The AIREDALE Indirect-Fired Outdoor Make-Up Air unit is a high-performance, gas-fired system designed for industrial and commercial applications. It provides fresh, heated air to facilities needing to replace air lost through ventilation or other processes. This unit features a weatherproof design, robust construction, and reliable performance, making it ideal for harsh outdoor conditions. It can be used in various applications, including manufacturing facilities, warehouses, and commercial buildings.
PDF
Download
Document
Advertisement
Advertisement
5-572.11 5H0762330001 December, 2023 INSTALLATION AND SERVICE MANUAL indirect gas-fired weatherproof make-up air units models HBP/HCP/HDP/HPP OBP/OCP/ODP/OPP WARNING 1. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. 2. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere. AVERTISSEMENT 1. Une installation, un réglage, une altération, une réparation ou une maintenance impropre risque de causer des dommages, des blessures ou la mort, et d’engendrer une exposition à des substances dont certains États ont déterminé qu’elles étaient cancérogènes ou pouvaient causer des malformations à la naissance et des problèmes de reproduction. Lisez bien les instructions d’installation, d’utilisation et de maintenance avant d’installer ou de réparer cet appareil. 2. Pour éviter la panne prématurée de l’échangeur thermique, ne placez AUCUN appareil à gaz à des endroits où les vapeurs corrosives (chlorées, halogénées ou acides) sont présentes dans l’atmosphère. All models approved for use in California by the CEC. FOR YOUR SAFETY IF YOU SMELL GAS: 1. Open windows. 2. Do not try to light any appliance. 3. Don’t touch electrical switches. 4. Extinguish any open flame. 5. Immediately call your gas supplier. POUR VOTRE SÉCURITÉ SI VOUS SENTEZ UNE ODEUR DE GAZ: 1. Ouvrez les fenêtres. 2. Ne tentez d'allumer aucun autre appareil. 3. Ne touchez pas aux interrupteurs électriques. 4. Éteignez toute flamme nue. 5. Appelez immédiatement votre compagnie de gaz. FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous. POUR VOTRE SÉCURITÉ L'utilisation et le stockage d'essence ou d'autres vapeurs et liquides inflammables dans des récipients ouverts à proximité de cet appareil sont dangereux. THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB. TABLE OF CONTENTS TABLE OF CONTENTS IMPORTANT 1. The use of this manual is specifically intended for a qualified installation and service agency. A qualified installation and service agency must perform all installation and service of these appliances. 2. This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. 3. Children should be supervised to ensure that they do not play with the appliance. IMPORTANT 1. Ce manuel est spécifiquement destiné au personnel d’une entreprise qualifiée d’installation et d’entretien. Toutes les opérations d’installation et d’entretien doivent être confiées à une entreprise qualifiée. 2. Cet appareil n’est pas conçu pour être utilisé ou entretenu par des personnes (y compris des enfants) dont les capacités physiques, sensorielles ou mentales sont réduites, ou qui n’ont pas l’expérience et les connaissances suffisantes, à moins d’être supervisées ou d’avoir obtenu des directives concernant l’utilisation de l’appareil par une personne responsable de leur sécurité. 3. Les enfants doivent être supervisés pour s’assurer qu’ils ne jouent pas avec l’appareil. INSPECTION ON ARRIVAL 1. 2. 3. 2 Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative. Check rating plate on unit to verify that power supply meets available electric power at the point of installation. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable). Inspection On Arrival .............................................................2 Special Precautions ..............................................................3 Hazard Intensity Levels ........................................................3 Special Design Requests / Unit Location ..............................6 Special Design Requests ................................................6 Unit Location ...................................................................6 Location Recommendations ...........................................6 Sound Attenuation / Roof Curb Installation ...........................8 Sound and Vibration Levels ............................................8 Curb or Sub-Base Mounted Sites ...................................8 Slab Mount Installation / Rigging Instructions .....................10 Slab Mounted Units .......................................................10 General Rigging Instructions .........................................11 Duct Installation / Utility Connections .................................12 Duct Installation ............................................................12 Utility Connections ........................................................12 Unit Installation ...................................................................14 Gas Connections ..........................................................14 Considerations for Elevation .........................................17 Manifold Pressure Adjustment ......................................17 Electrical Connections ..................................................18 Cooling Coil Units .........................................................20 Start-Up Procedure .............................................................22 Start-Up Procedure .......................................................22 Pilot Burner Adjustment ................................................23 Furnace Control Operating Sequence ..........................26 Cooling Coil Operation ..................................................28 Component/Option Locations .............................................29 Component Descriptions ....................................................30 General Performance Data .................................................37 General Performance Data .................................................38 Option & Accessory Pressure Drop Data ............................39 Blower Performance Data ...................................................40 General Performance Data .................................................42 Blower Sheave Assembly Data ...........................................43 Dimensions - Unit ...............................................................45 Dimensions - Unit Base ......................................................49 Dimensions - Roof Curbs ....................................................50 Dimensions - Cooling Coils .................................................51 Dimensions Rainhood, Remote Panel & Evaporative Cooler .................52 Weights ...............................................................................53 Maintenance .......................................................................54 Electrical Wiring ............................................................54 Cooling Coil Maintenance .............................................55 Cooling Coil Drain Pan and Drain System ....................55 Duct Furnace ................................................................55 Gas Piping & Controls ...................................................55 Manifold Assembly Removal .........................................56 Burner and Pilot Assembly Removal .............................56 Service & Troubleshooting ..................................................58 Start-Up Checklist ...............................................................60 Model Designations ............................................................61 Model Identification .......................................................61 Replacement Parts Ordering ........................................61 Model Nomenclature For System Units ..............................62 Weatherproof Model Nomenclature ..............................62 5-572.11 SPECIAL PRECAUTIONS WARNING SPECIAL PRECAUTIONS THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT, AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES. HAZARD INTENSITY LEVELS 1. 2. 3. 4. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern. PRÉCAUTIONS PARTICULIÈRES LES INSTRUCTIONS D'INSTALLATION ET D'ENTRETIEN DE CE MANUEL DOIVENT ÊTRE OBSERVÉES POUR ASSURER UN FONCTIONNEMENT SÉCURITAIRE, EFFICACE ET FIABLE. DE PLUS, LES PRÉCAUTIONS PARTICULIÈRES CIAPRÈS DOIVENT ÊTRE RIGOUREUSEMENT RESPECTÉES. SINON, IL Y AURAIT RISQUE DE DÉGÂTS MATÉRIELS OU DE PERTE, DE BLESSURE PERSONNELLE OU DE MORT D'HOMME. CES INSTRUCTIONS SONT SUJETTES À TOUTE DISPOSITION PLUS RESTRICTIVE DES CODES PROVINCIAL OU NATIONAL. HIÉRARCHIE DES NIVEAUX DE RISQUES 1. 2. 3. 4. DANGER : Indique un danger imminent qui, s'il n'est pas évité, entraînera INÉVITABLEMENT des blessures graves, voire mortelles. AVERTISSEMENT : Indique un danger potentiel qui, s'il n'est pas évité, RISQUE d'entraîner des blessures graves, voire mortelles. ATTENTION : Indique un danger potentiel qui, s'il n'est pas évité, PEUT entraîner des blessures mineures ou modérées. IMPORTANT : Indique une situation qui, si elle se matérialise, PEUT entraîner des risques pour la sécurité des personnes. 1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere. 2. Failure to follow proper lifting instructions and applicable safety procedures could result in property damage, serious injury, or death. Lifting should only be done by a qualified rigging company. Use ALL lifting points. Test lift to ensure proper balance and rigging. Never lift in high winds. 3. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing. 4. Gas pressure to appliance controls must never exceed 3.4 kPa (14" W.C. or 1/2 psi). 5. Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage. 6. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property. 7. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C. 8. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units. 9. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage. 10. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owners risk. DANGER Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere. DANGER Les appareils ne doivent pas être installés à un endroit où ils risquent d’être exposés à une atmosphère potentiellement explosive ou inflammable. 5-572.11 3 SPECIAL PRECAUTIONS CAUTION AVERTISSEMENT 1. Pour éviter la panne prématurée de l’échangeur thermique, ne placez AUCUN appareil à gaz à des endroits où les vapeurs corrosives (chlorées, halogénées ou acides) sont présentes dans l’atmosphère. 2. Le non-respect d’une bonne procédure de levage et des procédures de sécurité qui s’appliquent pourrait mener à des dommages matériels ou à des blessures graves, voire mortelles. Le levage doit être effectué uniquement par une entreprise spécialisée dans le gréage. Utilisez TOUS les points de levage. Testez le levage pour assurer un bon équilibre et un bon gréage. Ne procédez jamais au levage de l’appareil par vents forts. 3. Toutes les canalisations de gaz sur site doivent être testées (pression/fuites) avant usage. Ne recherchez jamais les fuites avec une flamme nue. Utilisez plutôt de l’eau savonneuse ou un produit équivalent. 4. La pression de gaz aux commandes de l’appareil ne doit jamais dépasser 3.4 kPa (35,5 cm C.E. ou 1/2 psi). 5. Débranchez l’alimentation électrique avant d’effectuer des connexions ou de travailler sur l’appareil. Respectez toutes les procédures de sécurité qui s’appliquent pour éviter toute mise en marche accidentelle. Le non-respect de cette directive peut entraîner des blessures ou la mort causées par un choc électrique ou des pièces mobiles, en plus d’endommager l’appareil. 6. Tous les appareils doivent être branchés de manière strictement conforme au diagramme fourni. Tout câblage différent de celui du schéma peut créer des risques de dommages matériels ou de blessures. 7. Tout câblage usine d’origine exigeant un remplacement doit être remplacé par un câble d’indice thermique nominal de 105 °C. 8. Pour réduire le risque de condensation, l’entrée minimum dans l’appareil au niveau de la mer, telle qu’indiquée sur la plaque de série, ne doit pas être moins de 5 % inférieure à la valeur d’entrée nominale des appareils à double valeur nominale. 9. Assurez-vous que la tension d’alimentation de l’appareil, comme indiqué sur la plaque de série, n’est pas de 5 % supérieure à la tension nominale. 10. Pour l’entretien et les réparations de cet appareil, utilisez uniquement des pièces d’origine certifiées. Pour la liste complete des pièces de rechange, consultez Modine Manufacturing Company. Le numéro de modèle complet, le numéro de série et l’adresse du fabricant figurent sur la plaque signalétique fixée à l’appareil. Toute substitution de pièce ou decommande non approuvée par le fabricant sera aux risques du propriétaire. 4 1. Appliances are designed for outdoor installation only. DO NOT LOCATE APPLIANCES INDOORS. 2. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes. 3. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage. 4. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced. ATTENTION 1. Ces appareils sont conçus pour une installation à l’extérieur seulement. NE PLACEZ PAS LES APPAREILS À L’INTÉRIEUR. 2. La purge de l’air des tuyauteries de gaz doit se faire selon la procédure ANSI Z223.1 de la dernière édition du « National Fuel Gas Code » ou des codes CAN/CGA-B149 du Canada. 3. Vérifiez que la tension d’alimentation de l’appareil n’est pas inférieure de plus de 5 % à la tension nominale inscrite sur la plaque de série. 4. Ne tentez pas de réutiliser un composant mécanique ou électrique qui a été mouillé. Ces composants doivent être remplacés. 5-572.11 SPECIAL PRECAUTIONS Table 5.1 - SI (Metric) Conversion Factors IMPORTANT To Convert Multiply By To Obtain To Convert Multiply By To Obtain "W.C. 0.24 kPa CFH 1.699 m3/min psig 6.893 kPa Btu/ft3 0.0374 mJ/m3 °F (°F-32) x 0.555 °C pound 0.453 kg inches 25.4 mm Btu/hr 0.000293 kW feet 0.305 meters gallons 3.785 liters CFM 0.028 m3/min psig 27.7 "W.C. 1. For installation only in locations not accessible to the general public. 2. Unit can be operated up to a maximum of 10,000 feet (3048 m). 3. To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%. 4. To prevent premature heat exchanger failure, observe heat exchanger tubes by looking at the heat exchanger through the field installed access openings in connecting ductwork or the unit access doors where viewing the heat exchanger is possible. If the bottom of the tubes become red while blower and duct furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 26 for Blower Adjustments. 5. Start up and adjustment procedures, installation, and service of these appliances must be performed by a qualified installation and service agency. 6. To prevent premature heat exchanger failure, with all control systems, a blower starting mechanism must be provided so that the blower is running or energized within 45 seconds of the gas control operation. 7. To check most of the Possible Remedies in the troubleshooting guide listed in Table 58.1, and refer to the applicable sections of the manual. IMPORTANT 1. À installer uniquement dans des endroits non accessibles au grand public. 2. L’unité peut être utilisée jusqu’à un maximum de 3048 m (10,000 ft). 3. Pour éviter une défaillance prématurée de l’échangeur de chaleur, le pouvoir calorifique du gaz utilisé ne doit pas excéder de plus de 5 % la valeur nominale inscrite sur la plaque signalétique de l’appareil. 4. Pour éviter la défaillance prématurée de l’échangeur de chaleur, examinez les tubes de l’échangeur de chaleur en le regardant à travers les ouvertures d’accès installées sur les lieux lors de la connexion des tuyaux ou les portes d’accès à l’unité où il est possible de voir l’échangeur de chaleur. Si le bas des tubes devient rouge lorsque la soufflante et la chaudière canalisée sont en marche, vérifiez que le régime de la soufflante est approprié pour l’application. Pour le réglage de la soufflante, reportezvous à la page 26. 5. Les procédures de démarrage et de réglage, l’installation et le service de ces appareils doivent être confiés à un centre d’installation et de service qualifié. 6. Pour éviter une panne prématurée de l'échangeur de chaleur, avec tous les systèmes de commande, un mécanisme de démarrage du ventilateur doit être fourni de manière à ce que le ventilateur soit en marche ou sous tension 45 secondes de l'opération de contrôle du gaz 7. Pour essayer la plupart des solutions possibles suggérées dans le guide de dépannage du Tableau 58.1 reportezvous aux sections correspondantes du manuel. 5-572.11 5 SPECIAL DESIGN REQUESTS / UNIT LOCATION Special Design Requests IMPORTANT Modine Manufacturing Company will sometimes build units with special features as requested by the customer. This manual only covers standard features and does not include any changes made for special feature requests by the customer. Units built with special features are noted with a 5-digit SPO (Special Product Order) Number on the Serial Plate 1. Pour installation uniquement dans des endroits non accessibles au public. 2. L’unité peut être utilisée jusqu’à un maximum de 3048 m (10,000 ft). STORAGE PRIOR TO INSTALLATION Location Recommendations If the unit is stored outside prior to installation, the unit should be covered. 1. Unit Location 2. DANGER 3. Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere. DANGER Les appareils ne doivent pas être installés à un endroit où ils risquent d’être exposés à une atmosphère potentiellement explosive ou inflammable. 4. 5. WARNING To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere. AVERTISSEMENT Pour éviter la panne prématurée de l’échangeur thermique, ne placez AUCUN appareil à gaz à des endroits où les vapeurs corrosives (chlorées, halogénées ou acides) sont présentes dans l’atmosphère. CAUTION 6. 7. When locating the furnace, consider general space and heating requirements and availability of gas and electrical supply. Unit must be installed on the positive pressure side of the circulating blower. Be sure the structural support at the unit location site is adequate to support the weight of the unit and any other required support structure. For proper operation the unit must be installed in a level horizontal position. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Be sure clearances are maintained to the combustion air inlet louvers and power exhauster discharge cover. Units are designed for installation on non-combustible surfaces or combustible surfaces with the minimum clearances shown in Figure 6.1 and Table 7.1. On units that have fresh air openings, a method should be provided to prevent water and debris from entering the unit such as a rainhood and bird screen, evaporative cooler, etc. On horizontal discharge units (Model Digit 2=B or C), adequate space must be provided to install the discharge duct as shown in Figure 12.1. to insure even air flow across the heat exchanger. Figure 6.1 Combustible Material & Service Clearances j Appliances are designed for outdoor installation only. DO NOT LOCATE APPLIANCES INDOORS. ATTENTION B B Ces appareils sont conçus pour une installation à l’extérieur seulement. NE PLACEZ PAS LES APPAREILS À L’INTÉRIEUR. SIDE VIEW IMPORTANT 1" (2.5 cm) 1. For installation only in locations not accessible to the general public. 2. Unit can be operated up to a maximum of 10,000 feet (3048 m). 36" (91 cm) ACCESS SIDE A C FRONT VIEW j Minimum clearance to combustible materials is 1" (2.5 cm) from rooftop. 6 5-572.11 UNIT LOCATION Figure 7.1 Matériaux combustibles et dégagemen j Tableau 7.1 Matériaux combustibles et dégagements Dégagements Dégagements minimaux recommandés jusqu’au matériau combustible pour l'entretien B Côté Côté op- Côté opposé Côté porte Avant et posé à porte à la Taille de d'accès arrière la porte d'accès porte modèle (A) (B) (C) (A) (C) B Vue latérale 2,5 cm (1”) 91 cm (36”) Côté porte d'accès A C Vue de face j Le dégagement minimal jusqu’au matériau combustible est de 2,5 cm (1 in) à partir du toit. 100/125 20” (51 cm) 3” (8 cm ) 0” 36” (91 cm) 150/175 25” (64 cm) 3” (8 cm ) 0” 42” (107 cm) 200/225 27” (69 cm) 4” (10 cm) 0” 42” (107 cm) 250/300 30” (76 cm) 5” (13 cm) 0” 48” (123 cm) 350/400 41” (104 cm) 11” (28 cm) 0” 6” (15 cm) 60” (152 cm) 500/600 30” (76 cm) 5” (13 cm) 0” 48” (123 cm) 700/800 41” (104 cm) 11” (28 cm) 0” 60” (152 cm) 840/960 41” (104 cm) 11” (28 cm) 0” 60” (152 cm) Table 7.1 Combustible Material & Service Clearances Minimum Combustible Material Clearances Recommended Service Clearances NonNonAccess Access Access Side Side Side (C) (A) (C) Model Size Access Side (A) Front & Rear (B) 100/125 20” (51 cm) 3” (8 cm ) 0” 36” (91 cm) 150/175 25” (64 cm) 3” (8 cm ) 0” 42” (107 cm) 200/225 27” (69 cm) 4” (10 cm) 0” 42” (107 cm) 250/300 30” (76 cm) 5” (13 cm) 0” 48” (123 cm) 350/400 41” (104 cm) 11” (28 cm) 0” 6” (15 cm) 60” (152 cm) 500/600 30” (76 cm) 5” (13 cm) 0” 48” (123 cm) 700/800 41” (104 cm) 11” (28 cm) 0” 60” (152 cm) 840/960 41” (104 cm) 11” (28 cm) 0” 60” (152 cm) 5-572.11 7 SOUND ATTENUATION / ROOF CURB INSTALLATION SOUND AND VIBRATION LEVELS 4. All mechanical equipment generates some sound and vibration that may require attenuation. For critical areas, an acoustical consultant should be retained to assist in the application. Locating the equipment away from the critical area is desirable within ducting limitations. Frequently, units can be located above utility areas, corridors, restrooms, and other non-critical areas. Generally, a unit should be located within 15 feet (457 cm) of a primary support beam to minimize structure deflections. Smaller defections usually results in reduced vibration and noise transmission. Install the unit over roof decking with 2" (5 cm) acoustic fiberglass lining within curb area for sound attenuation. The return air duct should be acoustically lined and should be installed with a flexible connection. If the ceiling space is used as a plenum, the acoustically lined return intake duct should form an inverted tee with five foot minimum legs in each direction. The discharge duct should be acoustically insulated and should have a flexible connection as illustrated. 5. 6. 7. Outside dimensions must be held when installing curb. Top surface must be level and straight to insure weathertightness. All corners must be square. Final electric and gas connections must be made after unit is installed to allow for tolerance in setting of unit on curb. For electrical power supply allow approximately eight feet of wire, plus provisions for weathertight flexible conduit for connection to unit, as required by local codes. Maintain a 12" (30 cm) minimum height from top of roof deck to top of curb. Caulk butt joints after curb is assembled and installed on roof structural members and roof flashing is added. Figure 8.2 - Typical Curb Details Curb Gasketing* or Caulk by Others 2"x4" (5x10 cm) Counterflashing Wooden (By Others) Nailing Strip* Roofing Curb* Material (By Others) Figure 8.1 - Suggested Sound Attenuation Insulation (By Others) Cant Strip (By Others) 2" (5 cm) Acoustic Fiberglass (By Others) Roof Insulation (By Others) Roof Truss 6" (15 cm) Inverted Channel Both Sides (By Others) Roof Deck *Available as a factory supplied, field installed accessory. CURB OR SUB-BASE MOUNTED SITES An optional roof curb is available to simplify site preparation and raise the unit above roof water and snow level for drainage. It can be installed with the roof, and in advance of the unit. A sub-base must be furnished by the installer if no curb is supplied for the roof. The sub-base, either steel or concrete, must provide required support with the unit bolted to sub-base. The following are some general guidelines for roof curb installed units: 1. The roof structure must be adequately designed to support the live weight load of the unit and any other required support structure. For the bearing loads normally encountered, the roof curb should be supported at points no greater than 5 feet (152 cm) apart. Additional truss reinforcement should be provided, if necessary. 2. Roof curb must be installed level. If roof is pitched it will be necessary to construct a sub-base on which to install the curb. 3. Roof curbs supplied by Modine are fabricated from 16 gauge galvanized steel and supplied knocked down for assembly on the job site. The curb consists of two side pieces, two end pieces, gasketing, four joiner angles, four 2"x4" (5x10 cm) wood nailing strips, nuts, bolts, and washers. Roof curbs over 120" (305 cm) long include two additional side pieces and two splice plates. Refer to the latest revision of Modine literature 5-590 for instructions. 8 5-572.11 ROOF CURB INSTALLATION SITES D’INSTALLATION SUR REBORD OU SOUS-FONDATION Figure 9.1 - Détails d’un rebord typique Un rebord de toit est proposé en option pour simplifier la préparation du site et rehausser l'appareil au-dessus des niveaux d'eau et de neige sur le toit pour l’évacuation. Il peut être installé avec le toit et avant l'appareil. Une sous-fondation doit être prévue par l’installateur si aucun rebord n’est fourni pour le toit. La sous-fondation, en acier ou en béton, doit offrir le soutien requis une fois l’appareil boulonné à celle-ci. Directives générales pour les appareils installés sur un rebord de toit : 1. La structure du toit doit être correctement conçue pour soutenir la charge utile de l'appareil et de toute autre structure de soutien requise. Pour les charges normalement rencontrées, le rebord de toit doit être soutenu à des endroits se trouvant à une distance maximale de 152 cm (5 ft). Au besoin, une poutre de renforcement supplémentaire devra être fournie. 