Control Panel DS7400XiV4-EXP
Release Notes
January 2005
Release Notes for Firmware Version 4.10
Table 1: Module Configuration Combinations
Trademarks
Cobox™ is a trademark of Lantronix.
1.0
Remote Programming
Compatibility
Use RPS-INT’L version 3.7.140 or later to program
the DS7400XiV4-EXP control panel.
Combination
Number
1
Module 1
(Address 13)
1
DX4010i
2
DX4020
2.0
2.1
Network Communication
The control panel can be configured to communicate
over an Ethernet network. Reports can be sent over
this network from the control panel to the central
station receiver. Remote programming can also be
conducted over this network. A DX4020 Network
Interface Module (NIM) is required for network
communication. Refer to the DX4020 Network Interface
Module Installer’s Guide (P/N: 49522) for installation
and configuration instructions. Refer to Section 2.1.1
Network Communication Report Routing on page 1
through Section 2.1.9 Programming Baud Rate for Network
Communication on page 5 for network communication
configuration information.
You can also connect a DX4010i to a serial printer for
report printing. Refer to Section 2.1.10 Programming
Modules 1 and 2 for RS-232 Printing on page 5 and
Section 2.1.11 RS-232 Printer Baud Rate Programming on
page 5 for RS-232 printer configuration information.
You can connect up to two modules to the control
panel; configure as described in Table 1.
Not used
2
DX4010i
2
DX4020
DX4020
4
DX4020
2
New Features in Firmware
Version 4.10
2
3
1
-
3
-
4
-
Module 2
(Address 14)
Not used
3
4
Supports both RS-232 printing and RPS direct connect.
Supports both central station reporting and RPS
programming.
On Module 2, the DX4010i only supports RS-232
printing.
On Module 2, the DX4020 only supports central station
reporting.
2.1.1
Network Communication Report Routing
Program whether open and close reports, alarm and
trouble reports, and system reports are routed using
the digital communicator (phone), network
communication (Internet Protocol [IP]), or both.
•
Address: 3025
•
Data Digit:
•
•
•
Data Digit 1: ____ (refer to Table 2;
default = 0)
Data Digit 2: Must = 0
Selections: 0 to 4
Table 2: Network Communication Report
Routing Options
Select Options
0
Disabled
Use IP with phone as
backup
Use phone with IP as
backup
Use IP only
Use both phone and IP
•
1
2
3
4
•
•
•
•
DS7400XiV4-EXP
2.1.2
Network Communication Routing
Table 4: HEX Character Values
Select how the control panel routes Network
Communication Mode attempts.
•
Address: 3026
•
Data Digit:
•
•
•
Data Digit 1: ____ (refer to Table 3;
default = 0)
Data Digit 2: Must = 0
Selections: 0 to 3
2.1.4
Table 3: Network Communication Routing
Select Options
0
Use IP Module 1 only
•
Use IP Module 2 only
Use IP Module 1 as primary and
Module 2 as backup
Use both IP Module 1 and 2
2.1.3
1
2
3
•
•
•
Network Communication Heartbeat Interval
Set the rate at which the DX4020 polls the receiver.
The heartbeat interval requires four data digits. For
example, to program a five-second heartbeat interval,
program Data Digit 1 as 0, Data Digit 2 as 0, Data
Digit 3 as 0, and Data Digit 4 as 5.
Program the heartbeat interval using HEX values.
Table 4 shows the keypad keys you must press to
generate HEX characters A through F. Table 19 on
page 8 shows the HEX-to-decimal conversion values.
•
Addresses: 3027
•
Data Digit:
•
•
•
•
Data Digit 1: ____
Data Digit 2: ____
Data Digit 3: ____
Data Digit 4: ____
•
Values: 0 (disabled), 5 sec to 65535 sec
•
Default: 0000 (disabled)
•
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads). Use
these selections to enter valid heartbeat values,
such as:
•
•
•
•
Keys Pressed
HEX Character
[*][0]
[*][1]
[*][2]
[*][3]
[*][4]
[*][5]
A
B
C
D
E
F
Network Communication Wait for Ack Time
Set the amount of time that the DX4020 waits for an
acknowledgment from the receiver before polling it
again.
The wait for acknowledgement time requires four data
digits. For example, to program a five-second ack
time, program Data Digit 1 as 0, Data Digit 2 as 0,
Data Digit 3 as 0, and Data Digit 4 as 5.
The ack time is programmed using HEX values. Table
4 shows the keypad keys you must press to generate
HEX characters A through F. Table 19 on page 8 shows
the HEX-to-decimal conversion values.
