MODEL: CLSE CLAMP-ON CURRENT SENSOR INPUT SPECIFICATIONS

MODEL: CLSE CLAMP-ON CURRENT SENSOR INPUT SPECIFICATIONS
MODEL: CLSE
CLAMP-ON CURRENT SENSOR
INPUT SPECIFICATIONS
Functions & Features
• Easy-to-install, spring-loaded, clamp-on type current
sensor
• Over-voltage clamp element for safety in open circuit
• Wide frequency band
• Screw terminal connection
Maximum working voltage: 480 V AC (primary side)
Operational range & overload capacity
CLSE-R5
CLSE-05
CLSE-10
CLSE-20
CLSE-40
CLSE-60
OPERATIONAL RANGE OVERLOAD CAPACITY *
5 A maximum
10 A continuous
50 A maximum
60 A continuous
100 A maximum
120 A continuous
200 A maximum
240 A continuous
400 A maximum
480 A continuous
600 A maximum
720 A continuous
*4000% of rating for 1 second
Caution 1: The output values may vary depending on the
accuracy of engagement at the clamp connection.
Caution 2: The sensor's mechanical construction may cause
it to generate resonance sound. However, it does not affect
the performance of the sensor.
MODEL: CLSE–[1][2]
INSTALLATION
ORDERING INFORMATION
• Code number: CLSE-[1][2]
Specify a code from below for each [1], [2].
(e.g. CLSE-R5/CE)
Confirm the correct sensor type described on the data sheet
of the combined transducer/transmitter module.
[1] POWER INPUT
R5: 5 A
05: 50 A
10: 100 A
20: 200 A
40: 400 A
60: 600 A
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Weight:
CLSE-R5: 45 g (1.6 oz)
CLSE-05: 40 g (1.4 oz)
CLSE-10: 75 g (2.6 oz)
CLSE-20: 180 g (6.3 oz)
CLSE-40: 300 g (10.5 oz)
CLSE-60: 330 g (11.6 oz)
PERFORMANCE in percentage of span
Frequency: 45 – 65 Hz (including the harmonic current up to
20 kHz)
For 65.1 Hz – 1.2 kHz, ratio error is ±2 %/In.
Maximum load: 10 Ω
Insulation resistance: ≥ 100 MΩ with 500 V DC
(sensor core to output terminal)
Dielectric strength: 2000 V AC @1 minute
(sensor core to output terminal)
[2] OPTIONS
STANDARDS & APPROVALS
blank: Without CE
/CE: CE marking
MODEL
RELATED PRODUCTS
CLSE-R5
CLSE-05
CLSE-10
CLSE-20
CLSE-40
CLSE-60
• Special cable (model: CLS-CN)
Used in combination with the CLSA-08C.
• Special cable (model: CLSA-08C)
PRIMARY SECONDARY
RATIO
PHASE DISPLACEMENT
RATING
RATING
ERROR
ERROR
5A
1.65 mA
±1%/In, ±2%/0.2 In
±1.5 ±1°
50 A
20 mA
±1%/In, ±2%/0.2 In
±1 ±1°
100 A
20 mA
±1%/In, ±2%/0.2 In
±0.5 ±1°
200 A
20 mA
±1%/In, ±2%/0.2 In
±1°
400 A
20 mA
±1%/In, ±2%/0.2 In
±1°
600 A
20 mA
±1%/In, ±2%/0.2 In
±1°
GENERAL SPECIFICATIONS
Construction: Clamp
Connection: M3 screw terminals (torque 0.3 N·m)
Housing material: Flame-resistant resin
Detachable number of times: Approx. 100 times
Applicable wire size: AWG22 or thicker (0.6 dia. or 0.3 mm2
or thicker; Max. 30 meters, twisted)
http://www.m-system.co.jp/
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EN 61326-1
Low Voltage Directive (2006/95/EC)
EN 61010-1
CLSE SPECIFICATIONS
ES-9234 Rev.4 Page 1/2
MODEL: CLSE
EN 61010-2-032
Measurement Category III
Pollution Degree 2
DIMENSIONS unit: mm (inch)
■ CLSE-R5, -05
4
26 (1.02)
4
(.16)
(.16)
2–M3 SCREW
50 (1.97)
37 (1.46)
26 (1.02)
10 dia.
l
(.39)
k
L
K
TERMINAL COVER
(detachable)
■ CLSE-10
4
4
31 (1.22)
(.16)
32.5 (1.28)
(.16)
55 (2.17)
2–M3 SCREW
40.5 (1.59)
l
16 dia.
(.63)
k
L
K
TERMINAL COVER
(detachable)
■ CLSE-40, -60
■ CLSE-20
34 (1.34)
(.16)
4
(.16)
4
74.5 (2.93)
49.5 (1.95)
2–M3 SCREW
40.5 (1.59)
(.16)
(1.42)
k
TERMINAL COVER
(detachable)
K
2–M3 SCREW
61 (2.40)
l
k
L
91 (3.58)
36 dia.
l
49 (1.93)
24 dia.
(.94)
4
(.16)
61 (2.40)
4
L
K
TERMINAL COVER
(detachable)
Specifications are subject to change without notice.
http://www.m-system.co.jp/
CLSE SPECIFICATIONS
ES-9234 Rev.4 Page 2/2
Was this manual useful for you? yes no