2. Le rebord de toit doit être installée de niveau. Si le toit est incliné, il faudra prévoir la construction d’une sousfondation sur laquelle le rebord sera installé. 3. Les rebords de toit offerts par Modine sont fabriqués avec de l’acier galvanisé de calibre 16 et fournis démontés pour l’assemblage sur le chantier. Le rebord comprend deux pièces latérales, deux pièces d’extrémité, des joints, quatre angles de menuisier, quatre bandes de clouage en bois de 5 x 10 cm (2" x 4"), des écrous, des boulons et des rondelles. Les rebords de toit mesurant plus de 305 cm (120") de longueur incluent deux pièces latérales supplémentaires et deux plaques d’épissure. Pour les instructions, reportez-vous à la dernière version de la documentation 5-590 de Modine. 4. Les dimensions extérieures doivent être respectées lors de l’installation du rebord. La surface supérieure doit être de niveau et droite pour assurer l’étanchéité météorologique. Tous les angles doivent être carrés. 5. Les branchements électriques et raccordements au gaz définitifs doivent être établis après l’installation de l'appareil sur le rebord. Pour l'alimentation électrique, comptez approximativement 2,4 m (8 ft) de câble et prévoyez un conduit flexible étanche pour le raccordement à l'appareil, selon les exigences des codes locaux. 6. Maintenez une hauteur minimale de 30 cm (12") du haut du platelage de toit jusqu’à la partie supérieure du rebord. 7. Calfeutrez les aboutages une fois le rebord assemblé et installé sur les membres structuraux du toit et après avoir ajouté le solin de toit. 5-572.11 Joint de rebord ou calfeutrage effectué par des tiers 5 x 10 cm (2” x 4”) Contre-solin Bande de (par des tiers) clouage en bois* Matériau de toiture Rebord* (par des tiers) Isolant (par des tiers) Tasseau biseauté (par des tiers) 5 cm (2”) Fibre de verre acoustique (par des tiers) Isolant de toit (par des tiers) Ferme de toit 15 cm (6”) Profilé des deux côtés Platelage de toit (par des tiers) *Disponible en accessoire installé sur le terrain. 9 SLAB MOUNT INSTALLATION / RIGGING INSTRUCTIONS Slab Mounted Units Table 10.1 - Slab Anchor Bolt Dimensions For Horizontal Discharge (Model Digit 2=B or C) For ground level installation of a horizontal-discharge unit, prepare a level concrete slab at least 4" (10 cm) thick on adequate footings and a generous bed of gravel for drainage (See Figure 10.1). The slab should include threaded 5/8-inch anchor bolts spaced as shown in Figure 10.1 and Table 10.1. Anchor bolts should extend at least 1.5" (4 cm) above the surface of the pad to allow clearance for mounting washers, nuts and bolts (mounting washers, nuts and bolts by others). The slab should extend out at least 6" (15 cm) around the perimeter of the unit. Digit 2 Model Size B All 150/175 All 82.91” 40.61” (2105.9 cm) (1031.5 cm) 200/225 All 82.91” 42.71” (2105.9 cm) (1084.8 cm) E, F, G, or H 82.91” 45.75” (2105.9 cm) (1162.1 cm) I, J, or K 118.5” 45.75” (3009.9 cm ) (1162.1 cm) E, F, G, or H 82.91” 57.27” (2105.9 cm) (1454.7 cm) I, J, or K 118.5” 57.27” (3009.9 cm ) (1454.7 cm) G or H 116.03” 45.75” (2947.2 cm) (1162.1 cm) I, J, K, or L 151.62” 45.75” (3851.2 cm) (1162.1 cm) G or H 116.03” 57.27” (2947.2 cm) (1454.7 cm) I, J, K, or L 151.62” 57.27” (3851.2 cm) (1454.7 cm) 840/960 All 185.02” 57.27” (4699.5 cm) (1454.7 cm) 100/125 All 106.89” 36.36” (2715.0 cm) (923.5 cm ) 150/175 All 106.89” 40.61” (2715.0 cm) (1031.5 cm) 200/225 All 106.89” 42.71” (2715.0 cm) (1084.8 cm) E, F, G, or H 106.89” 45.75” (2715.0 cm) (1162.1 cm) I, J, or K 142.48” 45.75” (3619.0 cm) (1162.1 cm) E, F, G, or H 106.89” 57.27” (2715.0 cm) (1454.7 cm) I, J, or K 142.48” 57.27” (3619.0 cm) (1454.7 cm) 350/400 700/800 Figure 10.1 - Slab-Mounted Make-Up Air Unit B C A 250/300 A & B ARE BETWEEN ANCHOR POINTS Figure 10.2 - Modèle d’air d’appoint installé sur dalle DALLE EN BÉTON SUR UN LIT DE GRAVIER (10 cm (4”) MINIMAL) B 10 350/400 A A ET B SE TROUVENT ENTRE LES POINTS D’ANCRAGE 5-572.11 B 100/125 500/600 CONCRETE SLAB ON GRAVEL BED (4” (10 cm) MIN) A 82.91” 36.36” (2105.9 cm) (923.5 cm ) 250/300 Modèles montés sur dalle Pour l’évacuation horizontale (dont le deuxième caractère du numéro de modèle = B ou C) Pour l’installation au niveau du sol d’un appareil à évacuation horizontale, préparez une dalle de béton de niveau d’une épaisseur d’au moins 10 cm (4") sur des semelles adéquates et un lit généreux de gravier pour l’évacuation (reportez-vous à la Figure 10.2). La dalle doit comprendre des boulons d’ancrage filetés de 5/8" espacés comme dans la Figure 10.2 et le Tableau 11.1. Les boulons d'ancrage doivent se prolonger au-delà de la surface de la dalle d’au moins 4 cm (1,5") pour permettre un dégagement suffisant pour la mise en place des rondelles, des boulons et des écrous (par des tiers). La dalle doit se prolonger d’au moins 15 cm (6") autour de l’appareil. Blower Type (Digit 16) SLAB MOUNT INSTALLATION / RIGGING INSTRUCTIONS Tableau 11.1 Dimensions des boulons d’ancrage à la dalle 2e chiffre Taille de modèle Type de ventilateur (16e chiffre) B 100/125 Tout 82.91” 36.36” (2105.9 cm) (923.5 cm ) 150/175 Tout 82.91” 40.61” (2105.9 cm) (1031.5 cm) 200/225 Tout 82.91” 42.71” (2105.9 cm) (1084.8 cm) E, F, G, or H 82.91” 45.75” (2105.9 cm) (1162.1 cm) I, J, or K 118.5” 45.75” (3009.9 cm ) (1162.1 cm) E, F, G, or H 82.91” 57.27” (2105.9 cm) (1454.7 cm) I, J, or K 118.5” 57.27” (3009.9 cm ) (1454.7 cm) G or H 116.03” 45.75” (2947.2 cm) (1162.1 cm) I, J, K, or L 151.62” 45.75” (3851.2 cm) (1162.1 cm) G or H 116.03” 57.27” (2947.2 cm) (1454.7 cm) I, J, K, or L 151.62” 57.27” (3851.2 cm) (1454.7 cm) 840/960 Tout 185.02” 57.27” (4699.5 cm) (1454.7 cm) 100/125 Tout 106.89” 36.36” (2715.0 cm) (923.5 cm ) 150/175 Tout 106.89” 40.61” (2715.0 cm) (1031.5 cm) 200/225 Tout 106.89” 42.71” (2715.0 cm) (1084.8 cm) E, F, G, or H 106.89” 45.75” (2715.0 cm) (1162.1 cm) I, J, or K 142.48” 45.75” (3619.0 cm) (1162.1 cm) E, F, G, or H 106.89” 57.27” (2715.0 cm) (1454.7 cm) I, J, or K 142.48” 57.27” (3619.0 cm) (1454.7 cm) 250/300 B A AVERTISSEMENT 350/400 500/600 700/800 C 250/300 350/400 Le non-respect d’une bonne procédure de levage et des procédures de sécurité qui s’appliquent pourrait mener à des dommages matériels ou à des blessures graves, voire mortelles. Le levage doit être effectué uniquement par une entreprise spécialisée dans le gréage. Utilisez TOUS les points de levage. Testez le levage pour assurer un bon équilibre et un bon gréage. Ne procédez jamais au levage de l’appareil par vents forts. Rigging and lifting of the units should only be done by a qualified rigging company and follow appropriate industry standards, including but not limited to the appropriate sections of ASME B30, OSHA 1910, and OSHA 1926. Four 3/4-inch holes at the extended ends of the mounting channels are supplied to facilitate lifting the unit with eyebolts furnished by the installer. With the lifting points identified, the units can be lifted by crane or helicopter. 1. Follow site preparation instructions for the roof curb, slab, or equipment stand before installation. 2. Check the Serial Plate(s) of unit with plans to be sure unit is properly located. Although units may look outwardly similar, their function, capacities, options, and accessories will often vary. 3. Check unit dimensions of both the unit base and the curb or stand on which the unit will be installed. 4. If the unit will be installed on a roof curb: a. Thoroughly clean and dry the top of the curb surface. b. Lay a bead of weather resistant caulking on top perimeter of roof curb as illustrated in Figure 8.2. Note: If roof curb is supplied by Modine, full perimeter gasket material is supplied and caulking is not necessary. 5. When lifting the equipment, connect sturdy steel cables, chains, or straps with eye loops as illustrated in Figure 11.1. For stability in lifting and lowering and to prevent damage to the unit, include a spreader bar as shown in Figure 11.1. Avoid twisting or uneven lifting of the unit. The cable length from the lifting point on the unit to the spreader bar should always be longer than the distance between the outer lifting points. 6. Test lift the unit to check for proper rigging balance before hoisting to the desired installation location. 7. Once lifted to the installation location, orient the hoisted unit to match the ductwork locations and set evenly on the curb or stand. 8. Following the instructions in this manual, make final unit connections for ductwork, utilities, and controls. Figure 11.1 - Typical Rigging General Rigging Instructions INSTALLER’S CABLES AND SPREADERS WARNING Failure to follow proper lifting instructions and applicable safety procedures could result in property damage, serious injury, or death. Lifting should only be done by a qualified rigging company. Use ALL lifting points. Test lift to ensure proper balance and rigging. Never lift in high winds. INSTALLER’S EYE BOLTS ROOF CURB 5-572.11 11 DUCT INSTALLATION / UTILITY CONNECTIONS Duct Installation 1. 5. The blower section inlet and/or return air connections, as well as the furnace furnace discharge are designed to accept 90° flanged ductwork as shown in Figure 12.1. To determine locations and dimensions of connections, refer to the dimensional drawings later in this manual. Figure 12.1 - Duct Connections UNIT INLET OR DISCHARGE OPENING 1/2" 6. On horizontal discharge units with Model Digit 2=B, provide removable access panels on the downstream side of the unit as shown in Figure 12.1. These openings should be large enough to view smoke or reflect light inside the casing to indicate leaks in the heat exchanger and to check for hot spots on the heat exchanger due to a lack of sufficient airflow (CFM). This is not required on horizontal discharge units with Model Digit 2=C because the cooling coil cabinet access door can be removed for this purpose. When a roof curb is used in conjunction with a factory supplied return air connector, the ductwork can be fastened to the connectors prior to the unit installation. The connectors will accept 90° flanged ductwork. See Figure 12.3. Figure 12.3 - Discharge and/or Return Air Connectors UNIT BASE 90° FLANGED DUCTWORK 2. 3. 4. 90° FLANGED DUCTWORK (BY INSTALLER) ACCESS PANEL FOR HORIZONTAL DISCHARGE UNITS (MODEL DIGIT 2=B) Provide an airtight seal between the ductwork and the unit. Seams with cracks in the ductwork should be permanently caulked and/or taped. All duct connections outside the building MUST be weathertight to prevent rain and snow from entering the ductwork. Acoustic duct liners are recommended on all internal supply and return air ducts. Provide uniform air distribution over the heat exchanger. Use turning vanes in the supply ductwork where required to obtain uniform air distribution. See Figure 12.2. Figure 12.2 - Recommended Discharge Duct Configs DIMENSION “B” SHOULD NEVER BE LESS THAN 1/2 OF DIMENSION “A” TURNING VANES (3” MAX) PROVIDE LEAK TIGHT ACCESS PANELS IN DISCHARGE DUCT FOR HEAT EXCHANGER INSPECTION. ROOF CURB RETURN AIR CONNECTOR DISCHARGE AIR CONNECTOR CAULK ALL MATING SURFACES BEFORE INSTALLING DUCTWORK TO CONNECTORS OR SETTING THE UNIT (CAULK BY INSTALLER) Utility Connections Utility and control connections can be made to the unit from the bottom for roof curb-mounted units or through the fixed side panels for horizontal supply and return units. Holes can be made in fixed side panels to accommodate utility connections as specified according to the unit dimensional drawings. Sealing of holes cut in the unit casing for utility connections should be done with care to prevent air and water leaks. Venting 1. TURNING VANES (3” MAX) PROVIDE LEAK TIGHT ACCESS PANELS IN DISCHARGE DUCT FOR HEAT EXCHANGER INSPECTION. 2. 3. 4. TURNING VANES (3” MAX) 12 5-572.11 Installation of venting must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/ CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units. Units are shipped with the power exhauster discharge cover factory installed. Do not modify or obstruct the combustion air inlet louvers or the power exhauster discharge cover. Do not add any vents other than those supplied by the manufacturer. THIS PAGE INTENTIONALLY LEFT BLANK 5-572.11 13 UNIT INSTALLATION Gas Connections 1. WARNING 1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing. 2. Gas pressure to appliance controls must never exceed 3.4 kPa (14" W.C. or 1/2 psi). 3. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units. AVERTISSEMENT 2. 3. 4. 1. Toutes les canalisations de gaz sur site doivent être testées (pression/fuites) avant usage. Ne recherchez jamais les fuites avec une flamme nue. Utilisez plutôt de l’eau savonneuse ou un produit équivalent. 2. La pression de gaz aux commandes de l’appareil ne doit jamais dépasser 3.4 kPa (35,5 cm C.E. ou 1/2 psi). 3. Pour réduire le risque de condensation, l’entrée minimum dans l’appareil au niveau de la mer, telle qu’indiquée sur la plaque de série, ne doit pas être moins de 5 % inférieure à la valeur d’entrée nominale des appareils à double valeur nominale. CAUTION Purging of air from gas supply line should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes. 5. ATTENTION La purge de l’air des tuyauteries de gaz doit se faire selon la procédure ANSI Z223.1 de la dernière édition du « National Fuel Gas Code » ou des codes CAN/CGA-B149 du Canada. IMPORTANT 6. 1. Unit can be operated up to a maximum of 10,000 feet (3048 m). 2. To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%. IMPORTANT 1. L’unité peut être utilisée jusqu’à un maximum de 3048 m (10,000 ft). 2. Pour éviter une défaillance prématurée de l’échangeur de chaleur, le pouvoir calorifique du gaz utilisé ne doit pas excéder de plus de 5 % la valeur nominale inscrite sur la plaque signalétique de l’appareil. 14 5-572.11 Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/ CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Model Digits 4-6 of the Model Nomenclature on page 62 and the value on the unit Model ID plate (not individual furnace serial plates) to determine the gas heating capacity in Thousands of Btu/hr (MBH). The Model ID plate is located on the blower section electrical compartment door. See Figure 61.3 for an example Model ID plate. For the length of pipe necessary, determine the pipe diameter from Table 16.1 or Table 16.2 for the unit heating capacity. Where several units are served by the same main, the total capacity and length of main must be considered. While the gas connection(s) on the unit may be smaller than the required supply pipe diameter, do not use pipe sizes smaller than what is required leading up to the unit. At the unit, reduce the pipe size down to the appropriate size (sizes 100-225 are 1/2" connections, 250-960 are 3/4" connections). Avoid pipe sizes smaller than 1/2". The inlet pressure to the unit must be 6-7" W.C. for natural gas and 11-14" W.C. for propane gas. When sizing the inlet gas pipe diameter, be sure the unit supply pressure can be met after the line pressure drop has been subtracted. If the line pressure drop is too high, refer to NFPA 54 National Fuel Gas Code for other gas pipe capacities. The gas piping to the unit can enter the unit from the side of the unit or from below. Install a ground joint union with brass seat and a manual shut-off valve external of the unit casing, and adjacent to the unit for emergency shutoff and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (See Figure 15.1). Verify the manual shut-off valve is gas tight on an annual basis. Provide a sediment trap before each unit in the line where low spots cannot be avoided. (See Figure 15.1). UNIT INSTALLATION Figure 15.1 - Recommended Sediment Trap/Manual Shut-off Valve Installation - Side or Bottom Gas Connection GAS SUPPLY LINE GAS SUPPLY LINE MANUAL GAS SHUT-OFF VALVE GROUND JOINT UNION W/ BRASS SEAT TO CONTROLS PLUGGED 1/8" NPT TEST GAGE CONNECTION 3" MIN. SEDIMENT TRAP 7. When Pressure/Leak testing, pressures above 14" W.C. (1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing. 5-572.11 15 UNIT INSTALLATION Table 16.3 - Burner Orifice Sizing and Gas Consumption Table 16.1 - Gas Pipe Capacities - Natural Gas j Pipe Length (ft) 10 20 30 40 50 60 70 80 90 100 125 150 175 200 250 Capacity in MBH by Nominal Pipe Diameter 3” 9,009 6,195 4,977 4,253 3,770 3,423 3,150 2,930 2,741 2,594 2,300 2,079 1,911 1,785 1,575 Model Size j G as pipe capacities based on Table 6.2.1 (a) of NFPA 54 for schedule 40 metallic pipe with inlet pressure less than 2 psi, with a pressure drop of 0.3" w.c. and gas specific gravity of 0.60. 300 1∕2” 138 95 76 65 58 53 48 44 42 40 35 32 29 27 24 3∕4” 287 197 159 135 120 109 100 93 87 83 74 66 61 57 50 1” 540 371 298 255 226 205 188 175 165 155 138 125 114 107 95 1 1∕4” 1 1∕2” 1,113 1,659 762 1,145 612 917 524 784 464 695 420 630 386 580 360 540 338 506 319 478 282 423 256 384 235 353 219 329 194 291 2” 3,203 2,195 1,764 1,512 1,344 1,218 1,113 1,038 974 921 816 739 680 632 561 2 1∕2” 5,103 3,507 2,814 2,405 2,132 1,932 1,775 1,659 1,554 1,470 1,302 1,176 1,082 1,008 894 Table 16.2 - Gas Pipe Capacities - Propane Gas k Pipe Length (ft) 10 20 30 40 50 60 80 100 125 150 175 200 250 1∕2” 291 200 160 137 122 110 101 94 89 84 74 67 62 Capacity in MBH by Nominal Pipe Diameter 3∕4” 1” 1 1∕4” 1 1∕2” 2” 2 1∕2” 3” 608 1,150 2,350 3,520 6,790 10,800 19,100 418 787 1,620 2,420 4,660 7,430 13,100 336 632 1,300 1,940 3,750 5,970 10,600 287 541 1,110 1,660 3,210 5,110 9,030 255 480 985 1,480 2,840 4,530 8,000 231 434 892 1,340 2,570 4,100 7,250 212 400 821 1,230 2,370 3,770 6,670 197 372 763 1,140 2,200 3,510 6,210 185 349 716 1,070 2,070 3,290 5,820 175 330 677 1,010 1,950 3,110 5,500 155 292 600 899 1,730 2,760 4,880 140 265 543 814 1,570 2,500 4,420 129 243 500 749 1,440 2,300 4,060 k Gas pipe capacities based on Table 6.3.1(d) of NFPA 54 for schedule 40 metallic pipe with inlet pressure of 11.0" w.c., with a pressure drop of 0.5" w.c. and gas specific gravity of 1.50. 16 100 125 150 175 200 225 250 350 400 500 l 600 l 700 l 800 l 840 m 960 m Gas Type Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Cfh Orifice Drill Size Natural j Propane k 96.1 30 120.2 25 144.2 30 168.3 27 192.3 23 216.3 20 240.4 25 288.7 20 336.5 27 384.6 23 240.4 25 288.7 20 336.5 27 384.6 23 336.5 27 384.6 23 40.0 45 50.0 42 60.0 45 70.0 43 80.0 42 90.0 39 100.0 42 120.0 39 140.0 43 160.0 42 100.0 42 120.0 39 140.0 43 160.0 42 140.0 43 160.0 42 Orifice Qty 2 2 3 3 3 3 4 4 6 6 4 4 6 6 6 6 j B ased on natural gas properties of 1050 Btu/ft³ and specific gravity of 0.60. k B ased on propane gas properties of 2500 Btu/ft³ and specific gravity of 1.50. l Model sizes 500-800 contain 2 furnaces. Values shown are per furnace. m Model sizes 840-960 contain 3 furnaces. Values shown are per furnace. 5-572.11 UNIT INSTALLATION CONSIDERATIONS FOR ELEVATION The standard ratings for the duct furnace(s) used in these units are certified for elevations up to 2000 feet above sea level. Operation at elevations above 2,000 feet requires ratings be reduced 4% for each 1000 feet above sea level per ANSI Z223.1. The exception is for units in Canada, CSA requires that ratings be reduced 10% for elevations between 2,001 and 4500 feet. The following instructions are for units that will be installed over 2,000 feet elevation. If this does not apply, you may skip ahead to the Electrical Connections section on page 18. Unit can be operated up to a maximum of 10,000 feet (3048 m). needed later for Start-Up. Proceed to the section on this page titled “Selection of the Proper High Altitude Kit”. Equation 17.1 - Manifold Pressure for Gas Heating Values Different Than Shown in Table 17.1 Where: Manifold Pressure Adjustment The unit manifold pressure is factory set for operation at elevations up to 2000 feet as follows: • For Natural Gas units, 3.5" W.C. based on a gas heating value of 1,050 BTU/ft³. • For Propane Gas units, 10.0" W.C. based on a gas heating value of 2,500 BTU/ft³. For higher elevations, some utility companies may derate the BTU content (heating value) of the gas provided at altitude to a lower value to allow certain heating appliances to be used with no manifold pressure adjustments. For this reason it is necessary that the supplying utility be contacted for detailed information about the gas type and BTU content (heating value) before operating any heater. Table 17.1 shows the standard derated heating values of natural and propane gases at various elevations. Table 17.1 - Gas Heating Values at Altitude (Btu/ft³) jkln Altitude (ft) Natural Gas 0-2,000 2,001-3,000 3,001-4,000 4,001-4,500 4,501-5,000 5,001-6,000 6,001-7,000 7,001-8,000 8,001-9,000 9,001-10,000 1,050 Propane 2,500 929 l 892 l 874 l 856 822 789 757 727 698 2,212 m 2,123 m 2,080 m 2,038 1,957 1,879 1,803 1,731 1,662 MPELEV = Manifold Pressure (" W.C.) at installed elevation BTUTBL = BTU/ft³ content of gas from Table 17.1 BTUACT = BTU/ft³ content of gas obtained from the utility company MPSL = Manifold Pressure (" W.C.), at Sea Level (use 3.5" W.C. for natural gas and 10.0" W.C. for propane) Note: For units equipped with two-stage or modulating gas controls, only the high fire manifold pressure needs to be adjusted. No adjustments to the low fire manifold pressure are necessary on these units. Selection of the Proper High Altitude Kit All units installed at elevations greater than 2000 feet above sea level require a kit, in addition to potential manifold pressure adjustment outlined in the previous step. To determine the proper kit to use, refer to Table 17.2 Table 17.3 shows the contents of the kit. For more information, refer to the latest revision of Modine Bulletin 75-530. Table 17.2 - High Altitude Kit Selection Table jkl Model Model Size All All Elevation Above Sea Level (ft) 2,001-5,500 5,501-6,500 6,501-7,500 Item Code 67248 67248 67248 j Applies to both installations in the U.S. and Canada. k Applies to both natural and propane gas. l S izes 75-400 require a kit qty. of 1, sizes 500-800 require a kit qty of 2, sizes 840-960 require a kit qty of 3. j Values shown are for 3.5" W.C. manifold pressure for Natural Gas and 10.0" W.C. for Propane Gas. If the local utility supplies gas with a different Btu/ft³ value, use Equation 17.1 to calculate the required manifold pressure. k Gas heating values shown are derated 4% per 1,000' of elevation (10% between 2,000' and 4,500' elevation in Canada) in accordance with ANSI Z223.1 and CSA-B149, respectively. l 945 Btu/ft³ for Canada m 2,250 Btu/ft³ for Canada n When installed at altitudes above 2,000', a pressure switch may need to be changed. Refer to Table 17.2 and Table 17.3 to determine if a switch change is required. If the utility is supplying gas with heating values SAME as shown in Table 17.1, the manifold pressure should remain set to 3.5" W.C. for natural gas and 10.0" W.C. for propane gas and you may proceed to the section on this page titled “Selection of the Proper High Altitude Kit”. If the utility is supplying gas with heating values DIFFERENT than shown in Table 17.1, use Equation 17.1 to determine the appropriate manifold pressure for the elevation and gas heating value being supplied. Note what that value is, as it will be Table 17.3 - High Altitude Kit Contents Item Code 67248 Kit Contents High Altitude Conversion Label Pressure Switch Installation Instructions Yes No Yes If a unit is to be installed at higher elevations AND converted from natural gas to propane gas operation, a propane conversion kit must be used in conjunction with the manifold pressure adjustment and high altitude kit listed above. For the Selection and Installation Instructions for propane conversion kits, please see the latest revision of Modine Bulletin 75-511. 5-572.11 17 UNIT INSTALLATION Electrical Connections 2. WARNING 1. Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage. 2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property. 3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C. 4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage. AVERTISSEMENT 1. Débranchez l’alimentation électrique avant d’effectuer des connexions ou de travailler sur l’appareil. Respectez toutes les procédures de sécurité qui s’appliquent pour éviter toute mise en marche accidentelle. Le non-respect de cette directive peut entraîner des blessures ou la mort causées par un choc électrique ou des pièces mobiles, en plus d’endommager l’appareil. 2. Tous les appareils doivent être branchés de manière strictement conforme au diagramme fourni. Tout câblage différent de celui du schéma peut créer des risques de dommages matériels ou de blessures. 3. Tout câblage usine d’origine exigeant un remplacement doit être remplacé par un câble d’indice thermique nominal de 105 °C. 4. Assurez-vous que la tension d’alimentation de l’appareil, comme indiqué sur la plaque de série, n’est pas de 5 % supérieure à la tension nominale. 3. 4. 5. 6. 