Dataprobe iBoot-G2 + network controlled power switch User Manual
Dataprobe iBoot-G2 is a versatile network-controlled power switch that offers remote power management, security enhancements, energy savings, and automated control capabilities. With its web-based interface and Telnet support, you can easily access and control connected devices from anywhere with an internet connection.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Congratulations on purchasing the best network controlled power switch available. The iBoot-G2 provides you the ability to reboot crashed devices with the click of a mouse. Be sure to read up on all the features of the iBoot-G2
Including:
Web Based setup and control
Telnet setup and control
Event Scheduling for real-time power control.
AutoPing: Automatic monitoring and action for failed equipment.
Management Utility: Easy Setup,
Firmware upgrades and Reset to Factory
Default
Easy Software Integration: Use the DxP
Protocol to build your own custom applications .
New iBoot Cloud Service – BETA – Control all your iBoots from one web portal.
1. Table of Contents
Technical Support and Warranty
Web Enabled
Power Switch
02/19/2014
2. Important Safety Instructions
When using this product, basic safety precautions should always be followed to reduce the risk of fire, electric shock, and injury to persons, including the following:
1. Read and understand all instructions.
2. Follow all warnings and marked on the product.
3. Unplug this product from the wall outlet before cleaning. Do not use liquid cleaners or aerosol cleaners. Use a damp cloth for cleaning.
4. Do not use this product in an outdoor environment or near water, for example, near a bath tub, wash bowl, kitchen sink, or laundry tub, in a wet basement, or near a swimming pool.
5. Do not place this product on an unstable cart, stand, or table. The product may fall, causing serious damage to the product.
6. Slots and openings in this product and the back or bottom are provided for ventilation to protect it from overheating; these openings must not be blocked or covered. The openings should never be blocked by placing the product on the bed, sofa, rug, or other similar surface. This product should never be placed near or over a radiator or heat register.
This product should not be placed in a built-in installation unless proper ventilation is provided.
7. This product should be operated only from the type of power source indicated on the marking label. If you are not sure of the type of power supply to your home, consult your dealer or local power company.
8. This product is equipped with a three wire grounding type plug, a plug having a third (grounding) pin. This plug will only fit into a grounding type power outlet. This is a safety feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not defeat the safety purpose of the grounding type plug.
Do not use a 3-to-2 prong adapter at the receptacle; use of this type adapter may result in risk of electrical shock and/or damage to this product.
9. Do not allow anything to rest on the power cord. Do not locate this product where the cord will be abused by persons walking on it.
10. Do not overload wall outlets and extension cords as this can result in the risk of fire or electric shock.
11. Never push objects of any kind into this product through slots as they may touch dangerous voltage points or short out parts that could result in a risk of fire or electrical shock. Never spill liquid of any kind on the product.
12. To reduce the risk of electrical shock, do not disassemble this product, but take it to a qualified serviceman when some service or repair work is required. Opening or removing covers may expose you to dangerous voltages or other risks.
Incorrect re-assembly can cause electric shock when the appliance is subsequently used.
13. Unplug this product from the wall outlet and refer servicing to qualified service personnel under the following conditions: a) When the power supply cord or plug is damaged or frayed. b) If liquid has been spilled into the product. c) If the product has been exposed to rain or water. d) If the product does not operate normally by following the operating instructions. Adjust only those controls that are covered by the operating instructions because improper adjustment of other controls may result in damage and will often require extensive work by a qualified technician to restore the product to normal operation. e) If the product has been dropped or has been damaged. If the product exhibits a distinct change in performance.
14. Avoid using a telephone (other than a cordless type) during an electrical storm. There may be a remote risk of electric shock from lightning.
15. Do not use the telephone to report a gas leak in the vicinity of the leak.
16. Do not exceed the maximum output rating of the auxiliary power receptacle.
Save These Instructions iboot-g2_v140219e iBoot-G2 Page 2
3. General Description
The iBoot-G2 is a network attached, IP addressed, web controlled AC power switch. Anyone with a web browser can access iBoot-G2 to perform power On, Off or Power Cycle (Reboot or Power Burst). iBoot-
G2 uses two levels of password for security. iBoot-G2 features international standard IEC320 connections and is compatible with power mains worldwide. A simple Web browser interface makes it easy to control power from anywhere in the world with a click of a mouse. iBoot-G2 also supports Telnet for text commands, as well as Dataprobe’s
Exchange Protocol (DxP) for interfacing to a variety of Dataprobe products and custom software development.
3.1. Uses for iBoot
• Remote reboot of any device, routers, servers, kiosks, etc. The device to be rebooted need not be network attached.
• Secure sensitive devices by keeping them powered off when not in use. This prevents hackers from seeing them at all times.
• Power down equipment when not needed for power savings and to save on wear and tear.
• Power up alert devices like sirens, lamps, messages; or control environmental system like heaters, coolers pumps, etc.
