TFP356. Sprinkler guards are detailed in technical data sheet TFP780. NOTICE The Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association (NFPA), in addition to DECEMBER 2022 the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. NFPA 13 prohibits installation of 1/2 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only. Sprinkler Identification Number (SIN) TY1131 . . . Upright 2.8K, 1/2 in. NPT TY1231 . . Pendent 2.8K, 1/2 in. NPT TY2131 . . . Upright 4.2K, 1/2 in. NPT TY2231 . . Pendent 4.2K, 1/2 in. NPT TY3131 . . . Upright 5.6K, 1/2 in. NPT TY3231 . . Pendent 5.6K, 1/2 in. NPT TY4131 . . . Upright 8.0K, 3/4 in. NPT TY4231 . . Pendent 8.0K, 3/4 in. NPT TY4831 . . . Upright 8.0K, 1/2 in. NPT TY4931 . . Pendent 8.0K, 1/2 in. NPT TFP171 TFP171 Page 2 of 12 * Temperature rating ** Pipe thread connections per is indicated on Deflector. ISO 7-1 can be provided on special request. ESCUTCHEON PLATE SEATING SURFACE 1 - Frame 2 - Button 3 - Sealing 5 - Compression Assembly Screw 4 - Bulb 6 - Deflector * 7 - Bushing 7 1 7/16" (11,1 mm) NOMINAL MAKE-IN 2-3/16" (55,6 mm) 3 2-1/4" (57,2 mm) 2 4 1-9/16" (39,7 mm) 5 6* 1/2" NPT ** WRENCH FLATS UPRIGHT PENDENT STYLE 10 or 20 RECESSED ESCUTCHEON 2-7/8" (73,0 mm) DIA. RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K-FACTOR, 1/2 IN. NPT * Temperature rating ** Pipe thread connections per is indicated on Deflector. ISO 7-1 can be provided on special request. 5 - Compression 3 - Sealing Assembly Screw 4 - Bulb 6 - Deflector * 1 2 2-3/16" (55,6 mm) 4 1-1/2" (38,1 mm) WRENCH FLATS UPRIGHT 1 - Frame 2 - Button 3 7/16" (11,1 mm) NOMINAL MAKE-IN 2-3/16" (55,6 mm) 1/2" NPT ** ESCUTCHEON PLATE SEATING SURFACE PENDENT STYLE 10 or 20 RECESSED ESCUTCHEON 5 6* 2-7/8" (73,0 mm) DIA. RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K-FACTOR, 1/2 IN. NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and NYC Approved EAC Approved Note: For complete approval information, including corrosion-resistant status, see Tables A, B, C and D. Maximum Working Pressure See Table E Discharge Coefficient K=2.8 gpm/psi½ (40,3 Lpm/bar½) K=4.2 gpm/psi½ (60,5 Lpm/bar½) K=5.6 gpm/psi½ (80,6 Lpm/bar½) K=8.0 gpm/psi½ (115,2 Lpm/bar½) Temperature Rating See Tables A and B Finishes Sprinkler: See Table D Recessed Escutcheon: Signal or Pure White, Grey Aluminum, Jet Black, Chrome Plated, or Natural Brass Physical Characteristics Frame �������������������������������������������������������Bronze Button������������������������������������������� Brass/Copper Sealing Assembly. . Beryllium Nickel w/TEFLON Bulb������������������������������������������������������������� Glass Compression Screw���������������������������������Bronze Deflector������������������������������������� Copper/Bronze Bushing (K=2.8)�����������������������������������������Bronze Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency, such as UL Listing based on the requirements of NFPA 13 and FM Approval based on the requirements of the FM Global Loss Prevention Data Sheets. Use only the style 10, 20, 30, or 40 recessed escutcheon, as applicable, for recessed pendent installations. TFP171 Page 3 of 12 * Temperature rating ** Pipe thread connections per is indicated on Deflector. ISO 7-1 can be provided on special request. 1 2 2-3/16" (55,6 mm) 2-3/16" (55,6 mm) WRENCH FLATS UPRIGHT 5 - Compression 3 - Sealing Assembly Screw 4 - Bulb 6 - Deflector * 3 7/16" (11,1 mm) NOMINAL MAKE-IN 1/2" NPT** ESCUTCHEON PLATE SEATING SURFACE 1 - Frame 2 - Button 4 1-1/2" (38,1 mm) 5 STYLE 10 or 20 RECESSED ESCUTCHEON PENDENT 6* 2-7/8" (73,0 mm) DIA. RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K-FACTOR, 1/2 IN. NPT * Temperature rating ** Pipe thread connections per is indicated on Deflector. ESCUTCHEON PLATE SEATING SURFACE ISO 7-1 can be provided on special request. 