Pentair Raychem HWAT System Installation And Operation Manual
Pentair Raychem HWAT System is designed for maintaining the temperature of thermally insulated pipes. It’s a reliable system used in various applications to prevent freezing, keep fluids at a desired temperature, and ensure proper operation of systems. It consists of self-regulating heating cables, RayClic connection kits, and controllers. The HWAT System is UL Listed and CSA certified for use in non-hazardous locations.
PDF
Download
Document
Advertisement
Advertisement
HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES THERMAL MANAGEMENT SOLUTIONS WWW.THERMAL.PENTAIR.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK HAZARD Raychem HWAT Systems must be installed correctly to ensure proper operation and to prevent shock and fire. Read these important warnings and carefully follow all the installation instructions. • To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Pentair Thermal Management requirements, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit breakers. • Approvals and performance are based on the use of Pentair Thermal Management parts only. Do not substitute parts or use vinyl electrical tape. • Bus wires will short if they contact each other. Keep bus wires separated. • Connection kits and heating cable ends must be kept dry before and during installation. • The black heating cable core is conductive and can short. They must be properly insulated and kept dry. • Damaged bus wires can overheat or short. Do not break bus wire strands when preparing the cable for connection. • Damaged heating cable can cause electrical arcing or fire. Do not use metal attachments such as pipe straps or tie wire. Use only Pentair Thermal Management approved tapes and cable ties to secure the cable to the pipe. • Do not attempt to repair or energize damaged cable. Remove damaged cable at once and replace with a new length using the Raychem RayClic-S splice kit. Replace damaged connection kits. • Use only fire-resistant insulation which is compatible with the application and the maximum exposure temperature of the system to be traced. ii Raychem-IM-H57548-HWATsystem-EN 16/08 Table of Contents 1 2 3 4 5 6 7 8 9 General Information 1 1.1 Use of the Manual 1 1.2 Safety Guidelines 2 1.3 Typical HWAT System 2 1.4 Electrical Codes 3 1.5 Approvals 3 1.6 Warranty 4 1.7 Trade Coordination 4 1.8 General Installation Notes 5 1.9 Tools Required 6 Heating Cable Verification and Selection 7 2.1 Heating Cable 7 Heating Cable Installation 8 3.1 Heating Cable Storage 8 3.2 Pre-Installation Checks 8 3.3 Installation 8 Heating Cable Components 14 4.1 General Connection Kit Information 14 Control and Monitoring 16 5.1 HWAT-ECO and ACCS-30 Controllers 16 Thermal Insulation 17 6.1 Insulating the System 17 6.2 Insulation Installation 17 Power Supply and Electrical Protection 20 7.1 Voltage Rating 20 7.2 Circuit Breaker Sizing 20 7.3 Electrical Loading 20 7.4 Ground-Fault Protection 21 Commissioning and Preventive Maintenance 22 8.1 Tests 22 8.2 Preventative Maintenance 24 Test Procedures 25 9.1 System Tests 25 9.2 Fault Location Tests 31 9.3 Cable and Connection Continuity Raychem-IM-H57548-HWATsystem-EN 16/08 iii 10 Test Procedures 34 11 Troubleshooting Guide 38 iv Raychem-IM-H57548-HWATsystem-EN 16/08 1 1 General Information 1.1 Use of the Manual This installation and operation manual is for Raychem HWAT Hot Water Temperature Maintenance systems installed on thermally insulated pipes only. This manual details how to install and operate an HWAT system. The HWAT System includes the HWAT-R2 heating cables, RayClic connection kits, and the HWAT-ECO or ACS-30 controllers. It is important to review this manual and the following documents with the installing contractor: • HWAT System Product Selection & Design Guide (H57538) • HWAT-ECO Data Sheet (H57339) • ACS-30 Mulitpoint Commercial heat-tracing Control System Data Sheet (H58261) • HWAT Heating Cable Data Sheet (H57512) • RayClic Connection System Data Sheet (H57545) • HWAT-ECO Installation and Operation Manual (H57340) • ACS-30 Programming Guide (H58692) For additional information, contact: Pentair Thermal Management 7433 Harwin Drive Houston, TX 77036 USA Tel: +1.800.545.6258 Tel: +1.650.216.1526 Fax: +1.800.527.5703 Fax: +1.650.474.7711 [email protected] www.thermal.pentair.com Important: For the Pentair Thermal Management warranty and agency approvals to apply, the instructions that are included in this manual and product packages must be followed. Raychem-IM-H57548-HWATsystem-EN 16/08 1 1 1.2 General Information Safety Guidelines The safety and reliability of any heat-tracing system depends on the quality of the products selected, and on proper design, installation, and maintenance. Incorrect design, handling, installation, or maintenance of any of the system components can cause underheating or overheating of the pipe, or damage to the heating cable system, and may result in system failure, electric shock, or fire. The guidelines and instructions contained in this guide are important. Follow them carefully to minimize these risks and to ensure that the HWAT System performs reliably. Pay special attention to the following: Important • Instructions marked • Warnings marked 1.3 WARNING Typical HWAT System A typical HWAT System is shown is Figure 1. The heating cable is cut to length in the field and is attached to the pipe with glass tape. A power connection kit connects the heating cable bus wires to power in a junction box. RayClic tees and splices accommodate pipe branches to connect two or three heating cables together. An end seal kit is used to terminate the end of the heating cable. A controller is used to set the maintain temperature and improve energy savings. 2 Raychem-IM-H57548-HWATsystem-EN 16/08 1 General Information Temperature sensor Insulation 180° Heating cable End seal Heating cable Pipe temperature sensor Thermal insulation ETL label Glass tape Tee Controller S BM To er powution o T trib dis el pan Splice Note: Partial pipe insulation shown here for clarity. All pipes must be fully insulated Power connection Figure 1: Typical HWAT heating cable system 1.4 Electrical Codes Section 427 of the National Electrical Code (NEC), and Part 1, Section 62 of the Canadian Electrical Code (CEC), in particular, govern the installation of electrical heat-tracing systems used on hot water pipes. All installations must be in compliance with this and any other applicable national or local codes. 1.5 Approvals HWAT-R2 heating cable and RayClic connection kits, are UL Listed and CSA certified for use in non-hazardous locations. The HWAT-ECO controller is c-ULus Listed and the ACS-30 controller is c-CSA-us certified (ACS-UIT) and c-UL-us Listed (ACS-PCM2-5) to Raychem-IM-H57548-HWATsystem-EN 16/08 3 1 General Information US and Canadian standards for us in non-hazardous locations. Refer to the specific product data sheets for details. 1.6 Warranty Pentair Thermal Management standard limited warranty applies to all products. An extension of the limited warranty period to ten (10) years from the date of installation is available if a properly completed on-line warranty form is completed within (30) days from the date of installation. The extension is valid for the HWAT-R2 heating cable, RayClic connection kits and accessories, but not the HWAT-ECO or ACS-30 controllers. You can access the complete warranty on www.thermal.pentair.com. 1.7 Trade Coordination Installation of an HWAT System can involve or impact the work of numerous trades. Therefore, effective and early coordination between trades is a critical aspect of all HWAT System Installations. The installation of the heating cable and connections must be properly scheduled, along with the scheduling of the risers and insulation installation. This guide will assist the installer throughout the installation process and must be reviewed by all affected trades before installation of the HWAT System begins. In a fast-track job, the HWAT System must be considered a critical path item: the pipe, heating cable, insulation, and wallboard must all be installed in the proper order, since the heating cable cannot be installed later. If, for example, the walls go up before the heating cable commissioning tests have been completed, it may be necessary to remove the walls in order to repair a damaged or improperly installed system. Ensuring that the installation of the HWAT System is included in the overall construction schedule will help ensure a successful and trouble-free installation. 4 Raychem-IM-H57548-HWATsystem-EN 16/08 1 1.8 General Information General Installation Notes Read and observe the instructions in this guide to insure that the HWAT System is installed successfully. • Accidental damage to the system can be minimized during construction by installing thermal insulation on the pipe immediately after the pipe has been traced and the heating cable has been tested. • Read all installation documentation to familiarize yourself with the system components. • Read and follow all warnings and recommendations. All involved trades should review this entire guide and assess the recommendations applicable to their scope of work. • All heat-traced pipes and equipment must be thermally insulated. Insulation is an important part of the HWAT System. For an effective system, the fiberglass insulation must be a specific thickness for each specific pipe size as detailed in Table 2 on page 17. • Do not install the HWAT System below the minimum installation temperature. ––The minimum installation temperature for HWAT heating cables is 0°F (–18°C) ––The minimum installation temperature for HWATECO is 40°F (5°C). • Ensure that your water heater temperature is set at your desired pipe maintain temperature. • Do not energize cable when it is coiled or on the reel. • Never use metal tie wire or pipe straps to secure heating cables to pipes. Important: Exceeding 185°F (85°C) for HWAT-R2 will decrease the power output of the heating cables over time. Raychem-IM-H57548-HWATsystem-EN 16/08 5 1 1.9 General Information Tools Required For installing cable and connection kits: • Utility knife • Diagonal cutters • Cable cutters • Tape measure • Screwdriver • Heat gun or propane torch For testing the heating cable: • Megohmmeter 2500 Vdc • Multimeter (voltage, resistance and capacitance) 6 Raychem-IM-H57548-HWATsystem-EN 16/08 2 2 2.1 Heating HeatingCable CableVerification Verificationand and Selection Selection Heating Cable The HWAT System includes HWAT-R2 heating cable designed to maintain the piping at specific temperature settings with the use of the HWAT-ECO or ACS30 controllers. Figure 2 shows the construction of the heating cable. Modified polyolefin outer jacket Tinned-copper braid Polymer-coated aluminum wrap Modified polyolefin inner jacket Self-regulating conductive core Nickel-plated copper bus wires Figure 2: HWAT-R2 heating cable The minimum control setpoint for HWAT-R2 is 105°F (40°C). The maximum control setpoint for HWAT-R2 is 140°F (60°C). Raychem-IM-H57548-HWATsystem-EN 16/08 7 3 3 Heating HeatingCable CableInstallation Installation 3.1 Heating Cable Storage • Store the heating cable in a clean, dry location. Temperature range: 0°F (–18°C) to 140°F (60°C). • Protect the heating cable from mechanical damage. 3.2 Pre-Installation Checks Check materials received: • Review the heating cable design and compare the list of materials to the catalog numbers of the heating cables and connection kits received to confirm that the proper materials are on site. The heating cable type is printed on its jacket. • The HWAT System is limited to 208 V or 240 V service when using the HWAT-ECO controller. When using the ACS-30 controller the voltage range is 208–277 V. Ensure that the service voltage available is correct. • Inspect the heating cable and connection kits to ensure there is no in-transit damage. • Verify that the heating cable jackets are not damaged by conducting the insulation resistance test (refer to Section 9) on each reel of cable. Do not power the heating cable when it’s on the reel. Check piping to be traced: • Make sure all mechanical pipe testing (i.e. hydrostatic testing/purging) is complete and the system has been cleared by the client for tracing. • Walk the system and plan the routing of the heating cable on the pipe. • Inspect the piping and remove any burrs, rough surfaces or sharp edges. 