3.2. Multiple Control Options
In addition to the Web control capabilities, iBoot-G2 features several other means to operate automatically or under computer control.
AutoPing: The AutoPing feature allows iBoot-G2 to automatically detect failed equipment and perform a timed reboot or other power control function (like turning on an indicator or siren). You set 1 or 2 IP addresses to be periodically pinged. When iBoot-G2 no longer detects a response from the address(es), the programmed power control function is actuated.
Telnet: iBoot’s Command Line Interface (CLI) allows direct control and setup through Telnet.
Dataprobe Exchange Protocol: iBoot-G2 supports the Dataprobe Exchange Protocol (DxP) This protocol allows Dataprobe products to communicate across networks, and allows developers to design custom applications to integrate iBoot-G2 into custom applications. For more information about DxP, contact
Dataprobe Applications Engineering and Support. iboot-g2_v140219e iBoot-G2 Page 3
4. Hardware Installation
4.1. Ethernet Connections
iBoot-G2+ supports 10/100 Ethernet using the cable supplied, or other suitable unshielded twisted pair (Cat 5) cabling. Activity (green) and
100Mb (amber) LEDs on the network connector indicate when the network connection is properly established and when the connection is 100 Mbit/s.
4.2. AC Power Connections
Connect the device to be powered ON and OFF to the IEC receptacle marked A/C Output. An IEC 320 to North American (NEMA 5-15) power cord is included for connecting the iBoot-G2 outlet to the device to be controlled.
If a cord with a different terminating receptacle is required, be sure it is properly rated and meets all the required local electrical standards. If the device to be powered uses an IEC320 receptacle and detachable power cord, an IEC to IEC extension cord can be used.
The iBoot-G2 can be connected to a power strip to allow simultaneous control of multiple devices.
Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105-125VAC or 10 Amps for 210-240VAC.
An LED Indicator next to the Switched Outlet will be On to indicate that the power is On at that outlet. This LED will turn Off to indicate that the power is Off to the outlet.
Connect the supplied power cord to the connector labeled A/C Input, and the other end to your AC source. If a power cord with a different terminating plug is required, be sure it is properly rated and meets all the required local electrical standards.
Connect 10/100 Ethernet
Outlet Cord for North
America Included
Source Additional
Power Cords Locally iboot-g2_v140219e
Power Cord for North
America Included iBoot-G2
Source Additional Outlet
Cables Locally
Page 4
4.3. Mounting Options
iBoot-G2 is suitable for desktop or shelf mounting. A mounting kit for wall and DIN rail mounting is available.
Order part:
1920034 Mounting Kit for iBoot-G2 G2 Series
Remove all cables from the unit prior to installing or removing any mounting hardware.
Installing the Wall Mounting Kit
1920033 Mounting Kit iBoot G2 Series
DIN Rail Mounting
1. Remove the four mounting screws from the underside of the unit.
Do disassemble not the unit.
1. Install the
Wall
Mounting Kit as shown.
2. Install the wall mounting ears to the unit using the screws removed in
Step 2
2. Install the
DIN rail clips using the four screws provided.
3. The unit is ready for wall mounting.
3. Ready for
DIN rail mounting.
4. Use M3 or #4 screws (not included) for attachment to suitable surface iboot-g2_v140219e iBoot-G2 Page 5
5. Initial Configuration
The Device Management Utility (DMU), available online at http://dataprobe.com/support/iboot.html
, provides the easiest means to find and configure your iBoot-G2 for use. It can discover all the iBoots on your network, display the current IP address of each, and allow setting of a valid IP address.
Install and run the Device Management Utility:
1. Download DMUSetup.exe
2. Run DMUSetup.exe
3. Run the DMU
Note: The IP address can only be set within the first two minutes of powering up the iBoot-G2 or pressing the reset button (see Section 11). The Setup Utility will only work with iBoots on the same physical subnet as the PC.
Once the DMU is run, click on Device | Discover to display all the iBoots on your network. The DMU will display the Location Name of the iBoot, The product
ID and Version Number, the current IP Address, and the MAC Address. Factory defaulted iBoots will display with the name New iBoot-G2 and have the factory default IP address of 192.168.1.254. If the IP address was assigned by a DHCP server, no changes to the IP Address are required.
The IP address field also indicates the port for web access that is used by the iBoot. The standard port for web browser control is factory default Port 80.
Change the IP Address
DMU Discovers Dataprobe Devices on your Network
Enter New IP Address for iBoot
1. Click on the row containing the iBoot-G2 to be set. The row will become highlighted.
2. From the menu select Set | IP Address
3. Enter the new IP Address into the form. Click OK when done.
4. A confirmation box is displayed. Click OK to clear the box.
Once the IP Address is set, other all other operational features of the iBoot-G2 can be set up. Click on
Discover again to refresh the display, highlight the desired iBoot-G2 and click on Manage | Launch
Browser. See Section 7 to configure the iBoot.