1 - Frame 2 - Button 3 - Sealing 5 - Compression Assembly Screw 4 - Bulb 6 - Deflector * 1 1/2" (12,7 mm) NOMINAL MAKE-IN 3 2-5/16" (58,7 mm) 2-1/4" (57,2 mm) 3/4" NPT ** WRENCH FLATS UPRIGHT 2 4 1-9/16" (39,7 mm) PENDENT 5 STYLE 30 or 40 RECESSED ESCUTCHEON 6* 2-7/8" (73,0 mm) DIA. RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K-FACTOR, 3/4 IN. NPT CEILING PLATE SEATING SURFACE 1 3 7/16" (11,1 mm) NOMINAL MAKE-IN 2-3/16" (55,6 mm) 1/2" NPT ** UPRIGHT 2-1/4" (57,2 mm) 2 4 1-9/16" (39,7 mm) 5 6 * WRENCH FLATS PENDENT 1 - Frame 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Compression Screw 6 - Deflector * * Temperature rating is indicated on Deflector. ** Pipe thread connections per ISO 7-1 can be provided on special request. CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K-FACTOR, 1/2 IN. NPT TFP171 Page 4 of 12 Installation The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) and 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 ft-lb to 14 ft-lb (9,5 N·m to 19,0 N·m). A leak tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 ft-lb to 20 ft-lb (13,4 N·m to 26,8 N·m). Higher levels of torque can distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the escutcheon plate by under or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Series TY-FRB Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accordance with the following instructions: corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Step 1. After installing the Style 10, 20, 30, or 40 Mounting Plate, as applicable, over the sprinkler threads and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Care must be taken to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. For more information, see Installation section. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench as shown in Figure 15. Apply the sprinkler wrench to the sprinkler wrench flats as shown in Figure 1 to 4. Step 3. After the ceiling is installed or the finish coat is applied, slide on the Style 10, 20, 30, or 40 closure over the Series TY-FRB Recessed Pendent Sprinkler and push the closure over the mounting plate until its flange comes in contact with the ceiling. Care and Maintenance Step 1. Install pendent sprinklers in the pendent position. Install upright sprinklers in the upright position. The TYCO Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Step 2. With pipe thread sealant applied to the pipe threads, handtighten the sprinkler into the sprinkler fitting. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench as shown in Figure 14. Apply the sprinkler wrench to the sprinkler wrench flats as shown in Figure 1 to Figure 5. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Series TY-FRB Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendent Sprinklers must be installed in accordance with the following instructions: Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. For more information, see Installation section. Initial and frequent visual inspections of random samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections according to NFPA 25 should suffice. Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition and the longterm integrity of the corrosion-resistant material, which can be affected by the corrosive conditions present. TFP171 Page 5 of 12 5/8±1/4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING 2-7/8" DIA. (73,0 mm) 2-1/4" DIA. (57,2 mm) 3/4" (19,1 mm) 1/4" (6,4 mm) MOUNTING PLATE 1/2±1/8" (12,7±3,2 mm) FACE OF SPRINKLER FITTING 2-7/8" DIA. (73,0 mm) 2-1/4" DIA. (57,2 mm) 1/4" (6,4 mm) MOUNTING PLATE 1/8" (3,2 mm) 1/8" (3,2 mm) MOUNTING SURFACE MOUNTING SURFACE CLOSURE 1/2" (12,7 mm) SERIES TY-FRB 1-5/16" (33,3 mm) 13/16" (20,6 mm) CLOSURE SERIES TY-FRB 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) FIGURE 6 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 IN. NPT FIGURE 7 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 IN. NPT 2-7/8" DIA. (73,0 mm) 2-7/8" DIA. (73,0 mm) 