7. Table 18.1 - 24V and Digital Control Wire Lengths CAUTION 1. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage. 2. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced. 8. ATTENTION 1. Vérifiez que la tension d’alimentation de l’appareil n’est pas inférieure de plus de 5 % à la tension nominale inscrite sur la plaque de série. 2. Ne tentez pas de réutiliser un composant mécanique ou électrique qui a été mouillé. Ces composants doivent être remplacés. 1. 18 Two copies of the job specific wiring diagram are provided with each unit, one located in the duct furnace electrical junction box and one in the electrical section of the unit located in the blower compartment. Refer to this diagram for all wiring connections. External electrical connections to be installed include: • Supply power (120, 208, 240, 480, or 600 volts). • Thermostats, remote monitoring panels, building pressure sensors, time clocks, or any other accessory control devices that may be supplied (24 volts). All supply power electrical connections are made in the electrical section of the unit. The low voltage (thermostat and accessory control devices) may be wired to either the electrical section or the duct furnace electrical junction box. Refer to the wiring diagram for the terminal location of all low voltage wiring. Refer to the unit dimensional drawings in this document for the location of the drill locator dimples in the side and bottom of the unit for field drilling the hole for the electrical conduit entry. Control wiring consists of both 24V analog control wiring and for models with Model Digit 12=9, low current digital control signal wiring. To avoid signal interference, the two types should be run in conduit separate from power wiring. The analog control wiring should be shielded at one end of the wiring run. Wiring should be stranded, twisted, and shielded communication wire. The wire gauge must be sized according to the National Electric Code or CSA code based on amp draw and length of run. Refer to Table 18.1 for maximum wire lengths that can be wired between components and the terminal block on the unit based on the wire gauge being used. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code. 5-572.11 Maximum Distance (feet) from Control Device to Unit Minimum Recommended Wire Gauge 24V Control Wiring Digital Control Wiring 22 20 18 16 14 n/a n/a 75 125 175 120 200 300 500 n/a FOR UNITS WITH MODEL DIGIT 12=9 (MODINE CONTROL SYSTEM OPTION): For field wiring to the factory terminal strip, the terminal strip connections are designed to clamp down on the wires. To properly connect the wires to the terminal strip: • Push a small flat-head screwdriver into the square hole on the terminal. Press firmly until the screwdriver hits the back stop and opens the terminal (see Figure 19.1). • Remove approximately 3/8” of insulation from the end of the wire and push the stripped wire into the oval hole in the terminal. • Remove the screwdriver. Pull on the wire to make sure that it is securely clamped in the terminal. • Make sure that the terminal clamp is in contact with bare wire (insulation removed). UNIT INSTALLATION Figure 19.1 - Terminal Strip Wiring (Model Digit 12=9) Oval Holes for Wiring (two rows each) Square Holes for Wire Release (two rows each) Terminal Numbers Test Probe Points 9. Factory Mounted Option Locations (Figure 29.1) for the factory mounted disconnect switch location and then review the unit to determine if a factory installed dead front disconnect switch was provided. Accessory field installed disconnect switches should be mounted where required by the National Electric Code as shown in Figure 29.1. For fusible disconnect switches, refer to the Model Identification plate for the fuse size and type. 12. The power supply must be within 5% percent of the voltage rating and each phase must be balanced within 2 percent of each other. If not, advise the utility company. 13.All outdoor electrical connections must be weatherized to prevent moisture from entering the electrical compartment. Figure 19.2 - Recommended Accessory Field Installed Disconnect Switch Mounting Locations Depending on the configuration of the unit controls, there may be sensors that are field installed. Review the unit ordered to verify that the sensors supplied match the configuration of the unit. The following are sensors that may be included for field installation (for installation instructions, refer to the instructions included with the individual sensors): • Supply Air Temperature Sensor This sensor is required on all units and is mounted in the supply air ductwork downstream of the unit discharge. • Outdoor Air Sensor This sensor is required on all units except 100% return air units. Depending on the unit configuration, the sensor may be duct mounted or remote mounted. • Return Air Sensor This sensor is required on all units that have a mixture of outside and return air. The sensor is mounted in the return air ductwork. • Space Temperature/Humidity Sensor This sensor is required on all units that have space temperature/humidity reset control. • Duct Pressure Sensor This sensor is required on all units that have duct pressure control through variable frequency drive control on the supply air blower. • Space CO2 Sensor This sensor is required on all units that have demand based ventilation control based on space CO2 concentration. • Duct Mounted Smoke Detector This sensor is mounted in the supply air or return air ductwork. Evaporative Cooler Installation For units equipped with an evaporative cooler (Model Digit 22=D), refer to Installation and Service Manual - Evaporative Coolers (Literature 5-588). Evaporative Cooler operating conditions. • Min. Water Pressure: 35 psig (241 kPa) • Max. Water Pressure: 100 psig (689 kPa) • Min. Water Temperature: 40 F (4 C) • Max. Water Temperature: 130 F (54 C) Conditions d’utilisation du refroidisseur par évaporation. • Pression d’eau : 241 kPa (35 psig) • Pression d’eau : 689 kPa (100 psig) • Température de l’eau : 4 °C (40 °F) • Température de l’eau : 54 °C (130 °F) Figure 19.3 - Evaporative Cooler (Model Digit 22=D) For further instructions on the above sensor(s), refer to the installation instructions that shipped with the sensor(s). 10. Make sure all multi-voltage components (motors, transformers, etc.) are wired in accordance with the power supply voltage. 11. The power supply to the unit must be protected with a fused or circuit breaker disconnect switch. Refer to the 5-572.11 19 UNIT INSTALLATION Cooling Coil Units Direct Expansion (DX) Piping Units with a cooling section (Model Digit 2=C or P) can be provided with a factory installed direct expansion (DX) coil, or the coil can be field supplied and installed by others. For units equipped with a factory installed cooling coil (Model Digit 23=1), refer to the packing slip to determine the coil type provided. The section includes a full coverage, 3-way sloping stainless steel drain pan to remove condensate from coil headers and piping components. Insulation is standard on outdoor units and optional on indoor units. The cabinet includes two doors, a removable upper door for service access to the coil once the plumbing has been installed and a lower door which includes a 1" drain connection to the exterior of the cabinet. Field connections for coil inlet and outlet piping can be made through the cabinet corner post or back of the unit. The cooling section duct transition includes 1.5" (3.8 cm) flanges for fastening the sides of the coil. The bottom duct transition is angled to remove any condensation that may be entrained in the supply air stream. For field supplied coils, do not exceed the maximum coil dimensions listed in Literature 82-135. If the coil supplied is smaller than the listed dimensions, field supplied blank off plates are required to prevent air bypass around the coil. The coil is supported by two 14 gauge support rails which contain mounting provisions for fastening 4"(10.2 cm), 5"(12.7 cm), 6"(15.2 cm), 7.5" (19.1 cm), and 10" (25.4 cm) deep coils. Figure 20.1 - Cooling Section (DX Coil Shown) Optional double wall construction The refrigerant lines should be insulated to prevent warming or cooling of the refrigerant. If the suction line is allowed to be cooled, liquid will condense in the line and can severely damage the compressor. If the liquid line is warmed, the refrigerant can "flash" into a gas. This will cause erratic operation of the expansion device and impair the heat transfer ability of the cooling coil. Long runs of piping need to be periodically supported to prevent excess vibration that can damage the piping and joints. It is recommended to provide dampening supports at intervals of length equivalent to 15 tube diameters. Figure 20.2 - General DX Piping SUCTION HEADER DISTRIBUTOR EQUALIZER LINE LIQUID LINE SUCTION LINE REMOTE SENSING BULB 2. 3. Optional Factory Installed DX coil. Fin spacings of 10,12 or 14 fins per inch Adjustable mounting bracket for 4 and 6 row coils 4. 5. 6. 7. Full coverage 3-way sloping 409 stainless steel drain pan Right or left hand coil header access to match gas controls 1” stubbed drain connection 8. Condensate Drain Pan Trap The condensate drain line needs to include a P-trap immediately downstream of the connection to the unit. This trap should extend at least 2" (5 cm) below the connection to prevent air pressure from forcing air into the unit. The trap should be primed with a water/glycol solution to prevent freezing. 20 NOZZLE EXPANSION VALVE (BY OTHERS) 1. DX single circuit (shown) and dual circuit coils available COIL 5-572.11 STRAPS SUCTION CONNECTION Inspect the refrigerant distributor and verify that the nozzle is in place. All field brazing welding should be performed using high quality materials and an inert gas purge (such as nitrogen) to reduce oxidation of the internal surface of the coil. The use of filter-dryers in the system piping is recommended along with a sight glass that has a moisture indicator. Connect the suction line and suction connection. Install the expansion valve (by others). Follow the expansion valve manufacturer's recommendations for installation to avoid damaging the valve. Connect the liquid line to the expansion valve. Pressurize the coil, expansion valve assembly and suction connection to 100 psig with dry nitrogen or other suitable gas. The coil should be left pressurized for a minimum of 10 minutes. If the coil holds pressure, the installation can be considered leak free. If the pressure drops by 5 psi or less, repressurize the coil and wait another 10 minutes. If the pressure drops again, there are more than likely one or more small leaks, which should be located and repaired. Pressure losses greater than 5 psi would indicate a larger leak, which should be isolated and repaired. Be sure to check valves and fittings as potential sites for leakage or bleed. Use a vacuum pump to evacuate the coil and any interconnecting piping that has been open to atmosphere. Measure the vacuum in the piping using a micron gauge located as far from the pump as possible (the vacuum at the pump will be greater than the rest of the system). Evacuate the coil to 500 microns or less then close the valve between the pump and the system. If the vacuum holds to 500 microns or less for one minute, the system is ready to be charged or refrigerant pumped down in another portion of the system can be opened to the coil. UNIT INSTALLATION A steady rise in microns would indicate that moisture is still present and that the coil should be further vacuumed until the moisture has been removed. 9. Failure to obtain a high vacuum is indicative of a great deal of moisture or a small leak. Break the vacuum with a charge of dry nitrogen or other suitable gas and recheck for leaks (soapy water works well). If no leaks are found, continue vacuuming the coil until the desired vacuum is reached. 10 All field piping must be self-supporting. Table 21.1 - Cooling Coil Performance Limits Cooling Model Type Size Min CFM 100 802 l 125 926 150 1,111 175 1,296 200 1,481 225 1,667 250 1,852 300 2,222 350 2,593 400 2,963 DX Single Circuit Dual Circuit Max CFM j Area (ft²) Max CFM j Area (ft²) Max Cooling (Tons) k 2,206 4.01 2,048 3.72 11.4 2,521 4.58 2,416 4.39 13.4 3,352 6.09 3,165 5.76 18.1 3,724 6.77 3,538 6.43 20.2 5,214 9.48 4,996 9.08 27.3 j Based on 550 feet per minute (FPM) coil face velocity. k Based on 95°F/75°F Entering Dry Bulb/Wet Bulb. l Model Size 100 minimum CFM for DX Dual Circuit is 745. 5-572.11 21 START-UP PROCEDURE Start-Up Procedure IMPORTANT 1. T o prevent premature heat exchanger failure, observe heat exchanger tubes by looking at the heat exchanger through the field installed access openings in connecting ductwork or the unit access doors where viewing the heat exchanger is possible. If the bottom of the tubes become red while blower and duct furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 26 for Blower Adjustments. 2. Start up and adjustment procedures, installation, and service of these appliances must be performed by a qualified installation and service agency. IMPORTANT 1. P our éviter la défaillance prématurée de l’échangeur de chaleur, examinez les tubes de l’échangeur de chaleur en le regardant à travers les ouvertures d’accès installées sur les lieux lors de la connexion des tuyaux ou les portes d’accès à l’unité où il est possible de voir l’échangeur de chaleur. Si le bas des tubes devient rouge lorsque la soufflante et la chaudière canalisée sont en marche, vérifiez que le régime de la soufflante est approprié pour l’application. Pour le réglage de la soufflante, reportezvous à la page 26. 2. Les procédures de démarrage et de réglage, l’installation et le service de ces appareils doivent être confiés à un centre d’installation et de service qualifié. Refer to page 60 for the Start-up Checklist. 1. Turn off power to the unit at the disconnect switch. Check that fuses or circuit breakers are in place and sized correctly. Turn all hand gas valves to the “OFF” position. 2. Remove the blower exterior panels and open the electrical compartment door. 3. Check that the supply voltage matches the unit supply voltage listed on the Model Identification plate. Verify that all wiring is secure and properly protected. Trace circuits to insure that the unit has been wired according to the wiring diagram. 4. Check to insure that the venting system is installed and free from obstructions. 5. Check to see that there are no obstructions to the intake and discharge of the unit. 6. Check the belt tension and sheave alignment. Refer to Blower Adjustments for proper belt tension. 7. Check bearings for proper lubrication. For units provided with pillow block bearings (See Model Nomenclature), refer to Lubrication Recommendations for requirements. 8. Check to make sure that all filters are in place and that they are installed properly according to direction of air flow. 9. Perform a visual inspection of the unit to make sure no damage has occurred during installation. 10. Turn on power to the unit at the disconnect switch. Check to insure that the voltage between duct furnace electrical box terminals 1 and 2 is 24V. 11. Check the thermostat, ignition control, gas valve, and supply fan blower motor for electrical operation. If these do not function, recheck the wiring diagram. Check to insure that none of the Control Options have tripped. 22 12. For units with a return air damper, the return air damper linkage needs to be adjusted. Refer to Damper Linkage Adjustment. 13. Check to make sure that the damper opens properly without binding. 14. Check the blower wheel for proper direction of rotation when compared to the air flow direction arrow on the blower housing. Blower wheel rotation, not air movement, must be checked as some air will be delivered through the duct furnace with the blower wheel running backwards. 15. Check the blower speed (rpm). Refer to Blower Adjustments for modification. 16. Check the motor speed (rpm). 17. Check the motor voltage. On three phase systems, check to make sure all legs are in balance. 18. Check the motor amp draw to make sure it does not exceed the motor nameplate rating. On three phase systems, check all legs to insure system is balanced. 19. Recheck the gas supply pressure at the field installed manual shut-off valve. The minimum inlet pressure should be 6" W.C. on natural gas and 11" W.C. on propane gas. The maximum inlet pressure for either gas is 14" W.C. If inlet pressure exceeds 14" W.C., a gas pressure regulator must be added upstream of the combination gas valve. 20. Open the field installed manual gas shut-off valve. 21. Open the manual main gas valve on the combination gas valve. Call for heat with the thermostat and allow the pilot to light for intermittent pilot ignition. If the pilot does not light, purge the pilot line. If air purging is required, disconnect the pilot line at outlet of pilot valve. In no case should the line be purged into heat exchanger. Check the pilot flame length (See Pilot Flame Adjustment). 22. Once the pilot has been established, check to make sure that the main gas valve opens. Check the manifold gas pressure (See Main Gas Adjustment) and flame length (See Air Shutter Adjustment) while the supply fan blower is operating. 23. Check to insure that gas controls sequence properly (See Control Operating Sequence). Verify if the unit has any additional control devices and set according to the instructions in the Control Options. 24. Once proper operation of the unit has been verified, remove any jumper wires that were required for testing. 25. Close the electrical compartment door. 26. Replace all exterior panels. 5-572.11 START-UP PROCEDURE Pilot Burner Adjustment The pilot burner is orificed to burn properly with an inlet pressure of 6-7" W.C. on natural gas and 11-14" W.C. on propane gas. Final adjustment must be made after installation. If the pilot flame is too long or large, it may cause soot and/or impinge on the heat exchanger causing failure. If the pilot flame is too short, it may cause poor ignition or result in the controls not opening the combination gas control. A short flame can be caused by a dirty pilot orifice. The pilot flame should be observed periodically to assure trouble-free operation. To Adjust the Pilot Flame 1. Create a call for heat from the thermostat. 2. Remove the cap from the pilot adjustment screw. For location, see the combination gas control literature supplied with unit. 3. Adjust the pilot length by turning the screw in or out to achieve a soft steady flame 3/4" to 1" long and encompassing 3/8"-1/2" of the tip of the flame sensing rod (See Figure 23.1). 4. Replace the cap from the pilot adjustment screw. Figure 23.1 - Correct Pilot Flame Flame Sensing Rod 3/4" to 1" 5-572.11 23 START-UP PROCEDURE Main Burner Adjustment 7. The gas pressure regulator (integral to the combination gas control) is adjusted at the factory for average gas conditions. It is important that gas be supplied to the duct furnace in accordance with the input rating on the serial plate. Actual input should be checked and necessary adjustments made after the duct furnace is installed. Over-firing, a result of too high an input, reduces the life of the appliance and increases maintenance. Under no circumstances should the input exceed that shown on the serial plate. Check/Adjust Pressure at the Combination Gas Valve This section applies to all units, regardless of gas control type. 1. Turn the field installed manual shut-off valve to “OFF”. 2. Remove the 1/8" pipe plug in the pipe tee or gas valve and attach a U-tube type water manometer which is at least 12" high and capable of reading to 0.1" W.C. See Figure 24.1. 3. Turn the field installed manual gas shut-off valve to “ON”. Figure 24.1 - Checking Gas Pressure with Manometer U-TUBE MANOMETER MANIFOLD TEE 4. 5. Create a high fire call for heat from the thermostat. Determine the correct high fire manifold pressure, which depends on gas type and gas control type. Review the furnace Model Digit 11 and 12 (not the system model number) and adjust the main gas pressure regulator spring to achieve the proper manifold pressure as shown in Table 24.1. For location of regulator adjustment, refer to the combination gas control literature supplied with the unit. 8. 9. Check/Adjust Pressure for the Modulating Valve This section only applies to units with Electronic Modulation gas controls (Model Identification Digit 12=4, 7, or 9). Refer to the appropriate instructions for the valve type on the unit. For Units with Model Digit 12=4 or 7: The low fire gas pressure needs to be adjusted. This needs to be repeated on each furnace in multiple furnace units. Using Figure 24.2 for item locations, this is accomplished as follows: 1. Disconnect power. 2. Remove all wires from Maxitrol Amplifier terminal “3” or duct furnace terminal “43” (if available). 3. Turn on power at the disconnect switch. 4. Remove the cover plate (2), maximum adjustment screw (4), spring (5), and plunger (8). A small magnet is useful for this purpose. CAUTION - The plunger is a precision part. Handle carefully to avoid marring or picking up grease and dirt. Do not lubricate. 5. Using minimum adjusting screw (9), adjust low fire manifold pressure to 0.56" W.C. for natural gas and 1.6" W.C. for propane gas. 6. Replace plunger and spring retainer, spring, and maximum adjusting screw in proper order. 7. Using maximum adjustment screw (4), adjust high fire manifold pressure to 3.5" W.C. for natural gas and 10" W.C. for propane gas. 8. Disconnect power. 9. Replace cover plate (2) and re-install all wires from Maxitrol amplifier terminal “3” or duct furnace terminal “43”. 10. After adjustment, move the field installed manual shut-off valve to the “OFF” position, remove the manometer, and replace the 1/8" pipe plug. N (Natural) P (Propane) Furnace Model Digit 12 1, 2, 4, 7 9 1, 2, 4, 7 9 24 1 10 2 3 4 5 9 Manifold Pressure 3.5” 4.0” 10.0” 10.5” 8 7 j F or units with Model Digit 12=9 and multiple furnaces, only one furnace will be Model Digit 12=9, the additional furnaces will be Model Digit 12=2, therefore pressures will be different for those furnaces. 6. (continued next page) Figure 24.2 - Maxitrol Modulating Valve Adjustments Table 24.1 - Manifold Gas Pressure - Main Valve Furnace Model Digit 11 After adjustment, move the field installed manual shut-off valve to the “OFF” position, remove the manometer, and replace the 1/8" pipe plug. After the plug is in place, move the field installed manual shut-off valve to the “ON” position and recheck pipe plugs for gas leaks with soap solution. Proceed to the section "Air Shutter Adjustment". If the unit has Electronic Modulation gas controls (Model Identification Digit 12=4, 7, or 9), skip steps 7 through 9 in this section and proceed to the next section "Check/Adjust Pressure for the Modulating Valve", otherwise continue to the next step. 5-572.11 6 1. TOP HOUSING 2. COVER PLATE 3. SEAL GASKET 4. MAX ADJUSTMENT SCREW 5. MAX ADJUSTMENT SPRING 6. SOLENOID 7. MIN ADJUSTMENT SPRING 8. PLUNGER 9. MIN ADJUSTMENT SCREW 10. MIN ADJUSTMENT SCREW STOP START-UP PROCEDURE Check/Adjust Pressure for the Modulating Valve (continued) 1. After the plug is in place, move the field installed manual shut-off valve to the “ON” position and recheck pipe plugs for gas leaks with soap solution. 2. Proceed to the section "Air Shutter Adjustment". 6. 7. 8. 9. Save the setting by simultaneously holding Buttons #1 and #2 until the LED turns OFF. If this is not performed within 5 minutes, the control will default to the previously saved settings and return to normal operating mode. Once the setting of the modulating valve has been completed, replace the valve cover removed earlier. Move the field installed manual shut-off valve to the “OFF” position, remove the manometer, and replace the 1/8" pipe plug. After the plug is in place, move the field installed manual shut-off valve to the “ON” position and recheck the pipe plug for gas leaks with soap solution. Proceed to the section "Air Shutter Adjustment". Figure 25.1 - Maxitrol EXA Modulating Valve BUTTON #2 SUPPLY POWER TERMINALS CONTROL SIGNAL TERMINALS BUTTON #1 1 2 3 4 POSITION FEEDBACK WIRING TERMINALS ON DIP SWITCHES (1=“OFF”, 2=“ON”, 3=“OFF”) 1 2 3 For Units with Model Digit 12=9: The high fire gas pressure needs to be adjusted first, followed by the low gas pressure. For multiple furnace units, this is only required on the duct furnace that has the modulating valve (Model Digit 12=9). This is accomplished as follows: 1. Verify the main valve (valve before the modulating valve) outlet pressure has been set to 4.0” W.C. for natural gas or 10.5" W.C. for propane gas per instructions and Table 24.1 on the previous page. For multiple furnace units, the furnaces without the modulating valves are to remain at 3.5" W.C. for natural gas or 10.0" W.C. for propane gas. For location of regulator adjustment, refer to the combination gas control literature supplied with the unit. 2. The Maxitrol EXA modulating valve series has a cover secured with two screws that must be removed. Once removed, there are a bank of (3) DIP switches and two buttons and a communication LED for the user interface as shown in Figure 25.1. 