IP Address Successfully Set
The DMU can also be used to return an iBoot-G2 to its Factory Default condition. This can be used to recover an iBoot-G2 with a lost password. Highlight an iBoot-G2 from the display and select Set | Factory
Defaults. This must be done within the first two minutes of powering up the iBoot or pressing the reset button. iboot-g2_v140219e iBoot-G2 Page 6
5.1. Other ways to set the IP Address
1. Automatically from a DHCP Server
2. Web Browser via the Set-up Page
3. Command Line Interface (Telnet) iBoot-G2 comes with factory installed IP address 192.168.1.254.
Setting the IP address from a DHCP Server
A DHCP server will automatically assign an IP address (dynamic address) as well as Subnet Mask and
Gateway to the iBoot-G2. If you reboot the iBoot-G2 with the IP Mode set for DHCP, the DHCP server will be able to assign an IP address. Once an IP address is assigned, you must check the DHCP server or use the iBoot-G2 DUM to see what address is assigned to the iBoot. You can lock the iBoot-G2 to the current address, by selecting IP Mode = Static without changing the addresses. Set the IP Mode either by using the web setup page, or via Telnet commands.
Setting the IP address using Web Browser
To set the IP address using a Web Browser, connect the Ethernet connection to your local network and apply power to iBoot.
Open your browser and access iBoot-G2 by entering the default (192.168.1.254) or current IP address into your browser's Address window. Enter the administrator credentials, click on Setup and follow the instructions on Page 10. iboot-g2_v140219e iBoot-G2 Page 7
6. Web Browser Operation
6.1. Password Protection
iBoot-G2 uses two username/password credential sets, one for power control only (User) and one that also provides access to the setup functions (Admin). This configuration can be changed to require
Administrator credentials at all times or allow unsecured User level control. See section 7.12.
Default Credentials:
Role Username (fixed) Password (settable) a i d m n
Administrator admin admin
Enter Username and Password
User user user
Open your browser and enter the IP address of iBoot-G2 into the address bar. If you have changed the IP address by any of the methods described, enter that address, otherwise, use the default IP address
192.168.1.254
Enter the username and password when prompted. When the proper username/password is received the
Control and Status Page is displayed. iBoot-G2 uses an inactivity timer for security. This timeout is user selectable from 0 to 99 minutes.
Setting to zero disables the timeout feature. When there is no activity for the set time in minutes, the user is automatically logged out and the username and password will need to be entered again for access. This is to prevent accidental lockout by leaving the user logged in.
As the iBoot-G2 allows only one Web user logged in at any time, use caution when disabling the timeout feature, as it is possible to lock out other users by forgetting to logout. Closing the browser will not log the user out and will lock out web access. If you do become locked out, access the iBoot-G2 via Telnet and reboot the unit, or press the reset button (see Section 11).
6.2. Mobile Browser Support
The standard web pages illustrated in this manual are for screen sizes 700 pixels wide and greater. For devices with screen widths below 700 pixels, the iBoot-G2 uses a set of mobile browser pages. The iBoot-G2 automatically detects the screen size and redirects automatically to the mobile pages.
The mobile pages do not support the setup functions. To access the setup functions, or to view the full desktop site, click on the Full Site button. iboot-g2_v140219e iBoot-G2 Page 8
6.3. Control and Status Page
Once the user is validated, the Control and
Status page is displayed. (Only one person can be connected to the iBoot-G2 at a time.).
This page provides automatic updates every 1 second.
To control the power, click on the appropriate button. During power cycling, the Power Status bar will indicate the temporary status, with a blue background. Once the cycle is complete, the status bar will revert to its original condition. To abort a power cycle, click on either Power On or
Power Off buttons.
If the AutoPing feature is in use, the page will also display the current status, OK or Failed, for each AutoPing in use, with a counter of how many times action was triggered. If connecting with the Admin credentials, reset buttons for the Trigger counter is provided.
If the iBoot-G2 is connected to a time server (see Section 7.5), The Home page will also show the five most recent history events, including the Outlet, Action, User and Time/Date of each event. The iBoot-G2 holds the last 32 events in memory. The user can access a complete history webpage, download the history in a .csv file, or clear the history.
Navigation Buttons:
Refresh: Use the Refresh button to obtain the latest status of iBoot. Using your browser's refresh button can lead to inadvertent power switching. If an NTP server is being used, the time of the last refresh will be shown in the upper right corner.
Setup: To access the Setup page, the administrator credentials are required. When logged in as User, the challenge for Administrator credentials will be displayed.
Logout: When you are finished with iBoot, click on
Logout. A Goodbye page will be displayed. This page has a URL link to re-connect with the iBoot.
The linkback URL is user settable. If no linkback is set, the hyperlink will be the unit’s IP Address. iboot-g2_v140219e iBoot-G2 Page 9
7. Web Setup
iBoot-G2 setup section consists of several pages. Access any page via the buttons on the left of the page.
Each time a setting is changed click on the Save button for that page to save the changes before moving to the next page.
