FLEX MODULE
USER MANUAL
POWER CONNECTIONS/OPERATIONS
INPUT PWR: The I/O module requires 24Vdc, 2.5A (60W power supply) for operation.
The acceptable range is 19~28Vdc. An alarm notification can be sent after a programmable delay if the input
power is no longer present.
BATT (12V): A single 12V lead acid battery is required for backup operation and to receive Power Loss
alarm notification. Do not use Li ion or other battery technology. Only use Sealed Lead Acid (SLA) type
batteries 2Ah to 10Ah. The 12V from the battery is converted to 24Vdc internally.
FUSED OUT: A 24V, 650mA auxiliary output power is available for external devices. This ouput will continue
to deliver 24V after the power is removed from the INPUT PWR terminals and operate off the battery. (DCUPS) The autonomy will depend on the battery capactiy and load. This circuit has an electronic fuse with an
auto-reset feature.
POWER ON/OFF switch and indications:
Batt Fuse: 3A battery fuse (automotive type - ATOF).
Input PWR Fuse: 3A 24Vdc incoming power fuse. (automotive type - ATOF).
Fuses are removed during shipping. They are kept in a small bag with the schematics.
SJE®
1
FLEX Module
ANALOG INPUTS
6 analog inputs: 4-20mA differential and optically isolated.
12-bit resolution: (4-20mA = 800-4000 counts)
For loop powered instruments, use the +24V terminal for excitation voltage.
Connect the signal to Alx+, and connect the Alx-terminal to COM.
Loop Powered
DIGITAL INPUTS
NPN circuitry. (Inputs are at 12Vdc, and COMs are Signal ground)
Connect to COM to activate the input.
Only use potential free contacts to trigger the inputs (dry contacts)
Digital input assignments:
D1
PUMP 1 RUNNING (RUN TIMES/CYCLES)
D2
PUMP 2 RUNNING (RUN TIMES/CYCLES)
D3
PUMP 3 RUNNING (RUN TIMES/CYCLES)
D4
PUMP 4 RUNNING (RUN TIMES/CYCLES)
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
FLOW TOTALIZER 1
FLOW TOTALIZER 2
ALARM 1
ALARM 2
ALARM 3
ALARM 4
ALARM 5
ALARM 6
ALARM 7
ALARM 8
ALARM 9
ALARM 10
SJE®
2
FLEX Module
FLOWMETER CONNECTION
It is possible to monitor both the instantaneous flow (4-20mA) and the accumulated volume (Digital
inputs D5, D6). Below is a connection example of a magnetic flowmeter. Please refer to your
flowmeter manual and/or contact your supplier for setup and wiring assistance.
AC
4-20mA
(Instant flow)
Digital Output
(Totalizer)
The 4-20mA signal can be connected to any of the open Analog inputs (AI1~AI6). This signal
from the flowmeter is typically not loop powered.
A pulse output from the flowmeter is required for volume totalization.
There are 2 digital inputs on the FLEX Module (D5 & D6) designed for volume totalizer derived
from a gallons/pulse signal (example 100 gal = 1 pulse). The max input frequency is
100 Hz. The minimum pulse width is 0.5ms.
Note: These 2 inputs are not for monitoring a frequency output proportional to the flow. When
the wiring and flowmeter configuration is complete, the value for the gallons/pulse found in
“Parameters” screen on the web portal must also be changed to match the flowmeter.
4-20mA
+
Flowmeter
Pulse
Flowmeter Wiring Example
SJE®
3
FLEX Module
RELAY OUTPUTS
Rated for 250V, 5A (resistive)*
R5 and R6 are Normally Closed (NC) and open upon activation.
Each relay will only activate for 2 seconds (momentary) when the button is pressed on the web portal.
CAUTION/DANGER
R1-NO R2-NO R3-NO
Machine may start unexpectedly and cause serious injury or death.
You must have confirmation that all personnel are free and clear
from moving parts and the electrical panel before activating the
relay remotely.
Only allow qualified operators to remotely activate the relay.
The relay remote operation must be part of a fail safe electrical
circuit that would shutdown the equipment before failing or cause
damage/injury.
R4-NO R5-NC R6-NC
Local and National safety codes must be followed.
RS 485 PORT BAUD RATE
The baud rate can be set via the dip switches on the FLEX Module.
The default is 9600 (required for communication with the SJE Panel Link™).