•
Addresses: 3029
•
Data Digit:
•
•
•
•
Data Digit 1: ____
Data Digit 2: ____
Data Digit 3: ____
Data Digit 4: ____
•
Values: 0 (disabled), 5 sec to 65535 sec
•
Default: 0000 (disabled)
•
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads). Use
these selections to enter valid ack time values,
such as:
•
•
•
0005 = 5 sec
000A = 10 sec
FFFF = 65535 sec
0000 = disabled
0005 = 5 sec
000A = 10 sec
FFFF = 65535 sec
DS7400XiV4-EXP Release Notes
© 2005 Bosch Security Systems
Page 2
4998154793B
DS7400XiV4-EXP
2.1.5
Network Communication Module 1 and
Module 2 Ack and Message Type
Configuration
2.1.6
Select if an acknowledgment from the receiver is
required for each alternate communication route. Also
select if anti-replay is required for each alternate
communication route.
Anti-replay is a strategy designed against replay
attacks. A replay attack occurs when a hacker records
a message sent over the network by Device A. The
hacker replays this message at a later time while
pretending to be Device A. This feature prevents
substituting a control panel and network interface
module (NIM) for delivering events over a network.
•
Addresses: 3031 (Module 1) and 3032 (Module 2)
•
Data Digit:
•
•
•
Data Digit 1 Select Options
Value
Do not use Central Station ack
Use Central Station acks
0
Table 6: Network Communication Routing
Anti-replay off
Anti-replay on
Use Cobox™ header
Do not use Cobox™ header
•
•
•
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads).
Network Communication Module 2 Central
Station IP Address
•
Address: 3037
•
Default: 00 00 00 00
•
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads).
2.1.8
1
1
Default: 00 00 00 00
Refer to Section 2.1.6 Network Communication Module 1
Central Station IP Address for more information.
Table 5: Ack Usage
0
•
Set the IP address of the Central Station receiver used
by Network Communication Module 2.
Selections: 0 or 1 for Data Digit 1; 0 to 3 for
Data Digit 2
Data Digit 2 Select Options
Set the IP address of the Central Station receiver used
by Network Communication Module 1.
Each section of the IP address is stored in Address
3033, in HEX format. After entering all four sections,
press [#] to accept the values. For example, to
program the IP address 172.16.17.11, enter AC 10 11
0B [#]. Table 4 on page 2 shows the keys you must
press to generate HEX characters A through F. Table
19 on page 8 shows the HEX-to-decimal conversion
values.
• Addresses: 3033
2.1.7
Data Digit 1: ____ (refer to Table 5;
default = 1)
Data Digit 2: ____ (refer to Table 6;
default = 0)
Network Communication Module 1 Central
Station IP Address
2
3
•
•
•
•
Enable or disable the network communication
module.
•
Addresses: 4019 (Module 1); 3041 (Module 2)
•
Data Digit:
•
•
Programming Modules 1 and 2 for Network
Communication
•
•
•
Data Digit 1: ____ (refer to Table 7;
default = 0)
Data Digit 2: Must = 0
Selections: 0 or 1 for Data Digit 1
Table 7: Network Communication Module 1 and 2
Configuration
Select Option
Value
Module disabled
Module enabled
0
1
DS7400XiV4-EXP Release Notes
4998154793B
Page 3
© 2005 Bosch Security Systems
DS7400XiV4-EXP
2.1.9
Programming Baud Rate for Network
Communication
Table 9: Parity, Flow Control, Stop Bits, and
Data Bits Configuration, Data Digit 2
If the Network Communication Module is enabled,
you must also configure its baud rate.
Select Options
0
1
2
3
DX4020 Network Interface Module:
Configure Addresses 4020 for Module 1
and 3042 if using Module 2 as 4 1. Refer
to Table 8 and Table 9 on page 4. Also
configure Addresses 4019 and 3041 as
1 0. Refer to Section 2.1.10 Programming
Modules 1 and 2 for RS-232 Printing on
page 4.
No Parity
•
•
•
•
RPS Direct Connection option for
programming using Module 1: Configure
Address 4019 as 1 0, and configure
Address 4020 as 2 5. Refer to Table 8
and Table 9 on page 4.
2 Stop Bits
8 Data Bits
Remote Programming is only available
through Network Communication Module
1.
