Bosch | D296 | EN Remote Test/Indicator Plate

D307
Installation Instructions
EN
Remote Test/Indicator
Plate
D307 | Installation Instructions | 1.0
Description
1.0 Description
Figure 1:
Use the D307 Remote Test/Indicator Plate with the
D296/D297 Long-Range Beam Smoke Detectors and
the D340 Series Duct Smoke Detector Housings (D340,
D341, D342, D343). This plate has LEDs to indicate
the detectors’ status and condition, a signal voltage test
point, and a key operated test switch.
D307 to D296/D297 Wiring
1
Fire
Alarm
2
– +
Alarm Loop
4
Install the D296/D297 and the D340 Series according
to the D296/D297 Installation Instructions (P/N: 31344)
and the D340 Installation Instructions (P/N: 48188).
Ensure the detectors are working properly.
Power Loop –
Power Loop +
Voltage In (+)
Voltage Out (+)
Install the D341/D342 Duct Smoke Detector Housing
or the D343 Duct Smoke Detector Housing according
to the D341/D342 Installation Instructions (P/N: 48196)
and the D343 Installation Instructions (P/N: 48199).
Ensure all wiring is unpowered before
routing.
2.1
1.
2.
2.2
Single D307 and D296/D297 Wiring
Connect the wiring between the D307 and the
D296/D297 as shown in Figure 1
Apply power and observe the LEDs.
a. The green LED lights steadily for 60 sec to 120
sec and then flashes. Refer to Table 1 on pages
5 and 6 for a description of the LED
indicators.
3
4 5 6 7 8 9
2.0 Installation
Mount the D307 on a standard double wire-mold box.
Eight conductors from the D296/D297 receivers or
D340 are required.
1. Mount the box no farther than 100 ft (30.5 m) from
the D296/D297 receivers or 500 ft (152 m) from
the D340.
2. Run the wiring from the receiver or duct housing
to the box using 18 AWG (1.2 mm) or larger wire.
Trouble 10 VDC to
Alarm
32 VDC
Remote Test
5
6
Voltage Monitor
7
Ground (–)
8
Red LED
9
Yellow LED
Green LED
10
11
12345678910 11 -
D296/D297 receiver
Fire alarm control panel (FACP)
Remote indicator plate connector
End-of-line resistor
Remote test (orange wire)
Voltage monitor (blue wire)
Ground (black wire)
Red LED (red wire)
Yellow LED (yellow wire)
Green LED (green wire)
D307
D307 and Multiple D296/D297 Wiring
Connect the wiring between the D307 and multiple
D296/D297s as shown in Figure 2 on page 3.
2.3
D307 to D340 Wiring
Connect the wiring between the D307 and D340s as
shown in Figure 3 on page 3 to wire the D307 and the
D340 Series.
The green LED lights steadily. Refer to Table 1 on
pages 5 and 6 for a description of the LED indicators.
2
Bosch Security Systems, Inc. | 9/06 | 32071K
D307 | Installation Instructions | 2.0
Installation
.
Figure 2:
Multiple D296/D297 Wiring
1
1
1
Fire Trouble 10 VDC to
Alarm Alarm 32 VDC
– +
3
Fire Trouble 10 VDC to
Alarm Alarm 32 VDC
Fire Trouble 10 VDC to
Alarm Alarm 32 VDC
– +
2
4 5 6 7 8 9
– +
2
4 5 6 7 8 9
2
4 5 6 7 8 9
Power Loop –
Power Loop +
Voltage In (+)
Voltage In (+)
Voltage In (+)
Voltage Out (+)
Voltage Out (+)
Voltage Out (+)
Remote Test
Voltage Monitor
4
Remote Test
5
6
Ground (–)
Red LED
Voltage Monitor
7
Yellow LED
Remote Test
5
8
7
Yellow LED
9
Voltage Monitor
6
Ground (–)
Red LED
Green LED
4
10
5
6
Ground (–)
Red LED
8
7
Yellow LED
9
Green LED
4
10
8
9
Green LED
10
11
123456-
D296/D297 receiver (3)
Remote indicator plate connector (3)
Fire alarm control panel (FACP) (3)
Remote test (orange wire) (3)
Voltage monitor (blue wire) (3)
Ground (black wire) (3)
Figure 3:
78910 11 -
Red LED (red wire) (3)
Yellow LED (yellow wire) (3)
Green LED (green wire) (3)
D307 (3)
Last set
D307 and D340 Wiring
GREEN
1
2
3
4
5
6
7
8
YELLOW
RED
BLACK
BLUE
ORANGE
+OUT
+IN
1
2
3
4
5
6
7
8
+OUT
ORANGE
BLUE
BLACK
RED
YELLOW
+IN
1
2
GREEN
3
2
1 - D341/D342 power card
2 - D307
3 - D340/D343 power card
Bosch Security Systems, Inc. | 9/06 | 32071K
3
D307 | Installation Instructions | 3.0
Testing
3.2
1.
3.0 Testing
Testing activates a fire alarm. Inform all
concerned personnel before performing
tests.
3.1
1.
2.
3.
D307 and D296/D297
Insert the operating key and turn the switch to
the TEST position for a minimum of 5 sec.
The red LED lights steadily and the system
sounds an alarm.
Turn the switch to RESET for a minimum of 1
sec.
The red LED turns off and the green LED lights
steadily for approximately 60 to 120 sec.
The receiver proceeds with its Setup Mode.
When the setup is completed, the green LED
begins flashing.
Connect a standard volt-ohm meter (VOM) to
the voltage monitor plugs. The voltage reading
must range between 3.8 VDC and 4.2 VDC.
You can also use the voltage monitor to check
the sensitivity level of the D296/D297. As the
signal level decreases because of dust or dirt
buildup on the lenses or system misalignment,
the voltage reading also decreases.