3.3 Installation • Pay out the heating cable, loosely stringing it along the pipe, making sure that the cable is always next to the pipe when crossing obstacles. • Install HWAT heating cable in straight runs along the pipe. Spiraling the heating cable is not necessary. 8 Raychem-IM-H57548-HWATsystem-EN 16/08 3 Heating Cable Installation • If the cable is on the wrong side of an obstacle such as a crossing pipe or I-beam, you will need to reinstall it or cut and splice it. • When installing the heating cable, the cable must not be compressed or pinched between two objects. Wall and floor penetrations and pipe hangers are particular areas of concern. Figure 3: Protecting the heating cable in floor penetrations • Run insulation through the pipe hanger ensuring that the pipe is not resting on the heater. Figure 4: Pipe hanger with heating cable • When making floor or wall penetrations, make sure the hole is large enough to accommodate the pipe and the thermal insulation. When sealing around pipes at floor penetrations, avoid damaging or cutting the heating cable, or pinching it between the pipe and the concrete. Raychem-IM-H57548-HWATsystem-EN 16/08 9 3 Heating Cable Installation • The heating cable must not be embedded directly in the sealing material; the pipe should have thermal insulation over it (if allowed by local codes) or the heating cable should be run through the penetration in a tube or conduit. If the conduit must be sealed, use a pliable fire-resistant material (Dow Corning Fire Stop, 3M Fire Barrier, or T&B FlameSafe) that can be removed if necessary. Figure 5: Multiple pipe floor penetration • On vertical piping groups, run the heating cable along the inside of the pipe close to other pipes so it will not be damaged if the pipe hits the side of the floor penetration. Run the heating cable over the outside of the pipe support. Do not clamp the heating cable to the pipe with the pipe support. • In high-rise construction it may be necessary to install the HWAT System 10 or 12 floors at a time to fit into the construction schedule. If so, the end of the heating cable should be sealed with a RayClic-E end seal and placed in an accessible location. This allows testing of one part of the heating cable at a time, and allows splicing it to another section when the system is complete. Paying out the cable: • Use a reel holder that pays out smoothly with little tension. If the heating cable snags, stop pulling. • Keep the heating cable strung loosely but close to the pipe being traced to avoid interference with supports and equipment. • Meter marks on the heating cable can be used to determine cable length. 10 Raychem-IM-H57548-HWATsystem-EN 16/08 3 Heating Cable Installation • Protect all heating cable ends from moisture, contamination and mechanical damage. Figure 6: HWAT cable layout When paying out the heating cable, AVOID: • Sharp edges • Excessive pulling force or jerking • Kinking and crushing • Walking on it, or running over it with equipment WARNING: Fire and shock hazard. Do not install damaged cable. Connection kits and cable ends must be kept dry before and during installation. Positioning heating cables If possible, position the heating cable on the lower section of the pipe, at the 4 or 8 o’clock positions, as shown below, to protect it from damage. Figure 7: Cable positioning Raychem-IM-H57548-HWATsystem-EN 16/08 11 3 Heating Cable Installation Attaching the heating cable Starting from the end opposite the reel, tape the heating cable to the pipe every 2 feet. Work back to the reel. Leave extra heating cable at the power connection, at all sides of splices and tees to allow for future servicing. See Table 1 on page 15. • Install heating cable connection kits immediately after attaching the heating cable. If immediate installation is not possible, protect the heating cable ends from moisture. Bending the cable When positioning the heating cable on the pipe, do not bend tighter than 1/2” radius. The heating cable does not bend easily in the flat plane. Do not force such a bend, as the heating cable will be damaged. 1/2" Figure 8: Bending technique Crossing the cable HWAT heating cables are self-regulating and may be overlapped whenever necessary without overheating or burning out. Cutting the cable Cut the heating cable to the desired length after it is attached to the pipe. HWAT can be cut to length without affecting the heat output per foot. Attachment tapes To ensure that the heating cable is in full contact with the pipe, use tape to attach the heating cable to the pipe every 2 ft (.6 m). Use Raychem GT-66 attachment tape. One roll will handle approximately 50 ft (15 m) of cable. 12 Raychem-IM-H57548-HWATsystem-EN 16/08 3 Heating Cable Installation Raychem GT-66 glass tape 2 ft. Figure 9: Attaching the heating cable To ensure sufficient heat transfer AT-180 aluminum tape must be used to install the heating cable on plastic pipes as shown in Figure 10. WARNING: Do not use metal attachments such as pipe straps or tie wire. Do not use vinyl-based electrical or duct tape. Use only Pentair Thermal Management approved tapes. Raychem HWAT heating cable Continuous AT-180 alluminum tape over heating cable Rigid plastic pipe Thermal insulation Figure 10: Installed on plastic pipe with aluminum tape Raychem-IM-H57548-HWATsystem-EN 16/08 13 4 4 Heating HeatingCable CableComponents Components 4.1 General Connection Kit Information Raychem RayClic connection kits must be used with HWAT-R2 heating cable. A complete circuit requires a power connection and an end seal. Splices and tees and other connection kits are used as needed. Use the HWAT System Design Guide (H57510) to select appropriate connection kits. Installation instructions are included with every connection kit. Steps for preparing the heating cable and installing connection kits must be followed. HWAT connection kit locations should be noted on “As Built” drawings. Connection kit locations should be marked on the outside of the insulation cladding with the labels provided in the kits. Alternate lighted end seal RayClic-PC powered connection RayClic-LE lighted end seal RayClic-S splice RayClic-E end seal RayClic-PT powered tee RayClic-PS powered splice RayClic-X cross tee HWAT heating cable RayClic-T tee Alternate connection kits Figure 11: RayClic connection system Connection Kit Installation • When practical, mount the connection kits on top of the pipe. All heating cable connections must be mounted above grade level. • Leave excess cable to serve as a service loop at all connection kits (power, splice, cross or tee) for future maintenance, as detailed in Table 1. The additional heating cable will easily pay for itself in time savings if it becomes necessary to check or replace a connection kit after installation. Splices and tees should have a service loop on each of the heating cables entering the connection kit. 14 Raychem-IM-H57548-HWATsystem-EN 16/08 4 Heating Cable Components Table 1: SERVICE LOOPS FOR EACH CONNECTION KIT Connection # of cable Cable length/ Total cable length kit name connections/kit connection (Service loop) RayClic-PC 1 2.0 ft (0.6 m) 2 ft (0.6 m) RayClic-S 2 1.0 ft (0.3 m) 2 ft (0.6 m) RayClic-T 3 1.0 ft (0.3 m) 3 ft (0.9 m) RayClic-X 4 1.0 ft (0.3 m) 4 ft (1.2 m) RayClic-PS 2 1.5 ft (0.5 m) 3 ft (0.9 m) RayClic-PT 3 1.3 ft (0.4 m) 4 ft (1.2 m) RayClic-E 1 NA NA RayClic-LE 1 2.0 ft (0.6 m) 2.0 ft (0.6m) • All power connection kits must be installed in accessible locations. Access to splices, tee kits and end seals is recommended for future modification or maintenance but is not required. • Locate junction boxes for easy access but not where they may be exposed to mechanical abuse. • Heating cables must be installed over, not under, pipe straps used to secure components. WARNING: The black heating cable core is electrically conductive and can short. It must be properly insulated and kept dry. Damaged bus wires can overheat or short. WARNING: Fire and shock hazard. Raychem brand specified components must be used. Do not substitute parts or use vinyl electrical tape. Raychem-IM-H57548-HWATsystem-EN 16/08 15 5 5 Control Controland andMonitoring Monitoring 5.1 HWAT-ECO and ACS-30 Controllers The Raychem HWAT-ECO controller is designed for use only with HWAT-R2 heating cables and must be used to ensure proper water temperature. Refer to the HWAT-ECO Installation and Operation Manual (H57340) for the installation and operation instructions of the controller. Figure 12: HWAT-ECO controller The ACS-30 Control System is also approved for use with HWAT-R2 heating cable. Refer to the ACS-30 Programming Guide (H58692) for the installation and operating instructions of the control system. (Optional) RMM2 L Heat-tracing system L TRO CON ER DULE-5 POWMO CM S-P ACC TRO CON ER DULE-5 POWMO CM S-P ACC N MO COM RM ALA N MO COM RM ALA ACCS-UIT2 ACCS-PCM2-5 ACCS-PCM2-5 Figure 13: ACS-30 Control System 16 Raychem-IM-H57548-HWATsystem-EN 16/08 6 6 Thermal ThermalInsulation Insulation 6.1 Insulating the System Pipes must be insulated with the correct thermal insulation to maintain the desired pipe temperatures. For pipes 1 1/4 inches and smaller, use insulation that is oversized by 1/4 inch to allow room for insulating over the heating cables. The thermal insulation schedule is shown in Table 2. Table 2: FIBERGLASS INSULATION SCHEDULE Copper pipe size (in) IPS insulation size (in) Insulation thickness (in) 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3/4 1 1 1/4 1 1/2 1 1/2 2 2 1/2 3 1/2 1 1 1 1/2 1 1/2 2 2 1/2 3 Important: For pipes 3 inches and larger, the thickness of insulation can be equal to the pipe diameter with one run of heating cable or 1/3 the pipe diameter with two runs of heating cable. 6.2 Insulation Installation • Before insulating the pipe, visually inspect the heating cable and connection kits to ensure they are properly installed and there are no signs of damage. Damaged cable or connection kits must be replaced. • Check that the insulation type and thickness complies with the insulation schedule detailed in Table 2. • Insulate the pipes immediately after the heating cable is installed and has passed all tests to minimize damage to the cable. • Insulate the pipe at floor and wall penetrations. Failure to do so will cause cold spots in the water system and could lead to damage to the heating cable. If local codes do not allow this, the heating cable should be run through a conduit or channel before the firestop is installed. Use a fire-resistant Raychem-IM-H57548-HWATsystem-EN 16/08 17 6 Thermal Insulation sealing compound such as Dow Corning Fire Stop, 3M Fire Barrier, or T&B Flame-Safe. • Do not use staples to close the insulation. Use tape or the adhesive-lined edge of the insulation to ensure that the seam remains sealed. Staples can damage the HWAT heating cable. Figure 14: Sealing the insulation seam • When installing splice, tee and end seal kits underneath the thermal insulation, mark the location of splices, tees, and end seals on the outside of the insulation, with labels provided in the kits, while installing the insulation. Use large diameter insulation or sheets to cover splices, tees, or service loops. Figure 15: Installing Connection kits above insulation. • All power connection kits must be mounted above the thermal insulation. 18 Raychem-IM-H57548-HWATsystem-EN 16/08 6 Thermal Insulation • Splice and Tee connection kits may be installed above the insulation using the optional SB-04 mounting bracket. The pipe and heating cable service loops must be fully insulated as shown above. Figure 16: Installing connection kits below insulation. • Make sure that all heat-traced piping, fittings, wall penetrations, and branch piping are insulated. Correct temperature maintenance requires properly installed and dry thermal insulation. Uninsulated sections of pipe can result in cold spots. • After installing insulation, electrical codes require that you install “Electric Traced” labels along the piping at suitable intervals (10-foot intervals recommended) on alternate sides. WARNING: Use only fire-resistant insulation, such as fiberglass. Raychem-IM-H57548-HWATsystem-EN 16/08 19 7 7 Power PowerSupply Supplyand andElectrical Electrical Protection Protection 7.1 Voltage Rating Verify that the supply voltage is either 208 or 240 volts as specified by the HWAT System design. 