P-SERIES
SUBMITTAL DATA: PCA-A36KA4 & PUZ-HA36NHA4
36,000 BTU/H CEILING-SUSPENDED HYPER HEAT-PUMP SYSTEM
Job Name:
System Reference:
Date:
Indoor Unit: PCA-A36KA4
Outdoor Unit: PUZ-HA36NHA4
GENERAL FEATURES
•
•
•
•
•
•
•
High heating capacity at low outside temperatures
Exhibits 100% of rated heating capacity at 5º F; 90% of rated heating capacity at -4º F
Built-in drain lift mechanism for condensate removal; lifts up to 33-7/16 inches
Wide air flow pattern for better air distribution; independently adjustable vanes
Auto wave airflow in heating mode—unit independently cycles through horizontal and vertical positions for a more even heat distribution
Self-check function—integrated diagnostics
Limited warranty: five years parts and seven years compressors
ACCESSORIES
Indoor Unit
□□ Condensate Pump (PAC-SH84DM-E)
□□ High-efficiency Filter (MERV 8) (PAC-SH89KF-E)
Outdoor Unit
□□ M-NET Adapter (PAC-SF81MA-E)
□□ Wind Baffle (One Piece)* (WB-PA2)
□□ Air Outlet Guide (One Piece)* (PAC-SG59SG)
*PUY(Z) requires two outlet guides or wind baffles for installation.
Controller Options
□□ Wireless Wall-mounted Remote Controller Kit (MHK1)**
□□ Portable Central Controller (MCCH1)**
□□ Outdoor Air Sensor (MOS1)**
□□ Wired Wall-mounted Controller (PAR-31MAA)**
□□ Simple MA Remote Controller (PAC-YT53CRAU)**
**See Submittal for information on each option.
□□ M-NET Adapter (PAC-SF81MA)
□□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan Controller (PAC-725AD)
□□ CN24 Relay Kit (CN24RELAY-KIT-CM3)
□□ CN32 Connector for Remote On/Off (PAC-715AD)
□□ Remote Temperature Sensor (PAC-SE41TS)
□□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□□ Wireless Remote Control with Receiver Kit (PAR-SL93B-E)
□□ i-see Sensor Corner Panel (PAC-SA1ME)
□□ Wireless Remote Control with Receiver and i-see Sensor Kit (PAR-SA92MW-E)
□□ i-see Sensor (PAC-SH91MK-E)
□□ Lockdown Bracket for Hand-held Controller (RCMKP1CB)
□□ Control/Service Tool (PAC-SK52ST)
SEACOAST PROTECTION
• External Outer Panel: Phosphate coating + Acrylic-Enamel coating
• Fan Motor Support: Epoxy resin coating (at edge face)
• Separator Assembly ; Valve Bed: Epoxy resin coating (at edge face)
• Screws (used outer side): Zinc nickel coating 5μm + Polyvinylidene chloride coating
“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants..
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
SPECIFICATIONS: PCA-A36KA4 & PUZ-HA36NHA4
Cooling
Rated Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,000 Btu/h
SEER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16.6 Btu/h/W
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,810 W
Heating at 47°F
Rated Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,000 Btu/h
HSPF (IV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3 Btu/h/W
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,270 W
Heating at 17°F
Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27,000 Btu/h
Rated Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,490 W
Maximum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 38,000 Btu/h
Maximum Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,720 W
Heating at 5°F
Maximum Capacity** . . . . . . . . . . . . . . . . . . . . . . . . . . 38,000 Btu/h
Maximum Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,550 W
* Rating Conditions per AHRI Standard
Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB
Cooling | Outdoor: 95º F (35º C) DB / 75º F (24º C) WB
Heating at 47º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 47º F | Outdoor: 47º F (8º C) DB / 43º F (6º C) WB
Heating at 17º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 17º F | Outdoor: 17º F (-8º C) DB / 15º F (-9º C) WB
Heating at 5º F | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 5º F | Outdoor: 5º F (-15º C) DB / 5º F (-15º C) WB
** Maximum Capacity is at full speed and performance for
INVERTER-driven System.
ELECTRICAL REQUIREMENTS
Power Supply . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
Breaker Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 A
Voltage
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . DC ±24V
Indoor - Remote Controller . . . . . . . . . . . . . . . . . . . . . MKH1 DC 3V
PAR-21MAAU DC 12V
PAR-FL32MA DC 3V
OPERATING RANGE
Indoor Intake Air Temp. Outdoor Intake Air Temp.
90º F (32º C) DB
115º F (46º C) DB
73º F (23º C) WB
Cooling
66º F (19º C) DB
Minimum
0º F** (-18º C) DB
59º F (15º C) WB
70º F (21º C) DB
Maximum 83º F (28º C) DB
59º F (15º C) WB
Heating
-13º F (-25º C) DB
Minimum 63º F (17º C) DB
-13º F (-25º C) WB
Maximum
Note: With optional wind baffle accessory installed. If not installed,
the minimum temperature will be 23º F (-5º C) DB.
Notes:
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
INDOOR UNIT
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 A
Blower Motor (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.97 F.L.A.
