Below you will find brief information for external sounder FA1700c, power supply module PS24, EOL resistor 610-7, Grade A Bell AB12. The FA1700c provides two notification appliance circuits for operating fire and burglary alarm notification appliances. Each circuit is rated as follows: 10VDC – 14VDC, 1.7A max., power-limited. The outputs has the following options: selectable for supervision, selectable to activate by individual zone assignments, selectable for confirmation of arming ding, selectable to chime when entry/exit or perimeter zones are faulted, selectable for steady or pulsing, selectable for no timeout or timeout of 2-30 minutes. If you purchased a kit containing the PS24 Power Supply Module, you may use this module to convert one or both FA1700c, 1.7A style-Y supervised Notification Appliance Circuits to 24VFW, 1.7A style-Y supervised Notification Appliance Circuits.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

FA1700c Installation Instructions | Manualzz
FA1700c
Installing External Sounders
The FA1700c provides two
Notification Appliance Circuits for operating fire and
burglary alarm notification appliances. Each circuit is
rated as follows: 10VDC – 14VDC, 1.7A max., powerlimited. NOTE: The total alarm current drawn from
Auxiliary Power 1, Auxiliary Power 2, polling loop, Bell
1, and Bell 2 cannot exceed 2.3 amps for batteryindependent operation.
The outputs has the following options:
•
Selectable for supervision.
•
Selectable to activate by individual zone
assignments
•
Selectable for confirmation of arming ding.
•
Selectable to chime when entry/exit or perimeter
zones are faulted.
•
Selectable for steady or pulsing
•
Selectable for no timeout or timeout of 2-30
minutes.
If you purchased a kit containing the PS24
Power Supply Module, you may use this
module to convert one or both
FA1700c, 1.7A style-Y
supervised Notification Appliance Circuits to
24VFW, 1.7A style-Y supervised Notification
Appliance Circuits.
UL
•
•
UL
Burglary Notification Appliance Circuits
must be programmed for a timeout of 16
minutes or longer.
Commercial fire alarm systems require
Notification Appliance Circuits to be
supervised.
This control complies with National Fire
Protection Association (NFPA) requirements for
temporal pulse sounding of fire notification
appliances.
Notification Appliance Circuit Supervision
When supervision is enabled, the
FA1700c monitors the Notification
Appliance Circuits wiring for open and short circuit
faults while the output is inactive. The system provides
a trouble indication (Zone 970 Bell 1; 971 Bell 2) when
an open occurs; or when a short occurs between the Bell
(+) and Bell (-) terminal wiring, or between the Bell (+)
terminal wiring and earth ground.
The FA1700c indicates the
trouble condition regardless of whether the system is
armed or disarmed. The zone displays on the keypads,
reports to the event log, and transmits to the central
station (if programmed) on Partition 1. The trouble is
cleared from the display by entering the user code +
OFF.
Wiring the Alarm Output
The wiring of the Notification Appliance Circuits
depends upon whether you are going to supervise the
circuit or not. Use the appropriate procedure below for
your application.
UL
Use only UL Listed sounding devices for UL
installations.
Compatible Alarm Indicating Devices
Model
ADEMCO AB12
System Sensor PA400B
(beige/PA400R (red)
System Sensor MA-12/24
System Sensor SS1215 ADA
System Sensor SS121575 ADA
System Sensor MASS1215 ADA
System Sensor MASS121575 ADA
System Sensor MA/SS-12
Wheelock LS1-12-VFR
Wheelock MS1-12-VFR
Wheelock MT-12-LS-VFR
Wheelock MT4-12-LS-VFR
Wheelock MT-12-MS-VFR
WheelockMT4-12-MS-VFR
Gentex GXS-2-15
Gentex GXS-2-1575
Gentex SHG-12-15
Gentex SHG-12-1575
Faraday 5336L-U-14-12-DC
Faraday 5337-L-U-14-12-DC
Device Type
Grade A Bell
Indoor piezo sounder
rated at 90dB @ 10 feet.
Horn
Strobe
Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Strobe
Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Strobe
Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
BELL 1 FACTORY DEFAULTS
BELL 1 IS CONFIGURED AS A BURGLARY BELL CIRCUIT
USE NONPOLARIZED GRADE A INDICATING DEVICES
(e.g., ADEMCO NO AB12 - SEE WIRING NOTES BELOW)
WIRING IS NOT SUPERVISED; CUT WHITE JUMPER, W1,
ON MAIN PCB.
ACTIVATES FOR ZONES 3-8 ALARMS (BY DEFAULT,
ZONES 3-8 ARE ASSIGNED TO BURGLARY PARTITION 1)
STEADY ALARM OUTPUT
16-MINUTE TIMEOUT.
BELL 2 FACTORY DEFAULTS
BELL 2 IS CONFIGURED AS A FIRE BELL CIRCUIT
USE POLARIZED INDICATING DEVICES.
CLASS B OPEN/SHORT SUPERVISION.
24-HR TROUBLE RESPONSE TO FAULTS.
ACTIVATES FOR ZONE 1-2 ALARMS (BY DEFAULT,
ZONES 1-2 ARE ASSIGNED TO FIRE PARTITION 1)
PULSED ALARM OUTPUT.
NO TIMEOUT
AB12 BELL/BOX WIRING
3
4
+
BELL 1
5
6
+
BELL 2
2k EOLR
(MODEL 610-7)
TO PANEL'S EARTH
GROUND (TB30)