•
Addresses: 4020 (Module 1); 3042 (Module 2)
•
Data Digit:
•
•
•
Data Digit 1: ____ (refer to Table 8;
default = 0)
Data Digit 2: ____ (refer to Table 9;
default = 0)
Selections: 0 to 5 for Data Digit 1; 0 to 7 for Data
Digit 2
ODD Parity
EVEN Parity
Software Flow
Control
Hardware Flow
Control
1 Stop Bit
Value
300 baud
1200 baud
2400 baud
4800 baud
9600 baud
14400 baud
0
1
2
3
4
5
•
•
•
•
•
•
5
•
•
•
•
•
7
•
•
•
•
•
•
•
6
•
•
•
•
•
•
•
•
•
2.1.10 Programming Modules 1 and 2 for RS-232
Printing
You can use Module 1 or 2 to connect the control
panel to an RS-232 printer. Most printers operate
using the default values, but some printers operate
more efficiently using optional program values. Refer
to Section 2.1.11 RS-232 Printer Baud Rate Programming
for baud rate configuration.
Consult the operating guide provided with your
printer to ensure that its configuration matches the
one programmed here.
•
Addresses: 4019 (Module 1); 3041 (Module 2)
•
Data Digit:
•
•
Table 8: Module 1 and 2 Baud Rate, Data Digit 1
Select Option
•
4
•
Data Digit 1: ____ (refer to Table 10;
default = 0)
Data Digit 2: ____ (refer to Table 11;
default = 7)
Selections: 0 or 1 for Data Digit 1; 0 through 7
for Data Digit 2
Table 10: RS-232 Printing Using Module 1 and 2
Select Option
Value
Module disabled
Module enabled for printing
0
1
Table 11: RS-232 Event Printing Configuration,
Data Digit 2
Select Options
0
No Events
Alarms, Troubles,
and Restorals
Opens and Closes
All Other Events
•
1
2
•
3
4
6
•
•
•
5
•
•
•
7
•
•
•
•
•
DS7400XiV4-EXP Release Notes
© 2005 Bosch Security Systems
Page 4
4998154793B
DS7400XiV4-EXP
Table 12 shows the available options when you install
two RS-232 modules on one system.
Print
Module 1
Module 2
Yes
Yes
Available Options
Direct Connect/ AltComm
Alt Comm RPS
Reporting
Connection
Yes
Yes
No
Yes
If both network modules are enabled, only
the second module prints history reports.
2.1.11 RS-232 Printer Baud Rate Programming
If using the Network Communication Module to
connect the control panel to an RS-232 printer, you
can configure the module’s baud rate.
•
Addresses: 4020 (Module 1); 3042 (Module 2)
•
Data Digit:
•
•
•
Door Access Control Module
(DACM) Support
Use Keypad/DACM Assignment Programming to
assign a keypad or DACM to a keypad bus address,
and to identify its area (partition).
Table 12: Network Module Options
Network
Module
2.2
The DS7400XiV4 supports up to eight DACMs. Each
DACM must have a unique keypad bus address.
You can only assign a DACM to Keypad
Bus Addresses 3 to 10.
You cannot assign a DACM and a keypad
to the same address.
Once a DACM is assigned to a keypad bus address,
the control panel forces Zones 9 through 16 to the
DACM door contact zone type. If you remove all
DACMs from the system, Zones 9 through 16 return
to their programmed values. Although the zone type is
forced, the zone function programming applies. Refer
to Table 14, and also the DS7400XiV4-EXP Control
Panel Reference Guide (P/N: 4998154963).
Table 14: DACM Address, Zone, and Zone
Function Addresses
Data Digit 1: ____ (refer to Table 13;
default = 0)
Data Digit 2: ____ (refer to Table 9;
default = 0)
Keypad Bus
Address that
DACM Occupies
3
4
5
6
7
8
9
10
Selections: 0 to 5 for Data Digit 1
Table 13: Module 1 and 2 Baud Rate, Data Digit 1
Select Option
Value
300 baud
1200 baud
2400 baud
4800 baud
9600 baud
14400 baud
0
1
2
3
4
5
Zone
Zone
Function Address
9
10
11
12
13
14
15
16
0039
0040
0041
0042
0043
0044
0045
0046
Refer to the DACM Installation Instructions
(P/N: F01U500999) for more information.
•
Addresses: 3132 to 3135
•
Data Digit: Refer to Table 15.
•
Defaults: Refer to Table 15. If using only one
keypad, the default is an Alpha keypad belonging
to Area 1. Otherwise, the default is 0.
DS7400XiV4-EXP Release Notes
4998154793B
Page 5
© 2005 Bosch Security Systems
DS7400XiV4-EXP
•
Selections:
•
Keypad/DACM Type: 0 to 4 (refer to Table
16). Select 4 for DACM.