3. Verify that the DIP switches are properly set to the "OFF" position for switches 1 and 3 and "ON" for switch 2. 4. Adjust the High Fire Setting as follows: a. Enable the unit controls and create a call for heat. b. Press and hold Button #1 on the modulating valve until the LED lights solid red, then release. c. With the valve now in the high fire setting mode, confirm or adjust the high fire manifold pressure to be 3.5" W.C. If the pressure needs to be adjusted, press or hold Button #1 to increase gas flow and press or hold Button #2 to decrease gas flow. d. If 3.5" W.C. cannot be attained, recheck the inlet gas pressure as described previously. After addressing any issues, if 3.5" W.C. still cannot be attained, step the valve closed using button #2 to the point where manifold pressure begins to be impacted. If the pressure at that point is less than 3.3" W.C., recheck your inlet pressure with the unit operating and adjust as required. e. Save the setting by simultaneously holding Buttons #1 and #2 until the LED turns OFF. If this is not performed within 5 minutes, the control will default to the previously saved settings and return to normal operating mode. 5. Adjust the Low Fire Setting as follows: a. Press and hold Button #2 on the modulating valve until the LED light blinks red, then release. b. With the valve now in the low fire setting mode, confirm or adjust the low fire manifold pressure to be no less than the minimum shown on the furnace serial plate in the box called “Min. Manifold Pressure”. If the pressure needs to be adjusted: c. Press or hold Button #1 to increase gas flow and #2 to decrease gas flow. It is best to push and release button #2 to single step the valve to the minimum manifold pressure. Holding the button is likely to cause the valve to close too far and lose flame. d. LED INDICATOR Air Shutter Adjustment Proper operation provides a soft blue flame with a well-defined inner core. A lack of primary air will reveal soft yellow-tipped flames. Excess primary air produces short, well-defined flames with a tendency to lift off the burner ports. For both natural and propane gas, the air shutters can be adjusted to control the burner flame height. The air shutters can be accessed by reaching behind the manifold tee in Figure 24.1. The larger models may require the removal of the manifold (see Manifold Assembly Removal). Adjusting the primary combustion air is achieved by resetting the primary air shutters (See Figure 56.1). Prior to flame adjustment, operate duct furnace for about fifteen minutes. The main burner flame can be viewed after loosening and pushing aside the gas designation disc on the side of the burner box. 1. To increase primary air, loosen the air shutter set screws and move the air shutters closer to the manifold until the yellow tipped flames disappear and a clean blue flame with a well defined inner cone appears. 2. To decrease primary air, move the air shutters away from the manifolds until flames no longer lift from burner ports, but being careful not to cause yellow tipping. 3. Re-tighten set screws after adjustment. 5-572.11 25 START-UP PROCEDURE Blower Adjustments All belt drive supply fan speed adjustments can be made with the adjustable sheave on the blower motor as follows: 1. Refer to page 43 to determine correct blower speed according to job requirements, then proceed to the next step. 2. Turn off power to the unit at the disconnect switch. If equipped with gas heat option, turn all hand gas valves to the “OFF” position. 3. Loosen the belt tension and remove the belt. 4. On the motor sheave, loosen the set screw on the side away from the motor (see Figure 26.1). Figure 26.1 - Motor Sheave Adjustment SET SCREW MOTOR SHAFT 6. 7. 8. Lubrication Recommendations The blower can be provided with either spider or pillow block bearings. Spider bearings are permanently lubricated and do not require lubrication. Pillow block bearings are shipped greased from the factory but will require lubrication. The bearings should be checked and lubricated before each heating season but a more frequent lubrication schedule may be required based on the environment in which the unit is installed, and the frequency of the equipment operation. Shell Alvania #2 lubricant is recommended. Damper Linkage Adjustment ADJUSTABLE HALF OF SHEAVE 5. 11. Check the motor amps to ensure the maximum motor amp rating is not exceeded. Verify airflow volume and repeat steps above for further adjustment. 12. If equipped with gas heat, turn on the gas and initiate burner operation. 13. Verify the temperature rise and supply air temperature of the heating section do not fall outside the range or exceed the maximums shown in Table 37.1. 14. After 24 hours of operation, retighten the setscrews to the torque listed in the owners manual on the bearing, sheave, and blower wheel to avoid damage to the unit. Turn outer side of motor sheave clockwise until motor sheave is fully closed. From fully closed position, turn outer side of motor sheave counterclockwise until the proper number of turns open are achieved. Turns should be done in half-turns (180° rotations). Each half turn results in a change of blower speed and air volume of approximately 2.5-5%. Adjusting the half of the sheave inward increases blower speed, adusting outward decreases blower speed. Tighten the set screw on the flat portion of the motor shaft. Replace the belt and verify that the belts are aligned in the sheave grooves properly and are not angled from sheave to sheave. If the unit is provided with a return air damper, to prevent shipping damage, the return air damper linkage is disconnected and the damper closed. Before operating the unit, the fresh and return air dampers must be connected. This is accomplished by the following: 1. The damper actuator should be de-energized and the fresh air damper in a fully closed position. 2. Open the return air damper in a fully open position. 3. Slide the connecting rod into the ball joint on the blade arm with the return air damper fully open. See Figure 26.3. 4. Tighten the 5/16" hex head screw on the ball joint. Figure 26.3 - Damper Linkage Adjustment BALL JOINT CONNECTING ROD BLADE ARM DAMPER BLADE Figure 26.2 - Belt Tension Adjustment Furnace Control Operating Sequence IMPORTANT To prevent premature heat exchanger failure, with all control systems, a blower starting mechanism must be provided so that the blower is running or energized within 45 seconds of the gas control operation. 3/4" DEFLECTION WITH 5 LBS. OF FORCE Retighten motor base. Motor base should be shifted for proper belt tension which is 3/4" deflection with about 5 lbs. of force. Refer to Figure 26.2. 10. Turn on power to the unit and initiate blower motor operation. Do not fire gas controls until blower adjustment has been made or unit may cycle on high limit control. IMPORTANT 9. 26 Pour éviter la panne prématurée de l'échangeur thermique, avec tous les systèmes de commande, un mécanisme de démarrage de la soufflerie doit être fourni pour que la soufflerie démarre dans les 45 secondes qui suivent l'activation de la commande de gaz. 5-572.11 START-UP PROCEDURE c. Furnaces are supplied with intermittent pilot systems with continuous retry, which both the main burner and pilot burner are turned off 100% when the thermostat is satisfied. Control Options (see page 30) could change the listed sequence of operation for the unit based on their function. The descriptions given below are for the basic duct furnace. Single Furnace Controls Single furnace units (Model Digits 4-6=100 through 400) are offered with different types of gas control: • Staged Control (Model Digit 12=1 or 2): These furnaces utilize a single- or two-stage combination gas valve, an ignition control, and a low voltage thermostat. • Electronic Modulating Control (Model Digit 12=4 or 7): These furnaces utilize a single-stage combination gas valve, an electronic modulating gas valve, a modulating amplifier, an ignition control, and one of the following: • Modulating room thermostat • Modulating duct thermostat with remote temperature set point adjuster • Building Management System (BMS) signal by others (an inverted signal where 0VDC is high fire and 10VDC is low fire). • Electronic Modulating Control with Modine Control System (Model Digit 12=9): These furnaces utilize a singlestage combination gas valve, an electronic modulating gas valve, a programmable microprocessor based controller, an ignition control, and different sensors depending on the application, but most commonly include: • A duct temperature sensor • A space temperature sensor • There is also BMS integration capability for BACnet or LonWorks protocol systems. The control operating sequence for all furnaces is as follows: 1. The thermostat calls for heat or is enabled by the BMS. 2. The power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster pre-purge time delay relay then closes after 20 to 40 seconds and energizes the gas control circuit. 3. The pilot valve opens and the spark igniter sparks in an attempt to light the pilot. The system will attempt to light the pilot for 70 seconds. If the pilot is not sensed for any reason, the ignition control will wait for approximately six minutes with the combination gas control closed and no spark. After six minutes, the cycle will begin again. After three cycles, some ignition controllers lockout for approximately one hour before the cycle begins again. This will continue indefinitely until the pilot flame is sensed or power is interrupted to the system. 4. Once the pilot is lit, the flame sensor proves the pilot and stops the spark igniter from sparking. 5. The main gas valve is opened and the main burner is controlled as follows: a. Single-Stage Furnaces (Model Digit 12=1): The main burner is lit to 100% full fire. b. Two-Stage Furnaces (Model Digit 12=2): The main burner is lit to 50% fire. If the temperature at the thermostat continues to fall, the thermostat will call for high stage heat and the main burner is lit to 100% full fire. odulating Room or Duct Thermostat (Model Digit M 12=4): The main gas valve is opened 100% and the burner firing rate is modulated between 40% and 100% full fire. A resistance signal (8000 to 12000 ohms) in the thermostat is converted by the modulating amplifier to an inverted DC voltage (between 0VDC for high fire to 12 VDC for low fire) and applied to the modulating gas valve to control the gas flow to the main burner. Note: When modulating duct sensing is utilized, a room override thermostat can be added. When the room override calls for heat, the burner modulates to full fire operation until the room override is satisfied. The unit then reverts back to duct sensing control. When equipped with both, either the duct sensor or the room override thermostat can call for heat. d. BMS Signal (Model Digit 12=7): The main gas valve is opened 100% and the burner firing rate is modulated between 40% and 100% full fire. A BMS 0-10VDC signal (inverted, such that 0 VDC is high fire and 10 VDC is low fire) is converted by the signal conditioner/ modulating amplifier into an inverted DC voltage (between 0VDC for high fire to 12 VDC for low fire) and applied to the modulating gas valve to control the gas flow to the main burner. The signal conditioner can accept a 0-10 VDC signal when all the dip switches are in the “OFF” position. Note: For further information regarding the operation of any of the electronic modulating system options above, consult the literature provided with the unit. e. Modulating with Modine Control System (Model Digit 12=9): The main gas valve is opened 100% and the burner firing rate is modulated between 40% and 100% full fire. Heating demand is determined by the Modine Control System through a comparison of the supply air or space temperature to setpoint and a DC voltage (between 2VDC for low fire to 10 VDC for high fire) is applied to the modulating gas valve to control the gas flow to the main burner. Note: Typically the temperature control is via supply air 6. 7. 5-572.11 with the space sensor used to reset the supply air temperature setpoint. For additional information, refer to the Modine Control System Manual, literature #74-510 that shipped with the unit. If the unit was provided with a time delay relay, the blower starts after 30 to 45 seconds. Once the temperature is satisfied, both the main and pilot valves close 100%. Blower operation may or may not continue, depending on application. 27 START-UP PROCEDURE Multiple Furnace Controls Multiple furnace units are available as two furnace units (Model Digits 4-6=500 through 800) and three furnace units (Model Digits 4-6=840 or 960) and with different types of gas control: • Staged Control (Model Digit 12=1): For control of multiple staged furnaces, each furnace would be individually controlled. Refer to the section for Single Furnace Controls, Staged Control (Model Digit 12=1). • Two furnace units would be controlled as 2-stage (50%/50%). • Three furnace units can be controlled as 3-stage (33%/33%/33%) or 2-stage (33%/67%). • Electronic Modulating Control (Model Digit 12=4): For control of multiple electronic modulating furnaces, one furnace is the Primary furnace featuring a modulating amplifier capable of driving modulating gas valves on Secondary furnaces. Because all valves are driven by one amplifier, all valves modulate at the same rate, from 40% to 100% full fire. Refer to the section for Single Furnace Controls, Electronic Modulating Gas Controls (Digit 12=4). • Electronic Modulating Control (Model Digit 12=7): For control of multiple electronic modulation furnaces for BMS control (0-10VDC control signal), each furnace would be individually controlled. Refer to the section for Single Furnace Controls, Electronic Modulation Control (Model Digit 12=7). • Modulating with Modine Control System (Model Digit 12=9): For control of multiple furnaces, one furnace features a modulating gas valve while additional furnaces are two stage furnaces. The Modine Control system seamlessly stages furnaces and modulates the primary furnace based on demand. the reduced airflows, the unit must be applied as follows: The unit has 2-stage or modulating gas controls. The unit is provided with a discharge air thermostat. The system does not include a room thermostat. Exception: See note below for units equipped with the Modine Control System option (Model Digit 12=9). The discharge air thermostat will prevent the unit from firing above the allowable 100°F rise when the unit is at or above the minimum CFM by monitoring the discharge air and going to low fire. A room thermostat, because it is located remote from the unit, could cause the unit to over-fire. Note for units equipped with the Modine Control System option (Model Digit 12=9): A space temperature sensor (Carel pAD) is permitted, as a call for heating from the space results in a reset of the supply air temperature setpoint that will still maintain a supply temperature that is at or below the maximum allowable discharge air temperature. Table 28.1 - Extended Range VAV Minimum Airflow Minimum Airflow (CFM) Input Rating (Digit 4-6) 100 125 150 175 200 225 250 300 350 400 500 600 700 800 840 960 Variable Air Volume Applications Units may be supplied with field installed variable frequency drives for applications where variable air volume is required. The minimum air flow may be reduced to as low as 30% of the full speed air flow, but not lower than the minimum airflow listed in Table 28.1 and Table 37.1, unless certain conditions are followed. Refer to the following section titled "Extended VAV Airflow Limits" for additional information. To determine the actual minimum allowable airflow, all unit selections must be performed with the AccuSpec configuration software. Within AccuSpec, multiple variable frequency drive speed control changeover options are available, which include these common selections: • Two speed which may be controlled by a manual high/low switch which may be factory mounted on the control panel or shipped loose for field installation or by exhaust fan interlocks. • Building management control which allows for an external signal of 0-10VDC to adjust the unit airflow. Additional options are available when the unit is configured with the Modine Control System option (Model Digit 12=9). Low ATR (Digit 10=H) Extended Standard Range 1,250 825 1,563 1,031 1,875 1,238 2,188 1,444 2,500 1,650 2,813 1,856 3,125 2,063 3,750 2,475 4,375 2,888 5,000 3,300 3,125 2,063 3,750 2,475 4,375 2,888 5,000 3,300 6,562 4,331 7,500 4,950 j Extended range minimum can be 75% of standard minimum. Extended range minimum can be 66% of standard minimum. Cooling Coil Operation 1. 2. Extended VAV Airflow Limits If certain conditions are followed, the allowable minimum CFM of the system can be extended to: 75% of the minimum listed CFM in Table 37.1 for high air temperature rise units (Model Digit 10=H) 66% of the minimum listed CFM in Table 37.1 for low air temperature rise units (Model Digit 10=L). Refer to Table 28.1 for a summary of the reduced minimum airflows, indicated in the column "Extended Range". To allow 28 High ATR (Digit 10=H) Extended Standard Range 750 563 938 703 1,125 844 1,313 984 1,500 1,125 1,688 1,266 1,875 1,406 2,250 1,688 2,625 1,969 3,000 2,250 - 5-572.11 Airflow must be properly distributed across the coil face and should not vary by more than 20%. Air velocities should be maintained between 200 and 550 feet per minute. Refer to Table 21.1. COMPONENT/OPTION LOCATIONS For location of standard and optional factory installed components, refer to Figure 29.1 and the descriptions on the following pages. Figure 29.1 - Factory Mounted Option Locations 1. Discharge Thermostat (not shown) 2. Low Gas Pressure Switch 3. High Gas Pressure Switch 4. Power Exhauster 5. Timed Freeze Protection 6. Ignition Controller 8. Control Relay 9. Time Delay Relay 10. Furnace Low Voltage Terminal Strip 11. Power Exhauster Relay 12. Furnace Supply Power Terminal Strip 13. Control Step Down Transformer 14. Control Relay 15. Blower Low Voltage Terminal Strip 16. Dead Front Disconnect Switch 17. Step Down Transformer Fuses 18. Step Down Transformer 19. Factory Installed Minimum Positioner 22. Return Air Fire Stat 23. Blower Housing 24. Pillow Block Bearings 25. Blower Motor 26. Filters 27. Fresh Air Damper 29. Rainhood and Birdscreen 30. Direct Drive Damper Actuator 32. Damper to Damper Linkage 33. Return Air Damper 35. Motor and Blower Vibration Isolation 36. Blower Support 37. Convenience Outlet 38. Blower Door Switch 39. Dirty Filter Switch 40. Motor Starter 41. Mild Temperature Thermostat 43. Warm-Up Stat 44. Blower Supply Power Terminal Strip 46. Electronic Modulating Amplifier 47. Electronic Modulating Gas Valve 48. Air Flow Proving Switch 49. High Limit Switch 50. Supply Air Fire Stat 51. Main Gas Valve 52. Burner Box 53. Direct Drive Damper Actuator 54. Discharge Damper For Modine Control System Units Only (Model Digit 12=9): Furnace Control Panel(s) for Modine Control System Equipped Units (Model Digit 12=9) 57 56 13 58 12 11 12 11 59 6 6 49 50 50 49 48 10 10 60 Single Furnace Units or Primary Furnace on Multiple Furnace Units Secondary Furnace(s) on Multiple Furnace Units 56. Carel pCOOEM+ Microprocessor Controller 57. Carel pLDPro User Interface Panel 58. Optional Control Relays 59. Optional Unit Enable Relay 60. Wiring Channels 61. Return Air Sensor (not shown) 62. Outside Air Sensor (not shown) 63. Mixed Air Sensor (not shown) 64 Carel pGD1 Digital Display/Interface Module (not shown) 5-572.11 29 COMPONENT DESCRIPTIONS All units include the standard (STD) features. The unit must be reviewed to determine the optional (OPT) features that may have been supplied with the unit. Refer to Figure 29.1 for the descriptions on the following pages. (1) Discharge Thermostat/Sensor – (OPT) The discharge thermostat or sensor is field installed in the discharge (supply) air ductwork. For additional information, refer to the thermostat vendor literature provided in the literature packet with the unit. Model Sizes 500-960 contain multiple furnaces so multiple thermostats/sensors may be included. The thermostat(s) provided can be one of the following: a. Two-Stage Capillary Thermostat (Digit 12=1 or 2) The thermostat capillary is to be field routed/installed in the ductwork. The thermostat body contains the setpoint adjuster that must be field set. SUPPLY DUCTWORK (BY OTHERS) SETPOINT ADJUSTER RIGHT LEFT CAPILLARY R B W R B W (2) Low Gas Pressure Switch – (OPT) The switch monitors the gas pressure upstream of all the gas controls and disables the ignition controller and combination gas valve if low gas pressure is experienced. The switch is automatic reset, allowing the unit to operate when gas pressure returns above the minimum setpoint. The switch should be set to insure that the minimum inlet gas pressure is available (6" W.C. for natural gas, 11" W.C. for propane gas). (3) High Gas Pressure Switch – (OPT) The switch monitors the gas pressure downstream of all the gas controls and disables the ignition controller and combination gas valve if high gas pressure is experienced right before the manifold. The switch is manual reset so that if the gas pressure is too high, a service person must check the unit to be sure the gas controls have not been damaged, then reset the switch to allow the unit to operate when gas pressure returns below the maximum setpoint. The switch should be set to insure that the maximum manifold gas pressure is not exceeded (3.5" W.C. for natural gas, 10" W.C. for propane gas). Low and High Gas Pressure Switches THERMOSTAT BODY (COVER REMOVED) b. Two-Stage Electronic Thermostat (Digit 12=1 or 2) The thermostat body is field installed remotely and includes the discharge air set point adjuster that must be field set. Refer to Literature 5-577 latest revision. (4) Duct Furnace Power Exhauster – (STD) The power exhauster, on a call for heat, creates a combustion draft through the duct furnace prior to the pilot being energized. The draft is proven through the power exhauster motor centrifugal switch that closes when the motor reaches full speed. The unit door includes a power exhauster discharge cover and inlet combustion louvers. For information about venting, refer to the Installation – Venting section. Note: Second stage S350 module not shown. c. Electronic Modulating Discharge Sensor (Digit 12=4) Includes a field installed mixing tube and discharge air sensor field installed in duct work. The set point adjuster is field installed remotely and must be field set. Refer to Literature 5-578 latest revision for instructions (5) Timed Freeze Protection (OPT) (All Except Digit 12=9) The timed freeze protection system includes a sensor factory installed in the discharge air stream. On initial start-up, the timed delay in the system allows the unit to go through the normal ignition sequence. The timed delay is a manual reset switch and adjustable for 1-10 minutes. In the event that the unit fails to fire after this period, the discharge air sensor will sense the cold air (30°-75°F adjustable) and will shut down the unit. For units with the Modine Control System option (Model Digit 12=9), this feature is integral to the control logic and utilizes existing sensors included with that option. Refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information. Timed Freeze Protection Module d. Supply Air Sensor (Model Digit 12=9) (not shown) Used on units with Modine Control System option, the sensor includes either a fixed or adjustable length sensor field installed in duct work. Refer to Literature 74-541 latest revision for instructions. 