7.2 Circuit Breaker Sizing Circuit breakers must be sized using the cable lengths shown in Table 3. Do not exceed the maximum circuit length shown for each breaker size. When using the HWAT-ECO controller install circuit breakers that incorporate 30-mA ground-fault circuit protection, or provide equivalent levels of groundfault protection. Ground-fault protection is integrated into the ACS-30 control system so no additional protection is required. Table 3: MAXIMUM CIRCUIT LENGTH IN FEET (METERS) 7.3 Breaker Size HWAT-R2 15 Amp 20 Amp 30 Amp 250 (75) 330 (100) 500 (150) Electrical Loading Over-current devices are selected according to the heating cable type, supply voltage, and circuit length to allow for start-up. The design specifies the size and type of over-current device. Piping systems are seldom installed exactly as the drawings show. If changes are made, make sure that all circuit lengths comply with Table 3. 20 Raychem-IM-H57548-HWATsystem-EN 16/08 7 7.4 Power Supply and Electrical Protection Ground-Fault Protection If the heating cable is improperly installed, or physically damaged to the point that water contacts the bus wires, sustained arcing or fire could result. If arcing does occur, the fault current may be too low to trip conventional circuit breakers. Pentair Thermal Management, the U.S. National Electrical Code, and the Canadian Electrical Code require both ground-fault protection of equipment and a grounded metallic covering on all heating cables. All HWAT heating cables meet the metallic covering requirements. Ground-fault protection must be provided by the installer. WARNING: To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Pentair Thermal Management requirements, agency certifications, and national electrical codes, groundfault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit breakers. WARNING: Disconnect all power before making connections to the heating cable. Raychem-IM-H57548-HWATsystem-EN 16/08 21 8 8 Commissioning Commissioningand andPreventive Preventive Maintenance Maintenance Pentair Thermal Management requires a series of commissioning tests be performed on the HWAT System. These tests are also recommended at regular intervals for preventive maintenance. Results must be recorded and maintained for the life of the system, utilizing the “Installation and Inspection Record” (refer to Section 11). Submit this manual with initial commissioning test results to the owner. Ensure that your water heater and mixing valve temperature are set at your desired pipe maintain temperature. Important: Exceeding185°F (85°C) for HWAT-R2 will decrease the power output of the heating cables over time. 8.1 Tests A brief description of each test is found below. Detailed test procedures are found in Section 9. Visual inspection Visually inspect the pipe, insulation, and connections to the heating cable for physical damage. Check that no moisture is present, electrical connections are tight and grounded, insulation is dry and sealed, and control and monitoring systems are operational and properly set. Damaged heating cable must be replaced. Once the heating cable is installed any repairs to pipes should be done very carefully. The heater must be shielded from excessive heat. Temperatures greater than 185°F will permanently damage the affected section of heater. Damage due to excessive external heat may or may not effect the operation of the entire circuit. A torch must not be used on the pipe, pipe hangers, or riser clamps after the heating cable has been installed on the pipe because this can cause permanent damage to the heating cable (even if it does not appear to be burned). Use a saw, not a torch, to cut riser clamps. If use of a torch is unavoidable, cut the fiberglass tape that holds the HWAT cable to the pipe on either side of the area to be heated, and pull the cable away from the pipe. Make sure you do not cut the HWAT cable. Shield the cable from the flame. 22 Raychem-IM-H57548-HWATsystem-EN 16/08 8 Commissioning and Preventive Maintenance Charred or damaged cable must be replaced to avoid the risk of arcing or fire. Figure 17: Shielding the cable from the flame Circuit length verification (capacitance test) The installed circuit length is verified through a capacitance measurement of the HWAT heating cable. Compare the calculated installed length against the system design. If the calculated length is shorter than the system design, confirm all connections are secure and the grounding braid is continuous. Insulation Resistance Insulation Resistance (IR) testing is used to verify the integrity of the heating cable inner and outer jackets. IR testing is analogous to pressure testing a pipe and detects if a hole exists in the jacket. Power check The power check is used to verify that the system is generating the correct power output. This test can be used in commissioning to confirm that the circuit is functioning correctly. For on-going maintenance, compare the power output to previous readings. The heating cable power output per foot is calculated by dividing the total wattage by the total length of a circuit. The current, voltage, operation temperature and length must be known. Circuit length can be determined from “as built” drawings, meter marks on the cable or with the capacitance test. The watts per foot can be compared to the heating cable outRaychem-IM-H57548-HWATsystem-EN 16/08 23 8 Commissioning and Preventive Maintenance put in Section 9 for an indication of heating cable performance: Ground-fault test Test all ground-fault breakers per manufacturer’s instructions. Cable and Connection Continuity Cable and connection continuity test verifies all the electrical connections are made properly. Pentair recommends conducing this test as the cable is installed to identify any potential problems immediately. This test can also be conducted after the entire cable run is installed but before end seals are applied. 8.2 Preventative Maintenance Recommended maintenance for HWAT Systems consists of performing the system tests for commissioning, and on a regular basis. Procedures for these tests are described in Section 9. Systems should be checked each year. If the HWAT System fails any of the tests, refer to Section 10 for trouble shooting assistance. Make the necessary repairs and replace any damaged cable immediately. De-energize all circuits that may be affected by maintenance. Protect the heating cable from mechanical or thermal damage during maintenance work. Maintenance records The “Installation and Inspection Record,” (refer to Section 11) should be filled out during all maintenance and repairwork and kept for future reference. Repairs Use only HWAT heating cable, HWAT-ECO or ACS‑30 controller, and RayClic connection kits when replacing any damaged heating cable system. Repair the thermal insulation to original condition or replace with new insulation, if damaged. Retest the system after all repairs or replacements. WARNING: Damage to cables or components can cause sustained electrical arcing or fire. Do not attempt to repair damaged heating cable. Do not energize cables that have been damaged by fire. Replace damaged cable at once by removing the entire damaged section and splicing in a new length using the appropriate RayClic splice kits. 24 Raychem-IM-H57548-HWATsystem-EN 16/08 9 9 Test TestProcedures Procedures 9.1 System Tests The following tests must be done after installing the RayClic connection kits, but before the thermal insulation is applied to the pipe: 1. Visual inspection 2. Insulation resistance test After the thermal insulation has been installed on the pipe, the following tests must be performed: 1. Visual inspection 2. Insulation resistance test 3. Circuit length verification (capacitance test) 4. Power test 5. Temperature test All test procedures are described in this manual. It is the installer’s responsibility to perform these tests or have an electrician perform them. Record the results in the Installation and Inspection Record in Section 11. 1. Visual inspection test • Check inside all power, splice and tee kits for proper installation, overheating, corrosion, moisture, or loose connections. • Check the electrical connections to ensure that ground and bus wires are insulated over their full length. • Check for damaged, missing or wet thermal insulation. • Check that end seals, splices, and tees are properly labeled on insulation cladding. • Check HWAT-ECO or ACS-30 controller for proper setpoint and operation. Refer to the HWAT-ECO Installation and Operation Manual or ACS-30 Programming Guide for details. 2. Insulation Resistance test Frequency Insulation resistance testing is required during the installation process, and as part of regularly scheduled maintenance, as follows: Raychem-IM-H57548-HWATsystem-EN 16/08 25 9 Test Procedures • Before installing the cable • Before installing components • Before installing the thermal insulation • After installing the thermal insulation • Prior to initial start-up (commissioning) • As part of the regular system inspection • After any maintenance or repair work Procedure Insulation resistance testing (using a megohmmeter) should be conducted at three voltages; 500, 1000, and 2500 Vdc. Potential problems may not be detected if testing is done only at 500 and 1000 volts. First measure the resistance between the heating cable bus wires and the braid (Test A), then measure the insulation resistance between the braid and the metal pipe (Test B). Do not allow test leads to touch junction box, which can cause inaccurate readings. Important: System tests and regular maintenance procedures require that insulation resistance testing be performed. Test directly from the HWAT-ECO, ACS30 or the junction box closest to the RayClic-PC. WARNING: Fire hazard in hazardous locations. Insulation resistance test can produce sparks. Be sure there are no flammable vapors in the area before performing this test. Insulation resistance criteria A clean, dry, properly installed circuit should measure thousands of megohms, regardless of the heating cable length or measuring voltage (500–2500 Vdc). The following criteria are provided to assist in determining the acceptability of an installation where optimum conditions may not apply. • All insulation resistance values should be greater than 1000 megohms. If the reading is lower, consult Section 10, Troubleshooting Guide. 26 Raychem-IM-H57548-HWATsystem-EN 16/08 9 Test Procedures Important: Insulation resistance values for Test A and B for any particular circuit should not vary more than 25 percent as a function of measuring voltage. Greater variances may indicate a problem with your heat-tracing system, confirm proper installation and/ or contact Pentair Thermal Management for assistance. Test A L1 L2 Test B Attach to pipe Figure 18: Insulation resistance test Raychem-IM-H57548-HWATsystem-EN 16/08 27 9 Test Procedures Insulation Resistance test procedure 1. De-energize the circuit. 2. Disconnect the HWAT-ECO or ACS-30 controller if installed. 3. Disconnect bus wires from terminal block. 4. Set test voltage at 0 Vdc. 5. Connect the negative (—) lead to the heating cable metallic braid or RayClic green wire. 6. Connect the positive (+) lead to both heating cable bus wires or RayClic black wires. 7. Turn on the megohmmeter and set the voltage to 500 Vdc; apply the voltage for 1 minute. Meter needle should stop moving. Rapid deflection indicates a short. Record the insulation resistance value in the Inspection Record. 8. Repeat Steps 4–7 at 1000 and 2500 Vdc. 9. Turn off the megohmmeter. 10. If the megohmmeter does not self-discharge, discharge phase connection to ground with a suitable grounding rod. Disconnect the megohmmeter. 11. Repeat this test between braid and pipe. 12. Reconnect bus wires to terminal block. 