PULM514UK.qxd
11/09/06
9:35
Page 1
UPS
Pulsar M
RT2U version.
2200/3000 VA
Modular on-line double
conversion UPS
Maximum availability
Ideal protection for:
RT3U version.
◗ Configuration. Double conversion
on-line UPS with automatic by-pass
and power correction factor.
◗ Continuous power supply.
Hot swappable batteries.
The HotSwap MBP (Maintenance
By-Pass) module allows the UPS
to be replaced without interrupting
the power supply.
HotSwap MBP 4DIN.
◗ Redundancy. The ModularEasy kit
makes it easy to parallel 2 standard
Pulsar M UPSs (N + 1 redundancy).
Totally flexibility
Pulsar M has unmatched
flexibility.
Servers, data storage and network equipment.
◗ Format. Pulsar M is
available in RT2U convertible
rack/tower version (optimised
for rack mounting) or RT3U
(for tower or shallow rack).
◗ Connections. With FlexPDU
and HotSwap MBP the Pulsar M
can be connected by sockets
or terminal blocks. They can be
installed as required behind, on
the side or on top of the unit.
Telephony - VoIP.
◗ Compatible with low power
factor loads. Pulsar M is rated
for 0.9 total power factor
(3000VA/2700 W and
2200VA/1980W).
Pulsar M and ModularEasy kit.
◗ Powershare. The Pulsar output sockets
◗ Interfaces. USB + serial + remote
start/stop + slot for optional
communications card.
are individually controlled to provide
load-shedding to maximise the backup
time. It also provides remote reboot and
sequential start-up as standard.
Medical equipment - Industrial processes.
◗ Long backup times. 1 to 4 EXB battery
units can be added to the Pulsar M. The
Pulsar 3000XL has a built-in high speed
charger for additional long backup times.
FlexPDU and HotSwap MBP can be
mounted in many different positions.
Minimum total cost
of ownership
◗ ModularEasy kit. A simple, low cost
solution for uprating by adding a
second standard UPS.
◗ Easy operation. Multilingual
display. Access to a wide range of
measurements and set-up menus.
Adjustable multilingual
display.
◗ Remote supervision. A wide range
of options using the Solution-Pac
supplied: SNMP and HTML, (Network
Management Card included with
Netpack versions), ModBus/JBus
and relay outputs.
Network Management Card
and MGE EPM Supervisor.
PULM514UK.qxd
11/09/06
9:35
Page 2
UPS - Pulsar M
1 LCD Multilingual display
-
5
7
3
6 languages,
displays measurements,
displays alarms,
access to control and set-up menus.
2 Panel for replacing batteries without
1
interrupting the output.
1
2
3 1 USB port + 1 serial port + remote ON/OFF
2
4
5 EXB units recognised automatically.
6 8 IEC 10A sockets, including 4 Powershare
6
8
programmable sockets and 1 IEC 16A
socket.
5
7
8
4
3
6
7 Communications card slot.
8 Mountings for HotSwap MBP and FlexPDU.
Specifications
MGE PowerServices™
2 year guarantee,
including batteries
Standard exchange of product in case
of failure, including batteries.
Associated services(1):
Warranty+: 3 year extended guarantee.
Start Up+: on site commissioning.
Warranty+ Silver: Warranty+ and Start Up+.
Warranty+ Gold: Warranty+ Silver
and 3 annual service visits.
1: Depending on the country, see
www.mgeups.com/services.
Communications software
and hardware
Solution-Pac software on CD-ROM
with each UPS
For monitoring the server(s) powered
by the UPS and for local and remote UPS
supervision.
Network Management Card (NMC) 2006
For connecting the UPS to an Ethernet
10/100 network, raising SNMP alarms and
supervising the UPS using a simple browser
interface.
NMC environment sensor
Monitoring the temperature, humidity
and 2 relay contacts via SNMP or HTML.
Enterprise Power Manager supervisor
For comprehensive management
of a set of UPSs using a Windows PC.
Management-Pac 2 suite
NMS integration kit: HP OpenView, IBM
Tivoli Netview, CA Unicenter, etc.
Management Card Contacts/Serial
To provide UPS status outputs via relay
contacts, emergency stop and a second
serial port.
NMC ModBus/JBus card
For combined SNMP, HTML and
ModBus/JBus supervision.
UPS Control remote display
2 To monitor the UPS status up to 25m
from the unit.