30 5-572.11 COMPONENT DESCRIPTIONS (6) Ignition Controller – (STD) The ignition controller is factory installed in the duct furnace electrical junction box with the spark ignitor and sensor located on the burner. For both natural and propane gas units, the ignition controller is 100% shut-off with continuous retry. On a call for heat, the system will attempt to light the pilot for 70 seconds. If the pilot is not sensed for any reason, the ignition control will wait for approx­imately six minutes with the combination gas control closed and no spark. After six minutes, the cycle will begin again. After three cycles, some ignition controllers lockout for approximately one hour before the cycle begins again. This will continue indefinitely until the pilot flame is sensed or power is interrupted to the system. (8) Control Relay – (OPT) The control relay(s) are factory installed in the duct furnace electrical junction box. The relay has a 24V coil with doublepole, double throw (DPDT) contacts. Refer to the unit wiring diagram for the switching function of the relay. The two normally open and two normally closed contacts are rated for a maximum of 30 amps @ 115V/1Ph. (9) Time Delay Relay – (STD) The time delay relay is factory installed in the duct furnace electrical junction box. The time delay relay allows the gas controls to operate for approximately 30 seconds before the blower starts. This allows the heat exchanger a warm up period so that the initial delivered air is not cold. The time delay relay also keeps the motor running for approximately 30 seconds after the call for heat has been satis­fied to remove the residual heat from the heat exchanger. For single phase units below 1-1/2 Hp, the time delay relay controls the motor directly. For single phase units 1-1/2 Hp and greater and all three phase units, the time delay relay controls the motor starter. (10) Furnace Low Voltage Terminal Strip – (STD) The terminal strip is labeled to match the electrical wiring diagram provided with the unit. All field wiring connections should be made to the top side of the terminals to prevent miswiring by modifying the factory wiring which is made to the bottom of the terminal strip. (15) Blower Low Voltage Terminal Strip – (STD) The terminal strip is labeled to match the electrical wiring diagram provided with the unit. All field wiring connections should be made to the right side of the terminals to prevent miswiring by modifying the factory wiring which is made to the left side of the terminal strip. (16) Dead Front Disconnect Switch – (OPT) WARNING Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage. AVERTISSEMENT Débranchez l’alimentation électrique avant d’effectuer des connexions ou de travailler sur l’appareil. Respectez toutes les procédures de sécurité qui s’appliquent pour éviter toute mise en marche accidentelle. Le non-respect de cette directive peut entraîner des blessures ou la mort causées par un choc électrique ou des pièces mobiles, en plus d’endommager l’appareil. The dead front disconnect switch is factory installed in the blower electrical section. The disconnect switch is designed so that it must be turned “OFF” before entry to the electrical control cabinet can be obtained (see Figure 31.1). When in the “OFF” position, power is disconnected to all unit wiring electrically following the switch (See Warning). For servicing the unit, the disconnect switch can be manually overridden by using a wrench and turning the disconnect switch shaft 90° clockwise. Figure 31.1 Dead Front Disconnect Switch Assembly BLOWER SECTION ELECTRICAL COMPARTMENT ACCESS DOOR DISCONNECT SWITCH HANDLE OPERATION INSTRUCTION LABEL (11) Power Exhaust Relay – (STD) The control relay is factory installed in the duct furnace electrical junction box. On a call for heat, the relay coil is energized resulting in the contacts energizing the power exhauster motor. (12) Furnace Supply Power Terminal Strip – (STD) The terminal strip is labeled to match the electrical wiring diagram provided with the unit. All field wiring connections should be made to the bottom side of the terminals to prevent miswiring by modifying the factory wiring which is made to the top of the terminal strip. DISCONNECT SWITCH HANDLE SHOWN IN THE "ON" POSITION (13) Control Step Down Transformer – (STD) The control step down transformer is located in the duct furnace electrical junction box. The transformer is used to step down the supply power (115V, 208V, 230V, 460V, 575V) to 24V for the gas controls, damper actuator, relays, etc. Refer to Model Digit 15 of the unit model nomenclature to determine the volt-amp (VA) capacity of the transformer. (14) Control Relay – (OPT) The control relay is factory installed in the blower electrical section. See description of Option 8 for additional details. SUPPLY POWER WIRING TERMINALS (SEE WARNING) DISCONNECT SWITCH HANDLE SHOWN IN THE "OFF" POSITION (17) Step Down Transformer Fuses – (OPT) The transformer fuses are factory installed in the blower electrical section. The fuses are included to protect the transformer. 5-572.11 31 COMPONENT DESCRIPTIONS (18) Step Down Transformer – (OPT) The step down transformer is factory installed in the blower electrical section. The transformer is required as follows: Without Evap Cooler (Model Digit 22=0) • Supply voltage of 460V/3Ph or 575V/3Ph (Model Digit 14=F or G). The transformer reduces the voltage to 115V for the power exhauster(s). With Evap Cooler (Model Digit 22=D) • Supply voltage of 208V/1Ph or 208V/3Ph (Model Digit 14=B or D). The transformer reduces the voltage to 115V for the evaporative cooler. The power exhauster(s) will be 208V. • Supply voltage of 460V/3Ph or 575V/3Ph (Model Digit 14=F or G). The transformer reduces the voltage to 115V for the power exhauster(s) and evaporative cooler. For all other configurations, the transformer is not required. (19) Minimum Positioner – (OPT) (All Except Model Digit 12=9) The factory installed minimum positioner is installed in the blower electrical section and is used with a modulating damper actuator to set the minimum percentage of outside air. The minimum positioner dial is manually set between 0 to 100% resulting in a 2 to 10 VDC signal being sent to the damper actuator. For units with the Modine Control System option (Model Digit 12=9), this feature is available as a damper control when configured properly and does not require a separate additional positioner.Refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information. Figure 32.1 - Minimum Positioner (22) Return Air Fire Stat – (OPT) The return air fire stat is factory installed in the blower electrical section with the sensor in the return air stream. In case of elevated temperatures at the sensor, the manual reset switch shuts down the entire unit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high temperature, take corrective action, and then reset the switch. (23) Blower Housing – (STD) The blower section contains a double width, double inlet (DWDI) blower wheel. Both sides of the blower must be free from obstructions for proper operation. For Right Hand units (Model Digit 9 = R), during operation the blower wheel should rotate in the clockwise direction when viewed from the service side of the unit. For Left Hand units (Model Digit 9 = L), the blower wheel should rotate in the counterclockwise direction when viewed from the service side of the unit. If necessary, interchange supply power wiring to reverse blower rotation. bearings. Spider bearings are permanently lubricated and do not require lubrication. Pillow block bearings are shipped non-greased from the factory and require lubrication before start-up. For lubrication recommendations, see Lubrication Recommendations. (25) Blower Motor – (STD) The blower motor can be provided in a variety of supply voltages, frame types, and motor horsepowers. Refer to the model nomenclature to determine the type of motor provided. The blower motor is supplied with an adjustable sheave that can be used to increase/decrease the blower RPM. For instructions on changing the blower RPM, refer to Blower Adjustments. (26) Filters – (OPT) When filters are supplied with the unit, a rack and the filters are factory installed in the blower section. The unit can be supplied with 2" permanent filters, 2" pleated throwaway filters in MERV 8 or 13 ratings. For filter replacement, refer to Maintenance. (27) Fresh Air Damper – (OPT) When a fresh air damper is supplied with the unit, the damper is used as an outside air shut-off damper. The damper is ultra low leak, Class II leakage resistance (less than 10 CFM/ft² at 1" W.C.) dampers with self-compensating stainless steel side seals and santoprene and galvanized steel blade seals. (29) Rainhood and Birdscreen – (OPT) The rainhood and birdscreen is shipped loose for field installation at the back of the blower section. For installation instructions, refer to Literature 5-589, latest revision. (30) Direct Drive Damper Actuator – (OPT) The direct drive damper actuator is factory installed on the side of the fresh air damper. The return air damper, if provided, is controlled by the damper linkage between the two dampers. All damper actuators are low voltage (24V). For Right Hand units (Model Digit 9 = R), during operation the actuator should rotate in the counterclockwise direction when viewed from the service side of the unit. For Left Hand units (Model Digit 9 = L), the actuator should rotate in the clockwise direction when viewed from the service side of the unit. Two different types of dampers actuators can be provided: Two Position and Modulating. • Two-Position Damper Actuator: A two-position actuator is provided with Air Control options (Model Digits 20-21=DA and EA). The actuator provides open/closed operation of the fresh air damper. When the actuator is energized, the fresh air damper is opened to 100% outside air in 75 seconds (for outside air percentages lower than 100%, refer to the following section, "Setting the Damper Limiter"). Actuators are spring return, so when the damper is de-energized, the fresh air damper will spring closed. Actuator include auxiliary switches (one normally open and one normally closed) that reverse when the damper actuator is at 85° rotation (adjustable). • Setting the Damper Limiter: The two-position damper limiter can be factory set to prevent the outside air damper from opening 100%. Field adjustment of the two-position damper limiter is accom­plished by the following: (continued next page) (24) Pillow Block Bearings – (OPT) The blower can be provided with either spider or pillow block 32 5-572.11 COMPONENT DESCRIPTIONS 1. 2. 3. 4. 5. 6. etermine the maximum outside air % required. D Locate the angle of rotation limiter on the actuator so that its edge lines up with the degree graduation on the actuator face corresponding to the required rotation. (See figure below which is shown at 50% rotation limit.) Position the limiter to the desired position, making sure the locating “teeth” on the limiter are engaged into the locating holes on the actuator. Fasten the limiter to the actuator using the screw provided. Test the damper rotation either manually with the manual crank or apply power. Re-adjust if necessary. If the damper end switch is being used in the control circuit and needs to be adjusted for the new limit position, refer to the next section, "Adjusting the Damper End Switch". Figure 33.1 - Two-Position Damper Actuator Limiter • Modulating Damper Actuator: A modulating actuator is provided with Air Control options (Model Digits 20-21=GA, GC, or GE). The actuator provides incremental operation of the fresh air damper (the return air damper is controlled by the fresh air damper position). Full 90° rotation of the actuator requires 150 seconds. Actuators operate using a 0-10 Vdc input signal from a damper controller. Actuators are spring return, so when the damper is de-energized, the fresh air damper will spring closed. For units with the Modine Control System option (Model Digit 12=9), when the damper control is modulating, Model Digits 20-21 will always be GA and the control will be integral to the Modine Control System control logic. Refer to the latest revision of the Modine Control System Manual, literature 74510 for additional information. (32) Damper to Damper Linkage – (OPT) Units with fresh and return air dampers include a damper actuator that controls the fresh air damper. The return air damper position is controlled by the fresh air damper through the connecting rod. For adjustment, refer to Damper Linkage Adjustment. (33) Return Air Damper – (OPT) When a return air damper is supplied with the unit, the damper is factory installed in the blower section. The return air damper is used as an air balancing damper so low leak, Class III leakage resistance (less than 40 CFM/ft² at 1" W.C.) dampers with selfcompensating stainless steel side seals and santoprene blade seals are used. PHILIPS SCREWDRIVER Adjusting the Damper End Switch: If the damper limiter was adjusted in the previous section, it may be required to adjust the Damper End Switch as follows: 1. The actuator must be in its fail-safe position. 2. Insert the crank handle into the Torx shaped hole in the center of the adjustable switch pointer as shown below. 3. Gently rotate the crank until the switch pointer is at the desired switch point in degrees as shown. (35) Motor and Blower Vibration Isolation – (STD) The motor vibration isolation is factory installed below the blower support bracket. The four (4) neoprene vibration mount grommets provide isolation of the blower housing and motor from the blower support channels. The blower duct connection is not rigidly mechanically fastened and the 1/4'' thick gasketing around the duct transition provides vibration isolation. Figure 33.3 - Blower/Motor Vibration Isolation Figure 33.2 - Adjusting the Damper End Switch BLOWER SUPPORT BLOWER SUPPORT RAIL NEOPRENE VIBRATION ISOLATOR (36) Blower Support – (STD) The blower supports are factory installed in the blower section. The blower supports are used to rigidly support the weight of the blower and motor during operation and shipping. 5-572.11 33 COMPONENT DESCRIPTIONS (37) Convenience Outlet – (OPT) Setting the Dirty Filter Switch The range of the switch is adjustable between 0.17" to 5.0" W.C. 1. Ensure that the unit filters are clean or replace if necessary. 2. Connect leads of a continuity tester to the NO and C terminals of the pressure switch. See the figure below. 3. Turn the set screw of the pressure switch clockwise until it stops. This will set the pressure at 5.0" W.C. and the continuity tester should be sensing an open circuit. 4. Begin turning the screw counterclockwise until the continuity tester senses a closed circuit. This determines the base pressure of the system. 5. Turn the screw clockwise until the continuity tester senses an open circuit and then one additional full turn (This is approx­imately 0.25" W.C.) This will allow for the increase in static pressure due to dirty filters. WARNING Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage. AVERTISSEMENT Débranchez l’alimentation électrique avant d’effectuer des connexions ou de travailler sur l’appareil. Respectez toutes les procédures de sécurité qui s’appliquent pour éviter toute mise en marche accidentelle. Le non-respect de cette directive peut entraîner des blessures ou la mort causées par un choc électrique ou des pièces mobiles, en plus d’endommager l’appareil. Figure 34.2 Dirty Filter Pressure and/or Air Flow Proving Switch The convenience outlet is factory installed in the blower section for providing power for 115V service equipment (trouble light, power tools, etc.). The 115V ground fault circuit interrupter (GFCI) is rated for 15 amps and includes test and reset switches. A separate field supplied 115V/1Ph power supply must be routed through the electrical section wall into the back of the convenience outlet junction box. (38) Blower Door Switch – (OPT) The blower door switch is installed inside the blower section door on the access side of the unit. If the door is removed, the switch interrupts power to the low voltage circuit. For single phase units 1-1/2 Hp and less, the switch de-energizes a relay that controls blower motor operation. For three phase units and single phase units 1-1/2 Hp and greater, the switch deenergizes the motor starter that controls blower motor operation. For servicing, the switch has an override position that can be manually pulled out to override the switch as shown below. For units with Modine Control System option (Model Digit 12=9), the switch is wired to a digital input on the unit controller. Figure 34.1 Blower Door Switch with Manual Override OPEN DOOR CLOSED DOOR POSITION POSITION OVERRIDE POSITION COM NC NO (39) Dirty Filter Switch – (OPT) The dirty filter pressure switch is factory installed in the blower electrical section. The switch monitors the pressure differential between the two sides of the filters. When the filters become dirty, the differential pressure increases and trips the pressure switch which energizes a light on the remote monitoring panel (for units with Modine Control System option (Model Digit 12=9), the switch is wired to a digital input on the unit controller). The switch must be field set with ductwork installed and the blower in operation. 34 POSITIVE PRESSURE CONNECTION NEGATIVE PRESSURE CONNECTION C NO PRESSURE ADJUSTMENT SET SCREW (40) Motor Starter – (OPT) The motor starter is factory installed in the blower electrical section. A motor starter is required for: • All three phase motors • Single phase motors 1-1/2 Hp and greater If the factory installed motor starter option was not ordered with a unit that requires it, a motor starter must be field supplied and installed. Alternatively for three phase motors, see also the Variable Frequency Drive option below. The overload module of the motor starter is designed to protect the motor from exceeding the nameplate amps. If the motor exceeds the amp draw on the current set point dial, the trip condition is indicated by a red color in the trip indicator window. The current set point dial is factory set to the motor full load amps listed on the motor nameplate. The motor starter can be placed in the automatic or manual reset positions. Automatic reset is accomplished by depressing the “RESET” button and turning the button 1/4 turn. When in the automatic reset position, if the overload module trips, the module will reset itself once the overload relay has cooled. In the manual reset position, if the overload module trips, the “RESET” button must be depressed before the blower can operate. The contactor module includes one (1) normally open auxiliary contact. The contact rating is 10 amps. (continued next page) 5-572.11 COMPONENT DESCRIPTIONS Figure 35.1 - Motor Starter A1 1 (47) Electronic Modulating Gas Valve – (OPT) An electronic modulating gas valve is provided factory installed in the duct furnace gas train when the unit is equipped with Electronic Modulating Gas Controls (Model Digit 12=4, 7, or 9). The gas valve modulates the firing rate between 40% to 100% full fire based on the input signal from the Electronic Modulation Amplifier (Model Digit 12=4), Signal Conditioner (Model Digit 12=7), or Modine Control System controller (Model Digit 12=9). For additional information, refer to the Furnace Control Operating Sequence section in this manual. A2 3 L1 5 L2 13 L3 NO CONTACTOR MODULE CURRENT SET POINT DIAL TRIP INDICATOR WINDOW 2 4 T1 6 T2 14 T3 NO RESET A2 OVERLOAD MODULE A R E S E T H NO 98 2 NC 97 T1 4 95 T2 96 6 T3 (40) Variable Frequency Drive – (OPT) The VFD controller adjusts the motor rpm to vary the unit air flow. The minimum air flow may be varied between 30 and 100% of the full speed air flow depending on the controls selection of the unit (refer to the section "Variable Air Volume Applications" on page page 28 for additional information). The control changeover options include two speeds, and building management control. For units with the Modine Control System option (Model Digit 12=9), additional control options may be available. Refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information. (41) Mild Temperature Stat – (OPT) (All Except Digit 12=9) The mild temperature thermostat is factory installed in the blower electrical section. The mild temperature thermostat is designed to lockout the burner during mild weather conditions which prevents the burner from cycling. The thermostat must be field set to the desired mild temperature condition (refer to the latest revision of Modine Literature 75-540). For units with the Modine Control System option (Model Digit 12=9), this feature is integral to the control logic and utilizes existing sensors included with that option. Refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information. (43) Warm-Up Stat – (OPT) (All Except Model Digit 12=9) A warm-up stat can be provided with Air Control options (Model Digits 20-21=EA, GC, or GE) and factory installed in the blower electrical section with the sensor in the return air stream. The warm-up thermostat monitors the return air temperature upon changing to the occupied mode and prevents the fresh air dampers from opening until the temperature of the return air has reached the desired set point (typically 65°F or 5°F below the room temperature). (44) Blower Supply Power Terminal Strip – (STD) The terminal strip is labeled to match the electrical wiring diagram provided with the unit. All field wiring connections should be made to the bottom side of the terminals to prevent miswiring by modifying the factory wiring which is made to the top of the terminal strip. (48) Air Flow Proving Switch – (OPT) The air flow proving switch is factory installed in the duct furnace electrical junction box. The air flow proving switch monitors the pressure differential between the duct furnace and the atmosphere. The purpose of the air flow proving switch is to cut power to the gas controls if a positive pressure is not measured by the switch. This could be caused by a lack of air movement through the heat exchanger. Note: The air flow proving switch will prevent any heat exchanger warm-up because the gas controls can not be energized until air flow is proven. Setting the Air Flow Proving Switch The range of the switch is adjustable between 0.17" to 5.0" W.C. 1. Set the thermostat or controller so that there is a call for heat. For units with the Modine Control System option (Model Digit 12=9), refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information. 2. Turn the set screw of the pressure switch clockwise until it stops. This will set the pressure at 5.0" W.C. 3. Turn the screw counter-clockwise until the gas controls light and then one additional full turn. This will allow for dirty filters or other slight system static pressure increases. (49) High Limit Switch The high limit switch is factory installed in the duct furnace electrical junction box. If the limit temperature is exceeded, the gas controls are de-energized. • Automatic – (STD): The automatic reset high limit will reset when the switch is cooled. (50) Supply Air Fire Stat – (OPT) The supply air fire stat is factory installed in the duct furnace electrical junction box with the sensor in the discharge air stream. In case of elevated temperatures in the supply air stream, the manual reset switch shuts down the entire unit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch. (51) Main Gas Valve – (STD) The main gas valve is factory installed in the duct furnace gas train. The main gas valve provides the pilot, regulator, main gas, and manual shutoff functions. For additional information, see the supplier literature included with the unit. (46) Electronic Modulation Amplifier – (OPT) An electronic modulation amplifier is provided factory installed in the duct furnace electrical junction box when the unit is equip­ped with Electronic Modulating Gas Controls (Model Digit 12=4). The amplifier processes the thermostat temperature and set point signals to modulate the firing rate between 40% to 100% full fire. For additional information, refer to Control Operating Sequence. 5-572.11 35 COMPONENT DESCRIPTIONS (52) Burner Box – (STD) The burner box is located in the duct furnace section and contains the burner and pilot assembly. The burner box includes an access panel for removal of the burner for inspection and servicing. (61) Return Air Sensor (not shown) - (OPT) This sensor is required on all units that have a mixture of outside and return air. The sensor is field mounted in the return air ductwork. It may be dry bulb only or enthalpy (temperature and humidity). (53) Direct Drive Discharge Damper Actuator – (OPT) The direct drive damper actuator is factory installed on the side of the discharge damper (available as an option on units with Model Digit 2=D or P). All discharge damper actuators are low voltage (24V), two-position, spring return type. For Right Hand units (Model Digit 9 = R), during operation the actuator should rotate in the counterclockwise direction when viewed from the service side of the unit. For Left Hand units (Model Digit 9 = L), the actuator should rotate in the clockwise direction when viewed from the service side of the unit. The actuator provides open/closed operation of the discharge air damper. When the actuator is energized, the damper is opened to 100% outside air in 75 seconds. Actuators are spring return, so when the damper is de-energized, the air damper will spring closed. Actuator include auxiliary switches (one normally open and one normally closed) that reverse when the damper actuator is at 85° rotation (adjustable). When the damper is closed, the unit is not operating. (62) Outside Air Sensor (not shown) - (OPT) This sensor is required on all units except 100% return air units and is field installed. Depending on the unit configuration, the sensor may be duct mounted or remote mounted. It may be dry bulb only or enthalpy (temperature and humidity). (54) Discharge Damper – (OPT) When a discharge air damper is supplied with the unit, the damper is factory installed in the downturn plenum section. The discharge air damper is used an outside air shut-off damper so ultra low leak, Class II leakage (less than 10 CFM/ft² at 1" W.C.) dampers with self-compensating stainless steel side seals and santoprene and galvanized steel blade seals are used. For Modine Control System Units Only (Model Digit 12=9) The following items may be included with units configured with the Modine Control System option: (63) Mixed Air Sensor (not shown) - (OPT) This sensor is required on all units that have a mixture of outside and return air and is factory mounted in the blower cabinet. The sensor is dry bulb temperature only. (64) Carel pGD1 Digital Display/Interface Module (not shown) - (OPT) The interface allows a user to access the Carel controller remotely for setpoint changes and to view the operational status of the equipment. The interface features an LED backlit graphic display and buttons for excellent visibility. Also included is a buzzer to indicate alarm conditions. The interface can be used as a handheld device or can be wall mounted. Maintenance personnel may wish to have the pGD1 mounted in an equipment control room. Refer to the latest revision of the Modine Control System Manual, literature 74-510 for additional information (56) Carel pCOOEM+ Microprocessor Controller The Modine Controls System utilizes a Carel pCOOEM+ programmable microprocessor controller that is factory installed in the duct furnace electrical section. (57) Carel pLDPro User Interface Panel The interface allows a user to access the Carel controller for setpoint changes and to view the operational status of the equipment. The interface features an LED backlit graphic display and buttons for excellent visibility. (58) Control Relays - (OPT) The control relay(s) are factory installed in the duct furnace electrical junction box. The relay has a 24V coil with doublepole, double throw (DPDT) contacts. Refer to the unit wiring diagram for the switching function of the relay. The two normally open and two normally closed contacts are rated for a maximum of 8A @ 230V/1Ph. (59) Unit Enable Relay - (OPT) The control relay is factory installed in the duct furnace electrical junction box and is used to enable the unit based on contact closure from a customer enable circuit. The closing of that contact will power a 24V relay from the unit mounted controller and enable the unit in On or Occupied mode. The relay provides electrical isolation to the controller for protection. (60) Wiring Channels with Cover - (STD) The wiring channels organize and separate high voltage and low voltage wiring. 