13. Reconnect the HWAT-ECO controller. 3. Circuit length verification (capacitance test) Connect the capacitance meter negative lead to both bus wires and the positive lead to the braid wire. Set the meter to the 200nF range. Multiply this reading by the Capacitance factor for the correct heating cable shown below to determine the total circuit length. Length (ft or m) = Capacitance (nF) x Capacitance factor (ft or m/nf) 28 Raychem-IM-H57548-HWATsystem-EN 16/08 9 Test Procedures Table 4: CAPACITANCE FACTORS Heating Cable HWAT-R2 Capacitance Factor ft/nF m/nF 5.8 1.8 Compare the calculated circuit length to the design drawings and circuit breaker sizing tables. Figure 19: Capacitance test 4. Power check The power output of self-regulating heating cable is temperature-sensitive and requires the following special procedure to determine its value: Important: Run hot water through the piping system before powering the HWAT-R2 heating cable. This will ensure the system is at a uniform pipe temperature. Dot not power the system when the pipe temperature is below 50F(10C). 1. Power the heating cable and allow it to stabilize for 2 hours, then measure current and voltage at the junction box. If a controller is used, refer to details below. 2. Measure the pipe temperature under the thermal insulation at several locations. 3. Calculate the power of the heating cable by multiplying the current by the input voltage and dividing by the actual circuit length. Volts (Vac) x Current (A) Power (w/ft or m) = Length (ft or m) The power calculated should be similar to the value generated by: Rated Power (w/ft or m) = Volts (Vac) x Rated Current Raychem-IM-H57548-HWATsystem-EN 16/08 29 9 Test Procedures Table 5: RATED CURRENT (A/FT OR M) Heating Cable HWAT-R2 Pipe Temperature 140˚F (60˚C) Rated Current (A/ft or m) .017 (.056) 5. Temperature test When testing an HWAT System for temperatures it is important to test in an appropriate sequence. Testing should start at the point of use closest to the water heater and progress out. Testing should be done after a minimum of 4 hours of no water usage. This will ensure that the temperatures indicated are not due to flow conditions. It is a good idea to turn off all cold water valves to eliminate the possibility of introducing cold water to the hot side via a cross connection. The following example illustrates a typical temperature test sequence for an HWAT System. 3 2 1 4 6 5 11 7 9 10 8 Figure 20: Typical temperature test sequence 30 Raychem-IM-H57548-HWATsystem-EN 16/08 9 9.2 Test Procedures Fault Location Tests There are three methods used for finding a fault within a section of heating cable: 1. Ratio method 2. Conductance method 3. Capacitance method 1. Ratio method The ratio method uses resistance measurements A at each end of the heating cable B to approxitaken mate the location of a bus wire short. A shorted heating cable could result in a tripped circuit breaker. If the resistance can be read on a standard ohm meter this method can also be used to find a fault Braid from a bus wire to the ground braid. This type of short would trip a GFPD and show a failedB reading. A Measure the bus-to-bus heating cable resistance at each end (measurement A and measurement B) of the suspected section. A B Figure 21: Cable resistance measurement test The approximate location of the fault, expressed as a percentage of the heating cable length from the front end, is: Fault location: D= A (A + B) x 100 Example: A = 1.2 ohms B = 1.8 ohms Fault location: D = 1.2 / (1.2 + 1.8) x 100 = 40% The fault is located 40% into the circuit as measured from the front end. To locate a low resistance ground fault, measure between bus and braid. Raychem-IM-H57548-HWATsystem-EN 16/08 31 9 Test Procedures A B Braid A B Figure 22: Low resistance ground-fault test The approximate location of the fault, expressed as a percentage of the heating cable length from the front end is: A Fault location: Example: D= A (A + B) B x 100 A = 1.2 ohms B = 1.8 ohms Fault location: D = 1.2 / (1.2 + 1.8) x 100 = 40% The fault is located 40% into the circuit as measured from the front end 2. Conductance method The conductance method uses the core resistance of the heating cable to approximate the location of a fault when the heating cable has been severed and the bus wires have not been shorted together. A severed cable may result in a cold section of pipe and may not trip the circuit breaker. Measure the bus-to-bus heating cable resistance at each end (measurement A and measurement B) of the suspect section. Since self-regulating cables are a parallel resistance, the ratio calculations must be made using the conductance of the cable. A B Figure 23: Cable resistance measurement Braid A 32 B Raychem-IM-H57548-HWATsystem-EN 16/08 9 Test Procedures The approximate location of the fault, expressed as a percentage of the heating cable length from the front end, is: Fault location: Example: D= 1/ A (1/A + 1/B) x 100 A = 100 ohms B = 25 ohms Fault location: D = (1/100) / (1/100 + 1/25) x 100 = 20% The fault is located 20% from the front end of the circuit. 3. Capacitance method This method uses capacitance measurement (nF) as described in "3. Circuit length verification (capacitance test)" on page 28, to approximate the location of a fault where the heating cable has been severed, or a connection kit has not been connected. Record the capacitance reading from one end of the heating cable. The capacitance reading should be measured between both bus wires twisted together (positive lead) and the braid (negative lead). Multiply the measured capacitance with the heating cable’s capacitance factor as listed in the following example: Example: HWAT-R2 = 16.2 nF Capacitance factor = 5.8 ft/nF Fault location = 42.2 nF x 5.8 ft/nF = 245 ft (75 m) from reading location As an alternative, capacitance values from each end. The ratio of one capacitance value taken from one end (A) divided by the sum of both A and B (A + B) and then multiplied by 100 yields the distance from the first end, expressed as a percentage of the total heating cable circuit length. See Table 4 on page 29, for capacitance factors. Fault location: Raychem-IM-H57548-HWATsystem-EN 16/08 C= A (A + B) x 100 33 9 9.3 Test Procedures Cable and Connection Continuity Test: To complete a continuity test it is best to start the installation with a power connection kit. A completed power connection kit allows for easier testing. The bus wires and braid can be temporarily connected together at the power connection end (Figure 24) and resistance can be tested at the other end as each additional component is added to the system. Procedure: 1. De-energize the circuit 2. Disconnect cable bus wires and ground wire 3. Temporarily connect cable bus wires and ground wire together with a wire nut (Figure 24) Figure 24: 4. Go to the end of the heating cable run and measure resistance using an ohm meter. 5. A resistance reading should be taken for each bus wire to braid and then bus wire to bus wire. Braid to A should equal Braid to B, A to B will be slightly higher. (Figure 25) Figure 25: 34 Raychem-IM-H57548-HWATsystem-EN 16/08 9 Test Procedures 6. If a higher reading is measured on one of the tests all connections are not completed and there is not continuity for one or both of the bus wires. 7. If resistance values of braid to A and braid to B are not within 20% of each other inspect all connection kits (splice, tee, and cross) between the power connection and the cable end that is being tested. 8. If resistance values of braid to A and braid to B are within 20% of each other the cable continuity is intact. Continue with system installation. 9. Repeat test procedures for all branch lines to verify entire heat tracing circuit. 10. After entire circuit passes continuity test, remove wire nut on power connection kit and connect to heat trace controller. Note: Readings can be taken at a previously installed RayClic power, splice, tee or cross connection by using the test ports available inside the component (see figure 26). Testing at a RayClic will only confirm continuity to the previous components; it will not verify continuity to the cable end seal. Figure 26: Raychem-IM-H57548-HWATsystem-EN 16/08 35 10 10 Troubleshooting Test ProceduresGuide Symptom Probable Causes Corrective Actio Low water temperature Insulation is wet, or missing. Remove wet insula with proper weathe HWAT-ECO controller lowered the pipe setpoint temperature because water heater is cold. Verify the HWAT-EC temperature, and s Ambient too low. Set the HWAT-ECO temperature. Improper voltage applied. Refer to the HWATto set the HWAT-EC Improper insulation thickness used. Contact your Penta confirm the design HWAT-ECO or ACS-30 was set incorrectly. Refer to the HWATor ACS-30 Program Cold water is being introduced into the hot water system. Verify that the plum Tripped circuit breaker See "Circuit breake Symptom Probable Causes Corrective Actio Low or no power output Low or no input voltage applied. Repair the electric The circuit is shorter than the design shows, due to splices or tees not being connected, or the heating cable having been severed. Check the routing drawings to refere tees. Locate and r recheck the power Improper component connection causing a high-resistance connection. Examine RayClic c loose wiring conne HWAT-ECO or ACS-30 set wrong or incorrectly wired. Refer to the HWAT (H57340) or ACS-3 settings. The heating cable has been exposed to excessive temperature, moisture or chemicals. Check the pipe tem power output of th Reduce pipe temp Thermal Managem Replace damaged Check the power o 36 Raychem-IM-H57548-HWATsystem-EN 16/08 10 Troubleshooting Guide Corrective Action ssing. Remove wet insulation and replace with dry insulation, and secure it with proper weatherproofing. owered the pipe ecause water heater is Verify the HWAT-ECO water heater setting, water heater temperature, and sensor placement; and correct as required. Set the HWAT-ECO or ACS-30 to the appropriate ambient temperature. ed. Refer to the HWAT-ECO Installation and Operation Manual (H57340) to set the HWAT-ECO to the correct voltage (208 or 240 Vac) ckness used. Contact your Pentair Thermal Management representative to confirm the design and modify as recommended. was set incorrectly. Refer to the HWAT-ECO Installation and Operation Manual (H57340) or ACS-30 Programming Guide (H58692) for the correct settings. oduced into the hot Verify that the plumbing fixtures and valves are operating properly. See "Circuit breaker trips" section of this Troubleshooting Guide. Corrective Action e applied. Repair the electrical supply lines and equipment. han the design or tees not being ing cable having Check the routing and length of heating cable (use “as built” drawings to reference actual pipe layout). Connect all splices or tees. Locate and replace any damaged heating cables. Then recheck the power output. connection nce connection. Examine RayClic connection kits for proper installation. Check for loose wiring connections and rewire if necessary. set wrong or Refer to the HWAT-ECO Installation and Operation Manual (H57340) or ACS-30 Programming Guide (H58692) for the correct settings. been exposed to , moisture or Check the pipe temperature. Verify heater selection. Check the power output of the heating cable per the design vs. actual. Reduce pipe temperature if possible or contact your Pentair Thermal Management representative to confirm design. Replace damaged heating cable. Check the pipe temperature. Check the power output of heating cable. Raychem-IM-H57548-HWATsystem-EN 16/08 37 10 Troubleshooting Guide Symptom Probable Causes Corrective Action Circuit breaker trips Circuit breaker is undersized. Recheck the design f exceed the maximum the circuit breaker, if Connections and/or splices are shorting out. Visually inspect the R Physical damage to heating cable is causing a direct short. Check for damage ar have been maintenan cable. Bus wires are shorted at the end. Check the end seal to short is found, the he by excessive current Circuit lengths too long Separate the circuit i circuit lengths. Nick or cut exists in heating cable or power feed wire with moisture present