5/8±1/4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING 2-1/4" DIA. (57,2 mm) 3/4" (19,1 mm) 1/4" (6,4 mm) MOUNTING PLATE 1/2±1/8" (12,7±3,2 mm) FACE OF SPRINKLER FITTING 2-1/4" DIA. (57,2 mm) 1/4" (6,4 mm) MOUNTING PLATE 1/8" (3,2 mm) 1/8" (3,2 mm) MOUNTING SURFACE MOUNTING SURFACE CLOSURE 1/2" (12,7 mm) SERIES TY-FRB 1-1/4" (31,8 mm) 3/4" (19,1 mm) FIGURE 8 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 IN. NPT CLOSURE SERIES TY-FRB 1-1/4" (31,8 mm) 1" (25,4 mm) FIGURE 9 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 IN. NPT TFP171 Page 6 of 12 2-7/8" DIA. (73,0 mm) 5/8±1/4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING 3/4" (19,1 mm) 1/4" (6,4 mm) 2-1/4" DIA. (57,2 mm) MOUNTING PLATE 1/2±1/8" (12,7±3,2 mm) FACE OF SPRINKLER FITTING 2-7/8" DIA. (73,0 mm) 1/2" (12,7 mm) 1/4" (6,4 mm) 2-1/4" DIA. (57,2 mm) MOUNTING PLATE 1/8" (3,2 mm) 1/8" (3,2 mm) MOUNTING SURFACE MOUNTING SURFACE CLOSURE 1-1/4" (31,8 mm) SERIES TY-FRB 3/4" (19,1 mm) CLOSURE SERIES TY-FRB 1-1/4" (31,8 mm) 1" (25,4 mm) FIGURE 10 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 IN. NPT FIGURE 11 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 IN. NPT 2-7/8" DIA. (73,0 mm) 2-7/8" DIA. (73,0 mm) 5/8±1/4" (15,9±6,4 mm) FACE OF SPRINKLER FITTING 3/4" (19,1 mm) 1/4" (6,4 mm) 2-1/4" DIA. (57,2 mm) MOUNTING PLATE 1/8" (3,2 mm) FACE OF SPRINKLER FITTING 1/2" (12,7 mm) 1/4" (6,4 mm) 2-1/4" DIA. (57,2 mm) MOUNTING PLATE 1/8" (3,2 mm) MOUNTING SURFACE MOUNTING SURFACE CLOSURE 1/2±1/8" (12,7±3,2 mm) 1-5/16" (33,3 mm) SERIES TY-FRB 13/16" (20,6 mm) FIGURE 12 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 IN. NPT CLOSURE SERIES TY-FRB 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) FIGURE 13 SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 IN. NPT WRENCH RECESS WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) FIGURE 14 W-TYPE 6 SPRINKLER WRENCH PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 15 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 7 of 12 K-Factor Type Pendent (TY1231) Upright (TY1131) 2.8 1/2 in. NPT Recessed Pendent (TY1231)a Figure 6 Recessed Pendent (TY1231)b Figure 7 Temperature Bulb Liquid Color 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green Sprinkler Finish 5 Natural Brass Chrome Plated Polyesterc 1, 2, 3, 4 1, 2, 4 NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant sprinklers. TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 K-FACTOR SPRINKLERS TFP171 Page 8 of 12 K-Factor Type Pendent (TY2231) Upright (TY2131) 4.2 1/2 in. NPT Recessed Pendent (TY2231)a Figure 8 Recessed Pendent (TY2231)b Figure 9 Temperature Bulb Liquid Color 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 286°F (141°C) Blue 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green 135°F (57°C) Orange 155°F (68°C) Red 175°F (79°C) Yellow 200°F (93°C) Green Sprinkler Finish3 Natural Brass Chrome Plated Polyesterc 1, 2 NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant sprinklers. TABLE B LABORATORY LISTINGS AND APPROVALS FOR 4.2 K-FACTOR SPRINKLERS TFP171 Page 9 of 12 K-Factor Type Pendent (TY3231) Upright (TY3131) 5.6 1/2 in. NPT Recessed Pendent (TY3231)a Figure 10 Recessed Pendent (TY3231)b Figure 11 Temperature Bulb Liquid Color 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Sprinkler Finish 8 Natural Brass Chrome Plated Polyesterc Lead Coated 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5, 7 1, 2, 3, 5, 6, 7 1, 2, 3, 5, 7 1, 2, 4, 5, 7 N/Ad 1, 2, 3, 4, 5, 7 N/A NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. d. Not available (N/A). 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. Note the following exceptions: • LPCB does not rate the thermal sensitivity of recessed sprinklers. • The recessed pendent (TY3231) sprinklers with a 286°F (141°C) temperature rating are not LPCB Approved. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. EAC Approved. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. TABLE C LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS TFP171 Page 10 of 12 K-Factor Type Pendent (TY4231) Upright (TY4131) 8.0 3/4 in. NPT Recessed Pendent (TY4231)a Figure 12 Recessed Pendent (TY4231)b Figure 13 Pendent (TY4931) 8.0 1/2 in. NPT Upright (TY4831) Temperature Bulb Liquid Color 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Orange Red Yellow Green Blue Sprinkler Finish9 Natural Brass Chrome Plated Polyesterc Lead Coated 1, 2, 3, 4, 5, 6, 7, 8 1, 2, 5, 8 1, 2, 5, 8 N/Ad 1, 2, 3, 5, 8 N/A 1, 2, 4, 5, 6, 8 1, 2, 5, 8 NOTES a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable. b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable. c. Frame and Deflector only. d. Not available (N/A). 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. EAC Approved. 9. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. TABLE D LABORATORY LISTINGS AND APPROVALS FOR 8.0 K-FACTOR SPRINKLERS TFP171 Page 11 of 12 Sprinkler Finish K-Factor 2.8 1/2 in. NPT 4.2 1/2 in. NPT 5.6 1/2 in. NPT 8.0 3/4 in. NPT 8.0 1/2 in. NPT Type Pendent (TY1231) and Upright (TY1131) Natural Brass Chrome Plated Polyester Lead Coated 175 psi (12,1 bar) N/A 2 175 psi (12,1 bar) N/A Recessed Pendent (TY1231) Pendent (TY2231) and Upright (TY2131) Recessed Pendent (TY2231) Pendent (TY3231) and Upright (TY3131) Recessed Pendent (TY3231) Pendent (TY4231) and Upright (TY4131) 250 psi (17,2 bar) or 175 psi (12,1 bar)1 175 psi (12,1 bar) 175 psi (12,1 bar) Recessed Pendent(TY4231) Pendent (TY4931) and Upright (TY4831) N/A 175 psi (12,1 bar) 175 psi (12,1 bar) NOTES 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. 2. Not available (N/A). TABLE E MAXIMUM WORKING PRESSURE TFP171 Page 12 of 12 P/N 57 – XXX – X – XXX SPRINKLER FINISH SIN TEMPERATURE RATINGS 330 2.8K UPRIGHT (1/2 in. NPT) TY1131 1 NATURAL BRASS 135 135°F (57°C) 331 2.8K PENDENT (1/2 in. NPT) TY1231 3 PURE WHITE POLYESTER (RAL9010)1 155 155°F (68°C) 340 4.2K UPRIGHT (1/2 in. NPT) TY2131 4 SIGNAL WHITE POLYESTER (RAL9003) 175 175°F (79°C) 341 4.2K PENDENT (1/2 in. NPT) TY2231 5 JET BLACK POLYESTER (RAL9005)2 200 200°F (93°C) 370 5.6K UPRIGHT (1/2 in. NPT) TY3131 7 LEAD COATED 286 286°F (141°C) 371 5.6K PENDENT (1/2 in. NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT (3/4 in. NPT) TY4131 391 8.0K PENDENT (3/4 in. NPT) TY4231 360 8.0K UPRIGHT (1/2 in. NPT) TY4831 361 8.0K PENDENT (1/2 in. NPT) TY4931 NOTES 1. Eastern Hemisphere sales only. 2. Available in only 2.8K, 4.2K, and 8.0K, 155°F (68°C) and 200°F (93°C); requires longer lead time to manufacture. TABLE F SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Warranty Ordering Procedure Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify*) finish, P/N (specify*) For warranty terms and conditions, visit www.tyco-fire.com. Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). * Refer to technical data sheet TFP770 Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) temperature rating, (specify) finish or coating, P/N (specify from Table F) Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a trademark of The Chemours Company FC, LLC
advertisement
Key Features
- Quick Response
- Standard Coverage
- Decorative
- Upright & Pendent
- Recessed Pendent
- Various K-Factors
- Multiple Temperature Ratings
- Corrosion-Resistant Options
Frequently Answers and Questions
What types of occupancies are Tyco TY-FRB Series sprinklers suitable for?
These sprinklers are designed for light or ordinary hazard commercial occupancies like banks, hotels, and shopping malls.
What types of installations are possible with Tyco TY-FRB Series sprinklers?
They offer upright, pendent, and recessed pendent configurations for flexibility.
Are there any restrictions on the use of Tyco TY-FRB Series sprinklers in new construction?
NFPA 13 prohibits installation of 1/2 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only.