36 5-572.11 GENERAL PERFORMANCE DATA Table 37.1 - General Performance Data Model Size (Digits 4-6) Btu/Hr Input j Btu/Hr Output j 100 100,000 81,000 125 125,000 101,250 150 150,000 121,500 175 175,000 141,750 200 200,000 162,000 225 250 300 350 400 500 600 700 800 840 960 225,000 250,000 300,000 350,000 400,000 500,000 600,000 700,000 800,000 1,050,000 1,200,000 182,250 202,500 243,000 283,500 324,000 405,000 486,000 567,000 648,000 850,500 972,000 Blower Style/Size (Digit 16) Size Temperature Rise (°F) Minimum CFM k Maximum CFM Maximum Minimum C or D 9-9 750 3000 100 25 E or F 12-12 1500 3750 50 20 C or D 9-9 937 3000 100 31 E or F 12-12 1500 4688 63 20 C or D 9-9 1125 3000 100 38 E or F 12-12 1250 5550 90 20 C or D 9-9 1312 3000 100 44 E or F 12-12 1312 5550 100 24 C or D 9-9 1500 3000 100 50 E or F 12-12 1750 5000 86 30 G or H 15-15 1750 6500 86 23 C or D 9-9 1687 3000 100 56 E or F 12-12 1750 5000 96 34 G or H 15-15 1750 6500 96 26 E or F 12-12 1875 5500 100 34 G or H 15-15 1875 6500 100 29 I, J, or K 18-18 3000 9375 63 20 E or F 12-12 2250 5500 100 41 G or H 15-15 2250 6500 100 35 I, J, or K 18-18 3000 11250 75 20 E or F 12-12 2625 5500 100 48 G or H 15-15 2625 6500 100 40 I, J, or K 18-18 4000 12000 66 22 E or F 12-12 3000 5500 100 55 G or H 15-15 3000 6500 100 46 I, J, or K 18-18 4000 12000 75 25 G or H 15-15 3125 6500 120 58 I, J, or K 18-18 4000 9375 94 40 L 20-18 4000 9375 94 40 G or H 15-15 3750 6500 120 69 I, J, or K 18-18 4000 11250 113 40 L 20-18 5000 11250 90 40 G or H 15-15 4375 6500 120 81 I, J, or K 18-18 4375 13000 120 40 L 20-18 4375 13000 120 40 G or H 15-15 5000 6500 120 92 I, J, or K 18-18 5000 13000 120 46 L 20-18 5000 14500 120 41 I, J, or K 18-18 6562 13000 120 61 L 20-18 6562 13000 120 61 I, J, or K 18-18 7500 13000 120 69 L 20-18 7500 14500 120 62 j R atings are shown for elevations up to 2,000 feet. For higher elevations, refer to section "Considerations for Elevation" on page 17. k For Variable Air Movement Applications, see page page 28. 5-572.11 37 GENERAL PERFORMANCE DATA Table 38.1 - Air Temperature Rise jkl Air Temperature Rise Through Unit (°F) Model Size Btu/Hr Input j Btu/Hr Output j 20 40 50 60 70 80 90 100 110 120 100 100,000 81,000 3,750 1,875 1,500 1,250 1,071 938 833 750 - - 125 125,000 101,250 4,688 2,344 1,875 1,563 1,339 1,172 1,042 937 - - 150 150,000 121,500 5,500 2,813 2,250 1,875 1,607 1,406 1,250 1,125 - - 175 175,000 141,750 5,500 3,281 2,625 2,188 1,875 1,641 1,458 1,312 - - 200 200,000 162,000 6,500 3,750 3,000 2,500 2,143 1,875 1,667 1,500 - - 225 225,000 182,250 6,500 4,219 3,375 2,813 2,411 2,109 1,875 1,687 - - 250 250,000 202,500 9,375 4,688 3,750 3,125 2,679 2,344 2,083 1,875 - - 300 300,000 243,000 11,250 5,625 4,500 3,750 3,214 2,813 2,500 2,250 - - 350 350,000 283,500 12,000 6,563 5,250 4,375 3,750 3,281 2,917 2,625 - - 400 400,000 324,000 12,000 7,500 6,000 5,000 4,286 3,750 3,333 3,000 - - 500 500,000 405,000 - 9,375 7,500 6,250 5,357 4,688 4,167 3,750 3,409 3,125 600 600,000 486,000 - 11,250 9,000 7,500 6,429 5,625 5,000 4,500 4,091 3,750 700 700,000 567,000 - 13,000 10,500 8,750 7,500 6,563 5,833 5,250 4,773 4,375 800 800,000 648,000 - 14,500 12,000 10,000 8,571 7,500 6,667 6,000 5,455 5,000 840 1,050,000 850,500 - - - 13,000 11,250 9,844 8,750 7,875 7,159 6,562 960 1,200,000 972,000 - - - 14,500 12,857 11,250 10,000 9,000 8,182 7,500 j Ratings are shown for elevations up to 2000 feet. For higher elevations, refer to section "Considerations for Elevation" on page 17. k Minimum Air Temperature Rise, Maximum Air Temperature Rise, and Maximum Discharge Air Temperature are as follows: -For Model Sizes 100-400, Min Air Temp Rise is 20°F, Max Air Temp Rise is 100°F, and Max Discharge Air Temp is 150°F. -For Model Sizes 500-800, Min Air Temp Rise is 40°F, Max Air Temp Rise is 120°F, and Max Discharge Air Temp is 150°F. -For Model Sizes 840-960, Min Air Temp Rise is 60°F, Max Air Temp Rise is 120°F, and Max Discharge Air Temp is 150°F. -Note that these are typical limits but may vary by Model Size. Refer to Table 37.1 for actual limits. l For Variable Air Movement Applications, see page 28. Air Temperature Limits The maximum allowable discharge air temperature is 150°F. The maximum allowable air temperature rise per furnace for Low Air Temperature Rise Units is 60°F. All system units are designed for a maximum allowable total static pressure of 3.0" W.C. 38 5-572.11 OPTION & ACCESSORY PRESSURE DROP DATA Table 39.1 - Option & Accessory Pressure Drop Tables (in ''W.C.) j Filters Unit Size 100/125 Digit 16 C, D, E, F 150/175 C, D, E, F 200/225 C, D, E, F, G, H E, F, G, H 250/300 500/600 I, J, K E, F, G, H 350/400 700/800 840/960 I, J, K Evap Cooler, 12” Media CFM 2” Permanent 2” Farr Aeropleat 2” Farr 30/30 Without Pre-Filters With Pre-Filters Downturn Plenum 741 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 4,630 1,111 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,200 5,556 1,481 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 1,852 2,000 2,500 3,000 3,500 4,000 4,500 5,500 6,500 7,250 1,925 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,400 11,111 2,593 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 2,593 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,050 12,000 12,500 13,000 0.02 0.02 0.04 0.06 0.08 0.11 0.13 0.16 0.20 0.21 0.02 0.03 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.21 0.23 0.02 0.02 0.04 0.05 0.06 0.08 0.10 0.11 0.14 0.16 0.18 0.02 0.03 0.04 0.06 0.08 0.10 0.13 0.19 0.26 0.32 0.01 0.03 0.05 0.08 0.11 0.15 0.20 0.25 0.33 0.38 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.01 0.02 0.03 0.04 0.05 0.07 0.09 0.12 0.14 0.17 0.20 0.22 0.24 0.02 0.03 0.05 0.07 0.10 0.13 0.16 0.20 0.25 0.26 0.03 0.04 0.06 0.09 0.11 0.14 0.18 0.21 0.25 0.27 0.30 0.03 0.04 0.05 0.07 0.09 0.11 0.13 0.16 0.19 0.22 0.25 0.05 0.05 0.07 0.10 0.12 0.15 0.18 0.25 0.34 0.41 0.03 0.05 0.08 0.11 0.15 0.19 0.24 0.30 0.38 0.43 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.18 0.02 0.02 0.04 0.05 0.07 0.10 0.12 0.15 0.18 0.22 0.26 0.28 0.30 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30 0.37 0.39 0.04 0.05 0.08 0.11 0.15 0.18 0.23 0.27 0.32 0.34 0.38 0.03 0.04 0.06 0.08 0.10 0.12 0.15 0.18 0.21 0.25 0.28 0.05 0.06 0.09 0.11 0.15 0.18 0.22 0.31 0.42 0.51 0.03 0.05 0.09 0.12 0.16 0.21 0.27 0.33 0.42 0.47 0.04 0.05 0.06 0.08 0.10 0.12 0.14 0.17 0.19 0.22 0.02 0.03 0.04 0.06 0.08 0.11 0.13 0.16 0.19 0.23 0.27 0.29 0.31 0.02 0.04 0.08 0.15 0.23 0.34 0.46 0.60 0.08 0.12 0.23 0.36 0.53 0.73 0.97 1.23 0.00 0.01 0.02 0.04 0.07 0.11 0.15 0.19 0.25 0.26 0.02 0.02 0.04 0.05 0.07 0.10 0.13 0.17 0.21 0.23 0.26 0.02 0.03 0.04 0.06 0.09 0.11 0.14 0.18 0.21 0.26 0.30 0.02 0.02 0.03 0.04 0.06 0.08 0.10 0.15 0.21 0.27 0.02 0.04 0.08 0.12 0.18 0.25 0.33 0.42 0.57 0.66 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.14 0.02 0.03 0.05 0.07 0.10 0.14 0.19 0.24 0.30 0.36 0.43 0.47 0.51 4000 Max CFM for Evap 0.03 0.09 0.05 0.15 0.09 0.24 0.14 0.34 0.20 0.46 0.27 0.61 0.35 0.77 0.45 0.95 0.55 1.15 0.60 1.23 5200 Max CFM 0.04 0.12 0.07 0.19 0.10 0.27 0.15 0.36 0.20 0.47 0.27 0.60 0.34 0.73 0.42 0.89 0.50 1.05 0.60 1.23 6000 Max CFM 0.05 0.15 0.06 0.17 0.09 0.24 0.13 0.32 0.17 0.41 0.23 0.52 0.29 0.64 0.43 0.91 0.60 1.23 6500 Max CFM 0.02 0.08 0.05 0.15 0.09 0.23 0.14 0.34 0.20 0.46 0.27 0.61 0.35 0.77 0.45 0.95 0.60 1.23 10400 Max CFM 0.05 0.16 0.07 0.20 0.10 0.25 0.13 0.32 0.16 0.39 0.20 0.47 0.24 0.55 0.29 0.64 0.34 0.74 0.39 0.85 0.03 0.11 0.04 0.14 0.08 0.22 0.12 0.31 0.18 0.42 0.24 0.55 0.32 0.70 0.40 0.86 0.50 1.04 0.61 1.24 11050 Max CFM Other Rainhood Discharge and Damper Birdscreen 0.03 0.05 0.07 0.10 0.13 0.16 0.19 0.22 0.25 0.26 0.02 0.03 0.05 0.08 0.10 0.14 0.18 0.22 0.27 0.29 0.33 0.03 0.05 0.08 0.10 0.14 0.18 0.22 0.27 0.32 0.38 0.45 0.07 0.08 0.09 0.12 0.14 0.16 0.19 0.25 0.31 0.37 0.07 0.12 0.16 0.22 0.28 0.35 0.42 0.51 0.64 0.71 0.03 0.04 0.05 0.07 0.09 0.11 0.14 0.17 0.20 0.23 0.03 0.04 0.07 0.11 0.17 0.23 0.30 0.38 0.48 0.58 0.69 0.75 0.81 0.01 0.01 0.02 0.03 0.04 0.05 0.07 0.09 0.11 0.11 0.01 0.01 0.02 0.02 0.04 0.05 0.06 0.08 0.10 0.11 0.13 0.01 0.01 0.02 0.04 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.02 0.02 0.03 0.04 0.06 0.07 0.09 0.13 0.18 0.23 0.02 0.04 0.07 0.11 0.16 0.21 0.28 0.35 0.47 0.53 0.01 0.01 0.01 0.01 0.02 0.02 0.03 0.04 0.04 0.05 0.01 0.01 0.01 0.02 0.04 0.05 0.08 0.10 0.14 0.17 0.21 0.23 0.26 j A ccessory / Option static pressure losses are approximate. Please consult the Accuspec selection software for static pressure losses at other than listed CFM. 5-572.11 39 BLOWER PERFORMANCE DATA Table 40.1 - Unit Performance Tables jk Digit Unit Size 16 100/125 C,D Start 125 100/125 E,F End 100 150/175 C,D Start 175 150/175 E,F 200/225 C,D Start 225 200/225 E,F 200/225 G,H Air Temp. Rise 0.25 CFM BHP RPM 100°F / - 741 670 80°F/100°F 926 0.13 758 62°F/77°F 1200 0.22 828 53°F/66°F 1400 0.30 982 41°F/51°F 1800 0.55 1145 34°F/42°F 2200 0.93 28°F/36°F 2600 1.45 1315 25°F/31°F 3000 2.16 1489 497 41°F/51°F 1800 0.28 553 34°F/42°F 2200 0.43 614 28°F/36°F 2600 0.63 680 25°F/31°F 3000 0.91 748 22°F/27°F 3400 1.26 802 20°F/25°F 3704 1.58 873 - / 23°F 4100 2.09 969 - / 20°F 4630 2.93 727 100°F/117°F 1111 0.19 793 86°F/100°F 1296 0.27 832 79°F/93°F 1400 0.32 994 62°F/72°F 1800 0.59 1166 51°F/59°F 2200 1.00 43°F/50°F 2600 1.58 1344 37°F/43°F 3000 2.35 1526 86°F/100°F 1296 474 79°F/93°F 1400 0.17 526 62°F/72°F 1800 0.28 588 51°F/59°F 2200 0.44 657 43°F/50°F 2600 0.67 729 37°F/43°F 3000 0.96 804 33°F/38°F 3400 1.35 880 29°F/34°F 3800 1.82 959 26°F/31°F 4200 2.40 24°F/28°F 4700 3.30 1058 1158 21°F/25°F 5200 4.40 871 100°F/113°F 1481 0.36 943 89°F/100°F 1667 0.48 975 85°F/95°F 1750 0.54 74°F/83°F 2000 0.76 1077 1181 66°F/74°F 2250 1.04 59°F/67°F 2500 1.38 1288 54°F/61°F 2750 1.79 1396 49°F/56°F 3000 2.28 1506 594 85°F/95°F 1750 0.29 642 74°F/83°F 2000 0.40 746 59°F/67°F 2500 0.68 857 49°F/56°F 3000 1.09 972 42°F/48°F 3500 1.66 37°F/42°F 4000 2.40 1091 1211 33°F/37°F 4500 3.34 30°F/33°F 5000 4.52 1332 425 85°F/95°F 1750 0.20 449 74°F/83°F 2000 0.26 507 59°F/67°F 2500 0.42 571 49°F/56°F 3000 0.65 639 42°F/48°F 3500 0.97 710 37°F/42°F 4000 1.38 783 33°F/37°F 4500 1.90 858 30°F/33°F 5000 2.54 933 27°F/30°F 5500 3.32 25°F/28°F 6000 4.25 1009 0.50 BHP RPM 0.15 0.21 0.31 0.41 0.69 1.10 1.65 2.39 0.41 0.58 0.81 1.11 1.48 1.83 2.35 3.23 0.28 0.37 0.42 0.72 1.16 1.76 2.57 0.25 0.28 0.41 0.59 0.83 1.15 1.55 2.05 2.66 3.58 4.71 0.48 0.61 0.68 0.92 1.21 1.57 2.00 2.51 0.43 0.54 0.85 1.29 1.88 2.65 3.62 4.82 0.33 0.40 0.58 0.83 1.17 1.60 2.14 2.81 3.61 4.57 808 846 916 975 1108 1254 1410 1573 622 662 710 766 825 873 938 1028 884 937 970 1109 1264 1429 1600 609 615 650 697 753 815 881 951 1023 1116 1212 1016 1078 1106 1197 1291 1389 1490 1593 723 759 845 942 1047 1157 1270 1387 546 562 603 654 713 776 842 911 982 1054 BHP 0.23 0.29 0.41 0.53 0.83 1.27 1.85 2.61 0.56 0.75 1.00 1.32 1.72 2.08 2.63 3.53 0.38 0.47 0.54 0.86 1.32 1.95 2.78 0.37 0.40 0.55 0.75 1.01 1.35 1.77 2.29 2.92 3.87 0.60 0.75 0.82 1.08 1.39 1.77 2.22 2.75 0.58 0.71 1.04 1.50 2.12 2.91 3.91 0.48 0.56 0.75 1.02 1.38 1.83 2.40 3.08 3.91 4.89 0.75 RPM 962 993 1052 1103 1220 1354 1500 1654 735 762 800 847 899 942 1001 1085 1023 1066 1093 1216 1356 1510 1673 734 737 760 796 842 895 955 1018 1085 1172 1144 1198 1224 1306 1393 1484 1579 1677 838 866 938 1024 1119 1221 1329 653 662 692 732 782 839 899 963 1030 1099 . Total Static Pressure, ''W.C. 1.00 1.25 1.50 BHP RPM BHP RPM BHP RPM 0.30 0.38 0.52 0.64 0.98 1.44 2.05 2.84 0.72 0.93 1.20 1.54 1.96 2.34 2.91 3.84 0.48 0.59 0.66 1.00 1.49 2.14 3.00 0.70 0.91 1.19 1.55 2.00 2.53 3.18 4.16 0.73 0.88 0.96 1.24 1.57 1.97 2.44 2.98 0.75 0.88 1.23 1.72 2.36 3.18 4.21 0.74 0.94 1.23 1.60 2.08 2.66 3.37 4.22 - 1093 1121 1173 1218 1325 1449 1585 1731 837 855 885 1731 970 1008 1062 1140 1148 1184 1208 1316 1444 1589 1743 859 887 925 972 1025 1083 1145 1227 1259 1309 1332 1407 1488 1573 1663 1756 944 966 1025 1101 1188 1284 1385 754 774 807 850 899 955 1014 1077 - 0.38 0.47 0.62 0.76 1.12 1.61 2.25 1.12 1.41 1.77 2.21 2.60 3.20 4.16 0.59 0.71 0.78 1.15 1.66 2.34 0.85 1.09 1.39 1.76 2.23 2.79 3.45 4.46 0.85 1.03 1.11 1.40 1.75 2.17 2.66 0.94 1.08 1.45 1.95 2.61 3.46 4.51 1.16 1.45 1.84 2.34 2.94 3.67 4.54 - 1212 1236 1282 1323 1422 1537 1666 942 965 997 1038 1072 1122 1194 1262 1293 1313 1410 1529 1664 952 972 1004 1044 1092 1146 1204 1281 1366 1411 1433 1502 1577 1658 1743 1042 1058 1108 1176 1255 1345 1441 851 877 914 958 1008 1064 1123 - 0.47 0.56 0.74 0.89 1.27 1.79 2.46 1.33 1.63 2.01 2.47 2.88 3.49 4.48 0.70 0.83 0.91 1.30 1.84 2.54 1.27 1.59 1.98 2.47 3.04 3.73 4.76 0.99 1.17 1.26 1.57 1.94 2.37 2.88 1.14 1.28 1.67 2.19 2.88 3.75 4.82 1.38 1.69 2.10 2.60 3.23 3.98 4.87 - 1320 1342 1384 1422 1513 1621 1744 1025 1042 1068 1104 1135 1180 1247 1369 1395 1412 1500 1610 1737 1052 1078 1114 1157 1206 1260 1333 1465 1507 1527 1592 1663 1739 1820 1134 1146 1188 1248 1320 1404 1495 925 944 975 1014 1061 1112 1168 - 2.00 BHP RPM 0.60 0.77 0.97 1.15 1.58 2.15 1.35 2.51 3.01 3.45 4.10 0.94 1.09 1.18 1.62 2.20 2.95 1.67 2.02 2.45 2.96 3.58 4.30 1.26 1.47 1.57 1.91 2.31 2.78 1.58 1.74 2.15 2.71 3.43 4.35 2.21 2.64 3.18 3.84 4.62 - 1514 1532 1568 1600 1681 1778 1638 1202 1229 1254 1291 1563 1582 1596 1667 1762 1877 1201 1218 1245 1280 1322 1369 1646 1682 1700 1758 1822 1892 1303 1309 1337 1384 1455 1518 1071 1093 1123 1161 1206 - 2.50 BHP RPM 0.86 0.99 1.22 1.42 1.90 2.52 3.04 3.58 4.04 4.74 1.21 1.37 1.47 1.95 2.57 2.47 2.94 3.49 4.14 4.90 1.54 1.77 1.88 2.26 2.69 2.07 2.23 2.67 3.27 4.03 4.98 3.23 3.80 4.48 - 1686 1702 1733 1762 1834 1923 1328 1347 1367 1398 1738 1752 1763 1823 1906 1348 1368 1396 1431 1472 1808 1842 1857 1910 1969 1458 1458 1475 1511 1563 1628 1202 1226 1258 - BHP 1.07 1.22 1.48 1.70 2.23 2.90 3.60 4.17 4.67 1.48 1.66 1.78 2.29 2.96 2.96 3.45 4.03 4.72 1.84 2.09 2.21 2.62 2.60 2.78 3.24 3.86 3.86 4.46 - 3.00 RPM 1840 1856 1884 1910 1976 2057 1446 1459 1474 1899 1909 1917 1967 2041 1469 1483 1505 1535 1958 1988 2003 2051 1600 1595 1604 1632 1307 1324 - j Total static pressure should include external static pressure and accessory / option static pressure from Table 39.1. Unit internal resistance has been included in the unit performance tables. k Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures. 40 5-572.11 BLOWER PERFORMANCE DATA Table 41.1 - Unit Performance Tables jk Digit Unit Size 16 Air Temp. Rise CFM 0.25 BHP RPM 250/300 E,F 100°F / 120°F 1852 M 0.26 0.39 83°F / 100°F 2222 Start 300 0.51 74°F / 89°F 2500 0.80 62°F / 74°F 3000 1.19 53°F / 63°F 3500 1.69 46°F / 56°F 4000 2.34 41°F / 49°F 4500 37°F / 44°F 5000 3.14 34°F / 40°F 5500 4.11 250/300 G,H 100°F / 120°F 1852 Start 300 83°F / 100°F 2222 0.28 74°F / 89°F 2500 0.35 62°F / 74°F 3000 0.53 53°F / 63°F 3500 0.76 46°F / 56°F 4000 1.07 41°F / 49°F 4500 1.45 37°F / 44°F 5000 1.92 34°F / 40°F 5500 2.50 31°F / 37°F 6000 3.16 28°F / 34°F 6500 3.96 250/300 I, J, K 46°F / 56°F 4000 37°F / 44°F 5000 31°F / 37°F 6000 1.94 2.93 26°F / 32°F 7000 4.24 23°F / 28°F 8000 6.40 20°F / 24°F 9259 End 250 - / 22°F 10000 7.97 - / 20°F 11111 10.79 100°F / - 2593 0.61 350/400 E,F 96°F / - 2700 0.67 Start 400 87°F / 100°F 2963 0.85 74°F / 85°F 3500 1.30 65°F / 74°F 4000 1.86 58°F / 66°F 4500 2.57 52°F / 59°F 5000 3.44 47°F / 54°F 5500 4.50 100°F / - 2593 0.43 350/400 G,H 87°F / 100°F 2963 0.57 Start 400 74°F / 85°F 3500 0.85 65°F / 74°F 4000 1.19 58°F / 66°F 4500 1.61 52°F / 59°F 5000 2.22 47°F / 54°F 5500 2.77 43°F / 49°F 6000 3.53 40°F / 46°F 6500 4.42 100°F / - 2593 350/400 I,J,K 87°F / 100°F Start 400 2963 65°F / 74°F 4000 52°F / 59°F 5000 1.37 43°F / 49°F 6000 2.20 37°F / 42°F 7000 3.34 4.84 32°F / 37°F 8000 6.75 29°F / 33°F 9000 26°F / 30°F 10000 9.13 24°F / 27°F 11000 12.01 23°F / 26°F 11500 13.66 532 582 625 706 793 882 974 1067 1161 424 447 492 542 594 649 706 767 822 881 559 632 707 804 862 949 668 686 730 826 918 1012 1109 1206 479 516 574 631 690 767 813 876 939 515 588 665 744 824 906 988 12.09 0.50 BHP RPM 0.39 0.54 0.68 0.99 1.41 1.94 2.62 3.44 4.44 0.34 0.43 0.52 0.72 0.98 1.31 1.72 2.22 2.81 3.52 4.34 0.97 1.51 2.29 3.33 4.69 6.91 8.52 11.40 0.80 0.87 1.06 1.54 2.13 2.87 3.78 4.87 0.62 0.79 1.09 1.45 1.91 2.46 3.12 3.91 4.82 1.07 1.69 2.58 3.77 5.33 7.29 9.72 12.66 14.34 665 703 736 803 878 958 1043 1130 1219 519 537 553 588 878 673 721 771 824 878 934 507 560 620 686 755 846 901 985 781 796 834 917 1000 1087 1177 1269 585 614 662 710 762 817 874 933 992 533 590 654 723 796 871 948 1027 1067 0.75 BHP RPM 0.54 0.70 0.85 1.19 1.64 2.20 2.90 3.76 4.78 0.49 0.61 0.71 0.93 1.21 1.57 2.00 2.52 3.14 3.87 4.72 1.25 1.84 2.66 3.75 5.16 7.45 9.09 12.03 1.01 1.08 1.28 1.80 2.42 3.18 4.12 0.84 1.02 1.35 1.74 2.22 2.80 3.49 4.30 0.77 0.89 1.37 2.04 2.97 4.22 5.83 7.85 10.33 13.32 - 782 810 836 893 959 1032 1109 1191 1275 623 634 646 674 707 746 789 834 882 933 984 583 626 679 738 802 887 939 1020 882 895 928 1002 1078 1158 1242 679 702 742 784 830 880 933 987 561 571 609 658 715 778 845 917 990 1065 - . Total Static Pressure, ''W.C. 1.00 1.25 1.50 BHP RPM BHP RPM BHP RPM 0.69 0.87 1.04 1.40 1.87 2.46 3.19 4.08 0.66 0.79 0.90 1.15 1.45 1.83 2.29 2.84 3.49 4.24 1.56 2.19 3.06 4.19 5.64 7.99 9.67 12.66 1.22 1.30 1.52 2.07 2.71 3.51 4.47 1.09 1.28 1.63 2.04 2.55 3.15 3.87 4.70 1.04 1.18 1.69 2.41 3.39 4.68 6.34 8.41 10.95 14.00 - 887 909 930 978 1036 1102 1174 1250 713 721 730 752 780 814 852 894 938 984 654 688 734 788 847 927 977 1054 975 986 1015 1081 1151 1226 1305 764 782 815 853 895 940 989 1040 639 646 679 721 772 830 893 960 1030 1103 - 0.85 1.05 1.23 1.62 2.12 2.73 3.49 4.40 0.85 0.99 1.11 1.38 1.71 2.11 2.59 3.16 3.83 4.61 1.89 2.56 3.46 4.64 6.14 8.55 10.27 13.31 1.45 1.53 1.76 2.34 3.01 3.84 4.84 1.35 1.56 1.93 2.36 2.89 3.52 4.25 1.34 1.49 2.03 2.79 3.82 5.16 6.87 8.99 11.58 14.68 - 985 1000 1016 1058 1109 1170 1236 1308 795 800 806 824 848 878 912 950 991 1035 719 748 787 836 891 966 1014 1087 1061 1071 1097 1157 1221 1291 1366 841 856 885 918 956 998 1042 709 715 742 779 826 879 938 1002 1069 1139 - 1.03 1.24 1.43 1.84 2.36 3.01 3.79 4.73 1.05 1.20 1.33 1.62 1.97 2.39 2.90 3.50 4.19 5.00 2.24 2.95 3.89 5.11 6.65 9.12 10.87 13.97 1.69 1.78 2.02 2.62 3.32 4.18 1.64 1.86 2.25 2.70 3.25 3.90 4.66 1.66 1.81 2.40 3.19 4.26 5.65 7.41 9.58 12.22 - 1074 1085 1099 1133 1179 1234 1296 1364 870 872 877 892 912 939 969 1004 1042 1084 781 804 838 882 933 1004 1050 1121 1142 1151 1174 1228 1288 1353 1142 926 951 980 1014 1053 1095 774 779 802 835 877 927 982 1043 1107 - BHP 1.39 1.64 1.85 2.31 2.88 3.58 4.41 1.47 1.65 1.81 2.13 2.52 2.99 3.54 4.18 4.93 3.77 4.79 6.09 7.72 10.30 12.12 2.19 2.29 2.56 3.22 3.97 4.88 2.26 2.50 2.93 3.41 4.00 4.70 2.36 2.54 3.18 4.05 5.20 6.68 8.53 10.80 13.54 - 2.00 RPM 1239 1242 1250 1275 1312 1358 1412 1005 1005 1006 1016 1031 1052 1077 1107 1140 908 935 971 1015 1079 1120 1290 1297 1316 1362 1414 1472 1046 1053 1072 1096 1124 1157 891 894 910 937 973 1016 1066 1121 1180 - 2.50 BHP RPM 1.79 2.06 2.30 2.81 3.42 4.17 1.94 2.14 2.32 2.68 3.11 3.62 4.22 4.90 4.67 5.75 7.13 8.83 11.52 13.41 2.73 2.84 3.13 3.84 4.65 2.94 3.20 3.66 4.19 4.81 3.14 3.34 4.04 4.98 6.21 7.77 9.70 12.07 14.90 - 1387 1385 1389 1406 1435 1474 1126 1123 1123 1129 1140 1156 1177 1202 1005 1025 1055 1093 1150 1187 1425 1431 1446 1486 1531 1165 1170 1183 1202 1226 995 997 1009 1030 1061 1099 1144 1194 1249 - BHP 2.21 2.52 2.78 3.33 3.99 4.78 2.44 2.67 2.87 3.27 3.74 4.28 4.92 6.77 8.22 10.00 12.79 14.74 3.30 3.42 3.74 4.50 3.68 3.96 4.45 4.00 4.20 4.96 5.96 7.26 8.90 10.92 13.37 - 3.00 RPM 1523 1517 1517 1529 1552 1584 1237 1231 1230 1232 1240 1253 1270 1110 1134 1167 1218 1252 1550 1555 1568 1602 1275 1277 1287 1090 1091 1099 1117 1144 1178 1219 1265 - j Total static pressure should include external static pressure and accessory / option static pressure from Table 39.1. Unit internal resistance has been included in the unit performance tables. k Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures. 5-572.11 41 GENERAL PERFORMANCE DATA Table 42.1 - Unit Performance Tables jk Unit Size 500/600 Digit 16 G or H Start 600 500/600 Start 600 I, J, K End 500 500/600 L Start 500 700/800 G or H Start 800 700/800 I, J, K Start 800 700/800 L End 700 840/960 I, J, K End 840 840/960 End 840 L Air Temp Rise 120°F / 106°F / 100°F / 120°F 93°F / 111°F 82°F / 99°F 74°F / 89°F 67°F / 81°F 62°F / 74°F 57°F / 68°F 120°F / 100°F / 120°F 93°F / 111°F 74°F / 89°F 62°F / 74°F 53°F / 63°F 46°F / 56°F 41°F / 49°F - / 44°F - / 43°F - / 40°F - / 40°F 62°F / 74°F 53°F / 63°F 46°F / 56°F 41°F / 49°F - / 44°F - / 43°F - / 40°F - / 40°F 120°F / 115°F / 105°F / 120°F 104°F / 119°F 94°F / 108°F 86°F / 99°F 80°F / 91°F 120°F / 104°F / 119°F 86°F / 99°F 65°F / 74°F 58°F / 66°F 52°F / 59°F 47°F / 54°F 43°F / 49°F 40°F / 46°F 65°F / 74°F 58°F / 66°F 52°F / 59°F 47°F / 54°F 47°F / 54°F 43°F / 49°F 40°F / 46°F - / 42°F - / 41°F 120°F / 111°F / 105°F / 120°F 97°F / 111°F 86°F / 99°F 78°F / 89°F 70°F / 80°F 65°F / 74°F 62°F / 71°F 60°F / 68°F 86°F / 99°F 78°F / 89°F 70°F / 80°F 65°F / 74°F 60°F / 68°F - / 63°F Total Static Pressure Inches "W.C. 0.25 0.50 0.75 1.00 1.25 1.50 2.00 2.50 3.00 CFM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM 3086 3500 3704 4000 4500 5000 5500 6000 6500 3086 3704 4000 5000 6000 7000 8000 9000 10000 10400 11000 11111 6000 7000 8000 9000 10000 10400 11000 11111 4321 4500 4938 5000 5500 6000 6500 4321 5000 6000 8000 9000 10000 11000 12000 13000 8000 9000 10000 11000 11050 12000 13000 14000 14500 6481 7000 7407 8000 9000 10000 11050 12000 12500 13000 9000 10000 11050 12000 13000 14000 0.62 529 0.82 0.84 575 1.06 0.97 598 1.20 1.18 633 1.43 1.61 693 1.88 2.13 755 2.43 2.77 818 3.10 3.53 882 3.89 4.41 946 4.80 0.46 401 0.69 0.69 443 0.95 0.82 464 1.09 1.43 542 1.75 2.31 624 2.68 3.51 709 3.94 5.09 797 5.57 7.11 885 7.65 9.62 975 10.21 10.77 1011 11.38 12.66 1065 13.31 13.04 1075 13.69 1.69 512 1.97 2.57 580 2.89 3.73 650 4.09 5.21 721 5.60 7.04 793 7.48 7.88 823 8.34 9.27 866 9.75 9.54 874 10.03 1.51 685 1.80 1.68 708 1.98 2.15 763 2.48 2.23 770 2.55 2.89 834 3.25 3.68 900 4.06 4.61 965 0.87 443 1.14 1.26 488 1.55 2.02 558 2.36 4.44 707 4.89 6.19 784 6.69 8.36 861 8.91 11.00 940 11.60 14.16 1019 14.81 17.88 1098 18.59 3.26 566 3.60 4.54 626 4.92 6.13 687 6.54 8.06 749 8.52 8.17 752 8.62 10.37 811 10.86 13.09 873 13.63 16.26 936 16.83 18.02 968 18.61 2.72 630 3.09 3.36 672 3.76 3.93 705 4.35 4.87 754 5.33 6.80 837 7.31 9.20 921 9.76 12.28 1010 12.89 15.60 1091 16.27 17.58 1134 18.27 19.71 1177 5.01 675 5.40 6.78 742 7.21 9.04 812 9.51 11.48 876 12.00 14.50 945 15.05 18.02 1013 18.61 620 658 678 709 762 818 876 936 996 496 527 544 609 682 760 842 926 1012 1046 1099 1109 565 626 691 758 827 855 897 905 760 780 89 836 895 956 421 558 619 755 827 901 976 1052 1129 611 667 724 782 785 842 902 963 994 685 723 754 799 878 958 1044 1123 1164 715 778 845 907 973 1039 1.03 1.30 1.45 1.69 2.17 2.75 3.44 4.25 0.95 1.23 1.39 2.09 3.07 4.38 6.07 8.20 10.81 12.01 13.97 14.36 2.26 3.22 4.46 6.01 7.93 8.80 10.24 10.52 2.11 2.30 2.82 2.90 3.62 4.46 1.42 1.87 2.73 5.35 7.20 9.47 12.22 15.48 19.30 3.95 5.30 6.97 8.98 9.09 11.37 14.17 17.41 19.21 3.48 4.17 4.79 5.90 7.83 10.33 13.52 16.95 18.97 5.80 7.64 9.99 12.51 15.62 19.21 703 1.26 779 1.50 736 1.54 807 1.80 753 1.70 822 1.97 779 1.96 846 2.24 827 2.46 889 2.77 878 3.07 936 3.40 932 3.79 986 4.15 988 4.63 1038 580 1.23 657 604 1.54 675 618 1.71 686 2.05 673 2.46 733 2.84 738 3.48 