or moisture in connections. Replace the heating c connections and splic resistance. GFPD is undersized (5 mA used instead of 30 mA) or miswired. Replace undersized G instructions. Symptom Probable Causes Corrective Action Low or inconsistent insulation resistance Nicks or cuts in the heating cable. If heating cable is no length for damage, e valves. If the system i one-by-one to isolate Short between the braid and heating cable core or the braid and pipe. 38 Arcing due to damaged heating-cable insulation. Replace damaged he Moisture present in the components. If moisture is present all conduit entries ar cannot enter power c wires are exposed to cable. (Drying the hea output of the heating Test leads touching the junction box. Clear the test leads f Raychem-IM-H57548-HWATsystem-EN 16/08 10 Troubleshooting Guide Corrective Action rsized. Recheck the design for startup temperature and current loads. Do not exceed the maximum circuit length for heating cable used. Replace the circuit breaker, if defective or improperly sized. ices are shorting out. Visually inspect the RayClic connection systems. Replace if necessary. ating cable is causing Check for damage around the valves and any area where there may have been maintenance work. Replace damaged sections of heating cable. at the end. Check the end seal to ensure that bus wires are not shorted. If a dead short is found, the heating cable may have been permanently damaged by excessive current and may need to be replaced. Separate the circuit into multiple circuits that do not exceed max circuit lengths. ating cable or power present or moisture Replace the heating cable, as necessary. Dry out and reseal the connections and splices. Using a megohmmeter, retest insulation resistance. mA used instead of Replace undersized GFPD with 30 mA GFPD. Check the GFPD wiring instructions. Corrective Action ating cable. d and heating cable pe. If heating cable is not yet insulated, visually inspect the entire length for damage, especially at elbows and flanges and around valves. If the system is insulated, remove the connection kits one-by-one to isolate the damaged the section. heating-cable Replace damaged heating-cable sections. components. If moisture is present, dry out the connections and retest. Be sure all conduit entries are sealed, and that condensate in conduit cannot enter power connection boxes. If heating-cable core or bus wires are exposed to large quantities of water, replace the heating cable. (Drying the heating cable is not sufficient, as the power output of the heating cable can be significantly reduced.) junction box. Clear the test leads from junction box and restart. Raychem-IM-H57548-HWATsystem-EN 16/08 39 11 11 Troubleshooting TroubleshootingGuide Guide Pentair Thermal Management Industrial Heat-Tracing Installation and Inspection Record Test Date:_______ Facility: Commission Inspection date: Inspected by (Name): Panel and Circuit Breaker Number: Water heater/mixing valve temperature setting (°F) Designed circuit length (ft): Capacitance test nF: Cap factor (Table 4): nF X Cap Factor= (ft/m) HWAT-ECO setting: Heating cable type: Voltage: Ambient Temp: Set point: Maintain Power factor Test Date: Visual Inspection Confirm 30-mA ground-fault device (proper rating/function) Confirm all electrical connections in the RayClic and HWAT-ECO are tight and wires secure. Visual inspection inside connection boxes for overheating, corrosion, moisture, loose connections and other problems. Proper electrical connection, ground, and bus wires insulated over full length. Correct thermal insulation used for each pipe size (Reference Table 2) Damaged or missing thermal insulation for the entire hot water piping system. Covered end seals, splices, and tees properly labeled on insulation. Check HWAT-ECO for moisture, corrosion, setpoint, switch operation Insulation resistance test Bus to braid (Test A) 500 Vdc 1000 Vdc 2500 Vdc Braid to pipe (Test B) 500 Vdc 1000 Vdc 2500 Vdc Power and temperature check Panel voltage (V) Circuit voltage (V) Circuit end (V) Circuit amps after 2 hours (A) Pipe temperature (°F) 40 Raychem-IM-H57548-HWATsystem-EN 16/08 megohm llation and Inspection Record 11 Troubleshooting Guide Test Date:_________ (Circuit Number) ) nction) HWAT-ECO are tight ating, corrosion, nsulated over eference Table 2) hot water piping system. n insulation. switch operation megohm megohm Raychem-IM-H57548-HWATsystem-EN 16/08 megohm megohm 41 42 Raychem-IM-H57548-HWATsystem-EN 16/08 Raychem-IM-H57548-HWATsystem-EN 16/08 43 WWW.THERMAL.PENTAIR.COM NORTH AMERICA EUROPE, MIDDLE EAST, AFRICA Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 [email protected] Tel: +32.16.213.511 Fax: +32.16.213.603 [email protected] ASIA PACIFIC LATIN AMERICA Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 [email protected] Tel: +1.713.868.4800 Fax: +1.713.868.2333 [email protected] Pentair, RayClic, and HWAT are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2004–2016 Pentair. THERMAL MANAGEMENT SOLUTIONS P000000272 Raychem-IM-H57548-HWATsystem-EN 16/08 HWAT-ECO INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEM ELECTRONIC CONTROLLER THERMAL MANAGEMENT SOLUTIONS WWW.THERMAL.PENTAIR.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK HAZARD Raychem HWAT Systems must be installed correctly to ensure proper operation and to prevent shock and fire. Read these important warnings and carefully follow all the installation instructions. • To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Pentair Thermal Management requirements, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit breakers. • Approvals and performance are based on the use of Pentair Thermal Management parts only. Do not substitute parts or use vinyl electrical tape. • Bus wires will short if they contact each other. Keep bus wires separated. • Connection kits and heating cable ends must be kept dry before and during installation. • The black heating cable core is conductive and can short. They must be properly insulated and kept dry. • Damaged bus wires can overheat or short. Do not break bus wire strands when preparing the cable for connection. • Damaged heating cable can cause electrical arcing or fire. Do not use metal attachments such as pipe straps or tie wire. Use only Pentair Thermal Management approved tapes and cable ties to secure the cable to the pipe. • Do not attempt to repair or energize damaged cable. Remove damaged cable at once and replace with a new length using the Raychem RayClic-S splice kit. Replace damaged connection kits. • Use only fire-resistant insulation which is compatible with the application and the maximum exposure temperature of the system to be traced. ii EN-RaychemHWATECOcontroller-IM-H57340 03/13 Table of Contents 1 2 3 4 5 6 7 General Information 1 1.1 Use of the Manual 1 1.2 Features 1 1.3 Technical Data 3 1.4 Care and Maintenance 7 1.5 HWAT Heating Cables 7 Installation 9 2.1 Installing the Controller 9 2.2 Wiring the Controller 13 Programming the Controller 26 3.1 Programming Overview 26 3.2 Initializing the Controller 27 3.3 Advanced Programming 33 Error/Alarms and Troubleshooting 45 Pre-Defined Programs 50 Heat-Up Cycle Graphs 52 Cool-Down Graph 54 EN-RaychemHWATECOcontroller-IM-H57340 03/13 iii B A C F TH E D IN H STA ELEC OT WAT LLATION HW TRO ER T AND ATNIC EMP OPE EC CON ERA RAT O TRO TURE ION LLER MA MAN INTE UAL NAN FOR CE S YSTE M RM AL M AN AG EM EN TS OL UT E ION S WW W.T H ER MA L.P EN T Item Qty A 1 B 1 C 2 D 2 E 1 F 1 AIR .CO M Description HWAT-ECO controller Temperature sensor with 13 ft (4 m) cable Mounting screws Mounting washers Aluminum tape Manual Figure 1: Kit contents iv EN-RaychemHWATECOcontroller-IM-H57340 03/13 6.5" (165 mm) A B C D E 3.4" (85 mm) F G H 2 ea - 1/2" conduit entries To water heater sensor To HWAT-ECO network/alarm entries A Power supply (green LED) B Power to heating cable (green LED) C Heat-up cycle (green LED) - increased risk of scalding D Pipe Temperature alarm (requires installed sensor) (green LED) E Alarm (red LED) F Escape, backspace; NO; or display maintain temperature setpoint G Arrow keys: to change menu selection or position the cursor H Confirm selection, new value or YES Figure 2: HWAT-ECO controller EN-RaychemHWATECOcontroller-IM-H57340 03/13 v vi EN-RaychemHWATECOcontroller-IM-H57340 03/13 1 1.1 General Information Use of the Manual This manual covers the installation and operation of the HWAT-ECO controller and must be used with the following additional documents: • HWAT System Product and Selection Design Guide (H57538) • HWAT System Installation and Operation Manual (H57548) Important: For the Pentair Thermal Management warranty and agency approvals to apply, the instructions included in this manual and product packages must be followed. 1.2 Features The Raychem HWAT-ECO controller is designed for operation with HWAT-Y2 and HWAT-R2 selfregulating heating cables. The HWAT-ECO controller provides the following features: • Flexible temperature control of hot water temperature maintenance systems. • Integrated function that lowers the maintain temperature during low use hours to save energy. • Heat-Up cycle function that increases the water temperature in a stagnant pipe. EN-RaychemHWATECOcontroller-IM-H57340 03/13 1 1 General Information • Building Management System (BMS) interface that receives a DC voltage to set the maintain temperature. • Alarm relay to signal power, temperature, or communication problems. • Pipe temperature monitoring, low temperature alarm and high temperature cut-out. • Master/slave function that allows one HWAT-ECO to control up to eight additional HWAT-ECO controllers. • 9 pre-defined programs that can be customized by the user. 2 EN-RaychemHWATECOcontroller-IM-H57340 03/13 1 1.3 General Information Technical Data Use Only for HWAT-Y2 and HWAT-R2 heating cables Maintain temperature setpoint 105˚F (40˚C) to 140˚F (60˚C) Hot water piping ambient temperature 60˚F (15˚C) to 80˚F (25˚C) Controller ambient temperature 40˚F (5˚C) to 105˚F (40˚C) ambient Switching capacity 24 A 208/240 Vac max. Operating voltage 208/240 (±10%), 60 Hz Internal power consumption 2.5 W Circuit protection (not provided with HWAT-ECO controller) Max. 30 A with 30 mA ground-fault protection Power terminal block 16–10 AWG (1.5–4 mm2) Use copper conductors only Internal temperature alarm 150˚F (65˚C) BMS control voltage 0–10 Vdc BMS cable maximum length 328 ft (100 m) EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 1 General Information Alarm contacts Max. 24 Vdc or 24 Vac, 1A, SPST, voltage free, NO/NC Alarm events • Loss of power • Controller reinitialized • Internal controller temperature too high • Lost date and time settings • Internal failure • Pipe temperature too high (optional) • Pipe heater temperature too low (optional) • Network error Power correction factor To increase or decrease your actual pipe maintain temperature or adjust for plastic pipe. Pipe temperature sensor Thermistor with 13 ft (4 m) lead provided. A PT100 RTD may be optionally used. Max length is 328 ft (100 m) 4 EN-RaychemHWATECOcontroller-IM-H57340 03/13 1 General Information Electromagnetic Complies to EN 5014-1 Compatibility (EMC) for emission and 60730-1 for immunity Real time clock Leap year correction Clock accuracy ±10 minutes per year Enclosure rating NEMA 12 (IP54) – indoor use only Enclosure material ABS Mounting Wall mount with two screws or optional DIN rail Conduit entries 2 ea – 1/2 in conduit entries Cable gland 3-hole grommet Maximum cable size: • 2-wire: 20 AWG (0.5 mm2) • 4-wire: 24 AWG (0.2 mm2) Default programs 9 pre-defined programs that can be customized by user Program settings 48 1/2-hour time blocks of the following program settings: Off, Economy, Maintain and Heat-Up cycle EN-RaychemHWATECOcontroller-IM-H57340 03/13 5 1 General Information Password 4-digit password protection Master/slave Master is selectable in the controller, up to 8 slaves can be connected Master/slave cable 2-wire, min. 24 AWG (0.2 mm2) twisted pair and insulation of 300 V, Max length cable is 100 m Parameters in memory All parameters are stored in nonvolatile memory, except time and date Clock backup time Rechargable Lithium battery. Battery will retain time and date for up to 30 days when power is lost Approvals 80BJ 6 Type 12 Energy Management Equipment (for use with HWAT-R2 and HWAT-Y2 heating cables only.) Weight 2 lbs (1 kg) Size 6.5 in x 3.4 in x 2.8 in (165 mm x 85 mm x 71 mm) EN-RaychemHWATECOcontroller-IM-H57340 03/13 1 1.4 General Information Care and Maintenance To clean the HWAT-ECO use a damp cloth. Do not use solvents. Do not pour water directly on the device. Do not use a water hose or high pressure cleaner. Important: In case of questions or product failure, please contact your Pentair Thermal Management representative, or call Pentair Thermal Management at 800-545-6258. 