7.1. Device Settings
Location ID: Set a 20 Character name to be displayed on the top of the Home page. This assists in identifying which iBoot-G2 is being accessed.
Cycle Time: 1 to 999 seconds power cycle time.
This is the length of time the power will be off during a reboot, or on during a power burst.
Initial State: The outlet can be set to the state it will assume when the iBoot-G2 is powered up or reset .
The choices are: On, Off and Last, meaning the state it was in when the power was removed or reset commenced.
Upgrade Enable: Check this box to allow remote firmware upgrades of the iBoot-G2. When this box is unchecked, firmware upgrades will not be allowed.
Auto Logout: This setting sets the automatic logout for inactivity on both the web and telnet users. It can be set from 0 to 99 minutes. 0 disables the Auto Logout feature.
As the iBoot-G2 allows only one Web user logged in at any time, use caution when disabling the timeout feature, as it is possible to lock out other users by forgetting to logout. Closing the browser will not log the user out and will lock out web access. If you do become locked out, access the iBoot-G2 via Telnet and reboot the unit, or press the reset button.
7.2. Network Settings
IP Mode: Select Static to set the IP address using the fields below, or DHCP to allow a DHCP server to set the IP Address.
IP address: Enter a static IP address. This will be automatically set if using DHCP
Subnet Mask: Enter the Subnet Mask. This will be automatically set if using DHCP
Gateway: Enter the Gateway. This will be automatically set if using DHCP
HTTP Port: This setting is used to allow access to iBoot-G2 on a port other than the Web standard
Port 80. If the port is changed, you will need to identify the port number when you enter iBoot's IP address into your browser. If the new port is 8080 then use the address http://192.168.1.254:8080 . iboot-g2_v140219e iBoot-G2 Page 10
Linkback URL: This setting allows control of the hotlink displayed on the Goodbye page. It allows use of the public IP address or DNS name instead of the internal IP Address of the iBoot-G2, which is the default setting. If this setting is left blank, the hotlink will be the IP Address of the unit. Enter up to 128 characters.
Telnet Port: This setting is used to allow access to the iBoot-G2 via telnet by ports other than standard 23.
DxP Port: This setting is used to allow access to the iBoot-G2 via Dataprobe Exchange Protocol (DxP) via ports other than standard 9100.
DxP Control and Query: These setting enable or disable the ability of the iBoot-G2 to be either controlled or queried via the DxP protocol.
Enable Cloud Services: This setting enables the iBoot for iBoot Cloud Services (iBCS). iBCS allows the iBoot to be monitored and controlled from a web portal from any browser. It allows multiple iBoots to be managed from a single portal. For a complete description of iBCS and setup instructions, see Section 8.
Note: All of the TCP/IP Settings require a reboot of the iBoot-G2, after clicking Save. A Reboot button will appear at the bottom of the page. The new settings will not take effect until the unit is rebooted. Reboot will not affect the power position of the iBoot-G2. Upon Clicking Reboot, the
Googbye page is displayed with a link to re-login. iboot-g2_v140219e iBoot-G2 Page 11
7.3. AutoPing
The AutoPing feature allows iBoot-G2 to automatically detect failed equipment and perform a timed reboot or other power control function (like turning on an indicator or siren).
You set one or two IP addresses to be periodically pinged. When iBoot-G2 no longer detects a response from these addresses, the programmed power control function is actuated.
The two addresses can be AND or OR linked so that both (AND) or either (OR) need to fail in order to take the selected action.
Examples:
Use AutoPing as server monitor: iBoot-G2 is installed with the device it monitors and automatically reboots if there is no response.
Ideal for: Kiosks & Servers
Use Auto-Ping as service monitor: iBoot-G2 is installed with the device to be rebooted, but pings a remote host to test the communication channel. Ideal for: DSL & Cable Modem
Verification. iBoot-G2 monitors network device and powers up alarm or redundant system when there is no response Ideal for: Hot Standby Servers,
Environmental Control, Alert for any Network
Failure.
7.4. AutoPing Settings
IP Address Enter the IP address of the device to be pinged.
Ping Frequency: Enter 1 to 999 seconds. The ping will go out to the selected device this often.
Fail Count: Enter 1-999 times the ping needs to fail consecutively before the selected action is taken.
When the fail count has been reached, the AutoPing action will be triggered.
A/B Logic: (AutoPing 1 only) Select from A Only, A
AND B, A OR B. With AND, both AutoPings need to exceed their fail count to trigger the Action. With
OR, the Action will be triggered if either AutoPing fails.
Control: Select Main for the internal power outlet, or Exp1, Exp2 for either of the two expansion ports. iboot-g2_v140219e iBoot-G2 Page 12
Action: Select from
None
Power On
Power On
– Latch
– Follow
AutoPing will not take any action upon Fail.
Upon triggering, iBoot-G2 will power on and remain so until changed via the web, telnet, DxP, etc.
Upon triggering, iBoot-G2 will power on. When the ping response returns, iBoot-G2 will power off.