791 3.91 809 4.84 857 5.31 886 6.58 928 7.10 965 8.76 1001 9.33 1048 11.43 1083 12.05 1081 12.64 1115 13.29 1132 14.64 1164 15.32 1141 15.03 1174 15.72 615 2.57 664 2.89 671 3.56 714 3.92 731 4.84 770 5.23 795 6.43 830 6.86 860 8.39 892 8.85 887 9.28 918 9.76 927 10.74 957 11.24 935 11.02 964 11.53 830 2.43 896 2.77 847 2.63 912 2.98 893 3.17 953 3.54 899 3.26 959 3.63 953 4.00 1009 4.40 1010 4.87 1062 591 1.72 657 2.04 623 2.20 683 2.54 677 3.10 731 3.49 801 5.82 845 6.30 869 7.72 909 8.25 939 10.04 976 10.62 1011 12.84 1045 13.47 1085 16.15 1117 16.83 1159 654 4.31 696 4.67 706 5.70 744 6.10 760 7.40 794 7.85 815 9.45 847 9.93 818 9.56 850 10.04 872 11.88 902 12.40 930 14.72 958 15.27 989 18.00 1015 18.59 1019 19.82 1045 736 3.88 785 4.30 772 4.60 818 5.04 800 5.23 845 5.69 843 6.27 885 6.76 918 8.36 956 8.90 995 10.91 1030 11.50 1078 14.16 1110 14.80 1154 17.63 1184 18.32 1194 19.69 1224 753 6.21 789 6.62 812 8.09 846 8.54 877 10.48 908 10.97 937 13.04 966 13.57 1000 16.18 1028 16.75 1065 19.82 1091 - 849 874 887 908 948 991 1038 749 790 842 903 970 1042 1118 1149 1197 1205 710 756 808 864 924 949 986 993 958 973 1011 1016 1063 717 740 782 888 949 1012 1079 1148 736 780 828 879 881 931 986 1041 832 863 888 926 994 1065 1142 1214 825 879 939 994 1054 - 1.75 2.07 2.25 2.53 3.09 3.74 4.51 2.42 3.24 4.35 5.80 7.64 9.92 12.69 13.95 16.01 16.41 3.23 4.29 5.64 7.30 9.33 10.25 11.76 12.05 3.13 3.34 3.93 4.02 4.81 2.37 2.90 3.89 6.79 8.79 11.21 14.11 17.52 5.05 6.52 8.30 10.42 10.53 12.92 15.83 19.19 4.72 5.49 6.16 7.26 9.44 12.10 15.45 19.02 7.05 9.00 11.47 14.11 17.33 - 916 937 949 968 1001 1044 1088 810 844 891 947 1010 1079 1152 1182 1228 1237 755 797 845 898 955 979 1015 1022 1018 1032 1066 1072 1116 774 794 832 930 987 1048 1112 1179 774 816 861 910 912 960 1013 1066 876 905 929 965 1030 1099 1173 1243 859 911 968 1022 1081 - 2.28 2.63 2.83 3.14 3.74 4.44 4.09 5.29 6.82 8.75 11.13 14.00 15.30 17.42 17.83 5.06 6.47 8.21 10.31 11.26 12.81 13.12 3.88 4.11 4.74 4.83 3.08 3.66 4.73 7.81 9.90 12.42 15.41 18.92 5.84 7.37 9.22 11.41 11.53 13.99 16.98 5.60 6.42 7.13 8.28 10.56 13.32 16.77 7.91 9.95 12.50 15.20 18.50 - 1038 2.84 1149 1054 3.23 1162 1064 3.44 1170 1080 3.78 1183 1110 4.43 1208 1145 946 5.01 1041 984 6.28 1072 1032 7.90 1113 1089 9.92 1163 1151 12.38 1220 1218 15.35 1283 1247 1290 1298 874 916 7.35 984 964 9.16 1027 1016 11.33 1074 1038 12.31 1095 1071 13.90 1126 1078 14.21 1132 1131 4.69 1236 1142 4.94 1245 1172 1176 879 3.84 974 894 4.47 985 924 5.62 1010 1009 8.87 1085 1061 11.04 1131 1117 13.66 1183 1176 16.74 1238 1239 848 6.66 918 885 8.25 950 925 10.17 987 969 12.43 1027 972 12.56 1029 1016 15.08 1070 1065 18.14 1116 960 6.52 1038 986 7.38 1061 1007 8.13 1081 1040 9.33 1111 1100 11.71 1166 1164 14.56 1226 1234 925 8.81 988 973 10.91 1032 1026 13.54 1081 1076 16.32 1129 1132 19.70 1181 - 3.44 3.86 4.09 4.45 7.33 9.03 11.13 13.69 10.14 12.38 13.38 4.65 5.33 6.55 9.96 12.23 14.93 7.51 9.17 11.15 13.48 13.61 16.20 19.33 7.48 8.39 9.17 10.43 12.90 9.73 11.91 14.61 17.46 - 1252 1262 1268 1279 1155 1191 1235 1287 1088 1131 1150 1063 1071 1091 1156 1199 1246 984 1012 1046 1083 1084 1123 1166 1112 1133 1151 1179 1230 1048 1088 1135 1179 - j Total static pressure should include external static pressure and accessory / option static pressure from Table 39.1. Unit internal resistance has been included in the unit performance tables. k Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures. 42 5-572.11 BLOWER SHEAVE ASSEMBLY DATA Adjusting the Blower Drive Sheave Setting All units include a sheave assembly indicated by Digit 19 of the model nomenclature. Within that assembly are the fixed blower sheave, adjustable motor sheave, and belt(s) to provide a method of adjusting the blower speed to balance the airflow based on actual external static pressure for the installation. The motor sheave is adjusted at the factory for external static conditions indicated on the order detail, however actual external static often varies from design, resulting in a need to adjust the equipment to provide correct design airflow. To determine how many turns open the motor sheave should be set for: 1. Locate the unit Model Identification Plate and identify the following model number digits: a. Digits 4-6 = Model Size b. Digit 16 = Blower Size c. Digit 19 = Sheave Arrangement 2. Use Table 39.1 to determine the individual static pressure drops for any features included on the unit for the design airflow. Add those and the design external static pressure to calculate the total static pressure. 3. Use Table 40.1 through Table 42.1 to determine the blower speed (RPM) required to meet the job requirements. 4. Use Table 44.1 to determine the RPM range and approximately blower speeds for each 1/2 turn open of the adjustable motor sheave. Find the RPM that is closest to one value shown to determine the turns open and set the motor sheave as described in the section "Blower Adjustments" on page page 26 Example: Determine motor sheave turns open for a unit operating at 4000 CFM with a design external static pressure (ESP) of 0.60"W.C. as follows: 1. From the Model Nomenclature: a. Model size (Model Digit 4-6) = 400 b. Blower size (Model Digit 16) = E c. Sheave arrangement (Model Digit 19) = J 2. From Table 39.1, the unit includes 2" Farr 30/30 Filters (0.08"W.C. static) and Rainhood & Birdscreen (0.07"W.C. static). Total static pressure is 0.08+0.07+0.60=0.75"W.C. 3. From Table 41.1, the blower speed is 1078 RPM. 4. From Table 44.1, the blower range is 1029-1332 RPM. The closest value to 1078 RPM in the row of Blower RPM by Sheave Turns Open is 1090 RPM, which corresponds to 4.0 turns open. If actual job ESP after installation was measured at 0.75"W.C., the process above would be repeated with the new TSP of 0.90"W.C. Figure 43.1 - Blower Section ADJUSTABLE MOTOR SHEAVE ON MOTOR 1/4" PERIMETER GASKETED BLOWER CONNECTION FILTER RACK BOTTOM SUPPORTED BLOWER AND MOTOR DIRECT DRIVE DAMPER ACTUATOR CONVENIENCE OUTLET (OPTION) BLOWER DOOR SAFETY SWITCH (OPTION) 5-572.11 43 BLOWER SHEAVE ASSEMBLY DATA Table 44.1 - Sheave Assembly Data Blower Type Digit 16 A or B (9-7 Blower) C or D (9-9 Blower) E or F (12-12 Blower) G or H (15-15 Blower) I or J (18-18 Blower with Under 15 HP Motor) K (18-18 Blower with 15 HP Motor & Up) L (20-18 Blower) 44 Sheave Digit 19 Blower RPM by Sheave Turns Open Setting (Approx.) 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 656-1001 1001 967 932 898 863 829 794 760 725 691 656 C, D, E 978-1265 1265 1236 1208 1179 1150 1122 1093 1064 1035 1007 978 F, G 1150-1561 1561 1520 1479 1438 1397 1356 1314 1273 1232 1191 1150 H, I 1526-1858 1858 1825 1792 1758 1725 1692 1659 1626 1592 1559 1526 J, K 1763-2147 2147 2109 2070 2032 1993 1955 1917 1878 1840 1801 1763 656 A, B RPM Range A, B 656-1001 1001 967 932 898 863 829 794 760 725 691 C, D, E 978-1265 1265 1236 1208 1179 1150 1122 1093 1064 1035 1007 978 F, G, H 1150-1561 1561 1520 1479 1438 1397 1356 1314 1273 1232 1191 1150 I, J, K 1526-1858 1858 1825 1792 1758 1725 1692 1659 1626 1592 1559 1526 L,M,N 1763-2147 2147 2109 2070 2032 1993 1955 1917 1878 1840 1801 1763 A, B 468-715 715 690 666 641 616 592 567 542 517 493 468 C, D, E 644-874 874 851 828 805 782 759 736 713 690 667 644 F, G, H 863-1078 1078 1057 1035 1014 992 971 949 928 906 885 863 I, J, K, Q 1029-1332 1332 1302 1271 1241 1211 1181 1150 1120 1090 1059 1029 L,M,N 1150-1438 1438 1409 1380 1352 1323 1294 1265 1236 1208 1179 1150 O, P 1327-1659 1659 1626 1593 1559 1526 1493 1460 1427 1393 1360 1327 A, B, C 410-625 625 604 582 561 539 518 496 475 453 432 410 D, E, F 568-771 771 751 730 710 690 670 649 629 609 588 568 G, H, I 767-958 958 939 920 901 882 863 843 824 805 786 767 J, K, L, O 934-1136 1136 1116 1096 1075 1055 1035 1015 995 974 954 934 M, N 1136-1380 1380 1356 1331 1307 1282 1258 1234 1209 1185 1160 1136 A, B, C 491-649 649 633 617 602 586 570 554 538 523 507 491 D, E, F, G 586-744 744 728 712 697 681 665 649 633 618 602 586 H, I, J 682-821 821 807 793 779 765 752 738 724 710 696 682 K, L, M, N 821-1009 1009 990 971 953 934 915 896 877 859 840 821 O, P, Q, R 995-1161 1161 1144 1128 1111 1095 1078 1061 1045 1028 1012 995 S, T, U 1101-1285 1285 1267 1248 1230 1211 1193 1175 1156 1138 1119 1101 A, B, G, H 826-1009 1009 991 972 954 936 918 899 881 863 844 826 C, D, I, J 995-1161 1161 1144 1128 1111 1095 1078 1061 1045 1028 1012 995 E, F, K, L 1101-1285 1285 1267 1248 1230 1211 1193 1175 1156 1138 1119 1101 M, N 1232-1438 1438 1417 1397 1376 1356 1335 1314 1294 1273 1253 1232 A, B 491-649 649 633 617 602 586 570 554 538 523 507 491 C, D, E 626-765 765 751 737 723 709 696 682 668 654 640 626 F, G, H, I, J, K 765-901 901 887 874 860 847 833 819 806 792 779 765 L, M, N, O, P, Q 901-1059 1059 1043 1027 1012 996 980 964 948 933 917 901 R, S, T, U, V 995-1161 1161 1144 1128 1111 1095 1078 1061 1045 1028 1012 995 W, X, Y, Z 1101-1285 1285 1267 1248 1230 1211 1193 1175 1156 1138 1119 1101 5-572.11 DIMENSIONS - UNIT Figure 45.1 - Outdoor STANDARD Blower Package Unit (Model Digit 2=B, Digit 16=A through H) n 500 - 800 Model Shown Y 33.50 33.50 48.00 Qty (4) Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes (spaced 2.0" apart) 2.32 Optional Rainhood & Birdscreen P (OVER ROOF) 3.97 E (Height) X F (Width) (Inside) 24.00 (Inside) 24.00 (Inside) K (INSIDE) N A 9.00 9.21 1 2 1 4.5 14.55 3 24.00 4.35 (Inside) Optional Return Air Duct Connection 2 24.94 Fresh Air Duct Connection 4 1 2 1.50 5.29 9.21 6.28 6.28 1.50 3.00 5.29 S Figure 45.2 - Outdoor STANDARD Blower Downturn Package Unit (Model Digit 2=D, Digit 16=A through H) n 500 - 800 Model Shown Z 29.32 33.50 33.50 48.00 Qty (4) Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes (spaced 2.0" apart) 2.32 Optional Rainhood & Birdscreen P Over Roof 3.97 A 24.00 (Inside) 9.21 4.27 24.00 (Inside) Downturn 1 Duct Connection 2 24.94 1 24.00 (Inside) Optional Return Air Duct Connection 2 T 24.00 (Inside) N K Inside 4.5 Fresh Air Duct Connection 14.55 3 4.35 4 1 9.21 2 1.50 1.50 5.29 5.29 6.28 3.00 6.28 Table 45.1 - Outdoor STANDARD Blower Unit (Model Digit 2=B or D, Digit 16=A through H) n Model Blower Type Furnace Size (Digit 16) Qty All 100/125 All 150/175 All 200/225 250/300 E, F, G, or H 350/400 E, F, G, or H G or H 500/600 G or H 700/800 1 1 1 1 1 2 2 Dimensions (Inches) A E F K N P S T Y Z 33.75 18.98 17.69 20.02 39.23 34.56 84.41 108.39 81.49 110.82 33.75 18.98 21.94 23.99 39.23 38.82 84.41 108.39 81.49 110.82 37.75 22.98 24.06 23.99 43.23 40.94 84.41 108.39 81.49 110.82 37.75 22.98 27.09 29.96 43.23 44.05 84.41 108.39 81.49 110.82 37.75 22.98 38.60 41.90 43.23 55.57 84.41 108.39 81.49 110.82 37.75 22.98 27.09 29.96 43.23 44.05 117.53 146.77 114.94 144.12 37.75 22.98 38.60 41.90 43.23 55.57 117.53 146.77 114.94 144.12 Gas Conn. 1/2 1/2 1/2 3/4 3/4 3/4 3/4 j For Right Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. k For Left Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. l For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. m For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. n All dimensions shown are in inches. 5-572.11 45 DIMENSIONS - UNIT Figure 46.1 - Outdoor EXTENDED Blower Package Unit (Model Digit 2=B, Digit 16=I, J, K, or L) n 500 - 800 Model Shown Y 47.27 E 36.58 BLOWER CABINET ROOF EXTENSION (”L” BLOWERS ONLY) 6.56 P (OVER ROOF) OPTIONAL RAINHOOD & BIRDSCREEN 2.32 3.97 22.98 (HEIGHT) X F (WIDTH) (INSIDE) 24.00 (INSIDE) 9.00 4.5 FRESH AIR 14.55 DUCT CONNECTION 9.21 4.29 2 24.94 1 1 QTY (4) DRILL LOCATOR DIMPLES FOR FIELD DRILLED ELECTRICAL CONDUIT ENTRY HOLES (SPACED 2.0" APART) 2 S 24.00 (INSIDE) 43.23 K (INSIDE) 4 1 9.21 3 24.00 (INSIDE) 3.00 2 4.35 1.50 5.29 6.28 1.50 5.29 6.28 OPTIONAL RETURN AIR DUCT CONNECTION Figure 46.2 - Outdoor EXTENDED Blower Downturn Package Unit (Model Digit 2=D, Digit 16=I, J, K, or L) n 500 - 800 Model Shown Z 29.32 47.27 E 36.58 BLOWER CABINET ROOF EXTENSION (”L” BLOWERS ONLY) 6.56 P (OVER ROOF) 2.32 OPTIONAL RAINHOOD & BIRDSCREEN 3.97 24.00 (INSIDE) 24.00 (INSIDE) K (INSIDE) 43.23 4.5 9.21 24.00 (INSIDE) 4.27 DOWNTURN DUCT CONNECTION QTY (4) DRILL LOCATOR DIMPLES 24.00 FOR FIELD DRILLED ELECTRICAL (INSIDE) CONDUIT ENTRY HOLES OPTIONAL RETURN AIR (SPACED 2.0" APART) DUCT CONNECTION 2 24.94 1 1 2 14.55 FRESH AIR DUCT CONNECTION 3 4.35 4 1 1.50 5.29 6.28 2 9.21 3.00 1.50 5.29 6.28 T Table 46.1 - Outdoor EXTENDED Blower Unit (Model Digit 2=B or D, Digit 16=I, J, K, or L) n Model Size 250/300 Dimensions (Inches) Blower Type Furnace (Digit 16) Qty E F K P S T Y Z I, J, or K 1 33.50 27.09 29.96 44.05 120.00 141.34 117.34 141.34 Gas Conn. 3/4 350/400 I, J, or K 1 33.50 38.60 41.90 55.57 120.00 141.34 117.34 141.34 3/4 500/600 I, J, K, or L 2 67.00 27.09 29.96 44.05 153.12 182.36 150.74 180.00 3/4 700/800 I, J, K, or L 2 67.00 38.60 41.90 55.57 153.12 182.36 150.74 180.00 3/4 840/960 I, J, K, or L 3 100.50 38.60 41.90 55.57 186.52 215.77 184.14 213.40 3/4 j For Right Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. k For Left Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. l For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. m For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. n All dimensions shown are in inches. 46 5-572.11 DIMENSIONS - UNIT Figure 47.1 - Outdoor STANDARD Blower Cooling Package Unit (Model Digit 2=C, Digit 16=A through H) n 105.49 48.00 33.50 24.00 QTY (4) DRILL LOCATOR DIMPLES FOR FIELD DRILLED ELECTRICAL CONDUIT ENTRY HOLES (SPACED 2.0" APART) OPTIONAL RAINHOOD & BIRDSCREEN P (OVER ROOF) 2.20 3.97 J (HEIGHT) X H (WIDTH) (INSIDE) G A 1 7.65 24.00 (INSIDE) 4.5 FRESH AIR DUCT CONNECTION 14.55 9.21 2 24.00 4.35 (INSIDE) OPTIONAL RETURN AIR DUCT CONNECTION 24.94 108.39 24.00 (INSIDE) N K (INSIDE) 3 9.21 4 1 2 1.50 1.50 3.00 5.29 5.29 6.28 6.28 Figure 47.2 - Outdoor STANDARD Blower Cooling & Downturn Packaged Unit (Model Digit 2=P, Digit 16=A-H) n 134.82 48.00 33.50 24.00 29.32 QTY (4) DRILL LOCATOR DIMPLES FOR FIELD DRILLED ELECTRICAL CONDUIT ENTRY HOLES (SPACED 2.0" APART) OPTIONAL RAINHOOD & BIRDSCREEN P (OVER ROOF) 2.20 3.97 G A 1 2 9.21 24.00 (INSIDE) 4.27 24.00 (INSIDE) DOWNTURN DUCT CONNECTION 137.63 4.5 9.21 4 1 2 1.50 1.50 5.29 OPTIONAL RETURN AIR DUCT CONNECTION 24.94 4.29 FRESH AIR DUCT CONNECTION 14.55 3 4.35 24.00 (INSIDE) N K (INSIDE) 24.00 (INSIDE) 3.00 5.29 6.28 6.28 Table 47.1 - Outdoor STANDARD Blower Unit (Model Digit 2=C or P, Digit 16=A through H) n j k l m n Dimensions (Inches) Model Size Blower Type (Digit 16) 100/125 All 33.75 28.75 21.00 25.00 20.02 39.23 34.56 1/2 150/175 All 33.75 28.75 24.00 25.00 23.99 39.23 38.82 1/2 200/225 All 37.75 32.75 27.00 28.00 23.99 43.23 40.94 1/2 250/300 E, F, G, or H 37.75 32.75 30.00 28.00 29.96 43.23 44.05 3/4 350/400 E, F, G, or H 37.75 32.75 42.00 28.00 41.90 43.23 55.57 3/4 A G H J K N P Gas Conn. For Right Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. For Left Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. All dimensions shown are in inches. 5-572.11 47 DIMENSIONS - UNIT Figure 48.1 - Outdoor EXTENDED Blower Cooling Package Unit (Model Digit 2=C, Digit 16=I, J, K, or L) n 141.34 24.00 33.50 36.58 47.27 QTY (4) DRILL LOCATOR DIMPLES FOR FIELD DRILLED ELECTRICAL CONDUIT ENTRY HOLES (SPACED 2.0" APART) OPTIONAL RAINHOOD & BIRDSCREEN 2.32 P (OVER ROOF) 3.97 28.00 (HEIGHT) X H (WIDTH) (INSIDE) 24.00 (INSIDE) 1 7.65 4.5 14.55 FRESH AIR DUCT CONNECTION 9.21 2 24.94 OPTIONAL RETURN AIR DUCT CONNECTION 24.00 (Inside) K (INSIDE) 3 24.00 (INSIDE) 9.21 4 1 2 1.50 3.00 1.50 5.29 5.29 143.98 N 6.28 6.28 Figure 48.2 - Outdoor EXTENDED Blower Cooling & Downturn Unit (Model Digit 2=P, Digit 16=I, J, K, or L) n 170.66 29.32 33.50 24.00 36.58 47.27 QTY (4) DRILL LOCATOR DIMPLES FOR FIELD DRILLED ELECTRICAL CONDUIT ENTRY HOLES (SPACED 2.0" APART) 2.32 OPTIONAL RAINHOOD & BIRDSCREEN P (OVER ROOF) 3.97 24.00 (INSIDE) 1 24.00 (INSIDE) 4.27 2 9.21 24.94 DOWNTURN DUCT CONNECTION OPTIONAL RETURN AIR DUCT CONNECTION 24.00 (INSIDE) 4.35 K (INSIDE) 4.5 FRESH AIR 14.55 DUCT CONNECTION 24.00 (INSIDE) 9.21 4 1 2 3 1.50 1.50 5.29 6.28 N 3.00 5.29 6.28 173.22 Table 48.1 - Outdoor EXTENDED Blower Unit (Model Digit 2=C or P, Digit 16=I, J, K, or L) n Model Size Dimensions (Inches) Blower Type (Digit 16) F H K N P Gas Conn. 250/300 I, J, or K 27.09 30.00 29.96 43.23 44.05 3/4 350/400 I, J, or K 38.60 42.00 41.90 43.23 55.57 3/4 j k l m n For Right Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. For Left Hand Access Units - Location of drill locator dimples/knockouts for field drilled gas connection entry holes - one side of unit and one on bottom. For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections. All dimensions shown are in inches. 48 5-572.11 DIMENSIONS - UNIT BASE Figure 49.1 - Unit Base Dimensions k A C To end of Unit F G M M 6.28 B J Drill Locator Dimple for Field Drilled Gas Connection Entry Hole Left Hand Access Units Inside E Drill Locator Dimple for Field Drilled Gas Connection Entry Hole Right Hand Access Units 6.28 M M Return Air Opening Supply Air Opening 24.00 Inside 4.29 Inside E 24.00 H 4.35 Inside Table 49.1 - Outdoor Unit Base Rail Dimensions for Model Digit 2=B or D k Dimensions (Inches) Model Blower Type Digit 2=B Digit 2=D Size (Digit 16) A C A C B E F Digit 2=B or D G H J M 100/125 150/175 200/225 250/300 250/300 All All All E,F,G, or H I, J, or K 84.41 84.41 84.41 84.41 120.00 81.49 81.49 81.49 81.49 117.34 113.63 113.63 113.63 113.63 149.22 110.82 110.82 110.82 110.82 146.66 37.36 41.61 43.71 46.75 46.75 19.52 23.49 23.49 29.46 29.46 78.66 78.66 78.66 78.66 114.23 53.72 53.72 53.72 53.72 84.29 1.53 1.53 1.53 1.53 1.28 34.50 38.75 40.85 43.89 43.89 7.49 7.63 8.69 7.21 7.21 350/400 350/400 E,F,G, or H I, J, or K 84.41 120.00 81.49 117.34 113.63 149.22 110.82 146.66 58.27 58.27 41.40 41.40 78.66 114.23 53.72 82.29 1.53 1.28 55.41 55.41 7.00 7.00 500/600 500/600 G or H I, J, K, or L 117.53 153.12 114.94 150.74 146.77 182.36 144.12 180.00 46.75 46.75 29.46 29.46 78.66 114.23 53.72 82.29 1.53 1.28 43.89 43.89 7.21 7.21 700/800 700/800 G or H I, J, K, or L 117.53 153.12 114.94 150.74 146.77 182.36 144.12 180.00 58.27 58.27 41.40 41.40 78.66 114.23 53.72 82.29 1.53 1.28 55.41 55.41 7.00 7.00 840/960 I, J, K, or L 186.52 184.14 215.77 213.40 58.27 41.40 114.23 82.29 1.28 55.41 7.00 Table 49.2 - Outdoor Unit Base Rail Dimensions Model Digit 2=C or P k Dimensions (Inches) Model Blower Type Digit 2=C Digit 2=P Size 100/125 150/175 200/225 250/300 250/300 350/400 350/400 (Digit 16) A C A C B E F Digit 2=C or P G H J M All All All E,F,G, or H I, J, or K E,F,G, or H I, J, or K 108.39 108.39 108.39 108.39 143.98 108.39 143.98 105.49 105.49 105.49 105.49 141.34 105.49 141.34 137.63 137.63 137.63 137.63 173.22 137.63 173.22 134.82 134.82 134.82 134.82 170.66 134.82 170.66 37.36 41.61 43.71 46.75 46.75 58.27 58.27 19.52 23.49 23.49 29.46 29.46 41.40 41.40 78.66 78.66 78.66 78.66 114.23 78.66 114.23 53.72 53.72 53.72 53.72 82.29 53.72 82.29 1.53 1.53 1.53 1.53 1.28 1.53 1.28 34.50 38.75 40.85 43.89 43.89 55.41 55.41 7.49 7.63 8.69 7.21 7.21 7.00 7.00 j Gas connection for 1st furnace. For Model sizes 500-800 add 33.5” for second furnace gas connection. For Model sizes 840-960 add 33.50” and 67.00” for second and third furnace gas connections. k All dimensions shown are in inches. 5-572.11 49 DIMENSIONS - ROOF CURBS Figure 50.1 - Roof Curb Dimensions k DISCHARGE AIR OPENING FOR UNITS WITH MODEL DIGIT 2= D OR P ONLY Table 50.1 - Roof Curb Dimensions Model Digit 2=B or D k Model Blower Type Size 100/125 150/175 200/225 250/300 250/300 350/400 350/400 500/600 500/600 700/800 700/800 840/960 (Digit 16) All All All E,F,G, or H I, J, or K E,F,G, or H I, J, or K G or H I, J, K, or L G or H I, J, K, or L I, J, K, or L Digit 2=B A 88.77 88.77 88.77 88.77 124.61 88.77 124.61 121.89 157.74 121.89 157.74 191.14 B C 76.77 76.77 76.77 76.77 112.61 76.77 112.61 109.89 145.74 105.98 109.89 145.74 105.98 179.14 105.98 D 39.76 39.76 73.16 Dimensions (Inches) Digit 2=D A B C D 117.98 105.98 117.98 105.98 117.98 105.98 117.98 105.98 153.83 141.63 105.98 35.85 117.98 105.98 153.83 141.63 105.98 35.85 151.10 139.10 105.98 33.12 186.98 174.98 105.98 69.00 151.10 139.10 105.98 33.12 186.98 174.98 105.98 69.00 220.39 208.39 105.98 102.41 Digit 2=B or D E 41.84 46.18 48.22 51.25 51.25 62.76 62.76 51.25 51.25 62.76 62.76 62.76 F 29.84 34.18 36.22 39.25 39.25 50.76 50.76 39.25 39.25 50.76 50.76 50.76 G 5.22 5.41 6.43 4.96 4.96 4.74 4.74 4.96 4.96 4.74 4.74 4.74 H 19.52 23.49 23.49 29.46 29.46 41.40 41.40 29.46 29.46 41.40 41.40 41.40 J 74.84 74.84 74.84 74.84 110.41 74.84 110.41 74.84 110.41 74.84 110.41 110.41 Table 50.2 - Roof Curb Dimensions Model Digit 2=C or P k Model Blower Type Size 100/125 150/175 200/225 250/300 250/300 350/400 350/400 (Digit 16) All All All E,F,G, or H I, J, or K E,F,G, or H I, J, or K Dimensions (Inches) Digit 2=P Digit 2=C A 112.74 112.74 112.74 112.74 148.59 112.74 148.59 B C 100.74 100.74 100.74 100.74 136.59 105.98 100.74 136.59 105.98 D 30.61 30.61 A 141.98 141.98 141.98 141.98 177.83 141.98 177.83 B 129.98 129.98 129.98 129.98 165.83 129.98 165.83 C 100.74 100.74 100.74 100.74 105.98 100.74 105.98 j Gas connection for 1st furnace. For Model sizes 500-800 add 33.5” for second furnace gas connection. For Model sizes 840-960 add 33.50” and 67.00” for second and third furnace gas connections. k All dimensions shown are in inches. 50 5-572.11 Digit 2=C or P D 29.24 29.24 29.24 29.24 59.85 29.24 59.85 E 41.84 46.18 48.22 51.25 51.25 62.76 62.76 F 29.84 34.18 36.22 39.25 39.25 50.76 50.76 G 5.22 5.41 6.43 4.96 4.96 4.74 4.74 H J 19.52 74.84 23.49 74.84 23.49 74.84 29.46 74.84 29.46 110.41 41.40 74.84 41.40 110.41 DIMENSIONS - COOLING COILS Figure 51.1 - DX Coil Drawing l Airflow Direction Rows 2 W 7.5 3 6 4 7.5 6 10 TOP VIEW L 1.5 1.5 Coil for Right Hand Units (Digit 9 = R) Headers on opposite side for Left Hand Units W Distributor Inlet (Liquid Line) Connection(s) (Second Inlet on Dual Circuit Coils) S FL FRONT VIEW H SIDE VIEW FH Airflow Direction 1.5 Suction Line Connections in direction of airflow (Second Inlet on Dual Circuit Coils) I Table 51.1 - DX Coil Dimensions l DX - Single Circuit DX - Dual Circuit Model Size Cooling MBH FH H S FL I L FL I L 100/125 All 27.5 30.5 1.5 21 28 24 19.5 29.75 22.5 150/175 All 27.5 30.5 1.5 24 31 27 23 33.25 28.5 Below 185 MBH 32.5 34.5 0.5 27 34 30 185 MBH & Up 32.5 34.5 0.5 27 34.5 30 25.5 35.75 28.5 Below 185 MBH 32.5 34.5 0.5 30 37 33 185 MBH & Up 32.5 34.5 0.5 30 37.5 33 28.5 38.75 31.5 Below 185 MBH 32.5 34.5 0.5 42 49 45 185 MBH & Up 32.5 34.5 0.5 42 49.5 45 40.25 50.5 43.25 200/225 250/300 350/400 j Single Circuit DX coils have 1 each Suction Line and Liquid Lines. Refer to AccuSpec for line size diameters. k Dual Circuit DX coils have 2 each Suction Line and Liquid Lines. Refer to AccuSpec for line size diameters. l All dimensions shown are in inches. 5-572.11 51 DIMENSIONS - RAINHOOD, REMOTE PANEL & EVAPORATIVE COOLER Figure 52.1 - Rainhood and Birdscreen Dimensions (inches) 1.09 A 1.14 42.66 Approx. 31.19 Table 52.1 - Rainhood and Birdscreen Dimensions (inches) 1.14 Rainhood & Birdscreen Model Size A 100/125 31.94” 150/175 38.24” 200/225 38.24” 250/300 41.34” 350/400 52.85” 500/600 41.34” 700/800 52.85” 840/960 52.85” 32.71 44.56 .75 Figure 52.2 - Evaporative Cooler (Model Digit 22=D) J-BOX Top View 1.25” PUMP C W/2 -1.50” Drain 1/2" 1/2" NPTNPT DRAIN NPT Overflow 1/2"1/2" NPT OVERFLOW 1.50 W 3.00” 1.50” 4.50” Side View Figure 52.3 - Remote Panel Dimensions (inches) OPTIONAL 1” PRE-FILTER RACK NOTES: 1. Holes visable on right side are also on the left side in the same location. 2. Holes on top are also on the back in the same location horizontally. 