Table 15: Address 3131 to 3135 Keypad/DACM
Assignment Programming
Address
3131
Data
Digit
1
Keypad/
DACM
1*
Default
Assigned
Value
1
2
2*
0
1
3
0
2
4
0
1
5
0
2
6
0
1
7
0
2
8
0
1
9
0
2
10
0
❒
❒
❒
❒
❒
❒
❒
❒
❒
❒
3132
3133
3134
3135
* Keypad only
Table 16: Keypad/DACM Type (Addresses 3131
to 3135)
Select Options
0
Disabled
•
Alpha (LCD) Keypad
LED Keypad
Master Keypad*
Door Access Control
Module
1
2
•
3
4
•
•
•
•
* If only using one area, do not select Master Keypads.
Only use a Master Keypad if you need to view multiple
areas from a single keypad.
DS7400XiV4-EXP Release Notes
© 2005 Bosch Security Systems
Page 6
4998154793B
DS7400XiV4-EXP
2.2.1
Keypad/DACM Partition Assignment
•
•
Addresses: 3139 to 3146
Data Digit: See Table 17
•
•
Default: 0
Selections: See Table 18
Use Table 17 and Table 18 to assign a keypad or DACM to an area (partition). Select an area assignment value
from Table 18, and enter that value in the appropriate data digit for each address in Table 17. For example, if you
want Keypad/DACM 1 to be assigned to Area 3, enter a “2” in Data Digit 1 for Address 3139.
Table 17: Address 3139 to 3146 Keypad/DACM Partition Assignment
Address
3139
3140
3141
3142
Data
Digit
1
Keypad/
DACM
1*
Default
Assigned
Value
Address
0
3143
2
2*
0
1
3
0
2
4
0
1
5
0
2
6
0
1
7
0
2
8
0
❒
❒
❒
❒
❒
❒
❒
❒
3144
3145
3146
Data
Digit
1
Keypad/
DACM
9
Default
Assigned
Value
0
2
10
0
1
11
0
2
12
0
1
13
0
2
14
0
1
15
0
❒
❒
❒
❒
❒
❒
❒
2
This Data Digit
must be 0.
0
* Keypad only
Table 18: Address 3139 to 3146 Keypad Partition Assignment Selections
Select Option
Value
Belongs to Area 1
Belongs to Area 2
Belongs to Area 3
Belongs to Area 4
Belongs to Area 5
Belongs to Area 6
Belongs to Area 7
Belongs to Area 8
0
1
2
3
4
5
6
7
The DACM Partition Assignment’s assigned value (Table 17 and Table 18) and the Zone Partition
Assignment’s assigned value must be the same.
For example, if you assign a DACM to Partition 2 and the DACM is tied to Zone 9, then you must
assign Zone 9 to Partition 2. For information on assigning the Zone Partition Assignment’s value, refer
to “Zone Partition Assignment” in the DS7400XiV4-EXP Control Panel Reference Guide
(P/N: 4998154963).
Refer to the DACM Operation Instructions (P/N: F01U500997) for instructions on using the DACM with the
control panel.
DS7400XiV4-EXP Release Notes
4998154793B
Page 7
© 2005 Bosch Security Systems
DS7400XiV4-EXP
Table 19: HEX-to-Decimal Conversion Values
Dec
Value
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
HEX
Value
01
02
03
04
05
06
07
08
09
0*0
0*1
0*2
0*3
0*4
0*5
10
11
12
13
14
15
16
17
18
19
1*0
1*1
1*2
1*3
1*4
1*5
20
21
22
23
24
25
26
27
28
29
2*0
Dec
Value
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
HEX
Value
2*1
2*2
2*3
2*4
2*5
30
31
32
33
34
35
36
37
38
39
3*0
3*1
3*2
3*3
3*4
3*5
40
41
42
43
44
45
46
47
48
49
4*0
4*1
4*2
4*3
4*4
4*5
50
51
52
53
54
Dec
Value
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
HEX
Value
55
56
57
58
59
5*0
5*1
5*2
5*3
5*4
5*5
60
61
62
63
64
65
66
67
68
69
6*0
6*1
6*2
6*3
6*4
6*5
70
71
72
73
74
75
76
77
78
79
7*0
7*1
7*2
7*3
7*4
Dec
Value
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
HEX
Value
7*5
80
81
82
83
84
85
86
87
88
89
8*0
8*1
8*2
8*3
8*4
8*5
90
91
92
93
94
95
96
97
98
99
9*0
9*1
9*2
9*3
9*4
9*5
*00
*01
*02
*03
*04
*05
*06
*07
*08
Dec
Value
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
HEX
Value
*09
*0*0
*0*1
*0*2
*0*3
*0*4
*0*5
*10
*11
*12
*13
*14
*15
*16
*17
*18
*19
*1*0
*1*1
*1*2
*1*3
*1*4
*1*5
*20
*21
*22
*23
*24
*25
*26
*27
*28
*29
*2*0
*2*1
*2*2
*2*3
*2*4
*2*5
*30
*31
*32
Dec
Value
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
HEX
Value
*33
*34
*35
*36
*37
*38
*39
*3*0
*3*1
*3*2
*3*3
*3*4
*3*5
*40
*41
*42
*43
*44
*45
*46
*47
*48
*49
*4*0
*4*1
*4*2
*4*3
*4*4
*4*5
*50
*51
*52
*53
*54
*55
*56
*57
*58
DS7400XiV4-EXP Release Notes
© 2005 Bosch Security Systems
Page 8
4998154793B
DS7400XiV4-EXP
3.0
•
•
Network Communication Attempts Use
AltComm Module 2 First, Then AltComm
Module 1: The control panel uses AltComm
Module 2 first before using AltComm Module 1
when attempting to communicate over an
Ethernet network. When attempting to
communicate over the telephone line, the control
panel uses Phone 1 first before using Phone 2.