1.5 HWAT Heating Cables Maintain temperature Depending on the ambient temperature and voltage, HWAT-Y2 is designed to maintain temperatures up to 125˚F (52˚C), and HWAT-R2 is designed to maintain temperatures up to 140˚F (60˚C). Installing the heating cables Install the HWAT heating cable system as instructed in the HWAT System Installation and Operation Manual (H57548). The controller must be installed by a professional electrical installer familiar with electrical safety codes and practices. EN-RaychemHWATECOcontroller-IM-H57340 03/13 7 1 General Information Ground-fault protection WARNING: To minimize the danger of fire from ­sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of approvals agencies, Pentair Thermal Management and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. The HWAT-ECO does not include ground-fault protection. Pre-Installation testing Prior to installing the HWAT-ECO controller, perform the insulation resistance (Megger) test and circuit length verification (Capacitance) test on the heating cable as detailed in the HWAT System Installation and Operation Manual (H57548). 8 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 2.1 Installation Installing the Controller Install the controller in an indoor, dry, clean, accessible location. If using the optional pipe temperature sensor, make sure you install the controller within 328 ft (100 m) of where you want to monitor the pipe temperature. Opening the controller WARNING: To prevent shock, always switch off the power supply (circuit breaker) before opening the controller. The HWAT-ECO has a removable front cover. Both the cover and the box have electronic parts and are connected to each other by a 14-pin connector. First unscrew the four screws in the cover. Carefully pull the cover straight out, not sideways! EN-RaychemHWATECOcontroller-IM-H57340 03/13 9 2 Installation Figure 3: Opening the controller Wall mounting the controller Mount the controller using either of the options below: 1. You can mount the controller to the wall using the two supplied screws and sealing rings in the two holes located inside the bottom part of the controller. 10 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation 5.9" (148 mm) 1.7" (43 mm) B A TEMP BMS Figure 4: Hole locations for mounting with screws EN-RaychemHWATECOcontroller-IM-H57340 03/13 11 2 Installation 2. Optionally you can mount the controller using DIN 35 Rail mounting. Optional Din Rail Mount (Rail not provided) Mounting Removing Press tab to remove box Figure 5: Mounting with DIN 35 Rail 12 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 2.2 Installation Wiring the Controller The diagram below shows the arrangement of the terminal blocks for power, alarm, pipe temperature sensor, BMS and network. HWAT-ECO General Arrangement Power terminal block Ø1 Ø2 Ø1 Ø2 HWAT Line Alarm terminal block Sensor, BMS, and network terminal block Ground B A TEMP BMS Figure 6: General arrangement for terminal blocks EN-RaychemHWATECOcontroller-IM-H57340 03/13 13 2 Installation The diagram below shows the connection of a single controller (without optional water heater sensor, BMS, network and alarm connections). Important: Tighten the terminal screws to 6 inchlbs. (0.68 N-m) Wiring diagram for HWAT-ECO To HWAT heating Incoming power cable 208/240 Vac Max Ground B A TEMP BMS 1/2" Conduits Ø RayClic-PC Max. 30 A ground fault Ø circuit breaker G 208-240 Vac HWAT heating cable Figure 7: Connecting a single controller (w/o sensor, BMS, network and alarm connections) 14 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation For controlling multiple HWAT circuits with the same programming parameters (i.e. voltage, maintain temperature, ambient temperature, economy temperature), connect the heating cable output relay to an external contactor coil(s). HWAT-ECO internal relay Ground Line voltage 208 V or 240 V Panel energized light ø1 ø2 ø3 N Three-pole main CB *Contactor coil (208 or 240 V) Three-pole main contactor HWAT-ECO internal switch Two-pole with 30-mA ground-fault trip (208/240 Vac) * Install contactor manufacturer’s recommended snubber circuit across the coil Power connection Heating cable End seal HWAT heating cable Two-pole with 30-mA ground-fault trip (208/240 Vac) HWAT heating cable Braid/pipe Figure 8: Multiple HWAT circuits connection Pipe temperature sensor (optional usage) Installation of the pipe temperature sensor is optional. If installed, the HWAT-ECO provides low temperature alarm and high temperature cut-out. The temperature sensor should be connected to a single or master controller only. Connect both wires EN-RaychemHWATECOcontroller-IM-H57340 03/13 15 2 Installation Alarm, Sensor, and BMS terminals B A TEMP PL6 BMS Alarm contact of the temperature sensor to the TEMP terminal in the controller (PL4). The sensor wires do not have a special polarity. To connect a wire, use a screwdriver to push down the orange tab on the side of the terminal. Put the wire into the hole and release the orange tab. Standard temperature sensor PL5 PL3 PL4 B A TEMP BMS PT100 sensor (2 wire) PL5 PL3 PL4 B A TEMP BMS short for PT100 Figure 9: TEMP terminal location and sensor wiring Optionally, PT100 RTDs from the water heater can be used. To install a PT100 sensor first connect a jumper between the terminals indicated in Figure 9, then connect the two wires from the RTD. If you are using a three wire sensor, remove the compensation lead and only connect the two measurement wires. 16 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation The pipe temperature sensor must be placed on 1-inch diameter pipes or larger, installed opposite from the HWAT heating cable to accurately measure the pipe temperature. The temperature sensor cable is 13 ft 3 in (4 m) in length, however the user can extend the cable up to 328 ft (100 m) by splicing a length of 300 volt, 18 AWG (0.75 mm2) cable. Temperature sensor Insulation 180° Heating cable Hot water out HWAT-Y2 HWAT-R2 Tempered water out A Hot water in Water heater B mixing valve Cold water in Figure 10: Positioning temperature sensor (optional) EN-RaychemHWATECOcontroller-IM-H57340 03/13 17 2 Installation Alarm wiring (optional) Alarm, Sensor, and BMS NC O NO terminals PL6 B A TEMP Alarm contact The alarm contact (24 Vac, 24 Vdc, 1A) inside the controller can be used to switch an external device. The contact is closed during operation and open during an alarm or ­during loss of power. In a network, all alarm contacts should be connected in series. BMS Figure 11: Connecting the alarm contact The alarm terminal (PL6) is located in the upper right corner of the controller and has the text “alarm contact” next to it. To connect a wire, use a screwdriver to push down the orange tab on the side of the terminal. Put the wire into the hole and release the orange tab. The wires used for the alarm contact should be rated for 300 V. See “Chapter 4, Error/ 18 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation Alarms and Troubleshooting” for more information about alarm conditions. The alarm contact is designed as a fail safe mode and can be wired for normally open (NO) or normally closed (NC) operation. The following table summarizes the relay positions in the different controller states: Position NC NO Power Off Open Closed Power On Closed Open Alarm Mode Open Closed Network The Master/slave function allows one HWAT-ECO to control up to eight additional HWAT-ECO controllers. Connect all HWAT-ECO controllers to each other in parallel using the A and B inputs on terminal (PL3). This means that several controllers will have two wires in one hole. The wire should be a twisted pair and be rated for 300 V. The total maximum length of this cable between all controllers is 328 ft (100 m). Be careful not to mix A and B connections. To connect a wire, use a screwdriver to push down the orange tab on the side of the terminal. Put the wire into the hole and release the orange tab. EN-RaychemHWATECOcontroller-IM-H57340 03/13 19 2 Installation MASTER BMS OPTIONAL BMS B A TEMP BMS TO SLAVE 2 TEMP WATER HEATER SENSOR NETWORK WIRE B A SLAVE 1 Figure 12: Networking controllers together The diagram below shows the connection of multiple ­controllers (with optional RS-485 connections). 20 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation Master Slave 1 Slave 2 RS-485 RS-485 Alarm L L 208/240V L L 208/240V BMS LL 208/240V HWAT heating cable HWAT heating cable Sensor HWAT heating cable Figure 13: Connecting multiple controllers (with RS-485) max. 20 AWG (0.5 mm2) max. 24 AWG (0.2 mm2) When multiple controllers are networked and you are using BMS and Alarm functions, you must use a 4-wire conductor. Figure 14: Combine alarm and BMS wire in 4-wire cable Important: For master/slave combination with alarm function, the alarms are connected in series by a RS485 wire. Since the cable gland grommet has only 3 holes, you must combine the alarm wire and the BMS wire in a 4-wire cable. EN-RaychemHWATECOcontroller-IM-H57340 03/13 21 2 Installation Building Management System (BMS) (optional) See Table 5 on page 39. Alarm, Sensor, and BMS terminals PL6 PL3 PL4 PL5 B A TEMP BMS Alarm contact The BMS input of the HWAT-ECO is a 0 to 10-Vdc input. If the controller is programmed to have a BMS connection, the BMS controls the temperature setpoint. Using 300-V rated cable, connect the BMS signal wire to terminal (PL5). Connect the ground wire to the “–” and the 0-10 V output to the “+” terminal. 0-10v ground BMS Figure 15: Connecting the BMS 22 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation Figure 16 shows the connection of a single controller (with optional sensor, BMS and alarm connections). Master Alarm BMS LL 208/240V Sensor RayClic-PC HWAT heating cable Figure 16: Single controller connection (with sensor, BMS, and alarm connections) EN-RaychemHWATECOcontroller-IM-H57340 03/13 23 2 Installation Closing the controller Position the cover in front of the wall-mounted box. The separation sheet inside the controller will help guide the cover and the connector. Push the cover onto the box. Note that the connector pins will offer some resistance. Put the screws in place and tighten to 10 inch-lbs (1.13 N-m). Figure 17: Closing the controller 24 EN-RaychemHWATECOcontroller-IM-H57340 03/13 2 Installation 02-11-2012 Maintain 09:30 * A B C D E F G H A Power supply (green LED) B Power to heating cable (green LED) C Heat-up cycle (green LED) - increased risk of scalding D Pipe temperature alarm (requires installed sensor) (green LED) E Alarm (red LED) F Escape, backspace; NO; or display maintain temperature setpoint G Arrow keys: to change menu selection or position the cursor H Confirm selection, new value or YES Figure 18: Controller display EN-RaychemHWATECOcontroller-IM-H57340 03/13 25 3 3.1 Programming the Controller Programming Overview Display functions Quickstart Any key to start The display has two lines with 16 characters each. The display shows the following text on start up: The HWAT-ECO has six buttons: Up/Down/Left/Right arrows Escape (ESC) button Enter button You can program the HWAT-ECO by simply executing the Quickstart program which is suitable for normal operations. In addition, advanced programming can be used to modify initial settings, set additional features such as BMS and Network Master, reinitialize the entire controller, or customize the pre-defined programs. 