5.57 1.25” 3.53 BLOWER SECTION 36.00” A 3.38 2.13 3.53 B 12" MEDIA Table 52.3 - Remote Panel Dimensions (inches) H Remote Panel Type A B C Light and Switch Panels Only 7.06” - 2.81” Light and Switch Panels with Single Stage Thermostat or Electronic Set Point Adjustor 10.60” 3.53” 4.58” Light and Switch Panels with Two Stage Thermostat 13.09” 6.03” 5.82” 1/2" NPT WATER INLET 4.50” 3.00” 2.56 .25” LEVELING LEGS 25.50” Table 52.2 - Evap Cooler Dimension, Performance, and Weight Data Blower Type Model Size (Digit 16) H (in.) 100/125 52 All 34 12” GlasDek Media (Digit 23 = D) W (in.) Maximum Cooling CFM Media Face Area (ft²) Maximum Face Velocity (ft/min) Dry Weight (lbs) Op. Weight (lbs) 30 4000 5.0 800 159 295 150/175 All 34 36 5200 6.5 800 169 336 200/225 All 38 36 6000 7.5 800 174 341 250/300 E,F,G, or H 38 39 6500 8.1 800 182 363 250/300 I, J, or K 56 39 10400 13.0 800 214 404 350/400 E,F,G, or H 38 51 8500 10.6 800 228 473 350/400 I, J, or K 47 51 11050 13.8 800 244 496 500/600 G or H 38 39 6500 8.1 800 182 363 500/600 I, J, K or L 56 39 10400 13.0 800 214 404 700/800 G or H 38 51 8500 10.6 800 228 473 700/800 I, J, K or L 47 51 11050 13.8 800 244 496 840/960 I, J, K or L 47 51 11050 13.8 800 244 496 5-572.11 WEIGHTS Table 53.1 - Unit Operating Weights j Dampers Digit 2 Model Blower Type Size (Digit 16) B D C P 100/125 All 474 578 584 688 6 26 46 150/175 All 511 621 626 736 6 29 52 200/225 All 588 707 714 833 6 29 250/300 E,F,G, or H 626 747 756 877 8 33 250/300 I, J, or k 875 996 1005 1126 15 350/400 E,F,G, or H 738 876 887 1025 12 350/400 I, J, or k 1019 1057 1168 1306 500/600 G or H 959 1080 n/a n/a 500/600 I, J, k, or L 1208 1329 n/a 700/800 G or H 1153 1291 n/a 700/800 I, J, k, or L 1352 1490 840/960 I, J, k, or L 1767 1905 Double Wall (all sections) Fresh Air Fresh & RainMotor Filters Only Return Air hood Digit 2 D C P 67 38 73 72 107 70 43 78 77 112 52 72 46 86 85 125 60 83 46 88 87 129 33 60 83 93 135 134 176 38 70 90 53 102 101 150 17 38 70 90 96 145 144 193 8 33 60 83 46 88 n/a n/a n/a 15 33 60 83 93 135 n/a n/a n/a 12 38 70 90 53 102 n/a n/a n/a n/a 17 38 70 90 96 145 n/a n/a n/a n/a 17 38 70 90 96 145 n/a n/a See Motor Data B Evap Cooler See Evaporative Cooler Data Base Unit j All weights in pounds and are approximate. Table 53.2 - Motor Operating Weights j Digit 17 - Motor Size Digit 14 Supply Voltage A - 115/60/1ph B - 208/60/1ph C - 230/60/1ph D - 208/60/3ph E - 230/60/3ph F - 460/60/3ph G - 575/60/3ph Digit 18 - Motor Type A or L B or M C or N D or P E or Q F or R G or S H or T I or W J or X K or Y V or Z 1/3 1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 1 - ODP 25 23 25 32 40 49 81 - - - - - 5 - TE 25 28 30 37 45 49 83 - - - - - 1 - ODP - 23 25 32 40 49 81 87 - - - - 5 - TE - 28 30 37 45 49 83 86 - - - - 1 - ODP 25 23 25 32 40 49 81 87 - - - - 5 - TE 25 28 30 37 45 49 83 86 - - - - 1 - ODP 17 18 21 - - - - - - - - - 2 - ODP HE - - - 83 94 99 83 94 141 126 220 250 5 - TE 15 23 26 - - - - - - - - - 6 - TE HE - - - 68 66 66 92 99 158 200 259 368 1 - ODP 17 18 21 - - - - - - - - - 2 - ODP HE - - - 40 46 54 87 94 130 126 217 250 5 - TE 15 23 30 - - - - - - - - - 6 - TE HE - - - 53 66 67 92 117 194 213 322 368 1 - ODP 17 18 21 - - - - - - - - - 2 - ODP HE - - - 40 46 54 87 94 130 126 217 250 5 - TE 15 23 30 - - - - - - - - - 6 - TE HE - - - 53 66 66 92 117 194 213 322 368 1 - ODP - 25 28 - - - - - - - - - 2 - ODP HE - - - 35 40 45 76 89 90 220 310 360 5 - TE - 24 33 - - - - - - - - - 6 - TE HE - - - 68 40 67 100 125 192 200 326 368 j All weights in pounds and are approximate. 5-572.11 53 MAINTENANCE WARNING When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk. AVERTISSEMENT tension should be rechecked shortly after the unit has been installed to check for belt stretching. After the initial start-up, monthly checks are recommended. Filters If the unit is supplied with a dirty filter switch and light, clean or replace the filters any time the dirty filter light comes on. Units which do not have a dirty filter warning light should have the filters checked monthly. Clean or replace if necessary. In dirty atmospheres, filter maintenance may be required more often. Figure 54.1 - Filter Replacement Arrangement for STANDARD Blower Size (Model Digit 16=A through H) Pour l’entretien et les réparations de cet appareil, utilisez uniquement des pièces d’origine certifiées. Pour la liste complete des pièces de rechange, consultez Modine Manufacturing Company. Le numéro de modèle complet, le numéro de série et l’adresse du fabricant figurent sur la plaque signalétique fixée à l’appareil. Toute substitution de pièce ou decommande non approuvée par le fabricant sera aux risques du propriétaire. FILTER SPACER B B CAUTION B C B C B B B B A A 150/175 100/125 75 FILTER SPACER Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced. A A A A A ATTENTION A C A A A A A C A A = 20'' x 25'' B = 16” x 25” C = 15” x 25” IMPORTANT 350/400 700/800 250/300 500/600 200/225 Ne tentez pas de réutiliser un composant mécanique ou électrique qui a été mouillé. Ces composants doivent être remplacés. FILTER SPACER TO BE INSERTED ON NON-ACCESS SIDE OF UNIT Figure 54.2 - Filter Replacement Arrangement for EXTENDED Blower Size (Model Digit 16 = I, J, K, or L) To check most of the Possible Remedies in the troubleshooting guide listed in Table 58.1, refer to the applicable sections of the manual. A A A D NON-ACCESS SIDE NON-ACCESS SIDE FILTER SPACER IMPORTANT A FILTER SPACER A Pour essayer la plupart des solutions possibles suggérées dans le guide de dépannage du Tableau 58.1 reportez-vous aux sections correspondantes du manuel. A A All heating equipment should be serviced before each heating season to assure proper operations. The following items may be required to have more frequent service schedule based on the environment in which the unit is installed, and the frequency of the equipment operation. Electrical Wiring The electrical wiring should be checked annually for loose connections or deteriorated insulation. Blower Assembly The blower assembly includes the bearings, drive sheaves and belts. Blower bearings should be checked and lubricated based on the blower manufacturer’s recommendations. Bearings should also be checked for any unusual wear and replaced if needed. Drive sheaves should be checked at the same time the bearings are inspected. Check to make sure the sheaves are in alignment and are securely fastened to the blower and motor shafts.Belt 54 FILTER SPACER 5-572.11 C A C 250/300 500/600 A C D A = 20'' x 25'' B = 16” x 25” C = 20” x 16” D = 15” x 25” A A B B 350/400 700/800 840/960 MAINTENANCE Cooling Coil Maintenance 1. 2. 3. eriodically, inspect the coil for signs of corrosion P and leaks. Repair and replacement of the coil and the connecting piping, valves, etc., must be performed as needed by a qualified technician. Should the coil surface need cleaning, caution should be exercised in selecting the cleaning solution as well as the cleaning equipment. Improper selection can result in damage to the coil and/or health hazards. Cleaning solutions must not be corrosive or cause damage to copper tube/aluminum fin coils. Clean the coil from the leaving airside so that foreign material will be washed out of the coil rather than pushed further in. Be sure to carefully read and follow the cleaning fluid manufacturer’s recommendations before using any cleaning fluid. For DX coils, replace the filter dryer(s) as needed. Cooling Coil Drain Pan and Drain System The drain pan, trap, and drain pipe must be cleaned regularly to avoid blockage that can reduce or stop water flow as follows: 1. At the beginning of the cooling season, inspect and clean the entire cooling coil cabinet and condensate drain pan to remove contaminants. 2. Inspect and clean the condensate drain trap and piping. The use of a cleanout opening at the top of the trap can help facilitate this maintenance. 3. Fill the trap with water to ensure proper operation and replace the cap on the cleanout opening to close the system. 4. During the end of cooling season shutdown of the system, disconnect and remove all water from the trap and drain to prevent freeze damage. If local building codes permit, the trap may be filled with an antifreeze solution. 5. If the unit is used year round, regularly inspect and clean the cooling coil cabinet, condensate drain pan, and trap/ drain system to ensure proper function. 6. Depending on climate, freeze protection of the trap may be required during non-cooling days. Duct Furnace When providing annual maintenance for the duct furnace, keep the unit free from dust, dirt, grease and foreign matter. Pay particular attention to: 1. The power exhauster discharge opening and the combustion air inlet louvers. 2. The burner ports and pilot burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these ports). To check the burner port and pilot burner orifice, see Burner and Pilot Assembly Removal. 3. The air shutters and main burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these orifices). To check the air shutters and main burner orifices, see for Manifold Assembly Removal. The heat exchanger should be checked annually for cracks and discoloration of the tubes. If a crack is detected, the heat exchanger should be replaced before the unit is put back into service. If the tubes are dark gray, airflow across the heat exchanger should be checked to insure that a blockage has not occurred or the blower is operating properly. Gas Piping & Controls The gas valves and piping should be checked annually for general cleanliness and tightness. The gas controls should be checked to insure that the unit is operating properly. (continued next page) 5-572.11 55 MAINTENANCE Manifold Assembly Removal To remove the manifold (Refer to Figure 56.1): 1. Shut off gas and electric supply. 2. Remove the side access panel. 3. Disconnect gas manifold at ground union joint. 4. Remove the two screws holding the manifold to the heat exchanger support. 5. Slide the manifold through the manifold bracket. 6. Clean the orifices and adjust the air shutters as necessary. 7. Follow steps 3-6 in reverse to install the manifold assembly. 8. Turn on the electric and gas supply. 9. Check the ground union joint for leaks with a soap solution. Tighten if necessary. 10. Install the side access panel. Figure 56.1 - Manifold Assembly Removal SERIAL PLATE ELECTRICAL JUNCTION BOX Burner and Pilot Assembly Removal To remove the burner (Refer to Figure 56.2): 1. Shut off gas and electric supply. 2. Disconnect the pilot supply line from the gas valve. 3. Disconnect the ignition cable from the ignition controller (located in the electrical junction box). Feed the cable through the bushing in the bottom of the junction box. 4. Remove the screws holding the burner side access panel. Attached to the panel are the burner retaining pins that align the burner. 5. Slide the burner assembly out. The pilot is attached to the burner assembly. 6. Examine the burner and pilot assembly for cleanliness and/or obstructions as necessary (see Duct Furnace for cleaning instructions). 7. Replace the burner assembly in reverse order. In replacing the burner, be certain that the rear burner slots are located properly on the burner retaining pins. Do not force the burner side access panel, it will not fit if the burner is not properly aligned. 8. Reconnect the ignition cable and pilot gas supply line. 9. Turn on the electric and gas supply. Figure 56.2 - Burner and Pilot Assembly Removal GROUND UNION JOINT MANIFOLD BURNER SIDE ACCESS PANEL PILOT ASSEMBLY IGNITION CABLE PILOT SUPPLY LINE HEAT EXCHANGER SUPPORT 56 5-572.11 AIR SHUTTERS (NOT SHOWN) ARE LOCATED ON THE MANIFOLD THIS PAGE INTENTIONALLY LEFT BLANK 5-572.11 57 SERVICE & TROUBLESHOOTING WARNING When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the unit for complete unit model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk ATTENTION Ne tentez pas de réutiliser un composant mécanique ou électrique qui a été mouillé. Ces composants doivent être remplacés. IMPORTANT To check most of the Possible Remedies in the troubleshooting guide listed in Table 58.1, refer to the applicable sections of the manual. AVERTISSEMENT Pour l’entretien et les réparations de cet appareil, utilisez uniquement des pièces d’origine certifiées. Pour la liste complete des pièces de rechange, consultez Modine Manufacturing Company. Le numéro de modèle complet, le numéro de série et l’adresse du fabricant figurent sur la plaque signalétique fixée à l’appareil. Toute substitution de pièce ou decommande non approuvée par le fabricant sera aux risques du propriétaire. IMPORTANT Pour essayer la plupart des solutions possibles suggérées dans le guide de dépannage du Tableau 58.1 reportez-vous aux sections correspondantes du manuel. CAUTION Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced. Table 58.1 - Troubleshooting Trouble Pilot does not light Main burners do not light (Pilot is lit) Lifting Flames (See Figure 59.1) Yellow Tipping (With propane gas, some yellow tipping is always present.) Flashback Possible Cause 1. 2. 3. Main gas is off. Power supply is off. Air in gas line. 4. Dirt in pilot orifice. 5. Gas pressure out of proper range. 6. 7. Pilot valve does not open. a. Defective ignition controller. b. Defective gas valve. No Spark at ignitor. a. Loose wire connections. b. Pilot sensor is grounded. c. Defective ignition controller. 8. Safety device has cut power. 1. 2. 3. 4. 5. 1. 2. Defective valve. Loose wiring. Defective pilot sensor Defective ignition controller. Improper thermostat wiring. Too much primary air. Main pressure set too high. 3. Orifice too large. 1. Insufficient primary air. 2. Dirty orifice. 5. 6. 7 8. 1. 2. 3. 4. 5. 1. 2. 3. Open manual gas valve. Turn on main power. Purge gas line. C heck for plugged pilot orifice and clean with compressed air if necessary. Adjust to a minimum for Natural Gas - 6” W.C. Minimum for Propane Gas - 11” W.C. Maximum 14” W.C. Check wiring for 24 volts to valve. a. Replace ignition controller. b. Replace gas valve. a. Check all ignition controller wiring. b. Replace sensor if cracked or worn c. Replace ignition controller. C heck all safety devices (High limit, air flow proving switch, power exhauster centrifugal switch, gas pressure switches, etc.) Determine and correct problem. Reset if necessary. Replace valve. Check wiring to gas valve. Replace pilot sensor. Replace ignition controller. Verify wiring compared to wiring diagram. Reduce primary air. Adjust to a maximum of 14” W.C. C heck orifice size with those listed on the serial plate. 1. Increase primary air. 2. C heck orifices and clean with compressed air if necessary. Check manifold, replace if necessary. 3. Misaligned orifice. 3. 1. Too much primary air. 1. Reduce primary air. 2. Main pressure set too high. 3. Orifice too large. 2. 3. Adjust to a maximum of 14” W.C. C heck orifice size with those listed on the serial plate. (Continued next page) 58 Possible Remedy 1. 2. 3. 4. 5-572.11 SERVICE & TROUBLESHOOTING (CONTINUED) Troubleshooting (Continued) Trouble Possible Cause Possible Remedy Floating Flames (See Figure 59.2) 1. 2. 3. Insufficient primary air. Main pressure set too high. Orifice too large. 4. 1. 2. Blocked vent cap. Main pressure set too high. Orifice too large. 3. 1. Blocked vent cap. Unit cycling on high limit. j a. Obstructions/leaks in duct system. b. Main pressure set too high. 1. Increase primary air. 2. Adjust to a maximum of 14” W.C. 3. Check orifice size with those listed on the serial plate. 4. Clean louvers in vent cap. 1. Adjust to a maximum of 14” W.C. 2. Check orifice size with those listed on the serial plate. 3. Clean louvers in vent cap. 1. a. Clean/correct duct system. b. Adjust to a maximum of 14” W.C. c. Check that blower motor operates within 45 seconds of when gas controls are energized. d. Adjust belt tension. e. Check/correct blower drive settings for proper rpm. f. Check/correct venting system. g. Replace high limit switch. 2. Adjust main gas pressure. (Minimum for Natural Gas — 6” W.C. Minimum for Propane Gas — 11” W.C.) 3. Adjust outside air damper to decrease outside air percentage (if possible). 4. Check/replace thermostat. Flame Rollout (See Figure 59.3) Not Enough Heat c. Blower motor not energized. d. Loose belt e. Blower speed too low. f. Blocked/damaged venting system. g. Defective high limit switch. Too Much Heat Power Exhauster Motor Will Not Start 2. Main pressure set too low. 3. Too much outside air. 4. Thermostat malfunction. 5. 6. Gas controls wired incorrectly. Unit undersized. 1. 2. Thermostat malfunction. Gas controls do not shut-off. a. Gas controls wired incorrectly. b. Short circuit. Main gas pressure set too high. Defective gas valve. Power supply is off. No 24V power to thermostat. Thermostat malfunction. Defective power exhauster relay. Defective power exhauster motor. 3. 4. 1. 2. 3. 4. 5. 5. Check unit wiring against the wiring diagram. 6. Check design conditions. If unit is undersized, an additional unit(s) or other heat source must be added. 1. Check/replace thermostat. 2. a. Check unit wiring against the wiring diagram. b. Check for loose or worn wires. 3. Adjust to a maximum of 14” W.C. 4. Replace gas valve. 1. Turn on main power. 2. Check control transformer. 3. Check/replace thermostat. 4. Replace power exhauster relay. 5. Replace power exhauster motor. j T he duct furnace comes standard with an automatic reset high limit switch that will shut-off the gas should the discharge air temperature become excessive. See Figure 29.1, indicator (49) for the location of the high limit switch. The switch should operate only when something is wrong with the unit operation. Anytime the switch operates, correct the difficulty immediately or serious damage may result. If the switch cuts off the gas supply during normal operation, refer to the “Not Enough Heat” section of Table 58.1. Figure 59.1 - Lifting Flame Condition Figure 59.2 Floating Flame Condition Figure 59.3 Flame Rollout Appearance 5-572.11 59 START-UP CHECKLIST Start-Up Checklist Indirect Gas-Fired Heating Equipment Job Name: Date: Address: Model No.: City & State: Order No.: Start-Up Check List “ALL ITEMS MUST BE CHECKED” Serial No.: 1. All shipping straps, braces, tie downs removed? 2. Unit installed level and secure? 3. Gas burner properly located and aligned? 4. Blower and motor alignment okay? 5. Bearings aligned and tight on shaft/bearing supports? 6. Electrical connections checked and secure? 7. Gas piping checked and tightened if necessary? 8. Any visible damage to unit? Describe: ______________________________________________ If damaged, was the damage repaired? 9. Air inlet and discharge checked for obstructions? 10. Bearings checked for proper lubrication? 11. Filters in place and correct to direction of air flow? 12. Belt tension checked? 13. Electric supply to unit: ______ Volts, ______ Hz, ______ Phase 14. Gas supply to unit: ______ Natural, ______ Propane 15. Gas supply pressure to unit: ______ " W.C., ______ PSIG 16. Inlet and/or discharge dampers operating correctly? 17. Blower rotation correct? 18. Blower speed: Hi Speed ______ RPM, Lo Speed ______ RPM 19. Motor speed: Hi Speed ______ RPM, Lo Speed ______ RPM 20. Is unit noisy? Excessive vibration? 21. Motor voltage: L1 ______ V, L2 ______ V, L3 ______ V 22. Motor amps: L1 ______ Amp, L2 ______ Amp, L3 ______ Amp 23. High temperature limit control continuity checked? 24. Burner light off Low Fire: Does entire burner light off? Hi Fire: Burner pressure reading? ______ " W.C. Is flame clean and stable? Does flame modulate in response to temperature control(s)? 25. Gas input checked? Input at maximum firing rate: __________ Btu/Hr Input at minimum firing rate: ‑__________ Btu/Hr 26. Gas piping checked for and free of leaks? 27. Has wiring been verified to match the unit wiring diagram? 28. Have all the modes of the sequence of operation been verified and tested? 29. What optional and/or accessory control devices have been set? Device: _______________ Setting: __________ (°F/psi/Inches W.C./etc.) Device: _______________ Setting: __________ (°F/psi/Inches W.C./etc.) Device: _______________ Setting: __________ (°F/psi/Inches W.C./etc.) _____ Yes _____ Yes _____ Yes _____ Yes _____ Yes _____ Yes _____ Yes _____ Yes ____ ____ ____ ____ ____ ____ ____ ____ No No No No No No No No _____ Yes _____ Yes _____ Yes _____ Yes _____ Yes ____ ____ ____ ____ ____ No No No No No _____ Yes _____ Yes ____ No ____ No _____ Yes ____ No _____ Yes ____ No _____ Yes ____ No _____ Yes _____ Yes _____ Yes ____ No ____ No ____ No _____ Yes _____ Yes _____ Yes ____ No ____ No ____ No _____ Yes _____ Yes _____ Yes ____ No ____ No ____ No Customer/Owner instructed in operation and maintenance of unit? _____ Yes ____ No Name of Person(s) Instructed: _______________________________________________________________ Comments: _____________________________________________________________________________ _____________________________________________________________________________ Start-Up Company Name: ________________________________ Phone: ___________________________ Signature:________________________________________________________ Date: _________________ 60 5-572.11 MODEL DESIGNATIONS Model Identification Modine weatherproof duct furnace/make-up air units contain an ETL/ETL Canada certified weatherproof duct furnace. This duct furnace is combined with either a blower section, or a blower and/or cooling and/or downturn sections to make a complete make-up air or heating/ventilating/cooling unit that is ETL/ ETL Canada certified. For this reason, two identification plates are used on these models. The Serial Plate is used to identify the duct furnace and its components. The Model Identification Plate is used to identify the complete model, including blower, cooling, and/or downturn sections. Figure 61.1 - Furnace Serial Plate Location SERIAL PLATE Replacement Parts Ordering When servicing, repairing or replacing parts on these units, locate the model identification plate of the unit and always give the complete Model Number and Serial Number from the model identification plate. The model identification plate is located on the blower section electrical compartment door. For a complete description of the model number, see Weatherproof Model Nomenclature on page 62. Figure 61.2 - Furnace Serial Plate (sample shown, actual data may vary) Figure 61.3 - Model Identification Plate (sample shown, actual data may vary) 5-572.11 61 MODEL NOMENCLATURE FOR SYSTEM UNITS Weatherproof Model Nomenclature 1 2 3 456 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 PT UC V MBH HE DS AS ATR GT GV SS SV TR BB HP MT SA AC EC CC 1 - Product Type (PT) H or O - Outdoor HVAC Unit 15 - Transformer (TR) 1 - 40 VA 2 - 75 VA 3 - 150 VA 2 - Unit Configuration (UC) B - Blower Package - Furnace & Blower C - Cooling Package - Furnace, Blower, & Cooling Cabinet D - Downturn Package - Furnace, Blower, & Downturn P - Packaged Unit - Furnace, Blower, Cooling Cabinet, & Downturn 16 - Blower Size & Bearing Type (BB) C - 9-9 Spider Bearings H - 15-15 Pillow Block Bearings D - 9-9 Pillow Block Bearings I - 18-18 Spider Bearings under 15 Hp E - 12-12 Spider Bearings J - 18-18 Pillow Block Brngs under 15 Hp F - 12-12 Pillow Block Brngs K - 18-18 Pillow Block Brngs, 15 Hp & Up G - 15-15 Spider Bearings L - 20-18 Pillow Block Bearings 3 - Venting (V) P - Power 4,5,6 - Furnace Input Rating (MBH) (Except for 840 & 960) 100 - 100,000 Btu/Hr Input 350 - 350,000 Btu/hr Input 125 - 125,000 Btu/Hr Input 400 - 400,000 Btu/Hr Input 150 - 150,000 Btu/Hr Input 500 - 500,000 Btu/Hr Input 175 - 175,000 Btu/Hr Input 600 - 600,000 Btu/Hr Input 200 - 200,000 Btu/Hr Input 700 - 700,000 Btu/Hr Input 225 - 225,000 Btu/Hr Input 800 - 800,000 Btu/Hr Input 250 - 250,000 Btu/Hr Input 840 - 1,050,000 Btu/Hr Input 300 - 300,000 Btu/hr Input 960 - 1,200,000 Btu/Hr Input 7 - Heat Exchanger/Burner/Drip Pan Material (HE) T - 409 Stainless Steel Heat Exchanger/Burner/Drip Pan 8 - Development Sequence Designation (DS) F - Single Stage M - 2-stage or Modulating 9 - Access Side (AS) R - Right Hand L - Left hand 10 - Air Temperature Rise (ATR) H - High 60°-100°F L - Low 20°-60°F 11 - Gas Type (GT) N - Natural with ignition controller P - Propane with ignition controller 12 - Gas Valve (GV) 1 - Single Stage 2 - Two Stage 4 - Electronic Modulation 7 - Electronic Modulation 0-10 Vdc External Input 9 - Electronic Modulation with Modine Control System 13 - Additional Safety Switches (SS) 0 - No Switches (Standard) 3 - High and Low Gas Pressure Switch (Premium) 14 - Supply Voltage (SV) A - 115/60/1 B - 208/60/1 C - 230/60/1 D - 208/60/3 62 E - 230/60/3 F - 460/60/3 G - 575/60/3 4 - 250 VA 0 - None 17 - Motor Horsepower (HP) A - 1/3 Hp L - 1/3 Hp with Motor Starter B - 1/2 Hp M - 1/2 Hp with Motor Starter C - 3/4 Hp N - 3/4 Hp with Motor Starter D - 1 Hp P - 1 Hp with Motor Starter E - 1-1/2 Hp Q - 1-1/2 Hp with Motor Starter F - 2 Hp R - 2 Hp Hp with Motor Starter G - 3 Hp S - 3 Hp with Motor Starter H - 5 Hp T - 5 Hp with Motor Starter I - 7-1/2 Hp W - 7-1/2 Hp with Motor Starter J - 10 Hp X - 10 Hp with Motor Starter K - 15 Hp Y - 15 Hp with Motor Starter V - 20 Hp Z - 20 Hp with Motor Starter 18 - Motor Type (MT) 1 - ODP 2 - ODP - High Eff. 5 - TE 6 - TE - High Eff. 19 - Sheave Arrangement (SA) A-Z - (See Sheave Tables) 20,21 - Air Control (AC) AA - RA Opening BA - FA Opening CA - FA & RA Openings DA - FA Dampers w/ 2 pos motor (No RA) EA - FA & RA Dampers w/ 2 pos motor GA - FA & RA Mod motor w/ 0-10 Vdc External Input GC - FA & RA Mod motor w/ Minimum Position (Factory Mounted) GE - FA & RA Mod motor w/ 3 pos. damper (100% RA, Variable, 100% OA) 22 - Evaporative Cooling (EC) 0 - None D - 12" GLASdek Media, Stainless Steel Casing 23 - Cooling Coil (CC) 0 - None 1 - Factory Installed Coil 5-572.11 THIS PAGE INTENTIONALLY LEFT BLANK 5-572.11 63 Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Phone: 1.800.828.4328 www.modinehvac.com © MODINE MANUFACTURING COMPANY 2023 ">
![](http://s1.manualzz.com/store/data/078845352_1-ed58325f84a65bd272b2ba1c7c8d52cd-210x147.png)
Advertisement
Key features
- Weatherproof design
- Gas-fired operation
- Industrial/Commercial applications
- Outdoor installation
- Fresh heated air supply
- Variable CFM output
Frequently asked questions
The manual highlights several safety considerations, including avoiding areas with corrosive vapors to prevent heat exchanger failure, ensuring proper lifting procedures, and disconnecting power before working on the unit. Always refer to the manual for detailed instructions.
The manual provides a table with minimum clearances for combustible materials based on the size of the unit. For example, a 200/225 size unit requires a 4” clearance to the side and 42” clearance to the front and rear.
The manual recommends using a soap solution or equivalent to check for leaks in the gas piping. Never use an open flame to check for leaks.