2.
D307 and D340
Insert the operating key and turn the switch to
TEST for a minimum of 10 sec.
The red LED lights steadily and the system
sounds an alarm.
Turn the switch to RESET for a minimum of 1
sec.
The red LED turns off and the green LED lights
steadily.
You can also use the voltage monitor to check
the D340’s sensitivity level after installation
(refer to the manufacturer’s detector head
installation instructions for proper levels).
For more information, refer to Table 1 (on pages
5 and 6) and to the related duct smoke detector
housing installation instructions:
•
D340 Installation Instructions (P/N: 48188)
•
D341/D342 Installation Instructions (P/N:
48196)
•
D343 Installation Instructions (P/N: 48199)
For more information, refer to Table 1 (on pages
5 and 6) and the D296/D297 Installation
Instructions (P/N: 31344).
4
Bosch Security Systems, Inc. | 9/06 | 32071K
D307 | Installation Instructions | 4.0
Troubleshooting
.
4.0 Troubleshooting
Table 1: Troubleshooting
Red
LED
OFF
Yellow
LED
OFF
Green
LED
ON
OFF
OFF
OFF
OFF
Flashing
OFF
D296/D297 Long-Range Beam Smoke Detector
Condition
Solution
The receiver is initializing and stabilizes
within 60 to 120 sec.
Normal
There is no voltage at the receiver.
Check for power at D307’s Terminal 1 (+)
and Terminal 5 (-), and at Terminal 2 (+) and
Terminal 5 (-).
OFF
ON
ON
Trouble
Check for power at the D296/D297’s
receiver Terminal 8 (-) and Terminal 9 (+).
Clear the beam path or realign the receiver.
OFF
ON
Flashing
The beam is blocked or misaligned.
Trouble
Clean the transmitter and receiver covers.
Flashing
If the reference voltage at the voltage
monitor is lower than 2 VDC, dust or dirt on
the lenses reduced the signal strength, or
vibration misaligned the receiver.
Trouble
Flashing
If the reference voltage at the voltage
monitor is greater than 4.8 VDC, the beam
strength increased because the beam
misaligned or the air quality improved.
Alarm
Determine the cause of the alarm.
Alarm and trouble
Reset the detector by moving the keyswitch
to RESET for a minimum of 1 sec or
resetting the control panel.
Determine the cause of the alarm.
Alarm occurred and then the beam was
blocked.
Reset the receiver by moving the keyswitch
to RESET for a minimum of 1 sec.
OFF
ON
ON
ON
OFF
ON
ON
OFF
Flashing
Flashing
Red
LED
OFF
Yellow
LED
OFF
Green
LED
OFF
OFF
OFF
OFF
Flashing
ON
ON
OFF
ON
Reset the detector by moving the keyswitch
to RESET for a minimum of 1 sec or
resetting the control panel.
Clear the beam path.
Invalid sensitivity setting
Set the receiver to the proper sensitivity
setting.
D340 Duct Smoke Detector Housing
Condition
Solution
No power to the loop or auxiliary.
Apply power to both loop and auxiliary.
Wiring is incorrectly connected.
Normal
Trouble
Correct the power or wiring connection.
The head is missing from the base, the head
is dirty, the cover is missing, or the wiring
harness to the base is unplugged.
ON
If the reference voltage does not return to
4 VDC, realign the receiver and press the
Receiver Setup switch.
Alarm
Clean or replace the head. Replace the
cover.
If the missing cover does not cause a
trouble condition, the tamper jumper is
disabled.
Determine the cause of the alarm and reset
the detector.
If the alarm does not reset from the D307,
the reset jumper might be disabled.
Bosch Security Systems, Inc. | 9/06 | 32071K
5
D307 | Installation Instructions | 4.0
Table 1:
Troubleshooting
Continued
Red
LED
OFF
OFF
Yellow
LED
OFF
OFF
Green
LED
ON
OFF
OFF
ON
ON
D341/D342 Duct Smoke Detector Housing
Condition
Solution
Normal
No power is applied or the wiring is
incorrectly connected.
Trouble
The head is dirty or is missing from the
base, or the cover is missing.
ON
ON
ON
Alarm
Yellow
LED
OFF
OFF
Green
LED
ON
OFF
OFF
Flashing
OFF
Trouble
ON
The cover is missing or the wiring harness
to the base is unplugged.
Alarm
OFF
Clean or replace the head, or replace the
cover.
If the missing cover does not cause a trouble
condition, the tamper jumper is disabled.
Determine the cause of the alarm and reset
the detector.
If the alarm does not reset from the D307,
the reset jumper might be disabled.
D343 Duct Smoke Detector Housing
Condition
Solution
Red
LED
OFF
OFF
ON
Correct the power or wiring connection.
Normal
No power is applied to the bus and auxiliary,
or the wiring is incorrectly wired.
Supply power to the bus and auxiliary.
Correct the power or wiring connection.
Replace the head or cover.
If the missing cover does not cause a trouble
condition, the tamper jumper is disabled.
Determine the cause of the alarm and reset
the detector.
If the alarm does not reset from the D307,
the reset jumper might be disabled.
6
Bosch Security Systems, Inc. | 9/06 | 32071K
D307 | Installation Instructions | 5.0
Specifications
.
5.0 Specifications
Table 2: Specifications
Voltage
Current Draw
Operating Temperature
10 VDC to 32 VDC
10 mA at 24 VDC, standby
20 mA at 24 VDC, alarm
140 mA at 24 VDC, test (D340 Series only)
-22°F to +130°F (-30°C to +54°C). For UL Listed requirements, the operating temperature
range is +32°F to 100°F ( 0°C to +37.8°C)