Power Off
Power Off
– Latch
– Follow
Upon triggering, iBoot-G2 will power off and remain so until changed via the web, telnet, DxP, etc.
Upon triggering, iBoot-G2 will power off. When the ping response returns, iBoot-G2 will power on.
Power Cycle
Times
Upon triggering, iBoot-G2 will cycle the power. If Power Cycle does not result in the ping response the iBoot-G2 can cycle again. The number of times the iBoot-G2 will cycle is set by the Times setting. To have the iBoot cycle power 3 times to get the system to respond again, set the Times to 3.
Wait: This is the length of time the iBoot-G2+ allows for a response to a ping.
With AutoPing operational, the main iBoot-G2 page will display the current status of this feature. The status will be OK to indicate that iBoot-G2 is receiving responses to the ping, or that the fail counter has not yet been exceeded.
If the fail count has been exceeded, the status will change to FAIL. The Trigger Counter indicates the number of times the AutoPing action has been triggered. A counter reset button is provided.
Note: All of the AutoPing Settings require a reboot of the iBoot-G2, after clicking Save. A Reboot button will appear at the bottom of the page. The new settings will not take effect until the unit is rebooted. Reboot will not affect the power position of the iBoot-G2. Upon Clicking Reboot, the
Goodbye page is displayed with a link to re-login.
7.5. Event Scheduling
iBoot-G2 can schedule up to eight reoccurring power events. Set the starting date and time, plus the action to be taken and any repeat cycle for each.
To enable the time scheduling function:
Enter an accessible Network Time
Server and check the Enable box. A list of public time servers is available at http://www.ntp.org/ Set your local time zone relative to GMT.
Once the time server is active, scheduled events can occur. Up to eight independent scheduled events can be programmed.
Date: Set the initial date for the event. The format for the date is mm/dd/yyyy.
Time: Set the initial time for the event. The format for the time is hh:mm with hours in 24 hour format. iboot-g2_v140219e iBoot-G2 Page 13
Repeat: Set the repeat multiplier, if desired. Set the number from 0 to 999 and either Days, Hours, or
Minutes. To have the schedule repeat every two days, set this number to 2.
Action: Set the event Action; On, Off or Cycle.
Hold/Run: Click Hold to pause the scheduled event. Click Run to re-start the scheduled event.
Delete: Delete the scheduled event.
Click Save to save the current settings. Click Reset to delete any unwanted changes.
7.6. Password Settings
The iBoot-G2 supports three modes of user and password operation.
Login Required: This mode supports both User and Admin users. Each user has a settable password.
Auto Login: This mode does not require a username of password for the User level operation.
No login challenge will be required for any mode of operation, until any setup function is requested.
The Admin username and password is required for any admin functions.
User Disabled: There is no User account. The Admin username and password will be required for operation and setup functions across all modes of operation. This is the factory default mode.
Two passwords are used by iBoot. In the Login Required mode, The User Password allows access to the control of iBoot, but not to the Setup functions. Clicking on the Setup button allows the Administrator to log in. Passwords can be up to 20 characters long and are case sensitive.
Enter the current password then the new password twice to confirm.
Default Credentials
Role
Administrator
User
Username (fixed) admin user
Password (user set) admin user iboot-g2_v140219e iBoot-G2 Page 14
8. iBoot Cloud Service – BETA
iBoot Cloud Service (iBCS) allows customers with iBoot to access and control multiple iBoots in multiple locations from a single portal with a single sign-on. iBCS will not only make using iBoots easier, by consolidating all units into one sign-on and interface, it will also enhance the number of situations where iBoot can be deployed.
Customers with Dynamic IP addressing will always be able to access their iBoot from any location.
Customers that do not allow in-bound connections can access their iBoots.
Service providers can manage multiple customer accounts with diverse security configurations iBoot Cloud service is currently in development and is made available to our current users free of charge.
Please note that as at this beta stage, service interruptions may occur or new versions of the iBoot firmware may be made available and necessary to keep current with the cloud development. The full
Terms of Service of the iBoot Cloud Service is available here .
While the Cloud Service is in Beta stage, the firmware in the iBoot is fully tested and released by
Dataprobe. If you do not enable the cloud capabilities of the iBoot, you can expect continuous and dependable operation.
8.1. iBoot Cloud Users Forum
Dataprobe has established a special users’ forum for iBoot Cloud Service Beta. Please use this forum to post any questions, comments and ideas about the iBoot Cloud Service. Registration is required to post to the forum. Find the iBoot Cloud Users Forum here .