26 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 3.2 Programming the Controller Initializing the Controller The first time you power up the controller, you must ­execute the Quickstart program to set the initial settings. Once initialized continue to power the controller for at least 6 hours to charge the internal battery. Table 1: QUICKSTART MENU Time and date Year Month Day Hour Minutes Select Year Select Month Select Day Select Hour Select Minutes Cable type HWAT-R2 “Press Enter for this cable type.” HWAT-Y2 “Press Enter for this cable type.” 208 Vac “Press Enter for this voltage type.” 240 Vac “Press Enter for this voltage type.” English “Press Enter for this unit type.” Metric “Press Enter for this unit type.” Voltage select Units Ambient temp. Maintain temp. Economy temp. “Enter ambient temp.” “Enter maintain temp. setpoint” “Enter economy temp. setpoint” EN-RaychemHWATECOcontroller-IM-H57340 03/13 27 3 Programming the Controller Table 1: QUICKSTART MENU Default program “Scroll to program and press Constant Enter.” Apartments Family home Prison Hospital Nursing home Hotel Sports center Convales. home During the Quickstart you can press the ESC button to go back to a previous menu. On startup the display will show the following text: Quickstart Any key to start Press a key to start, and the following menus appear: Time and Date Use the up/down arrows to select the year and press Enter. Then, select and enter the month, day, hour, and minutes. The time and date is contained in volatile memory, and is maintained during power outages by an internal rechargeable battery. Power the HWAT-ECO for at least 6 hours to charge the battery. 28 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller Cable type Use the up/down arrows to select HWAT-Y2 or HWAT-R2 cable used in your installation. Press Enter. Voltage Use the up/down arrows to select 208 V or 240 V (applied voltage to the cable). Press Enter. Units Use the up/down arrows to select English or Metric units. Press Enter. Ambient temperature The ambient temperature is the air temperature surrounding the hot water piping where the heating cable is installed. Use the up/down arrow keys to select from 60˚F (15˚C) to 80˚F (25˚C). Press Enter. If your design requires that the ambient temperature is significantly different from one location to another, you will need an HWAT-ECO controller for each ambient ­condition. Maintain temperature The maintain temperature setpoint is the water temperature that you set for normal use. Use the up/ down arrow keys to select the temperature. EN-RaychemHWATECOcontroller-IM-H57340 03/13 29 3 Programming the Controller The minimum temperature is 105˚F (40˚C) or the economy temperature, whichever is higher. The maximum temperature depends on cable type, voltage and ambient temperature. The programmed maintain temperature will display if you press the ESC button once the system is in operation. Table 2: MAXIMUM MAINTAIN TEMPERATURE (208-VOLT) Ambient temperature Heating cable 60˚F(15˚C) 70˚F(20˚C) 80˚F(25˚C) HWAT-Y2 120˚F (49˚C) 125˚F (52˚C) 125˚F (52˚C) HWAT-R2 140˚F (60˚C) 140˚F (60˚C) 140˚F (60˚C) Table 3: MAXIMUM MAINTAIN TEMPERATURE (240-VOLT) Ambient temperature Heating cable 60˚F(15˚C) 70˚F(20˚C) 80˚F(25˚C) HWAT-Y2 120˚F (49˚C) 125˚F (52˚C) 125˚F (52˚C) HWAT-R2 140˚F (60˚C) 140˚F (60˚C) 140˚F (60˚C) Economy temperature The economy temperature setpoint is the water temperature for periods during which hot water is not usually used (at night) or when a lot of hot water is used (peak period). Use the up/down arrows to select 30 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller the temperature. The minimum temperature is 105˚F (40˚C) and the maximum temperature is the selected maintain temperature. Default programs The HWAT-ECO has 9 pre-defined programs. (See “Chapter 5, Pre-Defined Programs” for more information.) Use the up/down arrows to select a predefined program. Press Enter. HWAT-ECO takes a few seconds to copy the pre-defined program to the internal memory. During this time a row of dots will show in the display. Pipe temperature This function also ensures that the delivered water temperature is not lower than the desired maintain temperature. Completing initialization The controller will start automatically when you finish selecting your Quickstart options. Additional settings are available in the Setup menu for advanced installations. See section 3.3 on page 33 for more information. Press Enter to start the controller. If you press the ESC button, you can retrace all menu items to check the settings. After starting the controller the display shows date, time, temperature setting and a “*” to EN-RaychemHWATECOcontroller-IM-H57340 03/13 31 3 Programming the Controller indicate that the controller is unlocked. If you wish to lock (password protect) the controller, see section 3.3.2.6 for instructions. Displaying Maintain Temperature Setpoint After finishing the Quickstart, the display will show the date, time, temperature mode and a star to indicate that the controller is unlocked. 02-11-2013 Maintain 09:13 While in operating mode, press ESC to view a bar graph that shows the maintain temperature setpoint. To enter the programming menu, press any other key. The controller will exit the menu automatically after five seconds of key inactivity. Figure 19: Bar graph Displaying Pipe Temperature When the optional pipe temperature sensor is connected, the controller will display date and time as above and alternate between temperature mode and pipe temperature. 32 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller 02-11-2013 Pipe T: 110°F 3.3 09:13 * Advanced Programming Advanced programming options are also available. Table 4 and the remainder of this section outline the advanced programming options that include modifying initial settings, setting additional features such as BMS and Network Master, reinitializing the entire controller, or customizing the pre-defined programs. EN-RaychemHWATECOcontroller-IM-H57340 03/13 33 3 Programming the Controller Table 4: ADVANCED PROGRAMMING MENU 1 Time and Date 1 Year 2 Month 3 Day 4 Hour 5 Minutes Select Year Select Month Select Day Select Hour Select Minutes 2 Setup (enter password if Lock is ON) 1 Main Temp “Enter maintain temp. setpoint” 2 Economy Temp “Enter economy temp. setpoint” 3 Ambient Temp “Enter ambient temp.” 4 Power Correction Selectable 5 Lock Lock/unlock Setup and Timer menus 6 BMS Select Yes/No 7 Network Master Select Yes/No 8 Reinitialize Select Yes/No 9 Short heater Select Yes/No 10 LTA (Low Temp Alarm) 1. Set Status 2. Set Temperature 3. Set Alarm Filter Time 4. Set Deadband Select Yes/No Enabled or Disabled 95°F (35°C) min 5-30 Minutes 4-18°F (2-10°C) 11 HTC (High Tem. Cut Out) 1. Set Status 2. Set Temperature 3. Set Alarm Filter Time 4. Set Deadband Enabled or Disabled Maximum 205°F 10-30 Minutes 4-18°F (2-10°C) 34 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller Table 4: ADVANCED PROGRAMMING MENU 3 Timer (enter password if Lock is ON) 1 Default program 2. Edit program Monday Tuesday Wednesday Thursday Friday Saturday Sunday 4 Holiday 5 Info Constant Apartments Family home Prison Hospital Nursing home Hotel Sports Center Convalesc. home Edit timer for Monday Edit timer for Tuesday Edit timer for Wednesday Edit timer for Thursday Edit timer for Friday Edit timer for Saturday Edit timer for Sunday On Off xxDays off Show firmware version number + Cable type + Sensor temp. Time and Date Use the up/down arrows to select the year and press Enter. Then select and set the month, day, hour and ­minutes. EN-RaychemHWATECOcontroller-IM-H57340 03/13 35 3 Programming the Controller Setup When Lock is on (no star in the lower right corner) enter a password to access the setup menu. The controller locks again after 60 seconds of inactivity. When Lock is off the following menus are directly ­accessible. 1. Maintain temperature The maintain temperature setpoint is the water temperature that you set for normal use. Use the up/ down arrows to select the temperature. The minimum temperature is 105˚F (40˚C) or the economy temperature, whichever is higher. The maximum temperature depends on cable type, pipe diameter, insulation thickness and ambient temperature. 2. Economy temperature The economy temperature setpoint is the water temperature for periods during which hot water is not usually used (at night) or when a lot of hot water is used (peak period). Use the up/down arrows to select the temperature. The minimum temperature is 105˚F (40˚C) and the maximum temperature is the selected maintain temperature. Press Enter. 3. Ambient temperature The ambient temperature is the air temperature surrounding the pipes where the heating cable is 36 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller installed. Use the up/down arrows to select from 60˚F (15˚C) to 80˚F (25˚C). Press Enter to confirm. If your design requires that the ambient temperature is significantly different from one location to another, you will need an HWAT-ECO controller for each ambient condition. 4. Power correction The power correction factor can be selected to increase or decrease your actual pipe maintain temperature or to adjust for using HWAT heating cables on rigid plastic pipes. The power correction factor can be adjusted from 0.6 to 1.40, increasing or decreasing the percent time the heating cable is powered during the duty cycle. For installation on rigid plastic pipe set the power factor at: HWAT-Y2: 1.20 HWAT-R2: 1.25 5. Lock (password) Use the up/down arrows to select Lock On/Off and press Enter. If you select ‘On’, you must enter a password using the left/right and up/down arrow buttons to select a 4-digit password. Press Enter. You will need to remember your 4-digit password whenever you wish to unlock the controller for EN-RaychemHWATECOcontroller-IM-H57340 03/13 37 3 Programming the Controller reprogramming. Once you unlock and reprogram, you will need to relock by entering your password. If Lock is On, the Setup and Timer menus are protected by the password. After you enter the password, the controller remains unlocked until five minutes of key inactivity or until you select Lock ‘On’ again. 6. Building Management System (BMS) You can activate the Building Management System option using this menu. When set to “Yes” the controller responds only to the voltage applied to the BMS terminal. For voltages ≤ 4 Vdc: heating cable is OFF. For voltages between 4.1 Vdc and 6.4 Vdc: maintain temperatures are set as indicated in Table 5. For voltages > 6.4 Vdc: 100% power is applied to the heating cable. See "Building Management System (BMS) (optional)" on page 22 for installation information. If Water heater is ON, it overrules the BMS temperature setting if necessary. 38 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller Table 5: BMS VOLTAGE INPUT Temp °F (°C) >147 (>64) 147 (64) 140 (60) 131 (55) 122 (50) 113 (45) 106 (41) Off HWAT-Y2 X X X X X HWAT-R2 X X X X X X X X U-BMS/U-GLT (VOLT) >6.4 6.4 6 5.5 5 4.5 4.1 0 7. Network Master In large installations where more than one HWATECO controllers are connected to each other, you must select one controller as the Master. This controller should be fully programmed and all slave controllers will use the Master settings. The master controller sends commands to all slave controllers to switch them ON or OFF. The master program is used for all controllers as follows: Slave controllers on the same phase (max. three controllers) will have a delayed ON and OFF. This way the start-up current of the cable will never occur at the same moment for these controllers (A, B and C). Slave controllers connected to a different phase will switch at the same time (1, 2 and 3). EN-RaychemHWATECOcontroller-IM-H57340 03/13 39 3 Programming the Controller After selecting “Master: Yes”, the slave controllers will initialize and show: :Slave: “x y” x= phase number (1 to 3) y= slave identification (A, B and C) The master controller is always 1 A, the slave controllers will get their number and identification automatically. Always check afterwards if all controllers have unique id-numbers, if not, check the RS485 cables and repeat this procedure. 