D
T
* To meet UL 508A, a Class 2 circuit must be used.
SJE®
4
FLEX Module
CONNECTING TO THE
CELLULAR GATEWAY MODEL
This cable is not symetrical.
Connect the end labeled
PW here.
PUMP WATCH
SJE Panel Link™
EXPRESS
ID:ID:67XXXG
67XXXG
TM
Panel Link RJ11
SJE®
5
FLEX Module
GENERIC - WEB PORTAL
INPUT SCAN TIMES
The odd number analog inputs AI1, AI3, AI5 have a scan time of 30s or less from the SJE Panel Link™
Gateway. The even number analog inputs AI2, AI4, AI6 have an update time of 90~120s update time.
Choose even number AIs for alarms requiring a longer time delay. Digital inputs have a 10s or less
scan time. Digital inputs also have a programmable time delay function that can be accessed in the
“Parameters” screen.
SJE®
6
FLEX Module
LIFT STATION - WEB PORTAL
The lift station web portal can be applied to the FLEX to monitor a duplex or triplex lift station.
In addition to the graphic change, it can monitor pump and station flows via volumetric flow
calculations. The current monitoring can be configured to only update when the pump is
running. The analog inputs are assigned as follows:
AI1
AI2
AI3
AI4
AI5
AI6
Duplex lift station
Level transmitter
Pump1 current transmitter (A)
Pump2 current transmitter (A)
Spare analog input
Spare analog input
Not used
Triplex lift station
Level transmitter
Pump1 current transmitter (A)
Pump2 current transmitter (A)
Pump3 current transmitter (A)
Spare analog input
Not used
The level and current gauges can be configured and a high and low threshold alarm setup.
Note: DI5 and DI6 (pulse flow monitoring) are enabled when the volumetric flow is not enabled.
SJE®
7
FLEX Module
Lift Station Web Portal
Parameter setup screen
The Pulse Flow meter is disabled if the
Volumetric Flow calculation is enabled.
Check box to mointor motor current only when the Pump is running.
SJE®
8
FLEX Module
SCALING THE ANALOG INPUTS
The raw data range is 800-4000 counts. To scale the input, click on the edit symbol then on the gauge.
Properties
Edit
Name
AI2 Tank (Psi)
Edit the name of the gauge
Min. Value
0
Set the Gauge display Min Value (Does not scale the input)
Max. Value
100
Set the Gauge display Max Value (Scales the input value for 20mA)
Step
20
Sets the number of ticks around the dial. (Max-Min)/Step
Click to save.
x
SETTING UP HIGH & LOW ALARMS
FOR EACH ANALOG INPUTS
Click on the gauge and the window below will appear.
x
Gauge Alerts
Properties
Edit
Min. threshold
60.25
Min. threshold alert text
AI2 Tank Low Pressure
Low Limit Alarm Message
Max. threshold
71.5
High Limit Alarm Setpoint
Max. threshold alert text
AI2 Tank High Pressure
Low Limit Alarm Setpoint
Select Users
Select Users
High Limit Alarm Message
Show percentage threshold
Account
Ok
Cancel
WEB PORTAL UPDATE FREQUENCY
The data is sent from the Gateway to the cloud server via cellular communication every 10 minutes for
updating the values on the portal and for data logging. This time period is interrupted if there is an alarm
or if the user presses “Get Status” on the web portal, in which case the data is sent immediately.
SJE®
9
FLEX Module
DIMENSIONS
4.5” (11.4 cm)
8.5” (21.6 cm)
MOUNTING
Din rail mount.
2.1” (5.3 cm)
4.8” (12.2 cm)
SJE®
10
FLEX Module
NEMA 4X PANEL
The FLEX Module is available in a NEMA 4X enclosure with the cellular Gateway, power supply and battery
backup.
PANEL LINK FLEX, 4G, LTE VZ, NEMA 4X, SJ
SCHEMATIC
3
3
800-746-6287
www.sjerhombus.com
1063017
SJE Panel Link™
TM
SJE®
11
FLEX Module
WIRING
SCHEMATIC
SJE®
12
FLEX Module
NOTES:
Manufactured by: SJE Inc.
Technical support: +1-800-746-6287
[email protected]
www.csicontrols.com
www.primexcontrols.com
www.sjerhombus.com
© 2022 SJE, Inc. All Rights Reserved. PN 1075132A 09/22
">