TO ZONE 6 - (TB23)
TO ZONE 6 - (TB24)
TO PANEL'S BELL –
(e.g., BELL 1; TB4)
TO PANEL'S BELL +
(e.g., BELL 1; TB3)
AB12 WIRING NOTES:
DISCONNECT THE AB12'S FACTORY-WIRED CONNECTION
FROM ITS TERMINAL #4 TO ITS OUTER BOX.
SET FIELD 3* 17 TO "1" TO ENABLE ZONE 6 TAMPER FUNCTION.
ASSIGN ZONE 6 TO A BURGLARY PARTITION. PROGRAM
IT FOR DAY TROUBLE/NIGHT ALARM RESPONSE (TYPE 05)
WHEN THIS BELL IS USED BY ONLY ONE BURGLARY
PARTITION. PROGRAM IT FOR 24-HR. AUDIBLE ALARM
RESPONSE (TYPE 07) WHEN THIS BELL IS USED BY
MORE THAN ONE BURGLARY PARTITION.
ALL WIRING FROM AB12 TO PANEL MUST BE RUN IN
CONDUIT.
2k EOLR
1
2
3
4
5
6
AB12 OUTER BOX
INNER LINER
belloutput-003-V0
TAMPER
SWITCHES
BELL
Figure 3-6: External Sounder Connections
Supervising the Notification Appliance Circuits
To wire the NAC using the supervision feature, perform
the following steps:
Step
1
2
Action
Install a 2K EOL resistor (Model 610-7,
supplied) across the last notification
appliance on each Notification Appliance
Circuit to be supervised.
Program Zone 970 (Bell 1) and zone 971 (Bell
2) with a response type of 19 (24-Hour
Trouble).
Disabling the Supervision of the Notification
Appliance Circuits
To install the NAC and disable the supervision feature,
perform the following steps:
Step
Action
1
Cut the white jumpers W1 (for Bell 1) and W2
(for Bell 2) on the main PC board.
2
Program Zone 970 (Bell 1) and zone 971 (Bell
2) with a response type of 00.
The Notification Appliance Circuits will not
respond unless the zones are assigned to them.
For fire alarms, the system displays “FIRE ALARM
SILENCED.” This message also displays if the
Notification Appliance Circuit is not supervised.
Auxiliary Relay Connections
The FA1700c provides a built-in
Form C relay with contacts rated at 28VAC/VDC, 2.8A.
The relay may be programmed (field 3✳61) for one of
the following functions:
•
Alarm Activation
•
Trouble/Supervisory Activation
•
4-Wire Smoke Detector Reset
•
Battery Saver
Alarm Activation
(3✳61 = 1 or 4) Steady activation in response to an
alarm.
If field 3✳61 = 1, the auxiliary relay remains active
until Aux. Relay Timeout expires or until User Code +
OFF is entered. This option can be used to provide an
unsupervised Notification Appliance Circuit for
supplementary strobes, sounders, etc. when wired to
the Aux Power 1 or a separate power supply, see Figure
3-7.
If field 3✳61 = 4, the auxiliary relay remains activated
until User Code + # + 67 is entered. This option can be
used for elevator recall or ventilator shutdown on fire
alarms. By default, the relay is set to activate on alarm
zones 1-8 with no timeout (field 3✳61 = 1).
When field 3✳61 = 1, the auxiliary relay can be
programmed to give a brief activation for confirmation
of arming ding (field 3✳57) or Chime Mode (field 3✳59).
ALARM
7
8
10
11
12
GROUND
AUX PWR #1
N.C.
N.O.
NOTES:
USE NON-POLARIZED INDICATING DEVICES.
WIRING IS NOT SUPERVISED.
DO NOT EXCEED RATINGS OF THE SUPPLY USED.
IF AUX. PWR. 1 OUTPUT IS USED, THE COMBINED
ALARM CURRENT DRAIN FROM AUX. PWR. 2,
BELL 1, AND BELL 2 CANNOT EXCEED 2.3A MAX.
9
POLE
AUX RELAY FACTORY DEFAULTS
ACTIVATES FOR ZONES 1-8 ALARMS
(STEADY ALARM OUTPUT).
NO TIMEOUT.
+
belloutput-005-V0
CAN DRAW POWER FROM
AUX. PWR. 1 OUTPUT OR
FROM SEPARATE SUPPLY.
Figure 3-7: Wiring Auxiliary Relay for Alarm Activation
Trouble/Supervisory Activation
(3✳61 = 0) Steady activation in response to any zone or
system related trouble condition or to any fire
supervisory condition. The auxiliary relay remains
activated until all fault conditions have been corrected
and a User Code + OFF is entered.
Battery Saver
(3✳61 = 3) When this option is selected, the auxiliary
relay is normally activated (e.g., N.O. and pole contacts
are connected) and de-activates 4 hours after the start
of AC Loss. Using this feature, non-critical loads, such
as supplementary keypads, can be disconnected from
the auxiliary power outputs, allowing a smaller
capacity battery to be used. The relay re-activates
within a few seconds after the AC power restores.
4-Wire Smoke Detector Reset
(3✳61 = 2) Momentary (6-second) activation in response
to a second entry of a User Code + OFF sequence
following a fire alarm condition. This interrupts power
to 4-wire smoke detectors connected to hardwired zones
1-8 and polling loop zones, allowing the detectors to be
reset. Power to the detectors should be wired to the
auxiliary relay and to Aux. Power 1 output, see Figure
3-8.
N.O.
7
POLE
8
N.C.
9
Aux. Pwr 1
10
AUXILIARY RELAY
+
+
11
Keypad Prt 1 12
BLK
-
4-WIRE SMOKE
DETECTORS
+
+
-
-
–
•
•
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
CONTROL
PANEL
ZONE
TERMINALS
(15-27)
+
HEAT
DETECTOR
-
2000
OHM
EOLR
4_wiresmk-005-V0
SHOWN POWERED.
RELAY OPENS WHEN
POWER IS LOST
Figure 3-8: Wiring Auxiliary Relay for Smoke Detector Reset on FA1700c