8. Reinitialize To Reinitialize all settings back to the factory settings (except time and date), set the “Reinitialize” menu to “Yes.” 9. Short Heater This feature allows you to activate a low current alarm: Yes: Allows low current such as when used as a demonstration, or to control a contactor. In this mode there is no low current alarm. No: Generates low current alarm when measured current is less that 300 mA. 10. LTA (Low Pipe Temperature Alarm) When the optional pipe temperature sensor option is installed, the HWAT-ECO controller monitors the temperature of the hot water distribution pipes 40 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller where the sensor is installed and can generate a low pipe temperature alarm. 1. Set Status: Enabled or Disabled 2. Set temperature: –– Minimum: 95°F (35°C) –– Maximum: < Maintain (or Economy) 3. Set Alarm filter time: 5–30 minutes 4. Set deadband: 4–18°F (2–10°C), 9°F (5°C default) 11. HTC (High Temperature Cut-Out) When the optional pipe temperature sensor option is installed, the HWAT-ECO controller monitors the temperature of the hot water distribution pipes where the sensor is installed and a high temperature cut-out can be set. High Temperature Cut-out: Minimum: > set point Maximum: 205°F (96°C) Alarm filter: 5–30 minutes (default 10) Dead band: > 5°F (3°C) default 0°F(6°C) Timer The Timer feature lets you re-program any of the pre-defined programs to suit your personnel requirements. Reprogramming is done graphically in 1/2 hour time blocks. A block can be set to Heat-Up EN-RaychemHWATECOcontroller-IM-H57340 03/13 41 3 Programming the Controller cycle, Maintain temperature, Economy temperature, or Off. See “Chapter 6, Heat-Up Cycle Graphs” for more information. Edit pre-defined programs To edit a program, switch Lock to Off. If password protected, you will need to enter the password to unlock the controller. After you enter the password, the controller remains unlocked until five minutes of key inactivity or the Lock ‘On’ is selected again Select temperature Use the up/down arrows to select the temperature: = Heat-up cycle = Maintain temperature = Economy temperature = Off Figure 20: Timer block options Select time block Use the left/right arrows to select the time block. Timer programming example from 00:00 to 08:00: 42 EN-RaychemHWATECOcontroller-IM-H57340 03/13 3 Programming the Controller .......... 00:00 – 00:30: Heat-up cycle 00:30 – 01:00: Heat-up cycle 01:00 – 01:30: Heat-up cycle 01:30 – 02:00: Heat-up cycle 02:00 – 02:30: Off 02:30 – 03:00: Off 03:00 – 03:30: Off 03:30 – 04:00: Off 04:00 – 04:30: Off 04:30 – 05:00: Economy 05:00 – 05:30: Economy 05:30 – 06:00: Economy 06:00 – 06:30: Economy 06:30 – 07:00: Maintain 07:00 – 07:30: Maintain 07:30 – 08:00: Maintain ........... Figure 21: Timer programming example Heat-Up cycle The HWAT-ECO can be programmed to power HWAT-Y2 or HWAT-R2 at full power for any selected number of hours. When hot water is not being used and the pipes are stagnant, the HWAT-ECO can raise the temperature of the water in the stagnant pipes. To determine the amount of time that is required to reach a desired temperature, refer to “Chapter 6, Heat-Up Cycle Graphs.” You must know the programmed maintain temperature, pipe sizes, system voltage and the type of heating cable to determine the amount of time that is required to reach a desired temperature. If the desired temperature can be reached in a timeframe that is less than when the pipes will be flowing again, the Heat-Up cycle can be programmed for the number of hours that are required and the desired temperature will be reached. To determine the amount of time that is EN-RaychemHWATECOcontroller-IM-H57340 03/13 43 3 Programming the Controller required to return back to the maintain temperature after the Heat-Up cycle is complete and the heating cable is off, refer to “Chapter 7, Cool-Down Graph.” Holiday This menu is used to set the controller to Off, timedoff, or to resume your timer program. On: The controller uses the normal operation the timer program. Off: The controller will not power the system until you select “Use timer”. xx Days off: You can select a number of days. The controller automatically returns to timer mode when the selected number of days have passed. Info The display shows the firmware version number, selected cable type and the current sensor temperature. Press Enter twice to update the sensor temperature on the display. 44 EN-RaychemHWATECOcontroller-IM-H57340 03/13 4 Error/Alarms and Troubleshooting Please ensure that the unit is correctly connected to the power supply and the heating cable is connected to the HWAT-ECO unit. Error code Definitions Cause/reasons Error 1: Remedy Internal temperature alarm; Temperature is too high. (> 65°C) Error 2: Pipe Sensor failure (Only when temperature alarm “enabled” selected) • Sensor or sensor cable defect • Low temp alarm or High temperature cut-out selected and sensor is not installed. Error 3: Network failure Two or more HWATECO’s are set as Master EN-RaychemHWATECOcontroller-IM-H57340 03/13 Turn off power and allow the controller to cool and then re-energize. The controller will lock out after three occurrences. If this does not restore the controller, replace the HWAT-ECO. Connect sensor to HWAT-ECO or turn off temperature alarm. Check sensor connections; replace sensor, check temperature sensor mounting Reinitialize MASTER (see "Setup" on page 36) 45 4 Error/Alarms and Troubleshooting Error code Definitions Cause/reasons Remedy Error 4: Internal Error Controller needs to be replaced. Contact Pentair Thermal Management representative Error 5: No/Low current alarm Ensure that the heating circuit is connected to power output of the HWAT-ECO. If controlling a contactor, ensure that the Short Heater Alarm is enabled. Error 6: Configuration Error Error 7: Pipe temperature too high 46 Refer to "Short Heater" menu. • If heating cable is longer that 15 ft. (4.5 m) then, Short heater = No • If heating cable is shorter than 15 ft. (4.5 m) then, Short heater = Yes • Verify High Temperature Cut-out (HTC) is set correctly. • Correct boiler or mixing valve (Only when HTC is setting. enabled) • Boiler temperature is • Verify HWAT-ECO programming. too high. • Verify that pipe insulation • Pipe temperature schedule is correct. too hot EN-RaychemHWATECOcontroller-IM-H57340 03/13 4 Error/Alarms and Troubleshooting Error code Definitions Cause/reasons Error 8: Remedy Time is lost Battery is drained due to not being powered for a long time. Error 9: Input time again (will be asked by the unit when a button is pressed) Pipe temperature is too low • Correct boiler/mixing valve temperature setting (Only when temperature • Ensure that the sensor is tight to pipe and insulated. alarm “yes” selected) Pipe temperature too • Verify power is connected to heating cable. low • Confirm Low Temperature Alarm (LTA) setting Confirm HWAT-ECO settings Confirm insulation schedule EN-RaychemHWATECOcontroller-IM-H57340 03/13 47 4 Error/Alarms and Troubleshooting Indications/Trouble shooting Cause/reasons Water temperature too low 48 Too low water temperature • Boiler temperature is too low • Cold water entering system • Heater used is different type than entered in program. • Entered value of ambient temperature is too high. • Insulation thickness is different than standard thickness. Remedy • Check boiler temperature and timer program • Mixing valves and janitor sinks may be allowing cold water to cross over to the hot water side. • Change heater type in HWAT-ECO (can only be done in quick install "Setup" on page 36 - Reinitialize) • Change value of ambient temperature • Adjust power correction factor if possible (see "Timer" on page 41) • Change insulation to match required schedule in HWAT installation manual. EN-RaychemHWATECOcontroller-IM-H57340 03/13 4 Error/Alarms and Troubleshooting Indications/Trouble shooting Cause/reasons Remedy Water temperature too high Too high water • Change heater temperature type in HWAT-ECO (can only be done • Heater used is differin quick install ent type than entered "Setup" on page 36 in program. - Reinitialize) • Insulation thickness is different than stan- • Adjust power correction factor if possible dard thickness. (see "Timer" on page • Entered value of 41) ambient temperature • Change value of is too low ambient temperature No display Loss of power Restore power Can’t access programming mode Controller is password-protected Enter your 4-digit password. If you forgot your password, enter the backup password: 6922 to unlock the controller EN-RaychemHWATECOcontroller-IM-H57340 03/13 49 5 Pre-Defined Programs I-0 = Heat-up cycle = Maintain temperature = Economy temperature = Off Constant Heat-up I Maintain Monday-Sunday Economy Off 00 I-1 02 04 06 08 10 12 14 16 18 20 22 24 Apartments Heat-up I Maintain Monday-Friday Economy Off 00 02 04 06 08 10 12 14 16 18 20 22 24 I Heat-up Maintain Saturday-Sunday Economy Off 00 I-2 02 04 06 08 10 12 14 16 18 20 22 24 Family home Heat-up I Maintain Monday-Sunday Economy Off 00 I-3 02 04 06 08 10 12 14 16 18 20 22 24 Prison Heat-up Maintain I Monday-Sunday Economy Off 00 50 02 04 06 08 10 12 14 16 18 20 22 24 EN-RaychemHWATECOcontroller-IM-H57340 03/13 5 Pre-Defined Programs re I-4 = Maintain temperature = Economy temperature = Off Hospital Heat-up Maintain Monday-Sunday Economy Off 00 4 I-5 02 04 06 08 10 12 16 18 20 22 24 14 16 18 20 22 24 14 16 18 20 22 24 16 18 20 22 24 18 20 22 24 14 Nursing home Heat-up Maintain Monday-Sunday Economy Off 00 4 I-6 02 04 06 08 10 12 Hotel Heat-up Maintain Monday-Sunday Economy Off 00 4 I-7 02 04 06 08 10 12 Sports center Heat-up Maintain Monday-Sunday Economy Off 00 4 4 = Heat-up cycle I-8 02 04 06 08 10 12 14 Convalescent home Heat-up Maintain Monday-Sunday Economy Off 00 02 04 06 08 10 12 EN-RaychemHWATECOcontroller-IM-H57340 03/13 14 16 51 6 Heat-Up Cycle Graphs To calculate heat-up and cooldown times when heat cycle is used. Pipe Temperature °F (°C) 125 (52) Heat-Up HWAT-Y2 120 (49) 115 (46) 208V 110 (43) 1-inch pipe 105 (41) 0 1/2-inch pipe 2-inch pipe 70°F (21°C) ambient 2 4 6 8 10 12 14 Time (hours) 16 18 20 22 24 Pipe Temperature °F (°C) 125 (52) 120 (49) 115 (46) 240V 110 (43) 1-inch pipe 105 (41) 0 52 1/2-inch pipe 2-inch pipe 70°F (21°C) ambient 2 4 6 8 10 12 14 Time (hours) 16 18 20 22 24 EN-RaychemHWATECOcontroller-IM-H57340 03/13 6 Heat-Up Cycle Graphs Pipe Temperature °F (°C) 150 (66) Heat-Up HWAT-R2 140 (60) 130 (54) 208V 1/2-inch pipe 120 (49) 1-inch pipe 110 (43) 70°F (21°C) ambient 105 (41) 0 2 4 6 8 10 2-inch pipe 12 14 16 18 20 22 24 Time (hours) Pipe Temperature °F (°C) 150 (66) 140 (60) 130 (54) 240V 1/2-inch pipe 120 (49) 1-inch pipe 110 (43) 70°F (21°C) ambient 105 (41) 0 2 4 6 8 10 2-inch pipe 12 14 16 18 20 22 24 Time (hours) EN-RaychemHWATECOcontroller-IM-H57340 03/13 53 7 Cool-Down Graph These cool down curves represent when the heating cable is turned off. 150 (66) Cool-Down 70°F (21°C) ambient 1/2-inch pipe 145 (63) 1-inch pipe 2-inch pipe 140 (60) Pipe Temperature °F (°C) 135 (57) 130 (54) 125 (52) 120 (49) 115 (46) 110 (43) 105 (40) 0 54 1 2 3 4 5 6 7 Time (hours) 8 9 10 11 12 EN-RaychemHWATECOcontroller-IM-H57340 03/13 WWW.THERMAL.PENTAIR.COM NORTH AMERICA EUROPE, MIDDLE EAST, AFRICA Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 [email protected] Tel: +32.16.213.511 Fax: +32.16.213.603 [email protected] ASIA PACIFIC LATIN AMERICA Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 [email protected] Tel: +1.713.868.4800 Fax: +1.713.868.2333 [email protected] Pentair and HWAT are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice © 2004–2013 Pentair. THERMAL MANAGEMENT SOLUTIONS EN-RaychemHWATECOcontroller-IM-H57340 03/13 ">
![](http://s1.manualzz.com/store/data/078290046_1-f7b13ac192d74387f970e3b3cde27d80-210x147.png)
Advertisement
Key features
- Self-regulating heating cables
- RayClic connection kits
- HWAT-ECO or ACS-30 controllers
- UL Listed and CSA certified
- Non-hazardous locations
Frequently asked questions
The minimum control setpoint for HWAT-R2 is 105°F (40°C).
The HWAT System is limited to 208 V or 240 V service when using the HWAT-ECO controller. When using the ACS-30 controller, the voltage range is 208–277 V.
The manual recommends using fire-resistant insulation like fiberglass, and specifies insulation thickness based on pipe size.