8.2. iBCS Setup & Operation
Use of the iBoot Cloud Services requires the iBoot to be configured to access the Internet. Please review the installation and configuration procedures to insure proper setup. a. Establish Account with iBoot Cloud Server
Visit http://iboot.co
from your browser
Click on Register
Complete the information iboot-g2_v140219e iBoot-G2 Page 15
Confirm Registration by clicking on the link provided in the email. b. Insure Proper iBoot-G2 Firmware iBoot Cloud Service requires version iBoot-G2 Firmware version 1.21.99 or greater. Check the bottom of any web page of the iBoot for the firmware version. If needed, download and install the proper iBoot
Firmware from http://dataprobe.com/support_iboot-g2.html
and install as instructed in Section 11 c. Enable Cloud Services on iBoot
Log into the iBoot with Administrator rights
Go to the Network Setup page
Click on the checkbox Enable Cloud Services:
Within 30 seconds, an 8 character activation code will appear.
This code is also a hotlink to the Cloud Service. d. Register iBoot with Cloud Account
Click on the Activation code to register the iBoot with the Service.
You will be re-directed to the Service. Log-in with your account and the iBoot will be automatically registered with your account.
Alternatively, you can log in to the Service and click on Add Device and enter the activation code in the field provided.
Congratulations. You are now on the cloud. e. iBCS Main Page
The iBCS main web page provides a menu bar with the following options:
Devices: List all registered iBoot units, ordered by their Name. Click on any iBoot line to manage that unit.
Locations: Group all iBoots by location. Click on any location to display or hide all the iBoots at that location.
Account: Display and edit account information and obtain account access history.
Help: Links to the iBoot Cloud Forum and
Dataprobe support pages. iboot-g2_v140219e iBoot-G2 Page 16
f. Control Power from the Cloud
The status screen will detail all the iBoots registered with the cloud. You can add locations and group iBoots by location.
Each iBoot displays the power status and AutoPing if configured.
Click on the box that holds the
Activation Code for the device you just entered. A modal box will appear with options to rename the device, move the device to a defined location or delete the device.
Give the device a name, and Click Rename Device.
The remainder of the modal is very similar to the iBoot web page.
Select Power ON, Power OFF or Cycle Power. g. Assign Names and Locations
You can establish multiple locations and assign each iBoot to a location. You can also name each iBoot independently from the Device Name that is displayed on the iBoot web page. To add locations, click on the Locations button on the menu bar, and then click
Add Location. Name the location and click the Add Location button. iboot-g2_v140219e iBoot-G2 Page 17
9. Command Line Interface
The iBoot-G2 Command Line Interface (CLI) provides a text based method for communicating with the iBoot. The syntax of the CLI uses a basic Set (change a variable) and Get (retrieve a variable). The CLI is accessed either through the Telnet protocol, which requires a Telnet client program, or via USB which requires a serial communications program like Hyperterminal. Dataprobe also provides a simple terminal program (EZ Term) at http://dataprobe.com/support/iboot.html
.
9.1. CLI Access
Via Telnet
Open the Telnet client and connect to the IP address set for the iBoot.
The CLI uses the same security options as the web browser. See section 7.12 for an explanation of the options for user setup and security.
When connection is successful, the User> prompt is displayed. Enter user or admin and press Enter.
The prompt will change to Password>. Enter the admin or user password and press Enter. The prompt will change to iBoot>. This indicates successful login. Enter commands as needed. When done, enter the logout command.
9.2. iBoot-G2 CLI Syntax
Command Description
Control Commands
Factory Default
These commands are used to monitor and control the outlet. set outlet <on | off | cycle> get outlet
Device Commands
This command controls the outlet.
This command returns the current status of the outlet.
These commands are available to the administrator only get location set location <20 char. max> set cycle <1-999> get cycle
This command returns the iBoot-
G2’s location ID.
This command is used to set the iBoot-
G2’s location ID.
This command is used to set the cycle time, in seconds
This command returns the current cycle time set upgrade enable <yes | no> Enables or disables the ability to upload new firmware to the iBoot-G2. get upgrade enable login logout
This command displays the upload enable status.
Prompts for admin credentials when logged in as user
Terminates the session reboot This command reboots the iBoot-G2.
New Boot
10
No iboot-g2_v140219e iBoot-G2 Page 18
Network Commands
get network set ipmode <static | dhcp>
All set commands require a reboot before they take effect. These commands are only available to the administrator.
This command will return all the network settings as shown below:
Mode: Static
IP Address: 192.168.1.254
Subnet: 255.255.255.0
Gateway: 192.168.1.7
HTTP Port: 80
Linkback URL: 192.168.1.254:8080
Telnet Port: 23
DxP Port: 9100
Timeout: 20
This command sets the ip address setting mode. Static mode locks the address as set, dhcp mode allows DHCP server to assign address.
This command is used to set the iBootG2’s ip address. 192.168.1.254 set ipaddress <dotted decimal> set subnet <dotted decimal> set gateway <dotted decimal> set http port <0-65535> set telnet port <0-65535> set dxp port <0-65535> set linkback <url>
This command is used to set the iBoot-
G2’s subnet mask.
255.255.255.0
192.168.1.1 This command is used to set the Gateway
This command sets the port that the iBoot-
G2’s web server listens for incoming connections on. When set to 0 the web server is disabled.