•
AltComm Remote Programming Callback Not
Available: You cannot program the control
panel for remote programming callback over an
Ethernet network.
•
Arming An Unlocked Door: You can arm an
area when a user command latches a door access
control module’s (DACM) door open, or a fire
alarm latches a DACM’s door open.
•
Fire Bell and DACM Operation: If the bell
output is set for fire and assigned to all areas
(partitions), then all DACMs in the system release
their doors during a fire alarm. If the bell output is
assigned to a certain area, only the DACMs in
that area release their doors.
•
Restoral Report Not Sent for Serial Interface
Module or AltComm Module: The control
panel does not send a restoral report when a serial
interface module, or an altcomm module with the
altcomm heartbeat parameter disabled, fails and
then restores.
•
Alarm Verification Not Available: Alarm
verification is not available in version 4.10 of the
DS7400XiV4.
•
“Do Not Use Central Station Ack” Option and
High Network Activity: Alarm reports sent over
an Ethernet network during periods of high
network activity might not reach the central
station if the “Do Not Use Central Station Ack”
option is selected. Refer to Table 5 on page 3 for
more information.
Known Issues in Firmware
Version 4.10
Multiplex Devices and Address 9995: To add
multiplex devices that do not have DIP switches,
use Address 9995. However, the first zone
displayed, Zone 009, is reserved for the first
DACM door contact. Press and hold [*] until
“MUX POINT” appears on the keypad’s display.
Enter the desired zone number for the multiplex
device.
•
Door Forced Open Condition Does Not Send a
Report: You must enable Addresses 3418
(Keypad Tamper) and 3419 (Keypad Tamper
Restoral) to send a Door Forced Open (DACM
Trouble 75) report.
•
DACM Trouble Events Do Not Show the
DACM Number: If a DACM experiences a
trouble event, such as a Tamper (72), Missing (73),
Door Held Open (74), or Door Forced Open (74),
the keypad does not show the number for that
DACM when it displays the trouble message.
•
Keypad and DACM Tamper and Restoral
Report Programming: Information on
programming keypad and DACM tamper and
restoral reports is missing from the control panel’s
documentation. Use Address 3418 for keypad or
DACM tamper reports, and Address 3419 for
keypad or DACM tamper restoral reports. If you
disable tamper and tamper restoral reports for
keypads, the keypads do not display tamper
messages. However, if you disable tamper and
tamper restoral reports for DACMs, the keypads
still display DACM tamper messages.
•
DX4010i Serial Interface Module “Printer
Error” Message: The control panel generates a
“Printer Error” message if you use the DX4010i to
create a direct connection to the remote
programming software (RPS) PC.
•
RPS Callback Address 3043: Enter an IP address
in Address 3043 if you want the control panel to
call the RPS PC over an Ethernet network.
•
Daylight Saving Time Missing from Reference
Guide: To enable Daylight Saving Time, set
Address 3478, Data Digit 2 to “1.” To disable
Daylight Saving Time, set Data Digit 2 to “0.”
•
Daylight Saving Time Not Working Correctly:
The Daylight Saving Time falls back an hour at
2:00 AM instead of 3:00 AM on the last Sunday in
October.
DS7400XiV4-EXP Release Notes
4998154793B
Page 9
© 2005 Bosch Security Systems
© 2004 Bosch Security Systems
www.boschsecuritysystems.com
4998154793B
Release Notes
1/05
DS7400XiV4-EXP
Page 10 of 10