Blower Motor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 W
Airflow (Lo - M1 - M2 - Hi) . . . . . . . . 775 - 850 - 920 - 990 Dry CFM
705 - 775 - 850 - 920 Wet CFM
Sound Pressure Level (Lo - M1 - M2 - Hi) . . 37 - 39 - 41 - 43 dB(A)
DIMENSIONS
W
D
H
UNIT INCHES / MM
63 / 1,600
26-3/4 / 680
9-1/16 / 230
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 lbs. / 36 kg
External Finish . . . . . . . . . . . . . . . . . . . . . . Munsell No. 6.4 8.9 / 0.4
Field Drainpipe Size O.D. . . . . . . . . . . . . . . . . . . . . 1-1/32” / 26 mm
OUTDOOR UNIT
Compressor . . . . . . . . . . . . . . . . . . . . . . . . DC Inverter-driven Scroll
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 8
Fan Motor (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.4 + 0.4 F.L.A.
Sound Pressure Level
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 dB(A)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 dB(A)
DIMENSIONS
W
D
H
INCHES / MM
37-3/8 / 950
13 + 1-3/16 / 330 + 30
53-1/8 / 1,350
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 lbs. / 120 kg
External Finish . . . . . . . . . . . . . . . . . . . . . . Munsell No. 3Y 7.8 / 1.1
Refrigerant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5/8” / 15.88 mm
Liquid Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8” / 9.52 mm
Max. Refrigerant Pipe Length . . . . . . . . . . . . . . . . . . . . . 245’ / 75 m
Max. Refrigerant Pipe Height Difference . . . . . . . . . . . . 100’ / 30 m
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
ventilation
If the piping is installed in the back
of the unit, remove the shaded portions from
the component at right. Then, reinstall the
component in its original position (the heat
exchanger might be clogged beause of dust.
DIMENSIONS: PCA-A36KA4
Min. 150mm
<5-29/32>
Min. 10mm
<3/8>
Service space
Min.
10mm<3/8>
(Knockout)
92
/8>
<3-5
92<3-5/8>
65<2-9/16>
Front piping hole
(Knockout)
Front trunking hole 40<1-9/16>
45<1-25/32>
73<2-7/8>
23<29/32>
Min.
500mm
<19-11/16>
19<3/4>
92
<3-5/8>
40<1-9/16>
92<3-5/8>
45<1-25/32>
2- 22.2<7/8>
Rear piping hole
(Knockout)
74<2-19/32>
40<1-9/16>
Rear trunking hole
(Knockout)
(2- 27<1-1/16>Knockout)
<3-5 92
/8>
92<3-5/8>
65<2-9/16>
Right trunking hole
(Knockout)
Handle
1/2 Conduit attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
Handle
Handle
Side Air Intake
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
Rear Air Intake
40<1-9/16> Conduit hole
FOUNDATION
<Foundation bolt height>
Min.
30mm
<1-3/16>
Conduit hole
(2- 27<1-1/16>Knockout)
55<2-3/16>
75
<2-31/32>
Right piping hole
(Knockout)
Air intake
73<2-7/8>
Conduit hole
(2- 27<1-1/16>Knockout)
Piping Knockout Hole Details
55<2-3/16>
63
<2-1/2>
27<1-1/16>
Handle
····Refrigerant GAS pipe connction (FLARE) 15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE) 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
Example of Notes
Min. 1000mm
<39-3/8>
Min. 10mm
<3/8>
FREE
27<1-1/16>
92<3-5/8>
63<2-1/2>
23<29/32>
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
55<2-3/16>
27<1-1/16>
1350<53-5/32>
Min.
150mm
<5-29/32>
Min.
500mm
<19-11/16>
3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS
30<1-3/16>
600<23-5/8>
220
<8-21/32>
66<2-5/8>
42<1-21/32>
Earth terminal
950<37-13/32>
Drain hole
5- 33<1-5/16>
71<2-13/16>
2
1
Handle
Service panel
Terminal Block
Left···Power supply wiring
Right····Indoor/Outdoor wiring
2-12 36 Oval hole
(Foundation Bolt M10<W3/8>)
145
145
145
<5-23/32> <5-23/32> <5-23/32>
322<12-11/16>
Air Discharge
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
175<6-7/8>
Rear Air Intake
175<6-7/8>
* 1 443<17-7/16>
330<13>
30<1-3/16>
23<29/32>
45<1-25/32>
Dimensions of space needed
for service access are
shown in the below diagram.
31<1-7/32>
417<16-13/32>
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
73<2-7/8>
63<2-1/2>
23<29/32>
635<25>
371<14-19/32>
219<8-5/8>
81<3-3/16>
56<2-7/32>
19<3/4>
370<14-9/16>
28<1-3/32>
53<2-3/32>
© 2014 Mitsubishi Electric US, Inc.
71<2-13/16>
Specifications are subject to change without notice.
Bottom piping hole
(Knockout)
Rear piping cover
Front piping cover
1076<42-3/8>
FORM# PCA-A36KA4 / PUZ-HA36NHA4 - 201406
* 1 447<17-19/32>
1 FREE SPACE (Around the unit) 2 SERVICE SPACE
DIMENSIONS: PUZ-HA36NHA4
Unit : mm<inch>
1340 Satellite Boulevard
Suwanee, GA 30024
Toll Free: 800-433-4822
www.mehvac.com