This command sets the port that the iBoot-
G2’s Telnet server listens for incoming connections on. When set to 0 the Telnet server is disabled
This command sets the port that the iBoot-
G2’s DxP protocol service listens for incoming connections on. When set to 0 the Protocol service is disabled.
Note: At least one of the above MUST NOT be 0. The CLI will protect against all 3 from being set to 0.
80
23
9100
This command sets the linkback URL displayed on the logout page.
192.168.1.254
This command sets the automatic network timeout in minutes 2 set timeout <0-999>
Autoping Commands
get autoping set autoping <1 | 2> ipaddress
<dotted decimal> set autoping <1 | 2> frequency
<1-999> set autoping <1 | 2> failcount
<1-999>
These commands require a reboot before they will take effect. These commands are available to the administrator only.
This command returns all of the AutoPing settings as shown below.
AutoPing 1 AutoPing 2
IP Address: 192.168.233.254 192.168.233.154
Frequency: 10 10
Fail Count: 3 3
--------------------------------
Mode: Single
Action: Cycle Once
This command is used to set the IP address of AutoPing 1 or
AutoPing 2
This command is used to set the frequency (how often the iBoot-G2 sends the ping) for each of the AutoPings.
0.0.0.0
10
This command is used to set the number of consecutive failures the AutoPings must detect before the AutoPing considers the pinged device to be failed.
3 iboot-g2_v140219e iBoot-G2 Page 19
set autoping mode <single | and | or> set autoping action <none | onlatch | on-follow | off-latch | offfollow | cycle> set autoping cycle <0-999> set autoping wait <1-999>
Sets single AutoPing (AutoPing 1) or two AutoPing relationship And or Or.
This command is used to set the action that the iBoot-G2 will perform when the autoping triggers.
Single
None
This command sets the maximum number of power cycles when the AutoPing triggers. 0 = Unlimited
1
This command sets the time, in seconds for the device to respond to a ping.
2
User Commands
These commands are only available to the administrator. set user account <yes | no> set login required <yes | no>
This command sets whether or not a user account is used. If
<n> only the administrator account is active
This command sets whether or not a login is required for user level operation. A login is always required for admin functions. set password <user | admin>
<old> <new> <repeat>
This command is used to set the password of either the user or administrator. n y user admin
Event Commands
get events set time enable <yes | no> set time server <dotted decimal> get time set event <1-8> <run | hold>
These commands are only available to the administrator.
This command displays all scheduled events as shown below. Example:
Date Time Repeats Action
1. 01/13/2013 16:00 every 1 Day(s) On Run
2. 01/13/2013 16:15 every 0 Day(s) On Run
3. 01/15/2013 17:00 every 1 Hour(s) Cycle Run
4. 02/16/2014 12:00 every 1 Day(s) Off Run
5. 02/16/2014 12:10 every 1 Day(s) On Run
6. 02/17/2013 01:05 every 0 Day(s) On Run
7. 02/18/2013 01:00 every 0 Day(s) On Run
8. 03/18/2014 01:00 every 0 Day(s) On Run
No This command enables or disables the use of the time server and scheduled events.
Note: When Adding new events through the CLI. Set this to no to prevent unintended power switching
This command is used to set the IP Address of a network time server.
69.90.182.55
Displays the current time and time server
Current Time: 16:10:41 01/27/2010
Server: 64.90.182.55
This command is used to all the event to run, or put the event on hold run iboot-g2_v140219e iBoot-G2 Page 20
set event <1-8> date
<mm/dd/yyyy>
This command is used to set the scheduled action’s start date. set event <1-8> time <hh:mm> This command is used to set the time the scheduled action will occur in 24 hour format. set event <1-8> action <on | off | cycle>
This command is used to set the scheduled action. set event <1-8> repeat <day | hour | minute>
This command is used to set how often the scheduled action will repeat. set event <1-8> mult <0-999> This command sets how often the event will repeat, the number of increments (as set by the command above) before the next event. del event <1-8> This command deletes the specified event
Prompts
User>
Password> iBoot > iBoot Reboot Required>
The CLI will use the following prompts:
This prompts the user to enter his user name (user or admin).
This is the first prompt that the user is presented with.
This prompts the user to enter his password.
This is the prompt that will be displayed after the user has successfully logged in.
This is the prompt that will be displayed whenever there have been changes made that require a reboot. This prompt will remain the active prompt until the iBoot-G2 has been rebooted. iboot-g2_v140219e iBoot-G2 Page 21
10. DxP Protocol
iBoot-G2 supports the Dataprobe Exchange Protocol (DxP) for inter device communications and to allow software developers to integrate Dataprobe product into custom applications. Through the DxP protocol, the developer can:
Turn on and off power to the Outlet
Pulse the Power On or Off for a specified about of time.