Headquarters
140, avenue Jean-Kuntzmann
Inovallée - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel.: +33 (0)4 76 18 30 00
PULM514UK-09/06
Pulsar M
2200
3000 - 3000 XL
Rating
2200 VA / 1980 W
3000 VA / 2700 W (1)
Format
RT2U (tower / rack 2U) and RT3U (tower / rack 3U)
Paralleling with Pulsar M ModularEasy kit(2)
Rating
4000 VA or 2 x 2200 VA redundant
6000 VA or 2 x 3000 VA redundant
Selection of uprating or
Automatic selection of uprating (2N)
redundancy
or redundancy (N+1)
Electrical characteristics
Architecture
On-line double conversion with automatic by-pass and power factor correction
Input voltage and frequency ranges
100/120/160/184 V(3) to 284V - 40 to 70 Hz
without using batteries
Output voltage and frequency 230V (adjustable to 200/208/220/240 V), 50/60 Hz auto-select or frequency converter mode
Connections
Input
1 IEC C20 (16A) or terminal block on HotSwap MBP HW (Hard-Wired)
Outputs
8 IEC C13 (10A) sockets + 1 IEC C19 (16A) socket on Pulsar M
Remotely controlled
2 groups of 2 x IEC C13 (10A) on Pulsar M
Powershare sockets
Additional outputs with
4 FR/Schuko sockets or 3 BS sockets
HotSwap MBP FR/DIN/BS/IEC/HW
or 6 IEC 10A sockets or terminal blocks (HW version)
Additional outputs with
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10A sockets
FlexPDU FR/DIN/BS/IEC
Batteries
Typical backup times for 50 and 70% of the VA rating except for Pulsar M 3000XL(4)
Pulsar M
17 mn / 12 mn
15 mn / 10 mn
Pulsar M + 1 EXB
85 mn / 60 mn
60 mn / 40 mn
Pulsar M + 4 EXB
285 mn / 200 mn
190 mn / 150 mn
Battery management
Automatic weekly test (period adjustable using LCD display or in software
supplied), automatic recognition of external battery units => continuous
maximisation of backup time + deep discharge protection
Interfaces
Indicators and display
3 LEDs + adjustable multilingual display: display of measurements,
access to control and set-up menus
Communication ports
1 USB port + 1 RS232 serial port(5) + 1 mini terminal block for remote ON/OFF and emergency stop
Communications card slots
1 slot for NMC Minislot 2006 card (included in Netpack version)
or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
0°C to 40°C continuous, 45 dBA
Operating temperature noise level
Performance - Safety - EMC
IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class
Approvals
CE, TüV GS, CB report, cTüV-US
Dimensions (H x W x D) / Weight
Pulsar M RT (3U)
131 x 440 x 490 mm
131 x 440 x 490 mm (compatible with
(compatible with 600 mm deep rack) / 30 kg
600 mm deep rack) / 30 kg (3000 XL = 18 kg)
Pulsar M RT2U
86 x 440 x 640 mm / 31 kg
86 x 440 x 640 mm / 31 kg
Pulsar M EXB RT3U
131 x 440 x 490 mm (compatible with 600 mm deep rack) / 42 kg
Pulsar M ModularEasy kit (2U)
86 x 440 x 400 mm / 10 kg
1: Maximum rating with EXB battery units =2400 W. 2: Pulsar M ModularEasy kit is a 2U module for paralleling 2 Pulsar M UPSs, available from
March 2007 - cannot be used with Pulsar M 3000 XL. 3: Lower limits for <20%, <33%, <66% and >=66% of nominal power. 4: except Pulsar M
3000 XL: UPS with high speed charger, without built-in batteries, for custom configurations: ask us for details. 5: USB and RS232 ports cannot
be used simultaneously.
Part numbers
Pulsar M RT
Pulsar M RT2U(6)
Pulsar M RT3U HotSwap(7)
Pulsar M RT2U Netpack(8)
Pulsar M EXB RT3U(6)
Pulsar M ModularEasy kit(6) (for
paralleling 2 Pulsar Ms)
Pulsar Rack Kit 2U/3U
(not supplied with Pulsar M RT)
Pulsar M 2200
68 400
68 401
FR: 68 406 DIN: 68 407 BS: 68 408
IEC: 68 409 HW: 68 410
68 411
Pulsar M 3000
68 402 - M 3000 XL : 68 404
68 403 - /
FR: 68 412 DIN: 68413 BS: 68 414
IEC: 68 415 HW: 68 416
68 417
68 405
68 418
68 441
6: Includes rack kit. 7: Pulsar M RT3U HotSwap = Pulsar M RT + rack kit + HotSwap MBP. 8: Pulsar M RT2U Netpack = Pulsar M RT2U +
NMC 2006 edition.
Due to developments in technical standards and the equipment described in this document, we cannot be held liable for compliance with the characteristics indicated by the images and text unless they are confirmed by us. All the brand names referred to in this document are protected by copyright.
Publication: MGE UPS SYSTEMS (September 2006) - Design and rewriting: 3c-evolution.com - Integration: Graphic Studio MGE: +33 4 79 37 87 66 – Translation: TTP: +33 4 78 66 47 99.
and emergency stop inputs.
4 EXB battery unit connector.