advertisement

Key Features

  • Two notification appliance circuits
  • 10VDC-14VDC, 1.7A max
  • Power-limited
  • Selectable for supervision
  • Selectable to activate by individual zone assignments
  • Selectable for confirmation of arming ding
  • Selectable to chime when entry/exit or perimeter zones are faulted
  • Selectable for steady or pulsing
  • Selectable for no timeout or timeout of 2-30 minutes
  • Supervision feature

Frequently Answers and Questions

What is the maximum current that can be drawn from the FA1700c?
The total alarm current drawn from Auxiliary Power 1, Auxiliary Power 2, polling loop, Bell 1, and Bell 2 cannot exceed 2.3 amps for battery-independent operation.
Can the FA1700c be used with non-polarized indicating devices?
Yes, the FA1700c can be used with non-polarized indicating devices, such as the ADEMCO AB12, but only when the circuit is not supervised. This is because the FA1700c uses polarity to detect open and short circuit faults, making it necessary to use polarized devices for supervised circuits.
What are the different options for activating the auxiliary relay on the FA1700c?
The auxiliary relay can be programmed for one of the following functions: Alarm Activation, Trouble/Supervisory Activation, 4-Wire Smoke Detector Reset, Battery Saver. Each option has different activation conditions and timeouts, allowing for flexible use in various applications.