Read the status of the Outlet
The DxP Protocol, as well as example code and scripts in a variety of languages are available at http://dataprobe.com/support/iboot.html
11. Firmware Upgrades
The iBoot-G2 can be field upgraded. Find the latest version or special purpose versions at http://dataprobe.com/support/iboot.html
Upgrading the firmware with a minor upgrade (i.e. 1.01.xx to 1.01.yy) will not alter the user defined settings. Major upgrades may or may not reset the iBoot-G2 to factory defaults. Check the release notes for the upgrade before making changes to you iBoot-G2.
1) Insure that the Upgrade Enable checkbox is checked in the Network Setup web page of the iBoot-G2
2) Run the Device Management Utility, available at the link above. If the iBoot-G2 you would like to upgrade is not visible in the list box, either
Select Device | Discover from the menu to locate iBoot-G2 units on the local network, or
Select Device | Add from the menu to add the IP address of the iBoot-G2.
Once the device is displayed in the list, highlight it
3) Select Manage | Upgrade Firmware
Enter User Name admin and the Password for the Administrator.
Enter the filename of the firmware, or click Browse and find the file of the firmware file to be used. iBoot-
G2 firmware uses the extension
.g2u If you don’t see any files of that type, ma ke sure the ‘Files of type’ box is set for iBoot-G2 or All
Files.
Click OK when all the details are entered.
4) The upload will begin, and a progress bar will be displayed.
5) When the firmware upload is completed, the iBoot-G2 will automatically reset and be ready for use. iboot-g2_v140219e iBoot-G2 Page 22
12. Troubleshooting
The iBoot-G2 has a recessed pushbutton switch in the event the unit is not performing as expected. Use the pushbutton as follows:
Action Result
Momentary
5 Seconds push
Hold in while and
Power up the iBoot
Soft Reset. Will not change outlet status.
Reset to Factory Defaults. Hold the button in until the Outlet LED is blinking, then release.
Recovery Mode. Allows upload of new firmware to the current IP Address. Will recover to the Factory default IP Address
192.168.1.254 if the database has been corrupted. iboot-g2_v140219e iBoot-G2 Page 23
13. Specifications
13.1. Physical
Height
Width
Depth
Weight
MTBF
Temperature
13.2. AC
Input
Input Cord
Voltage Range
Switched Receptacle
Capacity
2.0” 60mm
3.2” 82mm
4.2” 107mm
8.6 oz 244g
360,000 hours
0
– 50 degrees C
IEC 320 C14
16AWGX3C 10A 250 UL/CSA/VDE Rated (1.25mm2X3C)
Auto Sensing 105-240 VAC
IEC 320 C13
12 A Max at 105-125 VAC, 10 A Max at 210-240 VAC
13.3. Compliance
UL/cUL
CE
UL60950 Listed I.T.E
File No. E225914
Directives 89/336/EEC, 92/31/EEC and 93/68/EEC
EN 60950: 3rd Edition
EN 55022: 1998 Class B
Part 15 Class B FCC
13.4. Network
Dual 10/100 Unshielded Twisted Pair Ethernet Jacks.
IP Addressed, DHCP assigned or Static
Internal HTTP Web Server
Forms Processing Browser required
Telnet Server
User Settings Record your Setup here for reference
Location:
MAC Address:
IP Address:
Subnet Mask:
Gateway:
HTTP Port:
Auto-Ping Address:
Auto-Ping Port:
Heartbeat Port: iboot-g2_v140219e iBoot-G2 Page 24
14. Technical Support and Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of Three Years from the date of initial purchase. If the product should prove defective within that period, Seller will repair or replace the product, at its sole discretion. Repairs may be made with new or refurbished components and replacements may be new or refurbished at the Sellers sole discretion. Repaired or replaced units shall be warranteed for the balance of the original warranty, or 90 days, whichever is greater.
If Purchased from Dataprobe Inc.; Service under this Warranty is obtained by shipping the product (with all charges prepaid) to the address below. Seller will pay return shipping charges within the United States. Call Dataprobe
Technical Service to receive a Return Materials Authorization (RMA) Number prior to sending any equipment back for repair. Include all cables, power supplies, accessories and proof of purchase with shipment.
If purchased from an Authorized Dataprobe Reseller; Service under this Warranty is obtained by contacting your
Authorized Dataprobe Reseller.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT,
MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY LAW, ALL
IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANT ABILITY OR FITNESS FOR ANY
PURPOSE ARE LIMITED TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY
EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may have other rights which vary from jurisdictions to jurisdiction.
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability of fitness for any specific application.
Dataprobe Inc.
Technical Support: 201-934-5111 [email protected]
www.dataprobe.com/support.html
advertisement
Key Features
- Web Based setup and control
- Telnet setup and control
- Event Scheduling for real-time power control
- AutoPing: Automatic monitoring and action for failed equipment.
- Management Utility: Easy Setup, Firmware upgrades and Reset to Factory Default
- Easy Software Integration: Use the DxP Protocol to build your own custom applications.
- New iBoot Cloud Service – BETA – Control all your iBoots from one web portal.